CC-11-1036 (3)MANUEL SYNALOVSKI ASSOCIATES
November 8, 2011
Miami -Dade County
11805 sw 26th street, suite 150
Miami, Florida 33175
RE: Barry University — Wiegand Center
Room 253 Nursing Simulation
11300 N.E. 2"d Avenue
FD process number: M2011007923
FIRE
11/01/2011 Comment 9:
Response:
Comment 10:
Response:
Part one of comment #3; Please provide door schedule. The
minimum door width 2' -10" (32 "clear width). Please also include
door #103 in the door schedule.
A door schedule has not been provided although all doors being
installed as part of the project are labeled with a number and
identified in the provided keynotes on sheet A-201. Door #103 is
now shown as a 2' -10" door, which is specifically identified in
keynote #18.
Please for comments #5 (Provide fire class for the movable
partition, per U.L. Assembly.) and #6 (Indicate if building has a
sprinkler system.); pursue comment #2 first (Provide all info on
plans.)
A note stating that "the building is not equipped with a fire
sprinkler system" has been added to sheet A-201. In addition,
keynote 2 has been modified to state "Movable partition with one
36° door from manufacturer to be installed. Refer to sheet A -202
and specifications for more information. This partition is
manufactured with all welded steel and class °A° components. It
does not carry a fire rating, but is non - combustible."
Please contact our office if you have any further questions.
Michael Salus
Architecture • Planning • Interior Design
1800 Eller Drive, Suite 500 • Fort Lauderdale, FL 33316 • Telephone 954.961.6806 • Facsimile 954.961.6807
MANUEL SYNALOVSKI ASSOCIATES
August 19, 2011
Miami -Dade County
11805 sw 26th street, suite 150
Miami, Florida 33175
RE: Barry University - Wiegand Center
Room 253 Nursing Simulation
11300 N.E. 2"d Avenue
FD process number: M2011007923
ENVIRONMENTAL RESOURCES
7/19/2011 Comment 1: Proposed work involves removal of existing ceiling andn
wall as noted in drawing D- 101.... An asbestos survey is
required....
Response: The space is currently underway with the required
asbestos abatement. Proper paper work will be filed and
abatement will be completed prior to commencement of
work.
STRUCTURAL
8/1/2011
Comment 1:
Response:
Comment 2:
Response:
Comment 3:
Response:
Provide written response to comments.
Refer to the provided comment response.
Provide all info on plans.
All comments have been addressed and the necessary
revisions to the drawings have been completed.
Provide the door schedule, door 101 must be rated 3/4
hour rated and have closer.
Keynote 13 on sheet D -101 and keynote 20 on sheet A-201
have both been revised to call out for a rated door with a
closer to be installed in door location 101. All associated
partitions are now scheduled to be rated and fire dampers
are scheduled to be installed.
Architecture • Planning • Interior Design
1800 Eller Drive, Suite 500 • Fort Lauderdale, FL 33316 • Telephone 954.961.6806 • Facsimile 954.961.6807
Comment 4:
Response:
Comment 5:
Response:
Comment 6:
Response:
Comment 7:
Response:
Page 2
SHT A -201, GA is not referenced in the FFPC. Provide UL
assembly for fire rated partition.
The detail referencing °GA° has been removed and
replaced with U419 (UL 263) now shown on 5/A -202.
Provide fire class for the movable partition, per U.L.
Assembly.
The partition is manufactured with all welded steel and all
Class °A° components. It is not a UL fire rated wall (does
not carry a 1 hr Fire rating but is non - combustible).
Indicate if building has a sprinkler system, If so then
provide the location and relocation of heads.
This building is not equipped with a fire sprinkler system.
Resubmit.
All drawings have now been resubmitted with this
comment response document.
Please contact our office if you have any further questions.
MANUEL SYNALOVSKI ASSOCIATES
July 7, 2011
Miami Shores Village
Building Department
10050 N.E. 2'd Avenue
Miami Shores, Florida 33138
RE: Barry University - Wiegand Center
Room 253 Nursing Simulation
11300 N.E. 2'd Avenue
Parcel ID: 1223 -11 -0011
Permit No: 11 -1036
Building Critique Sheet
7/05/11
Comment 1:
Response:
Comment 2:
Response:
Comment 3:
Response:
Comment 4:
Response:
0
Plans must be approved by Miami Dade County Fire.
General contractor will assist with expediting the approval
process.
Plans must be approved by Miami Dade DERM.
General contractor will assist with expediting the approval
process.
All permit applications must be submitted prior to any
further review.
General contractor will provide all necessary information
for future reviews.
Provide a floor plan showing the egress to the exterior of
the building.
Refer To detail 9/A-201 for provided existing floor plan
showing egress route from scope of work to a protected
stair enclosure leading to the exterior of the building.
Architecture • Planning • Interior Design
1800 Eller Drive, Suite 500 • Fort Lauderdale, FL 33316 • Telephone 954.961.6806 • Facsimile 954.961.6807
1
r
Page 2
Comment 5: Provide the fire classification for the finishes on the folding
wall.
Response: The panels themselves are steel (primed steel skins) with
all non - combustible materials. The fabric finish to cover
the steel panels will be selected by the owner as the
project moves forward. Notation listed in the "General
Notes" identifies that the flame spread classification for all
interior finishes shall comply with FBC Table 803.5 and
NFPA Table A10.22.2..
Comment 6: Provide a detail of the retractable track at the door to show
compliance.
Response: A dimension has been added to detail 4/A-301 showing
that the required 12" of clear space on the push side of
the door has been provided.
Please contact our office if you have any further questions.
Thank y
Mic ael ..Ius
Pro ect Manager