Loading...
RF-16-1686 (2) CBB Engineering & Testing Co. 7450 Griffin Road,Suite 140,Davie,FL33314 Phone:(954)581-7115,Fax:(954)581-2415 www.cebb.net July 18,2016 To: MiamiShoresVillage Building Department 10050 NE 2nd Avenue Miami Shores,FL 33138 Roof Tile Uplift Test Report Test Date: July 18,2015 Permit#: RF-6-16-1686 Address: Swanson Residence 249 NW 9 1 A Street,Miami Shores,FL Contractor: Affordable Rooftec Roof Pitch: 3:12 Attachment method: Adhesive Pol set AH-160 Tile Type: Eagle Belair Roof Tile(NOA 15-0223.18) Device Used: "IMADA DPS 110"force gauge(Serial#340507) Total Sloped Roof Area: I 12.83s uares All Testing is in strict accordance with the Florida Building Code, 2014 Edition, High Velocity Hurricane Zone — Testing Application Standard(TAS) 106. Roof Area: 12.83 squares Total Number of Tests Number of tests Passed %Passed Field Area 1): 5.83 squares 10 T29-T38) 10 100% Perimeter Area(2): 7.00 squares 10(T19-T28) 10 100% No.of Corner Areas(3): 13 13 Tl-T13 12 100% Ridge/Hp Areas:37 cs 5(T14-T18) 5 100% Based upon the field tests, I certify that 100% of the static up-lift tests "PASSED"the nesting criteria of 35.0 lbfload, and meets the attachment resistance for adhesive Set Systems,as specified in the NOA. Should you have any questions regarding the above, or if require additional information, please do not hesitate to contact this office. Sincerely, CeBB Engineering&Testing Co. (NOA 13-0919.02) 07/18/2016 Eduard Bad ,P.E. Fla.Reg.No: 59997 For The Firm Cc: Affordable Rooftec Enc. Location Sketch Calibration Certificate Ce BB Engineering & Testing Co. 7450 Grin Road,Suite 140,Davie,FL33314 Phone:(954)581-7115,Fax.(954)581-2415 www.cebb.net T—Tested tiles and Passed; Total Area: 12.83 squares No.of tested Tiles: F—Tested tiles and Failed; -Field Area(1): 5.83 squares -Field Area: 16 M—Missing Tiles; -Perimeter Area(2): 7.00 squares -Perimeter Area: 16 B—Broken Tiles; -No.of Corner area(3): 13 -Corner areas: 13 -Ridge/hip areas: 37 pcs -Ridge/Hip areas: 5 12 F 1 _19_ 2 Comer Areas 30 16' 1 F' :l n' I I _ 3 --I --- Perimeter Areas 7 I — ---20--I 29 31 32 331 3.k'-23' I 1 1 -- ------------ --- 23 21 ja4'. 24 22 5' �+ I � --- 37 36 35 344 1 38 ------------- -C- 1 Heid Ares —2-5-1-7-1 __ 26 21 28 6 8 25 7 11' 30' _ r ~rte TAS 106 TESTS LOCATION SKETCH Permit#RF-6-16-1686 Swanson Residence 249 NW 91s`Street, Miami Shores,FL Legend: 29-38 Field tests 19-28 Perimeter tests 1-13 Corner tests 14-18 Ridge Tests Ce BB Engineering & Testing Co. 7450 Grin Road,Suite 140,Davie,FL33314 Phone:(954)581-7115,Fax.(954)581-2415 www.cebb.net 19-28 Perimeter tests 1-13 Corner tests 14-18 Ridge Tests TEST RESULTS =PASSED,F=FAILED Test Uplift Test Uplift Test Uplift Test Uplift Test Uplift Location Pull Test Location Pull Test Location Pull Test Location Pull Test Location Pull Test or or or or or 1 P 26 P 2 P 27 P 3 P 28 P 4 P 29 P 5 P 30 P 6 P 31 P 7 P 32 P 8 P 33 P 9 P 34 P 10 P 35 P 11 P 36 P 12 P 37 P 13 P 38 P 14 P 15 P 16 P 17 P 18 P 19 P 20 P 21 P 22 P 23 P 24 P 25 P Ce BB Engineering & Testing Co. 7450 Gilfn Road,Suite 140,Davie,FL33314 Phone:(954)581-7115,Fax:(954)581-2415 www.cebb.net mada�ca tisOA90 Tl0ae AOOA®R6D QMF-11-3-IM CALIBRATION CERTIFICATE Traceabiat: Calibration Date: March 22,2016 Dawnpt- I SM Carwkste4 Dae Dau Certificate 0 032216340507E Temp/M WM 2228016 972427-53815274 7232017 Temperature: 74 eF Hanger 2AA 22725080 4n92017 Humidity: 27 a/aRH W-set 4SZC 1846363AD 4=17 Model Number: DS2-110 weigbt tum 22305M 12/!32016 Serial Number. 340507 weight 2308 1416941 622018 Capacity: 110 Ibf Accuracy: 0.2%F.S.I I LSD Resolution: 0.1 Ibf Procedure: EXAOID Ilia document certifies that the above instrument has been calibrated and tested in accordance with]made calibration procedures conducted under the conditions noted with standards,wbich establish an unbroken link traceable to the International System of Unita(SI)via the relevant primary national or international standards, including the National Institute of Standards and Technology(NIST).This document must not be reproduced withont written anthodzetion from IMADA INC. TEST RESULTS AS FOUND AS LM TEST POINT ACTUAL ACTUAL t) Toro. .110.0 -109.9 b .109.9 2 0.0 0.0 0.0 3 Comp. 110.0 109.9 109.9 Technical Manager: 'r Noboru Umegaki Imade,tae 3100 Dodo Rd.,Sdte 707 NortbbrwI4 nllnoia 60052 btlpstAmmimada.eom &Mata imada®Iamda.o 1-800.3734989 tea.aac toavmto d 1%5 s`i� Miami shores Village 1211 ••••• Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 e0RiDA Tel: (305)795.2204 Fax: (305) 756.8972 RE: Permit# " d - DAT INSPECTION AFFIDAVIT �l licensed as a (n) Contractor/Engineer/Architect, (Print name and circle License Type) FS 468 Building Inspector nrl- License#: CG-� S 35 On or about , I did personally inspe t the roof deck nailing (D work at 1 �,� 9time ) (Complete Job Site Address) Based upon that examination I have determined the installation was done according to thte Hurricane Mitigation Retrofit Manual (Based on 553.844 F-S) Sign re State of Florida County of Dade: The undersigned, being the first duly sworn,deposes and says that he/she is the contractor for the above property mentioned. Sworn to and subscribed before me this da of ' P SIMONA LELUTIU s.5 MY COMMISSION EXPIRE t FF 15478 S:August 26,2018 Notary Public, Sate of Florida at Large B°"d�rte,Nofa,�p��,�Underw„ae s Dffrnc� �1 J 'General,Building,Residenfial,or Roofing Contractors or any individual certified under 468 F.S.to make such an inspection.Include ph>tographs of each plane of the roof with permit#and address#clearly shown marked on the deck for each inspection 0-&.4—n11nM1A 1rn1 nnno } 3 _ Permit,lit, � ' Miami Shores Village .� Pett 1� litf ° E 10050 N.E.2nd Avenue NWf0fCSf7f?ll ` " Miami Shores,FL 33138&-0000 -R — Ae Phone: (305)795-2204 �F7Ttr � fttS .. �n Issuef��1 Expiration:atlon: 1 2 / 1 Project Address Parcel Number Applicant L249NW 91 Street 1131010331330ANNE SWANSON mi Shores, FL 33150- Block: Lot: Owner Information Address Phone Cell ANNE SWANSON 249 91 Street (305)764-8842 MIAMI SHORES FL 33138- 249 91 Street MIAMI SHORES FL 33138- Contractor(s) Phone Cell Phone Valuation: $ 9,100.00 AFFORDABLE ROOFTEC, INC (954)962-9670 (954)931-8458 _. Total Sq Feet: 1283 Type of Work:Re Roof Available Inspections: Additional Info:RE ROOF CONCRETE TILES ATTACHED WIT Inspection Type: Classification:Residential Scanning:4 Up Lift Report Tin Cap Final Roof Tile In Progress Renailing Affidavit Review Roof Cap Sheet Fees Due Amount Pay Date Pay Type Amt Paid Amt Due Bond Type-Contractors Bond $500.00 Invoice# RF-6-16-60232 CCF $6.00 DBPR Fee $4.13 06/27/2016 Credit Card $761.26 $50.00 DCA Fee $4.13 06/17/2016 Credit Card $50.00 $0.00 Education Surcharge $2.00 Bond#:3123 Permit Fee-New Roof $275.00 Scanning Fee $12.00 Technology Fee $8.00 Total: $811.26 In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations pertaining thereto and in strict conformity with the plans,drawings, statements or specifications submitted to the proper authorities of Miami Shores Village. In accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate permits are required for ELECTRICAL,PLUMBING,MECHANICAL,WINDOWS,DOORS,R OFING and SWIMMING POOL work. OWNERS AFFIDAVIT: I certify that all the foregoin " or ation is acc t and that all work will be done in compliance with all applicable laws regulating construction and zoning. Futhermore,I authorize th above- am o tr t do the work stated. June 27, 2016 Authorized Signature:Owner / Ap licant C n c Agent Date Building Department Copy June 27,2016 1 Miami Shores Village Iz Building Department i JUN 17 201 10050 N.E.2nd Avenue,Miami Shores,Florida 33138 _ Tel:(305)795-2204 Fax:(305)756-8972 ––j4avv� INSPECTION LINE PHONE NUMBER:(305)762-4949 YY1YAovtn FBC ZOO'/ - BUILDING Master Permit No. ,b - /,6 -9C PERMIT APPLICATION Sub Permit No. ❑BUILDING ❑ ELECTRIC 0 ROOFING ❑ REVISION ❑ EXTENSION ❑RENEWAL PLUMBING ❑ MECHANICAL ❑PUBLIC WORKS ❑ CHANGE OF ❑CANCELLATION ❑ SHOP CONTRACTOR DRAWINGS JOB ADDRESS: 249 NW 91 Street City: Miami Shores County Miami Dade Zip- Folio/Parcel#:11-3101-033-1330 Is the Building Historically Designated:Yes NO X Occupancy Type: SFR Load: Construction Type: Structural Flood Zone: BFE: FFE: OWNER:Name(Fee Simple Titleholder): Anne Swanson Phone#:305-510-4978 Address:249 NW 91 st Street City: Miami Shores State: FL Zip: 33150 Tenant/Lessee Name: Phone#: Email: CONTRACTOR:Company Name: Affordable Rooftec Inc Phone#: 954-962-9670 Address: 2117 SW 57th Avenue City: West Park State: FL Zip: 33023 Qualifier Name: Miorika M Malinetescu Phone#: 954-931-8458 State Certification or Registration#: CCC 057535 Certificate of Competency#: DESIGNER:Architect/Engineer: Phone#: Address: 11 City: State: Zip: Value of Work for this Permit:$ 10o , C r) Square/Linear Footage of Work: /2 St 3 S I^ Type of Work: ElAddition IN Alteration ❑ New ❑ Repair/Replace ❑ Demolition Description of Work: Re-Roof- Concrete Tiles attached with large patty polyfoam Specify color of color ru tile: &xcj ti,e, - ��� NY- - 1AffyyJ -k" G fl \) Submittal Fee$ - Permit Fee$ CCF$ CO/CC$ Scanning Fee$ I �QQ Radon Fee$ . 13 DBPR$ —Notary$, Technology Fee$ Training/Education Fee$ Double Fee$ Structural Reviews$ Bond$ :J®® TOTAL FEE NOW DUE$ 26 I a 2(0 /y (Revised02/24/2014) ` t Bonding Company's Name(if applicable) Bonding Company's Address City State Zip Mortgage Lender's Name(if applicable) Mortgage Lender's Address City State Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS, FURNACES,BOILERS,HEATERS,TANKS,AIR CONDITIONERS,ETC..... OWNERS AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant. As a condition to the issuance of a building permit with an estimated value exceeding$2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also,a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will not be approved and a reinspection fee will be charged. Signature4/4 Signatur 0 NE rAGENT CONTRACTOR The foregoing instrument was acknowledged before me this The regoing instrument was acknowledged before me this (D day of Jurv- 20�J by L day of 12 20 ZI,; . by hj���hc is personally known to Miorika M Malinetescu ,who is personally known to me or who has produced as me or who has produced identification an who di identification and who did take an oat "4path. SIMONA:FF .a• y°o•. SIMONA LELUTIU MY COMMISSI759MY COMMISSION II FF 154759 NOTARY :o EXPIRES:Au18 NOTARY PUBLIC: p EXPIRES:August 26,2018 ""qBonded Th u Notaryvriters Pf,tO' Bonded Thra Notarq Public Undenyrf(ors Sign• Sign• P nt: Print: Simona Lelutiu Seal: Seal: �*a�ix**�rw�x�x�ra�rx���***�*� � * •*�x �a*�x��x��+��r��s�**ria*��x�x�x�*�x�*m*w��*�*s�rsss+�*+r��x��s�x«x�*s+rsx.*w�*+x�x��x�►*+�*+�*+r* C� APPROVED BY Plans Examiner Zoning Structural Review Clerk (Revised02/24/2014) Me IL seem nfiliamishoresVillage L ft Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 CONTRACTORS' REGISTRATION Fax: (305) 756.8972 IF CONT CTOR IS A FLORIDA STATE CERTIFIED CONTRACTOR: A. COPY OF QUALIFIER'S STATE LICENCES B. COPY OF LOCAL BUSINESS TAX RECEIPT C. COPY OF LIABILITY INSURANCE* D. COPY OF WORKERS COMPENSATION INSURANCE* (Workers Compensation EXEMPTION must have NOTICE TO OWNER form and Contractor Affidavit) IF CONTRACTOR HAS A MIAMI DADE COUNTY CERTIFICATE OF COMPETENCY: A. COPY OF CERTIFICATE OF COMPETENCY OF QUALIFIER B. COPY OF LOCAL BUSINESS TAX RECEIPT C. COPY OF STATE REGISTERED CONTRACTOR LICENSE OR MIAMI DADE COUNTY MUNICIPAL CONTRACTOR'S TAX RECEIPT. D. COPY OF LIABILITY INSURACE* E. COPY OF WORKERS COMPENSATION INSURANCE* (Workers Compensation EXEMPTION must have NOTICE TO OWNER form and Contractor Affidavit) *YOUR INSURANCE COMPANY MUST ISSUE A CERTIFICATE AS FOLLOW Certificate Holder: MIAMI SHORES VILLAGE BLDG DEPT 10050 NE 2ND AVE MIAMI SHORES, FL 33138 Certificate must specify the description of operations or contractor license number. e�esma�e��a��®eam®eoama®■���oa��ra�■®m®■®e®�®ae®®®oo®®®o®s���e■a■aeo��®aasr�r�r■®®■as�ne�eo BUSINESS NAME. Affordable Rooftec Inc BUSINESS ADDRESS: 2117 SW 57th Ave CITY West Park STATE FL ZIP 33023 BUSINESS PHONE: 9( 54 962-9670 FAX NUMBER 9( 54� 518-00-5— CELLPHONE( 951931 -8458 QUALIFIER'S NAME: Miorika M Malinetescu QUALIFIER'S LIC NUMBER: CCC 057535 RICK SCOTT�GOVERNOR ISECRETARY SIATE d- F'- J-5 DEPARTMENT OF BUSINESS AN =_BSIONAL REGULATION - =_ CONSTRUCTION BOARD � �f :,00057535 ROOFING CONTRACTOR = - Red below IS CERTIFIED ;Br the provisions of Chapter 489 FS. !ration date. AUG 31,2016 rj a 1 MALINETESCU, MIORIKA MONICA AFFORDABLE ROOFTEC INC n g 1108 N E 4TH CT HALLANDALE FL 33009 H ISSUED: 06104/2014 DISPLAYAS REQUIRED BY I-A%A SEQ L140604000107 BRO ARD COUNTY LOCAL BUSIMESS TAX RECEIPT 115 S.Andrews Ave., Rm.A-1 00, Ft. Lauderdale, FL 33301-1895—954-831-4000 VALID OCTOBER 1,2013 THROUGH SEPTEMBER 30,20 .6 ®SA: INCReceipt 9:185-3-125'ROOFING/SHEET METAL COVTRACT-OR Business Name:AFFORDABLE ROOFTEC ABusiness Type:(ROOFING CON'TR) Owner game:mIORIKA MONICA MALINETESCU Business Opened:l1/06/1998 Business Location:2117 SW 57 AVE St"ate/County1Ceifi/Re9:CCC057535 WEST PARK Exemption Code: Business Phone:954-456-0217 Rooms Seats Employees Machines Professionals 3 For Vending Business Only Number of Machines: Vending Type: Tax Amount Transfer Fee NSF Fee Penalty Prior Years Collection Cost Total Paid 27.00 0.00 0.00 1 0.00-1. 0.000.00 27-00 THIS RECEIPT MUST BE POSTED CONSPICUOUSLY IN YOUR PLACE OF BUSINESS THIS BECOMES A TAX RECEIPT This tax is levied for the privilege of doing business within Broward County and is non-regulatory in nature.You must meet all County and/or Municipality planning WHEN VALIDA[ED and zoning requirements.This Business Tax Receipt must!be transferred when the business is sold, business name has changed or you have moved the business location.This receipt does not indicate that the business is,legal or that it is in compliance with State or local laws and regulations. Mailing Address: MIORIKA MONICA MALINRTRSCU Receipt #WWW-13-00133050 2117 SW 57 AVE Paid 07/18/2015 27.00 HOLLYWOOD, FL 33023 qWe� q49 di P_ I CERTIFICATE OF LIABILITY INSURANCE °"'E``" °°"""r' = 06/13/16_ — — ——- — TMCERTtFICATE O I NOT AFFIRtYFATiVELY OR NEGATIVELY AMEND,EXTEND OR ALTER THE COVERAGE E CERTIFICATE HOLDER THIS ~. AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S),AUTHORIZED REPRESENTATIVE OR PRODUCER,AND THE CERTIFICATE HOLDER. IMPORTANT: If the eerUticate holder Is an ADDITIONAL INSURED,the policy(les)must be endorsed. H SUBROGATION IS WANED,subject to - -- -the terms and conditions of the Policy,certain policies may require an endorsement A statement on this certificate does not confer rights to the certificate holder in Neu of such endomement(s). PRODUCER --- - -NAME*----- ME _Greg Beyer _ — PHONE (954)725-0235 FAX No (954)725-0237 - 1 Fed USA Retail,Inc. �AltNo,Ezt►: _ -_-- -_--� -- .�1-l 1076 W.Sample Rd. Zgg ;—greg.ailianceinsSphoo.cgm Pompano Beach,FL 33064 � - ._-- N � --_COVERAGE-- -------- NAIC S -- Phone (954)725-0235 Fax (954)725-0237 — -- _INSURERA: Axis Surplus Ins Co INsu s AFFORW INSURED INSURER 13: Affordable Rooftec,Inc. INSURER C — -- -�---_ -- _--------__ _ -- 2117 SW 57th Ave INSURER D° — -- -- -- - INSURER E: — West Park,FL 33023 _ —_ -- INSURER F: - --- - - — COVERAGES CE_R_1FICATE NUMBER: REVISION NUMBER: THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED R T BOVE FOHE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT,TERM OR CONDITION OF ANY CONTRACTOR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY BE ISSUED OR MAY PERTAIN,THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES.LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS. I -- - — -- ILTR GENERALLIABILTIY INSR YWD;_____.POLICYNUMBER--- IMMID�Y1._tM _ : . LIMITS TYPE OF INSURANCE -y- ADDLSUBR, POLICY EFF ��Hyl.—� OCCURRENCE $ .500 000.00 _ D E TO RENTED 50,000.00 I COMMERCIAL GENERAL LIABILITY PR ISESLa oxurrertce) -: $_- CLAIMS-MADE �/ OCCUR FLGLN02428AX MED EXP(Anyone parson) 5,000.00 -- A _ N ! N 03/22/2016 03/22/2017 — — _ --— ------ --- ---' ,_PER OVAL&ADV INJURY $ 500,000.00 GENE RAL AGGREGA_TE $ 1,000,000.00_ GEN'L AGGREGATE LIMIT APPLIES PER `PRODUCTS-COMP/OP AGG $ 500,000.00 _ lv� -_- - - ---- -- — - -- -- - l a� $ - ---- _�_ E L - r-- ------ - POLICY '_ LOC AUTOMOBILE LUIBILnY INED SINGLE LIMB ANY AUTO BODILY INJURY(Per person) ALOOSWNED AUTOS LED n BODILY INJURY(Per accident; $ — HIRED AUTOS ASO NON-OWNED P O ERTY DAMAGE $ -- -. $ --=UMBRELLA LUU3 OCCUR--- --- - EACH OCCURRENCE — $ -- ---.__ - - - - - EXCESS LIAB---`- CLAIMS-MADE_; AGGREGATE ---- $ DED 1MORKERS COMPENSATION C STATU DTH- ; AND EMPLOYERS'LIABILITY YINANY PROPRIETORIPARTNERIEXECUTIVE I _ELIACH ACCIDENT $ OFFICERIMEMBER EXCLUDED? - N I A - -- --- ---- - Nder myesin NCH) E.L DISEASE-EA EMPLOYEE$ -- -_--- -- DESG�RIPTION OF OPERATIONS belaw _ E.L DISEASE POLICY LIMIT' $ DESCRIPTION OF OPERATIONS I LOCATIONS I VEHICLES(Attach ACORD 101,Addigorsl Remarks Schedule,N more space is required)-- ---- CCC 057535 CERTIFICATE HOLDER CANCELLATION SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE Miami Shores Village THE EXPIRATION DATE THEREOF,NOTICE WILL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. 10050 NE 2 Ave Miami Shores,FI 33138 AUTHORIZED REPRESENTATIVE --y -i----- ---— —---- --- ©1988-2010 ACORD CORPORATION. All rights reserved. ACORD 25(2010/05)QF The ACORD name and logo are registered marks of ACORD A� CERTIFICATE OF LIABILITY INSURANCE DATE ?E(MMIO N n THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER.THIS CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND,EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S),AUTHORIZED REPRESENTATIVE OR PRODUCER,AND THE CERTIFICATE HOLDER. IMPORTANT:If the certificate holder is an ADDITIONAL INSURED,the policy(las)must be endorsed.ff SUBROGATION IS WAIVED,subject to the tern:and conditions of the policy,certain policies may require an endorsement A statement on this certificate does not confer rights to the certificate holder in lieu of such endomement(s). PRODUCER CONTACT NAME: PHONE A1C,No,Ext): 1-800-277-1620 x48M FAX AIC,N,): 797-0704 FrankCrum Insurance Agency,Inc. E-MAIL ADDRESS: 100 South Missouri Avenue INSURERS AFFORDING COVERAGE NAIC0 Clearwater,FL 33756 INSURER A Frank Winston Crum Insurance Co. 11600 INSURED INSURER B: INSURER C: FRANKCRUM LIC/F AFFORDABLE ROOFTEC,INC. INSURER D: 100 SOUTH MISSOURI AVENUE INSURER E: CLEARWATER,FL 33756 INSURER F: COVERAGES CERTIFICATE NUMBER: 338464 REVISION NUMBER. THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAME ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT,TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY 13E ISSUED OR MAY PERTAIN,THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS,EXCLUSIONS AND CONDITIONS OF SUCH POLICIES.LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS. INSR TYPE OF INSURANCE ADDL SUER POLICY NUMBER POLICY EFF POLICY EXP LIMITS LTR INSRD WVD (M=DNYYY) (MWDDNYYY) GENERAL LIABILITY EACH OCCURRENCE $ COMMERCIAL GENERAL LIABILITY DAMAGE TO RENTED CLAIMS-MADE =OCCUR PREMISES aawrerrce $ tdED E7(P(Airy onepeBon) 3 PERSONAL&ADN KIURY S GENERAL AGGREGATE $ GENL AGGREGATE LUMT APPLIES PER PRODUCTS-COMPIOP AGG S POLICY PROJECT LOC $ AUTOMOBILE LIABILITYBIN-SINGLELIMiT $ seal ANY AUTO ALL OWNED SCHEDULED BODILY INJURY(Per person) $ AUTOS AUTOS BODILY INJURY(Par amideM) $ HIR-AUTOS MON-OWNED PROPERTY DAMAGE AUTOS aoddent S S UMBRELLA LIAO OCCUR EACH OCURRENCE $ EXCESS LU18 CLAIMS-MADE AGGREGATE S D- I RETENTION$ 3 WORKERS COMPENSATION AND WC201600000 01/01/2016 01/01/2017 X I STLIATUTORY OTH- A EMPLOYERS'LIABILITY Y/N MITS ER ANY PROPRIEfORIPARTNEWEXECUTIVE OFFICER(MEMBER EXCLUDED? L_J NIA E.L.EACH ACCIDENT $1,000,111M (Mandatory Is NIq Ifyes,descme mer EL DISEASE-EA EMPLOYEE $1,0110.0m DESCRIPTION OF OPERATIONS below EJ_OISEASE4n)UCY LIMIT $1 000 000 DESCRIPTION OF OPERATIONS 1 LOCATIONS 1 VEHICLES(Attach ACORD 101,Additional RemaNw,Schedule,N more space Is required) EFFECTIVE 03/19/2007,COVERAGE IS FOR 100%OF THE EMPLOYEES OF FRANKCRUM LEASED TO AFFORDABLE ROOFTEC,INC.(CLIENT)FOR WHOM THE CLIENT IS REPORTING HOURS TO FRANKCRUM.COVERAGE IS NOT EXTENDED TO STATUTORY EMPLOYEES. CERTIFICATE HOLDER CANCELLATION SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION DATE THEREOF,NOTICE VALL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. MIAMI SHORES VILLAGE BLDG.DEPT. AUTHORIZED REPRESENTATIVE 10050 NE 2ND AVE MIAMI SHORES,FL 33138-2382 +� ©1968-2010 ACORD CORPORATION.All rights reserved. ACORD 26(2010/06) The ACORD name and logo are registered marks of ACORD t: OFFICE OF THE PROPERTY A Summary Report Generated On:6/3/2016 Property Information Folio: 11-3101-033-1330 Property Address: 249 NW 91 ST Miami Shores,FL 33150-2258 OwnerANNE SWANSON 249 NW 91 ST Viz; Mailing Address r MIAMI SHORES,FL 33150 7 s.- Primary Zone 0800 SGL FAMILY-1701-1900 SQ i s N W91 'Si Sl Primary Land Use 0101 RESIDENTIAL-SINGLE FAMILY:1 UNIT Beds/Baths/Half 2/1/0 Floors 1 Living Units Actual Area 1,162 Sq.Ft Living Area 846 Sq.Ft ;V 1371HI Adjusted Area 1,020 Sq.Ft Lot Size 19,375 Sq.Ft Taxable Value Information Year Built 1940 2016 2015 2014 County Assessment Information Exemption Value $50,000 $50,000 $50,000 Year 2016 2015 2014 Taxable Value $102,956 $101,893 $100,688 Land Value $206,250 $152,250 $126,750 School Board Building Value $70,992 $70,992 $69,156 Exemption Value $25,000 $25,000 $25,000 XF Value $1,140 $928 $944 Taxable Value $127,956 $126,893 $125,688 Market Value $278,382 $224,1701 $196,850 City Assessed Value $152,956 $151,893 $150,688 Exemption Value $50,000 $50,000 $50,000 Benefits Information Taxable Value $102,956 $101,893 $100,688 Regional Benefit Type 2016 2015 2014 Exemption Value $50,000 $50,000 $50,000 Save Our Homes Cap Assessment Reduction $125,426 $72,277 $46,162 Taxable Value 1 $102,956 $101,893 $100,688 Homestead Exemption $25,000 $25,000 $25,000 Second Homestead Exemption $25,000 $25,0001 $25,000 Sales Information Note:Not all benefits are applicable to all Taxable Values(i.e.County,School Previous Sale Price OR Book-Page Qualification Description Board,City,Regional). 05/24/2010 $168,000 27312-2358 Qual by exam of deed Short Legal Description 10/01/2005 $325,000 23838-4727 Sales which are qualified MIAMI SHORES SEC 6 PB 10-39 04/01/1981 $49,000 11074-1382 Sales which are qualified E1/2 LOT 17&LOT 18 BLK 136 07/01/1977 $32,000 09734-1134 ISales which are qualified LOT SIZE 75.000 X 125 OR 11074-1382 0481 1 COC 23838-4727 10 2005 1 The Office of the Property Appraiser is continually editing and updating the tax roll.This website may not reflect the most current information on record.The Property Appraiser and Miami-Dade County assumes no liability,see full disclaimer and User Agreement at http://www.miamidade.gov/info/disdaimerasp Version: AFFORDABLE ROOFTECs INC 2117 S."'.57"Ave Ph:(954)962-9670 !'Fest Park,FL 33023 Fax:(953)513-007:- affordable incra'bellsouth.net Lic#CCC-057535 Date: 06/06/2016 Contract Submitted to: Job Address: Owner:Ms.Anne Swanson 249 NW 91 Street Attn:Silvia Ros—305-510-4978 Miami Shores,FL 33150 Silvia@SilviaRos.com WE HEREBY PROPOSE TO FURNISH ALL MATERIALS AND PREFORM ALL LABOR NECESSARY FOR THE COMPLETION OF THE JOB DESCREMON AND GUIDELINES BELOW: Scope of Vb1ork as follows:(14 Secure permit Remove existing roof down to wood sheathing&inspect condition of wood Re-nail existing sheathing to meet current codes Install 30#ASTM Felt base sheet with 1 W Ringshank nails,and 15/8°Tin Caps Install 26 Gauge Galy.34 EAVE drip metal Install 16°Valley metal,mechanical vents and lead flashing as needed Install New 45 L-Flashing as needed Install 90#Hot Mopped over 30If as per code Install metal ridge to secure ridge caps Install Boral,Crown,Eagle, or Hanson Tiles[Standard Concrete tiles only]-(Color selection by owner) All field tiles attached using polyfoam files system(large patty) Clean and haul all debris All local codes enforced Price includes up to 150'(one hundred fifty feet)of wood replacement—additional lumber wig be replaced at the following rates: $1.75 per square foot for plywood $3.00 per firwfoot for 1x6,U8,1x10 (DECKING) $3.50 per linear foot for 2x4,26,and 2x8(RAFTERS) $5.50 per linear foot for lx6,1x8,or 1x10(FASCIA) Note:Any a/c,plumbing,solar panels,or electrical work needed is the responsibility of the owner to secare.The owner is also responsible for gutter remove/replacement.Due to Hurricane code changes in Oct 2007 our price does not include engineering fees and/or hurricane straps. Contract Peace: $ 9,100.00 AFFORDABLE ROOFTEC,INC.WARRANTIES THE ABOVE WORK FOR TEN(10)YEARS ALL MATERIAL IS GUARANTEED TO BE AS SPECIFIED AND THE ABOVE WORK TO BE PERFORMED IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS SUBMITTED FOR THE ABOVE WORK AND COMPLETED IN A SUBSTANTIAL WORKMANLIKE MANNER Payment Process ind 'Procedury. 20%DEPOSIT ATCONTRACTSIGNING 20%ATDRY IN40%ATLOAD AND 20%ATFINAL Au PRICE QUOTES ARE FOR CASH OR CHECK PAYMENT ONLY SUBSEQUENT WORK WILL NOT BE PERFORMED U PREVIOUS DRAWS ARE PAID.ALL INVOICES ARE DUE UPON RECEIPT.ANY ALTERATION OR DEVIATION FROM AROVE SP CATIONS INVOLVING EXTRA COSTS WILL BE EXECUTED ONLY UPON WRITTEN ORDERS AND WILL INCUR ADDITIONAL CHAROVER AND ABOVE THE ESTIMATE ALL AGREEMENTS ARE CONTINGENT UPON STRIKES,ACCIDENTS OR DELAYS BEYO OUR NTROL WE ARE COVERED BY WORKMAN'S COMPENSATTON AND PUBLIC LIABILITY INSURANCE FOR THE PROPOSAL OF WO71B ABO WILL NOT BE ACCEPTED AS FORM OF PAYMENT y: '; r }' Vasile Malinetescu-Aresident GJIS TEM PROPOSAL MAY BE WITHDRAWN BY US IF NOT ACCEPTED WITHIN 30 DAYS Arceotance of Contract: THE ABOVE PRICES,SPECIFICATIONS AND CONDITIONS ARE SATISFACTORY AND ARE HEREBY ACCEPTED.YOU ARE AUTHORIZED TO THE WORK AS SPECIFIED.PAYMENT WILL BE MADE AS OUTLINED ABOVE Client Signature: � Date: Print Name: ,��Qp� Miami shores Village •�.. au. Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 �ORIDp' Tel: (305) 795.2204 Fax: (305) 756.8972 OWNERS'S AFFIDAVIT OF EXEMPTION ROOF TO WALL CONNECTION HURRICANE MITIGATION RETROFIT FOR EXISTING SITE- BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES PERSUANT TO SECTION 553.844 F.S. To: Miami Shores Village Building Department Date:a/ � 10l 10050 NE 2nd Ave Miami Shores, FI 33138 Re: Owner's Name: Pin WGnz'0n Property Address: 2 4 9 N ff)l g ,, 31�, o L 33 is Roofing Permit Number: t '� Dear Building Official: I certify that I am not required to retrofit the roof to wall connections of my building because: ` The just valuation for the structure for purpose of ad valorem taxation is less than $300,000,.00. Please attach proof of ad valorem taxation. ❑The building was constructed in compliance with the provisions of the Florida Building Codd(FBC) or with the provisions of 1994 edition of the South Florida Building Code(1994 SFBC) Signature Print Name State of Florida County of Bade�jgc��or� The undersigned, being the first duly swom, deposes and says that he/she is the owner for the above property mentioned, Sworn to and subscribed before me this day of l.)Y12 ZU� ,�iQtiq�1C`ya4,; SIMON:LELUTIU MY COMMISS54759. PEXPIRES.ANotary Public, Sate of Florida at Labr rge rrlal , uh 1, ;t eondodThro d201�rs e When the Just valuation of the structure for purpose of ad valorem�xaal to or more than$300,000.00,and the building was not constructed with FBC nor a 1994 SFBC.Then you must provide a building application from a General Contractor for the Roof to Wall connection Hurricane Mitigation. Revised on 5/21/2009 Florida Building Code 5th Edition(2014) ON RA JUN 19 2016 tilt igh-Velocity Hurricane Zone Uniform Permit Application Form, r�q� Section A(General Information) Ma r .v: Process No. contractor's Name Affordable Rooftec Inc (954) 962-9670 Job Address 249 NW 91st Street, Miami, FL 33150 ROOF CATEGORY ❑ Love Slope ❑ Mechanically Fastened Tile 13 Mortar/Adhesive Set Tiles ❑ Asphaltic Shingles ❑ Metal PanellShingles ❑ Wood Shingles/Shakes ❑ Prescriptive BUR-RAS 150 ROOF TYPE ❑ New roof ❑ Repair ❑ Maintenance IN Reroofing ❑ Recovering ROOF SYSTEM INFORMATION LoSlope Roof Area(SF} Steep Sloped Roof AREA(SSF} Total(SF) 1283 sr NA 1283 Section B (Roof Plan) Sketch Roof Plan: Illustrate all levels and sections, roof drains,scuppers, overflow scupp and gverflo drains. Include dimen- sions of sections and levels, clearly identify dimensions of elevated pressure zones and}bcaii of parapets Jim F d4 • • •• • • • •• • 2 • • • • • • • • • •• • • • • • •• • ed so 0 • •• •• • • • •• •• 000 • 0 0 066 • 0 Florida Building Code 5th Edition(2014) High-Velocity Hurricane Zone Uniform Permit Application Form Section D(Steep Sloped Roof System) Roof System Manufacturer: Eagle Roofing Products LLC Notice of Acceptance Number: 15-0223.18 Minimum Design wind Pressures, If Applicable(From RAS 127 or Calculations): P1:39.1 P1: 68.1 P1: 100.7 Deck Tye: Plywood Type Underlaynent: 130# ASTM Felt Type 2 Roof Slope: 3 : 12 ', Insulation: N/A Fire Barrier. N/A Ridge Ventilation? Fastener Type & Spacing. 11/4"Ringshank Nails w/15/80 Tincaps iField: 12"o/c,L a :60 o/c Dd e:4'o/c Adhesive Type: 190# ASTM w/ asphalt Type Cap Sheet: N/A l Mean Roof Height: 14 Roof Covering: Eagle-Bel Air-Arrowhead Gre . .. . . . . ... . Type &Size Drip 3x3 Eave 26 gauge G Ivn .. ... .. . . .. Edge: .. . ... . .. . ... . . . . ... . . . . . . . . . . . . . .. .. . . . .. .. ... . . . ... . . Florida Building Code 5th Edition(2014) High-Velocity Hurricane Zone Uniform Permit Application Form. Section E(Tile Calculations) For Moment based file systems, choose either Method 1 or 2. Compare the values for M,with the values from M,. If the M.values are greater than or equal to the M,values.for each area of the roof,then the the attachment method is acceptable. Method 1 "Moment Based Tile Calculations Per RAS 127" (P1.39.1 x x.0.278= 10.87)-Mg;7.71 =M,t 3.16 Product Approval M, 118.8 (P2: xa. 278 0. = 18.93)_Mg;7.71 =M2 11.22 Product Approval M 118. (P3:100.7 xis 0.278= 27.99)_Mg:7.71 =M, 20.28 Product Approval M, 118. Method 2"Simplified Tile Calculations Per Table Below" Required Moment of Resistance(M) From Table Below 32.2 Product Approval M, 118.9 M,required Moment Resistance' Mean Roof Height 15' 20' 25' 30' 40' Roof Slope 2:12 34.4 36.5 38.2 39.7 42.2 3:12 32.2 34.4 36.0 37.4 39.8 4:12 30.4 32.2 33.8 35.1 37.3 5:12 26.4 30.1 31.6 32.8 34.9 6:12 26.4 28.0 29.4 30.5 32.4 7:12 24.4 25.9 27.1 28.2 30.0 'Must be used in conjunction with a list of moment based the systems endorsed by the Broward County Board of Rules and Appeals. For Uplift based tie systems use Method 3. Compared the values for F with the values for Fr. If the F'values are greater than or equal to the Fr values,for each area of the roof,then the tile attachment method is acceptable. Method 3"Uplift Based Tile Calculations Per RAS 127" (P1: x L = x w:= )-W: x cos 0 = F„ Product Approval F' (P2: x L = x w:= )-W: x cos 0 =Fr2 Product Approval F (P3: x L = x w: =_)-W: x cos H = F,, Product Approval F' Where to Obtain Information Description Symbol Where to find Design Pressure P1 or P2 or P3 RAS 127 Table 1 or by an engineering analysis pre- pared by PE based on ASCE 7 Mean Roof Height H Job Site Roof Slope H Job Site Aerodynamic Multiplier Product Approval Restoring Moment die to Grhvfty; ; ; ; Mg Product Approval Attachment Resistance,i ••i ••i • • i ••• M, Product Approval Required Moment Resistance M� Calculated Minimum Attachment PgWstance. . 0 F' Product Approval Required Uplift Re�ijtan;e 0 •• F, Calculated Average Tile Weight ••• .. • W Product Approval Tile Dimensions L =length W=width Product Approval All calculations mustale sgbmgpcttathtVuilding efficial at the time of permit application. • • . • • • . • . . • •• •• 0.0 • • •• •e ••• • • • ••• • • Florida Building Code 5th Edition(2014) Section 152- HIGH—VELOCITY HURRICANE ZONES- REQUIRED ON's VERS NOTIFICATION FOR ROOFING CONSIDER4TIONS 1524.1 Scope. As it pertains to this section, it is the responsibility of the roofing contractor to provide the o%vner with the required roofing permit,and to explain to the owner the content of this section. The provisions of the Chapter 15 of the Florida Building Code,Building govern the minimum requirements and standards of the industry for rooting system installations. Additionally,the following items should be addressed as part of the agreement between the owner and the contractor. The owner's initial in the designated space indicates that the item has been explained. CAI- Renailing wood decks: When replacing roofing,the existing wood roof deck may have to be renailed in accordance with the current provisions of Chapter 16(High-Velocity Hurricane Zones)of the.(The roof deck is usually concealed prior to removing the existing roof system). �✓ 2. Exposed ceilings:Exposed,open beam ceilings are where the underside of the roof decking can be viewed from below. The owner may wish to maintain the architectural appearance;therefore,roofing nail penetrations of the underside decking may not be acceptable. The owner provides the option of maintaining this appearance. W3. Ot,er[low scuppers(wall outlets): It is required that rainwater flow off so that the roof is not overloaded from a buildup of water. Perimeter/edge vwalls or other roof extensions may block this discharge if overflow scuppers(wall outlets)are not provided. It may be necessary to install overflow scuppers in accordance with the requirements of:Chapter IS and 16 herein and the Florida Building Code,Plumbing. A wnDate's/ 'sSignatureeerr .. ... • . • . • .. • •• • • • • ••• • •• ••• •• • • • •• •• • ••• • •• • ••• • • • • ••• • • • • • • • • • • • • • •• •• • • • •• •• ••• • • • ••• • • MIAMI-DADE COUNTY MIAMIPRODUCT CONTROL SECTION 11805 SW 26 Street,Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES(RER) Miami,Florida 33175-2474 BOARD AND CODE ADMINISTRATION DIVISION (786)315-2590 F(786)315-2599 NOTICE OF ACCEPTANCE (NOA) �vw.miamidade.gov/economv Eagle Roofing Products LLC 1575 East C.R.470 Sumterville,FL 33585 SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be used in Miami-Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ). This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section (in Miami-Dade County)and/or the AHJ(in areas other than Miami-Dade County)reserve the right to have this product or material tested for quality assurance purposes.If this product or material fails to perform in the accepted manner,the manufacturer will incur the expense of such testing and the AHJ may immediately revoke,modify,or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein,and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: Be]Air,Bel Air Double Eagle,Ponderosa,Ponderosa Double Eagle,'Golden Eagle Low Profile Concrete Tiles LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city, state and following statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials,use,and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product, for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed,then it shall be done in its entirety. INSPECTION: A tppy-a>�ii egtVe jlQASpall be provided to the user by the manufacturer or its distributors and shall be available fol insf 8ctio$at1he job Afe at the request of the Building Oficial. This NOA revise,N94#12-0438.-04 and consists of pages 1 through 10. The submitted dbPgmQntapon.*as:-evle*p6 Ily f'iaspar J Rodriguez. , .. .. 0 see ••• . .. NOA No.:15-0223.18 PgUAP71•DADE COUNTY Expiration Date: 10/05/16 • • ^_� Approval Date: 09/24/15 • ••• • Page 1 of 10 ••• 0 0 0 009 0 0 ROOFING ASSEMBLY APPROVAL Category: Roofing Sub Category: Roofing Tiles Material: Concrete I. SCOPE: This approves a new roofing system using"Low Profile Concrete Tile" as manufactured by Eagle Roofing Products LLC in Sumterville, FL and described in Section 2 of this Notice of Acceptance. For locations where the pressure requirements, as determined by applicable Building Code does not exceed the design pressure values obtained by calculations in compliance with RAS 127 using the values listed in section 4 herein. The attachment calculations shall be done as a moment based system. 2.PRODUCT DESCRIPTION: Manufactured by Test Product Applicant Dimensions Specifications Description Bel Air Concrete Tile L= 17" TAS 112 Flat profile concrete roof tile equipped with two W= 12 ''/4" nail holes. For adhesive set,direct deck or Thickness= '/z" battened nail-on applications. Bel Air Double Eagle L= 17" TAS 112 Flat profile concrete roof file equipped with two Concrete Tile W= 12 '/4" nail holes. For adhesive set,direct deck or Thickness= %2" battened nail-on applications. Ponderosa Concrete Tile L= 17" TAS 112 Flat profile concrete roof tile with slate finish W= 12 '/4" equipped with two nail holes. For adhesive set, Thickness= '/Z" direct deck or battened nail-on applications. Ponderosa Double Eagle L= 17" TAS 112 Flat profile concrete roof file with shake finish Concrete Tile W= 12 '/4" equipped with two nail holes. For adhesive set, Thickness= '/a" direct deck or battened nail-on applications. Golden Eagle Concrete L= 17" TAS 112 Flat profile concrete roof file brushed finish Tile W= 12 '/4" equipped with two nail holes. For adhesive set, Thickness= ''/2' direct deck or battened nail-on applications. Trim Pieces L=varies TAS 112 Accessory trim,clay roof pieces for use at hips, W=varies rakes,ridges and valley terminations. varying thickness Manufactured for each file profile. .. ... . . . . . .. .. ... .. . . . .. NOA No.:15-0223.18 MAMI•DADE COUNTY ;,, •• •o o � � � � see � � Expiration Date: 10/05/16 . . . . Approval Date: 09/24/15 . . . . . . . . . . Page 2 of 10 . .. .. . . . .. .. ... . . . ... . . 2.1 EVIDENCE SUBMITTED: Test Agencv Test Identifier Test Name/Reuort Date PRI Asphalt Technologies ERPF-001-02-01 TAS 112 Aug.2006 Redland Technologies 7161-03 Static Uplift Testing Dec. 1991 Appendix III TAS 102 Redland Technologies 7161-03 Static Uplift Testing Dec. 1991 Appendix III TAS 102(A) Redland Technologies 7161-03 Wind Tunnel Testing Dec. 1991 Appendix H TAS 108(Nail-0n) Redland Technologies P0402 Withdrawal Resistance Testing of screw vs. Sept. 1993 smooth shank nails Redland Technologies Letter Dated Aug. 1, Wind Tunnel Testing Aug. 1994 1994 TAS 108 (Nail-On) Redland Technologies P09647-01 Wind Tunnel Testing Aug. 1994 TAS 108 (Mortar Set) The Center for Applied 94-084 Static Uplift Testing May 1994 Engineering, Inc. TAS 101 (Mortar Set) The Center for Applied 25-7094-(2,5,&8) Static Uplift Testing Oct. 1994 Engineering,Inc. TAS 102 The Center for Applied 25-7183-(5 thru 6) Static Uplift Testing Feb. 1995 Engineering,Inc. TAS 102 The Center for Applied 25-7214-(1, 5 , &8) Static Uplift Testing March, 1995 Engineering,Inc. TAS 102 The Center for Applied 25-7487-2 Static Uplift Testing Dec. 1995 Engineering,Inc. TAS 102 The Center for Applied 25-7496-(1 &4) Static Uplift Testing Dec. 1995 Engineering,Inc. TAS 102 The Center for Applied 25-7804-6 Static Uplift Testing Sep. 1996 Engineering,Inc. TAS 102 Celotex Corporation Testing 520109-1 Static Uplift Testing Dec. 1998 Service 520111-4 TAS 101 Celotex Corporation Testing 520191-1 Static Uplift Testing March 1999 Service TAS 101 Walker Engineering,Inc. Calculations Aerodynamic Multiplier Sep.2006 Walker Engineering,Inc. Calculations Restoring Moments Due to Gravity Sep.2006 .. ... . . • . . •• .. . . . . • . • . • • • .. ... .. . . . .. . 0:0 • 0 :0 . . . . . . . .. . . . . . .. . . & 00 • see • •• • NOA No.:15-0223.18 MLA A94DADE couPiTY Expiration Date: 10/05/16 Approval Date: 09/24/15 0Page 3 of 10 :090:. . . . ..... . . . . . . ... • • . 000 0 0 3 LBUTATIONS: 3.1 Fire classification is not part of this acceptance. 3.2 For mortar or adhesive set tile applications,a static field uplift test in accordance with TAS 106 shall be required,refer to applicable Building Code. 3.3 Applicant shall retain the services of a Miami-Dade County Certified Laboratory to perform quarterly test in accordance with TAS 112,appendix `A'. Such testing shall be submitted to the Miami-Dade County Product Control Section for review. 3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed section 4.1 herein. 3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated otherwise by the underlayment material manufacturers published literature. 3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with applicable Building Code. 4 INSTALLATION: 4.1 Eagle Roofing Products LLC Bel Air, Bel Air Double Eagle, Ponderosa, Golden Eagle,Ponderosa Double Eagle Flat Concrete Roof Tiles and its components shall be installed in strict compliance with Roofing Application Standard RAS 118,RAS 119 and RAS 120. 4.2 Data For Attachment Calculations Table 1: Average Weight (W) and Dimensions (I x w) Tile Profile Weight-W(Ibf) Length-I (ft) Width-w (ft) Bel Air, Bei Air Double Eagle, 11.4 1.42 1.03 Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile Table 2: Aerodynamic Multipliers -A (ft3) Tile Profile A(ft3) A (ft3) Batten Application Direct Deck Application Bel Air, Bel Air Double Eagle, 0.301 0.278 Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile .. ... . . . . . .. .. . . . . %: •.• . •.• • 0 so.. . . . . . .. . . 0 see so ... .. 1w1AM�•®ADE COUTiIY NOA No.:15-0223.18 v . , m - Expiration Date: 10/05/16 • . • Approval Date: 09/24/15 Page 4 of 10 .so* 0..... . . . .. ... . . . . . . . I Table 3: Restoring Moments due to Gravity- M9 (ft-lbf) Tile 3":12" 4":12" 5":12" 6":12" Greater than Profile 7":12" Bel Air, Bel Air Battens Direct Battens Direct Battens Direct Battens 'Direct Battens Direct Double Eagle, Deck Deck Deck Deck Deck Ponderosa, 7.48 7.71 7.37 7.59 7.22 7.44 7.05 7.27 6.86 7.07 Golden Eagle, Ponderosa Double Eagle Flat Tile Table 4: Attachment Resistance Expressed as a Moment - Mf(ft-lbf) for Nail-On Systems Tile Fastener Type Direct Deck Direct Deck Battens Profile (min 15/32" plywood) (min. 19/32" plywood) Bel Air, Bel 2-10d Ring Shank Nails 30.9 38.1 17.2 Air Double 1-10d Smooth or Screw 7.3 9.8 4.9 Eagle, Shank Nail Ponderosa, 2-10d Smooth or Screw 14.0 18.8 7.4 Golden Shank Nails Eagle, 1 #8 Screw 30.8 30.8 18.2 Ponderosa 2#8 Screw 51.7 51.7 24.4 Double 1-10d Smooth or Screw 24.3 24.3 24.2 Eagle Flat Shank Nail Field Clip) Tile 1-10d Smooth or Screw 19.0 19.0 22.1 Shank Nail Eave Clip) 2-10d Smooth or Screw 35.5 35.5 34.8 Shank Nails Field Clip) 2-10d Smooth or Screw 31.9 31.9 32.2 Shank Nails Eave Clip) 2-10d Ring Shank Nails' 50.3 65.5 48.3 1. Installation with a 4"tile headlap and fasteners are located a min. of 2Y2"from head of tile. .. ... .. . . . .. see a:*as ... .• • . . • . .. . . MIAMI•DADE COUNTY NOA No.:15-0223.18 ® • ••• Expiration Date: 10/05/16 • • • • • Approval Date: 09/24/15 • • • ••• • • • Page 5 of 10 •.. . • . •.. . . Table 5: Attachment Resistance Expressed as a Moment Mf(ft-lbf) for Two Patty Adhesive Set Systems Tile Tile Application Minimum Attachment Profile Resistance Bel Air, Bel Air Double Eagle, Adhesive' 31.32 Ponderosa, Golden Eagle, Ponderosa Double Eagle Flat Tile 1 See manufactures component approval for installation requirements. 2 Flexible Products Company TileBond Average weight per patty 13.9 grams. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 Average weight per patty 8 grams. Table 6: Attachment Resistance Expressed as a Moment- Mf(ft-lbf) for Single Patty Adhesive Set Systems Tile Profile Tile Application Minimum Attachment Resistance Bel Air, Bel Air Double Eagle, 31VITM 2-Component Foam Roof Tile Adhesive AH-160 118.93 Ponderosa, Golden Eagle, 3MTm 2-Component Foam Roof Tile Adhesive AH-160 40.44 Ponderosa Double Eagle Flat Tile 3 Large paddy placement of 45 grams of Pol ProTAA. 4 Medium paddy placement of 24 grams of Pol ProTm. Table 7: Attachment Resistance Expressed as a Moment- Mf(ft-lbf) for Mortar Set Systems Tile Tile Attachment Profile Application Resistance Bel Air, Bel Air Double Eagle, Ponderosa, Golden Mortar Set' 43.9 Eagle, Ponderosa Double Eagle Flat Tile 5 Tile-Tite Roof Tile Mortar. .. ... . . . . .. . .. . . . . ... . .. . . . . . .. . . MIAMI•DADE COUNTY NOA No.:15-0223.18 o • • • ••• • • Expiration Date: 10/05/16 • Approval Date: 09/24/15 �•••� �••,� Page 6of10 ... . . . ... . . I 5. LABELING : All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo (See Detail Below),or following statement: "Miami-Dade County Product Control Approved". EAIGLTia, FLORIDA (LOCATED ON UNDERSIDE OF TILE) OR EAGLE FL (LOCATED ON FRONTSIDE OF TILE) BEL AIR,BEL AIR DOUBLE EAGLE,PONDEROSA,GOLDEN EAGLE,PONDEROSA DOUBLE EAGLE CONCRETE ROOF TILE LABEL,SUMTERVILLE PLANT 6. BUILDING PERMIT REQUIREMENTS: 6.1 Application for building permit shall be accompanied by copies of the following: 6.1.1 This Notice of Acceptance. 6.1.2 Any other documents required by AHJ or applicable Building Code in order to properly evaluate the installation of this system. .. ... . . . . . .. . .. . . . . ... . .. ... .. . . . .. .. . . . . . .. . . •• . .. • • . 00 MIAMI•DADE 0.0 NOA No.:15-0223.18 •• • • • ••• . • Expiration Date: 10/05/16 • • • • • • • • Approval Date: 09/24/15 • • • ••• • • • Page 7 of 10 ••• 0 0 0 ••• • • PROFILE DRAWING 17 1 , a BEL AIR 17 1 23X . .. . . . . ... . BEL AIR DOUBLE EAGLE • 4141• • 41.41 • • 4141 • • • • • 4141 • • • 4141 • ••. • 41•4141 • • • • . NOA No.:15-0223.18 MLAP11•DADECouNTY Expiration Date: 10/05/16 0 0 • : : : : �: : : Approval Date: 09/24/15 • • • ••• • • . Page 8 of 10 • • • • • • • • • • • 4141 4141 • s • 4141 4141 .41• • • • 4141• • 0 '4 q'NN� 17 1 21A PONDEROSA Soy Elf _ 4 7 ae PONDEROSA DOUBLE EAGLE . .•• . ... 060 000 :0 000 000�uarsi�wve eouovry 0 0 NOA No.:15-0223.18 1 Expiration Date: 10/05/16 0:0 0:0 :0 Approval Date: 09/24/15 • • . • Page 9 of 10 . . . . . . . . . . • .• .. . . . .. .. ... . . . ... . . 17 12% GOLDEN EAGLE END OF THIS ACCEPTANCE . .. . . . . ... . .. ... .. . . . .. . ... . ... . . .. . . . . . .. . . MIAMI-RADE COUiVYY .• ••• •• • NOA No.:15-0223.18 •MOe Expiration Date: 10/05/16 0:0. . 9:0 Approval Date: 09/24/15 Page 10 of 10 . . . . . . . . . . MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF PERMITTING,ENVIRONMENT,AND REGULATORY AFFAIRS(PERA) 11805 SW 26 Street,Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami,Florida 33175-2474 T(786)315-2590 F(786)315-2599 NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/pera 3M Company 3M Center Building 0220-05-E-06 St.Paul,MN.55144-1000 SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami-Dade County PERA-Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction(AHJ). This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. PERA reserves the right to revoke this acceptance, if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein,and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION:3MTm 2-Component Foam Roof Tile Adhesive AR-160 LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,city,state and following statement: "Miami-Dade County Product Control Approved",unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials,use,and/or manufacture of the product or process.Misuse of this NOA as an endorsement of any product, for sales,advertising or any other purposes shall automatically terminate this NOA.Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This renews and revises NOA# 11-0124.QQ auMdu?dsfs•of pa4es 1 through 7. The submitted documentation was wAriewc%4y;kfex Tigara?• 0 see so* ••• ;• o.7 ••• ••• NOA No.:12-0228.18 MIAMNDADE COUNTY Expiration Date:05/10/17 Approval Date:05/10/12 ••• ••• Page 1 of 7 . . . . . . . . . . . .. •• ... .• .. .. ... . . .. . . ROOFING COMPONENT APPROVAL: Category: Roofing Sub Category: Roof tile adhesive Materials: Polyurethane SCOPE: This approves 3MTM 2-Component Foam Roof Tile Adhesive AH-160 as manufactured by 3M Company as described in Section 2 of this Notice of Acceptance.For the locations where the design pressure requirements,as determined by applicable building code,does not exceed the design pressure values obtained by calculations in compliance with Roofing Application Standard RAS 127,for use with approved flat, low,and high profile roof tiles system using 2-Component Foam Roof Tile Adhesive AH-160. Where the attachment calculations are done as a moment based system for single patty placement,and as an uplift based system for double patty systems PRODUCTS MANUFACTURED BY APPLICANT: Product Dimensions Test Product Description Specifications 3MTM 2-Component Foam N/A TAS 101 Two component polyurethane foam adhesive Roof Tile Adhesive AH- 160 Foam Dispenser RTF 1000 N/A Dispensing Equipment ProPack®30& 100 N/A Dispensing Equipment PRODUCTS MANUFACTURED BY OTHERS: Any Miami-Dade County Product Control Accepted Roof Tile Assembly having a current NOA which list moment resistance values with the use of 2-Component Foam Roof Tile Adhesive AH-160 roof tile adhesive. MANUFACTURING LOCATION: 1. Tomball,TX. PHYSICAL PROPERTIES: Prope Test Results Density ASTM D 1622 1.6lbs./ft.3 Compressive Strength ASTM D 1621 18 PSI Parallel to rise 12 PSI Perpendicular to rise Tensile Strength ASTM D 1623 28 PSI Parallel to rise Water Absorption ASTM D 2127 0.08 LbsJFe Moisture Vapor Transmission ASTM E 96 3.1 Perm/Inch Dimensional Stability •• • ISTM.D 2126 .. +0.07%Volume Change @-40°F.,2 weeks .: +6.0%Volume Change @ 58°F., 100%Humidity,2 . .. . . . . ... . • • weeks Closed Cell Content •• ••• AST M D 2856•• 86% . OV . . . . " NOA No.: 12-0228.18 MIAMMADE COUNTY go Expiration Date:05/10/17 • Approval Date:05/10/12 ••• ••• Page 2of7 . . . . . . . . . . . .. .. . . . .. .. ... . . . ... . . Note: The physical properties listed above are presented as typical average values as determined by accepted ASTM test methods and are subject to normal manufacturing variation. EVIDENCE SUBMITTED: Test Agency Test Identifier Test Name/Rep ort Date Center for Applied Engineering #94-060 TAS 101 04/08/94 257818-IPA TAS 101 12/16/96 25-7438-3 SSTD 11-93 10/25/95 25-7438-4 25-7438-7 SSTD 11-93 11/02/95 25-7492 SSTD 11-93 12/12/95 Miles Laboratories NB-589-631 ASTM D 1623 02/01/94 Polymers Division Ramtech Laboratories,Inc. 9637-92 ASTM E 108 04/30/93 Southwest Research Institute 01-6743-011 ASTM E 108 11/16/94 01-6739-062b[l] ASTM E 84 01/16/95 Trinity Engineering 7050.02.96-1 TAS 114 03/14/96 Celotex Corp.Testing Services 528454-2-1 TAS 101 10/23/98 528454-9-1 528454-10-1 520109-1 TAS 101 12/28/98 520109-2 520109-3 520109-6 520109-7 520191-1 TAS 101 03/02/99 520109-2-1 LIMITATIONS: 1. Fire classification is not part of this acceptance.Refer to the Prepared Roof Tile Assembly for fire rating. 2. 3Mrm 2-Component Foam Roof Tile Adhesive AH-160 shall solely be used with flat,low,&high tile profiles. 3. Minimum underlayment shall be in compliance with the Roofing Application Standard RAS 120. 4. Roof Tile manufactures acquiring acceptance for the use of 3MTM 2-Component Foam Roof Tile Adhesive AH- 160 roof tile adhesive with their tile assemblies shall test in accordance with TAS 101. 5. Roof Tile manufactures acquiring acceptance for the use of HANDI-STICK roof tile adhesive with their file assemblies shall test in accordance with TAS 101 with section 10.4 as modified herein. ! FI 2 '.. �;�:. . . . . .. F— .. . . . . ... .. . . . . . .. . . .. .. • NOA No.: 12-0228.18 MIAMI-DARE COUNTY • ••• • • Expiration Date:05/10/17 e e Approval Date:05/10/12 ••• ••• Page 3of7 . . . . . . . . . . . .. .. . . . .. .. ... . . . ... . . INSTALLATION: t. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 may be used with any roof file assembly having a current NOA that lists uplift resistance values with the use of 3MTm 2-Component Foam Roof Tile Adhesive AH-160. 2. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 shall be applied in compliance with the Component Application section and the corresponding Placement Details noted herein. The roof tile assembly's adhesive attachment with the use of 3MTm 2-Component Foam Roof Tile Adhesive AH-160 shall provide sufficient attachment resistance,expressed as an uplift based system,to meet or exceed the uplift resistance determined in compliance with Miami-Dade County Roofing Application Standards RAS 127. The adhesive attachment data is noted in the roof tile assembly NOA. 3. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 and its components shall be installed in accordance with Roofing Application Standard RAS 120,and 3M Company's 3MTm 2-Component Foam Roof Tile Adhesive AH- 160 Operating Instruction and Maintenance Booklet. 4. Installation must be by a Factory Trained'Qualified Applicator'approved and licensed by 3M Company. 3M Company shall supply a list of approved applicators to the authority having jurisdiction. 5. Calibration of the Foam Dispenser RTF 1000 dispensing equipment is required before application of any adhesive. The mix ratio between the"A" component and the"B"component shall be maintained between 1.0-1.15 (A): 1.0 (B). The dispense timer shall be set to deliver 0.0175 to 0.15 pounds per tile as determined at calibration. No other settings shall be approved. 6. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 shall be applied with Foam Dispenser RTF 1000 or ProPack®30& 100 dispensing equipment only. 7. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 shall not be exposed permanently to sunlight. 8. Tiles must be adhered in freshly applied adhesive.Tile must be set within 2 to 3 minutes after 3MTm 2- Component Foam Roof Tile Adhesive AH-160 has been dispensed. 9. 3MTm 2-Component Foam Roof Tile Adhesive AH-160 placement and minimum patty weight shall be in accordance with the'Placement Details'herein. Each generic tile profile requires the specific placement noted herein. Table 1:Adhesive Placement For Each Generic Tile Profile Tile Profile Placement Detail Single Paddy Weight Two Paddy Weight per Min.(grams) paddy Min.(grams) Flat,Low,High Profiles #1 35 N/A High Profile(2 Piece Barrel) #1 17/side on cap and 34/ an N/A Flat,Low,High Profiles #2 24 N/A Flat,Low,High Profiles 1 #3 8 .. ... .. . . . .. see ... ... .. . . . . . .. . . • •• •• NOA No.: 12-0228.18 MIAM4D4DE CO • • Expiration Date:05/10/17 UNTY ® , Approval Date: 05/10/12 •:• : •;• ; Page 4of7 . . . . . . . . . ... :0 . . ... . . LABELING: All 3MI'm 2-Component Foam Roof Tile Adhesive AH-160 containers shall comply with the Standard Conditions listed herein. BUILDING PERmff REQUIREMENTS: As required by the Building Official or applicable building code in order to properly evaluate the installation of this system. ADHESIVE PLACEMENT DETAIL I SINGLE PATTY Nail through plastic cement Paddy(Beneath 711e) Nail through plastic cement Paddy(Beneath Tile) Undedayment Underlayment In 10In. 2 Eave Cmuse Fasda Ea*Cmuse Fascia WUPWO Eave course only: Eave crouse only. Eave closure Eave Closure Keep adhesive approx Keep aft"approx. Drip edge 4 In.up from weepholes 4 in.up from weepholes Nall through plastic cernerd Paddy( 7110) 11)Piece MMO adhesive to addeve 17 to 23 Optional 20s for Nail thrmo plastic cement underkyMent square Inchas In contact With the to a"pitch appkftns I's 2)Turn cm %ce=h 112 In. TO I In.FXo."M=of cover tk Then Inslaill the Ille. Underiayment 10 in. EaveCmm Eave course oW. Em closure Remo Keep adfthwe�&Wvs ape top WIN from weepholes of the am Sheathing caursecovartIle, Abut tosecmudcourseot pan WeL Ensure am of OPS pan and cover ft are P*4-up Mortar 00 on longitudinal . edges of Iffe :aa*-- WeePhols Fascia B 4=sko-) 9:0 0*0 00• 0 :0 :0 0 •6 0,10 NOA No.: 12-0228.18 •TMIA COUNTY Expiration Date:05/10/17 M��D�E�C o Approval Date: 05/10/12 0:0 Page 5 of 7 AmEsiw PLACEMENT DETAIL 2 SINGLE PATTY Nail through plastic cement Paddy(Beneath Tile) Nail through plastic cement Paddy(Beneath rile) Undedaymert Underlayment 1 _ 7 in. 2 in. 7 In. Em Course o Fascia Fascia WWheb Eave Course Eave closure Eave ClearsDrip edge Nail through phuft cement per,(Beneath Tileq) Underlayment 7 In. In. Eave Clem Eave Course Fascia see 6:0 0 0 0 0 0 0 a 6 00 0 so 9 00 0 NOA No.: 12-0228.18 ff��IM�2ECOUNW Expiration Date:05/10/17 111"EMMUM Rub FREW Approval Date:05/10/12 Or Page 6 of 7 Amffmw PLACEMENT DETAIL 3 DOUBLE PATTY Nail through plastic cement Paddy Nail through plastic cement Single paddy under file (between tile) Underlayment Single paddy between tie o Pa* 21n.x 7 In.medium?7N (under tile) size paddy eave course only Single paddy 31n. "n.x 3 In. x 3 In. under tile in V- single 4 lrnL. 2 in. 2 Single paddy on 4 In. under- paddy on laynient under- layment Single paddy Fascia Eave course on top of file Weephole Single paddy In.X 7 in.medium Eave Eave closure on top of tile size paddy eave course Drip edge Fascia course only Nail through plastic cement Single paddy under file Single paddy between file Jr in.x 3 in. 4 In. Single paddy on underlayment 2 n. Single paddy Eave Closure on top of tile 2 in.x 7 In.medium Eave Course Fasciaske paddy eave course only END OF THIS ACCEPTANCE so- so: .00 0.0 so 01: 000 00 0 0*0 0:6 see fee 0: a 00 of 0 a 0 a NOA No.: 12-0228.18 QUNW 08• e• so* 0 •00 Expiration Date:05/10/17 Approval Date:05/10/12 0:0 • Page 7 of 7