EL-15-598 (2) e t R Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795-2204 Fax: (305)756-8972 Inspection Number: INSP-235108 Permit Number: EL-3-15-598 Scheduled Inspection Date: May 22, 2015 Permit Type: Electrical - Residential Inspector: Devaney, Michael Inspection Type: Final Owner: TOLEDO, JORGE & MAGALYS Work Classification: Alteration Job Address: 1279 NE 97 Street Miami Shores, FL 33138-2559 Phone Number Parcel Number 1132050090440 Project: <NONE> Contractor: JCL ELECTRICAL CORP Phone: (305)498-7268 Building Department Comments INSTALL RECEPTACLE, LIGHT SWITCHES LIGHTING Infractio Passed Comments INSPECTOR COMMENTS False AND SMOKE DETECTOR AS PER ELECTRICAL PLAN Inspector Comments Passed CREATED AS REINSPECTION FOR INSP-233886. CREATED AS Ef REINSPECTION FOR INSP-233758. Service not to code: 2 conductors under lug. 200 amp breaker with#1 conductors that are only rated 150 amp.. Failed ❑ Plans state 3/0 conductors in 2"conduit . 20 may 2015 Plans was revised but the 200 amp main breaker not changed to 150 amp. Grounding electrode conductor not connected to the cold water pipe or bldg. Correction ❑ steel. Needed Re-Inspection ❑ �- Fee 27- No Additional Inspections can be scheduled until re-inspection fee is paid. May 21,2015 For Inspections please call: (305)762-4949 Page 19 of 36 L-,i dab M;14 PA jo —,W.T v if Z1