PL-14-401 Inspection Worksheet
Miami Shores Village
10050 N.E.2nd Avenue Miami Shores, FL
Phone: (305)795-2204 Fax: (305)756-8972
Inspection Number: INSP-231582 Permit Number: PL-3-14-401
Scheduled Inspection Date: April 09 2015
P p Permit Type: Plumbing - Residential
Inspector: Diaz, Osvaldo
Inspection Type: Final
Owner: MATEO, RAYMOND AND DAMARIS Work Classification: Gas
Job Address:900 NE 100 Street
Miami Shores, FL 33138-
Phone Number
Parcel Number 1132060340220
Project: <NONE>
Contractor: J &J DAVIS PLUMBING SERVICE INC Phone: (954)680-6543
Building Department Comments
GAS Infractio Passed Comments
INSPECTOR COMMENTS False
Inspector Comments
Passed CREATED AS REINSPECTION FOR INSP-208246. GAS SHUT OF FOR
SHALL BE ACCESSIBLE
Failed
Correction ❑
Needed
Re-Inspection ❑
Fee
No Additional Inspections can be scheduled until
re-inspection fee is paid.
April 08,2015 For Inspections please call: (305)762-4949 Page 19 of 33
I
e ►
Miami .ores Village
Building Department MAR ®4 2014
10050 N.E.2nd Avenue,Miami Shores,Florida 33138 BY-
Tel:(305)795.2204 Fax:(305)756.8972
INSPECTION'S PHONE.NUMBER:(305)762.4949
f ry 9.' C 0
BUILDING Fermat Nw. �/ D
PERMIT APPLICATION Master PenWt No. � u �
PenWt Type: PLUMBING L57
JOB ADDRESS: qb I v
City: Miami Shores County: Miami bade
Folio/Parcel#: 113aQ G 03 H 0
Is the Building Historically Designated:Yes NO Flood Zone:
'IDOWNER:Name(Fee Simple Titleholder): rt6YlC 3 � __ ! Ph ne#: �l�{"W�-S -1C)
Address: Ct 00 "s o
City: Cn 't a 1 ,Lcln1�� State: dip: 3
Ten=t/Ussee Name: Phone#:
Email:
CONTRACTOR:Company Name: T l Phoc►e#: __
Address: O
City: ck - e, 1 State: R� Zig.
Qualifier Name: �� W d.�y 5 Phoned#: d 3
State Certification or Registration#: �'52 Certificate of Competency#:
�
Contact Phone#: Email Address:
DESIGNER:Architect/Engineer: Phone#:
Value of Work for this Permit:$ �Vl'S60-o )
[o) 3quarelLinear Footage of Work:
Type of Work: C]Address OAlteration car4ew ORepair/Replace ODemolition
Description of work: (\
Submittal.Fee$ Permit Fee$ CCF$ CO/CC$
Scanning]Fee$ Radon Fee$ DBPR$ Bond$
Notary$ Training/Education Fee$ Technology Fee$
Double Fee$ Structural Review$ _
TOTAL FLEE NOW DUE$ a
, Y
Bonding Company's Name(if applicable) _
Bonding Company's Address _
City State _ Zip
Mortgage Lender's Name(if applicable)
Mortgage Lender's Address
City Stag zip
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all la.ws. *guladng
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK,PLUMBP'•!.
WELLS,POOLS,FURNACES,BOILERS,HEATERS,TANKS and AIR CONDITIONERS,ETC.....
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in comp.; ;c6 Witli all
applicab;;,laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING CE' FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTENT) TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."'
Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding$2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certi,f ted copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved and a reinspection fee will be charged.
Signature Signature t
Owner or Agent ontractor
ging instrument was ac wledged before rate this The foregoing instrument wlen4wlodged before
10 w �s
s$ '20-ft by day of '' 20 f ,by
rsonally known to me or who has produced who i ersonallyknown o etre or who has produced—
As
roducedAs identification and who did take an oath. as identification and who did take n
o O
" Y PUBLIC: NOTARY PUBLIC:
ww c
cocoz U z �
S Z Sign: '� :_ m
. P1 trL7 Yl7 1 Print: , 4 i <
o „ m
3A + a S& Expire Expires: My Cotttnil�sion Es•
xpi
w
APPROVED BY 2-`,{r'`!` Plans Examiner Zoning
Structural Review Clark
(Revi=W12/2012XR@vised 09/10/070iMsed 06/10/2 9)(Ravieed 3/15/00)
i
M it:10 RL519VEOCE J{J�RdtS PLvM�tN�
�t �O0 Nt I oo 57
MAR 4 2014
KAWkE
-oil� ` k��ro� ,ca�`r �;r�Ql4 CC o
:04� � towe 07-e L)0 K 94-1
�p �10 tota,L K Cid,,; �,-R•
ekooK 94o.
Y
I /3 DSR (oS(C Btu•
�O 6'to ®bSK`fitJ' �i 31-10 D,E
D4'IDK-
l{w1� t9 1S2K.
d
v 11
F ,. cdQQ 3 Q�QG Tofati 3 DH (4.
p'tt an5ey fi&&#A (ot=3/q" e.
•2 0�+k i 1;`alt r �t7Q
��
Ia77.1 .
,
ti
GAS Qpr+I1sE ��Zo9 t'trN �'J '!gk-t F.
�IRtr�LPt:� 3ta� t'@P i 1Z A v , - D
'
$approved
r;
;; t'k44 py
• fits Ga4. - \
U•P.
' GAS PIPING INSTALLATIONS
Gas Undiluted Propane
TABLE 402.4(28) Inlet Pressure 11.0 in.w.c.
�- SEMIRIGID COPPER TUBING Pressure Drop 0.5 in.w.c.
Specific Gravity 1.50
INTENDED USE Sizing between single or second sta a(low-pressure regulator)and appliance.
TUBE SIZE Inch)
3/ 1/ 5/ 3
K&L 1/ / 2
Nominal
ACR
7/, 1/a13/,, -
Outside 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Le (ft) Capacity in Thousands of Btu per Hour
10 45 93 188 329 467 997 1,800 2,830 5,890
20 31 64 129 226 321 685 1,230 1,950 4,050
30 25 51 104 182 258 550 991 1,560 3,250
40 21 44 89 155 220 471 848 1,340 2,780
50 19 39 79 138 195 417 752 1,180 2,470
60 17 35 71 125 177 378 681 1,070 2,240
70 16 32 66 115 163 348 626 988 2,060
80 15 30 61 107 152 324 583 919 11910
90 14 28 57 100 142 304 547 862 1,800
100 13 27 54 95 134 287 517 814 1,700
125 11 24 48 84 119 254 458 722 1,500
150 10 21 44 76 108 230 415 654 1,360
175 NA 20 40 70 99 212 382 602 1,250
200 NA 18 37 65 92 197 355 560 1,170
250 NA 16 33 58 82 175 315 496 1,030
j 300 NA 15 30 52 74 158 285 449 936
350 NA 14 28 48 68 146 262 414 861
400 NA 13 26 45 63 136 244 385 801
450 NA 12 24 42 60 127 229 361 752
500 NA 11 23 40 56 120 216 341 710
550 NA 11 22 38 53 114 205 324 674
600 NA 10 21 36 51 109 196 309 643
650 NA NA 20 34 49 104 188 296 616
700 NA NA 19 33 47 100 180 284 592
750 NA NA 18 32 45 96 174 274 570
800 NA NA 18 31 44 93 168 264 551
850 NA NA 17 30 42 90 162 256 533
900 NA NA 17 29 41 87 157 248 517
950 NA NA 16 28 40 85 153 241 502
11000 NA NA 16 27 39 83 149 234 488
1,100 NA NA 15 26 37 78 141 223 464
1,200 NA NA 14 25 35 75 135 212 442
1,300 NA NA 14 24 34 72 129 203 423
1,400 NA NA 13 23 32 69 124 195 407
11500 NA NA 13 22 31 66 119 188 392
1,600 NA NA 12 21 30 64 115 182 378
1,700 NA NA 12 20 29 62 112 176 366
1,800 NA NA 11 20 28 60108 170 355
1,900 NA NA 11 19 27 58 105 166 345
2,000 NA NA i l 19 27 57 102 161 335
For SI: 1 inch=25.4 mm,1 foot=304.8 mm,1 pound per square inch=6.895kPa,1-inch water column=0.2488 kPa,
k 1 British thermal unit per hour=0.2931 W,1 cubic foot per hour=0.0283 m3/h,1 dune=0.01745 rad.
i.• Notes:
1.Table capacities are based on Type K copper tubing inside diameter(shown),which has the smallest inside diameter of the copper tubing products.
2.NA means a flow of less than 10,000 Btu/lin
3.All table entries have been rounded to three significant digits.
2009 INTERNATIONAL FUEL GAS CODE® 57
� N�ot"o RVc.,I✓€t4C€
' 1 �D . �00 K [DO VT a5�1-�l�
-- `�• �ZR1
MAR 0 4 1014
BY:
coil
�,,�.c• KAWkE 0 ISK. 54,j.
eVt,q
qOIL
: ttfkte .07-0 N0 K Q�t-1.
,
�0of� L (� 155 K %i�. �1-R
r d yea ooK �.a eu ,f (Zt1A® l y t'
BBQ O &0 k. B+V• _.
1� /3, R (v�K B•t�►
HREPIAIC cwt!iq Is2 K.
® qVK R 3\ AWROd
�F ,• L t°�Q �- Q; ' a7 rofaLp 3 D j K
p 0I4
�� dZ• ..e�rA on�eg f d/1 S 1�=31q
i of �� ,call
L
Approved
Disappro� v? �' l ``
8� - 7:
,61I
9 I5 K.m.FIIZEVLACE
FIEmLD
.
: r �
500 AciL, �ti
GAS PIPING INSTALLATIONS
Gas Undiluted Propane
TABLE 402.4(28) Inlet Pressure 11.0 in.w.c.
SEMIRIGID COPPER TUBING Pressure Drop 0.5 in.w.c. .
Specific Gravity 1.50
INTENDED USE Sizing between single or second stage(low-pressure regulator)and ap llence.
TUBE SIZE nch)
K&L 1/ 3/ 1/ 5/ 3/ 1 11/ 1 1/ 2
Nominal
ACR 3/ 1/' /R3/ 3/ 7/ 1 I13/
Outside 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Le (ft) Capacity In Thousands at Btu per Hour
10 45 93 188 329 467 997 1,800 2,830 5,890
20 31 64 129 226 321 685 1,230 1,950 4,050
30 25 51 104 182 258 550 991 1,560 3,250
40 21 44 89 155 220 471 848 1,340 2,780
50 19 39 79 138 195 417 752 1,180 2,470
60 17 35 71 125 177 378 681 1,070 2,240
70 16 32 66 115 163 348 626 988 2,060
80 15 30 61 107 152 324 583 919 11910
90 14 28 57 100 142 304 547 862 11800
100 13 27 54 95 134 287 517 814 1,700
125 11 24 48 84 119 254 458 722 1,500
150 10 21 44 76 108 230 415 654 1,360
175 NA 20 40 70 99 212 382 602 1,250
200 NA 18 37 65 92 197 355 560 1,170
250 NA 16 33 58 82 175 315 496 1,030
i 300 NA 15 30 52 74 158 285 449 936
350 NA 14 28 48 68 146 262 414 861
400 NA 13 26 45 63 136 244 385 801
450 NA 12 24 42 60 127 229 361 752
500 NA 11 23 40 56 120 216 341 710
550 NA 11 22 38 53 114 205 324 674
600 NA 10 21 36 51 109 196 309 643
650 NA NA 20 34 49 104 188 296 616
700 NA NA 19 33 47 100 180 284 592
750 NA NA 18 32 45 96 174 274 570
800 NA NA 18 31 44 93 168 264 551
850 NA NA 17 30 42 90 162 256 533
900 NA NA 17 29 41 87 157 248 517
950 NA NA 16 28 40 85 153 241 502
1,000 NA NA 16 27 39 83 149 234 488
11100 NA NA 15 26 37 78 141 223 464
1,200 NA NA 14 25 35 75 135 212 442
1,300 NA NA 14 24 34 72 129 203 423
1,400 NA NA 13 23 32 69 124 195 407
1,500 NA NA 13 22 31 66 119 188 392
1,600 NA NA 12 21 30 64 115 182 378
1,700 NA NA 12 20 29 62 112 176 366
11800 NA NA 11 20 28 60 108 170 355
1,900 NA NA 11 19 27 58 105 166 345
2,000 NA NA 11 19 27 57 102 161 335
For SI: 1 inch=25.4 mm,1 foot=304.8 mm,1 pound per square inch=6.895kPa,1-inch water column=0.2488 kPa,
1 British thermal unit per hour=0.2931 W,I cubic foot per hour=0.0283 m3/h,1 degree=0.01745 rad
Notes:
1.Table capacities are based on Type K copper tubing inside diameter(shown),which has the smallest inside diameter of the copper tubing products.
2.NA means a flow of less than 10,000 Btu/hr.
3.All table entries have been rounded to three significant digits.
2009 INTERNATIONAL FUEL GAS CODE® 67