RF-12-1269Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795 -2204 Fax: (305)756 -8972 Inspection Number: INSP - 178295 Permit Number: RF -7 -12 -1269 Scheduled Inspection Date: October 10, 2012 Inspector: Bruhn, Norman Owner: CHURCH, ST ROSE OF LIMA CATHOLIC Job Address: 415 NE 105 Street Miami Shores, FL Project: <NONE> Contractor: ISAACS ROOFING & INSULATION CORP Permit Type: Roof Inspection Type: Final Roof Work Classification: Tile /Flat Phone Number (305)758 -0539 Parcel Number 1122310430010 Phone: (305)234 -5234 Building Department Comments RE -ROOF TILE AND FLAT Passe Failed Correction Needed Re- Inspection Fee No Additional Inspections can be scheduled until re- inspection fee is paid. Inspector Comments CREATED AS REINSPECTION FOR INSP- 175668. Not ready NB October 09, 2012 For Inspections please call: (305)762 -4949 Page 23 of 46 ,•,. ,4a, IMIIDA.1NTERt4tATRNAL,EidyggERittio:P , y I • i8TN 14 • • • NM* 40004-14 tritGRAt ,• • 7',,4 * • • T ,,••■ •■7, """!!',"''': 777', , .;. ; • • . • A .7;ir zogam INFoRmA .1 7, 7 7 , • • • Ftaitctil)sitetri`atititiat frigineerititarui tOlittrit r!, 16701 MA!' 117 AVenue,'Matni, FL 3g177 ," " Telephone: (3D51.;37471.591-fax:.(305/378-19:9.7 .f44. ",, "4' •,7 4-4 , H•% a , Migrni-Deid0 Lab CertificatOri 077061Z11-Stamof Florida rgt,#27g73;,,4 .77 t .1* sT4r p , %. .1, • ' 4 .' OWiliet'aPlIfe: ' ., : • .- - • " ."'. Job Addrast: - 4 Roofing toritraddr: Ff.leithit Nara-ear:, y,,,..‘-e.g• .0z4,... __Fr.0.47, ‘ _ 49 isit...a04..,1 4C ' , • . ;., ' : • .,' ,,..: i ; .. Approxittata.ft?of HeIght....,,, .4- 7 , TYPe Atces§"ta,Rodf. OtherReq uired, Testing folteiy ' • Date 440-01 ' s , „, • 4 cifir's 31::: " EOPipitent.:F.'eX-11.0-0X,Shinioo instrurnent 4 te ,7 4 Da of,Inspection. : Test Ldotilon4 .011,12; . - •• • ' • -- _ ''••• - - -- 7,7 • * - ; t.,. '114ST • • PASS .F- FAIL; • .• • , • • a.: •!.■ ' . • . - • ' • • Tet .;•ification P or F •' IUSINUMNISMIIIIMENENDI MUM NIMME I INIS= IE MIRIMMMEMEIMENMMIEIIOMMMENMEID= = MU NIS O IMMEO 2 I MMVMAIEIUN E MM INSIMIMINEEMNEff I1111N 11111 111121111 M 111111 • 41 , t '4, TOSt 6 • 7, .13 " • -• MEM 111111111 •■.• •8' , 2„9: •. o ' , 46 *48' .6 —a7 .1—.477— 7; . . POrF. • !. 63 .4:: SEIM • „ NEE IFZIK11111 IIHM11111 -4:45 •- 1111111 • 67- ‚.4 tOcatkio MEI MOM • • • P or • tY-„6.9. • 70, MIN IMO , MINN 111E111111111111/11111NINSIKIN/1111121111111111 ,16 ; MEFF1111111111 48 • 20 MEMO 53 54 • - 4. 55 • • 56 , IIMEINIIIIIII MUM sa • . 75' 76'' 77 78 79 ao • ' • RIM 9.1 ,:, • 93 ' '94 95* 98' • 99 • '100' • a • BEM 11111111 MIN ,A4 1.74, ' - ' ':■■■ — - orama1••■■•••,• 4 " es, • 4 ACCORDANCE** THE CRITERIA OF PROfOtai.*AS 106, THIS ROOF AsstiorlotHis-PASSEO.THE STATIC, UPLIFT QUALITY ConitoOt*S-1., . . , • •Paiiirnetej• , •Perirpeter. 4. Field •Garners ' Hfris'• t, Ridges, Viniyagar M. Balakrisbnaii V $tate Floirida Lie # Q107., obAddress; Contractor: Other: aliktatBORt ENGIMEERING &TESTING LAL LLC ?&S&- QV 1_4 . 4 iJ t a '17.1 S kk X. Lt t D _ 4Le-- ROC) f t t-L (o-T6) t�siiiill lailEii si.illlil�iis�� :�ii��Y�ii■ allaitaiii ■a! ■11MINSil iliL` MTggal■ Mi1l1■■ slaslsf!■1111111111111it11iii 111i =111111M '1i111l1111■ 111111111111111112111M1111111111111111111111111111111111110LAIMENNI ■ma sal iEiailamiiaaiaiitain11muAn ilea ■■1alilal 11111111■aaalaaiaaiaataa1f111M1111rsa■ ■l ■1a■iia, ails #islss ml#ssl iarsllw:Al ma mammaaamannuandmanamashwuraisaimomana aa■ ■iia■a11111 eaaaaaaa 111111a11MINIr saa110a1t■ aiiliianaaaaaaaslaaii iiilaiiiml nmmiiiii 1 all aii iiiiII ii *SImiIi-ii$iRIllii/11iii■ ■aailiaialiia11a11111i1iili1MVIM ii IMMIAa ■■aiiaiiaililailali111iailliaa 0141MIPIIMIi 11111111RMIN111111111.111111111111111111111111111111111111111111111111111LAMIS 1111111111111111111.1111111111111d111111111MILIMMEIRMIIMMIIIIIIIIII 11111111111111111111111111111111111111111111111111111ifilla mansima n7mama■ ■ii iiiii tiii *Ii *itiiiiii iaUi1': 1�i1IUUI aaaaaaaitiitalataiaalaiaaa 1rfi%ai,m maiallafa■ ■ 11■t ii■ Iil i■tiili$Iiii1'iiiiait?'a11i11■ ■iallEaiaiaiiiaiillliaaiii 1111111 1 11ia1i • 111111x111111 sa11111ii111111ssa1iia■ allJ:!(ai['il�iaa■ ■ ■aiaiilillilEalaiiiaila lirElai:li;T salxllaal 1111111111111111111111111111111111111111111111111RNMEMWW1111MMIMISM aaaaa11111aaa11iaa111a11ai #.111i1iVIC"i11xiaaa a■111ii11i111ti11MII IiMIiiiI 1 MOMAI E ■ 1111 »a ■iia1i ■111$1111111 /1111 '11 *a1faia■ ■/ 1$ 11 ■1111•11Ma$IR$* *Miiialiia$i:Jtt' �:11111a1 ,a.a111111aaa1111117 111I1atal1MilLKIIIV111a11ii11 11111!"amsm"i"rl1aii"r"" " "" `, 1al1 aa111iaia aaaia11M riFIEENPAR Mit 721111111PIrlittitiMaarallillitanniniall ■1111111$ iailli1t r1111111. =11 111111afa■ 111a111101 A -11 s =:ii-e MIP144 ~�. 11 rhA ? 1111» 1111iiili1t lail Tit 11 E 5, r 4 ■a1a11 ge c i 'iiirll ARPlaiilr# I i'G111$ 11111111 Mahal! i MMEZINsi lniii �!��[ULilian ESIIMiITIPM:"11ia1■ asaa$l.URaU[!7' aal i EMJEVARLA. hiiiII AIMM>s ■1111i11iiailii iii maialll uaiiil ma Notes NOTICE OF COMMENCEMENT A RECORDED COPY GMT BE POSTED ON TIC Jett SAT PERMIT NO. AO /2-4 •:f r TAX OLIO STATE OF FLORIDA:,, COUNTY OF MIAMI -DADS THE f krl win be made to certain real'. th'( , „ 71 3, I , the b�Wrig ProPe►Y hformatiort 1 11111111111111111111111111 1111111111 11111111 CFN 2O12RO5147O7 OR Bk 2819E Ps 1492; (1ns) RECORDED 07/23/2012 11 :40:15 HARVEY RUVIN, CLERK OF COURT HIAtiI -DADE COUNTY, FLORIDA LAST PAGE. 1. Legal descr ptio elpr rty,a 2. Description of improvement tleddr !S .No /0,ys.1-_ tr mt of 8 . Lenn r }(7~ i SeCti 713 73(1Pe►soiis Wtt S z� Y` iia a ok OWner Upon whom notices or *r a g , OthBr dOpR11er1tq Abe served l fiS °prDldded by N� Ai'ttiita�d °sii4'1 n,si.:�+'..a•t::�... 8 m addition htmself; O fi fes fopobvU rg per�n(s) to race a 71 %1iIorl4Stie� _- :WS t� Name dares s 9. Expiration d of Hits Notice of Coferri etheht• 011 date l?i 11r iiii irOt I W Yi10yi1N1Oi� PA 'a YMEl rs MADE BY OWNIERAFi R THE RA`I1Otd OF I�ERID CHAPTER. 713. PART 1 CTION 713.13. A §TA I TOY• FF"�s . IF • N�,�7E D YO B , CO SULT 61 UR. ORltip o s 0tt� I� NG FTHE OR RECORDING YOUR NOTICE OF COMMENCEMENT. . , YQUR LE,NI7ffFi Q � J1 N p IG. WQR!{ C:QdI�iT _ Sr Print Name ���` keger/Partner/Markiger PrepareA By,. _i: /, . ; .. STA ,v .. for Persdr��° Litt °" A K 'identification: Print Name: (SEAL) IA 2C'I•, i1r ..11 T• nI• Under penal$ bf pet, y,. fuereitiA that 1 have read ilia f i eg&kig a}rd'; that the facts stated In it are true, to the best of my knowledge and belief. . Stgna, ;" ) of a s or i- BONDED THEW ATLANncBOxnnvccO,INC. - s Al s •` • Officer/ Director /PartneriManager who signed above: By nwrintatz NOT PiJ Uc :'iTATE OF FLOR Dg Reina Pine • Commission # EE092375 Expires: MAY 10, 2015. 123.01 -52 PAGES 210 By STAOF FLORIDA, COUNTY OF DADE I HEREBY Y CERTIFY that this is a true copy of the orllglr►a! 12n; re rrL„ day of WITNESS my hand and G;I ri9; HAR Y ' i CLERK, of C rcuit e County C.ou1s D.C. Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 INSPECTION'S PHONE NUMBER: (305) 762.4949 U DING PERMIT APPLICATION Permit Type: BUILDING REC=EIVED FBC,O n Permit No. eor � 120—i Master Permit No. ROOFING JOB ADDRESS: 4t S tJ t oS Sr. City: Folio/Parcel #: Miami Shores County: Miami Dade Zip: Is the Building Historically Designated: Yes NO Flood Zone: OWNER: Name (Fee Simple Titleholder): 1 • w :o t A- Phone #: Address: ��4 i s 0°C. Inc s T City: /2") • °Afv, �' < S State: Zip: as 1,5r2 Tenant/Lessee Name: Phone#: Email: CONTRACTOR: Company Name: •SAAC.3 .if 1, 4:: Phone #: O ..S8& 6(SJ- Address: e12 -2.5 .S . 17 l vAc li-k0.4) City: ‘----0s `,M €"r t 'A'( State: C) . Zip: Qualifier Name: Al A.si NS CO .Th.ni Z,.A4 'L Phone#: State Certification or Registration #: C c.c., 3 25 SS G Certificate of Competency #: Contact Phone #:1$G, • Zvi '1 S. CAI Email Address: DESIGNER: Architect/Engineer: Phone #: ®o Value of Work for this Permit: $ 1221600 ® Square/Linear Footage of Work: 2o,'1v0 0 5 iF ;• Type of Work: ❑Addition OAlteration UNew epair/Replace ❑Demolition Description of Work: 'ZS -1V-00 `r' 'no -Ca d'd c, � r4�t 'Co °C-1 AI Color thru tile: **** *** * * * * * * *:x***Fees* * ** **** ****** * *** ** ***mix *** * ******* * * ** Submittal Fee Permit Fee $ 7 CI CCF $ CO /CC $ Scanning Fee $�'' Radon Fee $ DBPR $ Bond $ Notary $ Training/Education Fee $ Technology Fee $ Double Fee $ Structural Review $ TOTAL FEE NOW DUE $ A 4 30 Bonding Company's Name (if applicable) Bonding Company's Address City State Zip Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and MR CONDITIONERS, ETC OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will not be apprpved and a reinspection fee will be charged. Signature Z(1�.�t„.c'�Kl��"'�"'Y Signature The forging instrument was acjjCn�wldged ,belfore me thi day o()0(12) , 20 /t, IS Contractor The foregoing instrument was acknowledged before me this ) � day of - i\- L , 20 ! tby i C d@) 1; arm"`' who is personally known to me or who has produced as identification and who did take an oath. who is personally known to me or who has produced As identification and who did take an oath. NOTARY PUBLIC: Sign, Pri My : mission Expire NOTARY PUBLIC STATE OF FLORIDA Comm# EE095931 5 414 ° **�x***x*av*�:*avav�::x�x****a� :,,.:���* @ �x *+ ��m��x****�x, v�x�a�xa�*a�*+ x+ ux�***: x**+ x+ x*avw* ***+ u�x�z*�x�xm***�x�xx��x� 'Mka*+x***** NOTARY PUBLIC: Sign: Print: \`\``\ 1111111II A ri ea 40, My Commission Expires: :�/'4 , ' e °`�: ° ,c; APPROVED BY 0 °�� Plans Examiner Structural Review (Revised 3 /I2/2012)(Revised 07 /10 /07)(Revised 06/10 /2009)(Revised 3/15/09) Zoning Clerk Permit No: 12 -1269 Job Name: July 18, 2012 Miami Shores Vivage Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 Page 1 of 1 Building Critique Sheet 1) Provide approval from Miami Dade County DERM. 2) Section B is incomplete and does not match the job. Follow the directions at the top of section B and resubmit. 3) Identify the roof system being used for each roof section. STOPPED REVIEW I called Alain and the office. Plan review is not complete, when all items above are corrected, we will do a complete plan review. If any sheets are voided, remove them from the plans and replace with new revised sheets and include one set of voided sheets in the re- submittal drawings. Norman Bruhn CBO 305 - 762 -4859 Florida Buildin High Velocity Hurricane Zor Section A (G`n )02 /0) 1 HIGH - VELOCITY HURRICANE ZONE! Master hermit No. La —1)- 1. Y Process No. Contractor's Name S ec t ,s 4=49 -ei c, `/3- /Vt /05-5,- ./ Job Address iLow Slope ❑ Asphaltic Shingles ROOF CATEGORY ❑ Mechanically Fastened Tile ❑ Metal Panel /Shingles "Mortar/Adhesive Set Tile 0 Wood Shingles /Shakes ❑ Prescriptive BUR -RAS 150 ROOF TYPE ❑ New Roof Reroofing ❑ Recovering ❑ Repair ❑ Maintenance ROOF SYSTEM INFORMATION Low Slope Roof Area (SF) Steep Sloped Roof Area (SF) Total (SF) soo 7%w /8cIeo Section B (Roof Plan) Sketch Roof Plan: Illustrate all levels and sections, roof drains, scuppers, overflow scuppers and overflow drains. Include dimensions of sections and levels, clearly-14 identify dimensions of elevated pressure zones and location of parapets. 'T( qo elfht:bn 164 tell -F4Y6 F 14- •Glee. it �- f Fla (Wilk .TSd .75# ?lox Sled g &veld 61,7 al Fr. Tile Rua System "Delivering Excellence Every Day" Roof System Manufacturer: Miami-Dade County Building & Neighborhood Compliance Department HVHZ Electronic Roof Permit Form Section D Tile Roof System I Verea Notice of Acceptance Number (NOA): 11-0722.02 Minimum Design Wind Pressures, If Applicable (from RAS 127 or Calculations): P 1: 45.1 P 2: P 3: 116..2 Maximum Design Wind Pressures, (From the NOA Specific system): 63.212 psf Fill in the specific roof assembly components. if a component is not required, insert not applicable (n/a) in the text box. Roof Slope: Roof Mean Height: "/12" 20 Method of Tile Attachment: ft. 1—Adhesive, Large Paddy Polyfoam Polypro-- Alternate Method of Tile Attachment per NOA: Drip Edge Size & Gauge: Drip Edge Material Type: Edge Fastener Type: [-3" face 26 ga.-: --Galvinized Metal-- 1/14" ring shank Hook Strip/Cleat gauge or weight: — Select Hook Strip — Deck Type: 6 11 6" T & Optional Insulation: In a Optional Nailable Substrate: n/a Optional Nailable Substrate Attachment: Basesheet Type: 30# Fastener Type for Basesheet Attachment: 1 1/4" ring shank and nails. Tile Underlayment (Cap Sheet ) Type: 90# Tile Underlayment Attachment Method: hot mopped Tile Profile: Section 1F. MIAMI "Delivering Excellence Every Day" Miami -Dade County Building & Neighborhood Compliance Department HVHZ Electronic Roof Permit Form Section E (Tile Calculations) Method 1 "Moment Based Tile Calculations Per RAS 127" For Moment based tile systems, use Method 1. Compare the values for Mr with the values from Mf. If the Mf values are greater than or equal to the Mr values, for each area of the roof, then the tile attachment method is acceptable. P1:i4�•1 xA, P 2: (78.6 ._.. x P3:1116.2 x 29.08 42.99 - Mg: - Mg: - Mg: 6.21 6.21 = Mr1: = Mr2: = Mr3: 10.00 22.87 36.78 5 5 5 63.21 63.21 Method 3 "Uplift Based Tile Calculations Per RAS 127" NOA Mf NOA Mf NOA Mf For Uplift ba • tile systems use Method 3. Compare the values for F' with the values for Fr. If the F' values are greater than or equal to the Fr values, for each area of the • of, then the tile attachment method is acceptable. P1: P2: P3: xw: xw: x W. Where to - W: - W: - W: x cos 0: = Fr1: x cos 0: = Fr2: x cos 0: = Fr3: MIN tain Information to complete tile calculations 5 NOA F' NOA F' NOA F' Where to Find Description Symbol Design Pressure P1 or P2 or P3 Table 1 RAS 127, engineer based on A by an engineer analysis prepared, signed and sealed by a professional E 7. Mean Roof Height Job Site Roof Slope Job Site Aerodynamic Multiplier Restoring Moment due to Gravity Attachment Resistance ct Approval (NOA) Product A Product Approv royal (NOA) NOA) Required Moment Resistance Calculated Minimum Attachment Resistance F' Required Uplift Resistance Fr Average Tile Weight W Product Approval (NOA) Product Approval (NOA) Tile Dimensions I = length w = width Calculated Product Approval (NOA) Section:C MIAMI COUNTY "Delivering Excellence Every Day" Miami -Dade County Building & Neighborhood Compliance Department HVHZ Electronic Roof Permit Form Section C page (Low Slope Roof Systems) Fill in the specific roof assembly components. if a component is not required, insert not applicable (n/a) in the text box. Top Ply: ROOF SYSTEM MANUFACTURER: Product Approval (NOA): 08- 1028.02 System Type: Wind Uplift Pressures, From RAS 128 or Sealed Calculations: (P1) Field: 42.8 (P2) Perimeters: (P3) Comers: psf psf psf Maximum Design Pressure From NOA: Roof Slope: Parapet Walls: 1/8 Deck Type: Support Spacing: Altemate Deck Type: Existing Roof: " : 12 Roof Mean Height: psf 10 No ❑ Yes Parapet wall Height: — Structural Concrete- " o/c ft. Fire Barrier: n/a Vapor Barrier: Anchor Sheet: n/a Anchor Sheet Fastener / Bonding Material: n/a Insulation Base Layer Size & Thickness: 1.5" ISO Insulation Base Layer Fastener / Bonding Material: Hot asphalt Insulation Top Layer Size & Thickness: 1/2" Perlite Insulation Top Layer Fastener / Bonding Material: [hot asphalt Base Sheet(s) & No. of Ply(s): Ruberoid 20 Base Sheet Fastener / Bonding Material: [hot asphalt Ply Sheet(s) & No. of Ply(s): n/a Ply Sheet Fastener / Bonding Material: ft. Ruberoid 170 FR Top Ply Fastening / Bonding Material: hot asphalt Surfacing: In/a SINGLE PLY MEMBRANE: Single Ply Manufacturer / Type: n/a Single Ply Sheet Width: No. of Single Ply 1/2 sheets: " 1/2 Sheet Width: Single Ply Membrane Fastening / Bonding Material: ❑ FASTENER SPACING FOR BASESHEET ATTACHMENT ❑ SINGLE PLY MEMBRANE ATTACHMENT 1. Field: ri " o/c @ Laps & rows " o/c 2. Perimeter: Ei " o/c @ Laps & ri rows Ej " o/c 3. Comer: 1-1" o/c @ Laps & rows , " o/c NUMBER OF FASTENERS PER INSULATION BOARD: 1. Field: 2. Perimeter: 3. Comer. ri Insulation Fastener Type : n/a WOOD NAILER TYPE AND SIZE: Wood Nailer Fastener Type and Spacing: EDGE & COPING METAL SIZES: Metal Material: Edge Size: Hook Strip Size: Edge Metal Attachment: — Galvanized Metal- -3" face 26 ga.— — SELECT EDGE METAL HOOK STRIP SIZE— Edge Coping Material: — SELECT PARAPET WALL COPING MATERIAL— Coping Size: ELECT COPING METAL SIZE OR THICKNESS Hook Strip Size: — SELECT COPING METAL HOOK STRIP SIZE— 1 Parapet Coping Metal Attachment: Section C2 COUNTY "Delivering Excellence Every Day" Miami -Dade County Building & Neighborhood Compliance Department HVHZ Electronic Roof Permit Form Illustrate Components Noted and Details as Applicable: Woodblocking, Gutter, Edge Terminations /Stripping /Flashing, Continuous Cleat, Cant Strip, Base Flashing, Counterflashing, Coping, Etc. Indicate: Mean Roof Height, Parapet Height, Height of Base Flashing, Component Material, Material Thickness, Fastener Type, Fastener Spacing Or: Submit Manufacturers Details that Comply with RAS -111 and Chapter 15 HVHZ, FBC. 13 "x3" drip edge I Ruberoid 20 170 FR 1.511 ISO 11/2" Perlite Par et Wall Height Me Ro of Height 10' file:/ / /Cl/Documents %20and %20Settings/ sky / Desktop /rooWo20permit%20forms /Section %20C2d.htm9 /5/2007 7:18:20 AM Section,:C Miami -Dade County Building & Neighborhood Compliance Department HVHZ Electronic Roof Permit Form "Delivering Excellence Every Day" Section C page (Low Slope Roof Systems) Fill in the specific roof assembly components. If a component is not required, insert not applicable (n/a) in the text box. Top Ply: ROOF SYSTEM MANUFACTURER: Product Approval (NOA): 09- 0224.01 System Type: Al Wind Uplift Pressures, From RAS 128 or Sealed Calculations: (P1) Field: 42.8 (P2) Perimeters: (P3) Comers: psf 108 psf psf Maximum Design Pressure From NOA: Roof Slope: Parapet Walls: 1/8 Deck Type: Support Spacing: Alternate Deck Type: Existing Roof: 0 " : 12 Roof Mean Height: psf 10 No ❑ Yes Parapet wall Height: —1" x 6" T & G- " o/c ft. Fire Barrier: 1n/a Vapor Barrier: Anchor Sheet: Anchor Sheet Fastener / Bonding Material: 1 1/4" ring shank nails and tin caps Insulation Base Layer Size & Thickness: 11.5" ISO Insulation Base Layer Fastener / Bonding Material: Hot asphalt Insulation Top Layer Size & Thickness: 1/2" Perlite Insulation Top Layer Fastener / Bonding Material: hot asphalt Base Sheet(s) & No. of Ply(s): Ruberoid 20 Base Sheet Fastener / Bonding Material: Ply Sheet(s) & No. of Ply(s): n/a Ply Sheet Fastener / Bonding Material: ft. Ruberoid 170 FR Top Ply Fastening / Bonding Material: hot asphalt Surfacing: Fn /a SINGLE PLY MEMBRANE: Single Ply Manufacturer / Type: Single Ply Sheet Width: No. of Single Ply 1/2 sheets: Single Ply Membrane Fastening / Bonding Material: " 1/2 Sheet Width: FASTENER SPACING FOR BASESHEET ATTACHMENT ❑ SINGLE PLY MEMBRANE ATTACHMENT 1. Field: 2. Perimeter: " o/c @ Laps & " o/c @ Laps & rows "o /c rows " o/c 3. Comer: " o/c @ Laps & rows ' " o/c NUMBER OF FASTENERS PER INSULATION BOARD: 1. Field: 2. Perimeter: El 3. Comer. Ei Insulation Fastener Type : WOOD NAILER TYPE AND SIZE: 2 "x 6" Wood Nailer Fastener Type and Spacing: 8d 8" o.c. EDGE & COPING METAL SIZES: Edge Metal Material: Edge Size: Hook Strip Size: Edge Metal Attachment: — Galvanized Metal- - SELECT EDGE METAL HOOK STRIP SIZE -- Coping Material: Coping Size: Hook Strip Si Parapet Coping Metal Attachment: [— SELECT PARAPET WALL COPING MATERIAL— ELECT COPING METAL SIZE OR THICKNESS - ze — SELECT COPING METAL HOOK STRIP SIZE -- rSection C2 MIAMI'DADE COUNTY', "Delivering Excellence Every Day" Miami -Dade County Building & Neighborhood Compliance Department HVHZ Electronic Roof Permit Form Illustrate Components Noted and Details as Applicable: Woodblocking, Gutter, Edge Terminations /Stripping /Flashing, Continuous Cleat, Cant Strip, Base Flashing, Counterflashing, Coping, Etc. Indicate: Mean Roof Height, Parapet Height, Height of Base Flashing, Component Material, Material Thickness, Fastener Type, Fastener Spacing Or: Submit Manufacturers Details that Comply with RAS -111 and Chapter 15 HVHZ, FBC. 170 FR Ruberoid 20 3" x 3" Drip edge 75# —11.5" ISO 1 11/2" Perlite 1 Parapet Mean 10' file:// /Cl/Documents %20and %20Settings/ sky / Desktop / root% 20permit %20forms /Section %20C2d.htm9 /5/2007 7:18:20 AM ft. Owner's Notification Form HVHZ 2010 "Delivering Excellence Every Day" SECTION 1524 HIGH VELOCITY HURRICANE ZONES — REQUIRED OWNERS NOTIFICATION FOR ROOFING CONSIDERATIONS 1524.1 Scope. As it pertains to this section, it is the responsibility of the roofmg contractor to provide the owner with the required roofing permit, and to explain to the owner the content of this section. The provisions of Chapter 15 of the Florida Building Code, Building govern the minimum requirements and standards of the industry for roofmg system installations. Additionally, the following items should be addressed as part of the agreement between the owner and the contractor. The owner's initial in the designated space indicates that the item, as been explained. 1. Aesthetics - workmanship: The workmanship provisions of Chapter 15 (High Velocity Hurricane Zone) are for the purpose of providing that the roofmg system meets the wind resistance and water intrusion performance standards. Aesthetics (appearance) are not a consideration with respect to workmanship provisions. Aesthetic issues such as color or architectural appearance, that are not part of a zoning code, should be addressed as pa of the agreement between the owner and the contractor. 2. Renailing wood decks: When replacing roofing, the existing wood roof deck may have to be renailed in accordance with the current provisions of Chapter 16 (High Velocity Hurricane Zones) of the Florida Build' g Code. (The roof deck is usually concealed prior to removing the existing roof system). 3. Common roofs: Common roofs are those which have no visible delineation between neighboring units (i.e. townhouses, condominiums, etc.). In buildings with common roofs, the roofmg contractor and/or owner 1 hould notify the occupants of adjacent units of roofmg work to be performed. Via 4. Exposed ceilings: Exposed, open beam ceilings are where the underside of the roof decking can be viewed from below. The owner may wish to maintain the architectural appearance; therefore, roofing nail penetrations of the underside of the decking may not be acceptable. The owner provides the option of maintaining this appearance. 5. Ponding water: The current roof system and/or deck of the building may not drain well and may cause water to pond (accumulate) in low -lying areas of the roof. Ponding can be an indication of structural distress and may require the review of a professional structural engineer. Ponding may shorten the life expectancy and performance of the new roofing system. Ponding conditions may not be evident until the original roofing system is removed. Ponding conditions should be corrected. rzz 6. Overflow scuppers (wall outlets): It is required that rainwater flow off so that the roof is not overloaded from a build up of water. Perimeter /edge walls or other roof extensions may block this discharge if overflow scuppers (wall outlets) are not provided. It may be necessary to install overflow scuppers in accordance with the requirements of: Chapter 15 and 16 herein and the Florida Building Code, Plumbing. 7. Ventilation: Most roof structures should have some ability to vent natural airflow through the interior of the structural assembly (the building itself). The existing amount of attic ventilation shall not be reduced. Exception: Attic spaces, designed by a Florida- licensed engineer or registered architect to eliminate the attic venting, venting shall not be required. Owner's /Agent's Signature: Contractor's Signature: Date: / Permit Number: Property Address: ... f_. o M PAMI. DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) MIAMI -DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175 -2474 T (786) 315 -2590 F (786) 315 -2599 www.miamidade.eov /pera Ceramica Verea Ctra. N -634 San Sebastian, Santiago, Km 683 Lanza S/N 15685 Mesia (Coruna) Spain SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County PERA - Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. PERA reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: Clay Spanish "S" Roof Tile LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved ", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA consists of pages 1 through 6. The submitted documentation was reviewed by Alex Tigera. APPROVED NOA No.: 11- 0722.02 Expiration Date: 03/13/13 Approval Date: 02/09/12 Page 1 of 6 ROOFING ASSEMBLY APPROVAL Category: Sub Category: Material: Roofing Roofing Tiles Clay 1. SCOPE This approves a roofing system using Clay Spanish "S" Roof Tile manufactured by Ceramica Verea, S.A. in La Coruna, Spain and is distributed by Ceramica Verea, USA, as described in Section 2 of this Notice of Acceptance. For locations where the pressure requirements, as determined by applicable Building Code does not exceed the design pressure values obtained by calculations in compliance with RAS 127 using the values listed in section 4 herein. The attachment calculations shall be done as a moment based system. 2. PRODUCT DESCRIPTION Manufactured by Applicant Dimensions Clay Spanish "S" Roof L = 19.5" Tile W = 11.3" Trim Pieces Length: varies Width: varies varying thickness 2.1 MANUFACTURING LOCATION 2.1.1. San Sebastian, Spain 2.2 EVIDENCE SUBMITTED Test Specifications ASTM C1167 ASTM C1167 Test Agency Test Identifier American Test Lab of South RT0706.01 -11 Florida IBA Consultants, Inc. 4709 -3 Product Description High profile clay roof tile. For direct deck, adhesive set applications. Accessory trim, clay roof pieces for use at hips, rakes, ridges and valley terminations manufactured for each tile profile. Test Name/Report ASTM C 1167 TAS 101 Date 07/19/11 12/21/07 NOA No.: 11- 0722.02 Expiration Date: 03/13/13 Approval Date: 02/09/12 Page 2 of 6 3. LIMITATIONS: 3.1 Fire classification is not part of this acceptance. 3.2 For mortar or adhesive set tile applications, a static field uplift test in accordance with TAS 106 may required, refer to applicable building code. 3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform quarterly test in accordance with TAS 112, appendix `A'. Such testing shall be submitted to the Building and Neighborhood Compliance Department — Product Control Section for review. 3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed section 4.1 herein. 3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated otherwise by the underlayment material manufacturers published literature. 3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with applicable building code. 4. INSTALLATION 4.1 Clay Spanish "S" Tile and its components shall be installed in strict compliance with Roofing Application Standard RAS -120. 4.2 Data For Attachment Calculations. Table 1: Average Weight (W) and Dimensions (I x w Tile Profile Weight -W (Ibf) Length -I (ft) Width-w (ft) Clay Spanish "S" Tile 8.3 1.625 0.942 Table 3: Restoring Moments due to Gravity - Mg (ft-lbf) Table 2: Aerodynamic Multipliers - A (ft3) Tile Profile 3 ":12" A (ft3) Batten Application A (ft3) Direct Deck Application Clay Spanish "S" Tile 7 ":12" or Greater N/A 0.37 Table 3: Restoring Moments due to Gravity - Mg (ft-lbf) Tile Profile 2 ":12" 3 ":12" 4 ":12" 5 ":12" 6 ":12" 7 ":12" or Greater Clay Spanish "S" Tile Direct Deck Direct Deck Direct Deck Direct Deck Direct Deck Direct Deck 6.46 6.36 6.21 6.01 5.74 5.40 Table 6: Attachment Resistance Expressed as a Moment - Mf (ft -Ibf) for Single Patty Adhesive Set Systems Tile Profile Tile Application Minimum Attachment Resistance Clay Spanish "S" Tile Polyfoam PolyProTM 63.212' 1 Large paddy placement weight 34.6 grams of PolyPro'TM. NOA No.: 11- 0722.02 Expiration Date: 03/13/13 Approval Date: 02/09/12 Page 3 of 6 5. LABELING 5.1 All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo as detailed below, or following statement: "Miami -Dade County Product Control Approved ". VEREA SPAIN CE LABEL FOR CLAY SPANISH "S" ROOF TILE (LOCATED ON THE SIDE OF TILE) 6. BUILDING PERMIT REQUIREMENTS: 6.1 Application for building permit shall be accompanied by copies of the following: 6.1.1 This Notice of Acceptance. 6.1.2 Any other documents required by Building Official or Applicable building code in order to properly evaluate the installation of this system. NOA No.: 11- 0722.02 Expiration Date: 03/13/13 Approval Date: 02/09/12 Page 4 of 6 PROFILE DRAWING CLAY SPANISH S ROOF TILE END OF THIS ACCEPTANCE NOA No.: 11- 0722.02 Expiration Date: 03/13/13 Approval Date: 02/09/12 Page 5 of 6 GREEN SUSTAINABLE ATTRIBUTES (GSA) SCOPE: This document is solely for the purpose of verification of Sustainable Attributes of construction materials. The documentation submitted has been reviewed by Miami -Dade County Product Control Section. G.I Component Name ECTANE AND TI Initial Reflectance Clay Spanish "S" Tile 0.39 Aged Reflectance Pending Initial Emmitance 0.83 Aged Emmitance Pending Solar Reflectance Index (SRI) 41 NOA No.: 11- 0722.02 Expiration Date: 03/13/13 Approval Date: 02/09/12 Page 6 of 6 MIAM DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY AFFAIRS (PERA) BOARD AND CODE ADMINISTRATION DIVISION NOTICE OF ACCEPTANCE (NOA) 3M Company 3M Center Building 0220- 05 -E -06 St. Paul, MN. 55144 -1000 MIAMI -DADE COUNTY PRODUCT CONTROL SECTION 11805 SW 26 Street, Room 208 Miami, Florida 33175 -2474 T (786) 315 -2590 F (786) 315 -2599 www.miamidade.eov /sera SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade County PERA - Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. PERA reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code including the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: 31WM 2- Component Foam Roof Tile Adhesive AH -160 LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved ", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This renews and revises NOA# 11- 0124.04 and consists of pages 1 through 7. The submitted documentation was reviewed by Alex Tigera. NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 1 of 7 ROOFING COMPONENT APPROVAL: Category: Sub Category: Materials: Roofing Roof tile adhesive Polyurethane SCOPE: This approves 3MTM 2- Component Foam Roof Tile Adhesive AH -160 as manufactured by 3M Company as described in Section 2 of this Notice of Acceptance. For the locations where the design pressure requirements, as determined by applicable building code, does not exceed the design pressure values obtained by calculations in compliance with Roofing Application Standard RAS 127, for use with approved flat, low, and high profile roof tiles system using 2- Component Foam Roof Tile Adhesive AH -160. Where the attachment calculations are done as a moment based system for single patty placement, and as an uplift based system for double patty systems PRODUCTS MANUFACTURED BY APPLICANT: Product Dimensions Test Product Description Specifications 3MTM 2- Component Foam N/A TAS 101 Two component polyurethane foam adhesive Roof Tile Adhesive AH- 160 Foam Dispenser RTF1000 N/A Dispensing Equipment ProPack® 30 & 100 N/A Dispensing Equipment PRODUCTS MANUFACTURED BY OTHERS: Any Miami -Dade County Product Control Accepted Roof Tile Assembly having a current NOA which list moment resistance values with the use of 2- Component Foam Roof Tile Adhesive AH -160 roof tile adhesive. MANUFACTURING LOCATION: 1. Tomball, TX. PHYSICAL PROPERTIES: Property Density Compressive Strength Tensile Strength Water Absorption Moisture Vapor Transmission Dimensional Stability Closed Cell Content MIAMI-DADE COUNTY APPROVED Test ASTM D 1622 ASTM D 1621 ASTM D 1623 ASTM D 2127 ASTM E 96 ASTM D 2126 ASTM D 2856 Results 1.61bs. /ft.3 18 PSI Parallel to rise 12 PSI Perpendicular to rise 28 PSI Parallel to rise 0.08 Lbs./Ft2 3.1 Perm / Inch +0.07% Volume Change @ -40° F., 2 weeks +6.0% Volume Change @158°F., 100% Humidity, 2 weeks 86% NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 2 of 7 Note: The physical properties listed above are presented as typical average values as determined by accepted ASTM test methods and are subject to normal manufacturing variation. EVIDENCE SUBMITTED: Test Agency Center for Applied Engineering Miles Laboratories Polymers Division Ramtech Laboratories, Inc. Southwest Research Institute Trinity Engineering Celotex Corp. Testing Services Test Identifier #94 -060 257818 -1PA 25- 7438 -3 25- 7438 -4 25 -743 8 -7 25 -7492 NB -589 -631 9637 -92 01 -6743 -011 01- 6739- 062b[1] 7050.02.96 -1 528454 -2 -1 528454 -9 -1 528454 -10 -1 520109 -1 520109 -2 520109 -3 520109 -6 520109 -7 520191 -1 520109 -2 -1 Test Name/Report TAS 101 TAS 101 SSTD 11 -93 SSTD 11 -93 SSTD 11 -93 ASTM D 1623 ASTM E 108 ASTM E 108 ASTM E 84 TAS 114 TAS 101 TAS 101 Date 04/08/94 12/16/96 10/25/95 11/02/95 12/12/95 02/01/94 04/30/93 11/16/94 01/16/95 03/14/96 10/23/98 12/28/98 TAS 101 03/02/99 LIMITATIONS: 1. Fire classification is not part of this acceptance. Refer to the Prepared Roof Tile Assembly for fire rating. 2. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 shall solely be used with flat, low, & high tile profiles. 3. Minimum underlayment shall be in compliance with the Roofing Application Standard RAS 120. 4. Roof Tile manufactures acquiring acceptance for the use of 3MTM 2- Component Foam Roof Tile Adhesive AH- 160 roof tile adhesive with their tile assemblies shall test in accordance with TAS 101. 5. Roof Tile manufactures acquiring acceptance for the use of HANDI -STICK roof tile adhesive with their tile assemblies shall test in accordance with TAS 101 with section 10.4 as modified herein. F -W 2 F'= MS NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 3 of 7 INSTALLATION: 1. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 may be used with any roof tile assembly having a current NOA that lists uplift resistance values with the use of 3MTM 2- Component Foam Roof Tile Adhesive AH -160. 2. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 shall be applied in compliance with the Component Application section and the corresponding Placement Details noted herein. The roof tile assembly's adhesive attachment with the use of 3MTM 2- Component Foam Roof Tile Adhesive AH -160 shall provide sufficient attachment resistance, expressed as an uplift based system, to meet or exceed the uplift resistance determined in compliance with Miami -Dade County Roofing Application Standards RAS 127. The adhesive attachment data is noted in the roof tile assembly NOA. 3. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 and its components shall be installed in accordance with Roofing Application Standard RAS 120, and 3M Company's 3MTM 2- Component Foam Roof Tile Adhesive AH- 160 Operating Instruction and Maintenance Booklet. 4. Installation must be by a Factory Trained 'Qualified Applicator' approved and licensed by 3M Company. 3M Company shall supply a list of approved applicators to the authority having jurisdiction. 5. Calibration of the Foam Dispenser RTF1000 dispensing equipment is required before application of any adhesive. The mix ratio between the "A" component and the "B" component shall be maintained between 1.0 -1.15 (A): 1.0 (B). The dispense timer shall be set to deliver 0.0175 to 0.15 pounds per tile as determined at calibration. No other settings shall be approved. 6. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 shall be applied with Foam Dispenser RTF1000 or ProPack® 30 & 100 dispensing equipment only. 7. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 shall not be exposed permanently to sunlight. 8. Tiles must be adhered in freshly applied adhesive. Tile must be set within 2 to 3 minutes after 3MTM 2- Component Foam Roof Tile Adhesive AH -160 has been dispensed. 9. 3MTM 2- Component Foam Roof Tile Adhesive AH -160 placement and minimum patty weight shall be in accordance with the 'Placement Details' herein. Each generic tile profile requires the specific placement noted herein. Table 1: Adhesive Placement For Each Generic Tile Profile Tile Profile Placement Detail Single Paddy Weight Min. (grams) Two Paddy Weight per paddy Min. (grams) Flat, Low, High Profiles #1 35 N/A High Profile (2 Piece Barrel) #1 17 /side on cap and 34 /pan N/A Flat, Low, High Profiles #2 24 N/A Flat, Low, High Profiles #3 8 NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 4 of 7 LABELING: All 3MTM 2- Component Foam Roof Tile Adhesive AH -160 containers shall comply with the Standard Conditions listed herein. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or applicable building code in order to properly evaluate the installation of this system. ADHESIVE PLACEMENT DETAIL 1 SINGLE PATTY Nall through plastic cement Underlayment (Beneath Tile) 1) Place enough adhesive to achieve 17 to 23 Optional 2x4's for s square inches In contact with the pan die tep pitch applicatlora To 11n. From 2) Tum covers upside down. Place adhesive 112ln` Then install the die. de edge ofcovertils /� 101n. E Course Underlayment Nall through plastic cement Eave course only: Keep adhesive approx. 41n. up from weepholes MIAMI-DADE COUNTY APPROVED Faso Eave Closure Remo top portion of the save course cover tile. Abut to second course of pan tiles Ensure cave end of pan and cover dies are flush at ears line. Eave dosure (mortar shown) Weephole Fascia Sheathing Optional Point-up Mortar an longitudinal edges of tile NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 5 of 7 ADHESIVE PLACEMENT DETAIL 2 SINGLE PATTY Nail through plastic cement M -4 21n. 41116." r rd." Fascia `� �• Weephole Eave closure Drip edge Underlayme 7 In. Paddy (Beneath Tile) MIAMI -DADE COUNTY APPROVED Nail through plastic cement Eave Course Paddy (Beneath Tile) Underlayment 7 In in. Eave Closure Eave Course Fascia NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 6 of 7 ADHESIVE PLACEMENT DETAIL 3 DOUBLE PATTY Nail through plastic cement Paddy (between tile) Paddy (under tile) %,''3in. x3in. Single paddy on under- layment _ Single paddy under tile Single paddy on top of tile MIAMI-DADE COUNTY APPROVED • In. X 7 In. medium size paddy eave Fascia course only Eave course Nail through plastic cement Nall through plastic cement Underlayment Single paddy under tile Single paddy between tile 2 In. x 7 In. medium size paddy eave course only Ain. x 3 in. / 41n. Single paddy on under - layment Single paddy on top of tile Eave Course Single paddy under tile Single paddy between tile QP- in. x3in. Single paddy on underlayment 4 in Single paddy on top of tile Eave Course Eave Closure 2 in. x 7 in. medium Fasda� paddy eave course only END OF THIS ACCEPTANCE Fascia Weephole Eave closure Drip edge NOA No.: 12- 0228.18 Expiration Date: 05/10/17 Approval Date: 05/10/12 Page 7 of 7 MIA M I.DADE BUILDING CODE COMPLIANCE OFFICE (BCCO) PRODUCT CONTROL DIVISION NOTICE OF ACCEPTANCE (NOA) MIAMI -DADE COUNTY, FLORIDA METRO -DADE FLAGLER BUILDING 140 WEST FLAGLER STREET, SUITE 1603 MIAMI, FLORIDA 33130 -1563 (305) 375 -2901 FAX (305) 375 -2908 GAF Material Corporation 1361 Alps Road Wayne, NJ 07470 SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed by the BCCO and accepted by the Building Code and Product Review Committee to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Division (In Miami Dade County) and /or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. BORA reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control Division that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code and the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: GAF RUBEROID® Modified Bitumen Roof System for Wood Decks. LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved ", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and /or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA revises NOA No. 07- 1203.01 and consists of pages 1 through 31. The submitted documentation was reviewed by Jorge L. Acebo. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 1 of 31 ROOFING SYSTEM APPROVAL Category: Sub - Category: Material: Deck Tvpe: Maximum Design Pressure Roofing Modified Bitumen SBS /APP Wood -75 psf TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT: TABLE 1 Product Leak BusterTM Matrix"' 307 Premium Asphalt Primer GAF Mineral Shield® Granules Leak BusterTM MatrixTM 305 Fibered Asphalt Emulsion Leak BusterTM MatrixTM 303 Premium Fibered Aluminum Roof Coating LeakBusterTM MatrixTM 322 Elastomeric Roof Coating LeakBusterTM Matrix"' 306 LeakBusterTM MatrixTM 204 Wet/Dry Roof Cement GAFGLAS® #75 Base Sheet GAFGLAS® #80 ULTIMATM Base Sheet GAFGLAS® Flex PlyTM 6 GAFGLAS® Ply 4 GAFGLAS® Mineral Surfaced Cap Sheet Test Dimensions Specification 5, 55 gallons ASTM D41 60 lb. Bags ASTM D1863 100 Ib. bags 5 gallons 1, 5 gallons 55 gallons 55 gallons 1, 5 gallons 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39,37" (1 meter) Wide ASTM D1227 Product Description Asphalt concrete primer used to promote adhesion of asphalt in built -up roofing. Granules for surfacing of exposed asphalt, cold process cement or emulsion. GAF Mineral Shield® Granules shall be used for flashing applications only. Surface coating for smooth surfaced roofs. ASTM D 2824 Fibered aluminum coating. ASTM D3019 ASTM D3409 ASTM D4586 ASTM D3409 ASTM D4601 ASTM D4601 ASTM D2178 ASTM D2178 ASTM D3909 Elastomeric roof coating. Asphalt emulsion fibered. Refined asphalt blended with a mineral stabilizer and fibers. Permits adhesion to wet and dry surfaces. Type II Asphalt impregnated and coated glass mat base sheet. Type II Asphalt impregnated and coated, fiberglass base sheet Type VI asphalt impregnated glass felt with asphalt coating. Type IV asphalt impregnated glass felt with asphalt coating. Asphalt coated, glass fiber mat cap sheet surfaced with mineral granules. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 2 of 31 Product GAFGLAS® EnergyCapTM Mineral Surfaced Cap Sheet GAFGLAS® EnergyCapTM BUR Mineral Surface Cap Sheet GAFGLAS® STRATAVENT® EliminatorTM Perforated GAFGLAS® Flashing GAFGLAS® STRATAVENT® EliminatorTM Perforated Nailable RUBEROID® SBS Heat- WeldTM Smooth RUBEROID® SBS Heat- WeIdTM Granule Roof Match"' SBS Mop Granule RUBEROID® SBS Heat- We1dTM 170 FR RUBEROID® SBS Heat- We1dTM PLUS RUBEROID® SBS Heat- We1dT"' PLUS FR RUBEROID® EnergyCap SBS Heat- WeIdTM PLUS FR RUBEROID® Modified Base Sheet RUBEROID® SBS Heat- We1dTM 25 Dimensions 39.37" (1 meter) Wide 39.37" (1 meter) wide 39.37" (1 meter) Wide various 39.37" (1 meter) Wide 1 meter (39.37 ") wide 1 meter (39.37 ") wide 107 sq. ft. (9.9 m2) 1 meter (39.37 ") wide 1 meter (39.37 ") wide 1 meter (39.37 ") wide 1 meter (39.37 ") wide 39.37" (1 meter) Wide 1 meter (39.37 ") wide Test Specification ASTM D3909 ASTM D3909 EnergystarTM Title 24 Compliant ASTM D3672 ASTM D4897 ASTM D3672 ASTM D4897 ASTM D6164 ASTM D6164 ASTM D6222 ASTM D5147 ASTM D6164 ASTM D6164 ASTM D6164 ASTM D6164 ASTM D4601, Type 1I, UL Type G2 BUR ASTM D6164 Product Description Asphalt coated, glass fiber mat cap sheet surfaced with mineral granules with factory applied layer of TOPCOAT® EnergyCoteTM. Asphalt coated, glass fiber mat cap sheet surfaced with mineral granules with factory applied EnergyCoteTM Fiberglass base sheet coated on both sides with asphalt. Surfaced on the bottom side with mineral granules embedded in asphaltic coating with factory perforations. Asphalt coated glass fiber mat flashing sheet available in three sizes. Fiberglass base sheet coated on both sides with asphalt. Surfaced on the bottom side with mineral granules embedded in asphaltic coating. Non -Woven Polyester mat coated with polymer - modified asphalt and smooth surfaced. Non -Woven Polyester mat coated with polymer modified asphalt and surfaced with mineral granules. Non -woven polyester mat coated with polymer modified asphalt and surfaced with colored mineral granules. Non -Woven Polyester mat coated with fire retardant polymer modified asphalt and surfaced with mineral granules. Non -Woven Polyester mat coated with polymer modified asphalt and surfaced with mineral granules. Non -Woven Polyester mat coated with fire retardant polymer modified asphalt and surfaced with mineral granules. A fiberglass mat reinforced, SBS modified bitumen cap membrane. Premium glass fiber reinforced SBS - modified base sheet Non -Woven Polyester mat coated with polymer - modified asphalt and smooth surfaced. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 3 of 31 Product RUBEROID® Mop Granule RUBEROID® MOP Smooth RUBEROID® MOP PLUS RUBEROID® MOP 170FR RUBEROID® MOP FR RUBEROID® TORCH Smooth RUBEROID® TORCH Granule RUBEROID® EnergyCap Torch Granule FR Roof MatchTM APP Torch Granule RUBEROID® TORCH PLUS RUBEROID® TORCH FR RUBEROID® 170FR TORCH RUBEROID® EnergyCap SBS Heat Weld Plus FR RUBEROID® 20 RUBEROID® 30 Dimensions 39.37" (1 meter) Wide 1 sq. roll 87 lbs. 39.37" (1 meter) Wide 39.37" (1 meter) Wide Test Specification ASTM D6222 ASTM D5147 ASTM D6298 ASTM D5147 ASTM D6164 ASTM D5147 ASTM D6164 ASTM D5147 39.37" (1 meter) ASTM D6164 Wide ASTM D5147 39.37" (1 meter) Wide 39.37" (1 meter) Wide 1 meter (39.37 ") wide 107 sq. ft. (9.9 m2) 39.37" (1 meter) Wide 39.37" (I meter) Wide 39.37" (1 meter) Wide 1 meter (39.37 ") wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide ASTM D6222 ASTM D5147 ASTM D6222 ASTM D5147 ASTM D6222 ASTM D5147 ASTM D6222 ASTM D5147 ASTM D6222 ASTM D5147 ASTM D6222 ASTM D5147 ASTM D6222 ASTM D5147 ASTM D6163 ASTM D5147 ASTM D6163 ASTM D5147 ASTM D6163 ASTM D5147 Product Description Non -woven polyester mat coated with polymer modified asphalt and surfaced with mineral granules. Non -woven polyester mat coated with polymer - modified asphalt and smooth surfaced. Non -woven polyester mat coated with polymer modified asphalt and surfaced with mineral granules. Non -Woven polyester mat coated with fire retardant polymer modified asphalt and surfaced with mineral granules. Non -Woven polyester mat coated with fire retardant polymer modified asphalt and surfaced with mineral granules. Heavy duty, polyester reinforced, asphalt modified bitumen membrane, smooth surface. Heavy duty, polyester reinforced, asphalt modified bitumen membrane, granule surface. A fiberglass mat reinforced, SBS modified bitumen cap membrane. Non -woven polyester mat coated with polymer modified asphalt and surfaced with colored mineral granules. Heavy duty, polyester reinforced, asphalt modified bitumen membrane, granule surface Heavy duty, polyester reinforced, coated with fire retardant asphalt modified bitumen membrane, granule surface. Heavy duty, polyester reinforced, coated with fire retardant asphalt modified bitumen membrane, granule surface. A fiberglass mat reinforced, SBS modified bitumen cap membrane. SBS modified asphalt base sheet reinforce with a glass fiber mat. Non woven fiberglass mat coated with polymer modified asphalt and surfaced with mineral granules. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 4 of 31 Product RUBEROIDD®30 FR RUBEROID®EnergyCap SBS 30 FR RUBEROID® ULTRACLAD® SBS RUBEROID® Dual FR Vent Stacks (metal and plastic) GAF Built -Up Roofing Asphalt RUBEROID® MOD Asphalt Asphalt L & Asphalt P TOPCOAT® Surface Seal SB LEAK BUSTERTM MatrixTM 715 MB Elastomeric Roofing Membrane EnergyCoteTM Coating VersaShield® TOPCOAT® FireShield® MB Leak BusterTM MatrixTM 531 WeatherCoteTM Elastomeric Flashing Grade LeakBusterTM MatrixTM 201 Premium SBS Flashing Leak BusterTM MatrixTM 102 SBS Adhesive Label Dimensions 39.37" (1 meter) Wide 1 meter (39.37 ") wide 39.37" (1 meter) Wide 39.37" (I meter) Wide 1001b. cartons, bulk 601b. kegs 5 gallons 5 gallons 2, 5 gallons 350 sq. ft roll 5, 55 gallons 5 gallons 5 gallons 5 gallons Test Specification ASTM D6298 ASTM D5147 ASTM D6163 ASTM D6163 ASTM D5147 ASTM D6164 ASTM D5147 TAS 100(A) ASTM D1929 ASTM D635 ASTM D312, Types I, II, III and IV ASTM D3412 ASTM D21 ASTM D1475 ASTM E1644 ASTM D6083 ASTM -D226 4869 Type I, 1I ASTM D412 ASTM D21 ASTM 1475 ASTM E1644 ASTM D3019 ASTM D3019 Product Description Non woven fiberglass mat coated with fire retardant, polymer modified asphalt and surfaced with mineral granules. A fiberglass mat reinforced, SBS modified bitumen cap membrane. Woven fiberglass mat coated with Polymer modified asphalt surfaced with aluminum, copper or stainless steel foil. Non -woven polyester and fiberglass mat coated with file retardant, polymer - modified asphalt and surfaced with mineral granules. One -way valve vent used to relieve built - up pressure within the roof system. GAF Vent Stacks are available in metal or plastic. Interply mopping and surfacing asphalt SEBS modified asphalt Surface coating for smooth surfaced and mineral surfaced roofs. Surface coating for smooth surfaced and mineral surfaced roofs. Highly reflective elastomeric coating Non - Asphaltic Fiberglass -Based Underlayment Elastomeric roofing membrane Surface coating for smooth surfaced and mineral surfaced roofs. Cold Applied Modified SEBS Asphalt Adhesive — Flashing Grade. Cold Applied Modified SEBS Asphalt Adhesive. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04 /08/09 Page 5 of 31 Product Leak BusterTM MatrixTM 202 SBS Flashing Cement Label Leak BusterTM MatrixTM 203 Plastic Roof Cement Label Leak BusterTM Matrix."' 103 Cold Process Adhesive Label LeakBusterTM Matrix"' 304 Non - Fibered Aluminum Roof Leak BusterTM MatrixTM 602 MB Xtra Elastomeric Roofing Membrane TOPCOAT® MB Plus Dimensions 5 gallons 5 gallons 5 gallons 5 gallons 5 gallons 5, 55 gallons Test Specification ASTM D4586 ASTM D4586 Product Description Cold Applied Modified SEBS Asphalt Adhesive — Flashing Grade. Standard Plastic Asphalt Roofing Cement ASTM D3019 Cold Applied Asphalt Adhesive. ASTM D2824, Type I ASTM D412 ASTM 13117 ASTM C794 ASTM G21 FTMS141.6271 ASTM D2196 ASTM D1475 ASTM E1644 ASTM D412, ASTM D21, ASTM D1475 ASTM E1644 Non- fibered. Aluminum pigmented, asphalt roof coating. Surface coating for smooth surfaced and mineral surfaced roofs. Water - based, low VOC, sprayable polymeric liquid, which cures to form a seamless rubber membrane. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 6 of 31 APPROVED INSULATIONS: Product Name EnergyGuardTM Fiberboard EnergyGuardTM Permalite EnergyGuardm Strip EnergyGuardTM Recover Board EnergyGuardTM Tapered Edge Strip EnergyGuardTM Polylso EnergyGuardTM RA, RN EnergyGuardTM Composite, RA DensDeck® DensDeck Prime® DensDeck DuraGuardTM Structodek® Structodek® TD SecurockTM APPROVED FASTENERS: Fastener Product Number Name 1. Drill -TecTM #12 Standard, #14 and #15 extra Heavy Duty Fastener, Heavy Duty Roofing Fastener 2. Drill -TecTM ASAP 3. Drill-Teem CR Base Sheet Fastener and Plate 4. Drill -TecTM Galvalume Plates 5. Drill-TecTM Polypropylene Plates 6. Drill -TecTM AccuTrac Plate Table 2 Product Description Fiberboard insulation Perlite insulation board Cut perlite board Perlite recover board Tapered perlite board Polyisocyanurate foam insulation Polyisocyanurate foam insulation Polyisocyanurate /wood fiberboard or perlite composite Water resistant gypsum board Water resistant gypsum board Water resistant gypsum board Wood fiber insulation board Flame Resistant High Density Wood Fiber board. Fiber reinforced roof board TABLE 3 Product Description Insulation fastener and Base Nay fastener for steel, wood & concrete decks. Pre - assembled Drill -TecTM Various Fasteners and metal and plastic plates. Base sheet fastening Various assembly. Manufacturer (With Current NOA) GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. G -P Gypsum Corp. G -P Gypsum Corp. G -P Gypsum Corp Knight Celotex Knight - Celotex USG Corporation Manufacturer Dimensions (With Current NOA) Various GAF Materials Corp. Round Galvalume stress plates. Round polypropylene stress plates. Square Galvalume® coated 3" Square steel plate. GAF Materials Corp. GAF Materials Corp. 3" and 3 '/2" GAF Materials Corp. 3" and 3 ' /Z" GAF Materials Corp. OMG NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04 /08/09 Page7of 31 EVIDENCE SUBMITTED: Test Agency Factory Mutual Research Corp. Underwriters Laboratories Trinity Engineering Test Identifier Description Date 3029832 4470 -TAS 114 05/11/07 3010215 4470 - TAS 114 03/01/01 3001276 4470 - TAS 114 01/28/99 1B9A8.AM 4470 - TAS 114 09/04/97 3D4Q2.AM 4470 - TAS 114 04/30/97 OD1A8.AM 4470 - TAS 114 04/01/98 TGFU.R19254 UL 790 10/27/06 4483.04 97 -1 TAS 114 06/06/97 PRI Asphalt Technologies, Inc. GAF - 020 -02 -01 ASTM D 249 02/01/02 ASTM D 4977 IRT -ARCON Inc. Trinity I ERD 02 -005 TAS 114 03/01/02 02 -014 TAS 114 04/08/02 01 -039 TAS 114 03/01/02 G6850.08.08 ASTM D6164 08/29/08 G6850.08.08 ASTM D6163 08/01/08 G6850.10.08 ASTM D6222 10/06/08 G6850.11.08 ASTM D6222 11/05/08 NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04 /08/09 Page 8 of 31 APPROVED ASSEMBLIES Membrane Type: SBS Deck Type 1I: Wood, Insulated Deck Description: 19132" or greater plywood or wood plank System Type A(1): Anchor sheet mechanically fastened, all layers of insulation adhered with approved asphalt. All General and System Limitations shall apply. One or more layers of any of the following insulations. Insulation Layer Insulation Fasteners Fastener (Table 3) Density/ft2 EnergyGuardTM Polylso, RA, RN, EnergyGuardTM Composite RA, Minimum 1" thick N/A N/A Wood Fiber, Structodek ®, Structodek® TD, EnergyGuardTM Recover Board Minimum 'A" thick N/A N/A EnergyGuardTM Perlite Minimum 3/" thick N/A N/A Note: All insulation shall be adhered to the anchor sheet in full mopping of approved hot asphalt within the EVT range and at a rate of 20-40 Ibs /100 ft2. Please refer to Roofing Application Standard RAS 117 for insulation attachment. Insulation listed as base layer only shall be used only as base layers with a second layer of approved top layer insulation installed as the final membrane substrate. Composite insulation panels may be used as a top layer placed with the polyisocyanurate side facing down. GAF requires either a ply of GAFGLAS® STRATAVENT® EliminatorTM Perforated Laid dry or a layer of EnergyGuardTM, Perlite or wood fiber overlay board on all polyisocyannrate applications. Fire Barrier: FireOutTM Fire Barrier Coating, VersaShield® Non-Asphaltic Fiberglass -Based (optional) Underlayment or SecurockTM. Anchor sheet: GAFGLAS® #80 ULTIMATM Base Sheet, STRATAVENT® Eliminator"' Nailabte Base Sheet, RUBEROID® Modified Base Sheet, RUBEROID® 20, RUBEROID® SBS Heat- We1dTM Smooth or RUBEROID® SBS Heat- WeIdTM 25 base sheet mechanically fastened to deck as described below; Fastening GAFGLAS® Ply 4, GAFGLAS® Flex PIyTM 6, GAFGLAS® #75 Base Sheet or any Options: of above Anchor sheets attached to deck with approved annular ring shank nails and tin caps at a fastener spacing of 9" o.c. at the lap staggered and in two rows 12" o.c. in the field. (Maximum Design Pressure —45 psf, See General Limitation #7) GAFGLAS® Ply 4, GAFGLAS® Flex PIyTM 6, GAFGLAS® #75 Base Sheet or any of above Anchor sheets attached to deck with Drill -TecTM #12 standard, #14 or # 15 Screws and 3" Drill -TecTM steel plate or Drill -TecTM AccuTrac Plates, 12" o.c. in 3 rows. One row is in the 2" side lap. The other rows are equally spaced approximately 12" o.c. in the field of the sheet. (Maximum Design Pressure —45 psf, See General Limitation #7) NOA No.: 09 -0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 9 of 31 GAFGLAS® Flex PIyTM 6, GAFGLAS® #75 Base Sheet or any of above Anchor sheets attached to deck with approved annular ring shank nails and tin caps at a fastener spacing of 9" o.c. at the 4" lap staggered and in two rows 9" o.c. in the field. (Maximum Design Pressure —52.5 psf, See General Limitation #7) GAFGLAS® #80 ULTIMATM, RUBEROID® 20, RUBEROID® Mop Smooth, base sheet attached to deck with approved annular ring shank nails and tin caps at a fastener spacing of 9" o.c. at the 4" lap staggered and in two rows 9" o.c. in the field. ( Maximum Design Pressure —60 psf, See General Limitation #7) GAFGLAS® #75 Base Sheet or any of above Anchor sheets attached to deck with Drill -TecTM #12 standard, #14 or # 15 Screws and 3" Drill -TecTM steel plate or Drill -TecTM AccuTrac Plates, 12" o.c. in 4 rows. One row is in the 2" side lap. The other rows are equally spaced approximately 9" o.c. in the field of the sheet. (Maximum Design Pressure —60 psf, See General Limitation #7) Any of above Anchor sheets attached to deck approved annular ring shank nails and 3" inverted Drill -TecTM insulation plates at a fastener spacing of 9" o.c. at the 4" lap staggered in two rows 9" in the field. (Maximum Design Pressure —60 psf, See General Limitation #7) GAFGLAS® #75 Base Sheet or any of above Anchor sheets attached to deck with Drill -TecTM #12 standard, #14 or # 15 Screws and 3" Drill-TecTM steel plate or Drill -TecTM AccuTrac Plates, 8" o.c. in 4 rows. One row is in the 2" side lap. The other rows are equally spaced approximately 9" o.c. in the field of the sheet. (Maximum Design Pressure —75 psf, See General Limitation #7) Base Sheet: (Optional) Install one ply of GAFGLAS® #75, GAFGLAS® #80 ULTIMATM Base Sheet, GAFGLAS® PLY 4, GAFGLAS Flex P1yTM 6, GAFGLAS® STRATAVENT® EliminatorTM Perforated (laid dry), RUBEROID® Modified Base Sheet, RUBEROID® MOP Smooth, RUBEROID® 20, RUBEROID® SBS Heat - WeIdTM Smooth or RUBEROID® SBS Heat- We1dTM 25 directly over the top layer of insulation. Adhere with any approved mopping asphalt applied within the EVT range and at a rate of 20-40 Ibsisq (see General Limitation #4). Ply Sheet: (Optional) One or more plies GAFGLAS® PLY 4, GAFGLAS® Flex PIyTM 6 sheet, GAFGLAS® #80, RUBEROID® MOP Smooth, RUBEROID® 20 adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. Membrane: One or more plies of RUBEROID® 20, RUBEROID® 30, RUBEROID® EnergyCap SBS 30 FR, RUBEROID® 30 FR RUBEROID® MOP Smooth, RUBEROID® Mop 170 FR, RUBEROID® Mop Granule, Roof MatchTM SBS Mop Granule, RUBEROID® MOP PLUS, RUBEROID® MOP FR, RUBEROID® ULTRACLAD® SBS, or RUBEROID® Dual FR fully adhered in an approved asphalt at an application rate of 25 lb. /sq. ± 15 %. NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 10 of 31 Surfacing: (Optional, required if RUBEROID® MOP Smooth or RUBEROID® 20 is top membrane) Install one of the following: 1. Gravel or slag applied at 400 lbs. /sq. and 300 lbs. /sq. respectively in a flood coat of approved asphalt at 60 lbs. /sq. or applied in a flood coat of Leak BusterTM Matrix"' 103 Cold Process Adhesive applied at a rate of 3 galJsq. 2. GAFGLAS® Mineral Surfaced Cap Sheet, GAFGLAS® Energy Cap Mineral Surfaced Capsheet adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20- 40lbs. /sq. 3. Leak Buster"' MalrixTM 303 Premium Fibered Aluminum Roof Coating, at 1.5 gal. /sq. 4. Leak BusterTM MatrixTM 715, Leak BusterTM Matrix"' 322, TOPCOAT® MB +, TOPCOAT® Fireshield Elastomeric Roofing Membrane, applied at 1 to 1.5 gal. /sq. 5. Leak Buster"' Matrix"' 602 MB Xtra Elastomeric Roofing Membrane, EnergyCote® roof coating applied at 1 to 1.5 gal. /sq. 6. TOPCOAT® Surface Seal, TOPCOAT® Fireshield® SB Solvent based Elastomeric Roofing Membrane applied at lto 1.5 gal. /sq 7. Advance Green Technologies Photovoltaic Laminate solar energy collector auxiliary roof equipment installed in compliance with manufacturer's specifications and applicable Building Codes. Maximum Design Pressure: See Fastening Above NOA No.: 09- 0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 11 of 31 WOOD DECK SYSTEM LIMITATIONS: 1 A slip sheet is required with Ply 4 and Flex Ply 6 when used as a mechanically fastened base or anchor sheet. 2. Minimum '/d' Dens Deck or '/2" Type X gypsum board is acceptable to be installed directly over the wood deck. GENERAL LIMITATIONS: 1. Fire classification is not part of this acceptance, refer to a current Approved Roofing Materials Directory for fire ratings of this product. 2. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with Product Control Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbsJsq., or mechanically attached using the fastening pattern of the top layer 3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved asphalt, panel size shall be 4' x 4' maximum. 4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam insulations when the base sheet is fully mopped. If no recovery board is used the base sheet shall be applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8" ribbons in three rows, one at each side lap and one down the center of the sheet allowing a continuous area of ventilation. Encircling of the strips is not acceptable. A 6" break shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt application of either system shall be at a minimum rate of 12 lbs. /sq. Note: Spot attached systems shall be limited to a maximum design pressure of -45 psf. 5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force (F') value of 275 lbf., as tested in compliance with Testing Application Standard TAS 105. If the fastener value, as field - tested, are below 275 lbf. insulation attachment shall not be acceptable. 6. Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based on a minimum fastener resistance value in conjunction with the maximum design value listed within a specific system. Should the fastener resistance be Tess than that required, as determined by the Building Official, a revised fastener spacing, prepared, signed and sealed by a Florida Registered Engineer, Architect, or Registered Roof Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal resistance value taken from Testing Application Standards TAS 105 and calculations in compliance with Roofing Application Standard RAS 117. 7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas. Fastener densities shall be increased for both insulation and base sheet as calculated in compliance with Roofing Application Standard RAS 117. Calculations prepared, signed and sealed by a Florida registered Professional Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is specifically referred within this NOA, General Limitation #9 will not be applicable.) 8. All attachment and sizing of perimeter nailers, metal profile, and /or flashing termination designs shall conform to Roofmg Application Standard RAS 111 and applicable wind load requirements. 9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e. field, perimeters, and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at enhanced pressure zones (i.e. perimeters, extended corners and corners). (When this limitation is specifically referred within this NOA, General Limitation #7 will not be applicable.) 10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and Rule 9B -72 of the Florida Administrative Code. END OF THIS ACCEPTANCE NOA No.: 09 -0224.01 Expiration Date: 11/06/13 Approval Date: 04/08/09 Page 31 of 31 TGFU.R1306 - Roofing Systems http: / /database.ul.com/cgi- bin/ XYV /template/LISEXT /1FRAME /s... 6. Deck: C -15/32 Incline: 1/2 Insulation: — One or more layers perlite, glass fiber, 9 -in. minimum, polyisocyanurate, urethane, perlite / polyisocyanurate composite, perlite /urethane composite, 1A -in. minimum. Base Sheet (Optional): — One or more plies Type G1 or Type G2 or Type G3. Membrane: — One or more plies "Ruberoid® Torch" (Smooth or Granule) or "Ruberoid® Torch Granule Plus" or "Ruberold® Mop" (Smooth or Granule) or "Ruberoid® Mop Plus Granule." Surfacing: — Gravel. 7. Deck: C -15/32 Incline: 1/2 Insulation (Optional): — One or more layers perlite, wood fiber, glass fiber, polyisocyanurate, urethane, perlite/polyisocyanurate composite, perlite /urethane composite, wood fiber / polyisocyanurate composite. Base Sheet: — Two or more plies Type G2 or Type G3. Ply Sheet (Optional): — One or more plies Type G1. Membrane: — One or more plies "Ruberoid® Torch" (Smooth or Granule) or "Ruberoid® Torch Granule Plus" or "Ruberoid® Mop" (Smooth or Granule) or "Ruberoid® Mop Plus Granule." Surfacing: — "Kamak No. 97" applied at 10 to 3 -gal /100 -ft2 or gravel. 8. Deck: NC Incline: 1/2 Insulation: — One or more layers perlte, glass fiber, A -In. minimum polyisocyanurate, urethane, perlite / polyisocyanurate composite, perlite /urethane composite, 10 in. minimum. Base Sheet (Optional): — One or more plies Type G1 or Type G2 or Type G3. Membrane: — One or more piles "Ruberoid® Torch" (Smooth or Granule) or "Ruberoid® Torch Granule Plus" or "Ruberoid® Mop" (Smooth or Granule) or "Ruberoid® Mop Plus Granule." Surfacing: — Grundy "AL MB Aluminum Roof Coating" applied at 1 to 2- ga1/100 -ft2. 9. Deck: C -15/32 Incline: 1/2 Insulation (Optional): — One or more layers perlite, glass fiber, 9 -in. minimum, polyisocyanurate, urethane, perlite /polyisocyanurate composite, perlite /urethane composite, phenolic, 1A in. minimum. Base Sheet: — One or more plies Type G2 "GAFGLAS® #75 Base Sheet ", or "Tri -Ply® #75 Base Sheet ", hot mopped or mechanically fastened in place. Ply Sheet: — One or more plies Type G1 "GAFGLAS® Ply 4" or'Tri -Ply® PIy 4" or "GAFGLAS® Ply 6" hot mopped in place. Membrane: — "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCapTM' Mop FR." Surfacing — (Optional): "GAF Fibered Aluminum Coating" applied at 1O-gal /100 -ft 2 or "GAF Weather Coat Emulsion" applied at 3 -gal /100 -ft2. 167 eck: C -15/32 Incline: • Insulation ( Optlnal): — Perlite, fiber glass, polyisocyanurate, urethane or perlite / polyisocyanurate composite. Base Sheet: — One or more layers Type G2 "GAFGLAS® #75 Base Sheet" or "Tri -Ply® #75 Base Sheet" or Type G3 "GAFGLAS® Mineral Surfaced Cap Sheet" or "Tri -PIy® Mineral Surfaced Cap Sheet" hot mopped or mechanically fastened. PIy Sheet (Optional): — One or more plies Type G1, hot mopped in place. Membrane: — "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCap"' Mop FR." 11. Deck: C -15/32 IncMe: 1/2 Insulation (Optional): — Periite, fiber glass, polyisocyanurate, urethane or perlite/polyisocyanurate composite, butt offset a minimum of 6 -in. from plywood deck joints. Base Sheet: — One or more plies Type G2 "GAFGLAS® #75 Base Sheet" or'Tri -PIy® #75 Base Sheet" or Type G3 "GAFGLAS® Mineral Surfaced Cap Sheet" or'Tri -PIy® Mineral Surfaced Cap Sheet" hot mopped or mechanically fastened. Ply Sheet (Optional): — One or more plies Type G1, hot mopped in place. Membrane: — One ply "Ruberoid® Torch Smooth" or "Ruberoid® Mop Smooth" or "Ruberoid® Mop Smooth 1.5" or "Ruberoid® Mop Smooth Plus" or "Ruberoid® Dual Smooth." Membrane: — One ply "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCap'" Mop FR." 12. Deck: NC Incfine: 1 Insulation (Optional): — Perliite, fiber glass, wood fiber, polyisocyanurate, urethane or perlite /polyisocyanurate composite. Base Sheet: — One or more layers Type G2 "GAFGLAS® #75 Base Sheet" or'Tri -PIy® #75 Base Sheet" or Type G3 " GAFGLAS® Mineral Surfaced Cap Sheet" or "Tri -PIy® Mineral Surfaced Cap Sheet ", hot mopped or mechanically fastened. Ply Sheet (Optional): — One or more plies Type G1 hot mopped in place. Membrane: — One ply "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCapr' Mop FR." 13. Deck: NC Incline: 1/2 Insulation (Optional): — Periite, fiber glass, wood fiber, polyisocyanurate, urethane or perlite/polyisocyanurate composite. Base Sheet (Optional): — One or more plies Type G2 or Type G3 base sheet, hot mopped or mechanically fastened. PIy Sheet (Optional): — One or more plies Type G1 hot mopped in place. Membrane: — One ply "Ruberoid® Torch Smooth" (smooth) or "Ruberold® Mop Smooth" or "Ruberold® Mop Smooth 1.5" or "Ruberoid® Mop Smooth Plus" or "Ruberold® Dual Smooth." Membrane: — One ply "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberold® Mop FR" or " Ruberold® EnergyCapr' Mop FR." 14. Deck: NC Incline: 9 of 49 7/10/2012 1:37 PM M1AMNDAD>" BUILDING CODE COMPLIANCE OFFICE (BCCO) PRODUCT CONTROL DIVISION NOTICE OF ACCEPTANCE (NOA) GAF Material Corporation 1361 Alps Road Wayne, NJ 07470 MIAMI -DADE COUNTY, FLORIDA METRO -DADE FLAGLER BUILDING 140 WEST FLAGLER STREET, SUITE 1603 MIAMI, FLORIDA 33130 -1563 (305) 375 -2901 FAX (305) 375 -2908 SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed by the BCCO and accepted by the Building Code and Product Review Committee to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ). This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Division (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. BORA reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control Division that this product or material fails to meet the requirements of the applicable building code. This product is approved as described herein, and has been designed to comply with the Florida Building Code and the High Velocity Hurricane Zone of the Florida Building Code. DESCRIPTION: GAF RUBEROID® Modified Bitumen Roof System for Concrete Decks. LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following statement: "Miami -Dade County Product Control Approved ", unless otherwise noted herein. RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product. TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA. ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety. INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This NOA revises NOA No. 08- 0108.06 and consists of pages 1 through 36. The submitted documentation was reviewed by Jorge L. Acebo IAPPROVED� NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 1 of 36 ROOFING SYSTEM APPROVAL Category: Sub- Category: Deck Type: Maximum Design Pressure Roofing SBS /APP, Modified Bitumen Concrete -495 psf TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT: TABLE 1 Test Product Product Dimensions Specification Description Leak BusterTM 3, 5, 55 gallons ASTM D 41 MatrixTM 307 Premium Asphalt Primer GAF Mineral ShieldTM Granules Leak BusterTM MatrixTM 305 Fibered Asphalt Emulsion Leak BusterTM MatrixTM 303 Premium Fibered Aluminum Roof Coating Leak BusterTM MatrixTM 204 Wet/Dry Roof Cement Leak BusterTM MatrixTM 304 Non Fibered Aluminum Roof Coating GAFGLAS® #75 Base Sheet GAFGLAS® #80 ULTIMATm Base Sheet GAFGLAS® FIexPIyTM 6 GAFGLAS® Ply 4 601b. & 100lb bags 5 gallons 1, 5 gallons 1, 5 gallons 5 gallons 39.37" (1 meter) Wide 39.37" (l meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide Asphalt concrete primer used to promote adhesion of asphalt in built -up roofing. ASTM D 1863 Granules for surfacing of exposed asphalt, cold process cement or emulsion. GAF Mineral ShieldTM Granules shall be used for flashing applications only. ASTM 1227 Surface coating for smooth surfaced roofs. ASTM D 2824 Fibered aluminum coating. ASTM D-4586 ASTM D -3409 ASTM D2824, Type I ASTM D 4601 Type 11 ASTM D4601 Type II ASTM D 2178 ASTM D 2178 Refined asphalt blended with a mineral stabilizer and fibers. Permits adhesion to wet and dry surfaces. Non-fibered aluminum pigmented, asphalt roof coating. Asphalt impregnated and coated glass mat base sheet. Asphalt impregnated and coated, fiberglass base sheet. Type VI asphalt impregnated glass felt with asphalt coating. Type IV asphalt impregnated glass felt with asphalt coating. NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 2 of 36 Product GAFGLAS® Mineral Surfaced Cap Sheet GAFGLAS® STRATAVENT® EliminatorTM Perforated GAFGLAS® Flashing GAFGLAS® STRATAVENT® EliminatorTM Perforated Nailable RUBEROID® SBS Heat- We1dTM Smooth RUBEROID® SBS Heat- We1dTM Granule RUBEROID® SBS Heat- WeIdTM 170 FR RUBEROID® EnergyCap SBS Heat Weld Plus FR RUBEROID® SBS Heat- We1dTM PLUS RUBEROID® SBS Heat -Weld PLUS 170 FR RUBEROID® SBS Heat- We1dTM 25 RUBEROID® EnergyCap SBS 30 FR RUBEROID® MOP Smooth ULTRACLAD® SBS Foil -Faced Membrane RUBEROID® Modified Asphalt Lite RUBEROID Modified Asphalt Plus Dimensions 39.37" (1 meter) Wide 39.37" (1 meter) Wide various 39.37" (1 meter) Wide 1 meter (39.37 ") wide 1 meter (39.3T') wide 1 meter (39.37 ") wide 1 meter (39.37 ") wide 1 meter (39.37 ") wide 1 meter (39.37 ") wide 1 meter (39.37") wide 1 meter (39.37 ") wide 39.37" (1 meter) Wide 1 sq. roll 101 lb. 60 Ib. kegs 60 Ib. kegs Test Specification ASTM D 3909 ASTM D 3672 ASTM D 4897 ASTM D 3672 ASTM D 4897 ASTM D -6164 ASTM D -6164 ASTM D -6164 ASTM D -6163 ASTM D -6164 ASTM D -6164 ASTM D -6164 ASTM D -6163 ASTM D5147 ASTM D6298 ASTM D6298 ASTM D312 ASTM D6152 Product Description Asphalt coated, glass fiber mat cap sheet surfaced with mineral granules. Fiberglass base sheet coated on both sides with asphalt. Surfaced on the bottom side with mineral granules embedded in asphaltic coating with factory perforations. Asphalt coated glass fiber mat flashing sheet available in three sizes. Fiberglass base sheet coated on both sides with asphalt. Surfaced on the bottom side with mineral granules embedded in asphaltic coating. Non -Woven Polyester mat coated with polymer modified asphalt and smooth surfaced. Non -Woven Polyester mat coated with polymer modified asphalt and surfaced with mineral granules. Non -Woven Polyester mat coated with fire retardant polymer modified asphalt and surfaced with mineral granules. A fiberglass mat reinforced, SBS modified bitumen cap membrane. Non -Woven Polyester mat coated with polymer modified asphalt and surfaced with mineral granules. Non -Woven Polyester mat coated with fire retardant polymer modified asphalt and surfaced with mineral granules. Non -Woven Polyester mat coated with polymer modified asphalt and smooth surfaced. A fiberglass mat reinforced, SBS modified bitumen cap membrane. Non -woven polyester mat coated with polymer modified asphalt. Does not have a factory applied surfacing. Woven fiberglass mat coated with polymer modified asphalt and surfaced with aluminum, copper or stainless steel foil. SEBS modified asphalt SEBS modified asphalt NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 3 of 36 Product RUBEROID® Modified Base Sheet RUBEROID® Mop Granule RUBEROID® Torch Smooth RUBEROID® Torch Plus (Granule) RUBEROID® Torch Granule RUBEROID® Torch FR RUBEROID® Mop Plus (Granule) RUBEROID® Mop FR RUBEROID® 20 RUBEROID® 30 RUBEROID® 30 FR RUBEROID® Mop 170 FR RUBEROID® SBS Dual FR Roof MatchTM APP Granular Roof MatchTM SBS Granular TopCoat® Surface Seal SB Leak BusterTM MatrixTM 715 MB Coating Dimensions 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 39.37" (1 meter) Wide 107 sq. ft. (9.9 m2) 107 sq. ft. (9.9 m2) 5 gallons 5 gallons Test Product Specification Description ASTM D4601 Premium glass fiber reinforced SBS- modified Type II, base sheet. Type G2 BUR ASTM D 6164 Non -woven polyester mat coated with ASTM D 5147 polymer modified asphalt and surfaced with mineral granules. ASTM D 6222 Heavy duty, polyester reinforced, asphalt ASTM D 5147 modified bitumen membrane. ASTM D 6222 Heavy duty, polyester reinforced, asphalt ASTM D 5147 modified bitumen membrane. ASTM D 6222 Asphalt impregnated, coated felt, surfaced ASTM D 5147 with mineral granules. ASTM D 6222 Non -woven polyester mat coated with fire ASTM D 5147 retardant polymer modified asphalt surfaced with mineral granules. ASTM D 6164 Non -woven polyester mat coated with ASTM D 5147 polymer modified asphalt and surfaced with mineral granules. ASTM D 6164 Non -woven polyester mat coated with fire - ASTM D 5147 retardant, polymer modified asphalt surfaced with mineral granules. ASTM D 6163 SBS modified asphalt base sheet reinforce ASTM D 5147 with a glass fiber mat. ASTM D 6163 Non woven fiberglass mat coated with ASTM D 5147 polymer modified asphalt and surfaced with mineral granules. ASTM D 6163 Non woven fiberglass mat coated with fire ASTM D 5147 retardant, polymer modified asphalt and surfaced with mineral granules.❑ ASTM D 6164 Non -woven polyester mat coated with fire ASTM D 5147 retardant polymer modified asphalt surfaced with mineral granules. ASTM D 6164 Non -woven polyester and fiberglass mat ASTM D 5147 coated with file retardant, polymer- modified asphalt and surfaced with mineral granules. ASTM D 6222 Non -woven polyester mat coated with ASTM D 5147 polymer modified asphalt and surfaced with colored mineral granules. ASTM D 6222 Non -woven polyester mat coated with ASTM D 5147 polymer modified asphalt and surfaced with colored mineral granules. Surface coating for smooth surfaced and mineral surfaced roofs. Surface coating for smooth surfaced and mineral surfaced roofs. NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 4 of 36 Test Product Product Dimensions Specification Description TOPCOAT® MB Plus 5 gallons ASTM D -3412 Surface coating for smooth surfaced and ASTM D -21 -96 mineral surfaced roofs. ASTM D -1475 ASTM E -1644 ASTM D -6083 Leak BusterTM 5 gallons MatrixTM 531 WeatherCoteTM Leak BusterTM 5 gallons MatrixTM 201 SBS Flashing Cement Leak BusterTM 5 gallons MatrixTM 102 SBS Adhesive Leak BusterTM 5 gallons MatrixTM 202 SBS Flashing Cement Leak BusterTM 5 gallons MatrixTM 203 Plastic Roof Cement Leak BusterTM 5 gallons MatrixTM 103 Gold Process Adhesive Vent Stacks (metal and plastic) EnergyCote® Roof Coating TOPCOAT® Surface Seal TOPCOAT® FireShield SB Solvent Base Elastomeric Roofing Membrane ASTM D3019 ASTM D3019 ASTM D4586 ASTM D4586 ASTM D3019 TAS 100(A) ASTM D 1929 ASTM D 635 Proprietary ASTM D-412 ASTM B -117 ASTM C -794 ASTM G -21 FTMS 141.6271 ASTM D -21 -96 ASTM D -1475 ASTM E -1644 ASTM D -412 ASTM B -117 ASTM C -794 ASTM G -21 FTMS 141.6271 ASTM D -21 -96 ASTM D -1475 ASTM E -1644 Surface coating for smooth surfaced and mineral surfaced roofs. Cold Applied Modified SEBS Asphalt Adhesive — Flashing Grade. Cold Applied Modified SEBS Asphalt Adhesive. Cold Applied Modified SEBS Asphalt Adhesive — Flashing Grade. Standard Plastic Asphalt Roofing Cement Cold Applied Asphalt Adhesive. One way valve vent used to relieve built -up pressure within the roof system. GAF Vent Stacks are available in metal or plastic. Surface coating for smooth surfaced and mineral surfaced roofs. Surface coating for smooth surfaced and mineral surfaced roofs. Surface coating for smooth surfaced and mineral surfaced roofs. NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 5 of 36 APPROVED INSULATIONS: Product Name EnergyGuardTM RA, RN EnergyGuardTM Composite EnergyGuardTM Fiberboard EnergyGuardTM Polylso EnergyGuardTM Perlite EnergyGuardTM Recover Board EnergyGuardTM High Density Fiberboard EnergyGuardTM Ultra Polylso DensDeck® DensDeck Prime® DensDeck DuraGuard'` SECUROCK® Structodek® APPROVED FASTENERS: Fastener Number Product Name TABLE 2 Product Description Polyisocyanurate foam insulation Polyisocyanurate /wood fiberboard or perlite composite Fiberboard insulation Polyisocyanurate foam insulation Perlite insulation board. Perlite recover board High density wood fiberboard insulation. Polyisocyanurate foam insulation High Density Fire Resistant Insulation Boards High Density Fire Resistant Insulation Boards High Density Fire Resistant Insulation Boards High Density Fire Resistant Insulation Boards Wood fiber insulation board 1. Drill -TecTM #12 Standard, #I4 and #15 extra Heavy Duty Fastener , Heavy Duty Roofing Fastener 2. Drill-TecTM ASAP 3. Drill -TecTM CR Base Sheet Fastener and Plate 4. Drill-TecTM GalvaIume Plates 5. Drill-TecTM Polypropylene Plates 6. Drill -TecTM AccuTmc Plate Steel Plates TABLE 3 Product Description Manufacturer (With Current NOA) GAF Materials Corp GAF Materials Corp GAF Materials Corp GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. Georgia Pacific Georgia Pacific Georgia Pacific USG Knight Celotex Manufacturer Dimensions (With Current NOA) Insulation fastener and Various GAF Materials Corp. Base PIay fastener for steel, wood & concrete decks. Pre - assembled Drill -TecTM Various GAF Materials Corp. Fasteners and metal and plastic plates. Base sheet fastening Various assembly. Round galvalume stress 3" and 3' /s" plates. Round polypropylene 3" and 3 '''A" stress plates. Square galvalume stress 3 x 3 plates. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp. GAF Materials Corp NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 6 of 36 EVIDENCE SUBMITTED: Test Agency/Identifier Factory Mutual Research Corp. Independent Roof Testing & Consulting of South Florida Exterior Research & Design, LLC Trinity I ERD Underwriters Laboratories, Inc. Name Current Insulation Attachment Requirements FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 - TAS 114 FMRC 4470 FMRC 4470 FMRC 4470 TAS 114 -J TAS 114 TAS 114 ASTM D6163 ASTM D6164 UL 790 -TAS 114 Report Date FMRC 1996 01.01.96 J.I. ODOA8.AM 07.09.97 J.I. 2B8A4.AM 07.02.97 J.I. 3005640 11.09.00 J.I.3006845 10.17.00 J.I.3005175 05.23.00 J.I. 3005177 05.19.00 J.I.3007500 06.15.00 J.I. 3008178 12.27.00 J.I. 3010215 03.01.01 J.I. 3009788 03.28.01 3017250 04.05.04 No.00001 03.30.00 No.00002 #4483.04.97 -1 06 -06 -97 #01881.09.03 -2 03.24.08 #01881.11.03 -2 -RI 08.21.07 #G6850.08.08 08.29.08 R1306, 00NK07638 07.17.00 NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 7 of 36 1 � i SYSTEMS A(3): ADHERED INSULATED SYSTEMS The following assembly is approved to a maximum design pressure per Insulation Maximum Design Pressure Table A. No substitutions shall be made: Deck Type: Concrete, primed. Anchor Sheet: Install one or more plies of GAFGLAS® #75, GAFGLAS® #80 ULTIMATM, (Optional) GAFGLAS® PLY 4, GAFGLAS® FIexPIyTM, RUBEROID® Modified Base sheet RUBEROID® Mop Smooth or RUBEROID® 20 mopped directly to the substrate. Adhere with any approved mopping asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. Insulations: See Insulation Maximum Design Pressure Table A below. Design Pressure is dependent on Insulation assembly # used in this system. Base Sheet Install one ply of GAFGLAS® #75, GAFGLAS® #80 ULTIMATM GAFGLAS® PLY 4, GAFGLAS® FlexPIyTM 6, RUBEROID® Modified Base Sheet or RUBEROID® 20, RUBEROID® MOP Smooth, directly to the insulated substrate. Adhere with any approved mopping asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. Ply Sheet: One, two or three plies of RUBEROID® 20, GAFGLAS® PLY 4 or GAFGLAS® (Optional) FlexPlyTM 6 ply sheet adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. Membrane: One or more plies of RUBEROID® Torch Smooth, RUBEROID® Torch Granule, RUBEROID® Torch Plus Granule, RUBEROID® Torch FR, RUBEROID® Torch 170FR, Roof MatchTM APP Granular or RUBEROID® 20, RUBEROID® MOP Smooth, RUBEROID® MOP Granule, RUBEROID® MOP 170FR, RUBEROID® SBS Dual FR, RUBEROID® ULTRACLADTm, RUBEROID® 30 and RUBEROID®30FR, RUBEROID®EnergyCap SBS 30 FR, RUBEROID® MOP PLUS and RUBEROID® MOP FR or RUBEROID® SBS Heat- We1dTM PLUS, RUBEROID® SBS Heat- We1dTM PLUS FR, RUBEROID® SBS Heat- We1dTM 170 FR, RUBEROID® EnergyCap SBS Heat Weld Plus FR, RUBEROID® SBS Heat- We1dTM, RUBEROID® SBS Heat - WeIdTM Smooth and RUBEROID® SBS Heat- We1dTM 25 applied according to manufacturer's application instructions. Surfacing: (Optional) Install one of the following 1. Gravel or slag applied at 400 lbs./sq. and 300 lbs./sq. respectively in a flood coat of approved asphalt at 60 lbs./sq. or applied in a flood coat of Leak BusterTM MatrixTM 103 Cold Process Adhesive applied at a rate of 3 gal. /sq. 2. GAFGLAS® Mineral Surfaced Cap Sheet, GAFGLAS® Energy Cap Mineral Surfaced Capsheet adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. 3. Leak BusterTM MatrixTM 303 Premium Fibered Aluminum Roof Coating, at 1.5 gal. /sq. 4. Leak BusterTM MatrixTM 715, Leak Buster MatrixTM 322, TOPCOAT® MB PLUS, TOPCOAT® FireShield Elastomeric Roofing Membrane, applied at 1 to 1.5 galJsq. 5. Leak BusterTM MatrixTM 602 MB Xtra Elastomeric Roofing Membrane, EnergyCote® roof coating applied at 1 to 1.5 galJsq. 6. TOPCOAT® Surface Seal, TOPCOAT® FireShield® SB Solvent based Elastomeric Roofing Membrane applied at Ito 1.5 galJsq. 7. Advance Green Technologies Photovoltaic Laminate solar energy collector auxiliary roof equipment installed in compliance with manufacturer's specifications and applicable Building Codes NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 12 of 36 Insulation Maximum Design Pressure Table A # Insulation Assemblies 1. Min. 1.5" EnergyGuardTM Composite RA, RN NP laid with the polyisocyanurate side down and bonded in a full mopping of an approved asphalt applied within the EVT range and at a rate of 20- 40 lbs. /sq. Maximum Desi . n Pressure —270 I sf See General Limitation #9 2. Base Layer: Min. 1" EnergyGuardTM RN. mopped in asphalt at the rate of 20- 401bs. /sq. Top Layer: Min. 'A" EnergyGuardTM Perlite adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20- 401bs. /sq. Maximum Design Pressure —322.5 psf (See General Limitation #9) 3. ardTM RA mopped in asp sqhalt at the rate of 20 -401bs /. Base Layer: Min. 1" EnergyGuardTM pp Top Layer: Min. Y2" EnergyGuardTM High Density Wood Fiber Board (g) adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbsisq. Maximum Desi Pressure — 307.5 , ' f See General Limitation #9 4. Base La er: Min. 1" Ener 3 uardTM RA mo. • ed in as shalt at the rate of 20-40 lbs. /s• . Top Layer: Min. %2" EnergyGuardTM Perlite adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20- 401bs. /sq. Maximum Design Pressure —165 psf (See General Limitation #9) 5. Base Layer: Two Min. 3/4" layers EnergyGuardTM Perlite adhered in a full mopping of approved as • halt a. • lied within the EVT ratite and at a rate of 20-40 lbsJs • . To L, er: Min. 'A" Dens-Deck® mo • • ed in as .halt at the rate of 20-40 lbsis • .. Maximum Design Pressure —172.5 psf (See General Limitation #9) 6. (Optional) Base Layer: Min. 1.5" EnergyGuardTM RA, EnergyGuardTM RN or 1 /2" High Density Fiberboard secured to underlying substrate with Insta -Stik Roofing Adhesive. Top Layer: One or more layers of Min. 1 "EnergyGuardTM RN, EnergyGuardTM RA, 1 /2" High Density Fiberboard or Min. 1/4" Dens -Deck secured to underlying substrate with Insta -Stik Roofing Adhesive. Maximum Desi Pressure —112.5 i sf See General Limitation #9 7. Base L er: Min. 1" Energy, GuardTM RA mo • • ed in as • halt at the rate of 20-40 lbs. /s • .. Top Layer: Min.''/2" EnergyGuardTM High Density Wood Fiber Board (c) adhered in a full mo. . in. of a • .roved asphalt a. .lied within the EVT range and at a rate of 20-40 lbsis • . Maximum Design Pressure —237.5 psf (See General Limitation #9) 8. (Optional) Base Layer: Min. 1.5" EnergyGuardTM RN, EnergyGuardTM RA or 1 /2" High Density Fiberboard secured to underlying substrate with Insta -Stik Roofing Adhesive. Top Layer: One or more layers of Min. 1" EnergyGuardTM RN, EnergyGuardTM RA, 1 /2" High Density Fiberboard, Structodek or Min. 1/4" Dens -Deck secured to underlying substrate with Insta- Stik Roofing Adhesive. Maximum Desi i Pressure —105 'f See General Limitation #9 9. Min. 1.75" EnergyGuardTM Composite laid with the polyisocyanurate side down and bonded in a full mopping of an approved asphalt applied within the EVT range and at a rate of 20-40 lbsisq. Maximum Design Pressure —270 psf (See General Limitation #9) NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 13 of 36 10. Min.'' 'A" EnergyGuardTM High Density Fiberboard or other Approved high density wood fiberboard or min. 1" EnergyGuardTM Perlite adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. Maximum Design Pressure —140 psf (See General Limitation #9) 11. Base Layer: Min. 2" EnergyGuardTM RN Top Layer: Min. '' /z" EnergyGuardTM Perlite adhered in a full mopping of approved asphalt applied within the EVT range at a rate of 20-40 lbs./sq. Maximum Design Pressure —322.5 psf (See General Limitation #9) 12. Base Layer: Min. 1.5" EnergyGuardTM Composite Top Layer: Min. 1.5" EnergyGuardTM Composite adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. Maximum Design Pressure —270 psf (See General Limitation #9) 13. Min. %" EnergyGuardTM Perlite adhered to the primed concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20 -40 lbs. /sq. Maximum Design Pressure —137 psf (See General Limitation #9) 14. Base Layer: Min 1.5" EnergyGuardTM RA, EnergyGuardTM RN, EnergyGuardTM Composite adhered to the concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20-40 lbs./sq.. Top Layer: Min. 1/2" EnergyGuardTM Perlite adhered to the base insulation layer or primed concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20- 40 lbs. /sq. Maximum Design Pressure —126 psf (See General Limitation #9) 15. Base Layer: Min. 11/4" EnergyGuardTM RA, EnergyGuardTM RN, EnergyGuardTM Composite adhered to the concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20-40 lbs./sq.. Top Layer: Min. ' /2" EnergyGuardTM fiberboard (c) or other approved wood fiberboard adhered to the base insulation layer or primed concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20-40 lbs./sq. Maximum Design Pressure —162 psf (See General Limitation #9) 16. Base Layer: Min. 11/4" EnergyGuardTM RA, EnergyGuardTM RN adhered to the concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20-40 lbs./sq.. Top Layer: Min. 3/4" EnergyGuardTM Perlite or other approved perlite insulation board adhered to the base insulation layer or primed concrete deck in a full mopping of approved asphalt applied within the EVT range at a rate of 20-40 lbs./sq.. Maximum Design Pressure —157 psf (See General Limitation #9) 17. Min. ' /2" EnergyGuardTM Perlite adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs. /sq. Maximum Design Pressure —90 psf (See General Limitation #9) 18. Min. 1.5" EnergyGuardTM Composite Deck is primed with GAF Asphalt/Concrete primer at a nominal rate of 0.75 ga/sq. Deck is covered with a RUBEROID® roof cover assembly fully adhered with hot asphalt applied at a minimum rate of 25 lb /sq (12 kg/m2) Maximum Design Pressure -360 psf (See General Limitation #9) NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 14 of 36 K CONCRETE DECK SYSTEM LIMITATIONS: 1. If mechanical attachment to the structural deck through the lightweight insulating concrete is proposed, a field withdrawal resistance testing shall be performed to determine equivalent or enhanced fastener patterns and density. All testing and fastening design shall be in compliance with Testing Application Standard TAS 105 and Roofing Application Standard RAS 117, calculations shall be signed and sealed by a Florida Registered Engineer, Architect, or Registered Roof Consultant. GENERAL LIMITATIONS: 1. Fire classification is not part of this acceptance, refer to a current Approved Roofmg Materials Directory for fire ratings of this product. 2. Insulation may be installed in multiple Layers. The first layer shall be attached in compliance with Product Control Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20- 40lbs. /sq., or mechanically attached using the fastening pattern of the top layer 3. All standard panel sizes are acceptable for mechanical attachment. When applied in approved asphalt, panel size shall be 4' x 4' maximum. 4. An overlay and/or recovery board insulation panel is required on all applications over closed cell foam insulations when the base sheet is fully mopped. If no recovery board is used the base sheet shall be applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8" ribbons in three rows, one at each side lap and one down the center of the sheet allowing a continuous area of ventilation. Encircling of the strips is not acceptable. A 6" break shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt application of either system shall be at a minimum rate of 12 lbs. /sq. Note: Spot attached systems shall be limited to a maximum design pressure of -45 psf. 5. Fastener spacing for insulation attachment is based on a Minimum Characteristic Force (F) value of 275 lbf., as tested in compliance with Testing Application Standard TAS 105. If the fastener value, as field - tested, are below 275 lbf. insulation attachment shall not be acceptable. 6. Fastener spacing for mechanical attachment of anchor/base sheet or membrane attachment is based on a minimum fastener resistance value in conjunction with the maximum design value listed within a specific system. Should the fastener resistance be less than that required, as determined by the Building Official, a revised fastener spacing, prepared, signed and sealed by a Florida Registered Engineer, Architect, or Registered Roof Consultant may be submitted. Said revised fastener spacing shall utilize the withdrawal resistance value taken from Testing Application Standards TAS 105 and calculations in compliance with Roofing Application Standard RAS 117. 7. Perimeter and corner areas shall comply with the enhanced uplift pressure requirements of these areas. Fastener densities shall be increased for both insulation and base sheet as calculated in compliance with Roofmg Application Standard RAS 117 and/or RAS 137. Calculations prepared, signed and sealed by a Florida registered Professional Engineer, Registered Architect, or Registered Roof Consultant (When this limitation is specifically referred within this NOA, General Limitation #9 will not be applicable.) 8. All attachment and sizing of perimeter nailers, metal profile, and/or flashing termination designs shall conform to Roofing Application Standard RAS 111 and applicable wind load requirements. 9. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e. field, perimeters, and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at enhanced pressure zones (i.e. perimeters, extended corners and corners). (When this limitation is specifically referred within this NOA, General Limitation #7 will not be applicable.) 10. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and Rule 9B -72 of the Florida Administrative Code. END OF THIS ACCEPTANCE NOA No.: 08- 1028.02 Expiration Date: 11/06/13 Approval Date: 02/25/09 Page 36 of 36 TGFU.R1306 - Roofmg`Systetns r 4 • 6. Deck: C -15/32 Incline: 1/2 http://database.ul.com/cgi-bin/XYV/template/LISEXTRFRAME/s... Insulation: — One or more layers perlite, glass fiber, .-in. minimum, polyisocyanurate, urethane, perlite / polyisocyanurate composite, perlite /urethane composite, 1A -in. minimum. Base Sheet (Optional): — One or more plies Type G1 or Type G2 or Type G3. Membrane: — One or more plies "Ruberoid® Torch" (Smooth or Granule) or "Ruberoid® Torch Granule Plus" or "Ruberoid® Mop" (Smooth or Granule) or "Ruberoid® Mop Plus Granule." Surfacing: — Gravel. 7. Deck: C -15/32 Incline: 1/2 Insulation (Optional): — One or more layers perlite, wood fiber, glass fiber, polyisocyanurate, urethane, perlite/polyisocyanurate composite, perlite/urethane composite, wood fiber / polyisocyanurate composite. Base Sheet: — Two or more plies Type G2 or Type G3. Ply Sheet (Optional): — One or more plies Type G1. Membrane: — One or more plies "Ruberoid® Torch" (Smooth or Granule) or "Ruberold® Torch Granule Plus" or "Ruberoid® Mop" (Smooth or Granule) or "Ruberold® Mop Plus Granule." Surfacing: — "Kamak No. 97" applied at 1, to 3 -gal /100 -ft2 or gravel. 8. Deck: NC Incline: 1/2 Insulation: — One or more layers perlite, glass fiber, 0 -in. minimum polyisocyanurate, urethane, perite / polyisocyanurate composite, perlite /urethane composite, lA In. minimum. Base Sheet (Optional): — One or more plies Type G1 or Type G2 or Type G3. Membrane: — One or more plies "Ruberold® Torch" (Smooth or Granule) or "Ruberold® Torch Granule Plus" or "Ruberoid® Mop" (Smooth or Granule) or "Ruberold® Mop Plus Granule." Surfacing: — Grundy "AL MB Aluminum Roof Coating" applied at 1 to 2- gaV100 -ft2. 9. Deck: C -15/32 Incline: 1/2 Insulation (Optional): — One or more layers perlite, glass fiber, A -in. minimum, polyisocyanurate, urethane, perlite / polyisocyanurate composite, pedte /urethane composite, phenolic, 1q in. minimum. Base Sheet: — One or more plies Type G2 " GAFGLAS® #75 Base Sheet ", or'Tri -Ply® #75 Base Sheet ", hot mopped or mechanically fastened in place. Ply Sheet: — One or more plies Type G1 "GAFGLAS® Ply 4" or "Tri -Ply® Piy 4" or "GAFGLAS® Ply 6" hot mopped in place. Membrane: — "Ruberoid® Mop 170 FR" or "Ruberold® Dual FR" or "Ruberoid® Mop FR" or "Ruberold® EnergyCapT" Mop FR." Surfacing — (Optional): "GAF Fibered Aluminum Coating" applied at 1A -gal /100 -ft2 or "GAF Weather Coat Emulsion" applied at 3 -gal /100 -ft2. t10 D,e0k: C -15/32 Incline: A — Insulation (Optional): — Perlte, fiber glass, polyisocyanurate, urethane or perlite/polyisocyanurate composite. Base Sheet: — One or more layers Type G2 "GAFGLAS® #75 Base Sheet" or'Tri -Ply® #75 Base Sheet" or Type G3 "GAFGLAS® Mineral Surfaced Cap Sheet" or "Tri -Ply® Mineral Surfaced Cap Sheet" hot mopped or mechanically fastened. Pty Sheet (Optional): — One or more plies Type G1, hot mopped in place. Membrane: — "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberold® EnergyCap"" Mop FR." 11. Deck: C -15/32 Incline: 1/2 Insulation (Optional): — Perlte, fiber glass, polyisocyanurate, urethane or perlite/polyisocyanurate composite, butt offset a minimum of 6 -in. from plywood deck joints. Base Sheet: — One or more plies Type G2 "GAFGLAS® #75 Base Sheet" or'Tri -Ply® #75 Base Sheet" or Type G3 "GAFGLAS® Mineral Surfaced Cap Sheet" or "Tri -Ply® Mineral Surfaced Cap Sheet" hot mopped or mechanically fastened. Pty Sheet (Optional): — One or more plies Type Gi, hot mopped in place. Membrane: — One ply "Ruberoid® Torch Smooth" or "Ruberoid® Mop Smooth" or "Ruberoid® Mop Smooth 1.5" or "Ruberoid® Mop Smooth Plus" or "Ruberoid® Dual Smooth." Membrane: — One ply "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCapT" Mop FR." 12. Deck: NC Incline: 1 Insulation (Optional): — Perlite, fiber glass, wood fiber, polyisocyanurate, urethane or perlite / polyisocyanurate composite. Base Sheet: — One or more layers Type G2 " GAFGLAS® #75 Base Sheet" or'Tri -Ply® #75 Base Sheet" or Type G3 " GAFGLAS® Mineral Surfaced Cap Sheet" or "Tri -Ply® Mineral Surfaced Cap Sheet ", hot mopped or mechanically fastened. Ply Sheet (Optional): — One or more plies Type G1 hot mopped in place. Membrane: — One ply "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCap'' Mop FR." 13. Deck: NC Incline: 1/2 Insulation (Optional): — Perlte, fiber glass, wood fiber, polyisocyanurate, urethane or perite / polyisocyanurate composite. Base Sheet (Optional): — One or more plies Type G2 or Type G3 base sheet, hot mopped or mechanically fastened. Ply Sheet (Optional): — One or more plies Type G1 hot mopped in place. Membrane: — One ply "Ruberoid® Torch Smooth" (smooth) or "Ruberoid® Mop Smooth" or "Ruberoid® Mop Smooth 1.5" or "Ruberoid® Mop Smooth Plus" or "Ruberoid® Dual Smooth." Membrane: — One ply "Ruberoid® Mop 170 FR" or "Ruberoid® Dual FR" or "Ruberoid® Mop FR" or "Ruberoid® EnergyCap""' Mop FR." 14. Deck: NC Incline: • 9 of 49 7/10/2012 1:36 PM Florida Department of 11,1 ' JUL 2 0 2612 = Environmental Protection Miami -Dade DERM Division of Air Resource Managemer>6 Y: �� Air Quality N.W. 1st Court, Division 701 . 1 st Court, 2nd Floor Miami, Florida 33136 NOTICE OF DEMOLITION OR ASBESTOS RENOVATION TYPE OF NOTICE (CHECK dNE ONLY): ErORIGINAL ❑ REVISED ❑ CANCELLATION TYPE OF PROJECT (CHECK NE ONLY): ❑ DEMOLITION ❑ RENOVATION C2I'ROOFING IF DEMOLITION, IS ITN ORDERED DEMOLITION? ❑ YES ❑ NO IF RENOVATION: IS IT AN EMERGE CY RENOVATION OPERATION? ❑ YES ❑ NO IS IT A PLANNEDkENOVATION OPERATION? ❑ YES ❑ NO Facility Name Sr i ?- a e-A ,+w re Ft 1. 11. Address 4, ,_ `a' Al E City 1°i A? AP/ • �► rC Site Building Size Prior Use: Present Use: ❑ COURTESY File # Process # F P1'96 (Square Feet) ❑ School/College/University Q School/Co Lege/University Facility Owner 4 VC' / s "4-1Cc? y A,a ' Address (4X-t--6=0,4 a ' !..Se' 2 City Contractor's Name SC5 /fit Address /72 A SoL), /,, City "710 State r," Zip County Consultant Inspecting Site # of Floors Building Age in Years ❑ Residence ❑ Small Business Other C ie .4 Je4nea j ❑ Residence ❑ Small Business Other Je Phone ( ) State Ar::r` Zip ?for �7 •49 v' cv .sa 4,e, j, /State J( Zip `3y /.lei Phone o) S) Is the contractor exempt from licensure under section 469.002(4), F.S.? ❑ YES El NO IV. Scheduled Dates: _Notice must be postmarked �1 working days before the project start date) r0 -1 -n 6estos Removal (mm/dd/yy) Start: 7 - 74- Yrnish: , �' �' Demo/Renovation (mm/dd/yy) Start: Finish: V. Descr�p'ffo °n o"Tplanned'demolition or renovation work to be performed and methods to be employed, including demolition or renovation techniques to be used and description of affected facility components. Procedures to be Used (Check All That Apply): ❑ Strip and Removal ❑ Glove Bag ❑ Bulldozer ❑ Wrecking Ball Er Wet Method ❑ Dry Method ❑ Explode ❑ Burn Down OTHER: VI. Procedures for Unexpected RACM: VII. Asbestos Waste Transporter. Name Address City .5 le 4,-7 Veer' Phone ( ) State Zip VIII. Waste Disposal Site: Name Address City State Zip n MIAMI -DADS p1'ri•1e��f® IX. RACM or ACM: Procedure,.including analytical. methods, employed to detect the presence of �M?: S ear t �l�id fti n r�ia6Te ACM. Th i is to oertiit) that the require Amount of RACM or ACM* Notification (s) Regarding asbestos have been square feet surfacing material square feet cementitious s' :,�a,°i:'`e• in ' = pliance with linear feet wipe square feet resilient floe n • plicable r ulationS. cubic feet f RACM off facility components r (' square feet asphalt roof,_ *Identify and describe 1urfacing material and other materials as applicable: Sign Dat I certify that the above information is correct and that an individual trained in the provisions of this regulation (40 CFR Part 61, Subpart M) will be on- site during the demolition or renovation and evidence that the required training has been accomplished by this person will be available for inspection during r}omial business hou - g y;'7,•. <-e-o4 L!"./ i'''"° .t (Print riaryle of Owner /Ciprator)�'�. (Signature of Owner /Operator (Date) (Contact phone #) DERM USE ONLY Postmark/Date Received ' � i � 4- iD # 161 01 -158 4/10 DISTRIBUTION: White —DERM Yellow Applicant Pink — Reserve Gold— Reserve BE iEVWW PL FINAL. APPROVAL .,� : AL DEPARTMENT ,J RESOURCES S EN A� IZ pc�pltRCES t *jig 110: _.-- DATE 2. ET5 Etv144o4A4f•€44 Asbestos Business License # ZA0000218 Mold Assessor Business License # MRSA1850 / Mold Remediator Business License # MRSR1932 Mold & Asbestos Surveys & Removal * Phase 1 Environmental Assessment * Air Monitoring & Analysis July 19, 2012 Saint Rose of Lima School 415 NE 105 Street Miami Shores, Florida RE: Saint Rose of Lima School 415 NE 105 Street Miami Shores, Florida Dear Sir: REPORT # FL12- 0552RAS Pursuant to your request and our agreement, ETS Environment, Inc. has performed an Asbestos Roof Survey on July 18, 2012 at the above referenced facility. SURVEY LIMITATIONS This inspection report is the result of a diligent search of the facility for asbestos containing roofing materials (ACRM). All analyzed samples were readily available to our surveyor. If in the course of a renovation or demolition activity, additional suspect materials become exposed, all activities should immediately cease and the suspect material brought to our attention for evaluation and recommendation(s) if necessary. The scope of this inspection to perform a survey of roof surfacing materials for suspect ACM. Therefore only roofing material was sampled and all other building material is NOT included in this inspection survey report. LABORATORY METHODS Each sample was returned to the laboratory at ETS Environment, Inc., logged, and stored for analysis. All analyses were performed using the Polarized Light Microscope (PLM) Method 40 CFR Ch.1, Pt. 763, Subt. F, App. A Pgs. 293 -299, 1 -1 -87 ed.; (Polarized Tight microscopy in conjunction with dispersion staining). The scope of our investigation consisted of the following: • Ten (10) random locations of roof system materials were chosen by our Certified Technician to secure as bulk samples for analysis. • Samples for asbestos analysis were taken on any visibly potential Asbestos Containing Materials (ACM). Samples were placed in plastic bags and labeled for further analysis. • All secured bulk samples were analyzed by Polarized Light Microscopy to verify asbestos content. • Preparation of final report 12334 73 COURT NORTH, ROYAL PALM BRACH, FL. 33412 (954)236 -0053 (561)333 -0624 FAX (561)333 -0684 SITE DESCRIPTION The roof of the building is a sloped wood deck with barrel tiles over a base sheet and built - up roof with a granulated surface. There is a drip edge along the perimeter of the roof. The roof area surveyed occupies approximately 18,000 ft2. CONCLUSIONS Based on our survey and bulk sample analysis, it was evident that NO asbestos fibers were found in any of the samples taken. CLOSING REMARKS ETS Environment, Inc. greatly appreciates the opportunity to provide quality environmental services at a reasonable cost. It has been a pleasure working with you and we look forward to doing so in the near future. Should you have any questions or comments, please do not hesitate to call. Respectfully submitted, ETS Environment, Inc. Dennis Emerson .H. AHERA Inspector Certificate No. 144519 ZA # 0000218 I hereby certify that the Roof Asbestos Survey conducted on July 18, 2012, at Saint Rose of Lima School, 415 NE 105 Street, Miami Shores, Florida, was performed by Dennis Emerson, an E.P.A. Accredited A.H.E.R.A. Inspector utilizing the Code of the Federal Regulation Standards, 40 C.F.R., Part 763, Subpart E, Section 763.80- 763.99 and the State Asbestos Regulations, Florida Statues 469.003. Reviewed by 5444 Re46 an.4 Seled 14:414 Ste, fL 7 i /f' '/Z Bruce Marchette, C.I.H. D - to Florida Certified Licensed Asbestos Consultant No. IA0000041 ETS ENVIRONMENT, INC. 2 ETS E4%f,%u4 BULK SAMPLE TRANSMITTAL FORM Client Name : Saint Rose of Lima School Project Name : Report Number: Saint Rose of Lima School 415 NE 105 Street Miami Shores, Florida FL12- 0552RAS Date Collected: 07/18/12 Sample # Location of Sample Description Condition Asbestos 1 Sloped Roof Base Sheet F.C. NAD 2 Sloped Roof Base Sheet F.C. NAD 3 Sloped Roof Base Sheet F.C. NAD 4 Sloped Roof Base Sheet F.C. NAD 5 Sloped Roof Base Sheet F.C. NAD 6 Flat Roof Membrane F.C. NAD 7 Flat Roof Membrane F.C. NAD 8 Flat Roof Membrane F.C. NAD 9 Flat Roof Membrane F.C. NAD 10 Flat Roof Membrane F.C. NAD Sampled By : Dennis Emerson NAD - NO ASBESTOS DETECTED SAMPLE CONDITION CODES G.C. Good Condition F.C. Fair Condition P.C. Poor Condition P.D Physical Damage W.D. Water Damage F Friable N.F. Non - Friable H. Con. High Contrast M. Con. Moderate Contrast L. Con. Low Contrast 3 ETS E4wd(4.4%n%u4 �. 12334 7311 Court North Royal Palm Beach, FI. 33412 (954) 236 -0053 Project : Saint Rose of Lima School Lab Code : 0374 Sample Number Anal. Init. Sample Item Description Asbestos Percentage & Type Identified Percentage & Type Non- Asbestos Fibers Percentage Non -Fiber Mat. 1 DKE Base Sheet NAD 7 -10 Fiberglass 8 -10 Cellulose 80 -85 Matrix 2 DKE Base Sheet NAD 7 -10 Fiberglass 8 -10 Cellulose 80-85 Matrix 3 DKE Base Sheet NAD 7 -10 Fiberglass 8 -10 Cellulose 80 -85 Matrix 4 DKE Base Sheet NAD 7 -10 Fiberglass 8 -10 Cellulose 80 -85 Matrix 5 DKE Base Sheet NAD 7 -10 Fiberglass 8 -10 Cellulose 80 -85 Matrix 6 DKE Membrane NAD 12 -15 Fiberglass 18 -20 Cellulose 65 -70 Matrix 7 DKE Membrane NAD 12 -15 Fiberglass 18 -20 Cellulose 65 -70 Matrix 8 DKE Membrane NAD 12 -15 Fiberglass 18 -20 Cellulose 65 -70 Matrix 9 DKE Membrane NAD 12 -15 Fiberglass 18 -20 Cellulose 65 -70 Matrix 10 DKE Membrane NAD 12 -15 Fiberglass 18 -20 Cellulose 65 -70 Matrix Dennis Emerson I.H. Microscopist N.A.D. = No Asbestos Detected 4 RFCETVED JUL 10 2012 POWER OF ATTORNEY KNOW ALL MEN BY THESE PRESENTS: That the most Reverend Thomas Wenski, as Archbishop of the Archdiocese of Miami, his successors in office, a corporation sole, has made, constituted and appointed, and by these presents does hereby make, constitute and appoint Sister Elizabeth A. Worley, C.O.O., his true and lawful attorney for him and in his name, place, and stead Giving and granting unto Sister Elizabeth A. Worley, C.O.O., his said attorney full power and authority to do and perform all and every act and thing whatsoever requisite an necessary to be done in and about the premises as fully, to all intents and purposes, as he might or could do if personally present, with full power of substitution and revocation, hereby ratifying and confirming all that Sister Elizabeth A. Worley, C.O.O., his said attorney or his substitute shall lawfully do or cause to be done by virtue hereof. In Witness Whereof, I have hereunto set my hand and seal this 1 g day of A.D., 2011 Signed, sealed and delivered in presence of: Witness: Witness Signature h?4l?c R Printed Na /14.0474 . �4..%t ted Name STATE OF FLORIDA COUNTY OF DADE ) SS: The Most Reverend Thomas Wenski as Archbishop of the Archdiocese of Miami his successors in office, a corporation sole I hereby certify that on this day, before me, an officer duly authorized to administer oaths and take acknowledgements, personally appeared The Most Reverend Thomas Wenski, as Archbishop of the Archdiocese of Miami, his successors in office, a corporation sole, known to me to be the person described in and who executed the forgoing instrument, who acknowledged before me that he executed the same, and an oath was not taken. X Said person is personally lcnown to me Said person provided the following type of identification: Witness my hand and official seal in the County and State last aforesaid this 1 9 day of ill A.D. 2011. My Commission Expires: 2 i5 MAYRA NEUUNA ROSSELL mcambeion OEMIMIS M y Wanks r i ll.Rhl