Florida Energy Efficiency Code For Building Construction
'r
EnergyGauge Summit® Fla/Com-2010, Effective Date: March 15, 2012 -- Form 506-2010
Total Building Performance Method for Commercial Buildings
PROJECT SUMMARY
Short Desc: Gym Description: Primal Fit Miami
Owner:
Addressl: 9537 NE 2nd Ave City: Miami Shores
Address2: State: FL
Zip: 33138
Type: Gymnasium Class: Renovation to existing buildi
Jurisdiction: MIAMI SHORES VILLAGE,MIAMI-DADE COUNTY,FL(232600)
Conditioned Area: 5449 SF Conditioned& UnConditioned Area: 5449 SF
No of Stories: 1 Area entered from Plans 5454 SF
Permit No: 0 Max Tonnage 5
If different,write in:
EnergyGauge Summit@ Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
1/21/2014 Paget of 7 I
i
Compliance Summary
Component Design Criteria Result
Gross Energy Cost (in $) 2,957.0 4,244.0 PASSED
LIGHTING CONTROLS PASSES
EXTERNAL LIGHTING None Entered
HVAC SYSTEM PASSES
PLANT None Entered
WATER HEATING SYSTEMS PASSES
PIPING SYSTEMS None Entered
Met all required compliance from Check List? Yes/No/NA
IMPORTANT MESSAGE
Info 5009 -- -- -- An input report of this design building must be submitted along with this
Compliance Report
�I
EnergyGauge Summit®Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
1/21/2014 Page 2 of 7
CERTIFICATIONS
I hereby certify that the pl ns and specificati s covered by this calculation are in compliance with the
Florida Energy Code
Prepar By: ARPE Enginee ing Building Official:
ate: l' �� Date:
I certify that this building is in compliance with the FLorida Energy Efficiency Code
Owner Agent: Date:
If Required by Florida law, I hereby certify(")that the system design is in compliance with the Florida
Energy Efficiency Code
Architect: Victor Bruce Reg No: AR-0017103
Electrical Designer: ARPE Engineering Reg No: 60236
Lighting Designer: ARPE Engineering Reg No: 60236
Mechanical Designer: ARPE Engineering Reg No: 60236
Plumbing Designer: ARPE Engineering Reg No: 60236
(") Signature is required where Florida Law requires design to be performed by registered design
professionals.
EnergyGauge Summit®Fla/Com-2010. Section 506.4 Compliant Software. Effective Date: March 15, 2012
1/21/2014 Page 3 of 7
1 /
Project:Gym
Title: Primal Fit Miami
_ Type: Gymnasium
(WEA File: FL MIAMI OPA_LOCKA.tm3)
Building End Uses
1) Proposed 2) Baseline
Total 187.40 335.90
$2,957 $5,305
ELECTRICITY(MBtulkWhl$) 187.40 335.90
54955 98431
$2,957 $5,305
AREA LIGHTS 14.60 51.30
: 4287 15019
$231 $810
MISC EQUIPMT 27.20 27.20
7984 7984
$430 $430
PUMPS& MISC 0.00 0.00
1 2
$0 $0
SPACE COOL 118.30 148.00
34676 43364
$1,866 $2,337
SPACE HEAT 1.00 1.50
294 437
$16 $24
VENT FANS 26.30 107.90
7713 31625
$415 $1,705
Credits Applied: None PASSES
Passing Criteria=4244
Design (including any credits)=2957
Passing requires Proposed Building cost to be at most 80% of
Baseline cost. This Proposed Building is at 55.7%
EnergyGauge Summit®Fla/Com-2010.Section 506.4 Compliant Software. Effective Date: March 15, 2012
1/21/2014 Page 4 of 7
External Lighting Compliance
Description Category Tradable? Allowance Area or Length ELPA CLP
(W/Unit) or No.of Units (W) (W)
(Sgft or ft)
None
Project: Gym
Title: Primal Fit Miami
Type: Gymnasium
(WEA File:FL MIAMI OPA LOCKA.tm3)
Lighting Controls Compliance
Acronym Ashrae Description Area Design Min Compli-
ID (sq.ft) CP CP ance
PrOZo1Spl 9,003 Exercise Area(Gym) 5,449 3 3 PASSES
PASSES
Project: Gym
Title: Primal Fit Miami
Type:Gymnasium
(WEA File: FL_MIAMI_OPA_LOCKA.tm3)
System Report Compliance
PrOSyl From AC#1 to AC#5 Constant Volume Air Cooled No. of Units
Split System<65000 Btu/hr 5
Component Category Capacity Design Eff Design IPLV Comp-
Eff Criteria IPLV Criteria liance
Cooling System Air Conditioners Air Cooled 13.50 12.23 0.10 PASSES
Split System<65000 Btu/h
Cooling Capacity
Heating System Electric Furnace 1.00 1.00 PASSES
Air Handling Air Handler(Supply)- 0.10 0.82 PASSES
System-Supply Constant Volume
Air Handling Air Handler(Return)- 0.10 0.82 PASSES
System-Return Constant Volume
Air Distribution ADS System(Sup) 6.00 PASSES
System(Sup)
Air Distribution ADS System(Ret) 6.00 PASSES
System(Ret)
PASSES
EnergyGauge Summit®Fla/Com-2010.Section 506.4 Compliant Software, Effective Date: March 15, 2012
1/21/2014 Page 5 of 7
Plant Compliance
Description Installed Size Design Min Design Min Category Comp
No Eff Eff IPLV IPLV liance
None
Project: Gym
Title: Primal Fit Miami
Type: Gymnasium
(WEA File: FL MIAMI_OPA_LOCKA.tm3)
Water Heater Compliance
Design Min Design Max Comp
Description Type Category Eff Eff Loss Loss liance
Water Heater 1 Electric water heater <= 12 [kW] 0.92 0.92 PASSES
PASSES
Piping System Compliance
Category Pipe Dia Is Operating Ins Cond Ins Req Ins Compliance
[inches] Runout? Temp [Btu-in/hr Thick [in] Thick [in]
[F] SF.F]
None
EnergyGauge Summit®Fla/Com-2010.Section 506.4 Compliant Software. Effective Date: March 15,2012
1/21/2014 Page 6 of 7
Project: Gym
Title: Primal Fit Miami
Type: Gymnasium
- (WEA File: FL_MIAMI_0PA_L0CKA.tm3)
Other Required Compliance
Category Section Requirement(write N/A in box if not applicable) Check
Report 506.4.2 Input Report Print-Out from EnergyGauge F1aCom attached
Operations Manual 303.3.1, Operations manual provided to owner
503.2.9.3,
505.7.4.2
Windows&Doors 502.3.2 Glazed swinging entrance&revolving doors: max. 1.0 cfin/ft2; all
other products:0.3 cfin/ft2
Joints/Cracks 502.3.3 To be caulked,gasketed,weather-stripped or otherwise sealed
Dropped Ceiling 502.3 Vented: seal&insulated ceiling. Unvented seal&insulate roof&
Cavity side walls
HVAC Efficiency 503.2.3 Minimum efficiencies:Tables 503.2.3(1)-(8)
HVAC Controls 503.2.4 Zone controls prevent reheat(exceptions);separate thermostatic
control per zone;
Ventilation 503.2.5 Outdoor air supply&exhaust ducts shall have dampers that
automatically shut when systems or spaces served are not in use.
Exhaust air energy recovery required for cooling systems
(Exceptions).
ADS 503.2.7.5 Duct sizing and Design have been performed
HVAC Ducts 503.2.7 Air ducts, fittings,mechanical equipment&plenum chambers
shall be mechanically attached,sealed, insulated&installed per
Table 503.2.7.2. Fan power limitations.
Balancing 503.2.9.1 HVAC distribution system(s)tested&balanced.Report in
construction documents.
Piping Insulation 503.2.8 HAC and service hot water. In accordance with Table 503.2.8.
Water Heaters 504 Performance requirements in accordance with Table 504.2.Heat
trap required.
Swimming Pools 504.7 Vapor-retardant or liquid cover or other means proven to reduce
heat loss on heated pools;Time switch(exceptions);readily
accessible on/off switch.
Motors 505.7.5 Motor efficiency criteria have been met
Lighting Controls 505.2,502.3 Automatic control required for interior lighting in buildings
>5,000 s.f.; Space control;Exterior photo sensor;Tandom wiring
with 1 or 3 linear fluorescent lamps>30W
EnergyGauge Summit@ Fla/Com-2010.Section 506.4 Compliant Software. Effective Date: March 15,2012
1/21/2014 Page 7 of 7
EnergyGauge Summit® v4.10
INPUT DATA REPORT
Project Information
Project Name: Gym Orientation: West
Project Title: Primal Fit Miami Building Type: Gymnasium
Address: 9537 NE 2nd Ave Building Classification: Renovation to existing building
State: FL No.of Stories: 1
Zip: 33138 GrossArea: 5449 SF
Owner:
Zones
No Acronym Description Type Area Multiplier Total Area
Istl Isq
1 PrOZol Zone 1 CONDITIONED 5449.4 1 5449.4 ❑
Spaces
�
No Acronym Description Type Depth Width Height Multi Total Area Total Volume
IN Ift] Iftj plier IsfJ Icq
1/21/2014 EnergyGauge Summit®v4.10 1
In Zone: PrOZol
1 PrOZo1Spl Zo0Sp1 Exercise Area(Gym) 98.90 55.10 12.00 1 5449.4 65392.7
Lighting
No Type Category No. of Watts per Power Control Type No.of
Luminaires Luminaire lW] Ctrl pts
In Zone: PrOZol
In Space: PrOZoISp1
I Compact Fluorescent General Lighting 40 35 1400 Manual On/Off 3 ❑
Walls
No Description Type Width H(Effec) Multi Area DirectionConductance Heat Dens. R-Value
[ftl lftl plier lst] [Btu/hr.sf. F] Capacity [lb/cf] [h.sf.F/Btu]
[Btu/sf.Fl
In Zone: PrOZol
1 PrOZo1Wal 8"CMU/3/4"ISO 55.10 13.00 2 716.3 West 0.2642 9.696 62.72 3.8 ❑
BT WN24"oc/5/8
Gyp
2 PrOZol Wal 8"CMU/3/4"ISO 98.90 13.00 1 1285.7 North 0.2642 9.696 62.72 3.8 ❑
BT WN24"oc/5/8
Gyp
Windows
No Description Type Shaded U SHGC Vis.Tra W H (Effec) Multi Total Area
[Btu/hr sf F] 1111 [111 plier Isf]
In Zone: PrOZol
In Wall: Pr0Zo1Wa1
1 PrOZo1Wa1Wil User Defined No 0.9000 0.68 0.66 4.00 10.00 5 200.0 ❑
1 PrOZo]Wa5Wil User Defined No 0.9000 0.68 0.66 4.00 10.00 5 200.0
1/21/2014 EnergyGauge Summit®v4.10 2
Doors
No Description Type Shaded? Width H(Effec) Multi Area Cond. Dens. Heat Cap. R-Value
IN Ift] plier [sfJ IBtu/hr. sf. F1 jlb/cfl [Btu/sf. Fj (h.sf.F/Btu]
In Zone: PrOZol
In Wall: PrOZo1Wal
1 PrOZolWalDrl Aluminum door, No 3.00 10.00 1 30.0 0.1919 43.67 0.53 5.21 ❑
1.25 in.
polystyrene
In Wall: PrOZo1Wa1
1 PCOZolWa5Drl Aluminum door, No 3.00 10.00 2 30.0 0.1919 43.67 0.53 5.21 ❑
1.25 in.
polystyrene
Roofs
No Description Type Width H(Effec) Multi Area Tilt Cond. Heat Cap Dens. R-Value
[ft] [ftl plier [sf] [deg] [Btu/hr. SE F1 [Btu/sf. F] [Ib/cf] [h.sf.F/Btul
In Zone: PrOZol
1 PrOZo1Rfl Mtl Bldg Roof/R-19 55.10 98.90 1 5449.4 0.00 0.0492 1.34 9.49 20.3 ❑
Batt
Skylights
No Description Type U SHGC Vis.Trans W H (Effec) Multiplier Area Total Area
[Btu/hr sf F1 (ft] Ift] [St] [Sq
In Zone:
In Roof:
1/21/2014 EnergyGauge Summit®v4.10 3
,
1 .
Floors
No Description Type Width H (Effec) Multi Area Cond. Heat Cap. Dens. R-Value
IN [ftl plier [sfl [Btu/hr.sC F[ [Btu/sf. FJ [lb/cfl [h.sf.F/Btul
In Zone: PrOZol
1 Pr0Zo1Fll Concrete floor, 55.10 98.90 1 5449.4 0.5987 9.33 140.00 1.67 ❑
carpet and rubber
pad
Systems
PrOSyl From AC#1 to AC#5 Constant Volume Air Cooled Split No. Of Units 5
System<65000 Btu/hr
Component Category Capacity Efficiency IPLV
1 Cooling System 60000.00 13.50 0.10 ❑
2 Heating System 17000.00 1.00 ❑
3 Air Handling System -Supply 1800.00 0.10 ❑
4 Air Handling System-Return 1800.00 0.10 ❑
5 Air Distribution System(Sup) 6.00 ❑
6 Air Distribution System(Ret) 6.00 ❑
Plant
Equipment Category Size 1nst.No Eff. IPLV
LI
Water Heaters
W-Heater Description Capacit3Cap.Unit I/P Rt. Efficiency Loss
1 Electric water heater 40 [Gal] 5 [kW] 0.9200 [Ef] [Btu/h] ❑
1/21/2014 EnergyGauge Summit®v4.10 4
1 1 .
Ext-Lighting
Description Category No.of Watts per Area/Len/No.of units Control Type Wattage
Luminaires Luminaire [AM/No] [W]
El
Piping
No Type Operating Insulation Nomonal pipe Insulation Is Runout?
Temperature Conductivity Diameter Thickness
[F] [ Btu-in/h.sf.F] [in] [in]
El
Fenestration Used
Name Glass Type No. of Glass SHGC VLT
Panes Conductance
[Btu/h.sf.F]
ASHULDb1CIrM User Defined 2 0.9000 0.6800 0.6600 ❑
ti-Oth frm
Materials Used
Mat No Acronym Description Only R-Value RValue Thickness Conductivity Density SpecificHea
Used (h.sf.F/Btu] IN ]Btu/h.ft.F] [Ib/cf] t
264 at o 0.0002 0.0050 26.0000 480.00 0.1000 Li
214 Mat1214 POLYSTYRENE,EXP., No 5.2100 0.1042 0.0200 1.80 0.2900 ❑
1-1/41N,
187 Mat1187 GYP OR PLAS No 0.4533 0.0417 0.0920 50.00 0.2000 ❑
BOARD,1/2IN
1/21/2014 EnergyGauge Summit®v4.10 5
151 Matll51 CONC HW,DRD, 140LB, No 0.4403 0.3333 0.7570 140.00 0.2000 ❑
4IN
178 Matl 178 CARPET W/RUBBER PAD Yes 1.2300 ❑
105 Matl105 CONC BLK HW, BIN, No 1.1002 0.6667 0.6060 69.00 0.2000 ❑
HOLLOW
269 Mat1269 .75" ISO BTWN24" oc No 2.2321 0.0625 0.0280 4.19 0.3000 ❑
23 Mat123 6 in. Insulation No 20.0000 0.5000 0.0250 5.70 0.2000 ❑
94 Mat194 BUILT-UP ROOFING,3/81N No 0.3366 0.0313 0.0930 70.00 0.3500 ❑
Constructs Used
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sLF] [Btu/sf.F] (Ib/cf] [h.sLF/Btu]
1002 Aluminum door, 1.25 in.polystyrene No No 0.19 0.53 43.67 5.2 ❑
Layer Material Material Thickness Framing
No. IN Factor
1 264 ALUMINUM, 1/16 IN 0.0050 0.000 ❑
2 214 POLYSTYRENE,EXP., 1-1/4IN, 0.1042 0.000 ❑
3 264 ALUMINUM, 1/161N 0.0050 0.000 ❑
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sLF] [Btu/sf.F] [Ib/cf) [h.sf.F/Btu]
1004 Concrete floor,carpet and rubber pad No No 0.60 9.33 140.00 1.7 ❑
Layer Material Material Thickness Framing
No. IN Factor
1 151 CONC HW,DRD, 140LB,41N 0.3333 0.000 ❑
2 178 CARPET W/RUBBER PAD 0.000 ❑
1/21/2014 EnergyGauge Summit®v4.10 6
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct [Btu/h.sf.Fl 1Btu/sf.F1 lib/cfl lb.sf.F/Btul
1014 8"CMU/3/4"ISO BTWN24"oc/5/8 Gyp No No 0.26 9.70 62.72 3.8 ❑
Layer Material Material Thickness Framing
No. IN Factor
1 105 CONC BLK HW, BIN,HOLLOW 0.6667 0.000 ❑
2 269 .75" ISO BTWN24" oc 0.0625 0.000 ❑
3 187 GYP OR PLAS BOARD,1/21N 0.0417 0.000 ❑
No Name Simple Massless Conductance Heat Capacity Density RValue
Construct Construct 1Btu/h.sf.Fl 1Btu/sf.F1 llb/cfl 1h.sf.F/Btul
1047 Mtl Bldg Roof/R-19 Batt No No 0.05 1.34 9.49 20.3 ❑
Layer Material Material Thickness Framing
No. IN Factor
1 94 BUILT-UP ROOFING,3/81N 0.0313 0.000 El
2 23 6 in. Insulation 0.5000 0.000 ❑
1/21/2014 EnergyGauge Summit®v4.10 7
Air System Sizing Summary for AC#1
Project Name: 13-1206 Primal Fit Miami 01/14/2014
Prepared by:ARPE Engineering, Inc. 11:50AM
Air System Information
Air System Name:----- _... .. .................. -------_.AC#1 Number of zones:--...-- .................
•Air System Type:.......................................Single Zone CAV Floor Area:.----------------- ----- 1840.0 sqft
Location: Miami Shores,Florida
Sizing Calculation Information
Calculation Months:.. Jan to Dec Calculation method:______Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load:..... .............. ............ -.... .... ..............8.0 Tons Load occurs at:... - - -- .._..Jul 1600
Total coil load:....------ ... - - -- - - _95.6 MBH OA DB/WB:- _ -- __--------------- -- .... -92.0/78.4 F
Sensible coil load:....... .................... ............................65.4 MBH Entering DB/WB:..------ ... ..... ....--...................78.9/66.4 F
Coil airflow:......._............................................ .................2496 CFM Leaving DB/WB:__. --- - -------------------------.......54.6/53.5 F
Sensible heat ratio:_._...--------------............-----..._......_....0.684 Coil ADP:......................................--------.................................51.9 F
Area per unit load:.....-_._................................................... 30.9 sgft/Ton Bypass Factor:-.._._.___-............................_....................0.100
Load per unit area:...............................__............._.............52.0 BTU/(hr-sgft) Resulting RH:--------------- ..................................................... 9 %
Design supply temp-------------------------__.---._...........---------.55.0 F
Central Heating Coil Sizing Data
Max coil load:.-.-- ------- -- - -... ....... - -53.1 MBH Load occurs at:............ ............ ......._........... ..-Des Htg
Coil airflow: .............-------------___....................................2496 CFM Ent DB/Lvg DB:-----------.................-.......................... 6.4/78.7 F
Load per unit area:_----._.-....------------...............................18.0 BTU/(hr-sgft)
Supply Fan Sizing Data
Actual max airflow:......................................._._----------------- 496 CFM Fan motor BHP:----- ------_ - ------------------------------ ------.0.44 BHP
• Standard airflow:-- - - - ................................. 2496 CFM Fan motor kW: .................. ..............-------------------------------0.33 kW
Actual max airflow per unit area:.....................................1.36 CFM/sqft Fan static:-__._----._-.--__.-_____._______-._.--------------------- .60 in wg
Outdoor Ventilation Air Data
Design airflow:....................................................................... CFM Airflow per person:.-----_...........................-.......-._ .-----..34.38 CFM/person
Airflow per unit floor area:.-._...----____-.-------_-------..-...._0.30 CFM/sqft
Space Sizing Data
Space Name Maximum Design Time of Peak Maximum Space Space
Cooling Airflow Load Heating Floor CFM/sgft
Sensible CFM Load MBH Area
MBH sqft
Zone 1 53.9 24961 Jun 1600 18.8 1840.0 1.36
Block Load 4.15 Page 1 of 1
System Input Data
Project Name: 13-1206 Primal Fit Miami 01/20/2014
Prepared by:ARPE Engineering, Inc. 03:07PM
General Details:
Air System Name: ...........................................AC#1
.Air System Type:.._------------- ---Single Zone CAV
Number of zones:_................_._._...- ---------..-................._.1
System Startup: 6
Duration of Operation: -----------_...._..24
Central Cooling Coil Data:
Used?:..... -... ................... ................-----------YES
Supply Air Temperature: __55.0 F
Coil Bypass Factor:.__._.._........................ ..............0.100
Central Heating Coil Data:
Used?: -- _ .-___ ........................................................YES
Supply Temperature: ---------- _--------...110.0 F
Supply Fan Data:
Configuration:. ...........Draw-thru
Fan Performance:............_........_----.....--..._........._.__---.--0.60 in wg
Ceiling Return Air Plenum Data:
Return Air Via:.......... ------ Ducted Return
Zones Included:
Zone Names
Zone 1
Thermostats Data:
Cooling T-stat:Occ: ...................................................75.0 F
Cooling T-stat:Unocc:----- 85.0 F
Heating T-stat:Occ:................ 70.0 F
Heating T-stat: Unocc:-.......................................................60.0 F
Safety Factors:
Cooling Sensible Safety Factor:........................_._.___------..0 %
Cooling Latent Safety Factor: _..............0 %
Heating Safety Factor:................_..................._......................0 %
Block Load 4.15 Page 1 of 1
Air System Sizing Summary for AC#2
Project Name: 13-1206 Primal Fit Miami 01/14/2014
Prepared by:ARPE Engineering, Inc. 11:48AM
Air System Information
Air System Name: ......................__. ..... . AC#2 Number of zones:...................... ..... .. -.... ........ _......1
Air System Type:. -.------- ---.---------.....Single Zone CAV Floor Area:. ......._..-------................._..................--1820.0 sqft
Location:_.........................................Miami Shores,Florida
Sizing Calculation Information
Calculation Months:...... ....................................Jan to Dec Calculation method: Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load:.................._ _.. __ _ .----... __.8.3 Tons Load occurs at:...........................- ------- __--Jul 1500
Total coil load:................... 99.4 MBH OA DB/WB: ..._.._...._................................... --92.3178.5 F
Sensible coil load:_ -_- -- ------.......................................69.7 MBH Entering DB/WB:........... ----.................78.7/66.2 F
Coil airflow:.................. 2737 CFM Leaving DB/WB:-- ....................................-..---.__55.1/54.0 F
Sensible heat ratio:............ 0.701 Coil ADP:---.---- .--.---.-............._._......................_-_._.._.._52.5 F
Area per unit load:..-----....................................................219.7 sgft/Ton Bypass Factor: --------- --- ---------.........................0.100
Load per unit area:_............................................................54.6 BTU/(hr-sqft) Resulting RH:....___......----.___...----- ------.-------------._-------49 %
Design supply temp:... _....... - - - 55.0 F
Central Heating Coil Sizing Data
Max coil load, ___-------..._.__.-----_----------------------26.7 MBH Load occurs at:-................_...................----._............... es Htg
Coil airflow:. ................. -- - ----------.__.----..__....-----2737 CFM Ent DB/Lvg DB:--------..-----...._............_................... F
Load per unit area:-------------_._._.............------------__-----------14.6 BTU/(hr-sgft)
Supply Fan Sizing Data
Actual max airflow:------------- -..................................2737 CFM Fan motor BHP:....................... ------ -0.48 BHP
- Standard airflow:.........................................._-----------------2736 CFM Fan motor kW:.--------- ------------- - -----------------..0.36 kW
Actual max airflow per unit area: ......................._.1.50 CFM/sqft Fan static:..................................-------_----- _.------ _-__.._.0.60 in wg
Outdoor Ventilation Air Data
• Design airflow:------------- ------------------------------.......................... 45 CFM Airflow per person:...--------------------------._.........................34.06 CFM/person
Airflow per unit floor area:-_....__-__..-__._-___._---_------0.30 CFM/sqft
Space Sizing Data
Space Name Maximum Design Ti a of Peak Maximum Space Space
Cooling Airflow Load Heating Floor CFM/sgft
Sensible CFM load MBH Area
MBH sqft
Zone 2 59.1 27371 Jul 1600 13.5 1820.0 1.50
Block Load 4.15 Page 1 of 1
System Input Data
Project Name: 13-1206 Primal Fit Miami 01/20/2014
Prepared by:ARPE Engineering,Inc. 03:09PM
General Details:
Air System Name:...................................._._... --_...__..-AC#2
Air System Type:..----------..............._ Single Zone CAV
Number of zones:..------------------ ............ - ..................1
SystemStartup:..._.. - .............. _.....-. .................6
Duration of Operation:._-------------------- -----------............._ --24
Central Cooling Coil Data:
Used?:...-----_...-...............------ ------------- _..__....YES
Supply Air Temperature:----.-------------------------.................55.0 F
Coil Bypass Factor:........... ------------- - 0.100
Central Heating Coil Data:
Used?:........-- .................. - ....._.. ..... - --- -----YES
Supply Temperature: - .......... . .... ............ ...110.0 F
Supply Fan Data:
Configuration:- ..—_....................----------------------------D raw-th ru
Fan Performance:..- _.................____.........................0.60 in wg
Ceiling Return Air Plenum Data:
Return Air Via:........___...-.........._.____-_...Ducted Return
Zones Included:
Zone Names I
Zone 2
Thermostats Data:
• Cooling T-stat:Occ:..--._..------.-----_.................. ----.75.0--...._....75.0 F
Cooling T-stat:Unocc:_----------------- ........................____ $5.0 F
Heating T-stat:Occ: -....................................... -_.70.0 F
Heating T-stat:Unocc:------------------------------------.............._60.0 F
Safety Factors:
Cooling Sensible Safety Factor:.---------_.. -------------------------0 %
Cooling Latent Safety Factor:._------------------------_...-------------- %
Heating Safety Factor:...... ------------------- .................0 %
Block Load 4.15 Page 1 of 1
� �--
. �
^ �
-
Air System Sizing Summary for AC#3
Project Name: 13-1206 Primal Fit Miami 01/14/2014
�
Air System Information
Air System Name:................ Number mzones:-------_ ..............----'--------------
Air System
--xAirsymem —SinoleZone CAV Floor .............. sqn
,
Location:_ -------------------'Miam/Shores,Florida
Sizing Calculation Information
Calculation womms:---------------JanmDec Calculation method: .- Transfer Function Method
Central Cooling Coil Sizing Data
Total coil|mm:------- ---------------------- ------o.1 Tons Load occurs at:................................... Jul 1500
Total coil|oad:--................ - ------------- - oa.0 mo� o�oo/va� - �nu.xnu.o r
Sensible coil|nau:- mJ MBH sntennuoe/vva:----- 78.7/6*.3 F
Coil airflow: -- ..........aaoo CFM Leaving oe/WB:............................... _55.1/54.0 r
Sensible heat ratio: -...................oJoo Coil ADP:..................................... '52.5 p
Area per unit load: . uo spn/Tun Bypass Factor:. ._ -_ ......................................u1oo
�
Load per unit area: 54.8 eTuK»r-oqn RK .............. *y m
Design supply r
Central Heating Coil Sizing Data
Max coil load ............................................ ........................2r.2 MBH Load occurs at:.............................-......... --�----Dws*tg
Coil aimow:.'_--' ------------------------------------------------------onux CFM Ent oB/LvgDB:..'—'__----....................... F
�
Load per unit area:.---------- -----------15.4 eru/(xr-oqn
Supply Fan Sizing Data
Actual max airflow:.--------------------osox CFM Fan motor BHP: ----------------o.46 BHP
Standard airflow..... -2657 CFM Fan motor kW: ------'oao wv
�
Actual max airflow per unit .51 oFw/sqn Fan smn :-.— ------ .................. oao mwm
� 'Outdoor Ventilation Air Data
� ' ^
Design airflow:---------------_-_-............--------------------sao CFM Airflow per person:-- _- --------- ------------ .......... xx.1a CFM/person
�
Airflow per unit floor areu:...'. oFm1sqft
�
Space Sizing Data
�
Space Name Maximum Design ime of Peak Maximum Space Space
Cooling Airflow Load Heating Floor CFM1sqft
Sensible Load MBH Area
Zone 3 57.4 26581 Jul 1600 13.8 1765.0 1.51
Block Load 4.15 Page 1 of I
�
1
( .
�
�
�
System Input Data
Project Name: 13-1206 Primal Fit Miami 01/20/2014
Prepared by:ARPE Engineering, Inc. 03:10PM
General Details:
Air System Name: -- - -...._._........ ..............AC#3
_Air System Type: Single Zone CAV
Number of zones:.....-------------------.------- ..____...._..........1
System Startup:.. --------------- - - 6
Duration of Operation:_._----- ---_...___.........._..............__24
Central Cooling Coil Data:
Used?:_... .... -..... - -- - ---.... ...................YES
Supply Air Temperature ..........................-.55.0 F
Coil Bypass Factor:.._............................._........_....._...-.--0.100
Central Heating Coil Data:
Used?:__._...__...__._...- -- - - - -------------------YES
Supply Temperature:__ _._...--....-.-.._........................110.0 F
Supply Fan Data:
Configuration:.._._._.._............ ..............................D raw-th ru
Fan Performance:.__.---...----------...--- ----------...------.0.60 in wg
Ceiling Return Air Plenum Data:
Return Air Via:............................................. Ducted Return
Zones Included:
Zone Names
Zone 3
Thermostats Data:
Cooling T-stat:Occ:.. ------ - ...._ - 75.0 F
Cooling T-stat:Unocc:------.-------_.... ..............................85.0 F
Heating T-stat:Occ:----- - ---- —- - .........70.0 F
Heating T-stat:Unocc:... .............................. ..............60.0 F
Safety Factors:
Cooling Sensible Safety Factor:................................. 0 %
Cooling Latent Safety Factor: 0 %
Heating Safety Factor:.......................................................... 0 %
Block Load 4.15 Page 1 of 1
Air System Sizing Summary for AC#4
Project Name:13-1206 Primal Fit Miami 01/20/2014
repared by:ARPE Engineering,Inc. 03:10PM
Air System Information
Air System Name:._......- ......-- ---.. .....-.... AC#4 Number of zones:...........................................
Air System Type:..._.....___._......._.._......Single Zone CAV Floor Area:.. ---------------------............................758.0 sqft
Location:....._......................._...........Miami Shores,Florida
Sizing Calculation Information
Calculation Months:......__-_.........._......................Jan to Dec Calculation method: Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load:_.._..._..---------- ___..._..._....._._...................4.4 Tons Load occurs at:...............-... -----.._..------- ----. --Aug 1500
Total coil load:..................... - ..... ..........52.4 MBH OA DB/WB:.._.... - - -- - 92.3/78.5 F
Sensible coil load:............................ --------,-....----.39.6 MBH Entering DB/WB:........................................-------------77.7165.0 F
Coil airflow:. . ....-------------....................---------- _ 1625 CFM Leaving DB/WB:.......................................................55.1/54.0 F
Sensible heat ratio: - --------------------------------- Coil ADP: - _ ---------------.. . ..._............... --.52.6 F
Area per unit load: .........................................173.7 sqft/Ton Bypass Factor: ............................................0.100
Load per unit area: ..69.1 BTU/(hr-sqft) Resulting RH:..................._.........._..................._.......__...-- ..48 %
Design supply temp:...----- - ------- _ - ----.... - 55.0 F
Central Heating Coil Sizing Data
Max coil load_---------------------------------------------- - ---------13.7 MBH Load occurs at:---------------- - ------ -------------------Des Htg
Coil airflow:-............ ..................... -- - ------------------1625 CFM Ent DB/Lvg DB: -------- -------_------------------66.9/74.7 F
Load per unit area:. .............. ---------_---..........-18.1 BTU/(hr-sqft)
Supply Fan Sizing Data
Actual max airflow:.. -.... - ... ......._............. ......1625 CFM Fan motor BHP:.._.... ........ ............. ..... ..... --- 0.28 BHP
• Standard airflow:......................... -. ........................1624 CFM Fan motor kW: ._.....__ .......................... 0.21 kW
Actual max airflow per unit area:........._....._.................. CFM/sqft Fan static:________....._.._.......................................__._.0.60 in wg
Outdoor Ventilation Air Data
Design airflow:---....---.---- ------.._.............................. .__.227 CFM Airflow per person:............-..--.........._._.--- ----._..__18.92 CFM/person
Airflow per unit floor area:.................._........ ____0.30 CFM/sqft
Space Sizing Data
Space Name Maximum Design Tia of Peak Maximum Space Space
Cooling Airflow toad Heating Floor CFM/sqft
Sensible CFM Load MBH Area
MBH sqft
Zone 4 35.1 16251 Jul 16001 8.4 758.0 2.14
( I 1 .2( *4
Block Load 4.15 Page 1 of 1
` .
'
System Input Data
Project Name: 13-1206 Primal Fit Miami 01/20/2014
-Prepared by:ARPE Engineering,Inc. 03:11 PM
General Details:
Air System Name:.-.._------ Ac#4 �
Ar System Type:.................................'-Single Zone CAV
,
Number of .
System Startup:............. ---'--------_-_--n
Duration mvvomovn:.------_--_---_—---2*
Central Cooling Coil Data: �
------.--Yso �
Supply Air Temperature:-------------------- ...........................ou.o F
Coil Bypass0.100
Central Heating Coil Data: �
Supply Temperature: -- ........................ r
Supply Fan Data:
ononouraoon:--- .........--'-......----------------_orav+mm
Fan 0.60 mwn
Ceiling Return Air Plenum Data:
Return Air wa:- -- - Ducted Return
Zones Included:
Zone NamesZone 4
"
'
Thermostats Data:
^
Cooling T-stat:ooc— ................................ F
Cooling T-statunnoc ...................................................m5.o F
HeannoT-stat:uoo:...—'--. p
HvannoT*tat:unocc--- ... ...uoo F
Safety Factors:
Cooling Sensible m
Cooling Latent Safety Factor:-----.................................. m
Heating Safety Factor:-...................... m
�
Block Load 4.15 Page 1 of 1
�
Air System Sizing Summary for AC#5
Project Name:13-1206 Primal Fit Miami 01/20/2014
Prepared by:ARPE Engineering,Inc. 03:12PM
Air System Information
Air System Name: - - -- ._---------------------- AC#5 Number of zones: -- ................. ..... ......_ ..........
-Air System Type:..__._----------------._..........Single Zone CAV Floor Area:---------------_----._..............................................1213.0 sqft
Location:--__................._.--------__......Miami Shores,Florida
Sizing Calculation Information
Calculation Months:__ ________........................Jan to Dec Calculation method:..__........Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load:._.- -------__................................................4.9 Tons Load occurs at:.-.................--------------------------............... ul 1500
Total coil load:.._......_..................-----..---------------...._. 59.2 MBH OA DB/WB:...... ---_-------------------- _...--- _.92.3/78.5 F
Sensible coil load:............................................._._...-- __..40.8 MBH Entering DB/WB:____-._.-------.-------------. ........_...79.4166.7 F
Coil airflow:... - -------- ----- - - — - . ..--..1560 CFM Leaving DB/WB: ------------ .._... .................55.1154.1 F
Sensible heat ratio:........ .......... .... - - ---0.689 Coil ADP: - - ._....__.................................................52.4 F
Area per unit load:._._._.---- --.-- --------_ ............ 45.7 sgft/Ton Bypass Factor:.__...........................................--------------- 0.100
Load per unit area: ............. ..... .... .. - 48.8 BTU/(hr-sgft) Resulting RH: -- _.......-.....-. ...... ........_.. .. .... ....48 %
Design supply temp:.... .......... .... ..........................55.0 F
Central Heating Coil Sizing Data
Max coil load_.....................------_ - . . ............. 16.8 MBH Load occurs at:................................................ .._.....Des Htg
Coil airflow:_- ---------- - ..... __.. .........................1560 CFM Ent DB/Lvg DB:--------------- ----... - -- -- 64.7174.7 F
Load per unit area:_---- -__-----____-._.__.......................13.9 BTU/(hr-sgft)
Supply Fan Sizing Data
Actual max airflow:-.-_ ----- ------------------------------------------1560 CFM Fan motor BHP:----------- --- -------------------------------._..._..0.27 BHP
Standard airflow:..... ..............._.._... -_----- -----....-1560 CFM Fan motor kW:----. ............._.....-------------------------.----------0.20 kW
Actual max airflow per unit area:__.._....-.....-------------------1.29 CFM/sgft Fan static:. ........................ _._....__ _.___._.._._. 0.60 in wg
Outdoor Ventilation Air Data
Design airflow:------------------..-...................................._._._--..364 CFM Airflow per person:.--------.......-...........................................30.33 CFM/person
Airflow per unit floor area:............. _0.30 CFM/sqft
Space Sizing Data
Space Name Maximum ` 'Design Time of Peak Maximum Space Space
Cooling Airflow Load Heating Floor 'CFM/sgft
Sensible CFM > Load MBH Area
MBH sgft
Zone 5 33.7 1560 Jul 15001 7.6 1213.0 1.29
1�
I.
Block Load 4.15 Page 1 of 1
System Input Data
Project Name: 13-1206 Primal Fit Miami 01/20/2014
Prepared by:ARPE Engineering,Inc. 03:12PM
General Details:
Air System Name: .... _..... ............................._........AC#5
Air System Type: Single Zone CAV
Number of zones:..----.......-----------__......._.._..... ..._.....1
System Startup: -- -- - -. 6
Duration of Operation: ................. .......24
Central Cooling Coil Data:
Used?:.....................- ........._......._._....... ..........................YES
Supply Air Temperature ________.55.0 F
Coil Bypass Factor:.._...................................... 0.100
Central Heating Coil Data:
Used?: ----- -------
-- _......._..-------- ........... ES
Supply Temperature:------------------------------------__.--..-.---110.0 F
Supply Fan Data:
Configuration:______.____------------------------------Draw-thru
Fan Performance:...__.... ----- .._........-------------------0.60 in wg
Ceiling Return Air Plenum Data:
Return Air Via: ..................................Ducted Return
Zones Included:
Zone Names -1
Zone 5
Thermostats Data:
Cooling T-stat:Occ:------------------------_------------ -- 75.0 F
Cooling T-stat:Unocc:------ .........._85.0 F
Heating T-stat:Occ:._.................................--------------..........70.0 F
Heating T-stat:Unocc:_-------------._____----- ---------._..60.0 F
Safety Factors:
Cooling Sensible Safety Factor:-._.__.-----..__..................._0 %
Cooling Latent Safety Factor:... _0 %
Heating Safety Factor:.............. ------ ----- ___._.__.-0 %
Block Load 4.15 Page 1 of 1
March 10, 2014
Miami-Dade County
Fire Rescue
11805 SW 26th Street
Miami, Florida 33175
Process Number: M2014004670
Dear Ricardo Gonzalez,
The following are the items discussed and revised in the drawings:
1. Occupancy Type and loads in sheet A-2 have been revised to show only Assembly with
incidental Business & Mercantile in the form of offices and an area for sales of clothing,
etc;
2. "Small Group" part of the tenant space calculated under "Exercise with Equipment" has
been graphically clarified by adding exercise equipment in sheet A-3;
3. Additional exit added in the west side of space and doors have been revised to show
out-swing.Sheet E-2 has been revised to show extra exit sign;
4. Inclined surfaces with a slope of 1:30 have been clearly shown in the plan;
5. Janitor's closet has been revised in sheet A-3 to show rated partition and a new door;
6. Janitor's closet door is shown as rated for 45 min. in sheet A-10;
We have met a couple of times to discuss the plans and the last time we met, I did not have the
electrical sheet revised showing the added exit sign.
Please contact me at 305-310-5030 if you have any questions and/or comments.
Sincerely,
ottv
Y?)
Victor J. Bruce A.I.A., LEED R AP
Vice President&Architect
AR-0017103
Al ,! asSOCIG'es Inc-
'�
i<7n,ihOreS.
i
I
I Li .SSOC ate S.f ie!
pw;'
MIAMIDADE
FIRE ENGINEERING & WATER SUPPLY BUREAU
11805 SW 26 STREET, SUITE 150, MIAMI, FL. 33175
TELEPHONE (786) 315-2771 EMAIL:
www.miamidade.gov/mdfr
� 1
I
FIRE REVIEW DISAPPROVAL COMMENTS
DATE: 2/18/14 FD TRACKING NUMBER: M2014004670 REVIEWED BY: RICK GONZALEZ
NAME OF PROJECT: PRIMAL FIT ADDRESS: 9537 NE 2 AVE MIAMI, FL.
1. PLEASE MAKE AN APPOINTMENT WITH PLANS EXAMINER TO DISCUSS
PLANS
2. FOR QUESTIONS,CONCERNS,OR CLARIFICATION ON DISAPPROVAL COMMENTS,YOU MUST
SCHEDULE A 2Q MINUTES DESIGN PROFESSIONAL APPOINTMENT. APPOINTMENTS ARE HELD ON
MONDAY'S&THURSDAY'S ONLY. APPOINTMENTS MAYBE SCHEDULED THE PREVIOUS
WORKING DAY OF THE APPOINTMENT BETWEEN THE HOURS OF 8:30AM AND 4:30PM BY CALLIN(
786-315-2771 OR LOGGING IN TOwww.miamidade.gov/buildingPLEASE KNOW THE ,
REVIEWER'S NAME AND DADE COUNTY PROCESS#OR FIRE TRACKING#.)"THESE
APPOINTMENTS ARE NOT PART OF THE REVIEW"
FAST TRACK FOR REWORK