RC-13-2385 (4.) �r F_ERNAND13 GOMEZ-PINA P.E. CONSULTING ENGINEER f 250 CATALONIA AVE, # 404 B CORAL GABLES, FL :331 :34 d OCT 2 12013 TEL: (305) 461 -21 Be FAX: (305) 461-2236 j STRUCTURAL CALCULATIONS Chee -Awai Residence 1370 NE 103 Rd Street Miami Shores F133138 TABLE OF CONTENTS • Design Criteria .........................................................................Sheet I • Wind Load Calculations ............................................................. Sheets 2—5 GOINF t4 S'e W • 'k ° a _ LL. . QF .to = OP, SS11 IONPL�� 6 0 "fill l l l"0 D V . F' STRUCTURAL CALCULATION WIND LOADS (ANSUASCE 7-10) Method 2 -Analytical Procedure Basic Wind Speed, V=175 mph (FBC 2010) Structural Category 2 Exposure Category D Importance Factor I =1.0(FBC 2010) Kd=0.85 By Calculations: Dosing Pressures for Components and Cladding Design Wind Pressure for Walls Roof Design Wind Pressure Doors and Windows Design Wind Pressure Design Pressure or Main Wind Force Resisting System Reactions : Gravity and Uplift of Truss and Girder truss e , MECAWind Version 2 . 1 . 0 . 8 per ASCE 7-10 Developed by MECA Enterprises, Inc. Copyright 2013 e;w ..Te=a rzr";�=• -T Date 7/16/2013 Project No. Company Name Designed By Address Description City Customer Name State Proj Location File Location: E:\2013 MARTA MACHIN BUSSINES\ISABELLA LOPEZ\2013-26 PRESSURE WINDOW AND DOORS\PRESSURE WINDOW AND DOORS.wnd Directional Procedure All Heights Building (Ch 27 Part 1) All pressures shown are based upon ASD Design, with a Load Factor of .6 Basic Wind Speed(V) = 175.00 mph Structural Category = II Exposure Category = D Natural Frequency = N/A Flexible Structure = No Importance Factor = 1.00 Kd Directional Factor = 0.85 Damping Ratio (beta) = 0.01 Alpha = 11.50 Zg = 700.00 ft At = 0.09 Bt = 1.07 Am = 0.11 Bm = 0.80 Cc = 0.15 1 = 650.00 ft Epsilon = 0.13 Zmin = 7.00 ft Slope of Roof = 3 : 12 Slope of Roof (Theta) = 14.04 Deg Ht: Mean Roof Ht = 19.92 ft Type of Roof = Hipped RHt: Ridge Ht = 21.58 ft Eht: Eave Height = 18.25 ft OH: Roof Overhang at Eave= 2.00 ft Roof Area = 4227.00 ft^ 2 Bldg Length Along Ridge = 78.00 ft Bldg Width Across Ridge= 42.00 ft Gust Factor Category I Rigid Structures - Simplified Method Gustl: For Rigid Structures (Nat. Freq.>l Hz) use 0.85 = 0.85 Gust Factor Category II Rigid Structures - Complete Analysis Zm: 0.6*Ht = 11.95 ft lzm: Cc* (33/Zm) ^0.167 = 0.18 Lzm: 1* (Zm/33)^Epsilon = 572.50 ft Q: (1/ (1+0.63* ( (B+Ht) /Lzm) ^0.63) ) ^0.5 = 0.93 Gust2: 0.925* ( (1+1.7*lzm*3.4*Q) / (1+1.7*3.4*lzm) ) = 0.89 Gust Factor Summary Not a Flexible Structure use the Lessor of Gu stl or Gust2 = 0.85 Table 26.11-1 Internal Pressure Coefficients for Buildings, GCpi+/_0.18 GCPi : Internal Pressure Coefficient Figure 27.4-1 External Pressure Coefficients Cp - Loads on Main Wind-Force Resisting Systems 1 . h L ehetaheta z � B B Kh: 2.01* (Ht/Zg) ^ (2/Alpha) = 1.08 Kht: Topographic Factor (Figure 6-4) = 1.00 Qh: .00256* (V) ^2*I*Kh*Kht*Kd = 43.28 psf Cpww: Windward Wall Cp(Ref Fig 6-6) = 0.80 Roof Area = 4227.00 ft^2 Reduction Factor based on Roof Area = 0.80 MWFRS-Wall Pressures for Wind Normal to 78 £t wall (Normal to Ridge) Wall Cp Pressure Pressure +GCpi (psf) -GCpi (pef) --------------- ------ ----------- ----------- Leeward Wall -0.50 -26.18 -10.60 Side Walls -0.70 -33.54 -17.96 Wall Elev Rz Rzt qz Press Press Total ft psf +GCpi -GCPi +/-GCpi ---------------- ------ ----- ----- ------- ------- ------- --------- Windward 21.58 1.10 1.00 43.88 22.05 37.63 48.23 Windward 20.00 1.08 1.00 43.31 21.66 37.24 47.84 Windward 10.00 1.03 1.00 41.19 20.22 35.80 46.40 Note: 1) Total = Leeward GCPi + Windward GCPi Roof Location CP +GCPi(pef) -GCpi(psf) ----------------------- ------- ---------- ---------- Windward - Min Cp -0.72 -34.27 -18.70 Windward - Max Cp -0.17 -14.04 1.54 Leeward Perp to Ridge -0.50 -26.18 -10.60 Overhang Top (Windward) -0.72 -26.48 -26.48 Overhang Top (Leeward) -0.50 -18.39 -18.39 Overhang (Windward only) 0.80 28.98 28.98 MWFRS-Wall Pressures for Wind Normal to 42 ft wall (Along Ridge) Wall CP pressure Pressure +GCpi (pef) -GCPi (psf) U --------------- ------ ----------- ----------- Leeward Wall -0.33 -19.88 -4.30 Side Walls -0.70 -33.54 -17.96 ... Wall Elev Kz Kzt qz Press press Total ft psf +GCpi -GCpi +/-GCpi ---------------- ------ ----- ----- ------- ------- ------- --------- Windward 21.58 1.10 1.00 43.88 22.05 37.63 41.93 Windward 20.00 1.08 1.00 43.31 21.66 37.24 41.53 Windward 10.00 1.03 1.00 41.19 20.22 35.80 40.10 Note: 1) Total = Leeward GCPi + Windward GCPi Roof - Diet from Windward Edge CP pressure pressure +GCpi(psf) -GCpi(psf) --------------------------------- ------ ---------- ---------- 0.0 ft to 10.0 ft -0.90 -40.90 -25.32 10.0 ft to 19.9 ft -0.90 -40.90 -25.32 19.9 ft to 39.8 ft -0.50 -26.18 -10.60 39.8 ft to 78.0 ft -0.30 -18.83 -3.25 MECAWind Version 2 . 1 . 0 . 8 ASCE 7-10 Developed by MECA Enterprises, Inc. Copyright 2013 www.me-arntez;i:_._.:T Date 7/16/2013 Project No. Company Name Designed By Address Description City Customer Name State Proj Location File Location: E:\2013 MARTA MACHIN BUSSINES\ISABELLA LOPEZ\2013-26 PRESSURE WINDOW AND DOORS \PRESSURE WINDOW AND DOORS.wnd Roof not -'" i r I sho"n � S 2; 1 ' 2 2' 1 ;2 i 4 ,. 1 5 S, a , 2t ----- 2 Runs a Hip Roof 7 c 0<=27 a Wind Pressure on Components and Cladding (Ch 30 Part 1) All pressures shown are based upon ASD Design, with a Load Factor of . 6 Width of Pressure Coefficient Zone "a" = 4.2 ft Description Width Span Area Zone Max Min Max P Min P ft ft ft^2 GCp GCp psf Psf -------------------------------------------------------------------------- WINDOW 1.25 3.58 4.5 4 1.00 -1.10 51.07 -55.39 WINDOW 1.25 3.58 4.5 5 1.00 -1.40 51.07 -68.38 WINDOW 2.67 2.58 6.9 4 1.00 -1.10 51.07 -55.39 WINDOW 2.67 2.58 6.9 5 1.00 -1.40 51.07 -68.38 WINDOW 7.83 3.50 27.4 4 0.92 -1.02 47.72 -52.05 WINDOW 7.83 3.50 27.4 5 0.92 -1.25 47.72 -61.68 WINDOW 2.58 4.58 11.8 4 0.99 -1.09 50.51 -54.84 WINDOW 2.58 4.58 11.8 5 0.99 -1.37 50.51 -67.27 WINDOW 2.75 4.58 12.6 4 0.98 -1.08 50.30 -54.63 WINDOW 2.75 4.58 12.6 5 0.98 -1.36 50.30 -66.84 WINDOW 4.25 6.17 26.2 4 0.93 -1.03 47.87 -52.19 WINDOW 4.25 6.17 26.2 5 0.93 -1.25 47.87 -61.98 DOOR 16.00 7.00 112.0 4 0.81 -0.91 43.05 -47.37 DOOR 16.00 7.00 112.0 5 0.81 -1.03 43.05 -52.34 DOOR 3.00 7.00 21.0 4 0.94 -1.04 48.60 -52.93 DOOR 3.00 7.00 21.0 5 0.94 -1.29 48.60 -63.45 DOOR 3.00 6.67 20.0 4 0.95 -1.05 48.76 -53.09 DOOR 3.00 6.67 20.0 5 0.95 -1.29 48.76 -63.77 DOOR 2.33 6.00 14.0 4 0.97 -1.07 49.95 -54.28 DOOR 2.33 6.00 14.0 5 0.97 -1.35 49.95 -66.15 Khcc:Comp. & Clad. Table 6-3 Case 1 = 1.08 �1 FORM 405-10 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: CHEE-AWAI Residence Builder Name: Street: 1370 NE 103rd ST Permit Office: Miami Shores City,State,Zip: Miami Shores,FL,33138- Permit Number. Owner. 1370 NE 103rd Stree Jurisdiction: 232600 Design Location: FL,Miami 1. New construction or existing Existing(Projects 9. Wail Types(2955.4 sqft.) Insulation Area 2. Single family or multiple family Multi-family a.Concrete Block-Int Insul,Exterior R=4.1 2556.70 ft2 b.Concrete Block-Int Insul,Adjacent R=11.0 398.67 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 .4. Number of Bedrooms 3 d.N/A R= ft2 5. Is this a worst case? No 10.Ceiling Types (3958.0 sgft.) Insulation Area a.Under Attic(Vented) R=30.0 3958.00 ft 6. Conditioned floor area above grade(ft2) 3958 b.N/A R= ft2 Conditioned floor area below grade(ft2) 0 c.N/A R= f12 11.Ducts R ft2 7. Windows(575.4 sqft.) Description Area a.Sup:Main,Ret:Main,AH:Main 6 525 a. U-Factor: Dbl,U=1.08 575.44 fig b.Sup: Attic,Ret:Attic,AH:Attic 6 200 SHGC: SHGC=0.50 b. U-Factor. N/A ft2 12.Cooling systems kBtu/hr Efficiency SHGC: a.Central Unit 58.5 SEER:16.00 b.Central Unit 36.0 SEER:16.00 c. U-Factor. N/A ft2 SHGC: 13.Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a.Electric Strip Heat 17.4 COP:1.00 SHGC: b.Electric Strip Heat 34.1 COPA.00 Area Weighted Average Overhang Depth: 2.601 ft. Area Weighted Average SHGC: 0.500 14.Hot water systems 8. Floor Types (3958.0 sqft.) Insulation Area a.Natural Gas Cap:66 gallons EF:0.660 a.Slab-On-Grade Edge Insulation R=0.0 2965.00 ft2 b. Conservation features b.Floor Over Other Space R=0.0 993.00 ft2 None c.NIA R= ft2 15.Credits Pstat Glass/Floor Area: 0.145 Total Proposed Modified Loads: 56.54 PASS Total Standard Reference Loads: 98.37 I hereby certify that the plans and specifications covered by Review of the plans and '-T14E S7- this fithis calculation are in compliance with the Florida Energy specifications covered by this ; o�D•n Code. calculation indicates complianceX p�;,•�� / � ` with the Florida Energy Code. O PREPARED BY: Z �y0/6 `�L(�" Before construction is completed DATE: zi this building will be inspected for compliance with Section 553.908 I hereby certify that this building,as designed,is in compliance Florida Statutes. with the Florida Energy Code. 00 WF OWNER/AGENT: ITI -40 BUILDING OFFICIAL: DATE: DATE: - Compliance requires completion f a Florida Air Barrier and Insulation Inspection Checklist OCT -'- 1 3 J 10/21/2013 7:45 AM EnergyGauge@ USA-FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 6 PROJECT Title: CHEE-AWAI Residence Bedrooms: 3 Address Type: Street Address Building Type: User Conditioned Area: 3958 Lot# Owner: 1370 NE 103rd Stree Total Stories: 2 Block/SubDivision: #of Units: 1 Worst Case: No PlatBook: Builder Name: Rotate Angle: 0 Street: 1370 NE 103rd ST Permit Office: Miami Shores Cross Ventilation: No County: Miami-Dade Jurisdiction: 232600 Whole House Fan: No City,State,Zip: Miami Shores, Family Type: Multi-family FL, 33138- New/Existing: Existing(Projected) Comment: CLIMATE / IECC Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range FL,Miami FL_MIAMI_INTL AP 1 51 90 70 75 149.5 56 Low BLOCKS Number Name Area Volume 1 Blockl 2965 21348 2 Block2 993 7149.6 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 Main 2965 21348 Yes 4 2 1 Yes Yes Yes 2 NewSpace2 993 7149.6 No 3 1 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab-On-Grade Edge Insulatio Main 258 ft 0 2965 ftz ____ 0.2 0 0.8 2 Floor Over Other Space NewSpace2 ____ 993 ft' 0 0.2 0 0.8 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch V # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Hip Barrel file 3125 ftz 0 ftz Dark 0.96 No 0.9 No 0 18.4 ATTIC V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC 1 Full attic Vented 300 2965 ftz Y N 10/21/2013 7:45 AM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 6 CEILING # Ceiling Type Space R-Value Area Framing Frac Truss Type 1 Under Attic(Vented) Main 30 2965 ft2 0.11 Wood 2 Under Attic(Vented) NewSpace2 30 993 ft2 0.11 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below _ 1 N Exterior Concrete Block-Int Insul Main 4.1 54 11 7 2 393.6 ft2 4.1 0 0.3 0 _ 2 S Exterior Concrete Block-Int Insul Main 4.1 76 9 7 2 550.0 ft2 4.1 0 0.3 0 _3 E Exterior Concrete Block-Int Insul Main 4.1 34 9 7 2 249.0 ft' 4.1 0 0.3 0 _4 W Exterior Concrete Block-Int Insul Main 4.1 50 0 7 2 358.3 ft2 4.1 0 0.3 0 5 N Exterior Concrete Block-Int InstNewSpace2 4.1 36 0 7 2 258.0 ft2 4.1 0 0.3 0 _6 S Exterior Concrete Block-Int InsLNewSpace2 4.1 36 0 7 2 258.0 ft2 4.1 0 0.3 0 7 E Exterior Concrete Block-Int InsLNewSpace2 4.1 34 2 7 2 244.9 111:2 4.1 0 0.3 0 _8 W Exterior Concrete Block-Int InstNewSpace2 4.1 34 2 7 2 244.9 ft2 4.1 0 0.3 0 9 W Garage Concrete Block-Int Insul Main 11 49 10 8 0 398.7 ft2 11 0 0.3 0 DOORS # Omt Door Type Space Storms U-Value Ft In In FtWidthArea 1 W Wood Main Wood .6 3 6 8 20 ft2 WINDOWS Orientation shown is the entered,Proposed orientation. Wall Overhang V # Omt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening 1 N 1 Metal Low-E Double Yes 1.08 0.5 9.0 ft2 4 ft 6 in 1 ft 1 in None None 2 N 1 Metal Low-E Double Yes 1.08 0.5 20.0 ft2 4 ft 6 in 1 ft 1 in None None 3 N 1 Metal Low-E Double Yes 1.08 0.5 37.5 ft2 2 ft 6 in 0 ft 11 in None None 4 S 2 Metal Low-E Double Yes 1.08 0.5 35.0 ft2 2 ft 6 in 1 ft 0 in None None 5 S 2 Metal Low-E Double Yes 1.08 0.5 96.7 ft2 2 ft 6 in 0 ft 8 in None None 6 S 2 Metal Low-E Double Yes 1.08 0.5 120.0 ft2 2 ft 6 in 1 ft 7 in None None 7 S 2 Metal Low-E Double Yes 1.08 0.5 13.5 ft2 2 ft 6 in 0 ft 11 in None None 8 S 2 Metal Low-E Double Yes 1.08 0.5 18.4 ft2 2 ft 6 in 0 ft 11 in None None 9 E 3 Metal Low-E Double Yes 1.08 0.5 29.6 ft2 2 ft 6 in 0 ft 11 in None None 10 E 3 Metal Low-E Double Yes 1.08 0.5 18.0 ft2 2 ft 6 in Oft 11 in None None 11 E 3 Metal Low-E Double Yes 1.08 0.5 6.4 ft2 2 ft 6 in 10 ft 4 in None None 12 E 3 Metal Low-E Double Yes 1.08 0.5 18.0 ft2 2 ft 6 in 10 ft 4 in None None 13 W 4 Metal Low-E Double Yes 1.08 0.5 18.0 ft2 2 ft 6 in 0111:11 in None None 14 W 4 Metal Low-E Double Yes 1.08 0.5 7.9 ft2 2 ft 6 in 0 ft 11 in None None 15 W 4 Metal Low-E Double Yes 1.08 0.5 29.6 ft2 2 ft 6 in 0 ft 11 in None None 16 N 5 Metal Low-E Double Yes 1.08 0.5 25.2 ft2 2 ft 6 in 0 ft 9 in None None 17 N 5 Metal Low-E Double Yes 1.08 0.5 18.8 ft2 2 ft 6 in 0 ft 9 in None None 18 S 6 Metal Low-E Double Yes 1.08 0.5 13.5 ft2 2 ft 6 in 0 ft 9 in None None 19 E 7 Metal Low-E Double Yes 1.08 0.5 40.5 ft2 2 ft 6 in 0 ft 9 in None None 10/21/2013 7:45 AM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 6 GARAGE # Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation 1 464.2 ft2 464.2 ft2 49.8 ft 8 ft 11 INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse Best Guess .0003 3114.6 170.99 321.56 .2548 6.5575 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Strip Heat None COP: 1 17.4 kBtu/hr 1 sys#1 2 Electric Strip Heat None COP: 1 34.12 kBtu/hr 2 sys#2 COOLING SYSTEM # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit Split SEER:16 58.5 kBtu/hr 1755 cfm 0.7 1 sys#1 2 Central Unit Split SEER:16 36 kBtu/hr 1080 cfm 0.7 2 sys#2 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Natural Gas None Garage 0.66 66 gal 70 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Collector Storage Cert # Company Name System Model# Collector Model# Area Volume FEF None None ft2 DUCTS —Supply— —Return— Air CFM 25 CFM25 HVAC# V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool 1 Main 6 525 ft2 Main 100 ft2 Default Leakage Main (Default) (Default) 1 1 2 Attic 6 200 ft2 Attic 40 ft2 Default Leakage Attic (Default) (Default) 2 2 10/21/2013 7:45 AM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 4 of 6 TEMPERATURES Programable Thermostat:Y Ceiling Fans: Cooling [[XX]]Jan [[XX]]Feb [[XX]]Mar [[XX]]A r [[XX]]Ma P[XQ]Jun 1[)XQ�Jul [[XX]]Au [[XX]]Se [[XX]]Oct P[Xq]Nov Dec Heatin [X]Jan [X]Feb [X]Mar [X]Apr [X]MaY [X]Jun [X]Jul [X]Au [X]Sep [X]Oct [X]Nov Dec Vent [[�Xll Jan [[�Xll Feb [[�X]]Mar [[XX]]A r [[�X]]Ma [[X11 Jun [[X11 Jul [[�X]]Aug [[�X1)Se [[XX]]Oct [[�X])Nov Dec Thermostat Schedule: HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 78 78 78 78 78 78 78 78 78 78 Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78 PM 78 78 78 78 78 78 78 78 78 78 78 78 Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 66 66 MECHANICAL VENTILATION Type Supply CFM Exhaust CFM Fan Watts HRV Heating System Run Time Cooling System None 0 0 0 0 1-Electric Strip Heat 0% 2-Central Unit 10/21/2013 7:45 AM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 6 FORM 405-10 Florida Code Compliance Checklist Florida Department of Business and Professional Regulations Residential Whole Building Performance Method ADDRESS: 1370 NE 103rd ST PERMIT#: Miami Shores, FL, 33138- MANDATORY REQUIREMENTS SUMMARY-See individual code sections for full details. COMPONENT SECTION SUMMARY OF REQUIREMENT(S) CHECK Air leakage 402.4 To be caulked, gasketed,weatherstripped or otherwise sealed. Recessed lighting IC-rated as meeting ASTM E 283.Windows and doors=0.30 cfm/sq.ft.Testing or visual inspection required. Fireplaces: gasketed doors&outdoor combustion air. Must complete envelope leakage report or visually verify Table 402.4.2. Thermostat& 403.1 At least one thermostat shall be provided for each separate heating and controls cooling system.Where forced-air furnace is primary system, programmable thermostat is required. Heat pumps with supplemental electric heat must prevent supplemental heat when compressor can meet the load. Ducts 403.2.2 All ducts, air handlers,filter boxes and building cavities which form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section 503.2.7.2 of this code. 403.3.3 Building framing cavities shall not be used as supply ducts. Water heaters 403.4 Heat trap required for vertical pipe risers. Comply with efficiencies in Table 403.4.3.2. Provide switch or clearly marked circuit breaker (electric)or shutoff(gas). Circulating system pipes insulated to=R-2 +accessible manual OFF switch. Mechanical 403.5 Homes designed to operate at positive pressure or with mechanical ventilation ventilation systems shall not exceed the minimum ASHRAE 62 level. No make-up air from attics, crawlspaces, garages or outdoors adjacent to pools or spas. Swimming Pools 403.9 Pool pumps and pool pump motors with a total horsepower(HP)of= 1 &Spas HP shall have the capability of operating at two or more speeds. Spas and heated pools must have vapor-retardant covers or a liquid cover or i / other means proven to reduce heat loss except if 70%of heat from site-recovered energy. Off/timer switch required. Gas heaters minimum thermal efficiency--78% (82%after 4/16/13). Heat pump pool heaters minimum COP=4.0. Cooling/heating 403.6 Sizing calculation performed&attached. Minimum efficiencies per Tables 503.2.3. Equipment efficiency verification required. Special equipment occasion cooling or heating capacity requires separate system or variable capacity system. Electric heat>10kW must be divided into two or more stages. Ceilings/knee walls 405.2.1 R-19 space permitting. t 10/21/2013 7:45 AM EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Page 6 of 6 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 57 The lower the EnergyPerformance Index,the more efficient the home. 1370 NE 103rd ST, Miami Shores, FL, 33138- 1. New construction or existing Existing(Projects 9. Wall Types Insulation Area 2. Single family or multiple family Multi-family a.Concrete Block-Int Insul,Exterior R=4.1 2556.70 ft' b.Concrete Block-Int Insul,Adjacent R=11.0 398.67 ft2 3. Number of units,if multiple family 1 c.N/A R= ft2 d.N/A R= ft' 4. Number of Bedrooms 3 Insulation Area 10.Ceiling Types 5. Is this a worst case? No a.Under Attic(Vented) R=30.0 3958.00 ft2 6. Conditioned floor area(ft2) 3958 b.N/A R= ft2 c.N/A R= ft 7. Windows`* Description Area 11.Ducts R ft2 a. U-Factor: Dbl,U=1.08 575.44 W a.Sup:Main,Ret:Main,AH:Main 6 525 SHGC: SHGC=0.50 b.Sup: Attic,Ret:Attic,AH:Attic 6 200 b. U-Factor: N/A ft' SHGC: 12.Cooling systems kBtu/hr Efficiency c. U-Factor: N/A ft2 a.Central Unit 58.5 SEER:16.00 b.Central Unit 36.0 SEER:16.00 SHGC: d. U-Factor. WA ft2 13.Heating systems kBtu/hr Efficiency SHGC: a.Electric Strip Heat 17.4 COP:1.00 Area Weighted Average Overhang Depth: 2.601 ft. b.Electric Strip Heat 34.1 COP:1.00 Area Weighted Average SHGC: 0.500 8. Floor Types Insulation Area 14.Hot water systems Cap:66 gallons a.Slab-On-Grade Edge Insulation R=0.0 2965.00 ft2 a.Natural Gas EF:0.66 b.Floor Over Other Space R=0.0 993.00 ft2 b. Conservation features c.N/A R= ft2 None 15.Credits Pstat I certify that this home has complied with the Florida Energy Efficiency Code for Building OST SpArF Construction through the above energy saving features which will be installed or exceeded in this home before final inspection. Otherwise,a new EPL Display Card will be completed) based on installed Code compliant features. ` �• ' Date: Builder Signature: Address of New Home: City/FL Zip: _ cOD WE *Note: This is not a Building Energy Rating. If your Index is below 70,your home may qualify for energy efficient mortgage(EEM)incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321) 638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. EnergyGauge®USA-FlaRes2010 Section 405.4.1 Compliant Software Residential System Sizing Calculation Summary 1370 NE 103rd Stree Project Title: 1370 NE 103rd ST CHEE-AWAI Residence Miami Shores, FL 33138- 10/21/2013 Location for weather data: Miami, FL -Defaults: Latitude(25.82) Altitude(7 ft.) Temp Range(L) Humidity data: Interior RH 50% Outdoor wet bulb 78F Humidity difference 58 r. Winter design temperature(MJ8 99%) 50 F Summer design temperature(MJ8 99%) 95 F Winter setpoint 70 F Summer setpoint 75 F Winter temperature difference 20 F Summer temperature difference 20 F Total heatina load calculation 31775 Btuh Total cooling load calculation 84796 Btuh Submitted heating capacity %of calc Btuh Submitted cooling capacity %of calc Btuh Total (Electric Strip Heat) 162.1 51520 Sensible (SHR=0.70) 112.2 66150 Latent 109.8 28350 Total 111.4 94500 WINTER CALCULATIONS Winter Heatin Load for 3958 s ft DuctgM) Load component Load 1 Window total 575 sqft 12430 Btuh Wall total 2360 sqft 3977 Btuh t Door total 20 sqft 240 Btuh Ceiling total 3958 sqft 2521 Btuh Floor total See detail report 6089 Btuh a Infiltration 194 cfm 4260 Btuh Duct loss 2260 Btuh Subtotal 31775 Btuh " Ventilation 0 cfm 0 Btuh '� c�ngste%) TOTAL HEAT LOSS 31775 Btuh WOW SUMMER CALCULATIONS Summer Cooling Load for 3958 sqft) Load component Load Window total 575 sqft 23246 Btuh Wall total 2360 sqft 3977 Btuh Door total 20 sqft 308 Btuh Ceiling total 3958 sqft 4286 Btuh Floor total 0 Btuh hxeac23%) Infiltration 145 cfm 3195 Btuh � `" 9C27%) Internal gain 22110 Btuh Duct gain 1857 Btuh Sens.Ventilation 0 cfm 0 Btuh Blower Load 0 Btuh Total sensible gain 58978 Btuh ceam�acs%� Latent gain(ducts) 590 Btuh o waws%) Latent gain(infiltration) 5727 Btuh ` Int0.(11%) Latent gain(ventilation) 0 Btuh o %) Latent gain(intemal/occupants/other) 19500 Btuh Total latent gain 25817 Btuh TOTAL HEAT GAIN 84796 Btuh EnergyGauge®System g 8th Edition PREPARED BY: DATE: ;„ v EnergyGauge®/USRFZB v3.1 i