Loading...
ELC-13-1490Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795 -2204 Fax: (305)756 -8972 nspection Number: INSP- 194637 Permit Number: ELC -7 -13 -1490 Inspection Date: July 19, 2013 Permit Type: Electrical - Commercial Inspector: Devaney, Michael Inspection Type: Final Owner: , BARRY UNIVERSITY Work Classification: Addition /Alteration Job Address: 11300 NE 2 Avenue Weber Hall Miami Shores, FL 33138 -0000 Project: <NONE> Contractor: C DAVIS ELECTRIC COMPANY, INC Buildina Department Comments Phone Number Parcel Number 1121360010160 -13 Phone: (954)432 -4334 FIRE ALARM Infractio Passed Comments INSPECTOR COMMENTS False Passed Ef Inspector Comments IT Failed Correction Needed ❑ Re- Inspection ❑ Fee No Additional Inspections can be scheduled until re- inspection fee is paid. For Inspections please call: (305)762 -4949 July 19, 2013 Page 1 of 1 Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 INSPECTION'S PHONE NUMBER: (305) 762.4949 BUILDING PERMIT APPLICATION Permit Type: Electrical JOB ADDRESS: 11300 NE 2nd Avenue - Weber Hall FBC 2010 Permit No. qq Master Permit City: Miami Shores County: Miami Dade Zip: 33161 FOlio/Parcel #: 1121360010160 -13 Is the Building Historically Designated: Yes NO X Flood Zone: OWNER: Name (Fee Simple Titleholder): Barry University Inc. Phone #: 305 -899 -3050 Address: 11300 NE 2nd Avenue City: Miami Shores State: FL zip: 33161 Tenant/Lessee Name: _ Barry University Phone #: 305- 899 -3050 Email: CONTRACTOR: Company Name: C. Davis Electric Co.. Inc. Phone #: 954 -432 -4334 Address: 1701 SW 100th Terrace City: Miramar State: FL zip: 33025 Qualifier Name: Charles E. Davis JR. phone#: 954 -432 -4334 State Certification or Registration #: EC0001038 Certificate of Competency #: Contact Phone #: (954) 275 -8381 Email Address: Ichristopher @cdaviselectric.com DESIGNER: Architect/Engineer: Phone #: Value of Work for this Permit: $ Y) I S0c) Square/Linear Footage of Work: Type of Work: ❑Address Alteration ONew ORepair/Replace ODemolition Description of Work: Fire Alarm devices installation for Weber Hall bathroom renovations Submittal Fee $ Permit Fee $ CCF $ CO /CC $ Scanning Fee $ Radon Fee $ DBPR $ Bond $ Notary $ Training/Education Fee $ Technology Fee $ Double Fee $ Structural Review $ TOTAL FEE NOW DUE $ Bonding Company's Name (if applicable) Bonding Company's Address — City State Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and AIR CONDMONERS, ETC..... OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will not be qpprov5youl a reinspection fee will be charged. Signature Signature Owner or Agent The foregoing instrument was acknowledged before me this 1:k day of t , 20 13 , by who is personally known to me or who has produced As identification and who did take an oath. NOTARY PUBLIC: . Contractor The foregoing instrument was acknowledged before me this 2nd day of July , 20.3, by ChadeS F nays ► j� who is personally known to me or who has produced Sign: Print: �v v.y�v My Commission Expires: app Notary Pubnc State of Florida Cheryl Beide Gerber My Commlw can DD988128 %a pd, Expires 05/08/2014 �k�k APPROVED BY vGr�Plans Examiner Structural Review (Revised 3 /12/2012)(Revised 07 /10/p7)(Revised 06 /10/2009)(Revised 3/15/09) identification and who did take an oath. NOTARY PUBLIC: Sign: Print: SUSa My Commission Expires: = *: Commission # EE 217497 Expires September 25, 2016 Ban MTiuuTroy Ken hum= NO-385-7019 Zoning Clerk •..:: STATE OF FLORIDA: COUNTY OF MIAMI -DADE: ,) I ATE OF IHEREBYC THE UNDERSIGNED hereby gives notice that Improvements will be made terms properly, and In accordance with Chapter 713, Florida Statutes, the fours infomratTan is provided in this Notice of Commencement. WITNESS my I HARVEY RUVII ey description of Interest In property: Name and address OR Bk 28708 Ps 2805; tips) RECORDED 07 103/2013 11:53:10 HARVEY RUL`IN? CLERK OF C:%I_IItiT MIAMI°-DADE COUNTYr FLORIDA LAST PAGE OA, COUNTY OF DADE 'that this is a true _c of the e n�d of , AD 20 and fhcial eat. E o ul n County Courts S� D.C. Space above reserved for use of recording office - �� r, r r ' z r/ i,--- '``7.,!fL�[r ✓i`+SS'r'��IRS:�+_� of fee simple titleholder: 4. Contractor's name, address and phone number., 0 8. In addition to himself, Owners designates the following 713.13(l)(b), Florida Statutes. to receive a copy of the Lienoes Notice as provided in Section ithe expiration date Is 1 year from the date of recording unless a different d0te Is s WARNING TO OWNER. ANY PAYMENTS MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICE OF COMMENCEMENT ARE CONSIDERED IMPROPER PAYMENTS UNDER CHAPTER 713, PART I, SECTION 713.13. FLORIDA STATUTES, AND CAN RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE COMMENCING WORK OR RECORDING YOUR NOTICE OF COMMENCEMENT. Signatures} of OwnagCM Owner {s }' Authorized Of loer /Director/Partner /Manager Prepared By Print Name Title/Office wee STATE OF FLORIDA COUNTY OF MIAMI -DADE The foregoing instrument was Prepared By Print Name _ Title /Office _ me this a day of � Z f By ❑ Individuaffy, or U as Sn y for A-^A � /�"a td . ersonally known, or U produced the following type of Tdentific Signature of Notary Public: Print Name: (SEAW VERI CATION PUMAWT TO SECTION 92.S�% FLORIDA STAW -19S u� °.•'•• Lh%i Noiwy Public Stats of Florida Under penalties of perjury, I declare that I have read the foregoing and � C Gather that the facts stated In it are true, to the best of my knowledge and belief. My CassanODW6126 ,res oigoat2o14 Signatures) of Ow er(s } °s Authorized C} fHcer /f?irectorlF'artnerlManagegoo By By M -01.s2 PAM3 en2 �6 DEp -{ Miami -Dade Fire Rescue Fire Alarm Pre - Submittal Checklist Based On WPA 72 200T Ed. & NFPA 1 and 1012009' Ed. COUNTY Designed by. " rive f. S ect�vC Phone a. Stgrnature: ���TMS Created by: MDFR 08/2012 Ul �DD��UMENT O N ALL FIRE ALARM PLAN SUBMITTALS 1 OF 2 M NOV Building r{Z M Number Is' with 611 M, • DOW 12-J12 ® 11 1 Pr Naive. Is pMgy2d In title blackgt YES NQ TWA 2 Address In tilts block shall match address in lkdWft UspL Computer Systenfjand attached permit appftcaton. if address contains a Butte ucdt nfenber or letter it shalt bs rovtded In titre blot-, to match Wft RM& System. The total coat of the installation to the customer is $ U and a copy of the contract or a notarized affidavit 3 from the owner showing this amount Is allachet 4 —W Fire Alarm S erns oposthy more Vian $O,OOf1 are treated or slarriped by a Florida ftMqW Profit The total number of DEVICES and COMPONEWS being MdaW is 8 The alarm quallfters sate license numb Is # Z b and a copy Is attached to plans. kl/ 7 Complete, current manufactuter's Specification do Installation sheets are attached for all control units, cornponents, devices, modules and relays, listed on 8 is this pemfit application for fire alarm work a result of a Notice Of Violation (NOV) issued by Mlami -Dade f�escr�e'> if yes, a copy of the Notice of Moleflon Is attac3hed.. . . ... . . This fire alarm: is required under C ina l*b( 23 (fill In the O Cy Chapter & Section from NFPA 101 9 OR, (_) Is a Ufa safety equivalency OR, U Is a non - required system or component. This is sn " EXISTIM (t G) Fire Alarm System° and Is stated as such on the plans. AHd will require dcorunentatknn R prior 10 approval of system as a (Local) Fire Alarm System in the form of the original Fire dept approved job copy set of fire alem plane or certified microfilm copy of same. 11 I This is a "NEW Lot Fire Alarm 5 and Is stated as on This Is an `EXISTING Central Station Sergi Fire Alarm System" and is stated as such on the lbs. A copy of the euisting 12 UB ILDING UL or ETL ceRfttcats, or FM Placard, spedfiCafty tdesttNyirrg this protected premise by address, and uniquely identifying this building's fire alarm is If the company that Issued the a left certificate or placard for this building's fire alarm system to different than ft company 13 applying for this permit; is the AffWavtt to Work on another Company's Cerffticated or Pkmded Fire Alarm System Provided? 14 This Is a NEW Certl ate- of - ed Station Service Fire Alarm SydeW and s-tetl ao such on the plans. 1s If this is a NEW 'Central Station Service Fire Alarm System," a copy of the UL or ETL certificate of FM placard Ran the contractor or from the Central S ,ion Senrto Comgn. 1ptftffw keft carrtitS el lacard is attached. . This Is an " EXISTING Remade Supervising Static Fire Alarm System" and Is stated as such on the plans. )w a reqube f8 dtmnmentation of pry approval of system as a Renate Supervising Station Fire Alarm System In the faun of the original Fire Dept: Wgroved job 10 of fire alarm plans or dantfied rnftrolitm qWof same. 17 ;This Is an `MS WWerfiow and - only and Is stated as such on pWm This is a NEW °Sprinkler Waterf ow and Supervisory Systern" only and is stated as such on plans. The system is monitored oil S—M 18 and proves emergency fdNE88 non through a Certificated L_j or Placarded f_) °Cernfral Station Service Fire Alarm °,art- Is stated as such!M the A complete sfal!2=9 of the PE QF WORM is stated on the plan. Please note fiat the complete ternant spade, In Its 19' entirety, will be Inspected for compliance with NFPA 72 (2007) and NFPA 101 (2009), or prior editions of Owe codas If applicable. Also outline scope of work with bolded dashed on flow Man and dw for existing systarns. 20 The building Is or and Is Indicated as such on the plans. 21 A description of the building IS provided, including fire sprinkler systems, fire suppression systems, number R stories, square t2IM Rer fkwa and 4MAM of ft W 2SEW Nor N tm.er 5 stories. 22 A location Key Is provided sib ther am of proposed work within the building. Also provided Is a Me keg for pErojdds wail., multiple buildings showing locallons of all addresses 23 Ali hhterconnecrted Flo Ccmtrol Fanelli are to stn as a single tom and monItmeti NFPA7 . 24 Theclassis to for Device 1dC Lkne Circuits SLC and NAC 25 The maxknum number of each device type Is provided for each 10C based on device load or each SLC, based on class and style, par NFPA 72 and the nanutad W 28 A specific of OperaW lrcl d ft all alarm, supervisory, trouble and control GU mm such as fire spafnkla , door release smoke control, elevator recap MMOOM gdems, and transmission of signals oifsite etc. are 222S42g an the Pim 27 The type of monitoring station, Central Statkn, Remote Supervift station. Listed P Supervising Station), whom alarm, signals are trapamitted clearly and 924!gy stated In the of NOME 28 1 Thee meghod of comTunwation f. the station is ink an the riser. 29 ff this bulkfing guns elevators triad are not capable of recap, It stall be stated as such on plans and writer documentation an elevator contractor's Lett heel aft that Tlevatare are not capable otproviding recap function° is . 30 If Oft hiding does not contain a fire alarm system, and the fire alarm panel is used exclusively for elevator reed, plans snap Geed as "Elevator and SuME&M Patter 31 Manufacturer, modal number and unique symbol for each model number Is provided for each device, modue, relay, componernt, and firs corir+ol Is 59ft in the bell WW- 32 Each device, module, appliance and component Is Identified with Its own unique number and indicated on the ficxrr plans and riser. IM Floor plans are drawn to IN scale or, if using anolner scale, an device coverage Is diagranrmad an the floor plan and all roam dimensions are Included. Designed by. " rive f. S ect�vC Phone a. Stgrnature: ���TMS Created by: MDFR 08/2012 Ul �DD��UMENT O N ALL FIRE ALARM PLAN SUBMITTALS 1 OF 2 M NOV Mlami -Dade Fire Rescue Fire Alarm Pre - Submittal Checklist MIAMFDu4DE Based On NFPA 72 2Wr Ed. & NFPA 1 and 1012009' Ed. 34 Ali rooms & spaces are their use, and the occupant loaf has been provided for all assembly use rooms with an load of 50 or arester. L/ 35 Ali row, existing, replaced of relocated devices are Ineieated on the floor plans and a compile riser diagram strewing all new and existing devices of the entire fire alarm systern Is movided. 36 Ceiling tw end Is ed for all gft mounted devices. AH devices artd cornporrer s located in areas In which the voltage, temperature, and humidity varlot ns exceed two conditions stated In WPA 72 are Rated for conditions and all such area are identified. 38 A note Is provided on the plans stating "Room containing FRCP, Booster Power Supply, Voice Evacuation and Amplifier panel(s), Dialer, or Radio Is met nc�afi ventilated", as 39 The FACP or Remote Annunciator and as applicable EVAC panel or Remote Microphone Is located at the male enkaranqobby In single tercet buHdbM or to a c mmon area main entrance/lo of a multi- tenant 40 The FACP, Communicators , NAC Panels and all sub-panels are protected with a smoke detector. 41 If a complete automatically activated system, not less than one manual fire alarm pull box shall be provided to Initiate system. The Pull box shag to located where AHJ sPecifies. -1.1k 42 If a manually activated system. the travel distance to reach a pug station is less than 200' feet and within 5' feet of all required floor and/or building aft. 43 All automatic bating devices are shown and are bated In accordance with NFPA 72, the manufacturer's specificallons, and accepted e 44 Area srnoke detectors, if used, shag provide coverage #TNOW the entire smoke canna ant 45 All vista notification appliances are plates per tables In NFPA 72 and each strobe has Its candela rating an the floor plan and riser. 46 Ali corridor spaced strobes are placed a maximum of 100' feet apart and within 15' feet from the ends of the corridor. 47 Ali s the entire shag meet the audible characteristics s of NFPA 72 and NFPA 101. 48 Beg used for water flow annunciation Is shown on floor plan, riser and legend. Beg shag he located so as to be visible and heard from m4m or panting area within close proximity to Fire Dept Connection DC . Flow Beg sequence of operations stag state as follows: 49 A) Flow hag shalt activate upon water flow only. B) Flaw beg shag continue to sand as long as water Is lowing. C FACP stag not be capable of geft Flom Beg. 50 The location of Backflow Preventor (BFPj Post Indicating Valve (PIV) and Fire Dept. Connection WDC) are indicated an the floor ens riser and legend for aprWed 51 Wags , racks shelves and ant that do not extend to calling, we shown with their gago www on floor Duct detectors or relays for duet detectors are shown on the floor plan and riser for all systems greater than 2000 CFM supply or 52 greater than 15,000 CFM return. Dud deters shag derive their 24 vote do power scarce from the Fire Alarm System to so" the monfloft ter ftft requirements of NFPA 72.4.4) for devices and conductors. Please show,coMplience on riser. 53 A complete system riser diagram Is provided showing each floor of the bugdtng with all zones and cincults labeled. 54 The conductor site and Qwft we adged for ch circuit on riser. The fire pump Is monitored for A) Pump or Motor Running, B) Loss of phase, C) Phase reversal, and, if applicable, D) Co ffar 55 connected to an alternate source: and are indicated at (_j a continuously marred location, or U the supervised fire alarm s 56 Show all rem an floor plan and clarity function on riser. (Sprinkler, Wet Chem., Dry Chem., Clean Agent, Foam, Elevator Shurd- Trip, Music Start -Down t?oa Relem and other Wft control furutions. 57 The AMPACITY of each Power Supply and NotifiCation Appliance Circuit is specified for each FACP & Power Supply Panel on M addklon the individual device current is specified on riser for each notification / ens A Strobes . 58 The total "ACytAW footage to the haft device along with voltage drop calculations are provided an plans for each NAC f r each power M4*y. 59 The wattap too Is indkatad for all 60 The wM a and load Is provided for each amplifier. 61 All bad ohm f� `STANDBY° & ALARM° used In calculations are high- lighted on the manuladurees specificallon or installation sheets. Also. AMPACIT- 01 emda ment/comoonents and circults are hlgh-lighted on manufacture's streets. 62 This system ladcutes Emergenc -i Voice Evacuation and Is provided with 15 minutes alarm poorer. In all high rises and with an occupant load areater than 300. 63 This system Is being provided back up power by an emergency generator and will provide 4 horns of standby power plus the e alarm 64 Battery calculations, detailed in chart forth, showing all information required per NFPA 72AA.1.5.3.1 are provided an plans fir each bedtwup power awl The replacement of the Fire Alarm Control Paired with anything other than the exact same make and mrodel number panel; or the 65 addition of a Fire Alarm Control Panel which will provide or replace any of the functions of ttre existing FRCP, shall require the tins alarm system to be up -graded to ant code standards, per code of Miami -Dade Corutty, Part Ito, Chapter 14, Article lid, Swan 14-66 9 & 10 66 M the scope of wait Inductors greater flan are -half of the entire We alarm system's devices, am the entire fire alarm system shag be u to current rode standards, code of Miami -Dade Count , Part lit, Chapter 14, Article III, Settn 14.68 9 Signature: Created by: MDFR 08 / 2012 IS iS A WRED DOCUMENT ON ALL FIRE ALARM PLAN SUBMITTALS 2OF2 STATE OF FLORIDA q DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION Q ELECTRICAL CONTRACTORS LICENSING BOARD (85 0) 487 -1395 1940 NORTH "WW1 TALLAHASSEE FL T 3TRFLT32399 -0783 RODE, LAURA L ADVANCED FIRE AND SECURITY INC 2780 GATEWAY DRIVE POMPANO BEACH FL 33069 Congratulations. With this license you become one of the nearly one million Floridians licensed by the Department of Business and Professional Regulation. STAE OF FC Rtb14 TM, . p range from architects to yacht brokers,RE$ Our professionals and businesses from . - „, GUA�fI01d ; „ fi •,, boxers to barbeque restaurants, and they keep Florida's economy strong.•, 5, EF0001' 26 ' 128002412 Every day we work to improve the way we do business in order to serve you bettter.l For information about our services, please log onto www.myflorldalicense.co There you can find more information about our divisions the that and regulations impact you, subscribe to department newsletters and learn more about the Department's initiatives. Our mission, at the Department WItcense Efolently, Regulate Fairly. We cgnstantly strive to serve you bet(gr so that you can serve your customers. Thank you for doing business In Merida, and cengratulafitsna an new license! { Z$ cERTI � ?� c�.�p9 as J;c� your sst�nm ' „ T5tti316 . j DETACH HERE 9 B 4 _ 6 t $ �. , DA.- C # 7TE O FLORI1. 861, . ... , D$P�ART�ENT1 iBUB' "� 8`S�1 AND PROFESSIONAL REG�IL�;TION" ' EIi$CTI "_�TTR'ACTORS' LICENSING BOARD: v r, ;t d s• r 4.r.:,t i.• k -SEQ# L12070501310 ... . , _ a • ... - ._ .. Dais _.�a�4 -mow .. . . ,.7/,05., 2.0:12: 12.8002412` E' .001it2. ` The ALARM" SY'STEM CONTRACTORfi #I`` ' l am id, below IS CERftFrIED under 616- provisidnS o :� Chapt Expiration date: AUG 31, 20144 RODE, LAURA" L A ADVANCED FIRE AND SEdURTTY s 2780 GATEWAY DRIVE` -POMPANO BEACH FL 33069: RICK SCOTT KEN LAWSON GOVERNOR SECRETARY DISPLAY AS REQUIRED BY LAW Eric Fechter 2780 Gateway Drive Pompano Beach, Florida 33069 office (954) 772.1700 fax (954) 772.0500 State License 0 EF 0001026 UL # 8- 7192.1 FM 17 30432$1 FIRE ALARM SYSTEM PROPOSAL Date: April 29, 2013 Name of Project; Weber Hail Q Barry University Contact Person: Mike Gagilano Company: C -Davis Electric Advanced Fire & Security, Inc. would like to submit the following Proposal for your review and acceptance: O El EQUIPMENT citu+rri 73 24 3 72 2 1 1 7 1 1 S 7 2 Engineer drawings dated Bill of Material, dated Changes per Plan Review Y ?. PART NUMBER FSP -851 FST 851 EP -135 B200SR NBG`l2LX N0812LOD solo SR P2R P2RK SRK AL1024ULX PS 1270 4126/2013 PART DESCRIPTION LOW PROFILE PHOTO DETECTORS HEAT DETECTORS WEATHERPROOF HEATS WITH MODULE SOUN13ER BASES FOR DETECTORS PULL STATIONS WEATHERPROOF PULL STATIONS SURFACE BOX - WIP PULL STATIONS STROBES (RED) MULTI CANDELA HORN STROBES (RED) WIP HORNISTROBE (RED) W I P STROBE - 75 ad (RED) ALTRONIX POWER SUPPLY, 8 AMP BATTERIES FOR POWER SUPPLY INCLUSIONS AND EXCLUSIONS Materi IaPrt_cinsn Included Excluded d ❑ AutoCad files to be provided by customer to Advanced Fire ............. _ D .................... ..... ..Q_._..._........- Professionat Engineer-mview;- Sign•and-Seafi provided -by- Advanced- Fire ........_..................... ................ 0 [] Professional Engineer review, Sign and Seal, by others )] ❑ .... Shop Drawings .. . [) ❑ Submmittal Packages 0 [] Florida Sales Tax [) [] Expedited Drawings [p ❑ Parts 0 [) UL or FM Certificate [] ❑ Programming 0 C) Spare Parts, per Specifications El (p Other: j] (a Others p ❑ As -Built Drawings ® [a Logbook .10 ❑ Final Inspections and NFPA Certification i -- ded Excluded [� Permit Fees ❑ O Permit Processing Fees ($78, per trip) _ j� Expedited Permit Fees ❑ n, Bond Expense ❑ El labor ❑ 21 Prevailing Wages Included ❑ [� Raceway wi Pulistring and standard backboxes ❑ [] Wiring and Terminations ❑ [] 120 vac Electrical Connections ❑ [] Duct Detector Installation & Mechanical Connections ❑ [] Lift Rental ❑ After -hours Installation ❑ R) Telephone Lines for off - premise Monitoring Q [] Rough Electrical Inspection ❑ Rough Fire inspection ❑ Cj Rough Smoke Detector Inspection ❑ After -hours Inspections [] Additional Inspections required by AHJ due to time limitations ❑ Additional Inspections to assist other trades ❑ to SRi (Special Request) Inspections - (Municipal Fees) ❑ El Customer Training at time of completion ❑ 21 Other: ❑ El Other. PRICING: Materlal $19,9".60 plus Bases Tax Labor $0.00 (foUlal below) TERMS: Net 30 upon receipt of Invoice. Charges will be Invoiced as the job progresses ACCEPTANCE: Customer: By: Name: By: Name: -Eric- Fetchtterr Date- Prices quoted are firm for Et) days. AHJ may require additional devices to meet Code requirements M2 '0[-�'Ooc, NOTE: ALL SHEET MUST BE REVIEWED MIAMI -DADE COUNTY BUILDING AND NEIGHBORHOOD COMPLIANCE DEPARTMENT Herbert S. Saffir Permitting and Inspection Center 11805 SW 26th Street (Coral Way) • Miami, Florida 33175 -2474 • (786) 315 -2100 APPLICATION FOR MUNICIPAL PERMIT APPLICANTS THAT REQUIRE PLAN REVIEW FROM MIAMI -DADE FIRE RESCUE AND /OR DEPARMENT OF ENVIRONMENTAL RESOURCES MANAGEMENT PROVIDE MUNICIPAL PROCESS NUMBER HERE Job Address 11300 NE 2ND AVENUE Contractor No. EC0001038 o Z Folio 112136001016013 az 0 0 ° Last four (4) digits of Qualifier No. 0021 C. Davis Electric Co., Inc. Lot Block x Contractor Name Charles E. Davis Jr. ao Qualifier Name �a Subdivision PBpg �z Address 1701 SW 100 Terrace Metes and bounds 52 4140 AC SE1 14 OF NE1 /4 LESS E35FT &LESS W40FT City Miramar State FL zip 33025 ( X] New Construction on [ j. Demolish Current use of property EDUCATIONAL - PRIVATE Vacant Land [ } Shell Only a ( J Alteration Interior ( } Addition Attached a Og [ ] Alteration Exterior [ ] Addition Detached Description of Work FIRE ALARM DEVICES a ( J Relocation of Structure [ } Re -Roof f0 INSTALLATION @ Weber Hall Sq. Ft. 'ets Flcors Enclosure [ ] Foundation Only V � � ( J Repair [ ] Repair Due to Fire � Value of Wvr % [ J MELD' ( ] Chg. Contractor Owner BARRY UNIVERSITY INC Address 11300 NE 2 AVENUE W Category ( ] Re4ssue W 2 City Miami Shores State FL zip 33161 [XJ MELE 04 y ( ] Re -Stamp I ( ] MLPG ( ] Revision w Phone 305 -865 -5707 Last four (4) digits of CL [ ] MMEC ( J Not Applicable for ( J FIRE Fire Owner's Social Security No. W Z Name L l Owner Za Address ac RZ Address City State Zip City State _Zip a n Y v1 L a Phone " ® `� W Phone I am requesting a Special Request Plan Review (SR# to be scheduled as soon as possible at the rate of $190 for the first hour ' it vaa and S65 per each add! al houri ditic the r to eas. Minimum charge one4iour. Date: f IT y 1" Request: WOE 24 Request: Date: ac 3'0 Request: Date: z ;3 1 am requesting Optional Plan Review (OPR) to be scheduled as soon as possible at the rate of S75 for each discipline. ° a Additional review fees may apply. g 0} 1s1 Request: Date: 01 2^6 Request: Date: 2 cc W 3" Request: Date: 123.01.192 1N09 i October 31, 2005 DN -5262 - A -103 �J N OT I F I E R® AFN300 and AFP -400 by Honeywell Analog Fire Panels Section: Intelligent Fire Alarm Control Panels GENERAL The AFP -300 and AFP -400 are compact, cost - effective, in- telligent fire alarm control panels with a total capacity of up to 563 points and an extensive list of powerful features. The AFP- 300/400 integrates conventional output circuits, such as notification, telephone, and speakers, with the in- telligent features of one or two signaling line circuits (SLC) and 198 or 396 intelligent/addressable points. FEATURES - One loop (AFP -300) or two loops (AFP -400) Style 4, 6 or 7. 198 intelligent devices per loop (99 intelligent detec- tors and 99 intelligent modules). - 396 intelligent device capacity on the AFP -400; 198 on the AFP -300. - VIEW®, HARSHTM, Advanced Multi- Sensor (AMS) op- tions. - Up to 68 internal circuits /relays, plus 99 programmable zone output relays for a total capacity of 563 points. Four integral Notification Appliance (signal) Circuits (NACs), Style Z or Y (Class A or B). - 6.0 A power supply, plus 6.0 A expanders. NACs may be programmed for Steady, March Time, Temporal, California code, or Canadian Two - Stage. - Modified California code, pulsed on time. - Tornado Warning activates different Notification Appli- ance Circuit code. - Alarm, Trouble, Supervisory, and Security relays, stan- dard. - Peer -to -peer network - ready. Intelligent features: ✓ Manual sensitivity adjustment — 9 levels. ✓ Pre -alarm intelligent sensing — 9 levels. ✓ Day /Night automatic sensitivity adjustment. ✓ Drift compensation. ✓ Multi - detector algorithm involves nearby detectors in alarm decision. ✓ Auto detector test (meets NFPA 72). ✓ Maintenance alert (two levels). ✓ Self - optimizing pre -alarm adjusts pre -alarm level to environment automatically. ✓ Activate local sounder base on pre - alarm. ✓ LED blink control for sleeping areas. ✓ Automatic device type check. ✓ Trouble after 20 detector verifications. - Releasing features: ✓ Ten independent hazards. ✓ Sophisticated cross -zone (three options). ✓ Delay timer and Discharge timers (adjustable). ✓ Abort (four options). California L s: State Fire Marshal o ,4 77170- 0028:182 LISTED CS118/733 7165- 0028:181 S635 City of M EA FM Chicago 17 -96 -E (AFP -400) CLASS 1: 1291 E 17 -96 -E Vol. II (AFP -300) APPROVED CLASS 2:1729E City of DENVER (AFP -400) 3 Z S 3 0 's Sensitivity windows: ✓ ION — 0.5 to 2.061foot obscuration. ✓ PHOTO — 0.5 to 2.35 9,61foot obscuration. ✓ MULTI- SENSOR — 0.71 to 4.0 9,61foot obscuration. ✓ VIEW® — 0.03 to 1.0617oot obscuration. Low - pressure CO2 support: ✓ Expanded soak timer – 0 to 9999 seconds. ✓ Manual release delay (10 seconds) type ID. ✓ `Second shot" monitor module type ID. ✓ Triple -coded notification circuit type ID. Voice and telephone features: ✓ Solid state message generation. ✓ Hard -wired voice control module options (single - address mode modules). HARSHT"' and NOTI- FIRE -NETTm are trademarks;VeriFireo, VIEW@ and NOTIFIER@ are registered trademarks of Honeywell International Inc. Microsoft@ and Windows@ are registered trademarks of the Microsoft Corporation. This document is not intended be used for installation purposes. We try to keep our 1S0 �00� product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact NOTIFIER. Phone: (203) 484 -7161 FAX: (203) 484 -7118 NOT 1 F 1 E R' 91 UNIIIN; 8 MANBflICI IIM by Honeywell 12 Clintonville Road, Northford, Connecticut 06472 QUALITY SYSTEM S DN -5262 - 10/31/05 — Page 1 of 10 1 7 r r- A ✓ Distributed voice options (XP transponders). r/ Firefighter telephone option. s/ 30- to 120 -watt high - efficiency amplifier. ✓ Backup tone generator and amplifier option. ✓ Dual channel option. • Telephone control module type ID. • Optional UDACT, 396 - channel digital alarm communi- cator transmitter with AC fail delay. • 80- character displays (up to 32) for remote annunciation. • ACS annunciators (EIA -485), including LDM custom. • Two -wire detector interface provides compatibility with many manufacturers' detectors for retrofit applications. • Integral printer interface (80- column and 40- column printers). • Integral 80- character LCD display, backlit (2 lines x 40 characters). • Field- programmable on panel or on PC, with program check, compare, simulate. • Full QWERTY keypad behind flip -down door. • Autoprogramming and Walk Test. • Identifies two devices set to the same address. • History file with 800 -event capacity in nonvolatile memory, plus separate 200 -event alarm -only file. Page 2 of 10 — DN -5262 • 10/31/05 • Programmable waterflow or supervisory selection per point. • Alarm Verification selection per point, with tally. • Verification Trouble counter. Trouble indication after a detector verifies 20 times. • Programmable Positive Alarm Sequence (PAS) Presignal per NFPA 72. • Silence inhibit and Auto Silence timer options. • Programmable non -alarm points for lower priority func- tions. • Remote ACK / Silence / Reset / Drill via addressable modules. • Maintenance Reports may be sorted via PC by compen- sation value (dirty detector), peak alarm value, or address. • Automatic time control functions, with holiday exceptions. • Dual rate charger for up to 90 hours of standby power. • Rapid poll algorithm for manual stations. Responds to alarm /activation in less than three seconds. • SLC loop maximum length 10,000 feet (3,048 m) @ 12 AWG (3.31 mm2). • Surface Mount Technology (SMT) electronics. • High -speed RISC 16 -bit microprocessor. • Extensive built -in transient protection. SAMPLE SYSTEM BLOCK DIAGRAM i� UP o 0 0 o °o TO 8 °0 32 D o D o 0 0 3 LCD-80 Remote Display /Control up to 68 fully programmable output circuits 0 z N W N O w 0 I w CD CD W 0 0 RS-485 AFP -400 shown in CAB -4 with voice alarm system RS -232 0 FCM -1 SLC Intelligent Loop 1 XP Transponder NAC r ---------- riv alU alU alU alU alU Lira U� Ual ❑al U� Ual alU o Lira Ual FSI -851 FSP -851 nr• Ual DEVICES MLLE ULira ° Ion Photo FST -851 alU alU alU Ual ❑al Ual ELE aILJ MLI Um UM Thermal — — — — — — — — — — • NBG -12LX FMM -1 alU Ual Fixed alU 1 Mu Lim I DC SLC Intelligent Loop 2 DEVICES FSP -851T FST -851R FAPT -851 Photo/ Thermal Advanced ----- - - - - -, NBG -12LX FMM -1 Thermal ROR Multi- Sensor I DC RS- 465 840 annunciator /control points AFP -400 shown in CAB -4 with voice alarm system RS -232 Y a o FCM -1 XP Transponder NAC 0 0 0 FCM -1 XP Transponder NAC r riv alU alU alU alU alU Lira U� Ual ❑al U� Ual alU o Lira Ual rio alU nr• Ual MLLE ULira alU alU alU Ual Lial Ual alU alU alU Ual ❑al Ual ELE aILJ MLI Um UM =LJ ELJ 1i LIM alU Ual alU Ual Mu Lim Y a o FCM -1 XP Transponder NAC 0 0 0 FCM -1 XP Transponder NAC C LO-1 o J o o o 0 o ACM -8R qCM /AEM -16AT LED Annunciator Relay Control LDM -32 Custom Graphics Optional 396 channel UDACT Universal Digital Alarm Communicator Transmitter Dual phone lines to Central Station RS -232 Terminal PRN Printer CRT -2 Terminal 1 T r The CPU - 300/400 EIA -232 EIA -485 Port SLC Loop #1 EIA -232 Terminal Port "Terminal Mode" EIA -485 Port (Style 4, 6, or 7) SLC Loop #2 (AFP -400 only) Printer Port ---, \ 11 / _ (Style 4,6, or 7) Slide -in Label EPROM I11111111 1 ON = [I on JOE soon F]IRFA The MPS -400 :::� Main Power Supply L I Resettable _- 24 VDC @ --------------------- `°----°–Jj---°-----°----°----°----°----°–I Pd4Ep RL*IIM d+' W MidIM BAtgWpM� O Tpp�llgl /E� PdMTS 9L=ED 3IEP�d � 911ETlCE �V�ME PESET r'll Tf9T _� �n ---------------------------------- V000000000 m®m ®I 0000000000 0 ®0=01 000000000 ® ®■ 001 ;0000 ®000 ® ®® a0�0 1.25 amps* each* The MPS -400 Main Power Supply 2 non - resettable Resettable 24 VDC circuits 24 VDC @ rated 1.25 amps 1.25 amps* each* AC Power 120/240 VAC (Field Selectable) 0006••• Battery (12 -60 A.H.) 80- Character (2 x 40) Back -Lit LCD Display -- Status LED's �– Control Switches Programming Keypad Flip -Down Door (covers the programming keypad) Form -C Alarm, Trouble, Supervisory, and Security contacts. (3 amps @ 30 VDC) (Note: Supervisory and Security contacts can be converted to alarm contacts.) NAC or Releasing circuits 1 & 2. Class A or Class B, a� �aP::::::::] 24 VDC * e ® ®e ® ®mm amps each.* O_ O �.r • • • 3 *The MPS -400 is a 6 amp power supply. Total power, ;P including internal modules, �H cannot exceed 6 amps. ii 6 6 UZC Coder Input Door Tamper Switch (STS -200) Meter Module Option (MPM -2) Page 4 of 10 — DN -5262 • 10/31/05 NAC or Releasing Circuits 3 & 4. Class A or B, 24 VDC @ 2.5 amps each.* Status/Trouble LEDs Optional Transmitter module (4XTM connector). Intelligent Sensing Intelligent Sensing is a set of software algorithms that provide the AFP- 300/400 with industry- leading smoke detection capability. The development of these sophisticated algorithms are made possible by the close coop- eration between Notifier and System Sensor, the world leaders in fire detection and alarm technology. These complex algorithms require many calculations on each reading of each detector, and are made possible by the very high speed microcomputer used by the AFP- 300/400 (16 -bit RISC Reduced Instruction Set Computer). O Drift Compensation and Smoothing. These al- gorithms (U.S. patent pending) identify and compensate for long -term changes in the analog readings from each smoke sensor. Long -term changes are usually caused Analog by dust accumulation inside the smoke chamber. Drift Reading compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces maintenance re- quirements by allowing the system to automatically per- form the periodic sensitivity measurements required by NFPA. Smoothing filters are also provided by software to remove transient noise signals, usually caused by elec- trical interference. Different smoothing algorithms are used, depending on the sensitivity selection of each de- tector. © Maintenance Warnings. When the drift compensation performed for a detector reaches a certain level, the performance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value, usually indicative of a hardware problem in the detector; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit. The Maintenance Alert level allows maintenance before the performance of the device is compromised. © Sensitivity Adjust. Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automatically between day and night. Nine levels of pre - alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre -alarm operation can be latching or self - restoring, and can be used to activate special control functions that are a subset of the alarm control program. O Self- Optimizing Pre - Alarm. Each detector may be set for "Self- Optimizing" pre - alarm. In this special mode, the detec- tor "learns" its normal environment, measuring the peak analog readings over a long period of time, and setting the pre -alarm level just above these normal peaks. This allows extremely sensitive pre -alarm capability with reasonable protection against non -fire signals. Prealarm Threshold Normal Threshold Time (days) �♦ Awa-4. f © Cooperating Multi- Detector Sensing. A feature of intelligent sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre -alarm o decisions. Using logic algorithms, each sensor can include up a Alarm to two other sensors in its decision. Without statistical sacrifice _ — — — — — — — —� in the ability to resist false alarms, it allows a sensor to increase C) Combined its sensitivity to actual smoke by a factor of almost 2 to 1. Multi- CO 3 sensors detector sensing also allows the combination of ionization with Y photoelectric technology in reaching an alarm decision. p Time (minutes) 5262aw5. f DN -5262 • 10/31/05 — Page 5 of 10 FIELD PROGRAMMING OPTIONS AUTOPROGRAM Autoprogram is a timesaving feature of the 300/400. It is a ROM tSE 3 " special software routine that allows the 300/400 to "learn" what devices are physically connected and automaticallyb .. load them in the program with default values for all param- eters. Requiring less than 30 seconds to run, this routine allows the user to have almost immediate fire protection in .1s. B0 dS 19 MODS 1-2: 93 DETS, 35 MODS a new installation, even if only a portion of the detectors PANE OUTPUTS:24 BELLS: 04 are installed. The routine will find all intelligent detectors and modules, and present them to the installer for edit of the de- fault option selections, if desired. If a device is found that already exists in memory, autoprogram skips over that device (only new devices or missing devices are presented to the installer). Often the installer will perform autoprogram as a first step in a new installation, then upload the program into a PC to add all custom labels and other information, then download from the PC to the 300/400. KEYPAD PROGRAM EDIT The 300/400 has the exclusive feature of full program cre- ation and edit capability from the front panel keypad, while continuing to provide fire protection. The architecture of the 300/400 software is such that each point entry carries its own program, including control -by -event links to other points. This allows the program to be entered with indepen- dent per -point segments, while the 300/400 simultaneously monitors other (already installed) points for alarm conditions. ENTER ; PROO .OFD STAT PASSWORD, THEN tNTE9,"- <ESUAPE1 TO -ABORT),* * * ** 0 =CLR 1 =AUTO 2= POINT 3= PASSWD 4= MESSAGE G =ZONES 6= PL FUNCT 7 =S5?STEM B= GHECIG Pl G In addition to avoiding system shutdown, program edit from the panel keypad has the advantage of not requiring an on -site PC. This can save significant installation time for minor program changes. The 3001400 site - specific program is password protected, and all information is stored in nonvolatile memory. Menu "trees" are provided to lead the trained installer through the program steps without the necessity to refer to the programming manual. VeriFire® Software PC software is available for off -line programming and test utility that can greatly reduce installation programming time, and increase confidence in the site - specific software. VeriFire® is a Windows based program providing techno- logically advanced capabilities to aid the installer. The in- staller may create the entire program for the 300/400 in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel. The program includes error checks for common program- ming mistakes, such as an input point that does not activate any outputs, or an output point that is not linked to any inputs. It also includes a simulation routine that will list all of the output points that are activated by a particular input point (alternatively, it will list all the input points that are linked to a particular output). Although this does not eliminate on -site testing, it greatly increases confidence in the final installa- tion. For example, a 200 -input and 100 - output point system, without using the software, could require 20,000 test ob- servations to verify all possible 1/0 links. The software includes a compare routine, pictured at right, that can also greatly help the installer. When a new program is created, it may be compared with a previous version and differences are highlighted. If the program is modified from the panel keypad, it may be uploaded into the PC, and com- pared with the previous version stored on disk. The identifi- cation of program differences greatly helps the installer in testing the installation. NFPA 72 requires that reacceptance test of a fire alarm system be performed on 100% of all points that are "known" to be modified. The software allows the installer to determine the exact points that are changed. 5262ve2.Dt Page 6 of 10 — DN -5262. 10/31/05 ysien PrRartreters , rro.Mrm+IMP +MN: K; PLACE YOUR dB CHAR, CUSTOM MESSAGE MERE tyi t_ ' ' .- t P ....... .... .. �s wm SAenee Tl�M.G'EQ =9BU yt {�p' -.. . Iaa VaAi- Taw W38 at Ode f F ed BSeA: r T + LOCAL V 5262ver1.tit , .. .. t_ ' ' .- t P ....... .... .. BASIC EQUIPMENT PACKAGES There are two packages available to configure an AFP -300 4 - or 400 system. The standard model, BE -300 or BE -400, is designed to mount in a NOTIFIER full -sized cabinet in the CAB -3/4 Series. The BE -300AA or BE -400AA is a minia- ture package designed for a smaller cabinet, the CAB - 400AA. Order one of the following BE packages: BE -400: Base Equipment includes the CPU (2 loops) module (CPU -400), an 80- character display, program- ming keypad, MPS -400 main power supply, installation instructions, chassis and required hardware. Order CAB -31-4 Series cabinet separately. BE- 400AA: Base Equipment for use with CAB -400AA mini cabinet. It is similar to BE-400 but for use in smaller cabinet. Includes MPS -40ORB and transformers. Supports one output option module. Order CAB -400AA cabinet separately. BE�300: Base Equipment includes the CPU (hoop) module (CPU -300), an 80- character display, program- ming keypad, MPS -400 main power supply, installation instructions, chassis and required hardware. Order CAB -31-4 Series cabinet separately. BE- 300AA: Base Equipment for use with CAB -400AA mini cabinet. It is similar to BE -300 but for use in smaller cabinet. Includes MPS -40ORB and transformers. Supports one output option module. Order CAB -400AA cabinet separately. CAB -3/4 Series: The AFP - 3001400 utilizes CAB -31-4 Series cabinets. See data sheets DN -3549 and DN- 6857. SYSTEM MODULES The AFP- 300/400 includes the ability to communicate with up to 8 conventional modules each with up to 8 circuits. Any mix of notification, relay, speaker, or telephone may be used. Choose any combination of up to eight output modules: ICMACE, CRM /CRE, DCM-4 or VCMNCE. ICM-4: Notification Appliance Circuit Module, provides four Style Y or Style Z alarm Notification Appliance Circuits. Maximum signaling current is 3.0 amps per circuit or 6.0 amps per module, subject to power supply _ mm limitations (includes auxiliary power 3 mm harness, ELRs and slide -in labels). E mm Includes OWOFF controls and ON /OFF LEDs See ICM-4 data sheet DN- 0010. ° ICE-4: Notification Appliance Circuit Expander, expands ICM -4 to provide a total of eight (8) Style Y or Style Z alarm Notification Appliance Circuits. Circuit ratings are same as 1CM -4. ai Msi iN i� ■ ■� (Maximum of one per ICM -4.) May also be = used to add four Notification Appliance Circuits to VCM-4. m See ICE-4 data sheet DN -0010. CRM-4: Control Relay Module, four (4) Form - C relay contacts, rated at 5.0 A, 120 VAC or 28 VDC (resistive) per circuit. Includes manual ON /OFF controls and LEDs. See CRM-4 data sheet DN -0461. € m o �m CRE-4: Control Relay Expander, expands CRM -4 to provide a total of eight (8) Form -C ■ ■ ■ ■1 relay contacts. (Maximum of one per CRM -4.) een= e I May also be connected to add four relays to ICM-4, TCM -2, TCM-4, or VCM -4. See CRE-4 data sheet DN -0461. ° VCM-4: Voice Control Module provides four Style Y or Style Z speaker "" 21 3 circuits, eight manual select switches M and indicators, slide -in labels, and plug - in terminal blocks. Move jumper to convert to telephone circuits with remote���°� ring signal and local call -in flash. May be expanded to 8 circuits with VCE -4, ICE - 4, or CRE-4. VCE-4: Voice Control Expander 3i9!9 i�li!i adds four circuits to VCM -4. ■ ■ ■� m Note: VCM-4 / VCE -4 combing- a m m tion must be 8 speaker or 8 m m E phone circuits. ,.., m o DCM-4: Dual Channel Module provides four Style Y or Style Z speaker circuits plus four channel A/B select relays. Not expandable. OTHER OPTION MODULES ARM-4: Auxiliary Relay Module, four (4) Form -C relays controlled by a relay module (CRM -4 or CRE -4). N.O. contacts 3 rated 20 amps, N.C. contacts rated 10 E amps at 125 VAC and 30 VDC. Maximum . of one for each CRM-4 or CRE-4. See ARM-4 data sheet DN -0461. VCC -1: Voice Control Center. Provides a variety of user selectable tones on a single channel. Up to two different tones or messages may be selected on a single channel. Also provides optional digital voice message capability and on -site programmable voice messages. Includes Audio Message Generator (AMG -1) microphone, cables, dress panels, and instructions. VTCC -1: Voice/Telephone Control Center. Provides all that the VCC -1 provides plus two -way Fire Fighter's Telephone (FFT -7) capability. TCC-1: Telephone Control ® ® ® ® ®® Center. Provides a stand - • - o ■. alone two -way Fire Fighter's ., 1ol IE . "m telephone (FFT 7S). Includes a ®8 © o cables, dress panel and instructions. 3 AMG -E: Audio Message E l i Generator (without micro- N phone)). Order in addition to VCC-1 or VTCC-1 if 3224a30.wmf two- channel system is required. FFT- 7/FFT -7S: Fire Fighters �� ■� 4 i Telephone control with O master handset. AA -30: Audio Amplifier - 30 watts. Switch -mode power. Includes • o ® ® . amplifier and audio DN -5262 • 10/31/05 — Page 7 of 10 input supervision, backup input, and automatic switchover, power supply, cables. AA- 120 1AA- 100.Audio Amplifier provides up to 120 watts of 25 VRms audio power for the AFP -400. The amplifier contains an integral chassis for mounting to a CAB -B31 -B4, - C31- -C4, or - D31- -D4 backbox (consumes one row). Switch -mode power. Includes audio input and amplified output supervision, backup input, and automatic switchover to backup tone. Order the AA -100 for 70.7 VRms systems and 100 watts of power. VROM -(n): Factory- programmed message for installation in AMG -1. Provides up to 24 seconds of evacuation message on nonvolatile memory chip. Choose one of many standard messages available. Up to two of these messages may be installed in one AMG. Includes VROM, instructions for installation and operation, and written text of message, 3576vrom.wmi XPIQ: Intelligent transponder designed for multi- channel applications. See XPIQ data sheet DN -6823. APS -6R: Auxiliary Power Supply ° (expander). Provides up to 6.0 °o °® amperes of regulated power for e° compatible Notification appliance circuits. Includes battery input and transfer relay, and overcurrent protection. Mounts on one of four a °® positions on a CHS -4L or CHS -4 ° chassis. See APS-61? data sheet DN- ° 5952, 5952cov.wmf FCPS 24: The FCPS -24 is a remote 6 -amp (4 -amp continuous) repeatedpower supply. See FCPS -24 data sheet DN -5132. FCPS - 24561-2458: Remote six -amp and eight -amp power supplies. See FCPS 2456✓ -2458 data sheet DN -6927. UZC 256: Programmable Universal Zone Coder provides positive non - interfering successive zone coding. Microprocessor - controlled, field - programmable from IBM- compatible PCs (requires programming kit). See UZC 256 data sheet DN -3404. LCD- 801LCD -80TM: 80- character, backlit LCD display. Mounts up to 6,000 ft. from panel. Up to 32 per AFP- 400. See LCD -80, LCD -80TM data sheet DN -3198. Page 8 of 10 — DN -5262 • 10/31/05 ACS: Annunciator Control Modules ACM -16AT, AEM -16AT, ACM -32A, and AEM -32A. See ACS data sheet DN -0524. AFM: Annunciator Fixed Modules AFM -16A, AFM -16AT, and AFM -32A. See AFM data sheet DN -0056. LDM: Lamp Driver Modules LDM -32, LDM -E32, and LDM - R32. See LDM data sheet DN -0551. ACM -817: Remote Relay Module with eight Form -C contacts. Can be located up to 6,000 ft. from panel on four wires. See ACM-81? data sheet DN -3558. RPT -485: Repeats EIA -485 over twisted pair or converts to fiber -optic medium. See RPT data sheet DN -4737. XP: The XP Series Transponder provides conventional monitor and control points. See XP data sheet DN -0759. E 3 • CHS-4: Chassis for mounting up to four APS -6R. CHS -4L: Low - profile four- •• •• position Chassis. Mounts two AA -30 amplifiers or one AMG - E and one AA -30. CHS -4114: Expansion b262&4L.wmf Chassis. Mounts up to four modules. Includes CHS-4, MP -1 (Module Dress Panel), and Expander Ribbon Cable. DP -1: Blank Dress panel. Provides dead -front panel for unused tiers or to cover AA- 30, AA -120, or AMG -E. = w 5262dpt.wmf CAB-4 Series: The CAB-4 Series cabinets are fabricated from 16 -gauge steel with unique full -front LEXAND reverse silk- screened for durability. The cabinet assembly consists of two basic parts: a backbox (SBB =4), and a locking door (DR-_4 )that may hinge right or left. Cabinets are arranged in four (4) sizes, A through D (B [two -tier] is pictured at right). A trim ring option is available for 5671 cab3.wmf semi -flush mounting. See CAB -4 Series data sheet DN -6857. LEXANO is a registered trademark of GE Plastics, a subsidiary of General Electric Company. CAB- 400AA: Provides small cabinet for CPU -400 and MPS- 400RB. Use with BE -400AA only. Space for one (only) output circuit module plus expander. MPS -400: Power Supply module. The MPS -400 includes 4 Notification Appliance Circuits (NAC) that can connect four Class A (Style Z) or Class B (Style Y) circuits. The NAC also can be used for Releasing applications. Includes four built -in system relays (alarm, trouble, security, and supervisory). For BE -400 replacement only. The MPS -400 is included in the BE kits. MPS- 40ORB: MPS -400 PC board only. Less transformers and mounting chassis. AGENCY LISTINGS AND APPROVALS See the first page of this catalog sheet for listing agencies and file numbers. These listings and approvals apply to the basic AFP -300 or AFP -400 control panel. In some cases, certain modules may not be listed by certain ap- proval agencies, or listing may be in process. Consult fac- tory for latest listing status. The AFP- 300/400 is UL Listed, per Standards 864 (Fire) and 1076 (Burglary). It meets NFPA 72 Local, Auxiliary, Remote Station, Proprietary, and Emergency Voice /Alarm Fire Sys- tem Requirements. SPECIFICATIONS • Primary input power, 120 VAC, 50/60 Hz, 3.0 Amps. • Total output 24 V power - 6.0 A." • Standard Bell circuits (4) per MPS -400 - 2.5 A each. • Four -wire detector power - 1.25 A. • Two non -reset regulated power outputs - 1.25 A each. • Battery charger range: 12 AH - 60 AH. (Use separate BB -55 cabinet for 55160 AH batteries.) • Charge high rate: 29.1 V. Float Rate: 27.6 V. Note: The MPS -400 has a total of 6.0 Amps of available power. This is shared by all internal modules and each MPS -400 circuit. SYSTEM CAPACITY: AFP -400 • Intelligent Signaling Line Circuits . ..............................2 • Intelligent Detectors .................... ............................198 • Addressable monitor /control modules ..................198 • Programmable internal hardware and output circuits (four standard) ...........................68 • Programmable software zones ... .............................99 • Special Programming zones ....... .............................14 • Programmable remote relay /annunciator points..... 99 • LCD -80 annunciators per system (observe power) 32 • ACS annunciators per system ... 10 Address x 64 points SYSTEM CAPACITY: AFP -300 • Intelligent Signaling Line Circuits . ..............................1 • Intelligent Detectors ..................... .............................99 • Addressable monitor /control modules ....................99 • Programmable internal hardware and output circuits (four standard) ...........................68 • Programmable software zones ... .............................99 • Special Programming zones ....... .............................14 • Programmable remote relay /annunciator points..... 99 • LCD -80 annunciators per system (observe power) 32 • ACS annunciators per system ... 10 Address x 64 points CONTROLS AND INDICATORS Program Keypad: QWERTY type (keyboard layout). 8 LED indicators: AC Power; Fire Alarm; Pre - Alarm; Secu- rity Alarm; Supervisory Signal; System Trouble, Disabled points, Alarm Silenced. Membrane Switch Controls: Acknowledge /Step; Silence; Evacuate; System Reset; Lamp Test. LCD Display: 80 characters (2 x 40) with long -life LED back- light. COMPATIBLE DEVICES, EIA -232 Port PRN -5: 80- column printer. See DN -6769. PRN -6: 80- column printer. See DN -6956. VS4095/S2: Printer, 40 column, 24 V. Mounted in external backbox. See DN -3260; order from Keltron, Inc. CRT -2: Video display terminal. See DN -3756. NAM -232W: Wire peer -to -peer NOTI•FIRE•NETTm net- work interface module. See DN -5331. NAM -232F: Fiber peer -to -peer NOTI•FIRE•NETTm net- work interface module. See DN -5331. COMPATIBLE DEVICES, RS -485 Port ACS Series: Remote Serial Annunciator /Control systems. See DN -0524. FDU -80: Remote LCD display, 80 characters. See DN -6820. LCD -80: Remote LCD display, 80 characters. See DN -3198. LDM Series: Remote custom graphic driver modules. See DN -0551. ACM -8R: Remote relay module, 8 Form -C relays. See DN -3558. NIB -96: Network Interface Board. See DN -0597. RPT -485 Series: Repeater, isolator and /or fiber optic mo- dem. See DN -4737. UDACT: Universal Digital Alarm Communicator Transmit- ter. See DN -4867. UZC -256: Zone Coder, up to 256 programmable codes. See DN -3404. COMPATIBLE INTELLIGENT DEVICES BEAMHK: Heating kit for transmitter /receiver unit of FSB - 200(S) below. See DN -6985. BEAMHRK: Heating kit for use with the reflector of FSB - 200(S) below. See DN -6985. BEAMLRK: Long -range accessory kit, FSB- 200(S) below. BEAMMRK: Multi -mount kit, FSB- 200(S) below. BEAMSMK: Surface -mount kit, FSB- 200(S) below. FSB -200: Intelligent beam smoke detector. See DN -6985. FSB -20OS: Intelligent beam smoke detector with integral sensitivity test. See DN -6895. FSI -851: Low - profile ionization detector. See DN -6934. FSP -851: Low - profile photoelectric detector. See DN -6935. FSP -851T: Low - profile photoelectric detector with 135 °F (57 °C) thermal. See DN -6935. FST -851: Thermal detector 135 °F (57 °C). See DN -6936. FST -851R: Thermal detector 135 °F (57 °C) with rate -of -rise. See DN -6936. FST -851 H: 190 °F (88 °C) high- temperature thermal detec- tor. See DN -6936. FSD -751 PL: Low -flow photo duct detector with housing. See DN -6955. FSD -751 RPL Low -flow photo duct detector with relay and housing. See DN -6955. FAPT -851: Acclimate PIusTM low- profile multi- sensor de- tector. See DN -6937. FSH -751: HARSHTm Hostile Area Smoke Head. See DN -6875. FSL -751: VIEW@ laser photo detector, will replace LPX- 751. See DN -6886. LPX -751: Low - profile VIEW@ laser photo detector. See DN -5306. DN -5262 • 10/31/05 - Page 9 of 10 NBG -12LX: Addressable pull station, visible LED. See DN -6726. B224RB: Low - profile relay base. B224BI: Isolator base for low- profile detectors. B71OLP: Low - profile base. Standard U.S. style. B501: European - style, 4" (10.16 cm) base. B501 BH: Sounder base, includes B501 base above. FMM -1: Monitor module. See DN -6720. FMM -101: Monitor module, miniature. See DN -6720. FDM -1: Monitor module, dual, two independent Class B cir- cuits. See DN -6720. FZM -1: Monitor module, two -wire smoke detectors. See DN -6720. FCM -1: Control module. See DN -6724. FRM -1: Relay module. See DN -6724. ISO -X: Isolator module. See DN -2243. XP Series: Transponder. See DN -0759. XP5 -M: Transponder, five monitor points. See DN -6625. XP5 -C: Transponder, five control points or Form -C relays. See DN -6625. Page 10 of 10 — DN -5262. 10/31/05 XP6 -C: Six - circuit supervised control module. See DN -6924. XP6 -MA: Six -zone interface module; connects intelligent alarm system to two -wire conventional detection zone. See DN -6925. XP6 -R: Six -relay (Form -C) control module. See DN -6926. XP10 -M: Ten -input monitor module. See DN -6923. XPIO: Intelligent quad transponder. See DN -6823. OTHER ACCESSORIES 4XTM: Plug -in Transmitter Module. Provides municipal box and remote station connection. BAT Series: Batteries; the AFP- 300/400 battery range is 12 AH to 60 AH. See DN -6933. ROM- AFP400: Panel software upgrade kit. Includes latest factory software (consult factory). BB- 55(F): Battery Box (required for 55160 AH). Order "F" suffix for red cabinet. VeriFire -CD: Programming kit for PC. Includes CD, cable, and instructions. VeriFire -CDUG: Same as VeriFire -CD above except it does not include the cable. Other options as listed in previous sections. AES 77441' 7788F.gxd 8/24/2009 11:04 AM Page 1 ` 4 WOOF ; 7744F/7788F.o.oz ES�lntefflNet CORPORATION For Alarm Monito6ng RF Subscriber Unit UL Fire, AA Burglary and NFPA -72 Compliant UL Listed UL Listed Central Station Remote Station 864 Ed. 9, 827, 1610, 365,681 CSFM NFPA RF Section 8.6.3.5 Advanced Wireless Alarm Monitoring The 7744F/7788F smart subscriber unit links an alarm panel to an alarm monitoring central station. This 2 -way transceiver and repeater in one is housed in a full size locking steel cabinet for superior performance. The 7744F/7788F supports a wide range of inputs such as NO /NC /EOL and direct voltage. It automatically senses wire and antenna cuts, and monitors battery and AC power status. Advanced status reporting, self- diagnostics and a built -in power supply make the 7744F/7788F the first choice for all wireless alarm communication needs. Full Data for Fire and Burglary Use with the optional Firetap for full fire data or the IntelliTap for full fire and burglary data. 7744F — 4 reversing FireTap 7770 polarity inputs plus 4 IntelliTap 7067 programmable EOL inputs NEMA 4 Enclosure 77881' ROOM""" 'E01.. inputs *01 zones High Gain Antenna Additional Back Up Battery Available in Burglary Beige or Fire Red • Options for Full Data for Fire and Burglary • Available in 7744F & 7788F Zone Configurations • Built -in Power Supply and Battery Charger • Local Annunciation Options on Board C YL IIS +yva'r `�J nrMoaa LISTED �VEWA NM Wireless mesh networking is an innovative technology adopted by many industries with applications that need to communicate data over a large geographic area with a high level of reliability at a low total cost of ownership. The advanced design and 2 -way communications capability provides easy installation, expansion, and management when compared to altemative communication methods, both wired andJ7reless: i AES_7744F 7788F.gxd 8/24/2009 11:04 AM Page 2 7744F/7788F RF Subscriber Unit Technical Specifications Radio Standard CSAA frequency ranges: 450 -470 MHz and 130 -174 MHz, VHF and UHF. Others available Standard Output Power 2 watts (requires FCC license) Power Input 16.5 VAC, 40VA UL listed Class II transformer required Voltage 12 VDC nominal Current 175mA standby; 800mA transmit Alarm Signal Inputs • 4 individually programmable Zones: NO /NC /EOL, trouble restore • RS -232 • Reversing voltage (7744F only) 12 or 24 VDC Operating Temperature Range 0° to 50 'C, 32° to 122 °F Storage Temperature Range -10° to 60 °C, 14° to 140 °F Relative Humidity Range 0 -85% RHC non - condensing Back up Battery 12V, 7.5 AHr Low Battery Reporting 22.5- minute test cycle AC Status Reports to central station after approximately 60 minutes without AC power, reports power restored after approximately 60 minutes of restored power. programmable from 60 to 180 minutes Antenna Cut (local reporting) Form 'C' Contact 1 AMP Size 13.25 "H x 8.5 "W x 4.3'D 34cm x 21.5cm x 11 cm Weight 6.4 Ibs, 2.9 Kilograms (excluding battery) Colors Available in standard Burglary Beige or Fire Red Please specify when ordering Available Options • 7788F RF subscriber unit with 8 EOL inputs • 7744F RF subscriber unit with 4 EOL inputs and 4 reverse polarity inputs • 7770 - FireTap • 7067 - IntelliTap • NEMA 4 Enclosure Please specify when ordering AES - lntelliNet°` is the industry leader in delivering high quality wireless mesh networks to the fire and security industry in commercial, corporate, government, and educational applications with its broad line of products and advanced network management tools. Users of AES - lntelliNet networks have gained significant revenue, communications, and cost advantages while meeting the high standards of reliability required for the fire and security industry. AES - lntelliNet alarm monitoring systems are deployed at hundreds of thousands of locations in over 130 countries. AgtL- IN V AES Intel %Net CORPORATION For Alarm Monitoring For more information Call 800 -AES -NETS (800 - 237 -6387) AES Corporation 1 285 Newbury Street I Peabody, MA 01960 USA Tel. +1 978 - 535 -7310 1 Fax +1 978 -535 -7313 1 Email info@aes- intellinet.com Web www.aes- intellinet.com Available configurations • 7788F, 8 EOL inputs • 7744F, 4 EOL inputs w/4 reverse polarity inputs i FOPS- 24S6(C /E) & FCPS- , 2458(C /E) 6- & 8 -Amp 24 -Volt Remote Power SuonlieS General The FCPS -24S6E (6 -amp) and FCPS -24S8E (8 -amp) are remote power supplies with battery charger. The FCPS- 24S61- 2458 may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may be used as stand -alone supplies. Pri- mary applications include notification appliance (bell) circuit (NAC) expansion (to support ADA requirements and NAC syn- chronization) or auxiliary power to support 24 volt system accessories. The FCPS -24S6/ -2458 provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either four Class B (Style Y) or Class A (Style Z, with ZNAC -4 option module). Alternately, the four outputs may be configured as all non - resettable, all resettable or two non - resettable and two resettable. The FCPS -24S6/ -2458 also contains a battery charger capable of charging up to 18 AH batteries. FCPS -24S6C & FCPS -24S8C are ULC- listed. NOTE. Unless otherwise specified, the terms FCPS -2456 and FCPS -24S8 used in this document refers to the standard FCPS - 2456 and FCPS -2458, FCPS -24S6C and FCPS - 24S8C, the FCPS -24S6E and FCPS -24S8E Features • UL- Listed NAC synchronization using System Sensor, Wheelock, or Gentex "Commander2" appliances. • Operates as a "sync - follower" or as a "sync- generator" (default). See note on page 2. • Contains two fully - isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped perma- nently "ON" (stand -alone mode). • Four Class B (Style Y) or four Class A (Style Z, with ZNAC -4 module) NACs. • 6 -amp (FCPS -24S6) or 8 -amp (FCPS -2458) full load out- put, with 3 amps maximum /circuit, in NAC expander mode (UL 864). • 4 -amp (FCPS -24S6) or 6 -amp (FCPS -24S8) continuous output in stand -alone mode (UL 1481). • Compatible with coded inputs; signals passed through. • Optional power - supervision relay (EOLR -1). • In stand -alone mode, output power circuits may be config- ured as: resettable, (reset line from FACP required), non - resettable, or a mix of two and two. • Fully regulated and filtered power output - optimal for pow- ering four -wire smoke detectors, annunciators, and other system peripherals requiring regulated /filtered power. • Power - limiting technology meets UL power - limiting require- ments. • Form -C normally - closed trouble relay. • Fully supervised power supply, battery, and NACs. • Selectable earth fault detection. • AC trouble report selectable for immediate 2 -hour delay. • Works with virtually any UL 864 fire alarm control which uti- lizes an industry- standard reverse - polarity notification cir- cuit (including unfiltered and unregulated bell power). • Requires input trigger voltage of 9 - 32 VDC. • Self- contained in compact, locking cabinet - 15 "H x 14.5 "W x 2.75 "D (cm: 38.1 H x 36.83W x 6.985D). dn- 6927:a NOTIFIER� by Honeywell Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter- ies. Battery charger may be disabled via DIP switch for applica- tions requiring larger batteries. Fixed, clamp -type terminal blocks accommodate up to 12 AWG (3.1mm2) wire. Specifications Primary (AC) Power: • FCPS - 24S6C/- 24S8C: 120 VAC, 60 Hz, 3.2A maximum. • FCPS - 24S6E/ - 24S8E: 240 VAC, 50 Hz, 1.6A maximum. • Wire Size: minimum #14 AWG (2.Omm2) with 600 V insula- tion. Control Input Circuit: • Trigger Input Voltage: 9 to 32 VDC. • Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V). Trouble Contact Rating: 5 A at 24 VDC. Auxiliary Power Output: Specific application power 500 mA maximum. Output Circuits: • +24 VDC filtered, regulated. • 3.0 A maximum for any one circuit. • Total continuous current for all outputs (stand -alone mode): — FCPS -24S6: 4.0 A maximum. — FCPS -24S8: 6.0 A maximum. • Total short -term current for all outputs (NAC expander mode): — FCPS -24S6: 6.0 A maximum. — FCPS -24S8: 8.0 A maximum. Secondary Power (Battery) Charging Circuit: • Supports lead -acid batteries only. • Float- charge voltage: 27.6 VDC. dn- 6927:a • 04/30/09 — Page 1 of 2 Maximum current charge: 1.5 A. Maximum battery capacity: 18 AH. Applications Example 1: Expand notification appliance power an additional 6.0 A (FCPS -24S6) or 8.0 A (FCPS - 2458). Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC -4). For example, the FACP notification appliance circuits will activate the FCPS when reverse - polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit. Example 2: Use the FCPS to expand auxiliary regulated 24- volt system power up to 4.0 A (FCPS -24S6) or up to 6.0 A (FCPS - 2458). Both resettable and non - resettable power options are available. Resettable outputs are created by con- necting the resettable output from the FACP to one or both of the FCPS inputs. Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expanding system architecture in various applications. For example, an addressable control module is used to acti- vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable control module. *NOTE. Addressable FACPs are capable of locating control and monitor modules at distances of up to 12,500 feet (3,810 meters). Sync Follower /Generator Note In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS -24S6/ -2458 can track (i.e. "follow ") the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS. When the FCPS -24S6/ -2458 is configured (via DIP switch set- tings) as a "sync follower;' the FCPS's NAC outputs track the strobe synchronization pulses present at the FCPS's sync input terminal. The pulses originate from an upstream FACP or other power supply. When the FCPS -24S6/ -2458 are configured (via DIP switch settings) as a "sync generator," the FCPS's sync input termi- nals are not used. Rather, the FCPS is the originator of the strobe synchronization pulses on the FCPS's NAC outputs. In "sync generator" mode, the sync type (System Sensor, Whee- lock, or Gentex) is selectable via DIP switch settings. Standards and Codes The FCPS -24S6 and FCPS -2458 comply with the following standards: • NFPA 72 National Fire Alarm Code. • UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode). • UL 1481 Power Supplies for Fire Alarm Systems. Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed: S635, S674 • ULC Listed: S635 (FCPS -24S6C & FCPS- 24S8C) • CSFM Approved: 7315 - 0028:225 • MEA: 299 -02 -E • FM Approved Ordering Information FCPS -24S6: 6.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15 "H x 14.5 "W x 2.75 "D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. FCPS - 24S6C: Same as above, ULC - listed. FCPS- 24S6R: Same as FCPS -2456 with red enclosure. FCPS- 24S6E: 6.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15 "H x 14.5 "W x 2.75 "D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. FCPS -24S8: 8.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15 "H x 14.5 "W x 2.75 "D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. FCPS -24S8C Same as above, ULC - listed. FCPS- 24S8R: Same as FCPS -2458 with red enclosure. FCPS- 24S8E: 8.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15 "H x 14.5 "W x 2.75 "D [cm: 38.1 H x 36.83W x 6.985D]), and installation instructions. ZNAC -4: Class A (Style Y) NAC option module. EOLR -1: 12/24 VDC end -of -line relay for monitoring four -wire smoke detector power. BAT-1270: Battery, 12 -volt, 7.0 AH (two required, see BAT Series data sheet DN- 6933). PS -1270: Battery, 12 -volt, 7.0 AH (two required, see PS Series data sheet DN -1109) System Sensor@ and NOTIFIERO are registered trademarks of Honeywell International Inc. 02009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. 1S0 9001 This document is not intended to be used for installation purposes. We try to keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. ENIIFA911i 8 MAMFA611MM All specifications are subject to change without notice. IVALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484 -7161, FAX: (203) 484 -7118. www.notifier.com Page 2 of 2 — dn- 6927:a • 04/30/09 COOPER Notification Weatherproof Appliances - Series AH Audibles, AS Audible Strobes, MT Multitone Strobes, RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories �A, all :I !] Description: Designed for life safety, performance and reliability, Cooper Notification's Wheelock cost effective weatherpoof notification appliances include: Weatherproof Appliances Series Strobes Horn Strobes Horns Multitone Horn Strobes Multitone Horns Speaker Strobes Speakers RSSWP ASWP AH -24WP, AH -12WP MTWP MT ET70WP ET -1010 All strobe models are UL dual listed - meeting both UL1638 and UL1971 requirements. As dual listed appliances, these weatherproof strobes, horn strobes and speaker strobes are listed for outdoor applications under UL 1638 as well as under UL 1971, the Standard for Safety Signaling Devices for Hearing Impaired. With an extended temperature range of —31 °F to 150 °F ( -35 °C to 66 °C), Wheelock weatherproof appliances meet or exceed UL outdoortest requirements for rain, humidity and corrosion resistance while providing multiple strobe intensity options, including the highest strobe ratings available for area coverage per NFPA 72 strobe spacing tables (up to 185 candela forwall mounting and 177 candela for ceiling mounting). To enable weatherproof mounting, Cooper Notification provides the industry's widest choice of mounting options for surface or unique semi -flush installation. Models are available for surface mounting to Wheelock weatherproof backboxes on walls or ceilings. The optional WP -KIT allows the weatherproof backboxes (IOB, WPBB or WPSBB) to be mounted to a recessed electrical box for concealed conduit installation. For semi -flush installation, the WPA* and WFPA* kits allow a customer to mount the weatherproof appliances to a recessed electrical box without the need for an external weatherproof backbox. See the Backboxes, Plates and Gaskets Table on page three of this document for a summarization of these mounting options and the required accessories. � � FM I L ® M � "� EA APPROVED E5946 151 -92 -E 7125 -0785:131 (ASWP) S5391 7125 -0785:146 (ET70WP) S2652 7125 -0785:156 (MTWP) 7300 -0785:154 (RSSWP) All models may be synchronized using the Wheelock DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. The horn output of horn strobes can be independently controlled on 2 -wire circuits using the Wheelock patented sync protocol. MTWP horn strobe models are 4 -wire appliances; the strobes can be synchronized while the audible can be connected to a coded fire alarm system or can be set to produce any of eight selectable tones. Features: • Approvals include: UL Standards 1971, 1638, 464 and 1480 California State Fire Marshal (CSFM), New York City (MEA), Factory Mutual (FM), Chicago (BFP) and ULC . See agency approvals by model number on page two of this document • Compliance with the following requirements: NFPA, UFC, ANSI 117. 1, OSHA Part 29, 1910.165, ADA • Weatherproof with extended temperature range of -40 °F to 150 °F (-40 *C to 66 °C)* • Dual Listed strobe models (UL 1638 and UL 1971) • Industry's highest strobe candela options • Synchronize using the Wheelock Sync Modules or panels with built -in Wheelock Patented Sync Protocol • Models with field selectable tone, dBA and candela settings • Wall or ceiling mounting options • Surface of semi -flush mounting • IN /OUT wiring termination accepting two #12 -18 AWG wires at each terminal The series RSSWP, ASWP, AH -24WP, MTWP- 2475W, and MT -12/24 have UL / ULC approval down to -40 °F. The ET -1010 and ET70WP have UL approval down to -40 °F. The AH -12WP has UL approval down to -31 °F. DOTE: All CAUTIONS and WARNINGS are identified by the symbol A.. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILiJRE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU ANDJOR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range. • All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table. Strobe Candela Ratings Order Code Strobe Order Code RSSWP- 2475W -FR Red 9013 RSSWP- 2475C -FR Red 4338 RSSWP- 2475W -FW White 3034 RSSWP - 2475C -FW White 4446 RSSWP - 24MCWH -FR Red 5161 RSSWP - 24MCCH -FR Red 5167 RSSWP - 24MCWH -FW White 5165 RSSWP - 24MCCH- FWWhite 5187 Audible Strobe 0.340 0.335 Audible Strobe 185 ASWP- 2475W -FR Red 9012 ASWP - 2475C -FR Red 4251 ASWP - 24MCWH -FR Red 5137 ASWP - 2475C -FW White 4502 ASWP - 24MCWH -FW White 5140 ASWP - 24MCCH -FR Red 5149 Multi -tone Strobe 177 73 ASWP - 24MCCH -FW White 5157 MTWP - 2475W -FR Red 8420 Multi -tone Strobe 185 MTWP - 2475W -FW White 3112 MTWP - 2475C -FR Red 4457 MTWP - 24MCWH -FR Red 5132 MTWP - 2475C -FW White 4478 MTWP- 24MCWH -FW White 5134 MTWP - 24MCCH -FR Red 5102 Speaker Strobe - X MTWP- 24MCCH -FW White 5122 ET70WP- 2475W -FR Red 9077 Speaker Strobe ET70WP- 2475W -FW White 3179 ET70WP- 2475C -FR Red 4452 ET70WP- 24185W -FR Red 4885 ET70WP- 2475C -FW White 4454 ET70WP- 24185W -FW White 4891 ET70WP- 24177C -FR Red 4845 ET70WP- 24135W -FR Red 4872 ET70WP- 24177C -FW White 4859 ET70WP- 24135W -FW White 4875 ET70WP- 24115C -FR Red 4550 ET70WP -2475 X ET70WP- 24115C -FW White 4732 UL Max. Current (Audible) Candela Ratings Series UL 1971 UL 1638 @ 77 -F UL 1638 e° -40 °F RSS, ET70WP and MTWP UL Max Current Strobe Only) ASWP High Med Low 2475 30 ** 180 115 0.138 0.168 0.155 0.150 MCWH 135 135 56 0.300 0.355 0.340 0.335 0.034 185 1 185 77 1 0.420 0.480 0.465 0.460 MCCH 115 115 47 0.300 0.355 1 0.340 0.335 Hi /Lo 177 177 73 0.420 0.480 1 0.465 0.460 24185 185 185 77 0.420 * *Wall mount rating only 24177 177 177 73 0.420 UL Max. Current (Audible) MTWP /MT 24 VDC MT 12 VDC BA HI STD HI STD Horn 0.108 0.044 0.177 0.034 Bell 0.053 0.024 0.095 0.020 March Time 0.104 0.038 0.142 0.034 Code 3 Horn 0.091 0.035 0.142 0.034 Code 3 Tone 0.075 0.035 0.105 0.021 Slow Whoop 0.098 0.037 0.142 0.035 Siren 0.104 0.036 0.152 0.030 Hi /Lo 0.057 0.025 0.114 0.026 Wall or Ceiling Mount E a MT AH ET -1010 Audible Order Code AH- 24WP -R Red 7416 AH- 12WP -R Red 7415 Horn MT- 12/24 -R Red 5023 Speaker ET- 1010 -R Red 3135 ET- 1010 -W White 3137 UL Max. Current AH 24 VDC 12 VDC High (99) dBA 0.080 0.192 Med (95) dBA 0.043 0.108 Low (90) dBA 0.021 0.058 UL Reverberant dBA @ 10 Feet Wafts 1/8 1/4 1/2 1 2 4 8 ET -1010 77 80 83 86 87 92 94 ET70WP 78 81 84 871 90 93 95 Model Number Agency Approvals Strobe UL MEA CSFM FM BFP RSSWP -2475 X X X X - RSSWP- 24MCWH X - X - RSSWP- 24MCCH X - X - Audible Strobe ASWP -2475 X X X X X ASWP -MCWH X - X - ASWP -MCCH X - X Multitone Strobe MTWP -2475 X X X X - MTWP -MCWH X X MTWP -MCCH X - X - Horns /Audibles AH -24WP X X X X X AH -12WP X X X X X MT -12/24 X X X X X Speaker Strobe ET70WP -2475 X X X ET70WP -185 X X X ET70WP -177 X - X X ET70WP -115 X X X ET70WP -135 X - X X 1 A Mounting Accessories WFPA Gasket Kit Backboxes, Plates, Gasket Kits Order Code WP -KIT Exposed Conduit 4486 Flush Plates WPSBB WPSBB + WP -KIT WFPA -R Red 4698 WFPA -W White 4701 WFP -R Red 4696 WFP -W White 4697 Backboxes ET -1010 Speakers WBB 10B -R* Red 5046 10B -W* White 5047 WPSBB-R* Red 9751 WPSBB -W* White 3033 WPBB -R* Red 9014 WPBB -W* White 4692 WBB -R Red 2959 WBB -W White 2960 Wiring Diagrams JOB WPSBB WPBB WBB Mounting Options: Backboxes, Plates, Gasket Kits Surface Mount Flush Mount Exposed Conduit Concealed Conduit RSSWP Strobes WPSBB WPSBB + WP -KIT WFP ET70WP Speaker Strobes JOB IOB + WP -KIT WFP ASWP Horn Strobes WPBB WPBB + WP -KIT WFPA AHWP Horns WBB FACP WFP ET -1010 Speakers WBB WFP MTWP Multitone Horn Strobes JOB IOB + WP -KIT WFP Multitone Horn IOB IOB + WP -KIT WFP *IOB, WPSBB and WPBB models include weep holes and plug in the event that moisture may have entered the appliance SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE IN UNISON. RED AND BLACK SHUNT -WIRES ARE SUPPLIED. FROM + + TO NEXT PRECEDING APPLIANCE APPLIANCE RED - - OR EOLR OR FACP BLACK STROBE AUDIBLE SERIES RSSWP, ASWP, AHWP, MTWP AND MT -12/24 APPLIANCES FROM TO NEXT PRECEDING + + APPLIANCE OR - APPLIANCE FACP OR EOLR PF SERIES MTWP APPLIANCES SYNCHRONIZED STROBE OPERATION WITH CODED FACP MTWP 0 Strobe Sync Circuit Module NAC #1 or PS Audible Power Circuit FACP Supply NAC #2 Note: Strobe circuit requires constant voltage. SERIES RSSWP /ASWP APPLIANCES SYNCHRONIZED W/ DSM MODULE SINGLE CLASS "A" NAC CIRCUIT DSM STROBE +0 NAC SYNC 0 CIRCUIT OUT 1 0 +IN1 ^uwT ST \ MINUS 1 FACP AUDIBLE jMINUS 2 +IN2 RSS "T"P ST TROBE NAC +OUT2 CIRCUIT RETURN Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery. #Refer to Data Sheet S7000 for Mounting Options NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc. dba Cooper Notification standard terms and conditions. ' ARCHITECTS AND ENGINEERS SPECIFICATIONS General Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor /Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices for - Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using either exposed conduit or concealed conduit, or semi -flush mounting to a recessed electrical box in walls or ceilings using Wheelock mounting accessories. Weatherproof Strobes Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77 °F shall be available. The strobes shall operate over an extended temperature range of —40 °F to 150 °F (-40 °C to 66 °C) and be listed for maximum humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). Weatherproof Audibles and Audible /Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor /Outdoor use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code -3 output that can be synchronized. The horns shall have at least 3 sound level settings. Horn /Strobe combinations shall be able to be synchronized on a single NAC. Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone Audible /Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized. The audibles shall be able to be coded when operated on a separate NAC. Weatherproof Speakers and Speaker /Strobes Weatherproof speakers and speaker /strobes shall be listed for Indoor /Outdoor use under UL Standard 1480. All speakers shall provide field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET -1010. They shall be listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series ET70WP. They shall be available for surface or semi -flush mounting to walls or ceilings and shall be listed to produce up to 93 dBA. Synchronization Modules When synchronization of strobes or temporal code -3 audibles is required, the appliances shall be compatible with the Wheelock Series DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built -in Wheelock Patented Sync Protocol. The strobes and audibles shall not drift out of synchronization at any time during operation. Series ASWP audibles and strobes shall be able to be synchronized on a 2 -wire circuit with the ability to silence the audible if required. The strobes on Series MT multitone audible /strobe appliances shall be able to be synchronized and shall be able to be operated on a separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC. Weatherproof Mounting Accessories Weatherproof mounting options shall include surface mounting or semi -flush mounting to walls or ceilings. Surface mounted appliances shall mount to Wheelock IOB, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit. For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock's WP -KIT to provide a weatherproof seal for the electrical box. Semi -flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3YEAR WARRANTY S9004 WP 06/11 i Cooper Notification is Wheelock' ® SAFEPATW WAVES, #0 COOPER N otifi cation 0 COOPER Notification Finally, Design and Safety Meet... Description: The Wheelock® ExcederTm Series of notification appliances feature a sleek modern design thatwill please building owners with reduced total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction. The Wheelock® ExcederTm Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit. All strobe models feature an industry first of 8 candela settings on a single appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTA9 Series of wall and ceiling notification appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting base can be pre -wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint and damage to the contacts. The Contact Cover also acts as a shunting device to allow pre -wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while it is on the UMB. When the Contact Cover is removed the circuit will show an open until the appliance is installed. The UMB allows for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra secure installation, while the ceiling models provide a captivated screw to prevent the screw from falling during installation. - Save up to 48% o in current draw* - Up to 9 models now in 1 appliance - Save up to 1 4% cost of installation ** Sleek Modern Aesthetics &� Finger Slide Switches Compatibility and Requirements Synchronize using the Wheelock® Sync Modules or panels with built -in Wheelock® Patented Sync Protocol Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage Strobes produce 1 flash per second over the "Regulated Voltage" range Compared to competitive models ** Compared to previous models Voltage Test Points Multiple Voltages 3 Audible Settings 90, 95, 99 dB 8 Candela Settings U Wall - 15/1575/30/75/95 /110/135/185 Ceiling - 15/30/60/75/95/115 /150/177 Universal Mounting Base LU) Ceiling and Wall Mounts to 5 Backbox Types Environmentally Friendly Low Current Draw Compatibility and Requirements Synchronize using the Wheelock® Sync Modules or panels with built -in Wheelock® Patented Sync Protocol Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage Strobes produce 1 flash per second over the "Regulated Voltage" range Compared to competitive models ** Compared to previous models _NOTE: All CAUTIONS and WARNINGS are Identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT W W W.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, ,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". • All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. • Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32•F to 120 °F (0•C to 49 "C) and maximum humidity of 93% (3 20/6) UL 464 (85% UL 1971). • Series Exceder'homs are under UL Standard 464 for audible signal appliances (Indoor use only). Horn Strobe Ratings per UL 1971 & UL 464 at 24 VDC 24 VDC 1 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 -33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0 -33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125 24 VDC 1 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 -33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0 -33.0 0.073 MM 0.087 0.128 0.139 0.163 0.186 0.230 0.272 SM 0.122 24 VDC 1 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 -33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0 -33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL 464 Model Regulated Voltage Range VDC 99 dB 95 dB 90 dB HN 16 -33.0 0.064 0.044 0.022 HNC 16 -33.0 0.084 0.044 0.022 HN 8.0 -17.5 0.047 0.026 0.017 HNC 8.0 -17.5 0.047 0.026 0.017 * UL max current rating is the maximum RMS current within the listed voltage range (16 -33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. , Specification & Ordering Information *12 VDC models feature 15 & 15/75 settings * *UMB = Universal Mounting Base NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and: conditions. Sync w/ SM, Strobe Mounting Candela DSM or 12/24 VDC* Options 6-Ak, PS-6 & PS -8 575/30/7 5/95 /110/135/185 X X UMB*" •_ HSW 15/1575/30/75/95 /110/135/185 X X UMB ** HSRC 15/30/60 /75/95/115/150/177 X X UMB ** HSWC 15/30/60 /75/95/115/150/177 X X UMB ** • STR 15/1575/30/75/95 /110/135/185 X X UMB ** STW . 15/1575/30 /75/95/110/135/185 X X UMB ** • STRC 15/30/60/75/95/115 /150/177 X X UMB ** ' STWC 15/30/60/75/95/115 /150/177 X X UMB ** HNR + X X UMB ** HNW • X X UMB ** HNRC X X _ UMB ** HNWC •• Sa x X UMB ** *12 VDC models feature 15 & 15/75 settings * *UMB = Universal Mounting Base NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and: conditions. - Architects and Engineers Specifications Tlse notification appliances shall be Wheelock® ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing- Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous ortemporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single -gang, double -gang, 4 -inch square, 3.5 -inch octal, 4 -inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock @'s SM, DSM Sync Modules, Wheelock@ Power Supplies or other manufacturer's panels with built -in Wheelock@ Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non - synchronized flash -rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock@ synchronization protocol. Wall Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM) Ceiling Appliances — UL Standard 1971, UL Standard 464 WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder - Spec Sheet 08/09 Cooper Notification is Wheelock' CREW SAFEPATH° WAVE COOPERNotification COOPER Wheelock Series NS Horn Strobes and Series NH Horns } Series NS Series NH Description: The Series NS Horn Strobe Appliances are designed for indoor, wall and ceiling mount applications. The Series NH Horn and the horn portion of the Series NS include a selectable continuous horn tone or temporal pattern (Code 3) with selectable dBA settings of 90 or 95 dBA. Strobe options include 1575cd or the Wheelock patented Multi - Candela strobe with field selectable candela settings of 15/30/75/110cd for wall mount and 15/30/75/95cd and 115/177cd for ceiling mount. These versatile Horn Strobe Appliances can be synchronized using the Wheelock SM, DSM Sync Modules or the PS- 24 -8MC Power Supply with the Wheelock patented Sync Protocol. Additionally, the audible may be silenced while maintaining strobe activation. All models of the Series NS and NH are designed for maximum performance, reliability and cost - effectiveness while meeting or exceeding the latest requirements of NFPA72 /ANSI 117.1/UFC and UL Standards 1971 and 464 as well as meeting ADA requirements concerning photosensitive epilepsy. The Wheelock patented 2 -Wire Series NS Horn Strobes and Series NH Horns offer more features with lower current draw than competitors. NS and NH Ceiling Mount Appliances will be available July 2006. mwoq,(O� ee Kiwi — ARRM E5946 151 -92 -E 7125 - 0785:142 S5391 Features: • Approvals include: UL Standard 1971, UL Standard 464, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP). See approvals by model number in Specifications and Ordering Information • ADA /NFPA/UFC /ANSI compliant • Complies with OSHA 29, Part 1910.165 • Wall mount model Field Selectable Candela Setting 15130/75/110cd (24 VDC Multi - Candela models) or 1575cd in 12 or 24 VDC • Ceiling mount model Field Selectable Candela Setting 15/30/75/95cd and 115/177cd (24 VDC Multi - Candela models) • Selectable Continuous Horn or Temporal (Code 3) • 2 Selectable dBA settings of 90 and 95 dBA in both tones • Patented Universal Mounting Plate • 12 and 24 VDC models with UL "Regulated Voltage" using filtered DC or unfiltered VRMS input voltage • Wall and Ceiling Mount • Ceiling models with same look as Wheelock round ceiling strobes and speakers • NH horn is selectable 12 or 24 VDC in 1 appliance • The strobes can be synchronized using the Wheelock sync modules or power supplies with built in Sync Protocol • Fast installation with IN /OUT screw terminals using #12 to #18 AWG wires NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION WINSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %). • Series NH homs are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Ratings Per UL Standard 1971 Table 2: dBA Ratings for Series NS /NH Horn Model Input Voltage VDC Regulated Voltage Range VDC /FWR Strobe Candela (CD) D Description Volume Reverberant dBA @ 10ft per UL 464 Anechoic dBA @ 10 ft 12 VDC 24 VDC 12 VDC 24 VDC NS -24MCW 24 16.0-33.0 15/30/75/110 Continuous Horn High 83 87 89 95 NS- 241575W 24 16.0-33.0 15 (75 on Axis) Low 76 81 84 90 NS- 121575W 12 8.0-17.5 15 (75 on Axis) Code 3 Horn High 79 82 89 95 NS -24MCC 24 16.0-33.0 15/30/75/95 Low 72 76 84 90 NS- 24MCCH 24 16.0-33.0 115/177 @12V Table 3: UL Max Current* Series NS /NH 24 VDC Audible Wall Mount Strobe Models Ceiling Mount Strobe Models NH -12/24 NS- 241575W NS -24MCW NS -24MCC NS- 24MCCH @24VDC 15/75cd 15cd 30cd 76cd 110cd 76cd 30cd 76cd 95cd 115cd 177cd High (95) dBA 24VDC 0.044 0.104 0.074 0.107 0.184 0.244 0.082 0.124 0.209 0.275 0.350 0.477 Low (90) dBA 24VDC 0.018 0.096 0.066 0.101 0.177 0.232 0.071 0.114 0.201 0.261 0.306 0.429 Series NS /NH 12VDC Audible Wall Mount * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. NH -12/24 Aud /Strobe @12V NS- 121575W High (89) dBA 12 VDC 0.021 0.220 Low (84) dBA 12VDC 0.012 0.210 Wiring Diagrams" NS /NH APPLIANCE FROM TO NEXT PRECEDING ±APPLIANCE APPLIANCE, SM /DSMiy+ OR EOLR PS- 12/24 -8M P, PS- 12/24 -8CP OR FACP - SIGNAL NS AND NH APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT WITH AUDIBLE SILENCE FEATURE 24 VDC SM F Agency Approvals + STROBE MEA CSFM - STROBE BFP Strobe 9404 A NAC X - Circuit N Sa NH� C+Audible X X X NS- 24MCW -FW 9405 P X EOLR - Audible 'Audible X NAC X X Circuit 7806 SPECIFICATION & ORDERING INFORMATION OTE: NS /NH must be set on Code 3 horn tone achieve synchronized temporal (Code 3) tone. efer to installation instruction (P83983, P83600 )spectively). For detail using SM or DSM Sync Module refer Data Sheet S3000 or Installation Instructions '83123 for SM and P83177 for DSM. For firing information on the power supplies refer to istallation Instructions P84515 for PS- 12/24 -8CP nd P84333 for PS- 12/24 -8MP. Model Number Order Code Strobe Candela Sync w/ SM, DSM or PS- 24 -8MC 24 VDC 12 VDC Mounting Options# Agency Approvals UL MEA CSFM FM BFP NS- 24MCW -FR 9404 15/30175/110 X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 24MCW -FW 9405 15/30/75/110 X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 241575W -FR 7806 15 (75 on Axis) X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 241575W -FW 7811 15 (75 on Axis) X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 121575W -FR 7816 15 (75 on Axis) X -- X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 121575W -FW 7818 15 (75 on Axis) X - X B,D,E,F,G,H,J,N,O,R,X X X X X X NH- 12124 -R 7449 - X X X B,D,E,F,G,H,J,N,O,R,X X X X X X NH- 12/24 -W 7500 - X X X B,D,E,F,G,H,J,N,O,R,X X X X X X NS- 24MCC -FR 3754 15/30/75195 X X - E X * X NS- 24MCC -FW 3753 15/30/75/95 X X - E X * X NS- 24MCCH -FR 3756 115/177 X X - E X * X NS- 24MCCH -FW 3755 115/177 X X - E X X NH- 12/24R -R 3752 - X - X B,D,E,F,G,H,J,N,O,R,X X * X NH- 12/24R -W 3751 - X - X B,D,E,F,G,H,J,N,O,R,X X * X NS and NH Ceiling Mount Appliances will be available July 2006. *Pending Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery. #Refer to Data Sheet S7000 for Mounting Options NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. ARCHITECTS AND ENGINEERS SPECIFICATIONS The audible /visual notification appliances shall be Wheelock Series NS Horn Strobe appliances and Series NH Horn appliances or a,pproved equals. The Series NS appliances shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing - Impaired for Indoor Fire Protection Service). The Series NH Horn shall be UL Listed under Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The audible portion of the appliance shall have a minimum of two (2) field selectable settings for dBA levels (90 and 95 dBA) and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series NS shall be of low current design. Where wall mount, Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for 15/30/75/110 candela. Where ceiling mount, Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for 15/30/75/95 candela or 115/177 candela. The selector switch for selecting the candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with the Wheelock SM, DSM Sync Modules or the Wheelock PS -24- 8MC Power Supplies with built -in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non - synchronized flash - rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation. The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single - gang, double -gang, 4 -inch square, 1 00m European type backboxes, orthe SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. ril■ri1rM 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631 -2148 Fax: (732) 222 -2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S2100 NS /NH 09/06 Description P_ 000 COOPER Notification Series RSS and RSSP Strobes and Strobe Plates The Wheelock patented Series RSS Strobe Appliances and Series RSSP Strobe Plates have lower current draw while maintaining outstanding performance, reliability and cost effectiveness. These versatile appliances will satisfy virtually all requirements for indoor, wall or ceiling mount applications. Strobe options for wall mount models include 1575 or the Wheelock Patented MCW multi - candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models include the patented MCC multi - candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. All models may be synchronized using the Wheelock SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. Synchronized strobes can eliminate possible restrictions on the number of strobes in the field of view. Wheelock's synchronized strobes offer an easy way to comply withADA recommendations concerning photosensitive epilepsy as well as meeting the requirements of NFPA 72. The Wheelock Series RSS Strobes employ a Patented Integral Strobe Mounting Plate that can be mounted to a single gang, double gang, 4" square, 1 00m European backboxes or the SHBB surface backbox. If the flush backbox has side or top space between it and the finished wall, the NATP (Notification Appliance Trimplate) may be used. It provides an additional .65" of trim for the Appliance. An attractive cover plate is provided for a clean, finished appearance on all models. The Series RSSP Multi - Candela Strobe Plates are a cost effective way to retrofit required wall strobe appliances to bells, homs, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with the Wheelock SBL2 surface backbox. x ccmar �� exraac .. ® M EA •" APPROVED S5391 151 -92 -E 7125 - 0785:141 7300 - 0785:154 m RSS Round Features • Approvals include: UL Standard 1971, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP) See approvals by model in Specifications and Ordering Information • ADA/NFPA/UFC /ANSI compliant. Meets OSHA 29 Part 1910.165 • Wall mount Multi - Candela models are available with Field Selectable Candela Settings of 15/30/ 75/110cd or 135/185cd. Single Candela models are available in 1575cd • Ceiling mount Multi - Candela models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd. (Round or Square) • Strobes produce 1 flash per second over the regulated voltage range • 12 and 24 VDC models with wide UL "Regulated Voltage" us- ing filtered (DC) or unfiltered VRMS input voltage • Synchronize using the Wheelock sync modules or panels with built -in Wheelock Patented Sync Protocol • Fast installation with IN /OUT screw terminals using #12 to #18 AWG wire For Weatherproof Series RSS See Datatsheet S9004 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU ANDIOR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %). • Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current* RSS /RSSP 241575W 24VDC Models RSS /RSSP -Wall Mount 24MCW I 24MCWH Ceiling Mount 24MCC I 24MCCH 1575cd I 15cd 1 30001 1 75cd 1110cd 11350d 1185cd 115cd 130cd 175cd 195cd 1115Cd 1177cd UL max* 1 0.090 0.060 10.092 10.165 10.220 10.300 10.420 10.065 1 0.105 10.189 10.249 1 0.300 1 0.420 RSS /RSSP RSS /RSSP 24VDC Wall Mount Models * RMS current ratings are per UL average RMS method. UL max current 121575W rating is the maximum RMS current within the listed voltage range (16 -33v for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at UL max* 0.255 the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Table 2: Audibles /Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Horns AH, NH, HS Motor Bells MB- G6 /G10 Speakers ET- 1010/1080, E70, ET70 Chimes CH70 SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT DSM STROBE + NAC SYNC 0 CIRCUIT OUT +OUT, +IN RSS RSS RSS \ Iy11NUS 1 FACP +AUDIBLE O MINUS 2 + IN 2 RSS RSS RSS NAC NAC +OUT2 CIRCUIT RETURN Wiring Diagrams 0 SERIES RSS /RSSP APPLIANCE FROM + + TO NEXT PRECEDING _ APPLIANCE APPLIANCE, SYNC OR EOLR MODULE, POWER SUPPLY OR FACP SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM #1 lt:Str obe NAC Cir. RSS RSS F DSM #2 A Strobe NAC Cir. S + RSS RSS C DSM #3 P Sync Strobe NAC Cir. + RSS RSS DSM Interconnecting wiring shown. Maximum of twenty (20) STROBE /PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON TO NEXT FROM APPLIANCE PRECEDING - ± OR EOLR APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP STROBE AUDIBLE STROBE /PLATE ASSEMBLY SM MODULE SINGLE AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY FROM + PRECEDING T TO NEXT APPLIANCE OR F APPLIANCE _ FACP Color WHITE Mounting Options * ** OR EOLR FROM + - — f — — — PRECEDING - STROBE — — — + TO NEXT STROBE OR STROBE, SYNC - - —T1 1 r — — Strobe — — — EOLR MODULE, POWER A NAC 15/30175/110 1 I 1 SUPPLY OR FACP X Circuit STROBE APPLIANCE # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer PS- 24 -8MC. Specifications and Ordering Information SERIES RSS /RSSP APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT Ceiling Mount SM Strobe Candela F 12 VDC + STROBE Color WHITE Mounting Options * ** Square or Round Agency Approvals - STROBE MEA CSFM FM Strobe RSS - 24MCW -FR 940 X A NAC 15/30175/110 X X Circuit B,D,E,F,G,H,J,N,O,R,X RSS RSS X CAudible X X X RSS - 24MCW -FW 9401 X - X 15/30/75/110 P EOLR X B,D,E,F,G,H,J,N,O,R,X Square Audible SERIES RSS /RSSP APPLIANCES SYNCHRONIZED WITH PS- 12/24 -8CP or PS- 12/24 -8MP Series PS- 12/24 -8MP OUTPUTS AS RSS EOLR F 1-4 4 -CLASS A "B" OR AS RSS C 2 -CLASS A" P AS RSS Series PS -12124 -8MP Model Order Code Wall Mount Ceiling Mount Non- Sync y Strobe Candela 24 VDC 12 VDC Color RED Color WHITE Mounting Options * ** Square or Round Agency Approvals UL MEA CSFM FM BFP RSS - 24MCW -FR 940 X - X 15/30175/110 X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS - 24MCW -FW 9401 X - X 15/30/75/110 X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 241575W -FR 7471 X - X j 15 (75 on Axis) X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 241575W -FW 7788 X - X 15 (75 on Axis) X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 121575W -FR 7476 X - X 15 (75 on Axis) - X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS- 121575W -FW 7468 X - X 15 (75 on Axis) - X X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS - 24MCC -FW 3158 X X 15/30/75/95 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS - 24MCC -FR 3157 - X X 15/30/75/95 X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS- 24MCCR -FW 3160 X X 15/30/75/95 X X B,D,E,F,G,H,J,N,O,R,X Round X X X X * RSS- 24MCCH -FW 3461 - X X 115/177 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS- 24MCCHR -FW 3463 X X 115/177 X X B,D,E,F,G,H,J,N,O,R,X Round X X X X * RSS - 24MCWH -FR 3465 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS - 24MCWH -FW 3464 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSSWP- 2475W -FR ** 9013 X X 180@ 77 -F 75@ -31 °F X X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSSWP - 2475W -FW** 3034 X X 180@° 77`F 75@ -31 °F X X X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSSP- 121575W -FR 7798 X X 15 (75 on Axis) - X X - D,E,Z Square X X X X X RSSP - 24MCW -FR 9402 X X 15/30/75/110 1 X - X - D,E,Z Square X X X X X RSSP- 241575W -FR 7793 X X 15 (75 on Axis) - - X - D,E,Z Square X X X X X *PENDING All models sync with Wheelock SM, DSM or PS- 12/24 -8CP or PS- 12/24 -8MP. # Models are available in either Red or White. Call Customer Service for Order Code & Delivery. * *For Weatherproof Series RSS Strobe specifications see data sheet S9004. ** *Refer to data sheet S7000 for mounting options. Arcniteas ana The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing- Impaired) for Indoor Fire Protection Service. The strobe shall beJisted for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry as the Wheelock Series RSS. The Series RSS Strobe shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built -in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single - gang, double -gang, 4 -inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The Appliance shall not have any mounting holes or screw heads visible when the installation is completed. The Series RSSP Multi - Candela orsingle candela Strobe Plate shall mountto eithera standard 4 inch square backboxforflush mounting, or the Wheelock SBL2 backbox for surface mounting. All notification appliances shall be backward compatible. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3YEAR WARRANTY Made in USA SO410 RSS /RSSP 02/08 Cooper Notification is Wheelock' AMR) SAFEPATH` WAVES, * COOPER Notification NOG -12LX Addressable Manual Pull Station General The Notifier NBG -12LX is a state -of- the -art, dual- action (i.e., requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel except FireWarden series panels, and the NSP- 25 panel. Because the NBG -12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built -in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word "ACTIVATED" appears to clearly indicate the station has been operated. • Captive screw terminals wire -ready for easy connection to SLC loop (accepts up to 12 AWG /3.25 mm2 wire). • Can be surface mounted (with SB -10 or SB -1 /0) or semi - flush mounted. Semi -flush mount to a standard single - gang, double -gang, or 4" (10.16 cm) square electrical box. • Smooth dual- action design. • Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. • Attractive shape and textured finish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG12TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. • Up to 99 NBG -12LX stations per loop on CLIP protocol loops. • Up to 159 NBG -12LX stations per loop on FlashScan® pro- tocol loops. • Dual -color LED blinks green to indicate normal on FlashS- can® systems. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications • Shipping Weight: 9.6 oz. (272.15 g) • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. • Maximum SLC loop current: 375 NA. • Temperature Range: 32 °F to 120 °F (0 °C to 49 °C) • Relative Humidity: 10% to 93% (noncondensing) • For use indoors in a dry location DN- 6726:C1 • H -240 NOTIFIER� by Honeywell The NBG -12LX Addressable Manual Pull Station Installation The NBG -12LX will mount semi -flush into a single -gang, dou- ble -gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB -10 or SB -1 /0 sur- face backbox. If the NBG -12LX is being semi -flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi -flush mounting with 4" (10.16 cm) or double -gang boxes (not with single -gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down /activated position. Once latched, the word "ACTI- VATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 — 159 on FlashScan® systems, 1 — 99 on CLIP systems). Architectural /Engineering Specifications Manual Fire Alarm Stations shall be non - coded, with a key - operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red - colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB -10 or SB -I /O; or semi -flush mounting on a standard single -gang, double -gang, or 4" DN- 6726:C1 •8/16/10 — Page 1 of 2 (10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. The loop poll LED shall be clearly visible through the front of the station. The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm. Product Line Information NBG -12LX: Dual- action addressable pull station. Includes key locking feature. SB -10: Surface backbox; metal. SB -1 /0: Surface backbox; plastic. BG12TR: Optional trim ring. 17021: Keys, set of two. NY- Plate: New York City trim plate Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. • UL / CUL Listed: S692 (listed for Canadian and non -Cana- dian applications) • MEA:67 -02 -E • CSFM:7150- 0028:0199 • FDNY: COA #6038 (NFS2 -640), COA #6058 (NFS2 -3030) • BSMI: C1313066760047 • U.S. Coast Guard: 161.002/23/3 (AFP -200); 161.002/27/3 (AM- 2020 /AFP -1010; 161.002/42/1 (NFS -640) • Lloyd's Register: 02/6007 (NFS -640); 94/60004 (E2) (AFP -200); 03/60011 (E1); 07/60007 (NFS2 -3030) • FM Approved Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. Notifier® and FlashScan® are a registered trademarks of Honeywell International Inc. 02010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I�O �oo� This document is not intended to be used for installation purposes. We try to keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. MMO 6 All specifications are subject to change without notice. GIOALIT7 SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484 -7161, FAX: (203) 484 -7118. www.notifier.com Page 2 of 2 — DN- 6726:C1 •8/16/10 NBG -12 Series Non -Coded Conventional Manual Fire Alarm Pull Stations General The NOTIFIER NBG -12 Series is a cost - effective, feature - packed series of non -coded manual fire alarm pull stations. It was designed to meet multiple applications with the installer and end -user in mind. The NBG -12 Series features a variety of mod- els including single- and dual- action versions. The NBG -12 Series provides an alarm initiating input signal to conventional fire alarm control panels (FACPs) such as the SFP Series, and to XP Transponders. Its innovative design, durable construction, and multiple mounting options make the NBG -12 Series simple to install, maintain, and operate. Features • Aesthetically pleasing, highly visible design and color. • Attractive contoured shape and light textured finish. • Meets ADA 5 lb. maximum pull- force. • Meets UL 38, Standard for Manually Actuated Signaling Boxes. • Easily operated (single- or dual- action, model dependent), yet designed to prevent false alarms when bumped, shaken, or jarred. • PUSH IN /PULL DOWN handle latches in the down position to clearly indicate the station has been operated. • The word "ACTIVATED" appears on top of the handle in bright yellow, further indicating operation of the station. • Operation handle features white arrows showing basic opera- tion direction for non - English- speaking persons. • Braille text included on finger -hold area of operation handle and across top of handle. • Multiple hex- and key -lock models available. • U.S. patented hex -lock needs only a quarter -turn to lock/ unlock. • Station can be opened for inspection and maintenance with- out initiating an alarm. • Product ID label viewable by simply opening the cover; label is made of a durable long -life material. • The words "NORMAL" and "ACTIVATED" are molded into the plastic adjacent to the alarm switch (located inside). • Four - position terminal strip molded into backplate. • Terminal strip includes Phillips combination -head captive 8/32 screws for easy connection to Initiating Device Circuit (IDC). • Terminal screws backed -out at factory and shipped ready to accept field wiring (up to 12 AWG /3.1 mm2). • Terminal numbers are molded into the backplate, eliminating the need for labels. • Switch contacts are normally open. • Can be surface- mounted (with SB -10 or SB -UO) or semi - flush mounted. Semi -flush mount to a standard single -gang, double -gang, or 4" (10.16 cm) square electrical box. • Backplate is large enough to overlap a single -gang backbox cutout by 1/2" (1.27 cm). • Optional trim ring (BG12TR). • Spanish versions (FUEGO) available (NBG- 12LSP, NBG- 12LPSP). • Designed to replace the legacy NBG -10 Series. • Models packaged in attractive, clear plastic (PVC), clam- shell- style, Point -of- Purchase packages. Packaging includes a cutaway dust/paint cover in shape of pull station. DN- 6643:A1 • 1 -410 �J NOTIFIER� by Honeywell Construction 6643 -,jpg • Cover, backplate and operation handle are all molded of durable polycarbonate material. • Cover features white lettering and trim. • Red color matches System Sensor's popular SpectrAlert® Advance horn /strobe series. Operation The NBG -12 manual pull stations provide a textured finger -hold area that includes Braille text. In addition to PUSH IN and PULL DOWN text, there are arrows indicating how to operate the sta- tion, provided for non - English- speaking people. Pushing in and then pulling down on the handle activates the normally -open alarm switch. Once latched in the down position, the word "ACTIVATED" appears at the top in bright yellow, with a portion of the handle protruding at the bottom as a visible flag. Resetting the station is simple: insert the key or hex (model dependent), twist one quarter -turn, then open the station's front cover, causing the spring - loaded operation handle to return to its original position. The alarm switch can then be reset to its normal (non - alarm) position manually (by hand) or by closing the station's front cover, which automatically resets the switch. Specifications PHYSICAL SPECIFICATIONS: pull station SB -10 SBa /O WBB WP -10 H 5.500 in. 5.500 in. 5.601 in. 4.25 in. 6.000 in. (13.97 cm) (13.97 cm) (14.23 cm) (10.79 cm) (15.24 cm) W 4.121 in. 4.125 in. 4.222 in. 4.25 in. 4.690 in. (10.467 cm) (10.478 cm) (10.72 cm) (10.79 cm) (11.913 cm) D 1.390 in. 1.375 in. 1.439 in. 1.75 in. 2.000 in. (3.531 cm) (3.493 cm) (3.66 cm) (4.445 cm) (5.08 cm) 6643dim2.thi ELECTRICAL SPECIFICATIONS: Switch contact ratings: gold - plated; rating 0.25 A @ 30 VAC or VDC. Auxiliary contact circuit (Terminals 3 & 4, NBG- 12LA): rated to 3.0 A @ 30 VAC or VDC. DN- 6643:A1 •04/22108 — Page 1 of 2 i ENGINEERING/ARCHITECTURAL SPECIFICATIONS Manual Fire Alarm Stations shall be non -code, with a key- or hex - operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key or hex. An operated station shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red colored LEXAN (or polycarbonate equivalent) with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger.' Stations shall be suitable for surface mounting on matching backbox SB -10 or SB -I /O; or semi -flush mounting on a standard single -gang, double -gang, or 4" (10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national /local requirements. Manual Stations shall be Under- writers Laboratories listed. NOTE. 'The words "F/RE/FUEGO" on the NBG -12LSP and NBG - 12LPSP shall appear on the front of the station in white letters, approximately 3/4" (1. 905 cm) high. Pre- Signal Models The NBG -12LPS and NBG- 12LPSP pull stations are non -coded manual pull stations which provide a FACP with two normally open alarm initiating input signals. "Pre- signal" input is activated by pushing in, then pulling down, the dual- action handle. A "gen- eral" alarm input signal can be manually activated via a momen- tary rocker switch mounted inside the unit. This general alarm switch can only be accessed by opening the cover with the sup- plied key /lock. See diagram at right. Agency Listings and Approvals The listings and approvals below apply to the NBG -12 Series pull stations. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status. • C(UL)US Listed: file S692. • CSFM approved: file 7150 - 0028:199. • FM approved (except NBG- 12LPS, NBG- 12LPSP). • MEA approved: file 67 -02 -E (NBG -12, NBG -12L, NBG- 12LOB, NBG- 12LA). • Lloyd's Register type approved: file 93/60141 (E3) (NBG -12, NBG -12L, NBG -12LA, NBG- 12LOB, NBG -12S). • U.S. Coast Guard approved: files 161.002/23/3 (AFP -200 with NBG -12, NBG -12L, NBG -12S); 161.002/42/1 (NFS -640 with NBG -12, NBG -12L, NBG -12S); 161.002/27/3 (AFP10101 AM2020 with NBG -12, NBG -12L, NBG -12S). • Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. Product Line Information NBG -12S: Single- action pull station with pigtail connections, hex lock. NBG -12: Dual- action pull station with SPST N/O switch, screw terminal connections, hex lock. NBG -12L: Dual- action pull station with SPST N/O switch, screw terminal connections, key lock. NBG- 12LSP: Same as NBG -12L with English /Spanish (FIRE/ FUEGO) labeling. NBG- 12LPS: Dual- action pull station with pre - signal option. NBG- 12LPSP: Same as NBG -12LPS with English /Spanish (FIRE/FUEGO) labeling. NBG- 12LOB: Dual- action pull station with key lock, outdoor applications listings (NBG - 121-0), and backbox. Includes SB -UO indoor /outdoor backbox, and sealing gasket. Model will also mount to WP -10 weatherproof backbox in retrofit applications. NOTE. NBG -12LO not available separately; NBG -12LO + approved backbox = NBG- 12LOB. Outdoor applications listings apply to NBG -12LOB combination. NBG -12LA: Dual- action pull station with key lock and annuncia- tor contacts. SB -10: Surface -mount backbox, metal. SB -110: Surface -mount backbox, plastic. (Included with NBG - 12LOB.) BG12TR: Optional trim ring for semi -flush mounting. WP -10: Outdoor use backbox. 17021: Keys, set of two. (Included with key -lock pull stations.) 17007: Hex key, 9/64 ". (Included with hex -lock pull stations.) NOTE. For addressable NBG -12LX models, see data sheet DN -6726. ROCKER SWITCH for Gener6 Alarm notification 1.300" (3.531) Dimensions Wre Length Strip Gauge 1� (2.540) 0.750" (1.905) 5.500" (13.970) (cm) FBG -12LPS TOGGLE SWITCH for Pre- Signal function NOTIFIERO, SpectrAlert® Advance, and System Sensor@ are registered trademarks of Honeywell International Inc. 02008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. MONEW0 3 mican, All specifications are subject to change without notice. RUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484 -7161, FAX: (203) 484 -7118. www.notifier.com Page 2 of 2 — DN- 6643:A1 •04/22/08 I I ONOTIFIEW Division of Pittway Corporation MMX -101 MONITOR MODULE INSTALLATION INSTRUCTIONS GENERAL MMX -101 Monitor Modules provide a two -wire, Style B (Class B) initiating circuit for normally -open (N.O.) contact fire alarm and supervisory devices. The MMX -101 is a compact unit that can be installed in a single gang junction box behind the monitored unit. Its small size and weight allow it to be installed without rigid mounting. NOTICE: This manual should be left with the owner /user of this equipment. INSTALLATION CAUTION Do NOT connect circuit wiring to control unit or modules or apply any power to any part of the system until after the circuit test has been performed. All wiring must be installed using the proper wire size and be in compliance with the National Electrical Code, all applicable local codes, and requirements of the authority having jurisdiction. 1. Connect the red and black wires to the positive ( +) and negative ( —) loop power leads of the control panel signal- ing line circuit (SLC), as indicated in Figure 2. 2. Connect the violet ( +) and yellow ( —) wires to a two -wire, normally -open initiating device. 3. Set the module address in accordance with system requirements. A given module can be set to any address between 00 and 99. 4. Install the module in the desired mounting location. CIRCUIT TEST For circuit test procedure, refer to Notifier Document 15531. UL Listed Compatible Control Panel Notifier (e AM2020 (_) TO NEXT DEVICE NOTES: O THE INITIATING CIRCUIT IS CURRENT LIMITED TO 290 pAMP MAX 10VOC NOM. ® DETECTION LOOP PROVIDES THE FOLLOWING SERVICES: - FIRE, AUTOMATIC/MANUAL WATERFLGW ALARM SERVICE WITH N.O. CONTACT DEVICES - SPRINKLER SUPERVISION WITH N.O. CONTACT DEVICES O DO NOT MIX SERVICES ® INITIATING CIRCUIT LINE REQUIREMENTS MAX. LENGTH - 2500' 47K EOL MAX. RESISTANCE -40 OHMS A2143 -00 Figure 1. Figure 2. Typical two -wire, Style B Initiating Circuit Configuration of an MMX -101 Monitor Module N500 -02 -00 156- 420 -05 Notifier, 12 Clintonville Road, Northford, CT 06472 t January 20, 2000 DN -6755 - K -150 NOT 1 F1 E R® PAM -1 and PAM -2 FIRE SYSTEMS Multi - Voltage Relay Modules Section: Miscellaneous GENERAL Air Products & Controls, Inc. PAM -1 and PAM -2 Multi -Volt- age Relay Modules are encapsulated multi - voltage de- vices. The PAM -1 relay provides 10.0 Amp Form -C con- tacts and may be energized by one of three input voltages: 24 VAC, 24 VDC, or 115 VAC. The PAM -2 relay provides 7.0 Amp Form -C contacts and may be energized by one of two input voltages: 12 VDC or 24 VDC. A red LED is provided on both models. When illuminated, it indicates the relay coil is energized. Either model may be mounted by using the double -sided adhesive tape, the self - drilling screw, or by placing loosely in a backbox. PAM -1 and PAM -2 Relay Modules are ideal for applica- tions where remote relays are required for control or status feedback. They are suitable for use with HVAC, tempera- ture control, fire alarm, security, energy management, and lighting control systems. SPECIFICATIONS Power requirements: for PAM -1: 0.015 Amps per posi- tion @ 24 VDC, 24 VAC, 115 VAC; for PAM -2: 0.015 Amps per position @ 12 VDC or 24 VDC. Relay: UL- recognized SPDT. Contact rating, PAM -1: 10.0 A @ 115 VAC; 7.0 A @ 28 VDC; 250 pA @ 5 VDC. Contact rating, PAM -2: 7.0 A @ 115 VAC; 7.0 A @ 28 VDC; 250 pA @ 5 VDC. Ambient temperature range: —58 °F to +185 °F ( -50 "C to +85 °C). Dimensions: 1.500" (38.100 mm) high x 1.000" (25.400 mm) wide x 0.875" (22.225 mm) deep, with 12"(304.8 mm) wire leads @ 18 AWG (0.75 mmz). WIRING DIAGRAMS California M EA Fire ®� 73 -92 -E Marshal Vol. XXI $State 7300- 1004:101 S3403 PRODUCT LINE INFORMATION PAM -1 Single SPDT relay with LED, double -sided adhesive tape, mounting screw, 12" (304.8 mm) leads and six wire -nuts. Powerrequire- ments: 0.015 Amps per position @ 24 VDC, 24 VAC, 115 VAC. Contact rating: 10.0 A @115 VAC, 7.0A @28 VDC, 250pA @5 VDC. PAM -2 Single SPDT relay with LED, double -sided adhesive tape, mounting screw, 12" (304.8 mm) leads and six wire -nuts. Powerrequire- ments: 0.015 Amps per position @ 12 VDC or 24 VDC. Contact rating: 7.0 A @ 115 VAC; 7.0 A @ 28 VDC; 250 pA @ 5 VDC. Relay- Energized LED WHT BLU C 0 BLK 0 YEL NC 10.0 Amp Contacts RED ORG NO € +--115VAC @0.015Amp 24 VAC @ 0.015 Amp 24 VDC @ 0.015 Amp 4 AT LEFT: Installation wiring ®©© BELOW: Installation wiring 1w, for PAM -2 model. ® ©/`. California M EA Fire ®� 73 -92 -E Marshal Vol. XXI $State 7300- 1004:101 S3403 PRODUCT LINE INFORMATION PAM -1 Single SPDT relay with LED, double -sided adhesive tape, mounting screw, 12" (304.8 mm) leads and six wire -nuts. Powerrequire- ments: 0.015 Amps per position @ 24 VDC, 24 VAC, 115 VAC. Contact rating: 10.0 A @115 VAC, 7.0A @28 VDC, 250pA @5 VDC. PAM -2 Single SPDT relay with LED, double -sided adhesive tape, mounting screw, 12" (304.8 mm) leads and six wire -nuts. Powerrequire- ments: 0.015 Amps per position @ 12 VDC or 24 VDC. Contact rating: 7.0 A @ 115 VAC; 7.0 A @ 28 VDC; 250 pA @ 5 VDC. Relay- Energized LED WHT BLU C 0 BLK 0 YEL NC 10.0 Amp Contacts RED ORG NO € +--115VAC @0.015Amp 24 VAC @ 0.015 Amp 24 VDC @ 0.015 Amp 4 AT LEFT: Installation wiring for PAM -1 model. BELOW: Installation wiring 1w, for PAM -2 model. Relay- Energized LED OV ( —) WHT BLU C O +24V GRY YEL NC 7.0 Amp Contacts +12V RED OR- NO This document is a not intended be used for installation purposes. try to keep our I�O �oo� product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact NOTIFIER. Phone: (203) 484 -7161 FAX: (203) 484 -7118 1 j N OTI FI E W 12 Clintonville Road, Northford, Connecticut 06472 mliffERI N a 1111IM 1 11110 DN -6755 • 01/20/00 — Page 1 of 1 W , FSP -851 and FSP -851 T Intelligent Plug -In Photoelectric Smoke Detectors with FlashScan® General Notifier 851 Series intelligent plug -in smoke detectors with integral communication provide features that surpass conven- tional detectors. Detector sensitivity can be programmed in the control panel software. Sensitivity is continuously moni- tored and reported to the panel. Point ID capability allows each detector's address to be set with decade address switches, providing exact detector location for selective main- tenance when chamber contamination reaches an unaccept- able level. The FSP -851 photoelectric detector's unique optical sensing chamber is engineered to sense smoke pro- duced by a wide range of combustion sources. Dual electronic thermistors add 135 °F (57 °C) fixed - temperature thermal sens- ing on the FSP -851T. FSP -851 and FSP -851T detectors are compatible with all Notifier intelligent Fire Alarm Control Pan- els (FACP). FlashScan® (U.S. Patent 5,539,389) is a communication pro- tocol developed by Notifier that greatly increases the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices in the group has new information, the panel's CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of ear- lier designs. Features • Sleek, low- profile design. • Addressable - analog communication. • Stable communication technique with noise immunity. • Low standby current. • Two -wire SLC connection. • FlashScan (NFS -320, NFS -640, NFS2 -640, NFS -3030, NFS2 -3030) and classic CLIP systems (AFP -100, AFP - 200, AFP -300, AFP -400, NFS -640, AM2020 /AFP1010, NFS -3030) compatible. • Rotary, decimal addressing (1 -99 on CLIP systems, 1 -159 on FlashScan systems). • Optional remote, single -gang LED accessory. • Dual LED design provides 3600 viewing angle. • Visible bi -color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan systems only). • Remote test feature from the panel. • Walk test with address display (an address on 121 will blink the detector LED: 12- [pause] -1 (FlashScan systems only). • Built -in functional test switch activated by external magnet. • Built -in tamper- resistant feature. • Sealed against back pressure. • Constructed of off -white BayblendO, designed to commer- cial standards, and offers an attractive appearance. • 94 -5V plastic flammability rating. • SEMS screws for wiring of the separate base. • Optional relay, isolator, and sounder bases. dn- 6935:al • H -202 NOTIFIER� by Honeywell FSP -851 with B71OLP base FSP -851T with B71OLP base Specifications Size: 2.1" (5.3cm) high x 4.1" (10.4cm) diameter installed in B501 base, 6.1" (15.5cm) diameter installed in B710LPbase. Shipping Weight: 5.2oz. (147g). Operating Temperature: FSP -851, 0 °C to 49 °C (32 °F to 120 °F); FSP -851 T, 0 °C to 38 °C (32 °F to 100 0F). Low temper- ature signal for FSP -851T at 45 °F +/- 10 °F (7.22 °C +/ 5.54 °C). Operating Altitude: to 10,000 feet. UL/ULC Listed Velocity Range: 0 -4000 ft/min. (1219.2 m/ min.), suitable for installation in ducts. Relative Humidity: 10 % -93% noncondensing. Thermal Ratings: Fixed - temperature setpoint 135 °F (57 0C). DETECTOR SPACING AND APPLICATIONS Notifier recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.144m) for ceiling heights 10 feet (3.148m) and higher. For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05 -1003, is available at systemsensor.com ELECTRICAL SPECIFICATIONS Voltage Range: 15 -32 volts DC peak. Standby Current (max. avg.): 300NA @ 24VDC (one com- munication every five seconds with LED enabled). LED Current (max.): 6.5mA @ 24VDC ('ON'). BASES AVAILABLE NOTE. 'A" suffix indicates ULC Listed model. dn- 6935:al • 05/19/09 — Page 1 of 2 B71OLP(A): 6.1" (15.5cm) diameter. B501(A): 4.1" (10.4cm) diameter. B501 BH -2(A) or 8501 BHT 2(A): Sounder base assembly. Includes B501 base. B224RB(A) Relay Base: Screw Terminals, up to 14AWG (2.Omm2); Relay Type, Form -C; Rating, 2.OA @ 30VDC resis- tive, 0.3A @ 11OVDC inductive, 1.OA @ 30VDC inductive; Dimensions, 6.2" (15.748cm) x 1.2" (3.048cm) x 1.2" (3.048cm). B224BI(A) Isolator Base: Dimensions, 6.2" (15.748cm) x 1.2" (3.048cm) x 1.2" (3.048cm); Maximum, 25 devices between isolator bases. Installation FSP -851 plug -in detectors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug in and remove detectors with- out using a ladder. Mount base on an electrical backbox which is at least 1.5" (3.81 cm) deep. Suitable mounting base boxes include: • 4.0" (10.16cm) square box. • 3.5" (8.89cm) or 4.0" (10.16cm) octagonal box. • Single -gang box (except relay or isolator base). • With 8501 BH -2 or B501 BHT -2 base, use a 4.0" (10.16cm) square box. • With B224RB or B224BI base, use a 3.5" (8.89cm) octago- nal box, or a 4.0" (10.16cm) octagonal or square box. NOTE. 1) Because of inherent supervision provided by the SLC loop, end -of -line resistors are not required. Wiring 7-taps" or branches are permitted for style 4 (Class `B) wiring. 2) When using relay or sounder bases, consult data sheet DN -2243 (ISO -X) for device limitations between isolator modules and isolator bases. Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed: S911 • ULC Listed: CS308 • MEA Listed: 225 -02 -E • FM Approved • CSFM:7272- 0028:206 • Maryland State Fire Marshal: Permit # 2122 • BSMI: 01313066760036 • CCCF: Certif. # 2004081801000017 (FSP -851T) Certif. # 2004081801000016 (FSP -851) • Lloyd's Register: 03/60011 Product Line Information NOTE: A "suffix indicates ULC listed model. FSP- 851:Low- profile intelligent photoelectric sensor. Must be mounted to one of the bases listed below. FSP- 851 A:Same as FSP -851 but with ULC listing. FSP- 851T:Same as FSP -851 but includes a built -in 135 °F (57 °C) fixed - temperature thermal device. FSP- 851TA:Same as FSP -851T but with ULC listing. BASES B71OLP: Standard U.S. low- profile base. B71OLPBP:Standard U.S. low- profile base, pkg. of 10. :B71OLPA:Standard U.S. low- profile base, ULC listing. B501BP:Standard European flangeless base, pkg. of 10. :B501A:Standard European flangeless base, ULC listing. B501BH- 2(A):Sounder base, includes B501 (A) base. B501 BHT 2(A):Same as B501 BH -2(A), but includes temporal sounder. B224RB(A):Intelligent relay base. B224BI(A):Intelligent isolator base. Isolates SLC from loop shorts. ACCESSORIES F1 10: Retrofit replacement flange for older style bases. Con- verts older high profile base for use with FlashScan detectors. RA40OZ(A):Remote LED annunciator. 3- 32VDC. Fits U.S. single -gang electrical box. Supported by B71 OLP(A) and B501 (A) bases only. SMK400E:Surface mounting kit provides for entry of surface wiring conduit. For use with B501 (A) base only. RMK400:Recessed mounting kit. For use with B501 (A) base only. SMB600:Surface mounting kit for use with B710LP(A). BCK- 20OB:Black detector covers, box of 10. For use with FSP -851 only. M02 -04- 00:Test magnet. M02 -09- 00:Test magnet with telescope stick. XR2B:Detector removal tool. Allows installation and /or removal of FlashScan Series detector heads from base in high ceiling installations. T55-1 27-010: Detector removal tool without pole. XP- 4:Extension pole for XR213. Comes in three 5 -ft. sections. Notifier® and FlashScan® are registered trademarks of Honeywell Interna- tional Inc. Bayblend® is a registered trademark of Bayer Corporation. 02009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. 'SO 9oo1 We try to keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. 94INUME 8 MIWIFA61111111111Ui All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484 -7161, FAX: (203) 484 -7118. www.notifier.com Page 2 of 2 - dn- 6935:al • 05/19/09 I K• FST -851 Series Intelligent Thermal (Heat) Detectors with FlashScan@ General Notifier FST -851 Series intelligent plug -in thermal detectors with integral communication has features that surpass conven- tional detectors. Point ID capability allows each detector's address to be set with decade address switches, providing exact detector locations. FST -851 Series thermal detectors use an innovative thermistor sensing circuit to produce 135 °F / 57 °C fixed - temperature (FST -851) and rate -of -rise thermal detection (FST -851 R) in a low- profile package. FST -851 H pro- vides fixed high- temperature detection at 190 °F /88 °C. These thermal detectors provide effective, intelligent property protec- tion in a variety of applications. FST -851 Series detectors are compatible with all Notifier intelligent Fire Alarm Control Pan- els, except FireWarden series panels. . FlashScanO (U.S. Patent 5,539,389) is a communication pro- tocol developed by Notifier Engineering that greatly enhances the speed of communication between analog intelligent devices and certain NOTIFIER systems. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel's CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of earlier designs. Features • Sleek, low- profile, stylish design. • State -of- the -art thermistor technology for fast response. • Rate -of -rise model (FST -851 R), 15 °F (8.3 °C) per minute. • Factory preset at 135 °F (57 0C); high- temperature model at 190 °F (88 °C). • Addressable by device. • Compatible with FlashScanO and CLIP protocol systems. • Direct dial entry of address 01 -159 for FlashScan® loops, 01 -99 CLIP mode loops. • Two -wire SLC connection. • Visible LEDs "blink" every time the unit is addressed. • 360° -field viewing angle of the visual alarm indicators (two bi -color LEDs). LEDs blink green in Normal condition and turn on steady red in Alarm. • Integral communications and built -in device -type identifica- tion. • Remote test feature from the panel. • Built -in functional test switch activated by external magnet. • Walk test with address display (an address of 121 will blink the detector LED 12- (pause) -1). • Low standby current. • Backward- compatible. • Built -in tamper- resistant feature. • Designed for direct - surface or electrical -box mounting. • Sealed against back pressure. • Plugs into separate base for ease of installation and main- tenance. Separate base allows interchange of photoelec- tric, ionization and thermal sensors. • SEMS screws for wiring of the separate base. • Constructed of off -white Bayblend®, designed to commer- cial standards, and offers an attractive appearance. dn- 6936:a1 • H -211 �J NOTIFIER8 by Honeywell FST -851 Series in B71OLP base • 94 -5V plastic flammability rating. • Remote LED output connection to optional RA40OZ remote LED annunciator. • Optional sounder, relay, and isolator bases. • Optional recessed (RMK400) or surface (SMK400E) base mounting kits. Specifications Size: 2.1" (5.3 cm) high x 4.1" (10.4 cm) diameter installed in B501 base, 6.1" (15.5 cm) diameter installed in B710LP base. Shipping weight: 4.8 oz. (137 g). Operating temperature range: FST -851 Series, FST -851 R: — 20 °C to 38 °C (-4 °F to 100 °F); FST -851 H: —20 °C to WC (-4 °F to 150 °F). Detector spacing: UL approved for 50 ft. (15.24 m) center to center. FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing. Relative humidity: 10% — 93% noncondensing. Thermal ratings: fixed- temperature setpoint 135 °F (57 °C), rate -of -rise detection 15 °F (8.3 °C) per minute, high tempera- ture heat 190 °F (88 °C). Altitude rating: 10,000 feet. ELECTRICAL SPECIFICATIONS: Voltage range: 15 - 32 volts DC peak. Standby current (max. avg.): 300 pA @ 24 VDC (one com- munication every 5 seconds with LED enabled). LED current (max.): 6.5 mA @ 24 VDC ( "ON "). BASES AVAILABLE: B71OLP: 6.1" (15.5 cm) diameter. 8501: 4.1" (10.4 cm) diameter. B501BH -2 or B501BHT2: Sounder base assembly. B224RB Relay Base: Screw terminals: up to 14 AWG (2.0 mm2). Relay type: Form -C. Rating: 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive. Dimensions: 6.2" (15.748 cm) x 1.2" (3.048 cm). B224BI Isolator Base: Dimensions: 6.2" (15.748 cm) x 1.2" (15.748 cm). Maximum: 25 devices between isolator bases. See Note 2 under Installation. Applications Use thermal detectors for protection of property. For further information, go to systemsensor.com for manual 156- 407 -00, Applications Manual for System Smoke Detectors, which pro- dn- 6936:a1 •06/8/09 — Page 1 of 2 1 r s; r vides detailed information on detector spacing, placement, zoning, wiring, and special applications. Installation The FST Series plug -in intelligent thermal detector uses a sep- arate base to simplify installation, service, and maintenance. Installation instructions are shipped with each detector. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. Suitable boxes include: • 4.0" (10.16 cm) square box. • 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box. • Single -gang box (except relay or isolator base). • With B501BH -2 or B501 BHT-2 base, use a 4.0" (10.16 cm) square box. • With B224RB or B224BI base, use a 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box, or a 4.0" (10.16 cm) square box. NOTE. 1) Because of the inherent supervision provided by the SLC loop, end -of -line resistors are not required. Wiring `T- taps" or branches are permitted for Style 4 (Class `B) wiring. 2) When using relay or sounder bases, consult data sheet DN -2243 (ISO -X) for device limitations between isolator modules and isolator bases. Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL Listed: S747 • ULC Listed: S6978MEA Listed: 383 -02 -E • FM Approved • CSFM:7270- 0028:196 • BSMI: C1313066760025 • CCCF: Certif. # 2004081801000018 • U.S. Coast Guard: 161.002/23/3 (AFP -200); 161.002/27/3 (AFP1010 /AM2020); 161.002/42/1 (NFS -640) • Lloyd's Register: 03/60011 Product Line Information "A" suffix indicates ULC Listed model. FST -851: Intelligent thermal detector. Must be mounted to one of the bases listed below. FST 851 A: Same as FST -851 but with ULC Listing. FST 851 R: Intelligent thermal detector with rate -of -rise feature. FST 851 RA: Same as FST -851 R but with ULC Listing. FST 851 H: Intelligent high- temperature thermal detector. FST 851 HA: Same as FST -851 H but with ULC Listing. BASES: B71OLP: Standard U.S. low- profile base B710LPBP: Standard U.S. low - profile base, pkg. of 10. B71OLP: Standard U.S. low - profile base. B710LP(A): Standard U.S. low- profile base. B501 BP: Standard European flangeless base, pkg. of 10 B501: Standard European flangeless base. B501(A): Standard European flangeless base, ULC Listing. BH501BH -2: Sounder base, includes B501 base above. BH501 BHT-2: Same as B501 BH -2, but includes temporal sounder. BH501 BHA: Sounder base, includes B501 base above BH501 BHTA: Same as BH501 BHA, but includes temporal sounder. B224BI(A): Intelligent isolator base. Isolates SLC from loop shorts. ACCESSORIES: F110: Retrofit replacement flange for older style high profile bases. Converts bases for use with FlashScan@ detectors. RA400Z(A): Remote LED annunciator. 3 — 32 VDC. Fits U.S. single -gang electrical box. Supported by B710LPBP(A) and B501 (A) bases only SMK400E: Surface mounting kit provides for entry of surface wiring conduit. For use with B501 (A) base only RMK400: Recessed mounting kit. For use with B501 (A) base only SMB600: Surface mounting kit for use with B710LPBP(A). BCK -20OB: Black detector covers, box of 10. M02 -04 -00: Test magnet. M02 -09 -00: Test magnet with telescope stick. XR2B: Detector removal tool. Allows installation and /or removal of FlashScan® Series detector heads from base in high ceiling installations. T55- 127 -010: Detector removal tool without pole. XP -4: Extension pole for XR213. Comes in three 5 -ft. sections. Notifier® and FlashScan® are a registered trademark of Honeywell International Inc. Bayblend® is a registered trademark of Bayer Corp. ®2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this docu- ment is strictly prohibited. This document is not intended to be used for installation purposes. 'SO 9001 We try to keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. MINME S mI1M67 " All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484 -7161, FAX: (203) 4847118. www.notifier.com Page 2 of 2 — dn- 6936:al • 06/8/09 + to Intelligent Bases B501 (A), B20OS(A), B200SR(A), B21 OLP(A), 82241 BI(A), B224RB(A), Mounting Kits, and Accessories General Intelligent FlashScanB and CLIP mounting bases and kits pro- vide a variety of ways to install NOTIFIER detectors in any application. Intelligent detectors can be mounted in either flanged or flangeless bases depending on junction box selec- tion (see Junction Box Selection Guide). Across this product line, detectors plug in easily to the base with SEMS screws; and models employ various 12 to 24 AWG wire ranges. Relay, isolator, and sounder bases can be used to meet local code requirements. Relay bases provide one Form -C contact relay for control of auxiliary functions such as door clo- sure and elevator recall. Isolator bases allow loops to continue to operate under fault conditions and automatically restore when the fault is removed. Sounder bases are available in temporal and non - temporal pattern versions depending on whether the signal is to be used for evacuation purposes. Specifications Diameter: — B501: 4.1" (104 mm). — B224BI, B224RB, B210LP: 6.1" (155 mm). — B200S /SR: 6.875" (17.46 cm). Wire gauge: — B22413I, B224RB: 14 to 24 AWG. — B210LP, B501, B200S /SR: 12 to 24 AWG. Temperature range: — B224BI, B224RB, B200S /SR: 32 °F to 120 °F (0 °C to 49 °C). — B210LP, 8501: -4 °F to 150 °F ( -20 °C to 66 °C). Humidity range: 10% to 93% RH, non - condensing. System temperature and humidity ranges: This system meets NFPA requirements for operation at 0 °C to 49 °C (32 °F to 120 0F); and at a relative humidity (noncondensing) of 85% at 30 °C (86 °F) per NFPA, and 93% t 2% at 32 °C t 2 °C (89.6 °F t 1.1 °F) per ULC. However, the useful life of the sys- tem's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humid- ity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15 °C to 27 °C (60 °F to 80 °F). Electrical Ratings FOR B200S/SR: External supply voltage: 16 to 33 VDC (VFWR) Standby current: 500 pA maximum. Alarm current: — B20OS: 25 mA maximum at high - volume setting; 15 mA maximum at low- volume setting. — B200SR: 35 mA maximum. SLC operating voltage: 15 to 32 VDC. SLC standby current: 300 NA. DN- 60054:E NOTIFIER� by Honeywell B200S(A), B200SR(A) Flanged Mounting Base B210LP(A) Sound output: measured in a UL reverberant room at 10 feet, 24 Volts (continuous tone). — B200S, high - volume: Greater than 85 dBA minimum. — B200S, low- volume: Greater than 75 dBA minimum. — B200SR: Greater than 85 dBA minimum. FOR B224RB, B224BI: Operating voltage: 15 to 32 VDC (powered by SLC). Standby ratings: <500 pA maximum @ 24 VDC. Set time (B224RB only): short delay 55 to 90 msec; long delay 6 to 9 seconds. Reset time (B224RB only): 20 msec maximum. Relay characteristics (B224RB only): two -coil latching relay; one Form -C contact; ratings (UUCSA): 0.9 A @ 125 VAC, 0.9 A @ 110 VDC, and 3.0 A @ 30 VDC. Product Line Information INTELLIGENT BASES 8501: Flangeless mounting base. B501 A: Flangeless mounting base, ULC Listed. B501 BP: Bulk pack of 6501 (10). B21OLP: Flanged mounting base. B21OLPA: Flanged mounting base, ULC listed B210LPBP: Bulk pack of B210LP (10). B20OS: Intelligent addressable sounder base capable of pro- ducing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and cus- tom tone. B200SA: Same as B200S with ULC - listing. B200SR: Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. B200SRA: Same as B200SR with ULC - listing DN- 60054:E • 7/22/2011 — Page 1 of 2 B224RB: Relay base. B224RBA: Relay base, ULC Listed. B224BI: Isolator base. B224BIA: Isolator base, ULC Listed. MOUNTING KITS AND ACCESSORIES SMB600: Surface mounting kit, flanged. F110: Retrofit flange for converting high - profile bases to low - profile. F110BP: Bulk pack of F110 (10). F210: Accessory flange ring for B210LP(A) base (new design). 6 -inch diameter. F210BP: Bulk pack of F210 (10). RA10OZ: Remote LED annunciator. RA10OZA: Remote LED annunciator, ULC Listed. M02- 04 -00: Detector test magnet. M02- 09 -00: Test magnet with telescoping handle. XR2B: Detector removal tool for current heads (T55- 127 -010 included). Junction Box Selection Guide XR2: Detector Remove Tool for use with low profile detector heads, and FSL -751. XP-4: Extension pole for XR2 /B (5 to 15 f ll.524 to 4.572 m). T55- 127 -010: Detector removal head. BCK -20OB: Black detector kit, package of 10 (for use with photo and ion detectors). WCK -20OB: White detector kit, package of 10 (for use with photo and ion detectors). Agency Listings and Approvals The listings and approvals below apply to intelligent bases as noted. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. • UL Listed: 3911 • ULC Listed: S911 • FM Approved • MEA: 22 -95 -E, 205 -94 -E Vol. 2; 257 -06 -E • CSFM: 7300 - 1653:0126, 7135 - 1653:0213, 7300 - 0028:0173, 7300 - 1653:0109 Base Models Single Gang 3.5" Oct. 4.0" Oct. 4.0" Sq. 4.0" Sq. with 3.0" mud ring 50 mm 60 mm 70 mm 75 mm B200S, B200SR Yes Yes Yes Yes Yes No No No No B501 No Yes No No Yes Yes Yes Yes No B21OLP Yes Yes Yes Yes Yes No No No No B224RB No Yes Yes Yes No No Yes Yes Yes B224BI No Yes Yes Yes No No No Yes Yes NOTE. Box depth contingent on base and wire size. Refer to National Electric Code or applicable local codes for appropriate recommendations. FlashScan ®, NOTIFIERO and System Sensor® are registered trademarks of Honeywell International Inc. 02011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I�O �oo� This document is not intended to be used for installation purposes. We try to keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. MOMS 6 NINIUFAMM All specifications are subject to change without notice. 1UA11TY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484 -7161, FAX: (203) 484 -7118. www.notifier.com Page 2 of 2 — DN- 60054:E • 7/22/2011