Roof Tile Uplift Test Report
Attention: Miami Shores Village, Building Division,
10050 NE 2nd Avenue, Miami Shores, FL 33138
Client: T & S Roofing Systems, Inc
Test Date: 12/31/2014
Property Address:
Permit # RF -3-14-587
900 NE 100 Street. Miami Shores. FI
Roof Pitch:
Type of Tile:
Roof Area:
5 in 12
Boral Roof Tile
35.00 squares
Tile Attachment Method:
Two Component Polyurethane Foam Adhesive -Poly Pro H 160
Field Instrument:
IMADA Force Gauge 0-100 Serial number: 243454
Test Location
Total Number of Tests
Field Uplift Pull Test
Test results
Perimeter Area: 15.00 sq
15
As per FBC 2010
Passed
Field Area: 20.00 sq
20
As per FBC 2010
Passed
No. of Corner: 15
15
As per FBC 2010
Passed
Ridge Areas: 180 PCs
15
As per FBC 2010
Passed
Important.
These laboratory results can change due to future weather impacts and/or unavoidable roof
traffic. Therefore, this report represents the TAS 106 results at the time of the test.
Please see attached a Roof Sketch for this project.
Cordially,
ACB2 Engi rig Inc. (NOA 09-1005.01)
Antoedo, PE
U
Fla. Reg. o: 36466
10126/
a
ACB2 Engineering Inc,
Engineering and Laboratory Services
5230 M Ie Avenue
Fort Lauderdale, Florida 33334
Phone: (954)245-8976 Fax: (954) 301-7776
_ T
i
1 ( f (r
t i
f fi rt
4L
1
B IkD G
Miami Shores Village
Building Department
10050 N.E.2nd Avenue, Miami Shores, Florida 33138
Tel: (305) 795.2204 Fax: (305) 756.8972
INSPECTION'S PHONE NUMBER: (305) 762.4949
PERMIT APPLICATION
MAR -1 b 2014
FBC 20
Permit No. _ /�
Master Permit No.AF' � 7 "v—?z-
Permit Type: BUILDING ROOFING
JOB ADDRESS: 0
City: Miami Shores County: Miami Dade Zip: (�
Folio/Parcel#:
Is the Building Historically Designated: Yes
OWNER: Name (Fee Simple
Ir"
Zone:
City: State: Zip: 737�
Tenant/Lessee Name: Phone#:
Email:
CONTRACTOR: Company Name: �� 1 "4e'he VI -A 5 Phone#:
Address: '1 1,^ � vkj '7,-;
City: �� 6 ""i
Qualifier Name: I
-:T� Zip:
State Certification or Registration #: ����' ��`� Z 3 rte Certificate of Competency #:�-
Contact Phone#: `}� "`1• Email Address:
DESIGNER: Architect/Engineer: Phone#:
Value of Work for this Permit: $i l 1300 Square/Linear Footage of Work: � � JrN
V
Type of Work: ❑Additi ❑Alteratioq Lrr� Oat ❑Repair/Replace ❑Demolition
Description of Work: V, P Oat `
Color thru
0 t �Co'
Submittal Fee $ Permit Fee
Scanning Fee $
Notary
Radon Fee $
Training/Education Fee $
Double Fee $ Structural Review $
CO/CC $
DBPR $ Bond
Technology Fee $
TOTAL FEE NOW DUE $
Bonding Company's Name (if applicable)
Bonding Company's Address
J
City
State
Mortgage Lender's Name (if applicable)
Mortgage Lender's Address
City
State
zip
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS,
WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONERS, ETC.....
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant. As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved and a reinspection fee will be charged.
u
Signature Signature .
Owner or Agent
Contractor
The foregoing i strument was ac owledge�jd�rb}°fore e s The foregoing i strument was cknowledged befor ma this �5
day of i�' ° , 20 , by ��� \�' �, ' day of , y
who is ersonally known to me or o has produced wh tkpersonally known for who has produced
As identification and who did take an oath. -- as identification and who did take an oath.
NOTARY PUBLIC:
Sign.
Print:
My Commission Expires:
APPROVED BY
you' -v4% otery Public State of Florida
aniel Perez
�• MyCommission ,EE123821
oEt�o~ Expires 08/21/2015
7 ` Plans Examiner
Structural Review
(Revised 3/12/2012)(Revised 07/10/07)(Revised 06/10/2009)(Revised 3/15/09)
NOTARY PUBLIC:
Si
Prim
My Commi iagXgireNotary Public Ste
_ Daniel Perez
y� oa My Cornmisolon EE
Expiros 08121/2015
Zoning
Clerk
5
, . OWNER'S AFFIDAVIT OF EXEMPTION
Roof to Wall Connection Hurricane Mitigation Retrofit for Existing Site -Built Single Family
Residential Structures
Pursuant to Section 553.844 F.S.
Date:
To:
Re: Owner's Name:
ul�
Property Address:' iAJ C
Roofing Permit Number:
Dear Building Official:
I U11AM4 certify that I am not required to retrofit the roof to wall connections of
my 6itildYng because
The just valuation for the structure for purposes of ad valorem taxation is less than $300,000.
The building was constructed in compliance with the provisions of the Florida Building Code (FBC) or with
the provisions of the 1994 edition of the South Florida Building Code (1994 SFBC)
�Olt;,
Signature of Property Owner
10 &/- f? F ()
Print Name
STATE OF FLORIDA COUNTY OF MIAMI -DARE
Sworn to i subs, bed before s
Day of 20�,
_ Personally known
or Produced Identification
When the just valuation of the structure for the purposes of ad valorem taxation is equal to or more than $300,000,
and the building was not constructed in compliance with the FBC nor with the 1994 SFBC, and affidavit of Roof to
Wall Connection Hurricane Mitigation Retrofit must be provided.
M IAM 1-DADE COUNTY PROPERTY APPRAISER
Lazaro Solis
PROPERTY APPRAISER
Property Information:
Folio
11-3206-0340220
Property Address
900 NE 100 ST
Owner Name(s)
RAYMOND MATEO
DAMARIS MATEO
Mailing Address
900 NE 100 STREET
MIAMI SHORES FL 33138
PrimaryZone
1100 SGL FAMILY - 2301-2500 SQ
Use Code
0101 RESIDENTIAL - SINGLE FAMILY
: 1 UNIT
Beds/Baths/Half
3/2/0
Floors
1
Living Units
1
Adj. Sq. Footage
2,295
Lot Size
18,455.2 SQFT
Year Built
1941
Full Legal Description
MIAMI SHORES SEC 8 PB 1433
LOT 10 TO 12 BLK 170
LOT SQE 156.400 X 118
COC 25289-3838 012007 5
Assessment Information:
Year 2013 2012
Land Value $198,723
Building Value $173,690 $177,620
Market Value 24,535 $376,343
Assessed Value $424,535 $301,732
Benefits Information:
Benefit
Type
2013
2012
Save Our Homes
Cap
Assessment
Reduction
$0
$74,611
Homestead
Exemption
$25,000
$25,000
Second
Homestead
Exemption
$25,000
$25,000
Note: not all benefits are applicable to all Taxable Values (ie County,
School Board, City, Regional).
Disclaimer:
Aerial Photography 2012
Taxable Value Information:
Year
2013
2012
Exemptlon/
Taxable
Exemption/
Taxable
County
$50,000/$374,535
$50,000/$251,732
School Board
$25,000/$399,535
$25,000/$276,732
City
$50,000/$374,535
$50,000/$251,732
Regional
$50,000/$374,535
$50,000/$251,732
Sale Information:
Date
Amount
ORBook-Page
Qualification Code
07/31/2012
$560,000
28223-4104
Qual by exam of deed
01/01/2007
$0
25289-3838
Qual by exam of deed
06/01/2004
$0
22416-4180
Qual by exam of deed
03/01/2004
$50,000
22416-4179
Qual on DOS, but significant
phy change since
04/01/2000
$290,000
19073-4445
2008 and prior year sales, Qua[
by exam of deed
The Office of the Property Appraiser and Marri-Dade County are continually editing and updating the tax roll and GIS data to reflect the latest property information and
GIS positional accuracy. No warranties, expressed or implied, are provided for data and the positional or thematic accuracy of the data herein, its use, or its
interpretation. Although this website is periodically updated, this information may not reflect the data currently on file at Mani -Dade County's systems of record. The
Property Appraiser and Marti -Dade County assumes no liability either for any errors, omissions, or inaccuracies In the Information provided regardless of the cause
of such or for any decision made, action taken, or action not taken by the user in reliance upon any information provided herein. See Miami -Dade County full disclaimer
and User Agreement at http://www.rriarridade.govMfo/disclairrer.asp.
Property information inquiries, comments, and suggestions email: pawebma[I@miarridade.gov
GIS Inquiries, comments, and suggestions email: gis@miamidade.gov Generated on: Wed Mar 05 2014
Section A/B
A
MIAMI.&D f Miami -Dade County HVHZ Electronic Roof Permit Form
"Delivering Excellence Every l?ay" r-�—
Section A (General information) '
>°.: fir: .. • �� " x; :� '���' � lhl,�. �� ,) �" -
�-: — /�
r
x' x
.. r'900 NE 100 ST
21 Low Slope 0 Mechanically Fastened Tile Mortar/Adhesive Set Tile
Asphaltic Shingles El Metal Panel/Shingles wood Shingles/Shakes
® Sprayed Polyurethane Foam El other.
Roof Type
® New Roof 0 Re -Rooting Recovering 0 Repair ® Maintenance
Are there Gas Vent Stacks located on the roof? H Yes ® No If yes, what type? El Natural ® LPGX
Roof System Information
Steep Sloped area (ft?) 3500 Total (fL2)
Low slope roof area (I1.2) 250 3750
Section B (Roof Plan)
Sketch Roof Plan: Illustrate all levels and sections, roof drains, scuppers, overflow scuppers and overflow drains. Include
dimensions of sections and levels, clearly identify dimensions of elevated pressure zones and location of parapets.
Perimeter Width (a°): Corner Size (a' a'):
■ 8
WPJ
y
s II T
F II f—s I L V
II II T Ipl �
� ELU
a
II �� II• NI " IIcc 0 0 0 15
lu
- z
Q ° m
Tile Roof System
MIAMI -RADE
Miami -Dade County HVHZ Electronic Roof Permit Form
Section D Tile Roof System
"Delivering Excellence Every Day"
Roof System Manufacturer: I BORAL ROOFING LLC
Notice of Acceptance Number (NOA): 13-0723.05
Minimum Design Wind Pressures, If Applicable (from RAS 127 or Calculations):.
P 1: 39.1 P 2:168.1 11 P 3: 100.7
Maximum Design Wind Pressures, (From the NOA Specific system): 31.3 psf
Fill in the specific roof assembly components. If a component is not required, insert not applicable (n/a) in the text box.
Roof Slope: 3 "/12"
Roof Mean Height: 8 ft.
Method of Tile Attachment:
--Adhesive, 2 Small Paddy Polyfoam Polypro—
Alternate Method of Tile Attachment per NOA:
Drip Edge Size & Gauge: --3" face 24 ga.—
Drip Edge Material Type:I --Gaivinized Metal—
Drip Edge Fastener Type: 11 1/4 RS NAILS
Hook Strip/Cleat gauge or weight: -- Select Hook Strip --
Deck Type: —5/8" Plywood—
Optional Insulation:
17
Optional Nailable Substrate:
Optional Nailable Substrate Attachment:
Basesheet Type:
#30 astm type 11
Fastener Type for Basesheet Attachment:
1 1/4 rs nails 6" oc and 12" field
Tile Underlayment (Cap Sheet) Type:
UnderRoof 2
Tile Underlayment Attachment Method:
SELF ADHERED
Tile Profile:
SAXONY 900
Section E
t +
MIAhIN E
0
"Delivering Excellence Every Day"
Miami -Dade County HVHZ Electronic Roof Permit Form
Section E (Tile Calculations)
Method 1 "Moment Based Tile Calculations Per RAS 127"
For Moment based tile systems, use Method 1. Compare the values for Mr with the values from Mf. If the Mf values are
greater than or equal to the Mr values, for each area of the roof, then the file attachment method is acceptable.
P 1: 39.1 X .313 = 12.23 - Mg: 8.03 = Mr1: 4.20 5 31.3 NOA Mf
P 2: 68.1 X 2,.313 = 21.31 - Mg: 8.03 = Mr2: 13`28 5 31.3NOA Mf
P 3: 100.7 X11.313 = 31.51 - Mg; 8.03 = Mr3: 23.48 S 31.3 NOA Mf
Method 3 "Uplift Based Tile Calculations Per RAS 127"
For Uplift based file systems use Method 3. Compare the values for F' with the values for Fr. If the F values are greater than or equal to the Fr values, for
each area of the roof, then the file attachment method is acceptable.
P1: x 1: = x w: = - W. = x cos 0: = Fr1: 5 _ NOA F
P2: X 1: X w: _ - W. _ _ . � x cos e: = Fr2: 5 NOA F
P3: x 1: = X w: = - W. _ x cos 0: M= Fr3: 5 NOA P
Where to Obtain Information to complete tile calculations
Description
Symbol
Where to Find
Design Pressure
P1 or P2 or P3
Table 1 RAS 127, or by an engineer analysis prepared, signed and sealed by a professional
engineer based on ASCE 7.
Mean Roof Height
H
Job Site
Roof Slope
8
Job Site
Aerodynamic Multiplier
Product Approval (NOA)
Restoring Moment due to Gravity
Mg
Product Approval (NOA)
Attachment Resistance
Mf
Product Approval (NOA)
Required Moment Resistance
Mr
Calculated
Minimum Attachment Resistance
P
Product Approval (NOA)
Required Uplift Resistance
Fr
Calculated
Average Tile Weight
W
Product Approval (NOA)
Tile Dimensions
=
I length
w = width
Product Approval (NOA)
Tile_Roof System
M4AMI•DADE
no Miami -Dade County HVHZ Electronic Roof Permit Form
Section D Tile Roof System
"Delivering Excellence Every Day"
Roof System Manufacturer: I BORAL ROOFING LLC
Notice of Acceptance Number (NOA): 13-0723.05
Minimum Design Wind Pressures, If Applicable (from RAS 127 or Calculations):
P 1: 39.1 P 2: 68.1 P 3:1100.7 _
Maximum Design Wind Pressures, (From the NOA Specific system): 31.3 psf
Fill in the speck roof assembly components. !f a component is not required, insert not applicable (n/a) in the text box.
Roof Slope: 712"
Roof Mean Height: 8 ft.
Method of Tile Attachment:
--Adhesive, 2 Small Paddy Polyfoam Polypro--
Alternate Method of Tile Attachment per NOA:
Drip Edge Size & Gauge: --3" face 24 ga.—
Drip Edge Material Type: I --Gaivinized Metal—
Drip Edge Fastener Type: 1 1 1/4 RS NAILS
Hook Strip/Cleat gauge or weight:-- Select Hook Strip --
Deck Type: _-5/8" Plywood—
Optional Insulation:
Optional Nailable Substrate:
Optional Nailable Substrate Attachment:
Basesheet Type:
#30 astm type II
Fastener Type for Basesheet Attachment:
1 114 rs nails 6" oc and 12" field
Tile Underlayment (Cap Sheet) Type:
UnderRoof 2
Tile Undedayment Attachment Method:
SELF ADHERED
Tile Profile:
SAXONY 900
Section E
MIAM PIDADE
"Delivering Excellence Every Day -
Miami -Dade County HVHZ Electronic Roof Permit Form
Section E (Tile Calculations)
Method 1 "Moment Based Tile Calculations Per RAS 127"
For Moment based tile systems, use Method 1. Compare the values for Mr with the values from Mf. If the Mf values are
greater than or equal to the Mr values, for each area of the roof, then the file attachment method is acceptable.
P 1: 39.1
XX .313
= 12.23
- Mg: 7.74
= Mr1: 4.49 . 5 31.3 NOA Mf
P2:168.1
x .313
= 21.39
- Mg; 7.74
= Mr2: 13.57 5 31.3 NOA Mf
P 3:1100.7 1
x X.313
= 31.51
- Mg; 7.74
= Mr3: 23.77 5 31.3 NOA Mf
Method 3 "Uplift Based Tile Calculations Per RAS 127"
For Uplift based file systems use Method 3. Compare the values for F with the values for Fr. If the F values are greater than or equal to the Fr values, for
each area of the roof, then the the attachment method is acceptable.
P1: x 1:
�
=
x w:
_
- W. =
Roof Slope
x cos 0: M= Fri:
_ 5
NOA P
P2: x 1:
Product Approval (NOA)
= �
X w:
_
_ W. =
Mf
X Cos 0: M = Fr2:
_ _ 5
_ _ _ NOA F
P3: x l:
Minimum Attachment Resistance
=
x w:
=
- W. =
Calculated
X Cos 0: El = Fr3:
5
NOA F
Where to Obtain Information to complete tile calculations
Description I Symbol I
Where to Find
Design Pressure
P1 or P2 or P3
Table 1 RAS 127, or by an engineer analysis prepared, signed and sealed by a professional
engineer based on ASCE 7.
Mean Roof Height
H
Job Site
Roof Slope
9
Job Site
Aerodynamic Multiplier
Product Approval (NOA)
Restoring Moment due to Gravity
Mg
Product Approval (NOA)
Attachment Resistance
Mf
Product Approval (NOA)
Required Moment Resistance
Mr
Calculated
Minimum Attachment Resistance
F
Product Approval (NOA)
Required Uplift Resistance
Fr
Calculated
Average Tile Weight
W
Product Approval (NOA)
Tile Dimensions
=
I length
w = width
Product Approval (NOA)
4. INSTALLATION
4.1 Saxony 900 (Slate, Shake & Split Shake) Concrete Roof Tile and its components shall be installed in strict
compliance with Roofing Application Standard RAS 118, RAS 119, and RAS 120.
4.2 Data For Attachment Calculations
Table 1: Average Weight (W) and Dimensions (I x W)
Tile Profile
Weight -W (lbf)
Length-1(ft)
Width -w (ft)
Saxony 900
Slate, Shake & Split Shake
11.5
1.417
1.08
Table 2: Aerodynamic Multipliers - X (ft3)
Tile
;L (ft)
X (ft3)
Profile
Batten Application
Dire Deck Applicatio
Monierl-ifetile Saxony 900
0.289
0.313
Slate, Shake & Split Shake
Table 3: Restoring Moments due to Gravity - Mg (ft-lbf)
Tile
2":12"
3":12"
4"•12"
6"•12"
6"•12"
711•12" or
Profile
greater
Saxony
Battens
Direct
Battens
erect
B ttens
Direct
Battens
Direct
Battens
Direct
I
Battens
I
Direct
900
Deck
Deck
Deck
Deck
Deck
Deck
Slate,
7.16
8.12
7.08
8.03
.97
7.91
6.82
7.74
6.65
7.55
6.46
7.34
Shake &
Split
Shake
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 5 of 10
Table 4: Attachment Resistance Expressed as a Moment - Mf (ft-lbf)
for Nail -On Systems
Tile
Profile
Fastener Type
Direct Deck
(min 15/32"
plywood)
Direct Deck
(min. 19/32"
plywood)
Battens
Saxony 900
2-10d Ring Shank Nails
30.9
38.1
17.2
Slate, Shake & Split
Shake
1-10d Smooth or Screw Shank Nail
7.3
-9.8
4.9
2-10d Smooth or Screw Shank Nails
14.0
18.8
7.4
148 Screw
30.8
30.8
18.2
2 48 Screws
51.7
51.7
24.4
1-10d Smooth or Screw Shank Nail (Field
Clip)
24.3
24.3
24.2
1-10d Smooth or Screw Shank Nail (Eave
Clip)
19.0
19.0
22.1
2-10d Smooth or Screw Shank Nails (Field
Clip)
35.5
35.5
34.8
2-10d Smooth or Screw Shank Nails (Eave
Clip)
31.9
31.9
32.2
Table 5: Attachment Resistance Expressed as a Moment Mf (ft-lbf)
for Two Patty Adhesive Set Systems
Tile
Tile Application
Minimum Attachment
Profile
Profile
Resistance
MonierLifetile Saxony 900
Adhesive
31.3
Slate, Shake & Split Shake
Slate, Shake & Split Shake
1 See manufactures component approval for installation requirements.
2 Dow Chemical TileBond Average weight per patty 13.9 grams.
Polyfoam Product, Inc. Average weight per patty 8 grams.
Table 6:
Attachment Resistance Expressed as a Moment - Mf (ft-lbf)
for Single Patty Adhesive Set Systems
Tile
Profile
Tile
Tile Application Minimum Attachment
Resistance
MonierLifetile Saxony 900
Slate, Shake & Split Shake
Profile
Polyfoarn Pol ProTm 118.9
Pol oam Pol ProTm 40.4
3 Large paddy placement of 45 grams of Pol Pro TM.
4 Medium paddy placement of 24 grams of Pol ProTm.
Table 7: Attachment Resistance Expressed as a Moment - Mf(ft-lbf)
for Mortar Set Systems
Tile
Tile
Minimum Attachment
Profile
Application
Resistance
MonierLifetile Saxony 900
Mortar Set
43.9
Slate, Shake & Split Shake
5. Tile-Tite Roof Tile Mortar
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 6 of 10
OWNER'S AFFIDAVIT OF EXEMPTION
Roof to Wall Connection Hurricane Mitigation Retrofit for Existing Site -Built Single Family
Residential Structures
Pursuant to Section 553.844 F.S.
Date:
To:
Re: Owner's Name: %AWo
r
Property Address: C
Roofing Permit Number:
Dear Building Official:
I 0 certify that I am not required to retrofit the roof to wall connections of
my build' g because:
The just valuation for the structure for purposes of ad valorem taxation is less than $300,000.
The building was constructed in compliance with the provisions of the Florida Building Code (FBC) or with
the provisions of the 1994 edition of the South Florida Building Code (1994 SFBC)
Signature of Property Owner
Print Name
=o4Pm pp�t Nota Pub t: State
Dan' I Perez
STATE OF FLORIDA COUNTY OF MIAMI -DARE• my c mmisijen ge
apo 08/21/2016
Sworn to and, subsc 'bed befores
Day of 20,
_ Personally known
or Produced Identification
When the just valuation of the structure for the purposes of ad valorem taxation is equal to or more than $300,000,
and the building was not constructed in compliance with the FBC nor with the 1994 SFBC, and affidavit of Roof to
Wall Connection Hurricane Mitigation Retrofit must be provided.
SECTION 1524
HIGH -VELOCITY HURRICANE ZONES—
REQUIRED OWNERS NOTIFICATION FOR ROOFING CONSIDERATIONS
1524.1 Scope.
As k pertains to this section, it Is the responsibility of the roofing contractor to provide the owner with the
required roofing permit, and to explain to the owner the content of this section. The provisions of Chapter 15 of
the Florida Building Cdde, Building govern the minimum requirements and standards of the industry for roofing
system Installations. Additionally, the following items should be addressed as part of the agreement between
the owner and the contractor. The owner's Initial in the designated space Indicates that the item has been
explained.
1. Aesthetics -workmanship: The workmanship provisions of Chapter 15 (High -Velocity
Hurricane Zone) are f6r the purpose of providing that the roofing system meets the wind
resistance and water Intrusion performance standards. Aesthetics (appearance) are not a
consideration with respect to workmanship provisions. Aesthetic issues such as color or
architectural appearance, that are not part of a zoning code, should be addressed as part of the
agreement between the owner and the contractor.
2. Renailing wood decks: When replacing roofing, the existing wood roof deck may have to
be renailed in accordance with the current provisions of Chapter 16 (High -Velocity Hurricane
Zones) of the. (The roof deck is usually concealed prior to removing the existing roof system.)
3. Common roofs: Common roofs are those which have no visible delineation between
neighboring units (i.e., townhouses, condominiums, etc.). In buildings with common roofs, the
roofing contractor and/or owner should notify the occupants of adjacent units of roofing work to
be performed.
An:4. Exposed ceilings: Exposed, open beam ceilings are where the underside of the roof decking
can be viewed from below. The owner may wish to maintain the architectural appearance;
therefore, roofing nail penetrations of the underside -of the decking may not be acceptable. The
owner provides the option of maintaining this appearance.
19
5. Ponding water: The current roof system and/or deck of the building may not drain well and
may cause water to pond (accumulate) In low-lying areas of the roof. Ponding can be an
Indication of -structural distress and may require the review of a professional structural engineer.
Ponding may shorten the life expectancy and performance of the new roofing system. Ponding
conditions may not be evident until the original roofing system is removed. Ponding conditions
should be corrected.
6. Overflow scuppers (wall outlets): It is required that rainwater flow off so that the roof Is not
overloaded from a buildup of water. Perimeter/edge walls or other roof extensions may block
this discharge if overflow scuppers (wall outlets) are not provided. it may be necessary to install
overflow scuppers in accordance with the requirements of: Chapter 15 and 16 herein and the
jj�� Florida Building Code, Plumbing.
�`UIL 7. Ventilation: Most roof structures should have some ability to vent natural airflow through the
Interior of the structural assembly (the building itself). The existing amount of attic ventilation
shall not .be reduced. it may be beneficial to consider additional venting which can result in
extending the service life of the roof.
Owner's/Agent's Signature ate Contractor's Signature ate
CNT4
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) .,w.miamidade.aov/economy
3M Company
3M Center Building 0220-05-E-06
St. Paul, MN. 55144-1000
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER -Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product
or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is
determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: 3MTM 2 -Component Foam Roof Tile Adhesive AH -160
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA 12-0228.18 and consists of pages 1 through 11.
The submitted documentation was reviewed by Juan E. Collao, R.A.
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 1 of 11
ROOFING COMPONENT APPROVAL:
Category: Roofing
Sub Category: Roof tile adhesive
Materials: Polyurethane
SCOPE:
This approves 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 as manufactured by 3M Company as
described in Section 2 of this Notice of Acceptance. For the locations where the design pressure requirements, as
determined by applicable building code, does not exceed the design pressure values obtained by calculations in
compliance with Roofing Application Standard RAS 127, for use with approved flat, low, and high profile roof tiles
system using 2 -Component Foam Roof Tile Adhesive AH -160. Where the attachment calculations are done as a
moment based system for single patty placement, and as an uplift based system for double patty systems
PRODUCTS MANUFACTURED BY APPLICANT:
Product Dimensions Test Product Description
Specifications
3MTM 2 -Component Foam N/A TAS 101 Two component polyurethane foam adhesive
Roof Tile Adhesive AH -
160
Foam Dispenser RTF 1000 N/A Dispensing Equipment
ProPack® 30 & 100 N/A Dispensing Equipment
PRODUCTS MANUFACTURED BY OTHERS:
Any Miami -Dade County Product Control Accepted Roof Tile Assembly having a current NOA which list moment
resistance values with the use of 2 -Component Foam Roof Tile Adhesive AH -160 roof tile adhesive.
MANUFACTURING LOCATION:
1. Tomball, TX.
PHYSICAL PROPERTIES:
ProveProverty Test Results
Density ASTM D 1622 1.6 lbs./ft.3
Compressive Strength ASTM D 1621 18 PSI Parallel to rise
12 PSI Perpendicular to rise
Tensile Strength ASTM D 1623 28 PSI Parallel to rise
Water Absorption ASTM D 2127 0.08 Lbs./Fe
Moisture Vapor Transmission ASTM E 96 3.1 Perm / Inch
Dimensional Stability ASTM D 2126 +0.07% Volume Change @ -40'F., 2 weeks
+6.0% Volume Change @158°F., 100% Humidity, 2
weeks
Closed Cell Content ASTM D 2856 86%
Note: The physical properties listed above are presented as typical average values as determined by
accepted ASTM test methods and are subject to normal manufacturing variation.
NOA No.: 13-0502.02
MiaHttioaoecoExpiration Date: 05/10/17
Approval Date: 12/12/13
Page 2 of 11
EVIDENCE SUBMITTED:
Test Agency
Test Identifier
Test Name/Report
Date
Center for Applied Engineering
#94-060
TAS 101
04/08/94
257818 -IPA
TAS 101
12/16/96
Trinity Engineering
25-7438-3
SSTD 11-93
10/25/95
25-7438-4
ASTM D 1623
04/18/12
25-7438-7
SSTD 11-93
11/02/95
25-7492
SSTD 11-93
12/12/95
Miles Laboratories
NB -589-631
ASTM D 1623
02/01/94
Polymers Division
Ramtech Laboratories, Inc.
9637-92
ASTM E 108
04/30/93
Southwest Research Institute
01-6743-011
ASTM E 108
11/16/94
01-6739-062b[1]
ASTM E 84
01/16/95
Trinity Engineering
7050.02.96-1
TAS 114
03/14/96
P36700.04.12
ASTM D 1623
04/18/12
P39740.02.12
TAS 101
02/21/12
TAS 123
Celotex Corp. Testing Services 528454-2-1 TAS 101 10/23/98
528454-9-1
528454-10-1
520109-1 TAS 101 12/28/98
520109-2
520109-3
520109-6
520109-7
520191-1 TAS 101 03/02/99
520109-2-1
LIMITATIONS:
1. Fire classification is not part of this acceptance. Refer to the Prepared Roof Tile Assembly for fire rating.
2. All approved products listed herein shall be labeled and shall bear the imprint or identifiable marking of the
manufacturer's name or logo and following statement: "Miami -Dade County Product Control Approved" or the
Miami -Dade County Product Control Seal as shown below.
3. 3NC 2 -Component Foam Roof Tile Adhesive AH -160 shall solely be used with flat, low, & high tile profiles.
4. Minimum underlayment shall be in compliance with the Roofing Application Standard RAS 120.
5. Roof Tile manufactures acquiring acceptance for the use of 3M"m 2 -Component Foam Roof Tile Adhesive AH -
160 roof tile adhesive with their tile assemblies shall test in accordance with TAS 101.
6. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 9N-3 of the Florida Administrative Code.
NOA No.: 13-0502.02
MIAMIDADE COON r Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 3 of 11
INSTALLATION:
1. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 may be used with any roof tile assembly having a current
NOA that lists uplift resistance values with the use of 3MTM 2 -Component Foam Roof Tile Adhesive AH -160.
2. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall be applied in compliance with the Component
Application section and the corresponding Placement Details noted herein. The roof tile assembly's adhesive
attachment with the use of 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall provide sufficient
attachment resistance, expressed as an uplift based system, to meet or exceed the uplift resistance determined in
compliance with Miami -Dade County Roofing Application Standards RAS 127. The adhesive attachment data is
noted in the roof tile assembly NOA.
3. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 and its components shall be installed in accordance with
Roofing Application Standard RAS 120, and 3M Company's 3MTM 2 -Component Foam Roof Tile Adhesive AH -
160 Operating Instruction and Maintenance Booklet.
4. Installation must be by a Factory Trained'Qualified Applicator' approved and licensed by 3M Company. 3M
Company shall supply a list of approved applicators to the authority having jurisdiction.
5. Calibration of the Foam Dispenser RTF 1000 dispensing equipment is required before application of any adhesive.
The mix ratio between the "A" component and the "B" component shall be maintained between 1.0-1.15 (A): 1.0
(B).
6. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall be applied with Foam Dispenser RTF 1000 or
ProPack® 30 & 100 dispensing equipment only.
7. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 shall not be exposed permanently to sunlight.
S. Tiles must be adhered in freshly applied adhesive. Tile must be set within 1 to 2 minutes after 3MTM 2 -
Component Foam Roof Tile Adhesive AH -160 has been dispensed.
9. 3MTM 2 -Component Foam Roof Tile Adhesive AH -160 placement and minimum patty weight shall be in
accordance with the 'Placement Details' herein. Each generic tile profile requires the specific placement noted
herein.
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 4 of 11
Table 1: Adhesive Placement For Each Generic Tile Profile
Minimum Paddy Contact
Minimum Paddy Gram
Tile Profile
Placement Detail
Area
Weight
Eave Course - Flat, Low, High
All Eave Course
17-23 sq. inches
45-65
Profiles
Flat, Low, High Profiles
#1
17-23 sq. inches
45-65
Flat Profile
42
10-12 sq. inches
30
Low Profile
#2
12-14 sq. inches
30
High Profile
#2
17-19 sq. inches
30
Flat, Low, High Profiles
43
Two Paddys: 8-9 sq. inches at
12 grams per paddy
head of tile 9-11 sq. inches at
overlap
Two -Piece Barrel (Cap Tile)
Two Piece
2 Beads (1 each longitudinal
17 grams per bead
edge) 20-25 sq. inches each
bead
Two Piece Barrel (Pan Tile)
Two Piece
65-70 sq. inches
34 grams under pan
LABELING:
All 3M'm 2 -Component Foam Roof Tile Adhesive AH -160 containers shall comply with the Standard Conditions listed
herein.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or applicable building code in order to properly evaluate the installation of this
system.
NOA No.: 13-0502.02
MIAMI•DADE COUNTY Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 5 of 11
ADHESIVE PLACEMENT DETAIL # 1
Nail through plastic cement Paddy (Beneath Tile)
(when required)
Underlayment
10 tn.
Battensoptlonal °
Eave Course
loin }
Fascia
2
Eave Closure
Nall through plastic cement
(when required)
Paddy (Beneath Tile)
Underlayment
101
21n.wide
,
Battens optional
loin. ��`- 21n.
Eave Closure
Eave Course
Fascia
Nall through plastic ce
(when required) Paddy (Beneath Tile)
IUnderlayment
10In x
2 in.wide \
Battens
optional rr
Eave Course Fascia
Weephole
Eave dosure
tO tm �2 hi. Drip edge
Flat/Low Profile Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown,
under the strengthening rib closest to the overlock
of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.
Medium Profile / Double Pan Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown
under the pan portion of the tile closest to the
overlock of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.
High Profile / Single Pan Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown
under the pan portion of the file closest to the
overlock of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm) — 23 (148.4 cm) square inch adhesive
contact with the underside of the tile.
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 6 of 11
ADHESIVE PLACEMENT DETAIL # 2
Nail through plastic cement Paddy (Beneath Tile)
(when required)
Underlayment
I�
It 71n �'
Battens optional
Eave Course
10(n.`~ asda
a in
Eave Closure
Nail through plastic cement
(when required)
Paddy (Beneath Tile)
Underlayment
a_
7 in.
�2 i n.
Battensoptional
ion. ``�� �'
2in
Eave Closure
Eave Course
Fascia
Flat/Low Profile Tile
1. Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
strengthening rib of the tile closest to the overlock of
the tile being set. Insure approximately 17 (109.7 cm)
— 23 (148.4 cm2) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 mm) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the
strengthening rib closest to the overlock of the tile
being set.
3. Continue in same manner. Insure approximately 10"
(64.5 cm2) - 12 (77.4 cm) square inch adhesive
contact with the underside of the tile.
Medium Profile / Double Pan Tile
1. Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
pan portion of the tile closest to the overlock of the
tile being set. Insure approximately 17 (109.7 cm) —
23 (148.4 cm) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 mm) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the pan
portion of the tile closest to the overlock of the tile
being set.
3. Continue in same manner. Insure approximately 12"
(77.4 cm2) - 14 (90.3 cm) square inch adhesive
contact with the underside of the tile.
(Instructions continued on next page)
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 7 of 11
ADHESIVE PLACEMENT DETAIL # 2 (CONTINUED)
Nail through plasticce
(when required)
Fadd (Beneath Tile)
Y
Underlayment
C2,
7 in.
tin.
2
Battens optional ,
a:
Eave Course
Fascia
Weephole
t0 in.Z in.
Eave closure
Drip edge
�l
APPROVED
High Profile / Single Pan Tile
1. Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
pan portion of the tile closest to the overlock of the
tile being set. Insure approximately 17 (109.7 cm2) —
23 (148.4 cm2) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 mm) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the pan
portion of the tile closest to the overlock of the tile
being set.
3. Continue in same manner. Insure approximately 17"
(109.7 cm2) - 19 (122.6 cm) square inch adhesive
contact with the underside of the tile.
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 8 of 11
ADHESIVE PLACEMENT DETAIL # 3
NuffluaughpNOccement pedtdg tsed
WhenrequiredI
Battens al a
// 6 t�addg(Under ULQ
r, F�
gqpe
i
Gntopdiffie
S
4s4fiw
er
gle paddy
an ��lerlaylaenrt `�` 3 x 41ow < �
1S ,M1i
f4ln
Rat/Low Profile Tile
NaBthroughplasticcement %gle paddy under tie
(when uquired)
padt9y (bet Ceti
Battens pad Wdertilel
optlanal o
Y 3
shwepad
an top e
5,addyan �.�.
q 4.y,. Y h qk �• -
to26n.
Lwe ®asure
Evre come-lasda
Medium PraflleTile
1. On the eave course only, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown, under
the strengthening rib for flat tile or under the pan
portion of the tile for low or high profile tile closest
to the Overlock of the tile being set. Leave
approximately 4" (10 1.6 mm) up from the eave
edge free of foam to prevent the expanded adhesive
from blocking the weep holes. Insure
approximately 17-23 int (109.7-148.4 cmZ) of
adhesive contact with the underside of the tile
2. Apply a 4" (101.6 mm) x 4" (101.6 mm) x 1" (25.4
mm) foam paddy onto the underlayment just below
the second course line positioned foam paddy
under the strengthening rib for flat tile, or under the
pan portion of the tile, closest to the underlock for
the second course tile to be installed. Insure
approximately 8-9 int (51.6-58.1 cm2) of adhesive
contact with the underside of the tile.
(Instructions continued on next page)
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 9 of 11
ADHESIVE PLACEMENT DETAIL # 3 (CONTINUED)
Wthmugh phmdc Sire paddy rLnder ft
$wehenrespdredi
Pasty dlesl
Omens M#(undertilef
eonI
4l
-sd➢n.
Single zz 11n.
a4 'aP
d# an
top of toe W Rh
R
Ewe Course
Weephsde
10In. tin. Eavedosure
Qdp edge
High pratl'Ee T1t0
3. Also apply a 2" (50.8 mm) x 411(101.6 nun) x 3/4"
(19 mm) paddy on top of the eave course tile
surface as shown, on top of the strengthening rib
for flat tile or on top of the pan portion of the tile,
closest to the underlock of the first course of tile.
Install second course of tile. Insure approximately
9 (58.1 cm2) - 11 (71cm2) square inch adhesive
contact with the underside of the tile at the overlap
and 7 (45.2 cm) - 9 (58.1 cm2) square inch
adhesive contact with the underside of the tile at
the head of the tile. Continue in same manner.
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 10 of 11
1) Place enough adhesive to achieve 65 to 70 sq.
In contact with the pan tile.
2) Tum covers upside down. Place adhesive in
to 1 In. from outside edge of covertile.
Then install the tile. Ensure 20to
Underlayment
(motar shown)
fascia
ADHESIVE PLACEMENT DETAIL
TWO PIECE BARREL
Steep pitch applications
(when required)
point -up Mortar
on longitudinal
edges of the
Remove top portion of the eave course cover tile.Abut to second course of
pan tiles. Ensure eave end of pan and cover tiles are flush at eave line.
Two Piece Barrel - High Profile Tile
Two Piece Barrel (Cap and Pan) Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown
under two adjacent pan tiles. Support eave tiles
from rocking until adhesive has a chance to cure.
2. Continue in same manner bringing two pan courses
up toward the ridge. Insure approximately 65
(419.4 cm) — 70 (451.6 cm2) square inch adhesive
contact with the underside of the pan tile.
3. Turn covers upside down exposing the underside of
the tile. Apply a minimum 1" (25.4 mm) x 10" (254
mm) bead of adhesive directly on the inner edge of
each side of the cover tile. Leave approximately
3/4" (19 mm) to 1" (25.4 mm) from the outside
edge of the tile, inward, free of foam to allow for
expansion.
4. Turn cover tile over after foam is applied and place
onto pan tile course. Insure a minimum of 20 (129
cm2) - 25 (161.3 cm2) square inch contact area on
each side of the cover tile to the pan tile. Continue
in same manner. Trim away any cured exposed
foam adhesive. Pointing of longitudinal edges of
the cover tiles are considered optional.
5. When additional nailing is required, 2" (50.8 mm)
x 4" (101.6 mm) nailers or the tie wire system
using galvanized, stainless steel, or copper wire and
compatible nails may be used.
END OF THIS ACCEPTANCE
NOA No.: 13-0502.02
Expiration Date: 05/10/17
Approval Date: 12/12/13
Page 11 of 11
M1W
r MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
Boral Roofing, LLC
7575 Irvine Center Drive, Suite 100
Irvine, CA 92618
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Saxony 900 Concrete Roof Tile
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration
date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA No. 12-0222.03 and consists of pages 1 through 10.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 1 of 10
ROOFING ASSEMBLY APPROVAL
Cateeory
Roofing
Sub -Category:
Roofing Tiles
Material:
Concrete
Deck Type:
Wood
1. SCOPE
This NOA approves a system using Saxony 900 (Slate, Shake & Split Shake) Concrete Roof Tile, as
manufactured Boral Roofing LLC in Lake Wales, FL. and described this Notice of Acceptance. For locations
where the pressure requirements, as determined by applicable Building Code does not exceed the design pressure
values obtained by calculations in compliance with RAS 127 using the values listed in the installation section
herein. The attachment calculations shall be done as a moment based system.
2. PRODUCT DESCRIPTION
Manufactured by
Test
Product
Applicant
Dimensions
Specifications
Description
Saxony 900 -Slate
1= 17"
TAS 112
Flat profile, interlocking, high-pressure
w = 13"
extruded concrete roof tile equipped with
thickness = 1-5/32"
two nail holes. For direct deck or battened
nail -on, mortar set or adhesive set
applications.
Saxony 900 -Split
1= 17"
TAS 112
Flat profile, interlocking, high-pressure
Shake
w = 13"
extruded concrete roof tile equipped with
thickness = 1-9/32"
two nail holes. For direct deck or battened
nail -on, mortar set or adhesive set
applications. Top surface available in 4
different configurations:
1. Complete tile brushed
2. Right half brushed (shown in
drawing)
3. Left half brushed
4. No brush
Saxony 900 -Shake
1= 17"
TAS 112
Flat profile, interlocking, high-pressure
w = 13"
extruded concrete roof tile equipped with
thickness =1-9/32"
two nail holes. For direct deck or battened
nail -on, mortar set or adhesive set
applications.
Trim Pieces
Length: varies
TAS -112
Accessory trim, boosted Barcelona, concrete
Width: varies
roof pieces for use at hips, rakes, ridges and
varying thickness
valley terminations manufactured for each
tile profile.
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 2 of 10
2.1 MANUFACTURING LOCATION
2.1.1 Lake Wales, FL.
2.2 EVIDENCE SUBMITTED:
Test Agency Test Identifier
Redland Technologies 7161-03
Appendix III
The Center for Applied 94-084
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
Redland Technologies
Redland Technologies
Redland Technologies
Redland Technologies
The Center for Applied
Engineering, Inc.
Atlanta Testing &
Engineering, Inc.
Celotex Corporation
Testing Service
Celotex Corporation
Testing Service
MIAMMADE COUNTY
94-060A
25-7183-6
25-7183-5
25-7214-1
25-7214-5
7161-03
Appendix H
Letter Dated Aug. 1, 1994
P0631-01
P0402
Project No. 307025
Test #MDC -77
R1.894
R2.894
R3.894
520109-1
520111-4
520191-1
Test Name/Report
Date
Static Uplift Testing
Dec. 1991
TAS 102 & TAS 102(A)
Static Uplift Testing
May 1994
TAS 101 (Mortar Set)
Static Uplift Testing
March, 1994
TAS 101 (Adhesive Set)
Static Uplift Testing
Feb. 1995
TAS 102
(2 Quik -Drive Screws,
Direct Deck)
Static Uplift Testing
Feb. 1995
TAS 102
(2 Quik -Drive Screws,
Battens)
Static Uplift Testing
March, 1995
TAS 102
(1 Quik -Drive Screw,
Direct Deck)
Static Uplift Testing
March, 1995
TAS 102
(1 Quik -Drive Screw,
Battens)
Wind Tunnel Testing
Dec. 1991
TAS 108 (Nail -On)
Wind Tunnel Testing
Aug. 1994
TAS 108 (Nail -On)
Wind Tunnel Testing
July 1994
TAS 108 (Mortar Set)
Withdrawal Resistance
Sept. 1993
Testing of screw vs. smooth
shank nails
Wind Driven Rain
Oct. 1994
TAS 100
Physical Properties
Aug. 1994
TAS 112
Static Uplift Testing Dec. 1998
TAS 101
Static Uplift Testing March 1999
TAS 101
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 3 of 10
Walker Engineering, Inc. Evaluation Calculations
25-7094 February 1996
Walker Engineering, Inc. Evaluation Calculations
25-7496 April 1996
Walker Engineering, Inc. Evaluation Calculations
25-7584 December 1996
25-7804b-8
25-7804-4 & 5
25-7848-6
Walker Engineering, Inc. Evaluation Calculations
25-7183 March 1995
Walker Engineering, Inc. Evaluation Calculations
Aerodynamic Multipliers January 2007
Walker Engineering, Inc. Calculations
Two Patty Adhesive Set April 1999
System
Walker Engineering, Inc. Evaluation Calculations
Restoring Moments Due to February 2007
Gravity
Nutting Engineers 130
TAS 112 January 2007
3. LIMITATIONS
3.1 Fire classification is not part of this acceptance.
3.2 For mortar or adhesive set file applications, a static field uplift test shall be performed in accordance with
TAS 106.
3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform quarterly test
in accordance with TAS 112, appendix `A'.
Such testing shall be submitted to the Building Code
Compliance Office for review.
3.4 Minimum underlayments shall be in compliance
with the applicable Roofing Applications Standards listed
section 4.1 herein.
3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated
otherwise by the underlayment material manufacturers published literature.
3.6 This acceptance is for wood deck applications.
Minimum deck requirements shall be in compliance with
the applicable Building Code.
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 4 of 10
5. LABELING
5.1 All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo as detailed
below, or following statement: "Miami -Dade County Product Control Approved".
LABEL FOR SAXONY 900 TILES (LAKE WALES FL PLANT)
LOCATED UNDERNEATH TILE
6. BUILDING PERMIT REQUIREMENTS
6.1 Application for building permit shall be accompanied by copies of the following:
6.1.1 This Notice of Acceptance.
6.1.2 Any other documents required by the Building Official or applicable building code in order to
properly evaluate the installation of this system.
MAMI-RADE COUNTY
�KI...•
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 7 of 10
NAIL HOLES
W
UNDERLOCK
SAXONY 900 - SLATE
5/32 " (Slate)
COVERLOCK
NOA No.: 13-0723.05
Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 8 of 10
,/ I
NAIL HOLES
1-9/32 " (Shake)
Note: Available Top Surface Finishes
S. Complete tile brushed
6. Right half brushed (shown in drawing)
7. Left half brushed
8. No brush
SAXONY 900 - SPLIT SHAKE
NOA No.: 13-0723.05
CMILAMMMADEWCONTT Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 9 of 10
NAIL HOLES
R
SAXONY 900- SHAKE
END OF TRIS ACCEPTANCE
7
1-9/32 " (Shake)
NOA No.: 13-0723.05
IMOD ��� Expiration Date: 04/26/17
Approval Date: 09/26/13
Page 10 of 10
MIANII-DARE COUNTY
MIAMN ADE PRODUCT CONTROL SECTION
® 11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
GAF
1361 Alps Road
Wayne, NJ 07470
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER -Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: UnderRoofrm 2
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA No. 11-1027.06 consists of pages 1 through 4.
The submitted documentation was reviewed by Juan E. Collao, R.A.
APPROVED
NOA No.: 13-1104.05
Expiration Date: 09/21/16
Approval Date: 02/20/14
Page 1 of 4
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub -Category: Underlayment
Material: Rubberized Asphalt
PRODUCT DESCRIPTION:
Manufactured by
Test
Product
Applicant Dimensions Specifications
Description
UnderRoofrM 2 39 %" x 67.8'
rolls TAS 103
Self -adhering reinforced membrane of rubberized
ASTM D 1970
asphalt with a polyester surfacing for use as an
underlayment in sloped tile and asphalt shingle roof
assemblies. Roof slopes of 2:12 —12:12 are
acceptable as indicated by local codes and
manufacturer's installation instructions.
MANUFACTURING LOCATION:
1. Fresno, CA
EVIDENCE SUBMITTED:
Test Agency
Test Identifier
Test Name/Report Date
Intertek Testing Services NA Ltd.
3077464-01
ASTM D 1970 08/23/06
3077464-02
TAS 103 08/23/06
3090131
ASTM D 1970/TAS 103 08/23/06
PRI Construction Materials
RGM-023-02-01
ASTM D 4798/TAS 103 05/16/07
Technologies
LIMITATIONS:
1. Fire classification is not part of this acceptance. Refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. This acceptance is for prepared roofing applications. Minimum deck requirements shall be in compliance with
applicable building code. UnderRoofrM 2 shall be installed in strict compliance with applicable Building Code.
3. UnderRoofrM 2 may be used in roof tile and asphalt shingle assemblies.
4. UnderRoofrM 2 shall be applied to a smooth, clean and dry surface with deck free of irregularities.
5. UnderRoofrM 2 shall not be applied over an existing roof membrane as a recover system but may be applied to
underlayment base sheets as listed in this approval.
6. UnderRoofrM 2 shall not be left exposed as a temporary roof for longer than 180 days after application.
7. Refer to Prepared Roofing system Product Control Notice of Acceptance for listed approval of this product with
specific prepared roofing products.
8. UnderRoofrM 2 may be used with any approved roof covering Notice of Acceptance listing UnderRoofrM 2 as a
component part of an assembly in the Notice of Acceptance. If UnderRoofrM 2 is not listed; a request may be
made to the Authority Having Jurisdiction (AHJ) or the Miami -Dade County Product Control Department for
approval provided that appropriate documentation is provided to detail compatibility of the products, wind uplift
resistance, and fire testing results.
9. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
NOA No.: 13-1104.05
MIAMI -DADS COUNTY Expiration Date: 09/21/16
Approval Date: 02/20/14
Page 2 of 4
.4 + I It
APPROVED ASSEMBLIES:
Deck Type 1: Wood, Non -insulated
Deck Description: 19/32' or greater plywood or wood plank
System E(1): Anchor sheet mechanically fastened to deck, membrane adhered.
Base Sheet: One or more plies of ASTM D 226 Type II or ASTM D 2626 compliant underlayments with a
minimum 4" side lap and a 6" end lap mechanically fastened to deck with approved nails and tin
caps 6" o.c. at the laps and two staggered rows 12" o.c. the field of the roll.
Membrane:
• Begin at lowest point on roof deck. Peel back the release film and align the membrane on the lower edge of
roof; pull the release film to peel back and apply membrane.
• Roll lower edges and seams with a hand roller. Use flat broom, squeegee or weighted roller to help lay flat and
ensure full adhesion of UnderRoofrM 2 to the anchor sheet.
• Where back nailing is required for steep slope applications, back nail and cover nails by overlapping with the
next sheet. Use acceptable fasteners such as approved nails and tin caps. Plastic caps are not acceptable.
Contact GAF technical services for other approved fasteners.
• Valley and Ridge applications: Begin at lowest point on valley or ridge, peel back the release film, center the
sheet over the valley or ridge and press firmly into place.
• End Laps must be a minimum 6" and Side Laps must be a minimum 4" in and properly aligned with the
existing selvedge edge.
• Install when temperatures are 45° F and rising, over clean, dry and smooth substrate.
• Flash vent pipes, stacks, chimneys and penetrations in compliance with Roof Assembly current product control
Notice of Acceptance and applicable building code.
• Roll or broom the entire membrane surface so as to have full contact with the surface, giving special attention
to the lap areas.
• UnderRoofrM 2 shall not be exposed for longer than 180 days after application. GAF reserves the right to
revise or alter the exposure time, not to exceed the preceding maximum exposure time.
• Wherever the adhesive back comes in contact with polyester surfacing such as end laps, penetrations and
flashing material must be set in a 1/8 inch toweling of LeakBusterTM Matrix® 201 Premium SBS Flashing
Cement made in accordance with ASTM D4586 - Type 1 or equal flashing cement.
• UnderRoofrM 2 is acceptable in foam applied and mechanically attached tile systems
• Consult manufacturer's installation instructions for complete installation requirements.
Surfacing: Roof Tile and Asphalt Shingle Assemblies.
NOA No.: 13-1104.05
Expiration Date: 09/21/16
Approval Date: 02/20/14
Page 3 of 4
J p c 10
LABELING:
All membranes or packaging shall bear the imprint or.identifiable marking of the manufacturer's name or logo, city and
state of manufacturing facility, and the following statement: "Miami -Dade County Product Control Approved" or the
Miami -Dade County Product Control Seal as shown below.
MIAMI-DADE COUNTY
W • • 1
BUILDING PERMIT REQUIREMENTS:
Application for building permit shall be accompanied by copies of the following:
I. This Notice of Acceptance.
2. Any other documents required by Building Official or Applicable building code in order to properly evaluate the
installation of this material.
ENI) OF THIS ACCEPTANCE
NOA No.: 13-1104.05
MIAMI -DAD, COUNTY Expiration Date: 09/21/16
Approval Date: 02/20/14
Page 4 of 4
APR 03
High Velocity Hufricone Zone Uniform Permit Application Form
Section Q (Low Stoped Roof System)
Fill In Specific Roof Assembly Components
and Identify Manufacturer
(If a component is not used, identify as *NA")
System Manufacturer. 01M .
NOA No.' Zm t`� 6 Q !2 7^
Design Wind Pressures, From RAS 128 or Calculations:
Pmaxl:� Pmax2: _ Pmax3: W
Max. Design Pressure, From the Specific NOA
System: H
Deck: Type: o'by,yj4W' 'OA
Gaugefrhickness•,
10
Slope:
AnchorlBase Sheet & No. of Ply(s): S V ��
i
Anchor/ as Shet FW nerBondin enal:
d
Insulation Base Layer. A
y
Base insulation Size and Thickness:�, i PS
Base Insulation Fastener/Bonding Materia�I; , Vgl Tem',
Top Insulation Layer. j�! r FT.
t
Top Insulation Size and Thickness: D �-(ee�apA Parapet
Top Insulation Fastener/Banding Material: QAgv% �. Heioht
Base Sheet(s) & No. of Ply(s): D °
FT.
Base Sheet Fastener/Bonding MaterlaI:,jkj
filc� Mean
A' Roof
Ply Sheet(s) & No. of Ply(s): Nib '1 Height
Ply Sheet Fastener/Bonding Material:0����
Top Ply: e i ' titt�
M-j
Top Ply Fastener/ Bonding Material: 1lfi(-
Fastener Spacing for Anchor/Base Sheet
Attachment
Field:, oc@ Lap, # Rows 1 @!- oc
Perimeter. 6 ` oc @ Lap, # Rows @ f✓ " oc
Comer: • ; oc @ Lap, # Rows A @ ° oc
Number of Fasteners Per Insulation
Board q
Field Perimeter' Corner
Illustrate Components Noted and
Details as Applicable:
Woodblocking, Gutter, Edge Termination,
Stripping, Flashing, Continuous Cleat, Cant
Strip, Base Flashing, Counter- Flashing,
Coping, Etc.
Indicate: Mean Roof Height, Parapet Height,
Height of Base Flashing, Component Material,
Material Thickness, Fastener Type, Fastener
Spacing or Submit Manufacturers Details that
Comply with RAS 111 and Chapter 16.
Surfacing: �1 1
u:\B & G Pormsacioting mctcenrootmg pacicet completextoci/ //2U12
MIAIJU ADE MIAMI -DARE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.eov/economv
GAF
1361 Alps Road
Wayne, NJ 07470
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction
materials. The documentation submitted has been reviewed and accepted by Miami -Dade County RER -
Product Control Section to be used in Miami Dade County and other areas where allowed by the
Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County
Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade
County) reserve the right to have this product or material tested for quality assurance purposes. If
this product or material fails to perform in the accepted manner, the manufacturer will incur the
expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such
product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it
is determined by Miami -Dade County Product Control Section that this product or material fails to
meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building
Code including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: GAF EverGuard® FreedomTM TPO with RapidSeamTM Technology Single Ply
Roofing System over Wood Decks.
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state
and following statement: "Miami -Dade County Product Control Approved", unless otherwise noted
herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has
been no change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or
change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an
endorsement of any product, for sales, advertising or any other purposes shall automatically terminate
this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of
NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and
followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is
displayed, then it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA No. 09-0506.03 and consists of pages 1 through 9.
The submitted documentation was reviewed by Juan E. Collao, R.A.
G,QPao-'
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Approval Date: 08/01/13
Page 1 of 9
t f
•
ROOFING SYSTEM APPROVAL
Category
Roofing
Sub -Category:
Single Ply Roofing
Material:
TPO
Deck Tvoe•
Wood
Maximum Design Pressure
-105 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
TABLE I
Test
Product
Product
Dimensions
Specification
Description
EverGuare FreedomTM TPO
Various
ASTM D 6878
Self -Adhered thermoplastic olefin
with RapidSeamTM Technology
reinforced membrane.
EverGuare FreedomTM TPO
Various
ASTM D 6878
Self -Adhered thermoplastic olefin
HW
reinforced membrane.
EverGuare TPO-45 Utility
Various
ASTM D 6878
Thermoplastic olefin reinforced
Flashing Strips
flashing membrane.
EverGuare UN -55 Detailing
Various
ASTM D 6878
Thermoplastic olefin reinforced
Membrane
flashing membrane.
EverGuare Coated Metal
4' x 10' sheets
US CS -245-62
TPO membrane laminated 25 Ga.
Sheets
galvanized sheet metal.
EverGuare TPO Preformed
4" x 4" x 4"
ASTM D 6878
Prefabricated molded one piece
Corners
20 pcs. Crtn.
corners.
EverGuare TPO Preformed
1" - 8" o.d.
ASTM D 6878
Pre molded vent pipe boots.
Vent Boots
6 pcs. Crtn.
EverGuare Cut Edge Sealant
1 quart
Proprietary
Solvent based sealant for TPO cut
squeezetube
edges.
EverGuard® Preformed
4"-8" x 50'
Proprietary
Low profile expansion joint cover.
Expansion Joint Cover
EverGuare Walkway Pads &
Pads
Proprietary
Standard duty walkway pads & rolls.
Rolls
1/8"x301106"
Rolls
1/8"x30"x50'
EverGuardo UN -55 Detailing
Various
ASTM D 6878
55 mil un -reinforced flashing
Membrane
membrane.
EverGuarda TPO Cover Tape
6" x 100' roll
.045" TPO membrane laminated to
white butyl tape.
EverGuare Preformed Split
Various
Split boots to accommodate most
Pipe Boot
pipes and conduits.
NOA No.: 13-0603.02
Expiration Date: 09/15/14
MIAMFDAINIFINDECO TY Approval Date: 08/01/13
Page 2 of 9
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Mu►r�NLecounmr Approval Date: 08/01/13
Page 3 of 9
Test
Product
Product
Dimensions
Specification
Description
EverGuare RTA Strip
6" x 100' roll
Reinforced TPO membrane with
pressure sensitive adhesive.
EverGuare Corner Curb Wrap
Various
Flash curbs
EverGuard® Self -Adhering
30 per carton
TPO Standing seam Batten Strips
Standing Seam
10' length
adhered to EverGuare TPO
membrane to simulate the appearance
of a metal standing seam roof.
Freedom 5'-0" Duel HW (Heat
5' x 50'
.060" thick TPO reinforced membrane
weld) Flashing
EverGuard® TPO Fluted Corner
8" diameter
Flashing outside corners of base and
nominal .05"
curb flashing.
non -reinforced
EverGuare Square Tube Wrap
Various
Square tube wrap
EverGuard® Inside Corner
6" x 6" x 5'/a"
Inside corners of base and curb
flashings.
EverGuare Pourable Sealer
9" x 6" x 4"
Pourable sealer.
Pocket
oval with 3"
base flange
EverGuare Drain
Various
Spun aluminum drain preflashed with
55 mil unreinforced TPO membrane.
EverGuard® Scupper
4" x 6" x 12"
TPO coated metal 55 mil
8" x 10" x 12"
unreinforced membrane
EverGuard® Vent
Vent manufactured out of reinforced
45 mil TPO membrane and
galvanized steel.
Storm SafeTM
40" wide
Proprietary
Synthetic Underlayment
FireOutTM Fire Barrier Coating
N/A
N/A
Low VOC, water-based coating
system that provides outstanding
flame spread and penetration to
combustible roof decks in the event of
fire.
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Mu►r�NLecounmr Approval Date: 08/01/13
Page 3 of 9
s
APPROVED INSULATIONS:
TABLE 2
Product Name
Product Description
Manufacturer
(With Current NOA)
EnergyGuardTM PolyIso, RA, RN,
Polyisocyanurate foam insulation
GAF
Ultra
EnergyGuardTM Perlite
Perlite insulation board.
GAF
EnergyGuardTM Composite, RA, RN
Polyisocyanurate foam insulation
with GAF
high density fiberboard or perlite
insulation.
Dens Deck®, Dens Deck PrimeTM
Water-resistant gypsum board
G -P Gypsum Corp.
StructodeO TD
Flame Resistant High Density Wood Knight-Celotex
Fiber board.
StructodeO
Insulation board
Knight-Celotex
SECUROCK®
various
G -P Gypsum
APPROVED FASTENERS:
TABLE 3
Fastener Product
Product
Manufacturer
Number Name
Description
Dimensions (With Current
NOA)
1. Drill-TecTM # 12 Standard
Insulation fastener for steel,
various GAF
& #14 HD Roofing
wood & concrete decks.
Fasteners
2. Drill-TecTM ASAP
Pre -assembled fasteners and
various GAF
metal and plastic plates.
3. Drill-TecTM Plastic
Round Polypropylene plate.
Plate Diameter: GAF
Polypropylene Plates
3" & 3-%2"
4. Drill-TecTM Metal
Round galvalume plate.
Plate Diameter: GAF
Insulation Plates
3" & 3-1/219
5. Annular Ring Shank Nails
Galvanized steel roofing nails
Nail: Various Others
& Tin Caps
with tin caps.
lengths (Dade County
Tin Caps: 1" Approved)
6. OlyBond500TM &
Dual component adhesive
N/A Olympic Mfg.
OlyBond Adhesive
fastener
Group, Inc.
Fastener
EVIDENCE SUBMITTED:
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Approval Date: 08/01/13
Page 4 of 9
Test AffenevAdentifier
Underwriters Laboratory, Inc.
Factory Mutual Research Corp.
IRT-ARCON
Exterior Research and Design, LLC
Name
Report
Date
UL 790
03CA38009
01/21/04
FM 4470
3139QLAM
01/08/98
FM 4470
3020588
03/24/04
TAS 114
02-005
01/18/01
TAS 114
04-025
07/13/04
TAS 114
02762.03.05
03/20/05
TAS 114
01515.02.06
02/8/06
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Approval Date: 08/01/13
Page 5 of 9
C., a
Deck Type 1I: Wood, Non -Insulated
Deck Description: Minimum 19/32' plywood to supports max. 24" o.c. with # 10 wood screws max.
6" o.c.
System Type E: (Optional) FireOutTM Fire Barrier Coating over the deck. Underlayment is
mechanically attached to the deck. Membrane fully or partially adhered to the
underlayment.
Underlayment: Storm SafeTM is mechanically fastened to deck as described below;
Fastening
Options: Underlayment is attached to the deck with FBC HVHZ tin -caps and nails at 9" o.c.
in the 4" laps and 9" o.c. in two staggered rows in the field.
(Maximum Design Pressure -45 psf, see General Limitation # 7)
Underlayment is attached to the deck with Drill-TecTM # 12 Fastener & 3" Plates
Spaced at 8" o.c. in the 4" laps and 8" o.c. in three staggered rows in the field.
(Maximum Design Pressure -105 psf, see General Limitation # 7)
Membrane: EverGuarde FreedomTM TPO with RapidSeamTM Technology 45, 60, 80 mil
adhered to insulation with a minimum 6" side lap fully self -adhered
or
EverGuard® FreedomTM TPO HW 45, 60, 80 mil (self -adhered) with a minimum 3"
side lap heat welded with a minimum 1.75" weld.
Surfacing:
(Optional)
1. Advanced Green Technologies Photovoltaic Laminate solar energy collector
auxiliary roof equipment installed in compliance with manufacturer's specifications
and applicable Building Codes.
2. EverGuare self -adhering Standing Seam Architectural Profiles installed in
compliance with manufacturer's specifications and applicable Building Codes.
3. TOPCOAT® Surface Seal, TOPCOAT® Fireshiele SB Solvent based
Elastomeric Roofing Membrane applied at Ito 1.5 gal./sq.
Maximum Design
Pressure: See fastening options above.
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Approval Date: 08/01/13
Page 8 of 9
•
WOOD DECK SYSTEM UmnATIONS:
1 A slip sheet is required with Ply 4 and Ply 6 when used as a mechanically fastened base or anchor
sheet.
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials
Directory for fire ratings of this product.
2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with
Product Control Approval guidelines. All other layers shall be adhered in a full mopping of
approved asphalt applied within the EVT range and at a rate of 20401bs./sq., or mechanically
attached using the fastening pattern of the top layer
3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved
asphalt, panel size shall be 4'x 4' maximum.
4. An overlay and/or recovery board insulation panel is required on all applications over closed cell
foam insulations when the base sheet is fully mopped. If no recovery board is used the base sheet
shall be applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip
mopped 8" ribbons in three rows, one at each side lap and one down the center of the sheet
allowing a continuous area of ventilation. Encircling of the strips is not acceptable. A 6" break
shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt application of either
system shall be at a minimum rate of 12 lbs./sq.
Note: Spot attached systems shall be limited to a maximum design pressure of -45 psf.
5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force (F') value of
275 lbf., as tested in compliance with Testing Application Standard TAS 105. If the fastener value,
as field-tested, are below 275 lbf. insulation attachment shall not be acceptable.
6. Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based
on a minimum fastener resistance value in conjunction with the maximum design value listed
within a specific system. Should the fastener resistance be less than that required, as determined by
the Building Official, a revised fastener spacing, prepared, signed and sealed by a Florida
Registered Engineer, Architect, or Registered Roof Consultant may be submitted. Said revised
fastener spacing shall utilize the withdrawal resistance value taken from Testing Application
Standards TAS 105 and calculations in compliance with Roofing Application Standard RAS 117.
7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these
areas. Fastener densities shall be increased for both insulation and base sheet as calculated in
compliance with Roofing Application Standard RAS 117 and/or RAS 137. Calculations prepared,
signed and sealed by a Florida registered Professional Engineer, Registered Architect, or Registered
Roof Consultant (When this limitation is specifically referred within this NOA, General
Limitation #9 will not be applicable.)
8. All attachment and sizing of perimeter nailers, metal profile, and/or flashing termination designs
shall conform to Roofing Application Standard RAS 111 and applicable wind load requirements.
9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e.
field, perimeters, and corners). Neither rational analysis, nor extrapolation shall be permitted for
enhanced fastening at enhanced pressure zones (i.e. perimeters, extended corners and corners).
(When this limitation is specifically referred within this NOA, General Limitation #7 will not
be applicable.)
10. All products listed herein shall have a quality assurance audit in accordance with the Florida
Building Code and Rule 9N-3 of the Florida Administrative Code.
END OF THIS ACCEPTANCE
NOA No.: 13-0603.02
Expiration Date: 09/15/14
Approval Date: 08/01/13
Page 9 of 9
. 'tGa13 06 - Roofing Systems
Membrane: — Two or more plies "Ruberoid@ 20" or "Ruberold@ 20 HT" or three or more plies Type G1 "GAFGLAS@" Ply 60, fully
adhered with hot roofing asphalt
'44arnkrane: — "EverGuard@ TPO FB Ultra" 45 -mil to 80-rntl or "EverGuard@ Extreme"" TPO FB Ultra" 50 -mil to 80 -mil, fully
adherdd with hot roofing asphalt or mechanically fastened or adhered- with "LRF Adhesive MP -or "LRF Adhesive O" applied as a -
nominal PA -In. diameter bead with a maximum on -center spacing of 12 -in. applied parallel to the slope of the roof.
8. Deck: C-15/32
Incline: 1/4
Insulation. — Any UL Classified polyisocyanurate, minimum 3 -in, thick, mechanically fastened or fully adhered with hot roofing
asphalt or adhered with "LRF Adhesive M".
Base Sheet. — One or more plies Type G1 orType G2 or "GAF Stratavent@ Eliminator'"' Venting Base Sheet (Nallable)",
mechanically fastened.
Membrane: — Two or more plies "Ruberold® 20" or "Ruberold@ 20 HT" or three or more plies Type Gi "GAFGLAS@ Ply 60, fully
adhered with hot roofing asphalt..
Membrane: — "EverGuard@TPO FB Ultra" 45-mll to 6D -mil or " EverGuard@ Extremee" TPO FB Ultra" 50-mll to BO-mll, fully
adhered with hot roofing asphalt or mechanically fastened or adhered with "LRF Adhesive M" or "LRF Adhesive O" applied as a
nominal a/4 -In. diameter bead with a maximum on -center spacing of 12-1n. applied parallel to the slope of the roof.
9, Deck: NC
Incline: 9/4
Insulation (Optional). — Wood fiber or glass fiber or perlite,1/ -In. thick minimum, mechanically fastened or fully adhered with
hot roofing asphalt or adhered with "LRF Adhesive M" or OMG Inc "Olybond Fastening System" applied as a nominal e/4 -in. bead
or "GAF 2 -Part Roofing Adhesive" applied as a nominal 21/a -in. bead with a maximum on -center spacing of 12 -In. or any UL
Classified insulation adhesive applied per the manufacturer's Installation instructions.
Membrane: — "EverGuard@ TPO F8 Ultra" 45-m11 to 80-mll or" EverGuard@ Extreme'l"TPO FB Ultra" 50 -mil to 80-mll, fully
adhered with hot roofing asphalt or mechanically fastened or adhered with "LRF Adhesive M" or "LRF Adhesive 0" applied as a
nominal 814 -in. diameter bead with a maximum on -center spacing of 12 -In. applied parallel to the slope of the roof.
10, Deck: NC
Incline:. TA
Insulation (Optional): — Minimum V. -In. thick wood fiber over any UL Classified polyisocyanurate, any thickness.
Membrane: — "EverGuard@ Freedom'"' TPO" 45 -mil to 80 -mil or "EverGuard@ Extreme," Freedom," TPO HW" 50 -mil to 80-mll,
self -adhered,
11. Deck. NC
Incline: 2
Membrane: — "EverGuard@ Freedom,,' TPO" 45-mll to 80 -mil or "EverGuard@ Extreme," Freedom""' TPO HW" 50 -mil to 80 -mil,
self -adhered.
12. Decks C-15/32
Incline: 2
Insulation (Optional): — Any UL Classified, any thickness.
Barrier Board: — Minimum'/4-in, thick Georgia-Pacific Gypsum LLC "DensDeck(@ Roofboard" or "DensDeck Prime@ Roofboard"
or "DensDeck DuraGuard"" Roofboard", mechanically fastened with all butt joints In barrier board staggered a minimum of 6-1n.
from butt joints in plywood deck,
Membrane: — "EverGuard@ Freedom""' TPO" 45 -mg to 80-m11 or "EverGuard@ Extreme*" Freedom," TPO HW" 50 -mil to 80 -mil,
self -adhered.
13. Deck: NC
Incline: 1/4
Insulation (Optional): — "EnergyGuard74" or "EnergyGuard^" RA" or EnergyGuard„” RN" or "EnergyGuardT"' RF" or
"EnergyGuard,," Ultra" or "EnergyGuardT"' RHO or wood fiber or glass fiber or perlite, any thickness.
Slip Sheet (Optional):— One ply "StormSafeT°", mechanically fastened
Membrane: — "EverGuard@ Freedom,"' TPO" 45 -mil to 80 -mil or "EverGuard@ Extreme''" Freedom*'" TPO HW" 50 -mil to 80 -mil,
self -adhered.
14. Deck: C-15/32
Incline: 2%
Barrier Board: — Minimum 1/4-!n. thick Georgia-Pacific Gypsum LLC "DensDeck® Roofboard" or "DensDeck Prime@ Roofboard"
or "DensDeck DuraGuardTM Roofboard", mechanically fastened with all butt joints In battler board staggered a minimum of 6 -In.
from butt joints In plywood deck.
Membrane: — "EverGuard@ Freedom'"' TPO" 45 -mil to 80 -mil or "EverGuard@ Extreme," Freedom"TPO HW" 50 -mil to 80 -mil,
self adhered.
15. Deck: NC
Incline; 'A
Insulation (Optional): — "EnergyGuard'"'" or "EnergyGuardT" Ultra" or "EnergyGuard'"' RA" or "EnergyGuard'"' RN" or
"EnergyGuard,," RHO, any thickness.
Membrane: — "EverGuard@ Freedom""' TPO" 45-mll to 80 -mil or "EverGuard@ Extreme," FreedomT" TPO HW" 50 -mil to 8D-mll,
16=.rk-C_1513l—�� Incline: 1
Primer. — "FireOut' "" applied at a rate of 1-gal./100-fL2.
Base Sheet (Optional): — One ply Type G2, mechanically fastened.
Slip Sheet (Optional); — One ply "StormSafeTm" or "VersaShleld@ IS" or "VersaShield@ 2S" or Atlas Roofing Corp. "FR -10" or
"FR -50", mechanically fastened.
Membrane: — "EverGuard@ Freedom"" TPO" 45 -mil to 80 -mil or "EverGuard@ ExtremeT'' Freedom"" TPO HW" 50-mll to 80 -mil,
self -adhered.
17. Deck: NC Incline: 'A
... --. f. 1-- 7o17v1r/1777? Q A/FR/chnumarre.hlml?name=... 11/20/2013
'Miami Shores Village
Building Department
10050 N.E.2nd Avenue
Miami Shores, Florida 33138
Tel: (305) 795.2204
Fax: (305) 756.8972
March 28, 2014
Permit No: RF 14-587
Building Critique Review
1. Provide detail and specifications for the low slope roof system.
Ismael Naranjo
Building Official
Plan review is not complete, when all items above are corrected, we will do a complete
plan review.
If any sheets are voided, remove them from the plans and replace with new revised
sheets and include one set of voided sheets in the re -submittal drawings.