EL-15-598 (2) e t R
Inspection Worksheet
Miami Shores Village
10050 N.E. 2nd Avenue Miami Shores, FL
Phone: (305)795-2204 Fax: (305)756-8972
Inspection Number: INSP-235108 Permit Number: EL-3-15-598
Scheduled Inspection Date: May 22, 2015 Permit Type: Electrical - Residential
Inspector: Devaney, Michael
Inspection Type: Final
Owner: TOLEDO, JORGE & MAGALYS Work Classification: Alteration
Job Address: 1279 NE 97 Street
Miami Shores, FL 33138-2559 Phone Number
Parcel Number 1132050090440
Project: <NONE>
Contractor: JCL ELECTRICAL CORP Phone: (305)498-7268
Building Department Comments
INSTALL RECEPTACLE, LIGHT SWITCHES LIGHTING Infractio Passed Comments
INSPECTOR COMMENTS False
AND SMOKE DETECTOR AS PER ELECTRICAL PLAN
Inspector Comments
Passed CREATED AS REINSPECTION FOR INSP-233886. CREATED AS
Ef REINSPECTION FOR INSP-233758. Service not to code:
2 conductors under lug.
200 amp breaker with#1 conductors that are only rated 150 amp..
Failed ❑ Plans state 3/0 conductors in 2"conduit .
20 may 2015
Plans was revised but the 200 amp main breaker not changed to 150 amp.
Grounding electrode conductor not connected to the cold water pipe or bldg.
Correction ❑ steel.
Needed
Re-Inspection ❑ �-
Fee 27-
No Additional Inspections can be scheduled until
re-inspection fee is paid.
May 21,2015 For Inspections please call: (305)762-4949 Page 19 of 36