MC-11-1283 (2)Inspection Worksheet
Miami Shores Village
10050 N.E. 2nd Avenue Miami Shores, FL
Phone: (305)795 -2204 Fax: (305)756 -8972
CL
CC- 11- 5 ho
Inspection Number: INSP - 173308 Permit Number: MC -7 -11 -1283
Scheduled Inspection Date: June 25, 2012
Inspector: Perez, JanPierre
Owner: , BARRY UNIVERSITY
Job Address: 11300 NE 2 Avenue NEW DOORM
Miami Shores, FL 33138 -0000
Project: BARRY UNIVERSITY
Contractor: HILL YORK SERVICE CORP
Permit Type: Mechanical - Commercial
Inspection Type: Final
Work Classification: New
Phone Number
Parcel Number 1121360010160 -37
Phone: (305)756 -6501
Building Department Comments
2 AIR COOLED CHILLERS, UNDERVENT PIPING,
CHILLED WATER PIPING IN BUILDING WITH CVHILLED
WATER (*FCU), OUTSIDE AIR UNITS, EXHAUST WITH
DUCT WORK
l'Z
Passed
►%J
Failed
Correction
Needed
Re- Inspection
Fee
No Additional Inspections can be scheduled until
re- inspection fee is paid.
Inspector Comments
T &B REPORT OK STILL MISSING KITCHEN HOO
REINSPECTION FOR INSP- 162095. need T &B rep
CALL JASON AT 954 -668 -9743
JPP CREATED AS
rt and kitchen hood jpp
June 22, 2012
For Inspections please call: (305)762 -4949
Page 13 of 43
CERTIFIED
TEST & BALANCE
CC II -5S0
CERTIFIED TEST, ADJUST AND
BALANCE REPORT
DATE: 06 /12/12
PROJECT: BARRY UNIVERSITY RESIDENCE HALL
LOCATION: 11300 NE 2" AVENUE, MIAMI SHORES, FLORIDA 33161
NM URI ,d
C APPROVED OROS
O REVISE & MON
O FOND o a
TO 1101101041,
EMU OF
ARCM '1 ECT: CANNON - DESIGN
DESIGN ENGINEER: E D S A
GENERAL CONTRACTOR: MOSS AND ASSOCIATES, INC.
MECHANICAL CONTRACTOR: HILL YORK SERVICE CORPORATION
NEBB TAB CONTRACTOR: CERTIFIED TEST & BALANCE, INC.
2499 GLADES RROAD, SUITE 106A
BOCA RATON, FLORIDA 33431
DENNIS T. MIRANDA, PRESIDENT
CERTIFICATION NUMBER: 3064
(561) 961 -5068- OFFICE
(561) 961 -5069 -FAX
0113
CERTIFIED
TEST.& BALANCE
PROJECT: BARRY UNIVERSITY RESIDENCE HALL
LOCATION: 11300 NE 2N0 AVENUE, MIAMI SHORES, FLORIDA 33161
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM
MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN
ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL
STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL
SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEEB
TOLERANCES, ARE NOTED IN THE TEST- ADJUST - BALANCE REPORT PROJECT
SUMMARY.
NEBB CONTRACTOR: CERTIFIED TEST & BALANCE, INC.
REG. NO: NEBB 3064 CERTIFIED BY: iii DATE: 06 /12/12
SUBMLTIED & CERT'D1ED BY:
BROWARD CO. NO.: 98 -CTB -833 -W
NEBB CONTRACTOR: CERTIFIED TEST & BALANCE, INC.
TAB SUPERVISOR: DENNIS T. MIRANDA
REG. NO.: NEBB 3064
DATE: 06 /12/12
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 05/22/12 Page: 1
SYSTEM
1
RTU -1
RTU -2
LOCATION
I
ROOF
ROOF
AREA SERVED
OUTSIDE AIR NORTH
E
OUTSIDE AIR SOUTH
MANUFACTURER
TRANE
TRANE
MODELNUMBER
TCH301E300AB
TCH301E300AB
SERIAL NUMBER
1
113210877D
113210985D
FAN DATA
DESIGN
u i : I: NI
DESIGN
MEASURED
TOTAL CFM * OUTLET
3240
3276
3050
3194
OUTSIDE AIR CFM
3240
3276
3050
3194
S.P. TTL / EXT
1.5
.76
1.5
.90
INLET / DISCHARGE
NS
.35/.41
NS
.411.49
FAN RPM
NS
NA
NS
NA
MOTOR DATA
DESIGN
u i : 1:
DESIGN
u i 9.f. 1:
MOTOR HP / HZ
I
7.5
7.5
7.5
7.5
VOLTAGE / PHASE
208/3
207/208/206
208/3
207/206/208
AMPERAGE / SF
18.6
5.6/6.2/5.7
j
18.6
5.4/5.8/5.9
MOTOR RPM
3475
NA
3475
NA
MOTOR PULLEY
3 X 1 1/8
s
3 X 1 1/8
FAN PULLEY
19 X 1 3/16
19 X 13/16
BELTS / POSITION / C—C
(1) B X 94 / FIXED
(1)B X 96 / TOP
OUTSIDE AIR DUCT SIZE
62 X 1812
62 X 18 Y2
Comments:
Readings By: Craig Maurer, Bart Serino
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 05/22/12 Page: 2
SYSTEM
RTU -3
LOCATION ROOF
AREA SERVED OUTSIDE AIR CENTER
MANUFACTURER TRANE
MODEL NUMBER TCH301E300AD
SERIAL NUMBER 113210931D
FAN DATA DESIGN MEASURED
3725 3913
3725 3913
TOTAL CFM * OUTLET
OUTSIDE AIR CFM
S.P. 'ITL / EXT
INLET / DISCHARGE
FAN RPM
DESIGN
MEASURED
1.5
NS
NS
1.27
.71/.56
NA
MOTOR DATA
DESIGN
MEASURED DESIGN
MEASURED
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
7.5
208/3
18.6
3475
7.5
207/206/207
5.9/6.1/5.7
NA
MOTOR PULLEY
3X11/8
FAN PULLEY
19 X 1 3/16
BELTS / POSITION / C-C
(1) B X 94 / FIXED / NA
OUTSIDE AIR DUCT SIZE 62 X 18 %2
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 05/22/12 Page: 3
SYSTEM AHU- 1 - 1 AHU- 1 -2
LOCATION
AREA SERVED
MANUFACTURER
MODFJ NUMBER
SERIAL NUMBER
FAN DATA
CEILING
1ST FLOOR LOBBY
ENVIRO TEC
HPPO8
CEILING
RECEPTION
ENVIRO TEC
HPPO8
NS
NS
DESIGN
MEASURED DESIGN MEASURED
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
/ EXT
INLET / DISCHARGE
FAN RPM
800
800
0
NS
NS
NS
803
803
0
NA
NA
HIGH
800
800
0
NS
NS
NS
738
738
0
NA
NA
HIGH
MOTOR DATA
DESIGN
MEASURED DESIGN
MEASURED
MOTOR HP! HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
208/1
1.6
NS
207
1.21
HIGH
208/1
1.6
NS
206
1.31
HIGH
MOTOR PULLEY
FAN PULLEY
BELTS / POSITION / C-C
OUTSIDE AIR DUCT SIZE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY Date: 05/22/12 Page: 4
SYSTEM
AHU -1 -3 AHU -1-4
LOCATION
CEILING CEILING
AREA SERVED
LAUNDRY 1ST FLOOR MAIL ROOM
MANUFACTURER
ENVIRO "1 'EC ENVIRO TEC
MODEL NUMBER
HPPO8 HPPO8
SERIAL NUMBER
NS NS
FAN DATA
DESIGN
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET
900
763 800
833
RETURN AIR CFM
900
763 800
833
OUTSIDE AIR CFM
0
0 0
0
S.P. '11L / EXT
NS
NA NS
NA
INLET / DISCHARGE
NS
NA NS
NA
FAN RPM
NS
HIGH NS
HIGH
MOTOR DATA
DESIGN
MEASURED DESIGN
MEASURED
MOTOR HP / HZ
I
VOLTAGE / PHASE
208/1
206 208/1
206
AMPERAGE / SF
1.6
1.25 1.6
1.3
MOTOR RPM
NS
HIGH NS
HIGH
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C -C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SUE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
V
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 05/22/12 Page: 5
SYSTEM
AHU-1-5
AHU-1-6
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
CEILING
MECH. RM.
1ST FLOOR OFFICE
MULTI PURPOSE
ENVIRO '1F,C
ENVIRO TEC
HPPO8
CDV
SERIAL NUMBER
NS
NS
r
FAN DATA
DESIGN
MEASURED
DESIGN
MEASURED
TOTAL CFM * OUTLET
600
570
1490
1474
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. T11 / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
560
40
NS
NS
NS
528
1290
1270
42
200
204
NA
NS
NA
NA
NS
NA
DESIGN
LOW
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
IA
1A.
NS
DESIGN
(2) i/4
HIGH
MEASURED
IA
208/1
207
208/1
206
1.6
.97
4.4
1.4/1.5
NS
LOW
NS
HIGH
MOTOR PULLEY DIRECT DRIVE
FAN PULLEY DIRECT DRIVE
BELTS / POSITION / C-C DIRECT DRIVE
OUTSIDE AIR DUCT SIZE 6 X 6
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
10" ROUND
Comments:
Readings By: Craig Maurer, Bart Serino
V
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/4/12 Page: 6
SYSTEM
AHU-1-7 AHU-1-7A
LOCATION
CEILING CEILING
AREA SERVED
RETAIL SERVING
MANUFACTURER
ENVIRO TEC ENVIRO TEC
MODEL NUMBER
HPP16 I-IPP20
SERIAL NUMBER
NS NS
FAN DATA DESIGN
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET 1600
1653 1985
1868
RETURN AIR CFM 1400
1457 1985
1868
OUTSIDE AIR CFM
200
196 0
0
S.P. TTL / EXT NS
NA NS
NA
INLET / DISCHARGE NS
NA NS
NA
FAN RPM
NS
MOTOR HP / HZ (2) 'A
MED NS
(2) 1/4 (2) 1/4
HIGH
(2) V4
VOLTAGE / PHASE 208/1
206 208/1
207
AMPERAGE / SF 4
1.18/1.10 4
1.21/1.19
MOTOR RPM NS
MED NS
HIGH
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
10" ROUND 10" ROUND
Comments:
Readings By: Craig Maurer, Bart Serino
an
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/4/12 Page: 7
SYSTEM AHU-1-7B
AHU-1-8
LOCATION
CEILING
CEILING
AREA SERVED
DINING
LOUNGE
MANUFACTURER
ENVIRO
ENVIRO TEC
MODEL NUMBER
HPP12
HPPO8
SERIAL NUMBER
NS
NS
r-
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
MOTOR PULLEY
DESIGN
MEASURED
1200
1000
200
NS
NS
NS
1174
964
210
NA
NA
HIGH
DESIGN
600
540
60
NS
NS
NS
MEASURED
615
550
65
NA
NA
MED
(2) V4
208/1
2
NS
(2) 1/4
206
.79/.71
MED
1/4
208/1
1.6
NS
1/4
206
.96
MED
DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE
OUTSIDE AIR DUCT SIZE 10" ROUND
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
7 X 6
Comments:
Readings By: Craig Maurer, Bart Serino
CrB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/4/12 Page: 8
SYSTEM
AHU-1-9 AHU-2-1
LOCATION
CEILING CEILING
AREA SERVED IsT FLOOR TELECOM SECURITY ELEV LOBBY
MANUFACTURER
ENVIRO '1EC ENVIRO TEC
MODEL NUMBER
HPPO8 HPPO8
SERIAL NUMBER
NS NS
FAN DATA DESIGN
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET 600
678 * 800
734
RETURN AIR CFM 600
678 800
734
OUTSIDE AIR CFM 0
0 0
0
S.F. 1 / EXT NS
NA NS
NA
INLET / DISCHARGE NS
NA NS
NA
FAN RPM NS
MOTOR DATA DESIGN
LOW NS
MEASURED DESIGN
HIGH
MEASURED
MOTOR HP / HZ
1/4
VOLTAGE / PHASE 208/1
206
208/1
207
AMPERAGE / SF 1.6
.97 1.6
1.31
MOTOR RPM NS
LOW
NS
HIGH
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:* Low speed.
Readings By: Craig Maurer, Bart Serino
as
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /4/12 Page: 9
SYSTEM
AHU -2 -2
AHU -2 -3
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
SERIAL NUMBER
FAN DATA
CEILING
LOUNGE
ENVIRO 'I'EC
CEILING
STUDY ROOM
ENVIRO TEC
HPPO8
NS
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. TTL / EXT
INLET / DISCHARGE
FAN RPM
HPPO8
NS
DESIGN MEASURED DESIGN
800 770 600
800 770 600
MEASURED
0
NS
NS
NS
0
NA
NA
HIGH
0
NS
NS
NS
575
575
0
NA
NA
LOW
MOTOR DATA
DESIGN
MEASURED DESIGN
MEASURED
MOTOR HP / HZ
1/4
1/4
1/4
1/4
VOLTAGE / PHASE
208/1
206
208/1
207
AMPERAGE / SF
1.6
1.26
1.6
.96
MOTOR RPM NS
HIGH NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE ! DIRECT DRIVE
BELTS / POSITION / C -C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /6/12 Page: 10
SYSTEM
AHU -3 -1
AHU -3 -2
LOCATION
AREA SERVED
MANUFACTURER.
MODEL NUMBER
SERIAL NUMBER
CEILING
ELEVATOR LOBBY
ENVIRO TEC
HPP12
NS
CEILING
LOUNGE
ENVIRO TEC
HPP12
NS
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. Tit / EXT
INLET / DISCHARGE
FAN RPM
DESIGN
1000
1000
0
NS
NS
NS
MEASURED
1005
1005
0
NA
NA
HIGH
DESIGN
1000
1000
0
NS
NS
NS
MEASURED
994
994
0
NA
NA
HIGH
MOTOR DATA
DESIGN
MEASURED
DESIGN
MEASURED
MOTOR HP / HZ
(2) 1/6
(2) 1/6
(2) 1/6
(2) 1/6
VOLTAGE / PHASE
AMPERAGE / SF
208/1
206
208/1
206
2
.72/.75
2
.79/.74
MOTOR RPM
MOTOR PULLEY
FAN PULLEY
NS
HIGH
DIRECT DRIVE
DIRECT DRIVE
NS HIGH
DIRECT DRIVE
DIRECT DRIVE
BELTS / POSITION / C -C
OUTSIDE AIR DUCT SIZE
DIRECT DRIVE
NA
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
1
aB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /6/12 Page: 11
SYSTEM AHU -3 -3
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
SERIAL NUMBER
FAN DATA
CEILING
LAUNDRY ROOM
ENVIRO '1 EC
HPPO8
NS
DESIGN
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET
600
572
RETURN AIR CFM
600
572
OUTSIDE AIR CFM
0
0
S.P. TTL / EXT NS
NA
INLET / DISCHARGE
NS
NA
FAN RPM NS
LOW
MOTOR DATA DESIGN
MEASURED
DESIGN
MEASURED
MOTOR HP / HZ
14
VOLTAGE / PHASE
208/1
208
AMPERAGE / SF 1.6
.97
MOTOR RPM NS
LOW
MOTOR PULLEY DIRECT DRIVE
FAN PULLEY DIRECT DRIVE
BELTS / POSITION / C -C DIRECT DRIVE
OUTSIDE AIR DUCT SIZE NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
r
Date: 06 /7/12 Page: 12
SYSTEM
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
SERIAL NUMBER
AHU -1.5
CLOSET
101
ENVIRO TECH
CDV
FCU110815 -04B
AHU -1.5
CLOSET
102
ENVIRO TECH
CDV
FCU110815 -045
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. 'I°1'L / EXT
INLET / DISCHARGE
FAN RPM
DESIGN
575
MEASURED DESIGN
MEASURED
651
575
0
NS
NS
NS
651
0
NA
NA
LOW
575
575
0
NS
NS
NS
605
605
0
NA
NA
LOW
MOTOR DATA
DESIGN
MEASURED
DESIGN
MEASURED
MOTOR HP / HZ
1/,/60
'/,/60
1/,/60
W60
VOLTAGE / PHASE 208/1
207/1
208/1
207/1
AMPERAGE / SF 2.7
.97 2.2
.98
MOTOR RPM NS
LOW
NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C -C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
aB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /08/12 Page: 13
SYSTEM
AHU -2.0 AHU -1.5
LOCATION
CLOSET
CLOSET
AREA SERVED
103
104
MANUFACTURER
ENVIRO "I 'EC
ENVIRO 'I EC
MODEL NUMBER
CDV
CDV
SERIAL NUMBER
FCU110815 -04B
FCU110815 -045
FAN DATA
TOTAL CFM * OUTLET
DESIGN
800
MEASURED
845
DESIGN
475
MEASURED
595
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. TTL / EXT
INLET / DISCHARGE
FAN RPM
800
0
NS
NS
NS
845
0
NA
NA
MED
475
0
NS
NS
NS
595
0
NA
NA
LOW
MOTOR DATA
DESIGN
MEASURED
DESIGN
MEASURED
MOTOR HP / HZ
'/,/60
'/,/60
1/4/60
'//60
VOLTAGE / PHASE 208/1
207/1
208/1
208/1
AMPERAGE / SF 2.2
1.2 2
.97
MOTOR RPM NS
MED NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C -C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
crn
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/08/12 Page: 14
SYSTEM AHU-1.5
AHU-1.5
LOCATION
CLOSET CLOSET
AREA SERVED
105 107
MANUFACTURER
ENVIRO 1EC ENVIRO TEC
MODEL NUMBER
CDV CDV
SERIAL NUMBER
FCU110815-04 FCU110815-04B
FAN DATA DESIGN
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET
575
634
575
667
RETURN AIR CFM 575
634
575
667
OUTSIDE AIR CFM
0 0
0
S.P. TTL EXT NS
NA NS
NA
INLET! DISCHARGE NS
NA
NS
NA
FAN RPM NS
LOW NS
LOW
MOTOR DATA DESIGN
MEASURED DESIGN
MEASURED
MOTOR HP / HZ 1/4/60
1/4/60 1/4/60
1/4/60
VOLTAGE / PHASE 208/1
207/1 208/1
208/1
AMPERAGE / SF 2
.98 2.2
.98
MOTOR RPM NS
LOW NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/08/12 Page: 15
SYSTEM
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
SERIAL NUMBER
FAN DATA
TOTAL CFM*FAN
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
MOTOR PULLEY
FAN PULLEY
BELTS / POSITION / C-C
OUTSIDE AIR DUCT SIZE
AHU-1.5
CLOSET
108
ENVIRO 1EC
CDV
FCU110815-05
DESIGN
575
575
575
0
NS
NS
NS
DESIGN
1/4/60
208/1
2
NS
MEASURED
648
648
648
0
NA
NA
LOW
MEASURED
1/4/60
207/1
.98
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
AHU-1.5
CLOSET
109
ENVIRO TEC
CDV
FCU110815-05
DESIGN
575
575
575
0
NS
NS
NS
DESIGN
1/4/60
208/1
2
NS
MEASURED
638
638
638
0
NA
NA
LOW
MEASURED
%/60
207/1
.97
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
_ ...........aB
... .
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /08/12
Page: 16
FAN NO
AHU -1.5
AHU -1.5
AHU -1.5
LOCATION
SERVING
CLOSET
CLOSET
ROOM 110
ROOM 111
CLOSET
ROOM 112
MODEL NO CDV
CDV
CDV
SERIAL NO
MFGR
FCU 110815 -04D FCU 110815 -04B
ENVIO 'TECH ENVIO TECH
FCU110815 -04
ENVIO TECH
FAN DATA
DESIGN CFM
RETURN AIR
DESIGN MEASURED DESIGN MEASURED
575 644 575 653
575 644 575 653
DESIGN MEASURED
575 640
575 640
OUTSIDE AIR
STATIC
PRESSURE
0 0
NS NA
0 0 0 0
NS NA NS NA
RPM FAN
HP /HZ
VOLTAGE
NS LOW NS LOW
'/4/60 '/4/60 '/4/60 'V4/60
208 207 208 207
NS LOW
/60 '/4/60
208 207
PHASE 1
1
AMPERAGE / SF 2.2 .98
2.2 .97 2.2 .97
RPM MOTOR
NS LOW NS LOW NS LOW
MFR PULLEY DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
FAN PULLEY
BELT /
POSITION / C-C
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
0113
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/08/12
Page: 17
FAN NO
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
AHU -1.5 AHU -2.0
AHU -2
CLOSET CLOSET
CLOSET
ROOM 113 ROOM 114
ROOM 133 STAFF APT.
CDV CDV
CDV
FCUI 10815 -04 FCUI 10815 -04
FCU110815 -04
ENVIO TECH ENVIO TECH
ENVIO TECH
DESIGN
MEASURED
DESIGN MEASURED
DESIGN MEASURED
575
626 800
869
750 835
575
626 800
869
750 835
0
0
0
0
0 0
NS
NA
NS
NA
NS NA
NS
LOW
NS
MED
NS HIGH
'/4/60
'/4/60 '/4/60
'/4/60
'/4/60
/60
208
208 208
207
208 207
1
1
2
.98 2
1.3
2 1.5
NS
LOW NS
MED.
NS HIGH
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE
BELT /
POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
07'13
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/05/12 Page: 18
SYSTEM
AHU -1.5
AHU -1.5
LOCATION
CLOSET
CLOSET
AREA SERVED
ROOM 201 ROOM 202
MANUFACTURER
ENVIRO I EC ENVIRO TEC
MODEL NUMBER
CDV CDV
SERIAL NUMBER
FCU110815 -04B FCU110815 -04B
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
DESIGN
575
575
OUTSIDE AIR CFM
S.P. TTL / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
0
NS
NS
NS
DESIGN
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
1/,/60
208/1
2.2
NS
MEASURED DESIGN
657 575
657 575
0 0
NA NS
NA NS
LOW NS
MEASURED DESIGN
%/60 1/4/60
207/1 208/1
.98 2.2
LOW NS
MEASURED
671
671
0
NA
NA
LOW
MEASURED
1/4/60
207/1
.99
LOW
MOTOR PULLEY DIRECT DRIVE DIRECT DRIVE
FAN PULLEY DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C -C DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/05/12 Page: 19
SYSTEM AHU-2.0 RIGHT
AHU-1.5
LOCATION
CLOSET
CLOSET
AREA SERVED
ROOM 203
ROOM 204
MANUFACTURER
ENVIRO iEC
ENVIRO TEC
MODEL NUMBER
CDV
CDV
SERIAL NUMBER
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. I 1L / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
MOTOR PULLEY
FCU110815-0413
DESIGN
800
800
0
NS
NS
NS
DESIGN
1/4/60
208/1
2.2
NS
MEASURED
790
790
0
NA
NA
MED.
MEASURED
Y4/60
207/1
1.5
MED.
DIRECT DRIVE
FCU110815-04B
DESIGN
475
475
0
NS
NS
NS
DESIGN
W60
208/1
2.2
NS
FAN PULLEY
DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA
MEASURED
658
658
0
NA
NA
LOW
MEASURED
1/4/60
204/1
.98
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/05/12 Page: 20
SYSTEM AHU-1.5 LEFT
LOCATION
AREA SERVED
MANUFACTURER
AHU-1.5 RIGHT
CLOSET
CLOSET
ROOM 205
ROOM 207
ENVIRO ..1EC
ENVIRO 1'EC
MODEL NUMBER
CDV
CDV
SERIAL NUMBER
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. 1'1L / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
MOTOR PULLEY
FAN PULLEY
BELTS / POSITION / C-C
OUTSIDE AIR DUCT SIZE
FCU110815-04
FCUI10815-04B
DESIGN
MEASURED DESIGN
MEASURED
575
601
575
642
575
0
601
0
NS
NS
NS
NA
NA
LOW
575
0
NS
642
0
NA
NS
NA
DESIGN MEASURED
NS LOW
DESIGN MEASURED
W60
208/1
2.2
NS
1/4/60
207/1
.98
LOW
1/4/60
208/1
2.2
NS
1/4/60
207/1
.97
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/05/12 Page: 21
SYSTEM
AHU-1.5 LEFT
LOCATION
AREA SERVED
MANUFACTURER
AHU-I .5 LEFT
CLOSET
ROOM 208
ENVIRO TEC
CLOSET
ROOM 209
ENVIRO TEC
MODEL NUMBER
SERIAL NUMBER
CDV
FCU110815-B4
CDV
FCU110815-B4
FAN DATA
DESIGN
MEASURED
DESIGN
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. TTL / EXT
INLET / DISCHARGE
FAN RPM
575
575
0
NS
NS
NS
642
642
0
NA
NA
LOW
575
575
0
NS
NS
NS
MEASURED
633
633
0
NA
NA
LOW
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
DESIGN
MEASURED
DESIGN
MEASURED
1/4/60
1/4/60
V4/60
208/1
207/1
208/1
2.2
.97
2.2
NS
LOW
NS
1/4/60
208/1
.99
LOW
MOTOR PULLEY
FAN PULLEY
BELTS / POSITION / C-C
OUTSIDE AIR DUCT SIZE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
an
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /05/12 Page: 22
SYSTEM
AHU -1.5 RIGHT
AHU -1.5 RIGHT
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
SERIAL NUMBER
CLOSET
ROOM 210
ENVIRO TEC
CDV
FCU110815 -04B
CLOSET
ROOM 211
ENVIRO TEC
CDV
FCU110815 -04B
FAN DATA
DESIGN
MEASURED
DESIGN
MEASURED
TOTAL CFM * OUTLET
575
684
575
673
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. TTL / EXT
INLET / DISCHARGE
FAN RPM
575
0
NS
NS
NS
684
0
NA
NA
LOW
575
0
NS
NS
NS
673
0
NA
NA
LOW
MOTOR DATA
DESIGN
MEASURED DESIGN
MEASURED
MOTOR HP / HZ
%/60
'/,/60
'//60
'/,/60
VOLTAGE / PHASE
208/1
207/1
208/1
207/1
AMPERAGE / SF
MOTOR RPM
MOTOR PULLEY
FAN PULLEY
BELTS / POSITION / C -C
OUTSIDE AIR DUCT SIZE
2.2
NS
DIRECT DRIVE
.98
2.2
.97
LOW
NS
LOW
DIRECT DRIVE
DIRECT DRIVE
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
an
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /06/12
Page: 23
FAN NO
AHU -1.5 LEFT
AHU -1.5 LEFT
AHU -2.0 LEFT
LOCATION
CLOSET
CLOSET
CLOSET
SERVING
ROOM 212
ROOM 213
ROOM 214
MODEL NO
CDV
CDV
CDV
SERIAL NO
FCU110815 -04
FCU110815 -04
FCUI 10813 -04
MFGR
ENVIRO TECH
ENVIRO TECH
ENVIRO TECH
FAN DATA
DESIGN
MEASURED
DESIGN
MEASURED
DESIGN
MEASURED
DESIGN CFM
575
637
575
644
800
885
RETURN AIR
575
637
575
644
800
885
OUTSIDE AIR
0
0
0
0
0
0
STATIC
PRESSURE
NS
NA
NS
NA
NS
NA
RPM FAN
NS
LOW
NS
LOW
NS
MED.
HP /HZ
'/4/60
'/4/60
'/4/60
'/4/60
'/4/60
'//60
VOLTAGE
208
207
208
205
208
206
PHASE
1
1
1
1
1
1
AMPERAGE / SF
2
.98
2
.97
2
13
RPM MOTOR
NS
LOW
NS
LOW
NS
MED.
MTR PULLEY
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
BELT /
POSITION / C-C
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
aB
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/06/12
Page: 24
FAN NO
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
AHU -L5 LEFT
AHU -1.5 RIGHT AHU -2.0 LEFT
CLOSET
CLOSET CLOSET
ROOM 231
ROOM 232 ROOM 233
CDV
CDV CDV
FCU110815 -04
FCU110815 -04 FCU110815 -04
ENVIO 1'EC
ENVIO TEC ENVIO 'lEC
DESIGN
MEASURED
DESIGN
MEASURED
DESIGN MEASURED
575
653 575
663 800
845
575
653 575
663
800
845
0
0 I 0
0
0
0
NS
NA
NS
NA
NS
NA
NS
LOW NS
LOW
NS
%4/60
1/4/60
1/4/60
1/4/60 '/4/60
208
207 208
208
208
1
1
1
1
1
2
.98
2
.97 2
MED.
/60
205
1
1.3
NS LOW NS LOW
DIRECT DRIVE DIRECT DRIVE
NS MED.
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
BELT /
POSITION / C -C
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
CM
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/06/12 Page: 25
FAN NO
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
AHU -1.5 LEFT
AHU -1.5 AHU -1.5
CLOSET
CLOSET CLOSET
ROOM 234
ROOM 235 ROOM 237
CDV
CDV CDV
FCUI 10815 -04
FCUI 10815 -04 FCU110815 -04
ENVIRO TEC
ENVIRO TEC ENVIRO TEC
DESIGN
MEASURED
DESIGN
MEASURED DESIGN MEASURED
475
601 575
633
575
647
475
601
575
633 575
647
0
0
0
0 0
0
NS
NA
NS
NA
NS
NA
NS
LOW NS
LOW
NS
'/ / 60
1 /a /60 1//60
%4/60 %/60
208
207 208
207 208
1
2
1.0 2
.99 2
MED.
1A /60
207
1
1.1
NS LOW
DIRECT DRIVE
NS LOW
DIRECT DRIVE
NS MED.
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
BELT /
POSITION / C -C
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
GB
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/06/12
Page: 26
FAN NO
AHU -1.5
AHU -1.5 AHU -1.5 LEFT
LOCATION
SERVING
MODEL NO
SERIAL NO
CLOSET
ROOM 238
CLOSET
ROOM 239
CDV
FCU110815 -04B
CDV
FCU110815 -04
CLOSET
ROOM 240
CDV
FCU110815 -04
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
ENVIRO TEC
DESIGN MEASURED
575 638
575 638
0 0
NS NA
ENVIRO TEC ENVIRO 1EC
DESIGN MEASURED DESIGN MEASURED
575 651 575 652
575 651 575 652
0 0 0 0
NS NA NS NA
NS LOW
NS LOW NS MED
HP /HZ '/4/60 1/4/60 '/4/60 '/4/60 '/a /60 1//60
VOLTAGE
PHASE
208 207 208 207 208 207
AMPERAGE / SF 2 1.0
2
RPM MOTOR NS
LOW NS
.99
LOW
2
NS
1.1
MED.
MTR PULLEY
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
BELT /
POSITION / C-C
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
cm
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12
Page: 27
FAN NO AHU -1.5
AHU -1.5
AHU -1.5
LOCATION
CLOSET CLOSET
CLOSET
SERVING ROOM 241 ROOM 242 ROOM 243
MODEL NO CDV
CDV
CDV
SERIAL NO FCU 110815 -04
FCU110815 -04
FCU110815 -04
MFGR ENVIRO TEC
ENVIRO TEC ENVIRO TEC
FAN DATA DESIGN
MEASURED
DESIGN
MEASURED DESIGN MEASURED
DESIGN CFM 575
649 575
657
575
648
RETURN AIR 575
649
575
657 575
648
OUTSIDE AIR 0
0
0
0 0
0
STATIC
PRESSURE
NS
NA
NS
NA
NS
NA
RPM FAN NS
LOW
NS
LOW NS
HP /HZ '/4/60
'/4/60
'//60
'/4/60
/60
VOLTAGE 208
207
208
208 208
PHASE 1
1
1
AMPERAGE / SF 2
.98
2
.97 2
LOW
%4/60
207
1
.98
RPM MOTOR NS LOW
MTR PULLEY DIRECT DRIVE
NS LOW
DIRECT DRIVE
NS LOW
DIRECT DRIVE
FAN PULLEY DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
BELT / DIRECT DRIVE
POSITION / C -C
DIRECT DRIVE DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
crB
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12
Page: 28
FAN NO
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
AHU -2.0
AHU -1.5 AHU -1.5
CLOSET
CLOSET CLOSET
ROOM 244
ROOM 301 ROOM 302
CDV
CDV CDV
FCU110815 -04B
FCU110815 -04 FCU110815 -04
ENVIRO TEC
ENVIRO TEC ENVIRO TEC
DESIGN
MEASURED
DESIGN
MEASURED
DESIGN MEASURED
800
885 575
648
575
637
800
885 575
648
575
637
0
0 0
0
0
0
NS
NA NS
NA NS
NA
NS
MED. NS
LOW
NS
LOW
'/4/60
%4/60 '/4/60
'/4/60 '/4/60
'/4/60
208
207 208
207 208
207
1
1
2
1.3 2.2
.97 2.2
.98
NS
MED NS
LOW NS
LOW
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
BELT / DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
POSITION / C -C
Comments:
Readings By: Bart Serino, Craig Maurer
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12 Page: 29
SYSTEM AHU-2.0
AHU-1-5
LOCATION CLOSET
CLOSET
AREA SERVED ROOM 303
ROOM 304
MANUFACTURER ENVIRO TEC
MODEL NUMBER CDV
ENVIRO TEC
CDV
SERIAL NUMBER NS
NS
FAN DATA DESIGN
TOTAL CFM * OUTLET 800
RETURN AIR CFM 800
MEASURED
830
830
DESIGN
475
475
MEASURED
589
589
OUTSIDE AIR CFM 0
0
0
0
S.P. 11L / EXT
INLET / DISCHARGE
NS
NS
NA
NA
NS
NS
NA
NA
FAN RPM NS
MED.
MOTOR DATA DESIGN
MEASURED
NS
DESIGN
LOW
MEASURED
MOTOR HP / HZ 1/4/60
1/4/60
'/4/60
1/4/60
VOLTAGE / PHASE
AMPERAGE / SF
208/1
207
208/1
207
2.2
1.2
2.2
.97
MOTOR RPM NS
MED.
NS
LOW
MOTOR PULLEY DIRECT DRIVE
DIRECT DRIVE
FAN PULLEY DIRECT DRIVE
DIRECT DRIVE
BELTS / POSITION / DIRECT DRIVE
DIRECT DRIVE
OUTSIDE AIR DUCT SIZE NA
NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12 Page: 30
SYSTEM
AHU-1.5 AHU-1-5
LOCATION
CLOSET CLOSET
AREA SERVED
ROOM 305 ROOM 307
MANUFACTURER
ENVIRO 1EC ENVIRO TEC
MODEL NUMBER
CDV CDV
SERIAL NUMBER
--r
FAN DATA DESIGN
NS NS
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET 575
634 575
643
RETURN AIR CFM 575
634 575
643
OUTSIDE AIR CFM 0
0 0
0
S.P. I 11, / EXT NS
NA NS
NA
INLET / DISCHARGE NS
NA NS
NA
FAN RPM NS
LOW NS
LOW
MOTOR DATA DESIGN
MEASURED DESIGN MEASURED
MOTOR HP / HZ V4/60
1/4/60 1/4/60
1/4/60
VOLTAGE / PHASE 208/1
208 208/1
207
AMPERAGE / SF 2
.98 2.2
.97
MOTOR RPM NS
LOW NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12 Page: 31
SYSTEM
AHU -1.5 AHU -1 -5
LOCATION
CLOSET CLOSET
AREA SERVED
ROOM 308 ROOM 309
MANUFACTURER
ENVIRO TEC ENVIRO TEC
MODEL NUMBER
CDV CDV
SERIAL NUMBER
NS NS
FAN DATA
DESIGN
MEASURED DESIGN
MEASURED
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P.TTL /EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
575
637
575
637
0
NS
0
NA
NS
NS
NA
LOW
DESIGN MEASURED
1/4/60
1/4/60
575
575
0
647
647
0
NS
NS
NA
NA
NS
DESIGN
1/4/60
LOW
MEASURED
1/4/60
VOLTAGE / PHASE
208/1
207
208/1
208
AMPERAGE / SF
2
.98
2
.99
MOTOR RPM NS
LOW NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
aB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06 /07/12 Page: 32
SYSTEM
LOCATION
AREA SERVED
MANUFACTURER
MODEL NUMBER
SERIAL NUMBER
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. 1"1'L / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
MOTOR PULLEY
AHU -1.5 AHU -1 -5
CLOSET
CLOSET
ROOM 310
ROOM 311
ENVIRO '1'EC
ENVIRO TEC
CDV
CDV
NS
DESIGN
575
575
0
NS
NS
NS
DESIGN
1/4/60
208/1
2.2
NS
MEASURED
632
632
0
NA
NA
LOW
MEASURED
1/4/60
208
.97
LOW
DIRECT DRIVE
NS
DESIGN
575
575
0
NS
MEASURED
643
643
0
NA
NS
NS
DESIGN
1/4/60
208/1
2.2
NS
FAN PULLEY
DIRECT DRIVE
BELTS / POSITION / C -C
DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA
NA
LOW
MEASURED
%/60
207
.98
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
a13
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12 Page: 33
SYSTEM
AHU 1.5 AHU 1 5
LOCATION
CLOSET
CLOSET
AREA SERVED
ROOM 312
ROOM 313
MANUFACTURER
ENVIRO TEC
ENVIRO TEC
MODEL NUMBER
CDV
CDV
SERIAL NUMBER
FAN DATA
TOTAL CFM * OUTLET
RETURN AIR CFM
OUTSIDE AIR CFM
S.P. TIL / EXT
INLET / DISCHARGE
FAN RPM
MOTOR DATA
MOTOR HP / HZ
NS
NS
DESIGN
575
575
0
MEASURED DESIGN
659
659
0
NS NA
NS NA
NS LOW
575
575
0
NS
NS
NS
DESIGN MEASURED DESIGN
MEASURED
639
639
0
NA
NA
LOW
MEASURED
'/,/60
' /a /60
'/4/60
'/./60
VOLTAGE / PHASE
208/1
207
208/1
208
AMPERAGE / SF
2
.98
2
.97
MOTOR RPM NS
LOW NS
LOW
MOTOR PULLEY
DIRECT DRIVE DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE DIRECT DRIVE
OUTSIDE AIR DUCT SI7F
NA NA
Comments:
Readings By: Craig Maurer, Bart Serino
as
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12 Page: 34
SYSTEM
AHU -2.0
LOCATION
CLOSET
AREA SERVED
ROOM 314
MANUFACTURER
MODEL NUMBER
ENVIRO TEC
CDV
SERIAL NUMBER
NS
FAN DATA
DESIGN
MEASURED
DESIGN
MEASURED
1
TOTAL CFM * OUTLET
800
835
RETURN AIR CFM
800
835
OUTSIDE AIR CFM
0
0
S.P. 't'IL / EXT
INLET / DISCHARGE
NS
NS
NA
NA
FAN RPM
NS
MED.
MOTOR DATA
DESIGN
MEASURED
DESIGN
MEASURED
MOTOR HP / HZ
'/4/60
'/,/60
VOLTAGE / PHASE
208/1
207
AMPERAGE / SF
2
1.3
MOTOR RPM
NS
MED.
MOTOR PULLEY
FAN PULLEY
DIRECT DRIVE
DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
GB
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
FAN NO
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
Date: 06/07/12
Page: 35
AHU -1.5 LEFT
AHU -1.5 RIGHT AHU -2.0 LEFT
CLOSET
CLOSET CLOSET
ROOM 331
ROOM 332 ROOM 333
CDV
CDV CDV
FCU110815 -04
FCU110815 -04B FCU110815 -04
ENVIRO TEC
ENVIRO TEC ENVIRO TEC
FAN DATA DESIGN
DESIGN CFM 575
RETURN AIR 575
OUTSIDE AIR 0
STATIC NS
PRESSURE
RPM FAN NS
HP /HZ '4/60
VOLTAGE 208
PHASE 1
AMPERAGE / SF 2
RPM MOTOR NS
MTR PULLEY
FAN PULLEY
MEASURED DESIGN
MEASURED DESIGN MEASURED
654 575
662
800
883
654 575
662
800
883
0
0
0 0
0
NA NS
NA NS
NA
LOW NS
LOW NS
%4/60 %/60
'/4/60 '/4/60
207 208
208 208
.98 2
.97 2
BELT /
POSITION / C-C
Comments:
LOW NS
LOW NS
MED.
'/ / 60
207
1
1.2
MED.
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE
Readings By: Bart Serino, Craig Maurer
DIRECT DRIVE DIRECT DRIVE
GB
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12
Page: 36
FAN NO
LOCATION
SERVING
AHU -1.5
AHU -1.5
AHU -1.5
CLOSET CLOSET
ROOM 334 ROOM 335
CLOSET
ROOM 337
MODEL NO
CDV
CDV CDV
SERIAL NO
MFGR
FCU110815 -04 FCU110815 -04B FCU110815 -04
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
ENVIRO TEC ENVIRO TEC ENVIRO TEC
DESIGN MEASURED DESIGN
4-
MEASURED DESIGN MEASURED
475
989
575
475
989
575
0
0
0
NS
NA
NS
662
662
0
NA
575
575
0
NS
639
639
0
NA
NS
LOW NS
LOW
NS
LOW
1/4/60
1/4/60
1/4/60
'/4/60
%4/60
1/4/60
208
207
208
208
208
207
PHASE
1
1
1
1
1
1
AMPERAGE / SF
2
.97
2
.98
2
.98
RPM MOTOR
MTR PULLEY
FAN PULLEY
BELT /
POSITION / C-C
NS 1 LOW
NS
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
NS LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
Comments:
Readings By: Bart Serino, Craig Maurer
07'13
CERTIFIED
TEST & BALANCE
Alit HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12
Page: 37
FAN NO
AHU -1.5
LOCATION
CLOSET
1
AHU -1.5
AHU -1.5
CLOSET
CLOSET
SERVING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
BELT /
POSITION / C-C
Comments:
ROOM 338
ROOM 339 ROOM 340
CDV
FCU110815 -04B
ENVIRO TEC
DESIGN MEASURED
575
575
0
NS
NS
1/4/60
208
1
2.2
NS
674
674
0
NA
LOW
1/4/60
207
1
.97
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
Readings By: Bart Serino, Craig Maurer
CDV
FCU110815 -04B
ENVIRO TEC
DESIGN MEASURED
575
575
0
NS
NS
1 /a /60
208
1
2.2
NS
653
653
0
NA
LOW
1/4/60
208
1
.98
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
CDV
FCU1 10815 -04B
ENVIRO TEC
DESIGN MEASURED
575
575
0
NS
NS
1/4/60
208
1
2.2
NS
659
659
0
NA
LOW
1 /a /60
207
1
.97
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
an
CERTIFIED
TEST & BALANCE
AIR HANDLER UNIT DATA SHEET
Project: BARRY UNIVERSITY
Date: 06/07/12
Page: 38
FAN NO AHU -1.5
AHU -1.5 AHU -1.5
LOCATION CLOSET CLOSET CLOSET
SERVING
ROOM 341
ROOM 342
ROOM 343
MODEL NO
CDV
CDV
CDV
SERIAL NO
FCU110815 -04
FCU110815 -04
FCU110815 -04
MFGR
FAN DATA
DESIGN CFM
RETURN AIR
OUTSIDE AIR
STATIC
PRESSURE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
BELT /
POSITION / C -C
Comments:
ENVIRO TEC
DESIGN
575
575
0
NS
NS
'/4/60
208
1
2
NS
MEASURED
647
647
0
NA
LOW
%4/60
207
1
.98
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
Readings By: Bart Serino, Craig Maurer
ENVIRO TEC
DESIGN
575
575
0
NS
NS
'/4/60
208
1
2
NS
MEASURED
659
659
0
NA
LOW
'14/60
207
1
.97
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
ENVIRO TEC
DESIGN
575
575
0
NS
NS
'/4/60
208
1
2
NS
MEASURED
661
661
0
NA
LOW
'/4/60
207
1
.98
LOW
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
aB
CERTIFIED
TEST & BALANCE
AIR HANDLING UNIT DATA SHEET
Project: BARRY UNIVERSITY
SYSTEM
AHU -2
Date: 06/07/12 Page: 39
LOCATION
CLOSET
AREA SERVED
ROOM 344
MANUFACTURER
ENVIRO 'rEC
MODEL NUMBER
CDV
SERIAL NUMBER
FCU10815 -045
FAN DATA
DESIGN
MEASURED
DESIGN
MEASURED
TOTAL CFM * OUTLET
800
809
RETURN AIR CFM
800
809
OUTSIDE AIR CFM
S.P. TTL / EXT
0
NS
0
NA
INLET / DISCHARGE
NS
NA
FAN RPM
NS
MED.
MOTOR DATA
MOTOR HP / HZ
VOLTAGE / PHASE
AMPERAGE / SF
MOTOR RPM
DESIGN
MEASURED
DESIGN
MEASURED
'/60
%/60
208/1
2.2
NS
208
1.3
MED.
MOTOR PULLEY
DIRECT DRIVE
FAN PULLEY
DIRECT DRIVE
BELTS / POSITION / C-C
DIRECT DRIVE
OUTSIDE AIR DUCT SIZE
NA
Comments:
Readings By: Craig Maurer, Bart Serino
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
EXHAUST FAN DATA SHEET
Date: 06N09/12
Page: 40
FAN NO
LOCATION
SERVING
EF -2
EF -3
EF-4
CEILING
CEILING
CRII,ING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
S.P.
SUCTION /
DISCHARGE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
BELT /
POSITION / C -C
Comments:
MEN
VQ200
NS
ACME
DESIGN
150
NS
NS
NS
NS
120
1
1.8
NS
MEASURED
188
NA
NA
NA
NA
122
1
1.1
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
Readings By: Craig Maurer
WOMEN
VQ200
NS
ACME
DESIGN
150
NS
NS
NS
NS
120
1
1.8
NS
MEASURED
175
NA
NA
NA
NA
121
1
1.1
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
CHILL PUMP ROOM
VQ200
NS
ACME
DESIGN
200
NS
NS
NS
NS
120
1
1.8
NS
MEASURED
252
NA
NA
NA
NA
NA
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
cn3
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
EXHAUST FAN DATA SHEET
FAN NO EF -6
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
Date: 06/09/12
Page: 41
MAIN ELECTRIC
FAN DATA
VQ500
NS
ACME
DESIGN MEASURED
ROOF
TRASH CHUTE
PDU100RFH
11J1745 -12
ACME
DESIGN MEASURED
DESIGN MEASURED
DESIGN CFM
S.P.
SUCTION /
DISCHARGE
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
BELT /
POSITION / C -C
Comments:
Readings By: Craig Maurer
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
DIRECT DRIVE
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
EXHAUST FAN DATA SHEET
Date: 06/07/12
Page: 42
FAN NO
LOCATION
SERVING
MODEL NO
SERIAL NO
MFGR
FAN DATA
DESIGN CFM
S.P.
SUCTION /
DISCHARGE
RPM FAN
HP /HZ
VOLTAGE
PHASE
AMPERAGE / SF
RPM MOTOR
MTR PULLEY
FAN PULLEY
EF -8 EF -9
CEILING CEILING
TRASH ROOM
ELEVATOR MECH. ROOM
VQ500
VQ500
NS NS
ACME ACME
DESIGN
400
MEASURED DESIGN
451
400
MEASURED DESIGN MEASURED
424
NS
NA
NS
NA
NS
NA
NS
NA
NS
NA
NS
NA
NS
NA
NS
NS
115
121
115
121
1
1
1
1
2.2
1.9
2.2
2.0
NS
NA NS
NA
DIRECT DRIVE DIRECT DRIVE
DIRECT DRIVE DIRECT DRIVE
BELT / DIRECT DRIVE 1 DIRECT DRIVE
POSITION / C -C
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU -1
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 05/21/12 Page: 43
Floor: 3RD NORTH
TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA
FPM
CFM
#1
#2
FPM
CFM
CORR
1
CD
24 X 24
1.0
85
59
89
308
2
CD
6X6
1.0
60
133
66
309
3
CD
6X6
1.0
60
105
310
4
311
5
CD
CD
6X6
1.0
60
120
64
62
6X6
1.0
60
130
65
312
6
CD
6X6
1.0
60
89
65
313
7
CD
6X6
1.0
60
81
64
CORR
8
CD
24 X 24
1.0
85
65
81
314 9 CD 6 X 6 1.0 60 96 62
306 10 SW 8 X 6 1.0 100 155 108
307 11 CD 6 X 6 1.0 60 94 65
320 12 SW 8 X 6 1.0 100 85 89
305 13 CD 6 X 6 1.0 60 120 60
CORR 14 CD 24 X 24 1.0 85 74 79
CORR
15
CD
24 X 24
1.0
STTL
85
1080
77
1603
STTL
84
1103
Comments:
Readings By: Craig Maurer
CTI3
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU -1
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
NO.
TYPE
SIZE AREA
CORR
208
209
210
211
212
213
CORR
CORR
214
206
207
220
CORR
205
16
CD
6X6 1.0
DESIGN
i
FPM
CFM
85
Date: 05/21/12 Page: 44
Floor: 2ND NORTH
TEST CFM
#1
#2
86
17
CD
6X6 1.0
60
132
18
CD
6X6 1.0
60
110
81
65
61
19
20
CD
CD
6X6 1.0
60
139
64
6X6 1.0
60
166
21
CD
6X6 1.0
60
112
22
CD
6X6 1.0
60
125
23
CD
6X6 1.0
60
91
24
CD
6X6 1.0
85
87
25
26
CD
SW
6X6 1.0
60
118
8X6 1.0
100
110
27
28
CD
sw
6X6 1.0
60
101
8X6 1.0
100
115
29
CD
6X6 1.0
85
45
30
CD
6X6 1.0
60
81
S'1 "1'L
1080
1618
S1 1L
64
63
60
78
84
64
109
64
105
81
62
1105
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU -1
AIR OUTLET DATA SHEET
Date: 05/21/12 Page: 45
Floor: 1ST NORTH
AREA
SERVED
OUTLET
NO. TYPE SIZE AREA
CORR 31 CD 24 X 24 1.0
108
32 CD
6X6
1.0
DESIGN TEST CFM MEASURED
FPM CFM #1 #2 FPM CFM
85 71
60
123
111 35 CD 6X6 1.0
112 36 CD 6X6
113 37 CD 6X6 1.0
CORR 38 CD 24 X 24 1.0
114 39 CD 6 X 6 1.0
1.0
60 126
60 84
60 106
60 102
85 85
60 117
58
61
62
85
63
106 40 SW 7'/4 X 5'/4 .26 385 100 388/101 354 92
=11111111111111111n11 61111111M111111.11111111111111111111
120
42 SW 7'/4 X 5'A
.26 385 100 312/94
CORR 43 CD 24 X 24 1.0
105
44
CD
6X6
1.0
369 96
85 54 79
60 11I 66
CORR 45 CD 24 X 24 1.0 85 59 77
STTL 1080 1446 STTL 1068
TOTAL 3240 TOTAL 3276
L
Comments:
Readings By: Craig Maurer
am
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU-2
AIR OUTLET DATA SHEET
Date: 05/21/12 Page: 46
Floor: 18T
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE AREA FPM CFM
#1 #2 FPM CFM
STORE 1
CORR 2 CD 24X24 1.0
137 3 CD 12 X 12 1.0
136 4
AHU1 -8 5 DUCT
6
7 DUCT
SW
8X6
1.0
50
284
53
85
149
91
100
CD
12 X 12
1.0
100
CORR
AHU1 -5
7X6
.29
207
60
CD
24 X 24
1.0
85
6X6
.25
160
40
152 8
CORR 9
CD
24 X 24
1.0
300
186
188
259/75
96
109
108
224 65
89
104/26
168 42
218
278
CD
24 X 24
1.0
85
110
92
CORR 10 CD 24 X 24 1.0
85
96
90
STI'L
990
1612
S'1'1'L
1017
Comments:
Readings By: Craig Maurer
......CTI3
........ .
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU -2
AIR OUTLET DATA SHEET
Date: 05/21/12 Page: 47
Floor: 1ST
AREA
SERVED
OUTLET
DESIGN TEST CFM
MEASURED
NO. TYPE
237
11
248
12
CORR
SIZE AREA FPM CFM #1 #2
SW 6X6
CD 71/4X51/4
13 SW 24 X 24 1.0
1.0
60
FPM CFM
153
64
.26 384 100 338/88
419
109
235 14 CD 6X6 1.0
CORR 15 CD 24 X 24 1.0
239 16 CD 6 X 6 1.0
238 17 CD 6 X 6
CORR 18 CD 24 X 24
241 19 CD 6X6 1.0
85 99
60 172
85 88
60 134
90
65
92
62
1.0
60 735
60
1.0
85
72
87
240 20 CD 6 X 6 1.0
60 99
236
25
CD
6X6
1.0
50
40
52
SI'I L 1030
1605
STTL 1092
Comments:
Readings By: Craig Maurer
CM
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU -2
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
NO.
TYPE
SIZE
AREA
1
DESIGN
Date: 05/21/12 Page: 48
Floor. 3RD
TEST CFM
MEASURED
FPM
CFM
#1
#2
FPM
CFM
337
336
348
CORR
335
339
338
341
CORR
CORR
340
343
342 38
CORR 39
344 40
26
27
28
29
30
31
32
33
34
35
36
37
CD
CD
6X6
1.0
60
104
24 X 24
1.0
50
90
SW
CD
CD
CD
CD
CD
CD
CD
CD
CD
CD
CD
CD
7'X5Ya
24 X 24
6X6
6X6
6X6
6X6
.26
1.0
1.0
1.0
1.0
1.0
100
85
60
566/147
60
60
60
68
93
408
125
135
115
24 X 24
1.0
85
63
24 X 24
6X6
6X6
6X6
24 X 24
6X6
1.0
1.0
1.0
1.0
1.0
1.0
S'ITL
85
60
60
60
85
60
1030
88
104
93
97
68
122
1512
STTL
TOTAL
65
54
106
89
64
65
60
64
91
90
62
65
60
87
63
1085
3194
Comments:
Readings By: Craig Maurer
1
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU-3
AIR OUTLET DATA SHEET
Date: 05/21/12 Page: 49
Floor: 1ST
AREA
SERVED
OUTLET
DESIGN TEST CFM
MEASURED
NO,
TYPE SIZE
CORR
102
101
117
CORR
104
103
118
CORR
CORR
AHU1 -4
133
1
CD
24 X 24
AREA FPM
1.0
ICFM #1 I
#2
FPM
CFM
85 72
86
2
CD
6X6 1.0
60 81
64
3
4
CD
CD
6X6 1.0
60 74
65
6X6 1.0
60 92
64
5
6
CD
CD
24 X 24 1.0
85 66
6X6 1.0
60 81
7
CD
6X6 1.0
60 79
8
SW
71/4X5 1A .26 385
100 392/102
9
10
CD
SW
24 X 24 1.0
85 69
24 X 24 1.0
85 65
11
DUCT
6 X 6 .25 200
50 220/55
220
12
SW
6X6 1.0
60 86
S1"1 'L
850 922
S'1'1L
79
61
58
107
79
77
55
63
858
Comments:
Readings By: Craig Maurer
(TB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTU -3
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET DESIGN
Date: 05/21/12 Page: 50
Floor 2N
TEST CFM
MEASURED
NO. TYPE
SIZE
AREA FPM CFM
#1
#2
FPM CFM
CORR
202
201
CORR
217
203
218
200
CORR 21
231 22
232 23
CORR 24
234 25
249 26
233 27
247 28
STAIR 29
13
14
15
16
17
18
19
20
CD 24 X 24
CD 6X6
CD 6X6
CD 24 X 24
62
85
89
63
85
64
62
82
SW 7 1/4X5
CD 6X6
427/111
101
SW 7'4X5'/4
CD 24 X 24
CD 24X24
CD 6X6
CD 6X6
473/123
63
1.0
1.0
85
60
59
400 104
65
392 102
70
81
104
64
1.0
60
132
CD 24 X 24
CD 6X6
1.0
1.0
85
60
68
112
SW 7'4X5'/4
CD 6X6
SW 7 1/4X5
SW 12X8
.26
1.0
.26
1.0
Comments:
Readings By: Craig Maurer
100
60
404/105
100
107
352/92
200
STIL 1435
163
1489
65
78
63
408 106
62
400 104
184
STTL 1442
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: O/A RTES.-3
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 05/21/12 Page: 51
Floor: 3R'
TEST CFM
MEASURED
NO, 1 TYPE
SIZE 1 AREA
304
30 CD
6X6 1 1.0
FPM
CFM
#1
#2
FPM
CFM
60 81
62
CORR
31
CD 24 X 24 1 1.0
85
0
84
302
301
CORR
32
33
34
CD 6X6
CD 6X6
1.0
60
84
60
1.0
60
82
65
CD 24 X 24 1 1.0
85
50
80
317
35
SW 71/4X5 'A 1 1.0
100
126
108
303
36
CD
24 X 24
1.0
60
69
65
318
37
SW
7 %X5'h
1.0
100
103
109
300
38
CD
24 X 24
1.0
75
53
70
332
39
CD
6X6
1.0
60
104
66
331
40
CD
6X6
1.0
60
85
62
CORR
41
CD
24 X 24
1.0
85
59
79
CORR
42
CD
24 X 24
1.0
85
53
77
334
43
CD
6X6
1.0
60
81
64
349
44
SW
7Y4X51/
1.0
100
137
104
303
45
CD
24 X 24
1.0
60
33
62
347
46
SW
7'/X5Y4
.26
100
381/101
101
STAIR
47
CD
12X8
1.0
200
182
184
T
STTL
1435
S'1 1'L
1502
TTL
3913
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/05/12 Page: 52
Floor: 1
TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA
FPM
CFM
#1
AHU1 -1
LOBBY
LOBBY
STAIRW.
1
2
CD
CD
24 X24
1.0
400
383
#2
FPM
CFM
24X24
1.0
400
287
3
SW
12X8
1.0
100
166
TTL
900
836
ITL
355
348
100
803
AHU -1 -2
RECEPT.
RECEPT.
1
CD
24 X 24
1.0
400
377
2
CD
24 X 24
1.0
400
361
TTL
800
738
11L
377
361
738
AHU1 -3
LAUNDR
LAUNDR
AHU1 -4
MAIL RM
MAIL RM
MAIL V.
MAIL V.
OFFICE
OFFICE
1
CD
24 X 24
2
CD
24 X 24
1.0
450
341
1.0
450
436
11L
900
777
TTL
384
379
763
1
CD
24 X 24
1.0
150
162
2
CD
24 X 24
1.0
150
121
3
CD
24 X 24
1.0
150
147
4
CD
24 X 24
1.0
150
143
5
CD
24 X 24
1.0
100
102
6
CD
24 X 24
1.0
100
105
ITL
800
840
TTL
163
160
152
148
104
106
833
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 53
Floor: 1
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE, AREA FPM
CFM #1 #2 FPM CFM
AHU1 -5
148 1 CD
24 X 24
1.0
150
194
148
148 2 CD 24 X 24 1.0
150 183
138
150 3 CD
149 4 CD
24 X 24
1.0
150
199
143
24 X 24
1.0
150
182
141
i IL 600 758
TTL 570
AHU1 -6
MULTI P. 1 CD 12 X 12 1.0
50 123
54
MULTI P. 2
CD
24 X 24
1.0
240
237
240
MULTI P. 3 CD 24 X 24 1.0
240 235
231
MULTI P. 4
CD
24 X 24
1.0
240
245
235
MULTI P. 5 CD 24 X 24 1.0
240 224
MULTI P. 7 CD 24 X 24 1.0
240 196
234
Tit 1490 1486
i'IL 1474
Comments:
Readings By: Craig Maurer
crs
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AREA
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 05/24/12 Page: 54
Floor: 1
TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA FPM
CFM
#1
#2
FPM
CFM
AHU1 -7
C -STORE 1 CD 24 X 24 1.0 150 165 163
C -STORE 2 CD 24 X24 1.0 150 169 162
C -STORE 3 CD 24 X 24 1.0 200 173 190
C -STORE 4 CD 24 X 24 1.0 200 197 208
C -STORE
5
CD
24 X 24
1.0
200
170
196
C -STORE
6
CD
24 X 24
1.0
200
190
218
C -STORE
C -STORE
7
8
CD
CD
24 X 24
1.0
200
225
199
24 X 24
1.0
150
175
158
C -STORE
9
CD
24 X 24
1.0
150
200
159
11,
1600
1664
TTL
1653
AHU1 -7A
SERV
1
CD
24 X 24
1.0
480
121
451
SERV
2
CD
24 X 24
1.0
480
149
447
SERV
3
CD
24 X 24
1.0
325
119
311
SERV
4
CD
24 X 24
1.0
325
90
304
SERV
5
CD
24 X 24
1.0
50
0
54
SERV
6
CD
24 X 24
1.0
325
80
301
TTL
1985
559
1"1'L
1868
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: MU
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/05/12 Page: 55
Floor
TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA
#1
#2
FPM
CFM
AHU1 -7B
SAND.
SAND.
SAND.
SAND.
SAND.
SAND.
1
2
3
4
5
CD
CD
CD
CD
CD
24 X 24
24 X 24
24 X 24
24 X 24
24 X 24
1.0
1.0
1.0
1.0
1.0
6
CD
24 X 24
1.0
200
200
200
200
200
TTL 1200
175
189
201
173
204
215
1157
TTL
190
203
199
183
214
185
1174
Comments:
Readings By: Craig Maurer
.........au
........
CERTIFIED
TEST & BALANCE
Project: BARRY UN1VERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 56
Floor: l
MEASURED
FPM CFM
1
AHU1 -8
LOUNGE 1 CD 24 X 24 1.0
LOUNGE 2 CD 24 X 24 1.0
LOUNGE 3 CD 24 X 24 1.0
LOUNGE 4 CD 24 X 24 1.0
150 149 148
150 195
150 175
150
162
AHU1 -9
TELECOM 1 DUCT 19 X 12 �A 1.62
370 600 419/678 419 678
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
Date: 06/06/12 Page: 57
Floor: 2
DESIGN TEST CFM
MEASURED
NO.
TYPE SIZE AREA
FPM
CFM #1
#2
FPM
CFM
AHU2 -1
ELEV. L.
ELEV.L.
AHU2 -2
LOUNGE
LOUNGE
AHU2 -3
STUDY
STUDY
1
2
CD 24 X 24
CD 24X24
1.0
400 370
1.0
400 364
f1'L
800 734
TTL
372
364
734
1
2
CD 24 X 24
CD 24X24
1.0
400 392
1.0
400 378
ITL
800 770
TTL
392
378
770
1
CD 24 X 24
1.0
300 348
2
CD 24 X 24
1.0
300 374
1'i'L
600 722
ITL
284
291
575
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 58
Floor: 3
AREA
SERVED
OUTLET
DESIGN
TEST CFM
MEASURED
NO.
AHU3 -1
ELEV. L.
ELEV.L.
AHU3 -2
LOUNGE
LOUNGE
AHU3 -3
STUDY
STUDY
1
TYPE
SIZE AREA
FPM
CFM
#1
#2
FPM
CFM
1
2
CD 24X24 1.0
CD 24 X 24 1.0
TTL
500
500
1000
505
500
1005
TTL
505
500
1005
1
2
CD 24X24 1.0
CD 24 X 24 1.0
500
274
500
283
TTL
1000
557
'1'1L
502
492
994
1
CD 24 X 24 1.0
300
303
2
CD 24 X 24 1.0
300
260
TTL
600
563
TTL
291
281
572
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU -2, EXHAUST
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/08/12 Page: 59
Floor. 1
TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA
FPM
CFM
#1
#2
FPM
CFM
RM 133
KITCHEN
LIVING R
BED A
1
CD
12X6
1.0
100
84
90
2
3
CD
CD
12X 12
12 X 12
1.0
1.0
BED B 4 CD 12 X 12 1.0
BED C 5 CD 6 X 6 1.0
BEDD 6 CD 6X6 1.0
250
150
340
169
150 125
50 89
315
177
TTL 750 877
151
52
50
TTL 835
EXHAUST
BATH C 1 CD 10 X 10 1.0
75
83
BATH D 2 CD 10 X 10 1.0
75
75
Comments:
Readings By: Bart Serino
3 CD 10X10 1.0
GB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 60
Floor: 1
OUTLET
NO. TYPE SIZE
DESIGN
AREA FPM
TEST CFM MEASURED
CFM #1 #2 FPM CFM
SW
12X8
1.0
RM 102
A
TTL
250
226
254
75 102
96
575 622
'ITL 605
1 SW 12X8
1.0
250 340
322
B 2 SW 12X8 1.0
C 3
250 315
329
CD
10X10
1.0
75
0
0
IIL 575
655
I IL
651
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 61
Floor: 1
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE
AREA FPM
CFM #1 #2 FPM CFM
RM 103
A 1 SW
2 SW
C 3 SW
D 4 SW
12X8
12X8
12X8
1.0
1.0
1.0
200 203
150 ns
150 206
200 188
100 65
800 877
E 5 CD 12X12 1.0
TTL
205
160
210
95
TTL
845
A
B
1 SW
12X8
1.0
400 510
512
2
CD
6X6
1.0
75
120
83
TTL 475 630
1 "1'L 595
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AIM
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 62
Floor 1
AREA
SERVED
OUTLET
DESIGN
TEST CFM MEASURED
NO.
TYPE SIZE
AREA
RM 105
A
B
C
FPM I CFM
#1
#2 FPM CFM
1
SW 12X8
1.0
250
255
265
2
SW 12X8
1.0
250
285
3
CD 6X6
1.0
75
109
TTL 575
649
274
95
1'1'L 634
RM 107
A
B
C
1
SW 12X8
1.0
2
SW 12X8
1.0
3
CD 6X6
1.0
250
250
75
TTL 575
301
273
145
719
280
277
110
i°lL 667
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 63
System: AHU Floor: 1
DESIGN TEST CFM MEASURED
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 64
Floor: 1
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE AREA
FPM
CFM #1 #2 FPM CFM
RM 110
A 1 SW 12X8 1.0 250
B 2 SW 12X8 1.0 250
C 3 CD 6X6 1.0 75
TTL 575
280
140
710
1 "IL
279
95
644
RM 111
A
B
1 SW 12X8
1.0
250 310
277
2
SW
12X8
1.0
250
245
275
RM 112
A
B
1
SW
12X8
2 SW 12X8 1.0
C 3 CD 6X6 1.0
1.0
250 325
250 242
75 120
I'1'L 575 689
279
265
96
1'I'L 640
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: ABU
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 65
Floors 1
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE AREA
FPM CFM #1 #2 FPM CFM
RM 113
A
B
1 SW 12X8 1.0
250 290
271
2 SW 12X8 1.0
250 234
261
C
3
CD
6X6
1.0
75
110
94
TTL
575
634
1 1L
626
RM 114
A
1
SW
12X8
1.0
200 215
210
B
2
SW
12X8
1.0
150
190
170
C
3
SW
12X8
1.0
D 4 SW 12X8
1.0
E
5
CD
10X10
1.0
150
205
175
200 185
204
100
106
110
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
OUTLET
NO.
TYPE
SIZE
AREA
RM 201
A
B
C
RM 202
A
B
C
RM 203
A
B
C
D
E
DESIGN
Date: 06/05/12 Page: 66
Floor: 2
TEST CFM
MEASURED
FPM
CFM
#1
#2
FPM
1
SW
6X10
1.0
250
335
2
SW
6X10
1.0
250
268
3
CD
6X6
1.0
75
131
1 f
575
734
I1'L
280
277
110
657
1
SW
6X 10
1.0
250
241
2
SW
6X10
1.0
250
380
3
CD
6X6
1.0
75
130
ITL
575
751
275
285
111
671
1
SW
6X10
1.0
200
195
2
SW
6X10
1.0
150
195
3
SW
6X10
1.0
150
206
4
SW
6 X 10
1.0
200
230
5
CD
8X8
1.0
100
46
1 1'L
800
892
Comments:
Readings By: Bart Serino
210
140
162
198
80
790
11'L
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 67
Floor: 2
AREA
SERVED
OUTLET
DESIGN TEST CFM
MEASURED
RM 204
A
B
RM 205
A
B
C
RM 207
NO. TYPE SIZE AREA FPM CFM #1 #2 FPM CFM
1 SW 16X6 1.0
400 589
CD
t
TTL 475 723
1 SW 6 X 10 1.0
250 340
2
SW
6X10
1.0
250
233
658
3 CD 6X6
1.0
75 123
TTL 575 696
240
259
102
1"1'L 601
1 "1'L 575 703 '! TL 642
Comments:
Readings By: Bart Serino
CTB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 68
Floor: 2
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE AREA FPM CFM #1
#2 FPM CFM
RM 208
A
1 SW 6 X 10 1.0
2 SII!
e X 10 1.0
CD
250 328
270
250
75
95
TTL
575
683
FIL
642
RM 209
A 1 SW 6X10 1.0
250 329
271
B 2 SW 6 X 10 1.0
250 235
265
C
RM 210
CD
6X6
1.0
75
98
97
I IL 575 662
1 °l'L 633
A 1 SW 6 X 10 1.0
250 365
282
B 2 SW 6 X 10 1.0
250 260
310
C
3
CD
6X6
1.0
75
156
92
ITL 575
781
TTL
684
Comments:
Readings By: Bart Serino
GB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 69
Floor .2
AREA
SERVED
NO. TYPE SIZE AREA FPM
OUTLET
DESIGN TEST CFM MEASURED
CFM #1 #2 FPM CFM
RM 211
A
B
1 SW 6 X 10 1.0
250 295
283
2
SW
6 X 10
1.0
250
347
291
3
CD
6 X 6
1.0
75
140
99
1 I L 575 782
I IL 673
RM 212
A
B
1 SW 6 X 10 1.0
2 SW 6 X 10 1.0
3 CD 6 X 6
250 290
273
250 105
267
1.0
75
310
97
TTL 575
705
1 L
637
RM 213
A 1 SW 6 X 10 1.0 250 295
202
B
2
SW
6 X 10
1.0
250
296
285
3 CD 6 X 6
1.0
75 110
97
I IL
575 750
IrL
644
Comments:
Readings By: Bart Serino
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
Date: 06/05/12
Floor: 2
DESIGN TEST CFM
Page: 70
MEASURED
NO.
TYPE
SIZE
AREA
CFM #1
#2
FPM
CFM
RM 214
A
B
C
D
E
1
SW
6X10
1.0
200 285
230
2
3
4
SW
SW
SW
5
CD
6 X 10
6X10
6X10
8X8
1.0
1.0
1.0
I.0
150 210
150 208
200 219
1°l'L
100 95
800 1017
179
190
189
107
874
1 1L
227
167
169
215
107
885
Comments:
Readings By: Bart Serino
CTB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/06/12 Page: 71
Floor. 2
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE
SIZE AREA
FPM CFM
#1 #2 FPM CFM
RM 231
1 CD 10X 10 1.0
2
CD
10 X10
1.0
74
81
RM 234
RM 235
1 CD 10 X 10 1.0
2 CD 10X10 1.0
1 CD 10X 10 1.0
1 CD 10 X 10 1.0
68
70
83
84
2 CD 10 X10 1.0
85
RM237
1 CD 10X10 1.0
79
2 CD 10X10 1.0
85
Comments:
Readings By: Bart Serino
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
Date: 06/05/12 Page: 72
Floor: 2
DESIGN TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA
FPM
CFM #1
#2
FPM
CFM
A 1 SW 6 X 10 1.0
350 278
B 2 SW 6X10 1.0
CD 6X6 1.0
289 282
A 1 SW 6X10 1.0
350 280
B 2 SW 6 X 10 1.0
CD 6X6 1.0
250 275
110 108
11'L 575
SW 6 X 10 1.0
SW 6 X 10 1.0
C 3 SW 6 X 10 1.0
D 4 SW 6 X 10 1.0
195 204
248 155
CD 8 X 8 1.0
245 179
274 201
1 "1'L 800
Comments:
Readings By: Bart Serino
CrB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AIIU
AIR OUTLET DATA SHEET
Date: 06/06/12 Page: 73
Floor: 2
AREA
SERVED
OUTLET
DESIGN TEST CFM
MEASURED
NO. TYPE
SIZE
AREA
FPM
CFM #1
#2
FPM CFM
RM 234
A
B
RM 235
A
B
1 SW 6 X 10 1.0
400 520
504
2
CD
6 X 6
1.0
1 SW 6 X 10 1.0
2
SW 6 X 10
1.0
3
CD
6 X 6
1.0
75
TTL 475
250
250
110
97
630 TM 601
302 260
265
275
75
96
98
TTL 575 663
633
RM 237
A 1 SW 6 X 10 1.0
B 2 SW 6 X 10 1.0
C3CD6X6I.0
250
250
75
360 272
241 276
120
11L 575 721
99
647
RM 238
A 1 SW 6 X 10 1.0 250
296
276
B 2 SW 6 X 10 1.0 250
254
263
C 3 CD 6 X 6 1.0 75
105
99
I IL 575
655
I IL 638
Readings By: Bart Serino
cm
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/05/12 Page: 74
Floor. 2
AREA
SERVED
OUTLET
DESIGN
TEST CFM
NO.
TYPE SIZE
AREA
FPM
CFM
#1
#2
RM 239
A
B
C
RM 240
A
B
C
RM 241
A
B
C
1
SW 6 X 10
1.0
250
330
2
SW 6 X 10
1.0
250
257
3
CD 6X6
1.0
75
105
TTL
575
692
"1TL
279
276
96
651
1
SW 6X 10
1.0
250
320
2
SW 6 X 10
1.0
250
255
3
CD 6X6
1.0
75
130
TTL
575
705
11L
277
279
96
652
1
SW 6X10
1.0
250
315
2
SW 6X 10
1.0
250
260
3
SW 6X6
1.0
75
120
.F1'L
575
695
1`1L
278
272
99
649
Comments:
Readings By: Bart Serino
cm
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06106/12 Page: 75
Floor: 2
AREA
SERVED
NO.
TYPE SIZE
RM 242
A
B
C
RM 243
A
B
C
RM 244
A
B
C
D
E
AREA FPM
TEST CFM
CFM
#1
#2
1
SW 6 X 10
1.0
250
321
MEASURED
FPM
CFM
2
3
SW 6X 10
CD 6X6
1.0
1.0
TTL
250
75
575
291
170
782
l_l.L
281
275
101
657
1
SW 6X 10
1.0
250
290
2
SW 6 X 10
1.0
250
300
3
CD 6X6
1.0
75
101
'ITL
575
691
1'1'L
276
269
103
648
1
SW 6X 10
1.0
200
214
2
SW 6 X 10
1.0
150
210
3
SW 6 X 10
1.0
150
197
4
5
SW 6 X 10
CD 8X8
1.0
200
200
1.0
100
89
800
910
Comments:
Readings By: Bart Serino
Y1'L
217
178
174
221
95
885
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 76
System: AHU Floor: 3
AREA OUTLET DESIGN
SERVED
NO. TYPE SIZE AREA FPM
CFM
TEST CFM MEASURED
#1 #2 FPM CFM
RM 301
A 1 SW 6 X 10 1.0 250 275
B 2 SW 6 X 10 1.0 250 346
C 3 CD 6 X 6 1.0 75 120
281
279
88
TTL 575 741
'1'1L 648
RM 302
A 1 SW 6 X 10 1.0
B 2 SW 6X 10 1.0
C 3 CD 6X6 1.0
250 297
250 320
75 111
275
281
81
1'I'L 575 725 I IL 637
A 1 SW 6 X 10 1.0
B 2 SW 6X 10 1.0
200 197
150
167
205
155
C 3 SW 6 X 10 1.0 150 234 160
D 4 SW 6 X 10 1.0
E 5 CD 8X8
200
191
209
1.0
100 82
101
1'iL 800 891
1'i'L 830
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06107/12 Page: 77
Floor: 3
AREA
SERVED
OUTLET
DESIGN TEST CFM
MEASURED
NO. TYPE SIZE AREA FPM CFM #1 #2
FPM CFM
RM 304
t
1
TTL 475 622
11L 589
RM 305
A 1 SW 6X10 1.0
B
C
2
SW
6X10
1.0
250
250
3
CD
6X6
1.0
75
325
278
315
275
109
81
A
1
SW
6X 10
1.0
B 2 SW 6X10 1.0
C 3 CD 6X6 1.0
RM 308
250
250
75
rrL 575
292
281
107
80
724
1 I 643
A
1 SW
6 X 10
1.0
B 2 SW 6X10 1.0
C 3 CD 6X6 1.0
Readings By: Craig Maurer
250
250
75
I IL 575
264
269
378
286
101
82
743
637
aB
CERTIFIED
TEST & BALANCE
AIR OUTLET DATA SHEET
Project: BARRY UNIVERSITY
System: AHU
AREA OUTLET
SERVED
NO. TYPE SIZE
T
RM 309
Date: 06/07/12 Page: 78
Floor: 3
DESIGN TEST CFM
AREA FPM
250 263
281
C
3 CD 6X6 1.0
75 125
575 77.11111
250 345 275
A
B 2 SW 6X 10 1.0
C
RM 311
A
B
C
RM 312
A
B 2 SW 6X10 1.0
C 3
1
SW
6X10
1.0
80
250 287
272
3 CD 6X6 1.0
75 131
85
1 1L
575
763
11'L
632
1 SW 6 X 10 1.0
250 339
279
2 SW
6X 10
1.0
3
CD
6X6
1.0
TTL
250 305
283
75
96
81
575 740
11'L 643
1
SW
6X10
1.0
250
401
289
250 272
286
CD
6X6
1.0
75
129
84
TIT,
575 802
1 °IL 659
Readings By: Craig Maurer
as
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/07112 Page: 79
Floor: 3
TEST CFM MEASURED
NO.
TYPE
SIZE
AREA
FPM
CFM
#1
#2 FPM
CFM
6 X 10 1.0 200 198
6 X 10 1.0 150 165
301
TOILET
SHOWER
10 X 10
10 X 10
Readings By: Craig Maurer
cm
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
OUTLET
NO. TYPE
SIZE
AREA
DESIGN
FPM
Date: 06/07/12 Page: 80
Floor 3
CFM
#1
1 CD 10X 10
1.0
1 CD 10X 10
1.0
1 CD 10X 10
1.0
1 CD 10X 10
2 CD 10X 10
1.0
1.0
1 CD 10X 10
2 CD 10X 10
1.0
1.0
1 CD 10X 10
1.0
2 CD 10X 10
1.0
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/07/12
Floor: 3
TEST CFM
Page: 80A
NO.
TYPE
SIZE
AREA
FPM
CFM
#1
#2
FPM
CD 10 X 10 1.0 79
CD 10X10 1.0 82
CD 10 X10 1.0 81
CD 10 X10 1.0 84
CD 10X10 1.0 75
CD 10 X 10 1.0 82
RM314
CD 10 X 10 1.0 79
CD 10 X10 1.0 87
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 81
Floor: 3
AREA
SERVED
OUTLET
DESIGN
TEST CFM MEASURED
NO.
TYPE
SIZE
AREA
FPM
CFM
#1
#2 FPM
CFM
RM 331
SW 6 X 10 1.0 250 350 280
SW 6 X 10 1.0 250 277 275
CD 6X6 1.0 75 96 99
575 723 IIL 654
SW 6 X 10 1.0 250 351 273
SW 6 X 10 1.0 250 243 284
CD 6X6 1.0 75 110 105
I"I'L 575 704 I"1L 662
SW 6 X 10 1.0 200 202 230
SW 6 X 10 1.0 150 243 167
SW 6 X 10 1.0 150 203 170
D 4 SW 6 X 10 1.0 200 225 222
E 5 CD 8X8 1.0 100 69 94
1'1L 800 945 7 "I'L 883
Comments:
Readings By: Bart Serino
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 82
Floor:3
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE AREA FPM CFM #1 #2 FPM CFM
RM334
A 1 SW 6 X 10 1.0 400 505
499
CD
75
EFL 475 599
1'1'L 589
RM 335
A
1
SW
6 X 10
1.0
250
340
289
B 2 SW 6X10 1.0
250 260
275
C
3
CD
6X6
1.0
75
120
98
TTL 575 720
1 TL 662
RM337
B
2
SW
6X10
1.0
250
228
265
C 3 CD 6X6 1.0
75 130
94
1 "1L 575 708
1'1L 639
RM 338
A 1 SW 6X 10 1.0
250 292
285
B
2
SW
6 X 10
1.0
250
330
280
C
3
CD
6X6
1.0
75
130
109
11L 575 752
674
Readings By: Bart Serino
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: AHU
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 83
Floor: 3
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE SIZE AREA
FPM CFM #1 #2 FPM CFM
RM 339
A
B 2 SW 6X 10 1.0
C
RM 340
A
B 2 SW 6 X 10 1.0
C 3
RM 341
1
SW
6X10
1.0
250
360
281
250 219
3 CD 6 X 6 1.0
75
98
!IL
575
677
'1"1'L
276
96
653
1 SW 6 X 10 1.0
250 333
283
250 246
279
CD
6X6
1.0
75
107
97
TTL
575
688
1 1L
659
A
B
C
1 SW
6 X 10
1.0
250
320
277
2 SW
6X10
1.0
250
239
274
3 CD
6X6
1.0
75 101
96
fIL
575
660
TTL
647
Comments:
Readings By: Bart Serino
GB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: ABU
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 84
Floor .3
AREA
SERVED
NO.
OUTLET
DESIGN TEST CFM MEASURED
TYPE SIZE AREA FPM
RM 342
A 1 SW 6 X 10 1.0
SW
6 X10
1.0
3 CD
6 X 6
1.0
CFM #1 #2 FPM CFM
250
250
75
330
240
105
TTL 575 675
279
281
99
11L 659
RM 343
A
B
1 SW 6 X 10 1.0
250
2
SW
6 X 10
1.0
C 3 CD 6 X 6
1.0
RM 344
A
1
SW
6 X 10
1.0
B
2
SW
6 X 10
1.0
C 3 SW 6 X 10 1.0
D
E
4
SW
6 X 10
1.0
331
250 270
75 120
TTL
575 721
200
150
150
200
273
288
98
IIL 661
190
198
165
183
5 CD
8 X 8
1.0
100 93
ITL 800 829
192
167
160
191
99
ITL 809
Comments:
Readings By: Bart Serino
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/4)8/12 Page: 85
Floor:1
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO TYPE SIZE AREA
RM 101
TOILET 1 EF 12 X 12 1.0
SHOWER 2 EF 12 X 12 1.0
RM 102
TOILET 1 EF 12 X 12 1.0
SHOWER 2 EF 12 X 12 1.0
RM 103
FPM CFM #1 #2 FPM CFM
50
74
50
90
50
84
50
71
TOILET 1 EF 12 X 12 1.0
50
75
SHOWER 2 EF 12 X 12 1.0
50
80
RM 104
RM 105
TOILET 1 EF 12 X 12 1.0
SHOWER 2 EF 12 X 12 1.0
RM 107
TOILET 1 EF 12 X 12 1.0
SHOWER 2 EF 12 X 12 1.0
50
46
50
84
Comments:
Readings By: Craig Maurer
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/9/12 Page: 86
Floor: 1
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
RM 108
TOILET
NO TYPE SIZE AREA FPM CFM #1 #2 FPM CFM
1
EF 12
88
SHOWER 2 EF 12 X 12 1.0
50
76
RM 109
TOILET 1
EF
12 X 12
1.0
50
83
SHOWER 2
EF
12 X 12
1.0
50
88
RM 110
TOILET 1
EF
12 X 12
1.0
50
82
SHOWER 2 EF 12 X 12 1.0
50
83
RM 111
TOILET 1 EF 12 X 12 1.0
50
77
SHOWER 2 EF 12 X 12 1.0
50
83
RM112
TOILET 1 EF 12 X 12 1.0
50
88
SHOWER 2
EF
12 X 12
1.0
50
83
RM 113
TOILET 1
EF
12 X 12
1.0
50
77
SHOWER 2 EF
12 X 12
1.0
50
81
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AREA
SERVED
AIR OUTLET DATA SHEET
Date: 0619112 Page: 87
Floor: 1
DESIGN TEST CFM MEASURED
NO TYPE SIZE AREA FPM CFM #1 #2 FPM CFM
TOILET
SHOWER
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/06/12 Page:
Floor: 2
AREA
SERVED
OUTLET
DESIGN TEST CFM
MEASURED
NO.
TYPE
SIZE
AREA FPM
CFM #1
#2
FPM
CFM
RM 201
1
CD
10 X 10
1.0
70
2
CD
10 X10
86
RM 202
1
CD
10 X 10
74
2
CD
10X10
77
RM 203
1
CD
10 X 10
85
RM 204
CD
10 X 10
74
RM 207
1
CD
10X10
1.0
77
2
CD
IOX 10
1.0
79
RM 208
1
Comments:
CD
2 CD
Readings By: Bart Serino
10 X10 1.0
10 X10 1.0
74
78
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/06/12 Page: 89
Floor. 2
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
RM 209
NO.
TYPE SIZE AREA FPM CFM #1 #2 FPM CFM
1 CD 10 X 10 1.0
CD
10 X 10
RM s
1 CD 10X10 1.0
2 CD 10X10 1.0
80
78
RM 211
CD 10 X 10 1.0
2
CD
10 X 10
1.0
75
76
RM 212
1
CD
10 X 10
1.0
80
2
CD
10X 10
1.0
83
RM 213
1
CD
10X 10
1.0
81
2 CD 10X10 1.0
83
RM 214
1 CD 10X10 1.0
83
2 CD
10 X 10
1.0
75
Comments:
Readings By: Bart Serino
GB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06 /06/12 Page: 9 0
Floor: 2
AREA
SERVED
OUTLET
DESIGN
TEST CFM
MEASURED
NO. TYPE
SIZE
AREA
FPM CFM
#1
#2
FPM
CFM
RM 238
1 CD
10X 10
1.0
85
2 CD
10 X 10
1.0
84
RM 239
1 CD
10 X 10
2 CD
10 X 10
1.0
85
1.0
81
RM 240
1 CD
10X 10
1.0
90
2 CD
10 X10
1.0
45
RM 241
1 CD
10X 10
1.0
84
CD
10X 10
1.0
80
RM 242
1 CD
10 X 10
1.0
86
2 CD
10x10
1.0
81
RM 243
1 CD 10X10
1.0
65
2 CD 10X10
1.0
77
Comments:
Readings By: Bart Serino
•cn3
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF - 1
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/07/12 Page: 91
Floor: 2
TEST CFM MEASURED
NO. TYPE
SIZE
AREA
#1
#2 FPM CFM
RM 244
1
2
CD
CD
10 X 10
1 0 X 10
1.0
1.0
78
80
Comments:
Readings By: Bart Serino
Cri3
CERTIFIED
TEST & BALANCE
AIR OUTLET DATA SHEET
Project: BARRY UNIVERSITY
System: EF -1
Date: 06/09112 Page: 92
Floor: 3
DESIGN TEST CFM
NO TYPE SIZE AREA FPM CFM #1 #2
Comments:
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AREA
SERVED
AIR OUTLET DATA SHEET
OUTLET
Date: 06/09/12
Floor. 3
DESIGN TEST CFM
Page: 93
MEASURED
NO TYPE SIZE AREA FPM
CFM #1
#2
FPM
CFM
RM 308
TOILET
1
EF 12 X 12
1.0
50
76
SHOWER
2
EF 12X12
1.0
50
85
RM 309
TOILET
1
EF 12 X 12
1.0
50
81
SHOWER
RM 310
TOILET
SHOWER
2
EF 12X 12
1.0
50
84
1
EF 12 X 12
1.0
50
79
2
EF 12X12 1.0
50
82
RM 311
TOILET
1
EF
12 X 12
1.0
50
81
SHOWER
2
EF
12 X 12
1.0
50
84
1
EF
12 X 12
1.0
50
2
EF
12X 12
1.0
50
1
EF
12 X 12
1.0
50
Readings By: Craig Maurer
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
OUTLET
DESIGN
Date: 06/08/12 Page: 94
Floor: 3
TEST CFM
NO
TYPE
SIZE AREA
FPM CFM
#1
#2
FPM
1
EF
2
EF
12 X 12 1.0
12 X 12 1.0
50
50
Comments:
Readings By: Craig Maurer
x
CM
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 95
Floor. 3
NO. TYPE SIZE AREA FPM CFM
1 CD 10X 10 1.0
RM 332
1 CD 10 X10 1.0
1 CD 10 X 10 1.0
88
1 CD 10X 10 1.0
2 CD 10 X 10
RM 337
2
CD
10 X 10
1.0
84
Comments:
Readings By: Bart Serino
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1
AIR OUTLET DATA SHEET
Date: 06/07/12 Page: 96
Floor 3
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
NO. TYPE
RM 338
SIZE
AREA FPM
CFM #1
#2 FPM
CFM
1 CD 10X10 1.0
79
2 CD 10 X 10 1.0
81
RM 337
1 CD 10X10 1.0
78
2 CD 10X10 1.0
84
RM 340
1
CD
10 X 10
1.0
82
2 CD
10 X 10
1.0
83
RM 341
1 CD 10X 10 1.0
81
2 CD
10 X 10
1.0
83
RM 342
1
CD
10 X 10
1.0
83
2 CD 10 X 10 1.0
85
RM 343
1
CD
10 X 10
1.0
84
2 CD 10X10 1.0
67
Comments:
Readings By: Bart Serino
aB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1 TRASH CHUTE
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 97
Floor: 2N° & 3
AREA
SERVED
OUTLET
DESIGN
TEST CFM MEASURED
NO TYPE SIZE AREA
FPM CFM
#1 #2 FPM CFM
214D FL
1
EG
714X714
.39
256
100 313/121
274
107
3RD FL
2 EG 71/2X 7Y2 39
256
100 285/111
282
110
200
217
Comments:
Readings By: Craig Maurer
CTB
CERTIFIED
TEST & BALANCE
Project: BARRY UNIVERSITY
System: EF -1 0
AIR OUTLET DATA SHEET
Date: 06/08/12 Page: 98
Floor: 1 -3
AREA
SERVED
OUTLET
DESIGN TEST CFM MEASURED
RM 319
NO. TYPE SIZE AREA
FPM
CFM #1 #2 FPM CFM
JANITOR 1
CD 10X10
1.0
50
51
RM 119
JANITOR 1 CD 10 X 10 1.0
50
51
Comments:
Readings By: Bart Serino
Abbreviations
AC
Air Conditioning Unit
LD
Linear Diffuser.
AHU
Air Handling Unit
LWT
Leaving Water Temperature
BHP
Brake Horsepower
MAU
Make -up Air Unit
CD
Ceiling Supply Diffuser
MAX
Maximum
CFM
Cubic Feet Per Minute
MIN
Minimum
CHWR
Chilled Water Return
NA
Not Applicable
CHWS
Chilled Water Suppply
NI
Not Installed
CWR
Condenser Water Return
NS
Not Stated
CWS
Condenser Water Supply
OBD
Opposed Blade Damper
DD
Direct Drive
OD
Outside Diameter
DP
Differential Pressure
OA
Outside Air
EAT(DB)
Entering Air Temp.(Dry Bulb)
RA
Return Air
EAT(WB)
Entering Air Temp.(Wet Bulb)
REQ'D
Required
EF
Exhaust Fan
RG
Return Grille
ESP
External Static Pressure
RH
Relative Humidity
EWT
Entering Water Temperature
RPM
Rotations Per Minute
FCU
Fan Coil Unit
RTU
Rooftop Unit
FLA
Full Load Amps
SA
Supply Air
FPB
Fan Powered Box
SF
Safety Factor
FPM
Feet Per Minute
SLOT
Slot Diffuser
GPM
Gallons Per Minute
SP
Static Pressure
HP
Horsepower
SWR
Side Wall Register
HPACU
Heat Pump AC Unit
TSP
Total Static Pressure
HWR
Heated Water Return
T -STAT
Thermostats or Sensor
HWS
Heated Water Supply
TYP
Typical
ID
Inside Diameter
V.D.
Volume Damper
INAC
Inaccessible
VAV
Variable Air Volume
LAT(DB)
Leaving Air Temp(dry bulb)
VFD
Variable Frequency Drive
LAT(WB
Leaving Air Temp(wet bulb)
WSHP
Water Source Heat Pump
GB
CERTIFIED
TEST & BALANCE
INSTRUMENT CALIBRATION DATA SHEET
INSTRUMENT
SERIAL
NUMBER
DATE
CALIBRATED
DATES OF USE
FLUKE 51
TEMPERATURE
MEASUREMENT
6574136
1/5/12
NA
FLUKE SOPK 2A
IMMERSION
7297 -1
1/5/12
NA
FLUKE 80PK 3A
SURFACE
7297 -2
1/5/12
NA
FLUKE 322
VOLTAGE /AMPERAGE
85760374
9/3/11
06/01/12
EXTECH RH390
% RELATIVE
HUMIDITY
09059988
1/5/12
06/01/12
SHORTRIDGE ADM-
860
FLOOW HOOD
M01378
8/22/11
06/16/12
HE STICHT 4401 -H
ROTATIONAL SPEED
85069
9/3/11
06/01/12
TESTO 417
AIR VELOCITY
MEASUREMENT
02128816
9/3/11
06/01/12
SHORTRIDGE HDM-
300
WATER FLOW
MEASUREMENT
W98051
4/5/11
NA
Miami Shores Village
Building Department
10050 N.E.2nd Avenue, Miami Shores, Florida 33138
Tel: (305) 795.2204 Fax: (305) 756.8972
INSPECTION'S PHONE NUMBER: (305) 762.4949
BUILDING
PERMIT APPLICATION
FBC 20
JUL 1 & Re'Dcj&
pern,i,Norn�11-ia83
Master Permit No. 1 ` - 5 AL
Permit Type: MECHANICAL
OWNER: Name (Fee Simple Titleholder): �,22 �e�cri kev)..'4,tc..$,A,�41 Phone#: 305 '-$`i'i —305t
Address: a301, g0F_ %h ,. yy
City: tAt,;J' \ � 4 State: ft,— Zip: 33MM 1
Tenant/Lessee Name: ` ` �a., � ` et c , \.1 Phone#: .Sc – 3o9
Email: % �%r�'vla �?5 G 4\ • )nor,N-
JOB ADDRESS: )11 ItY0
City: Miami Shores County: Miami Dade Zip: VL 1
Folio/Parcel #: Ws.,Q 3 , GOCW
Is the Building Historically Designated: Yes
NO Flood Zone:
CONTRACTOR: Company
Name: / / 1 , *it, ,
Phone #: 494 "S6 gri
Address: J 5 5. And t au
City: / i 1LLIV[f do
state:
Qualifier Name: M ,( i'1-- K 1C../rniq � -�
State Certification or Registration #: oo X/ %0
Zip: 333/40
Phone#: �j
Certificate of Competency #: /23--23(1k i '1
Contact Phone#: c 5 /4. E2.5 — Zq' J Email Address:
DESIGNER: Architect/Engineer: ice' ; f/ 1/ %r k
Gl5unn4lrsoft a h; LI'j rk. (N\
Phone #: 4,511°- 6-2 -247/
Value of Work for this Permit: $ f 1SC OC:d Square/Linear Footage of Work:
*New ORep '/Replace ODemolition
Type of Work: UAddress A OAlteration . I I� p
Description of Work: a A- I k ((�'JL t �} )C.- j tikl )I ` r
Pi cti4- C� uta i�� W 0+1 ar O E i 1M!
I-AAC' W kg:7
******** * * * * * * * * * * * * * * * * * *$ ** * * * * * * * * ** e * ** ********* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Permit F 31k b CCF $ CO /CC $
Radon Fee $ DBPR $ Bond $
Technology Fee $
Submittal Fee $
Scanning Fee $
Notary $ Training/Education Fee $
Double Fee $ Structural Review $
TOTAL FEE NOW DUE
-71 tt T-tg
Bonding Company's Name (if applicable)
Bonding Company's Address
City State Zip
Mortgage Lender's Name (if applicable)
Mortgage Lender's Address
City State Zip
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS,
WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONERS, ETC
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved reinspection fee will be charged.
411
Signature
Sr,
Owner or Agent y'�
The foregoing instrument was acknowledged before me this /3 The foregoing instrument was acknowledged before me this 2 '
day of S 1-7 , 20 it , by 0, r3. �4.4, ���� �,� - day of \tA , 2011 d , by Ivy COIL I t ,
who is personally known to me or who has produced who is personally known to me or who has produced
As identification and who did take an oath. as identification and who did take an oath.
NOTARY PUBLIC: NOTARY PUBLIC:
Signature L+
Contractor
Sign:
Print: t1 L � '�-�✓t� � �e'�
My Commission Expires:
APPROVED BY
�V �u�� Notary Public State of Florida
4 Cheryl Saida Gerber
My Commiss on 01396131213 ?ofpoC Expires 05108/2014
Sign:
Print:
My Commission Exp.
O
° ": MY COMMISSION # DD702722
-.•;
,8, f, EXPIRES August 07, 2011
(407) 398 -0153 FloridallotaryService.com
*********************** ****** *** * * * * * * * * ***** * ****+k**
niner Zoning
Structural Review
(Revised 07 /10 /07)(Revised 06 /10/2009)(Revised 3/15/09)
Clerk