EL-15-3087 Inspection Worksheet
Miami Shores Village
10050 N.E.2nd Avenue Miami Shores, FL
Phone: (305)795-2204 Fax: (305)756-8972
Inspection Number: INSP-253470 Permit Number: EL-12-15-3087
Scheduled Inspection Date: February 24,2016 Permit Type: Electrical - Residential
Inspector: Devaney, Michael Inspection Type: Final
Owner: SMITH, PATRICE AND SCOTT Work Classification: Alteration
Job Address:358 NE 101 Street
Miami Shores, FL 33138- Phone Number
Parcel Number 1132060135280
Project: <NONE>
Contractor: LONGMAN ELECTRIC INC Phone: (305)758-1211
Building Department Comments
MOVE FPL ELECTRIC WIRING UNDERGROUND FOR infractio Passed Comments
OUTSIDE POOL INSTALLATION OVERHEAD TO INSPECTOR COMMENTS False
UNDERGROUND CONVERSION OF POWER LINES
Inspector Comments
Passed CREATED AS REINSPECTION FOR INSP-252247.
F .
Failed
Correction ❑
Needed
Re-Inspection ❑
Fee
No Additional Inspections can be scheduled until
re-inspection fee is paid
February 23,2016 For Inspections please call: (305)762-4949 Page 37 of 40
Permit NO. 5-3087
sKO1 S i, Miami Shores Village ■ PeTTiTi!Type"",Et trla d lil#ttlsi8l
t
10050 N.E.2nd Avenue NE
Miami Shores,FL 33138-0000 rm
Phone: (305)795-2204 Pe xitStatus:- ` OV,
�cuRm� Expiration: 06114/20..
Jssue Date: 1 211 71201 5 p� 1
Project Address Parcel Number Applicant
358 NE 101 Street 1132060135280
Miami Shores, FL 33138- Block: Lot: PATRICE AND SCOTT SMITH
Owner Information Address Phone Cell
PATRICE AND SCOTT SMITH 358 101 Street
MIAMI SHORES FL 33138-
358 101 Street
MIAMI SHORES FL 33138-
Contractor(s) Phone Cell Phone $ 3,200.00 •.
LONGMAN ELECTRIC INC (305)758-1211 Valuation:
Total Sq Feet: 00
Type of Work:MOVE FPL ELECTRIC WIRING UNDERGROUN Available Inspections:
Additional Info:
Inspection Type:
Classification:Residential
Review Electrical
Scanning:3
Fees Due Amount Pay Date Pay Type Amt Paid Amt Due
CCF $2.40
DBPR Fee Invoice# EL-12-15-58040
$2.25 12/15/2015 Credit Card $50.00 $119.90
DCA Fee $2.25
Education Surcharge $0.80 12/17/2015 Credit Card $ 119.90 $0.00
Permit Fee-Additions/Alterations $150.00
Scanning Fee $9.00
Technology Fee $3.20
Total: $169.90
In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations.
pertaining thereto and in strict conformity with the plans,drawings,statements or specifications submitted to the proper authorities of Miami Shores Village. In
accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate permits are
required for ELECTRICAL,PLUMBING,MECHANICAL,WINDOWS,DOORS,ROOFING and SWIMMING POOL work.
OWNERS AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating
constructionnnd,,zoning. Futhermoyeluth rize the above-named contractor to do the work stated.
�� QJC_ December 17, 2015
Authorized Signature:Owner / Apgicant / Contractor / Agent Date
Building Department Copy
December 17,2015 1
Miami Shores Village CEIVE �
g DEC 16 2015
Building Department
10050 N.E.2nd Avenue,Miami Shores,Florida 33138
Tel: (305)795.2204 Fax: (305)756.8972
INSPECTION'S PHONE NUMBER:(305)762.4949
FBC 20/ V" "
BUILDING Permit No.,A- -Z
PERMIT APPLICATION master Permit No.
Permit Type: Electrical
JOB ADDRESS: 358 NE 101 st St.
City: Miami Shores County: Miami Dade Zip: 33138
Folio/Parcel#:
Is the Building Historically Designated:Yes NO XXX Flood Zone:
OWNER:Name(Fee Simple Titleholder):Scott F. Smith Phone#:786-385-9426
Address:358 N E 101 st St.
City: Miami Shores State: FL Zip: 33138
Tenant/Lessee Name: Phone#:
Email: sfsmithpatdce@msn.com
CONTRACTOR:Company Name: Longman Electric, Inc. Phone#: 305.758.1211
Address: 95 NE 166th Street
City: Miami State: FL Zip: 33162
Qualifier Name:—ftPhone#: 3 cos -- 7.�5.9® 6W
State Certification or Registration#: E ®O 3-?) 3 Certificate of Competency#:
Contact Phone#: 3&5,23 53 QjJ Email Address:
DESIGNER:Architect/Engineer: Phone#:
Value of Work for this Permit:$ 7 , 9 t!�)OP v Square/Linear Footage of Work:
Type of Work: ❑Address Alteration ONew ORepair/Replace ❑Demolition
Description of Work:
Move FPL electric wiring underground for outside pool installation.
459K-
/ate
Submittal Fee$ L Permit Fee$ CCF$ CO/CC$
Scanning Fee$ Radon Fee$ DBPR$ Bond$
Notary$ Training/Education Fee$ Technology Fee$
Double Fee$ Structural Review$
TOTAL FEE NOW DUE$
Bonding Company's Name(if applicable)
Bonding Company's Address
City State Zip
Mortgage Lender's Name(if applicable) Flagstar Bank
Mortgage Lender's Address 500 Ross Street, Room 154-470
City Pittsburgh State PA Zip 15262
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK,PLUMBING,SIGNS,
WELLS,POOLS,FURNACES,BOILERS,HEATERS,TANKS and AIR CONDITIONERS,ETC.....
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant. As a condition to the issuance of a building permit with an estimated value exceeding$2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not a approved and a re' spection fee will be charged.
n
Signature Le Signature
Owner or Agent Contractor
The foregoing instrument was acknowledged before me this The foregoing instrument was acknowledged before me this
day of &,20&,by S� day of ,20 i�,by AJ;C;h a G I
who is personally known to me or who has produced who i ersonally known o me or who has produced
As identification and who did take an oath. as identification and who did take an oath.
NOTARY PUBLIC: NOTARY PUBLIC:
ANAMARIA VILLEGAS RODRIGUEZ
ISSION#FF019495
Sign: b •. `' Sign: i
Print t of ce.com Print: M :A 1
My Commission Expires: S 1 LO J'10 1-1 My Commissio Notary Public State of Florida
Michelle Perez
o� My Commission FF 000321
opP1� Expires 04/08/2017
aRakakakakakakakaBakakakakckakakakakakakakakaeaS.ak�aStakakakakakakakakakakakakakakakakakakakakakakakekakakakakakakakakakakakakakakagakakekakakakakak ak
APPROVED BY �� ��s�Plans Examiner Zoning
Structural Review Clerk
(Revised 3/12/2012)(Revised 07/10/07)(Revised 06/10/2009)(Revised 3/15/09)
r
358 NE 101 Street
Miami Shores, FL 15 201
Longman Electric
EC13003713 . •
200 AMP
Nema 3R
PANEL
METER
1 Phase
200 AMP 22KAIC
120/240
3#2/0 THHN
22 KAIC 2" PVC
GRN Bridge
F— #4 Ground
FPL ROD 10'X5/8 ROD 10'X5/8 Cold Water
00
.. ... .. . . . ..
ELECTRICAL REVIEW
• ... . .;• 0; .:.
APPR®VE DATE
000 0
...
. ;•; • •
4
358 NE 101 Street
Miami Shores
LOAD CALCULATION
2500 sqft x 3VA= 7500
Small Appliance 3000
Laundry 1500
Dishwasher 1200
Microwave 1200
Pool Pump 2000
Pool Light 500
Dryer 5000
Pool Heater 8000
Refrig 1000
Stove 10000
Water Heater 4500
45400
-10000
35400 10000
x 40% 14160.00
14160.00 24160
10000 air conditioning
34160 full VA
34160 / 240 = 142.3333 amperage
Longman Electric
EC 13003713
844 NE 98 Street. ,•
Miprnt"FI1•43.15$ : :•
•••