PL-12-1188
Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795 -2204 Fax: (305)756 -8972 Inspection Number: INSP- 175230 Permit Number: PL -6 -12 -1188 Scheduled Inspection Date: August 15, 2012 Inspector: Hernandez, Rafael Owner: ARFELD, MARTA Job Address: 55 NW 102 Street Miami Shores, FL Project: <NONE> Contractor: SUN STAR ENERGY LLC Permit Type: Plumbing Residential Inspection Type: Final Work Classification: Solar Phone Number Parcel Number 1131010180090 Phone: (561)287 -1118 Building Department Comments SOLAR HOT WATER Passed Failed Correction Needed Re- Inspection Fee No Additional Inspections can be scheduled until re- inspection fee is paid. Inspector Comments August 14, 2012 For Inspections please call: (305)762 -4949 Page 14 of 34 I 111111 11111 11111 11111 11111 11111 11111 1111 1111 NOTICE OF COMMENCEMENT A RECORDED COPT MUST BE POSTED ON THE JOB SITE AT TIME OF FIRST INSPECTION PERMIT NO. TAX FOUO NO. t)-�'jb 1 - oiS -d�5b STATE OF FLORIDA: COUNTY OF MIAMI -DADS THE UNDERSIGNED hereby gives<notice that knproverr►ents will be made to certain real property, and in accordance with Chapter 713, Florida Statutes, the following information Is provided in this Notice of Commencement. CFN 20121R05.39862 OR Bk 28211 Ps 0919; (1t?s) RECORDED 08/01/2012 11:101:007 HARVEY RUVIH, CLERK OF COURT MIAMI—DADE COUNTY, FLORIDA LAST PAGE 9 Space above reserved for use of recording office 1. Legal description of property and street/address: 0' 1c6 -b i i t?st 1 S V — 441 p y 1 d t -3' 1 2. Description of improvement: Se./ qb— 3. Owner(s) name and address: Y"Y1/ L+i - ter, Interest in property: b ° ^— o^ a.1 Name and address of fee simple titleholder 4. Contractor's name, address and phone number. Sti , Y1 - skim e, Tx;� e- Q.C� -r� '3-1. f 5. Surety: (Payment bond required by owner from contractor, If any) Name, address and phone number. Amount of bond $ 6. Lender's name and address: nF FLORIDA, COUNTY OF DADE AJ4) / �, - 1' 'tape/ :xl-ie q v.' g' 723 -��� b 7. Persons within the State of Florida designated by Owner upon Wiitli `ft 'ti t ' ' nus tt lived as Section 713.13(1)(a)7..Aorida Statutes, rq' fr,t0 !q 0 00 Name, address and phone number I c1* C A,D. 20 8. In addition to himself, Owners designates the following person) 713.13(1)(b), Florida Statutes. Name, address and phone number. By 9. Expiration date of this Notice of Commencement: (the expiration date is 1 year from the date of recording unless a different date is specified) WARNING TO OWNER ANY PAYMENTS MADE BY THE OWNER AFTER THE EXPIRATION OF THE NOTICE OF COMMENCEMENT ARE CONSIDERED IMPROPER PAYMENTS UNDER CHAPTER 713, PART I, SECTION 713.13. FLORIDA STATUTES, AND CAN RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO. YOUR PROPERTY. A NOTICE OF COMMENCEMENT MUST-BE RECORDED AND POSTED ON THE JOEL SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE COMMENCING WORK OR RECORDING YOUR NOTICE OF COMMENCEMENT. Signature(s) of tV s) o Prepared By Print Name Title /Office STATE OF FLORIDA COUNTY OF MIAMI -DADE The f Ding intro nt as ck r wl edged before me this 7 Individually, or 0i'as for C I Personally known, or roduc ed the following type of Identificatic • L L.. Signature of Notary Public: ; Print Name: 1a' (SEAL) VERIFICATION PURSUANT TO SECTION 92.525. FLORIDA STATUTES Under penalties`of perjury, I declare that I have read the foregoing and that the facts stated in It are true, to the best of my knowledge and belief. Signatu (s) of Owner(s) or O»fer(s)'s Authorized Officer /Director/Partner /Manager who sig ,ASE s 3n ed Officer/Director/Partner /Manager Prepared By Print Name Title/Office day of Wf Efertda omm.' x res a 3t. 2^' Commiss MOW' c= State of Florida My Comm. Expires May 31, 2016 Commission # EE 203923 By 123.01 0 By -1 • 2 lo t Mes.(Iti Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 3 138 Tel: (305) 795.2204 Fax: (305) 756.8972 INSPECTION'S PHONE NUMBER: (305) 762A949 BUILDING PERMIT APPLICATION FBC 2010 Permit Type: PLITIVERING OWNER: Name (Fee Simple Titleholder): hi ct. SL-1> Phone#: 305— ' T5.33 1_- C .11:1 \ JUN 28 BY: Permit No Master Permit No. Address 0 2ir r City: lrY‘ "Po-"" ° r exts State: / n- eN, zip: 3 °S- 0 ( Tenant/Lessee Name: Phi:Met Email: JOB ADDRESS: 6. \\) LaJ ( 0 t-v- c City: Miami Shores County: Miami Dade Zip: Folio/Parcel#: ) 1 3/o -- 01 0 c)7 0 Is the Building Historically Designated: Yes Flood Zone: CONTRACTOR: Company Name: -1-+C:r c-6-1 t "07 Phone#: Address: 7i3 City: ,t(A, (4,-1qm/fel State: zip:' Qualifier Name: -y 71 5 4-° Phone#: State Certification orltegistration #: CT-C- 1 7 Certificate oftompetency #: Contact Phone#: -1-‘61 /1 1 e Email Address: 50 V LL »i C 0 frtyp, DESIGNER: Architect/Engineer: Phone#: Value of Work for this Permit: $ 'SE3 ) Square/Linear Footage of Work: ODemolition DescriptiffirbfiVUork: Lotion fiul? 1,AJR 0544-31 ******* *******************************pees******************************************** Submittal Fee $ Permit Fee $ CCF $ CO/CC $ Scanning Fee $ Notary $ Training/Education Fee $ Technology Fee $ Double Fee $ Structural Review $ Radon Fee $ DBPR $ Bond $ TOTAL FEE NOW DUE $ 2_0K -7x 19 Bonding Company's Name (if applicable) Bonding Company's Address City State Zip Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and AIR CONDMONERS, ETC OWNER'S Al}FIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also, a certified copy of the recorded notice of corrimencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will not be approved and a reinspection fee will be charged. Signature y� Owner or Agent The foregoing instrument was acknowledged before me this ILIA day of -, v.^.d. , 20 , by 1®h+6a -ft3-0-. who is personally known to me or who has produced I `t p t As identification and who did take an oath. NOTARY PUBLIC: Sign My Commissio Notary P • State of Florida . ,.z Commission • EE 203923 a. * * * * * * * * * * * * * * * * * * * * * * * * ** * * * * * * * * * * * * * * ** APPROVED BY Signature Contractor The foregoing instrument was acknowledged before me this/ V day of ✓rte , 20/ 1 , by J ' • e el , who is personally known to me or who has produced r - 1� as identification and who did take an oath. NOTARY PUBLIC: * * * * * * ** **** **** ** **** *** ***e ** -< * * **** *** - **** T * ***** ** * * ** ** Vie, (Revised 07 /10 /07)(Revised 06 /10/2009)(Revised 3/15/09) Plans Examiner Zoning Structural Review Clerk -sus)skzur-aQA e= ; °f'° CERTIFICATE- OF LIABILITY INSURANCE oATE,m.,.1YYtnr; 6/14!2012 THIS CERTIFICATE' IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE CERTIFICATE DOES NOT AEFIRMATIVEELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BELOW THIS CERTIFICATE' OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), REPRESENTATIVE OR PRODUCER, AND THEE CERTIFICATE HOLDER. HOLDER. THIS BY THE POLICIES AUTHORIZED IMPORTANT: If the certificate holder is an ADDITIONAL INSURED, the poilcy(Ies) must be endorsed. If SUBROGATION IS WAIVED, sublet to the terms and condit(ons of the policy, certain policies' may require an endorsement. A statement on this certificate does not confer rights to the certificate holder in lieu of such endorsements }. PRODUCER Commercial Coverages' Inc 1000 Pelican Bay Drive Daytona Beach; FL 32119 CONTACT NAME: PHONE ■, . 3$6 -756 - $551 Not: 3$6,756 »2344 ADDRESS: INSURER(S) AFFORDING COVERAGE NAIL # INSURER A: CYPRESS PROPERTY $t CASUALTY INsURED SUN STAR ENERGY LLC 723 FAIRWAY DR NEW SMYRNA BEACH, FL 32168 1r•r.ti 171 A;AL e. w.... ...:....- .--- .- ._- .- ._.�.--- INSURER B : 03/25/12 INSURER EACH OCCURRENCE INSURER D : DAMAGE TO RENTED PREMISES (Ea aagmence1 . INSURER 8 : INSURER P: CLAIMSMADE • RAYi pL19 RUM THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BLOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD' INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WWOH THIS CERTIFICATE MAY Be ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, . EXCLUSIONS CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED SY PAID CLAIMS, LTR TYPE OFINSURRNCE INSR WVD : POLICY NUMBER ( fDDDYD(YYYY1' .fMWDA1KYYYI. LASTS A GENERAL UABIUTY COMMERCIAL GENERAL L BIWY CFLI017026 03/25/12 03/25/13 EACH OCCURRENCE $ 1000000 DAMAGE TO RENTED PREMISES (Ea aagmence1 . $ 100000 CLAIMSMADE / Y :'OCCUR MEDExP(nnyarOParson) $ 5000 PERSONAL & ADV INJURY GENERAL AGGREGATE PRODUCTS - COMP/OPAGO $. 1000000 $ 2000000 8 2000000 GEM AGGREGATE UMIY APPLIEIS PER. 1 POLICY t I ( 1 LOC $ AUTOMOBU:EUABIUTY __ (Ea DSINGLELiMR ANY AUTO ALL OYVNED AUTOS HIRED At1TOS SCHEDULED AUTOS AD AUTOS BODILY INJURY (Pet peraoni $- BODILY INJURY (Per accident) $ PROPERTY DAMAGE (Par occident) $ $ ffMBREU.A UAB EXCESS t:IAB OCOUR CLAIMS-MADE EACH OCCURRENCE AGGREGATE S 5 DEO [RETENTION$ WORKERS'COMPEN$ATION AND EMPLOYERVatuTit UA ANY PROPRIETOR/PAR-IRE UT E YIN OFFICERIMEMBER'EXCLUDEDV IMandatorylnNHl It desaibe UMW' DESCRIPTION OF OPERATIONS belay N 1 A ( ITO YS LIMITS ` TSI I ER E.L. EACH ACCIDENT $ E. UISEA$E. EA EMPLOYEE b E,L.SEASE - POLICY LIMIT 5 DBSCRIPTIDN OP OPERATIONS 1 LOCATIONSIVE}fJCLES (Attach ACCORD 141,Additlbnal Remarks Schedule, It mare space Is regtdred) "=Iii ieIf A' •r [Aril .-... fu,.,va i/Ar ELLATION MIAMI SHORES VILLAGE BUILDING DEPARTMENT 10050 NE 2ND AVE MIAMI SHORES, FL 33138 SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. AUTHORIZED REPRESENTATIVE ACORD 25 (251.01013) -- 01988.2010 ACORD The ACORD name and logo are registered marks of ACORD ORPORATION. All rights reserved. A'R °® CERTIFICATE OF LIABILITY INSURANCE °��`��°°"'""' 6/15/2012 THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUTHORIZED REPRESENTATIVE OR PRODUCER, AND THE CERTIFICATE HOLDER. IMPORTANT: If the certificate holder Is an ADDITIONAL INSURED, the policy(les) must be endorsed. If SUBROGATION IS WAIVED, subject to the terms and conditions of the policy, certain policies may require an endorsement. A statement on this certificate does not confer rights to the certificate holder in lieu of such endorsement(s). PRODUCER Agency Svc - Branch 8 0 fax 469 Geneva FL 32732 CONTACT Jim IIraeth PHONE FAX INC. No. Ezt): (407) 349 -9283 (A/C,No):(800) 853 -6102 ADDLSs: jim. uraeth@apexco.net INSURERS) AFFORDING COVERAGE NAIC tt INSURERA:Association Insurance Company 25496 INSURED Sun Star Energy LLC 723 Fairway Dr New Smyrna Beach FL 32168 INSURER a : INSURER C : INSURERD: $ INSURERE: $ INSURER F : CLAIMS -MADE COVERAGES CERTIFICATE NUMBER: Cert ID 12709 REVISION NUMBER: THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL. THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS INSR 1,TR TYPE OF INSURANCE ADDL INSR SUBR WVD POLICY NUMBER POLICY EFF (MM/DDIYYYY) POLICY EXP (MMIDD1YYYY1 LIMITS GENERAL LIABWiY COMMERCIAL GENERAL LIABILITY EACH OCCURRENCE $ DAMAGES (RENTED PREMISES (Ea occurrence) $ CLAIMS -MADE OCCUR MED EXP (My one person) $ PERSONAL & ADV INJURY $ GENERAL AGGREGATE $ GEN'L AGGREGATE POLICY LIMIT APPLIES PER PRO- JECT LOC PRODUCTS - COMP/OP AGG $ $ AUTOMOBILE LIABILITY ANY AUTO SOS OWNED HIRED AUTOS _ SCHHED LED NON-OWNED AUTOS COMBINED tSINGLE LIMIT (Ea $ BODILY INJURY (Per person) $ BODILY INJURY (Per accident) $ PROPERTY DAMAGE (Per dent) $ $ UMBRELLA UAB EXCESS LAB _ OCCUR CLAIMS -MADE EACH OCCURRENCE $ AGGREGATE $ DED RETENTION $ $ WORKERS COMPENSATION AND EMPLOYERS' WIBILITY ANY PROPRIETOR / PARTNER /EXECUTIVE OFFICERIMEMBER EXCLUDED? (Mandatory In NH) fl yes, describe under DESCRIPTION OF OPERATIONS below Y/N N / A MC7010349601 5/3/2012 5/3/2013 . STATU- OTH- TORY waifs ER E.L. EACH ACCIDENT $ 100,000 E.L. DISEASE - EA EMPLOYEE $ 100, 00 0 E.L DISEASE - POLICY LIMIT $ 500,000 $ $ DESCRIPTION OF OPERATIONS / LOCATIONS 1 VEHICLES (Attach ACORD 101, Additional Remarks Schedule, If more space Is required) CERTIFICATE HOLDER CANCELLATION Miami Shores Village Building Department 10050 NE 2nd Avenue Miami Shores FL 33138 SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. AUTHORIZED REPRESENTATIVE (./ l - ACORD 25 (2010/05) ©1988 -2010 ACORD CORPORATION. All rights reserved. The ACORD name and logo are registered marks of ACORD Page 1 of 1 Miami Shores Village Building Department 10050 N.E.2nd Avenue. Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 CONTRACTORS' REGISTRATION ALL CONTRACTORS MUST PROVIDE COPIES OF LICENCES AND INSURANCES EACH TIME A PERMIT IS SUBMITTED. ONTRACTOR IS A FLORIDA STATE CERTIFIED CONTRACTOR: COPY OF QUALIFIER'S STATE LICENCES COPY OF LOCAL BUSINESS TAX RECEIPT COPY OF LIABILITY INSURANCE (CERTIFICATE HOLDER TO BE MIAMI SHORES VILLAGE BLDG DEPT) COPY OF WORKERS COMPENSATION LEITHER CERTIFICATE OR EXCEMPTION) IF CONTRACTOR HAS A MIAMI DADE COUNTY CERTIFICATE OF COMPETENCY: A. COPY OF CERTIFICE OF COMPETENCY OF QUALIFIER B. COPY OF LOCAL BUSINESS TAX RECEIPT B. COPY OF MIAMI DADE COUNTY MUNICIPAL CONTRACTOR'S TAX RECEIPT C. COPY OF LIABILITY INSURACE (CERTIFICATE HOLDER MUST BE MIAMI SHORES VILLAGE BLDG DEPT) D. COPY OF WORKERS COMP INSURANCE (EITHER CERTIFICATE OR EXEMPTION) YOUR INSURANCE COMPANY MUST ISSUE A CERTIFICATE HOLDER AS FOLLOW: MIAMI SHORES VILLAGE BLDG DEPT 10050 NE 2ND AVE MIAMI SHORES, FL 33138 COMPLETE CONTRACTOR'S INFORMATION BUSINESS NAME: C-T'ceti BUSINESS ADDRESS: -723 `^'"41 t' 14(2-, CITY Ile -w Cr'`yr1- Z .3`)) 69, STATE ( ZIP CODE 3 2 1 6 2: BUSINESS PHONE: ("CA ) l') ` i) 1 Ig FAX NUMBER (L( ) 9 LI- CELL PHONE (� ) 377 `3'' ' QUALIFIER'S NAME: Yy" 0 wed QUALIFIER'S LIC NUMBER: CC t 1 tt 28( 5 7 E -MAIL ADDRESS (IF APPLICABLE): v''� �"t' ��^ ,47 k y Created on 3119109 BY MLDV 1 RV 3126109 MLDV tee, 1 , c 12 10:44e lntegraClean & Dry. LLL BOWEN, JIMMY L; Doing Business As SUN STAR ENERG... lutes: 1. www. m} rfloridalicense .comiLicenseDetail.asp ?SID- &id -31E.. of 1 (2 42.56 PM 2/25re011 Licensee Details Licensee Information Name: 130WEN, JIMMY L (PrimElry Name) SUN STAR ENERGY, L.L.C. (DBA Name) Main Address: 723 FAIRWAY DR NEW SMYRNA BEACH Florida 32168 County: VOLVSIA License Mailing: LicenseLocation : License Information License Type: Certified Plumbing Contractor Rank: Cert Plumbing License Number: CFC1428197 Status: Current,Acttve Licensure Date: 03/17/2010 Expires: 08/31/2012 Special Qualifications Qualification Effective Construction Business 03/17/ 2010 Fingerprint (Construction Industry Licensing 09/15/2009 Board) View Related License Information View License Complaint n tact .Its :: 1949 _.. rS.h.t tntaa,5.treelF .F1- .3239..2 :: C.all._Ce te.C@dbttcsS? .fl•us :: C,:s:orner Cont act Cent :r: 3 4-3' :395 Tha Sate of FICr 1A s 6.^ a ^` G °^- WOycr. Copy Z-•ZO)O.S Ey.i2tAgy_Stalvnitrit Ur Jer FlerWa Idv., e•rN•• rive o-.louc •e:,orcts I( wu. ,'o ru: %:s ^t , Otto e-•nali address . rrleated 'r response to a pj'vbc•re:.Or(S reluest, d) plc. Satter f. ec•rOn.c ntifl ro trms e•+tay. .rste. , ',tact •t.e cffice oy pI rte or by traditional mail it you have any Que$ nns reco,dtr9 DtpR.'S acc <ss■ti.o, phase co 'tact our W Master Al bm d:lar.state:•..R.US. 2125/2011 12:45 Ply MIAMI -DADE COUNTY DEPARTMENT OF PERMITTING, ENVIRONMENT AND REGULATORY AFFAIRS 11805 SW 26TH ST. SUITE 207 MIAMI FL, 33175 (786) 315 -2880 STATE CONTRACTOR'S CERTIFICATE OF VOLUNTARY REGISTRATION WITH MIAMI -DADE COUNTY ISSUED APRIL 25, 2012 THIS IS TO CERTIFY THAT SUN STAR ENERGY LLC CONTRACTOR CERTIFICATE NO.: CFC1428197 TRADE: PLUMBING REGISTRATION EXPIRATION DATE: 08/31/2012 HAVING MET THE REGISTRATION REQUIREMENTS CF MIAMI -DADE COUNTY, IS REGISTERED AS A STATE CONTRACTOR IN THE FOLLOWING CATEGORY(S): 0001 PLUMBING WITH ALL WORK TO BE DONE UNDER THE SUPERVISION, DIRECTION AND CONTROL OF QUALIFYING AGENT BOWEN JIMMY L S.S.N. - -8330 ALTERATION, REPRODUCTION OR TRANSFER OF THIS CERTIFICATE IS PRO IBITED. SUN STAR ENERGY LLC • 723 FAIRWAY DR NEW SMYRNA BEACH CHARLES DANGER, P.E. SECRETARY, CONSTRUCTION TRADES QUALIFYING BOARD FL 32168 2011 /2012 Volusia County Business Tax Receipt Issued pursuant to F.S. 205 and Volusia County Code of Ordinances Chapter 114-1 by: Volusia County Revenue Division - 123 W Indiana Ave, Room 103, DeLaud, FL 32720 — 386 - 736 -5938 Volusia County FLORIDA BUSINESS TYPE Plumbing Contractor Receipt # 2010321015 Expires: September 30, 2012 Business Location: 723 FAIRWAY DR Business Name: Owner Name: Mailing Address: SUN STAR ENERGY,L.L.C. MICHELLE APHOLZ PO BOX 29 STERLING, PA 18463 CODE COUNT 301P 1 TAX $18.00 • This receipt indicates payment of a tax, which is levied for the privilege of doing the type(s) of business listed above within Volusia County. This receipt is non- regulatory in nature and is not meant to be a certification of the holder's ability to perform the service for which he is registered. This receipt also does not indicate that the business is legal or that it is in compliance with State ar local laws and regulations. • The business must meet all County and /or Municipality planning and zoning requirements or this Business Tax Receipt may be revoked and all taxes paid would be forfeited. • The information contained on this Business Tax Receipt must be kept up to date. Contact the Volusia County Revenue Division for instructions on making changes to your account. THIS PORTION OF THE BUSINESS TAX RECEIPT MUST BE - - - POSTED CON '!QUOuS -1 -Y . YOUR PLA -OED BUSINESS Volusia County Business Tax Receipt Revenue Division - 123 W Indiana Ave, Room 103, DeLand, FL 32720 — 386 -736 -5938 DATE PAID: 07/19/2011 PAYMENT Lockbox-10-00100074 RECEIPT #: TOTAL TAX: 18.00 PENALTY: 0.00 TOTAL PAID:18.00 Business Name: Owner Name: Mailing Address: SUN STAR ENERGY,L.L.C. MICHELLE APHOLZ PO BOX 29 STERLLNG, PA 18463 Receipt # 201103210015 Expires: September 30, 2012 Business Location: 723 FAIRWAY DR PLEASE DETACH THIS PORTION OF THE BUSINESS TAX RECEIPT FOR YOUR RECORDS r d ciitr- ajq -n!c X71 ',n dcc,n, cn»n MIAMI -DADE COUNTY DEPARTMENT OF PERMITTING, ENVIRONMENT AND REGULATORY AFFAIRS 11805 SW 26TH ST. SUITE 207 MIAMI FL, 3317= (786i 315 -2880 STATE CONTRACTOR'S CERTIFICATE OF VOLUNTARY REGISTRATION WITH MIAMI -DADE COUNTY ISSUED APRIL 25, 2012 THIS IS TO CERTIFY THAT SUN STAR ENERGY LLC CONTRACTOR CERTIFICATE NO.: CFC1428197 TRADE: PLUMBING REGISTRATION EXPIRATION DATE: 08/31/2012 HAVING MET THE REGISTRATION REQUIREMENTS CF MIAMI -DADE COUNTY, IS REGISTERED AS A STATE CONTRACTOR IN THE FOLLOWING CATEGORY (S): 0001 PLUMBING WITH ALL WORK TO BE DONE UNDER THE SUPERVISION, DIRECTION AND CONTROL OF QUALIFYING AGENT BOWEN JIMMY L S.S.N. - -8330 ALTERATION, REPRODUCTION OR TRANSFER OF THIS CERTIFICATE IS PROHIBITED. CHARLES DANGER, P.E. SECRETARY, CONSTRUCTION TRADES QUALIFYING BOARD SUN STAR ENERGY LLC 723 FAIRWAY DR NEW SMYRNA BEACH FL 32168 12 10.44e mtegia■Jtrali u 6,,J. BOWEN, ItiviMY L; Doing Business As SUN STAR ENERG.. luips:/. Www. m ynoridalicense.com/LicenseDetail .asp ?SIII?-r&id=311:.. '2 42.56 PM 2/29x4011 Licensee Details Licensee Information Name: Main Address: County: License Mailing: LicenseLocati on : License Information License Type: Rank: License Number: Status: Licensure Date: Expires: Special Qualifications Construction Busi ness 03/17/ 2010 Fingerprint (Construction Industry Licensing 09/15/2009 Board) BOWEN, 3IMMY L (Primary Name) SUN STAR ENERGY, L.L.C. (OBA Name) 723 FAIRWAY DR NEW SMYRNA BEACH Florida 32168 VOLUSI A Certified Plumbing Contractor Cert Plumbing CFC1428197 Current,Active 03/17/2010 08/31/2012 Qualification Effective View Related License Information View License Complaint c■ntact.Us 1949_!t9rSh.MQ�L! .StreeS.Jsi�lah�.siee.F) .3239$ :: C.aI .CentE.0 QbRC.sS? fi.us :: C,;s :o'ner Contact Cent:: 4-3' :?9E Thu! 7'.ace C` FIC, dd S c, c ., y V OvCr C,opyr,ght.?pZ—.2010 St,.1te, of FIQricia Pr: a.cy_S++ a_ am4^S Uruer FiC :NA +d':•_ e•;dresiea r e D.:•,aC •...on1f :! ,G " ,. .:"t ... e• '- i acid•-ass .leased •- response to a • p.10K•re;;Qni; i °7krest, e*" tone n•eii :^ drib ?':M1.. ,t`5[Qd� :: Act 're cff,ce 7, phone o: Oy traditional maJ t' you nave any %,es-Anns n:cwclr9 t R's AU4 '•.20 AC..:•; %Sb■ R'•, PI': LSO : ;iltaCt OVr'V• •lastee At webmaJ dbpr.st F . f 1 2.25i2011 12:45 P h' �'v,.n� �e,1o�y �l�,L cy,c+�9,cca� !�° CERTIFICATE— OF LIABILITY INSURANCE °6J1arz` 'o�z"' THIS CERTIFICATE IS ISSUED AS A MA t I ti3 OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUTHORIZED REPRESENTATIVE OR PRODUCER, AND THE CERTIFICATE HOLDER. ILMIPORTANT: if the cer8ficate holder is an ADDITIONAL INSURED, the pelf (wiles) must be endorsed. If SUBROGATION IS WAIVED, subject to the terns and. conditions of the policy, certain policies may require. an endorsement. A statement on this certificate does not confer rights. to the certificate holder in lieu of such endorsement(e)- PRODUCER Commercial Coverages Inc 1000 Pelican Bay Drive Daytona Beach, FL 32119 COp}TACT P1 386- 756 -8551 ; FAX Nor. 386- 756 -2344 � INSURER($) AFFORDING COVERAGE NAIC a INSURER A: CYPRESS PROPERTY & CASUALTY INSURER B : INSURED SUN STAR ENERGY LLC 723 FAIRWAY DR NEW SMYRNA BEACH, FL 32188 INSURER C 03/25/13 INSURER D: S 1000000 INSURER E : $ 100000 INSURER. F : - — van vr�nc -- mcyto V1Y iv t100OGPC THIS IS TO CERTIFY THAT THE POLICIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS. INNTSRR TYPE OF INSURANCE AODL JNSSR SUER w POLICY NUMBER POLICY EFF (NEWDD/YYYY) POLICY EXP (MWDD/YYYY) UMRS A GENERAL ✓ LIABILITY COMMERCIAL GENERAL LIABILITY GFL1017026 03/25/12 03/25/13 EACH OCCURRENCE S 1000000 PREMISES 1EaENo RENTED $ 100000 CLAIMS -MADE II 1 OCCUR MED EXP (Any«te person) $ 5000 PERSONAL & ADV INJURY GENERAL AGGREGATE $ 1000000 $ 2000000 GEM AGGREGATE LIMIT APPLIES PER. ✓ IPOLICY n n LOC PRODUCTS - COMP/OP AGO $ 2000000 AUTOMOBILE LIABILITY CCCOMBINEDISINGLE LIMIT $ ANY AUTO ALL OWNED AUTOS HIRED AUTOS SCHEDULED AUTOS NON-OWNED BODILY INJURY (Per person) $ BODILY INJURY (Per accident) I PROPERTY DAMAGE (Perarddent) $ $ UMBRELLA UAB EXCESS UAB — OCCUR CLAIMS -MADE EACH OCCURRENCE $ AGGREGATE $ DEO 1 1 RETENTION$ $ WORKERS COMPENSATION AND EMPLOYERS' UAWLITY Y / N ANY PROPRIETOR/ PARTNER/EXECUTIVE OFFICER/MEMBER EXCLUDED? ( I (Mandatory in NH) ttttyyeasa, DES(( RIP71 OF OPERATIONS lre1 ee N / A WC STATU• 1 OTH TORY LIMITS I ER E.L. EACH ACCIDENT $ E.L. DISEASE • EA EMPLOYEE` 5 E.L DISEASE -POLICY LIMIT $ DESCRIPTION OF OPERATIONS / LOCATIONS / VEHICLES (Attach ACORD 101, Additional Remarks Schedule, I more space H required) CFRTiE r TR tdrm r1Ca - • -L__. _ MIAMI SHORES VILLAGE BUILDING DEPARTMENT 10050 NE 2ND AVE MIAMI SHORES, FL 33138 SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION DATE THEREOF, NOTICE WELL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. AUTHORIZED REPRESENTATIVE ®1988 -2010 ACORD ACORD 25 (2010105) The ACORD narne and logo are registered marks of ACORD ORPORATION. All rights reserved. '4, °RO CERTIFICATE OF LIABILITY INSURANCE DATE 6115/24 2m THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER THE COVERAGE AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUTHORIZED REPRESENTATIVE OR PRODUCER, AND THE CERTIFICATE HOLDER. IMPORTANT: If the certificate holder Is an ADDITIONAL INSURED, the policy(ies) must be endorsed. If SUBROGATION IS WAIVED, subject to the tents and conditions of the policy, certain policies may require an endorsement. A statement on this certificate does not confer rights to the certificate holder In lieu of such endo = : �: , s). PRODUCER Agency Svc - Branch P 0 Box 469 Geneva FL 32732 `•T. Jim IIraeth (• C No Est): (407) 349 -9283 (AFC No): (800) 853 -6102 • E•DRES): jim.uraeth@apexco.aet INSURER(S) AFFORDING COVERAGE NAIC 0 INSURER A:Association Insurance Company naSURER6: 25496 INSURED Bun Star Energy LLC 723 Fairway Dr New Smyrna Beach FL 32168 ww1INSI s A wr•■ INSURER C : INSURERD: INSURER E: $ INSURER F $ • ■■■••■IV1l SWIM ENGR. THIS IS TO CERTIFY THAT THE POUCIES OF INSURANCE LISTED BELOW HAVE BEEN ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY BE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS. LLTTRR TYPE OF INSURANCE ADDL IPISR W.YD POLICY NUMBER POLICY EFF (MMM IDD/YYYY) POLICY IMP (MMIDD/YYYY) LIMITS GENERAL L.IABILITT COMMERCIAL GENERAL LIABILITY EACH OCCURRENCE $ DAMAGE $ ( RENTED PREMISES (Ea occurrence) $ CLAIMS -MADE OCCUR MED EXP (Any one pion) $ PERSONAL & ADV INJURY $ GENERAL AGGREGATE $ GEN1 AGGREGATE LIMIT APPLIES PER 7 POUCY PRO- JECT LOC PRODUCTS - COMP/OP AGG 5 AUTOMOBILE UABILITY ANY AUTO AUTOS OWNED HIRED AUTOS AUTOS SCHEDULED NON -OWNED AUTOS COMBINED SINGLE LIMIT (Ea accident) $ BODILY INJURY (Per person) $ BODILY INJURY (Per accident) $ PROPERTY DAMAGE (Per accident) $ $ UMBRELLA LUIS EXCESS LIAR — OCCUR CLAIMS -MADE EACH OCCURRENCE $ AGGREGATE $ DED RETENTION $ $ A WORKERS COMPENSATION AND EMPLOYERS' UAMILTY Y/N ANY PROPRIETOR/PARTNER/EXECUTIVE OFFICER/MEMBER EXCLUDED? (Mandatory In NH) ((y DESCRIPTION OF OPERATIONS below N / A WCV010349601 5/3/2012 5/3/2013 WC STATU- OTH- X TORY LIMITS ER EL. EACH ACCIDENT $ 100,000 E.L. DISEASE - EA EMPLOYEE $ 100, 000 EL. DISEASE - POUCY LIMIT $ 500,000 $ $ DESCRIPTION OF OPERATIONS / LOCATIONS / VEHICLES (Attach ACORD 101, Additional Remarks Schedule, If more apace Is required) r•CBT1cer•A•C Lane nen CANCELLATION Miami Shores Village Building Department 10050 NE 2nd Avenue Miami Shores FL 33138 SHOULD ANY OF THE ABOVE DESCRIBED POLICIES BE CANCELLED BEFORE THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN ACCORDANCE WITH THE POUCY PROVISIONS. AUTHORIZED REPRESENTATIVE ACORD 25 (2010/05) © 1988-2010 ACORD CORPORATION. All rights reserved. The ACORD name and logo are registered marks of ACORD Page 1 of 1 Permit No: 12 -1188 Job Name: June 29, 2012 Miami Shores Village Building Department Building Critique Sheet 10050 N.E.2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 Page 1 of 1 1) The plan that shows the location of the roof mounted equipment is unreadable. Provide a legible copy. 2) The plans submitted are not legible. The notes and print are too small. Provide plats in a sufficient size to read. MD Ord 8-10 Plan review is not complete, when all items above are corrected, we will do a complete plan review. If any sheets are voided, remove them from the plans and replace with new revised sheets and include one set of voided sheets in the re- submittal drawings. Norman Bruhn CBO 305 - 762 -4859 Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 Date: Date: Permit #: (2 /ter Planning & Zoning Critique Sheet s " ae-4; Review Completed by: David A. Dacquisto Miami Shores Viiiage Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 Solar Installation Requirements Check type of Solar System to be installed: ❑ Solar Thermal ❑ Solar Electrical ❑ Solar Hybrid Required Inspections: Required Inspections: Required Inspections: PLumbing Solar Final Electrical Solar Rough Electrical Solar Rough Electrical Solar Final Electrical Solar Final Electrical Solar Final Structural Solar Final Structural Solar Final PLumbing Solar Final Structural Solar Final Owner Notification: Installation of roof mounted photovoltaic or solar support systems typically require roof system Penetrations to allow attachment to the structure which may create additional long -term roof system maintenance requirements and /or jeopardize roof system manufacturer's warranties. Roof mounted solar systems generally required removal and reinstallation of solar panels /arrays in order to perform routine roof system maintenance, repair or replacement. I hereby acknowledge that I have read and understand the above notification on this day of °7 / , 20 Print owner name " Y\ 11-C Owner signat Property address S w 1 Permit # Notary stamp Print Notary , Miami Shores, FL moll THOMAS Nonry Public • State of Florida My Comm. Expires May 31, 2016 Commission # EE 203923 Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795 -2204 Fax: (305)756 -8972 Inspection Number: INSP - 175232 Permit Number: RC -6 -12 -1189 Scheduled Inspection Date: August 13, 2012 Inspector: Bruhn, Norman Owner: ARFELD, MARTA Job Address: 55 NW 102 Street Miami Shores, FL Project: <NONE> Contractor: SUN STAR ENERGY LLC Permit Type: Residential Construction Inspection Type: Final Work Classification: Solar Phone Number Parcel Number 1131010180090 Phone: (561)287 -1118 Building Department Comments SOLAR WATER HEATER INSTALLATION ON ROOF IN REAR Failed Correction Needed Re- Inspection Fee No Additional Inspections can be scheduled until re- inspection fee is paid. Inspector Comments August 10, 2012 For Inspections please call: (305)762 -4949 Page 11 of 48 Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972 INSPECTION'S PHONE NUMBER: (305) 762.4949 BUILDING PERMIT APPLICATION RECEIVED JUN 282012 FBC 2010 Permit No. i2C-- l '� I Master Permit No. FLA 2 I 1 Kr Permit Type: BUILDING ROOFING JOB ADDRESS: 5 N IN l C3 `_ r• A-1-' t �- City: Miami Shores County: Folio/Parcel #: 1 1- 3 1 b 1 - 01S 0 Miami Dade Zip: 3 3 , s Is the Building Historically Designated: Yes NO Flood Zone: OWNER: Name (Fee Simple Titleholder): m r4.11-4-6‘ A °V I- Phone #: 3 ixse 3i- Address: 6 2,.c S ez_ City: Prl e^ W" = C l^ 04 a 5 State: 1^ I 0- Zip: 33 r fC) Tenant/Lessee Name: Phone #: Email: CONTRACTOR: Company Name: .S v a'1 Cr- v-`N- ..,,-.0 <g y LL-C._ Phone #: 5-6) -1.-10 1 / j g Address: 11;3 1 City: N e W cmy rt Iva. % re...... c-e__-- State: 1 ®'>- ` a" c, Zip: 31-1 t `b Qualifier Name: --J ° " ° v"` `( PB 0 l-✓ aI Phone #: 56.1 - 2 $7 -/) / y State Certification or Registration #: C C-- 1 4-11-5r1 C) 7 Certificate of Competency #: Contact Phone #: 51, 1 " Z S7 _ 1 1 1 ii Email Address: SI, In S÷- c,✓ i v.. e s9/ t-1,C a- e'vr+ c-' 1 . C 0311 DESIGNER: Architect/Engineer: Phone #: 500.00 m000tt opoi 13 iC�f�rl 0i ( � 013k? e. eration ew `'*M OPair/Rep1a C/IIDemoliittio_ nn q�� to.) I WyJti 2 Color thru tile: ********* ******** * * * * * * * * * * * * * * ** *Fees * * * * *.. x�x **** *** ** * ** �********* * ****** * * * *** Submittal Fee $ Permit Fee $ ' CCF $ CO /CC $ Scanning Fee $ Radon Fee $ Notary $ Training/Education Fee $ Double Fee $ Structural Review $ DBPR $ Bond $ Technology Fee $ TOTAL FEE NOW DUE $ 44 (oc Bonding Company's Name (if applicable) Bonding Company's Address City State Zip Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, HEATERS, TANKS and AIR CONDITIONERS, ETC OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will not be approved and a reinspection fee will be charged. Owner or Agent The foregoing instrument was acknowledged before me this 414- day of---1 ufue- , 20 L, by 1 who is personally known to me or who has produced TriPL NOTARY PUBLIC: As identification and who did take an oath. Sign: Pri My Commission Expire My COMM Expires May 31, 2016 4 � •,# Commission # EE 203923 Signature Contractor The foregoing instrument was acknowledged before me this it4k day of —1 U r%Q , 20 31-, by J rv' 3 o t.�'✓l , who is personally known to me or who has produced b � as identification and who did take an oath. NOTARY PUBLIC: Sign: PrintD0 My Commissi ***************************************************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** APPROVED BY tofFfJ Plans Examiner Structural Review (Revised 3 /12/2012)(Revised 07 /10 /07)(Revised 06 /10/2009)(Revised 3/15/09) Zoning Clerk • SCOPE OF WORK: I DESIGNED PER: INSTALLATION OF A SOLAR WATER HEATING ASCE 7 -10 SYSTEM WITH A ROOF TOP COLLECTOR The LeverEdge DOMESTIC HOT WATER (DHW) INSTALLATION NOTES: WIND LOAD: WIND: RISK CATEGORY II DESIGNED FOR 200 MPH EXPOSURE CATEGORY D GENERAL: THIS DRAWING AND THE SPECIFICATIONS HEREON ESTABLISH THE MINIMUM REQUIREMENTS FOR DHW EQUIPMENT ON BUILDINGS IN FLORIDA 60 FEET OR LESS IN HEIGHT AND AT ROOF ANGLES FROM FLAT UP TO 45 DEGREES. PER THIS PARTICULAR INSTALIATION DOCUMENT, The LeverEdge DHW SOLAR PANELS MAYBE INSTALLED PARALLEL TO THE ROOF PLANE WITH HOLD DOWNS FLUSH ON TOP OF THE UPPER SURFACE OF THE ROOF COVERING OR TILTED -UP TO ACHIEVE BETTER SOLAR COLLECTION. FLUSH -MOUNT SHALL REQUIRE 4- ANCHORS' (3/8 -INCH DIAMETER CRS, CORROSION RESISTANT STEEL) IN PZ -1 & PZ -2, EXPOSURES B ,C, D IN AU. WIND ZONES UP TO AND INCLUDING 200 MPH. 'ANCHORS CAN EITHER BE, AT CONTRACTORS CHOICE, 4• ANCHORS FOR ASINGLE COLLECTOR OR 4- ANCHORS FOR TWO COLIECTORSTHRU USE OF APPROVED RACKING TO TIE THE TWO COLLECTORS TOGETHER -SEE FIGURE 2 TILT-UP IS PERMITTED ONLY WITH THE FOLLOWING STIPULATIONS: A) NO INSTALLATIONS OUTSIDE OF PRESSURE ZONE 1; e1 USE ONLY OEM HARDWARE- EXCEPT BI4TEK5 PER FIGURE 2: C) COLLECTOR LONG AXIS HORIZONTAL AND 30 DEGREES MAXIMUM TILT ANGLE: D) WIND ZONE 140 MPH AND LESS REQUIRE 4- ANCHORS PER TILT -UP COLLECTOR: 1) WIND ZONES GREATER THAN 140 MPH REQUIRE 6 ANCHORS PER TILT -UP COLLECTOR AND MINIMUM TILT POLE WALL THICKNESS OF WITH-INCH. CONTRACTOR SHALL KEEP LAG BOLT LOADING TO UNDER 528 POUNDS OF UPLIFT. REFER TO WIND LOAD CALCULATIONS AT HTTP:// WVIVJ. CADNCE .US /SWAVWDLOAOCALCULATIONSPDF WHEN LAG OMIT IS EXCEEDED CONTRACTOR SHALL USE MORE LAGS, }BOLTS OR ALL- THREAD ROD. FOUR I-BOLTS OR ALL- THREAD ROCS CAN HANDLE THE LOAD OF 2 -EACH, 405F SOLAR COLLECTORS IN ALL LOADING CASES ON THE CHART. WHEN STRAYING INTO P22, INCREASE ANCHORS 50% ON THE PORTION OF THE COLLECTOR IN PZ2. ABSOLUTELY NO INSTALLATIONS IN PZ3. TESTING: The LeverEdge DHW COLLECTORS HAVE PASSED MIAMI TESTING LABS WIND LOAD TESTING OF -202 PSF PER ASTM 1330 (MTL FILE NUMBER 95- 1249).THIS ENGINEER HAS EVALUATED THE INSTALLATION COMPONENTS AND HARDWARE CURRENTLY PROVIDED BY The LevePEdge AS OEM INSTALLATION KITS AND FOUND THEM TO MEET THE REQUIREMENTS OF THE FLORIDA BUILDING CODE CURRENT AS OF THE DATE OF THIS PLAN. THERE SHALL BE NO SUBSTITUTION OF OTHER VENDOR MATERIALS WITHOUT PRIOR APPROVAL OF THIS ENGINEER THRU The LeverEdge. HARDWARE THIS ENGINEER HAS DETERMINED THAT THE HOIIFW WN HARDWARE AND FASTENERS SUPPUED BY The Leve:Edge WILL WITHSTAND HURRICANE FORCE WINDS LIP TO AND INCLUDING 200 MPH 3- SECOND GUSTS. THE ONLY REMAINING VARIABLE OF SIGNIFICANCE IS THE ATTACHMENT OF THE HOLD DOWNS TO THE UNDERLYING ROOF S05CM USING OEM HARDWARE LAGGING OF TLE DHW COLLECTORS FOR FLUSH MOUNT INSTALLATION (PARALLEL WITH THE ROOF SURFACE AND AS CLOSE THERETO AS PERMITTED BY OEM HARDWARE SHALL BE ALLOWED IN EXPOSURE CATEGORY B AND C AND IN BOTH PZ1 AND P22 AT MEAN ROOF HEIGHTS OF GO-FT OR LESS AND IN ALL WIND ZONES THRU 200 MPH SO LONG AS THE FOLLOWING CAUTIONARY RULES ARE OBSERVED. LAGS SHALL BE CORROSION RESISTANT STEEL, 3/g INCH DIAMETER MINIMUM OR BETTER. LAGSSHALLACHIEVE AT LEAST 3- INCHES OF THREAD EMBEDMENT IN RAFTER OR5(,OCKING., MEASUREMENTS MUST BE CAREFULLY MADE AND PILOT HOLES SHALL BE DRILLED TO ENSURE HITTING IM,ERLYING RAFTERS OR TRUSSES AND TO AVOID WOOD SPLITTING. SPECIAL PROCEDURES TO USE WHEN, IN THE INSTALLER'S OPINION, HITTING THE CENTER OF TRUSS OR RAFTER WITH A LAG CANNOT BE ASSURED. EITHER USE A 3/8 INCH ( MIN) Y.P. BOLT GRABBING THE TRUSS /RAFTER OR ER INCH DIAMETER (MIN( ALL THREAD ROD PLUS STANDARD FENDER & LOCK WASHERS AND NUT THRU MINIMUM 4° BY 4. BY 9° BLOCKING ON THE UNDERSIDE OF THE ROOF SHEETING. WHERE BLOCKING METHOD IS USED, INSTALLER SHALL APPLY A GENEROUS BEAD OF CONSTRUCTION ADHESIVE FOR MIMMUMOF I FT ALONG THE NEAR JOINTS OF THE ROOF TRUSS AND SHEETING ON EACH TRUSS ON BOTH SIDES OF THE BLOCKING -SEE FIGURE 2 ON THIS SHEET. PLUMBING SHALL BE PER FIGURE 1. FLORIDA PLUMBING CODE SHAD. BE ADHERED TO: PARTICULAR ATTENTION GIVEN TO PROTECTION AGAINST OVER - PRESSURE AND FREEZING • PER FLORIDA MECHANICAL CODE, CHAPTER 14, ANTI PER The LeverEdge INSTALLATION INSTRUCTIONS. THIS DRAWING SHOWS THE 1131 VERSION PLUMBING. HOWEVER THERE ARE OTHER VARIANTS ( PHOTO - VOLTAIC PUMP, INDIRECT, AND/OR DRAIN -BACK( WHICH, ALTHOUGH NITS' 5 ONLY SHOWN HEREON, ARE COVERED BY THIS SEALED DRAWING -SO LONG AS INSTALLED PER The AverEdge WATERPROOFING INSTALLER SHALL ADHERE TO REQUIREMENTS OF FBC CHAPTER 15 (ROO NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE THAT THE SOLAR INSTALLATION INITIAL INSTALLATION OR AS THE SYSTEM AGES'. QUESTIONS: INSTALLERS, AUTHORITIES HAVING JURISDICTION, OR OTHERS MAY CONTACT THIS ENGINEER DIRECTLY -CELL' 813 650 7246, E -MAIL' AU. fl SOLAR SYSTEM COLLECTOR: 1 APPLICABLE CODE: MODEL: AE-21 /AE-24/A1-261A1-211/AE-32/AE-40/ MSC21 / MSC-32 7 MSC.O/SHC- 21 7SHC- 32/000.40 2010 FLORIDA BUILDING CODE VOID WITHOUT RAISED OR ELECTRONIC SEAL, MAY NOT BE USED FOR PLANS ON FILE, EVERY PERMIT PULLED REQUIRES A SEALED ELECTRONIC PLAN OR SEALED ORIGINAL PAPER COPY OF THIS PLAN SOLAR UNIT (THERMAL OR PV) WIND FORCES SOLAR UNITS INSTALLED PER THIS PLAN SHALL NOT FARM PART OF THE GUIDING ENVELOPE UKEA WINDOW, DOOR SOUGHT, OR BIPV. SOLAR UNITS SHALL BE MOUNTED ABOVE ROOF SURFACE UKE AN AC CONDENSER THEREFORE, SOLAR UNITS THUS INSTALLED DO NOT REQUIRE A PRESSURE RATING AS DO ENVELOPE COMPONENTS SUCH AS WINDOWS, DOORS, & SKYUGHTS. SOLAR UNITS SHALL BE MOUNTED VERY CLOSE TO THE ROOF SURFACE THIS PROVIDES PRESSURE EQUALIZATION BETWEEN THE ROOF SURFACE AND THE BACK OF THE SOLAR UNITS. TH6 RESULTS IN NO SIGNIFICANT CHANGE IN THE LOADS ON THE 000F FRAMING FORA PARALLEL MOUNT AND MODEST CHANGES IF TILT UP. HOWEVER THE INTERNAL AND EXTERNAL COMPONENTS OF WIND PRESSURE DECOUPLE, E.G. THE ROOF RESETS THE INTERNAL WIND PRESSURES AND THE SOLAR UNITS RESIST THE EXTERNAL WIND PRESSURES THE EXTERNAL WIND FORCES ARE THEN TRANSFERRED TO THE ROOF FRAMING THAUTHE SOLAR ATTACHMENT HARDWARE WIND CALCULATIONS UM( HERE: HTTP:// WWW .GEZELMANPECOM /GENERIC/2010FBC WINDCALCSHTM GENRAL NOTE: ALL HOT WATER SOLAR COLLECTORS SOLD IN THIS STATE ARE REQUIRED TO HAVE BEEN TESTED BY THE FLORIDA SOLAR ENERGY CENTER AND BEAR ITS CERTIFICATION LABEL THE COLLECTORS LISTED MINIS PLAN COMPLY WITH THOSE REQUIREMENTS. FURTHER INFORMATION MAY BE Arr'FCSED ON LINE AT: HTTP:/ /WWW.FSEC.UCF.EDU /EN/ INDUSTRY /TESTING /STCOLLECTORS/HOT WATER_RATINGS/INDEX.HTM NO PZ3 IN HVHZ COLLECTOR I el CERTIFY THAT THIS DESIGN& SPECIFICATIONS MEET THE REQUIREMENTS OF THE CURRENT FLORIDA BUILDING CODE. ALLEN GEZELMAN 16502 HANNA RD. LU(Z. FLORIDA 33549 PH. 613 650 7246 ABeW88000eImen PE.COM WS W.Ge0eIma,PEAO,R RAISED OR ELECTRONIC SEAL g ROOF ROOF TRUSS FRONT ELEVATION TWO COLLECTORS MAY BE MOUNTED ON 1.251ALUM ANGLE ATTACHED TO BOTTOM FRAME WALL SPANNING BOTH COLLECTORS AND SINGLE SET OF OEM HARDWARE EXISTING ROOF TRUSS, TOP CHORD 1 DIA. SPACER W/ WATERPROOF SEALANT OEM HOLD DOWN. LAGGING ?GRIMM OVER TRUSS; MP LAG BOLT OR J- BOLT (HOOKS TRUSS) NOTICE TO AHJ, CONTRACTOR, OWNER, & OTHER ENGINEER - SEALED DETAILS &SPECIFICATIONS FOR INSTALLATION OF BOTH DOMESTIC HOT WAFER SYSTEMS. AE& E MADE IN THE SAME PIANT SUGHT PHYSICAL DIFFERENCES, THESE EQUIVALENT STRUCTU SHOWN ON THIS PIAN SHEET, BECAUSE AE °LANE LEADER MSC -TYP. SHINGLE, MET, FLAT TILE DETAIL. 1/2. rc 1'DIABPACER, LENGTH ADJUST FLUSH W/ TOP OF TILE PROVED `ISTEMWs UT M. SPA UST FL SF'+W /T YPIOF TILE IA SPA ERI NATERPRO0F_SE T (OLP):THIS PLAN PROVIDES STAR CORPORATION (MSC) `- ...- UFACEURIRWHIIETHEREARE ... Y, & THERMALLY. AE DETAILS' AT: P'1/ aermlarmm/ WHERE APPLICABLE FILL CAVITY UNDER TILE W/ EXPANSION CONST. FOAM EXISTING ROOF TRUSS, k" TOP CHORD ALL AFFIDAVITS, DESIGNS. OPINIONS. CALCULA GEZELMAN PE AND HIS ASSOCIATES ON ANY AND ALL (ENGINEERS JOINT CONSTRUCTION DOCUMENT CO CONSTRUCTION CONTRACT) CURRENT AT THE THEE THEREOF ARE DIRECTED NOT TO USE THE AFFIDAVIT, D SERVICE OFFERED SY ALLEN GEZELMAN PE AND HIS ASSOCIA HTTP.I/ GEZELMANPE .COWREFERENCE/AGIC•700PDF ALL THREAD ROD, J BOLT OR LAG MOUNTING BRACKET ALUM. TU01 FILL Wi 1 -PART POURABLE WATERPROOF CONSTRUCTION SEALANT 0' DIRECT'D'SYSTEM THIS DRAWING SHOWSTheLeverEdge DHW 10' (DIRECT) SYSTEM AND MIS PARTICULARSYSTFM'S PLUMBING. THEREAREOMER SLIGHTLY DIFFERENT, The Lere:EdgeDHW SYSTEM VARIANTS WHICH ARE ALSO COVERED BYTHS SFAIF0 DRAWING. THIS ISBECA SETHECNRCALELEMENT— THECOUECIONS)AND ROOF MOUNTING DETAILS REMAIN THE SAME WHETHER The LeverEdge. DHW SYSTEM BEINGINSTALIED SA DIRECT, IN- DIRECT OR DRAIN-BACK MODELS WHICH CAN RECONFIGURED WIRIETHER AN A/COR PHOTO - VOLTAIC PUMP ORD /C CONTROLLED ELECTRIC PUMP f COLLECTOR SENSOR • 4 SOLAR LOOP DRAT MOTORIZED BALL VAL SOLAR LOOP EN IS OLATION VALVE EXPANSION TANK DIFFERENTIAL CONTROL HOT WATER OUTLET COLD WATER INLET SHUT OFF VALVE BACKUP ELECTRIC ELEMENT DIP TUBE STORAGE T TANK SENSO TANK DRAIN o 01 FIGURE 1 Rpm F CUTS LEDGEND flO.AIJ0N VALVE(OPRONAU. Z1A TAN(8L4R.Y SHUTOFF L SOLAR LOOP DRAM (OPIIDNAU Q1 FREEZE PROTECTION VAX (MORAL) 4'.4cF TEMPERATURE/PRESSLIE TEMP VALVE PFESSUE RELIEF VALVE EI AIR *NT (OPRONAU S «� MOTOR BALL. VALVE 0 EECTRO PIA.P AC/13C U FXPAN&ON TAW (OPTIONAL./ AW MTUBE ALUM TUBE PITCH PAN TILE ROOF: CUT OUT RECTANGLE FOR PITCH PAN, INSTALL AND FILL W/ 1 -PART POURABLE WATER PROOF CONSTRUCTION SEALANT ALUM TUBE PITCH PAN ALL THREAD POD, J BOLT OR LAG ALTERNATE. TILE ROOF MOUNTING DETAIL SCAIE:a'. 1'0' oz FIGURE 2 BCNEYN4E8 EXPLANATORY INFORMATION ENLARGED VIEWING & HYPERUNKS: PRINT VERSION OF THIS PLAN PROVIDES MINIMUM INFORMATION NEEDED BY USERS. ELECTRONIC VERSION (EV) PROVIDES MAGNIFIED VIEWING UP TO 6400%. EV ALSO PROVIDES IHYPERUNK ACCESS TO OEM MANUALS AND ABUNDANT OTHER SUPPLEMENTARY INFORMATION. EV MAY BE ACCESSED AT HTTP:// WWW. GEZELMANPE .COM /GENERIC/AS.L3.WH- I0.PDF THERE ARE THREE PROPRIETARY RACK SYSTEMS APPROVED FOR USE WITHTHM PLAN. THESE MAYBE USED TO SUPPLEMENT OR TO REPIACETHE DETAILS SHOWN IN FIGURE E. IN ALL CASES REFER TO OEM INSTRUCTIONSFOR DETAILS/SYSTEM BEING USED. IN THE EVENT OF A CONFLICT BETWEEN OEM INSTRUCTIONS AND THIS PLAN, OEM INSTRUCTIONS SHALL PREVAIL OEM MANUALS MAYBE ACCESSED ELECTRONICALLY USING THE FOLLOWING HYPERUNKS: HTTP //W W W.UNISTRUT.COM/ LITERATURE /INOEXPHP700C=N014&P05l HTTP:j /WWWJRONWDGECOM /FILES /XRS /IRONNDGE XRS_2 RAIL SYSTEM.POF HTTP1/ /W W W.UNIRAC COM/POF /11227.POF STRUCTURAL LOADING: THIS PLAN WAS ENGINEERED FOR THE ENTIRE STATE OF FLORIDA INCLUDING HVHZ THE SOLAR EQUIPMENT REPRESENTED ON THIS PLAN IMPOSES A POSITIVE LOAD UPON THE ROOF STRUCTURE OF LESS THAN APSE. MY UPLIFT PRESSURE CALCULATIONS MAY ILE VIEWED AT: HTTP //W W W. GEZELMANPE .COM /GENERIC/2A10FBC_W INDCALCS.HTM QUESTIONS REGARDING ROOF PRESSURE ZONES ARE REFERRED TO THE A5CE 20 DIAGRAM FOUND ON PAGE 5 AT TF'E ABOVE UNIRACIHYPENWNE °FIGURE 3 03 „wNTa t TYP. BARREL TILE ROOF MOUNTING DETAIL 00511: t -IT'. 144 APPLY CONSTR. ADHESIVE MEDIUM BEAD BOTH SIDES OF INTERFACE BETWEEN ROOF SHEETING AND TRUSS 1 FOOT IN EACH DIRECTION STARTING FROM 'SPANNER' TO WHICH COLLECTOR MOUNT FOOT -PAD IS SECURED BY ALL - THREAD ROD. EXISTING ROOF fan IN. M011NTQ. Q CTOR M UJ CTR R ET OEM HOLLDOWN: —"' LAGGING ( POSITION OVER TRUSS) J - BOLT (HOOKS 7RUSS) B1OCKING (BETWEEN TRUSSES) SEALANT FOR WATERPROOFING ttega 404 BETWEEN TRUSSES IN CONTACT WI PLYWOOD '-1YP. BEAD OF CONSTR. EXISTING ROOF TRUSS, TOP CHORD NOTE -THERE SHALL BE AT LEAST 4 HOLD -DOWN ATTACHMENTS FOR EACH SOLAR COLLECTOR ON A ROOF. TYP. MOUNTING DETAIL SCAM 1-712. MOUNTING BRACKETS HINGE MOUNT CLIP 3181 -16 FINISHED HDC NUT 101X0 .072' ALUMINUM SQUARE TUBE TILT KIT - DECK ANCHOR EM FURNISHED FASTENER 1/4' -20 X 1/2' HEX CAP SCREW 3/8-•16 X 4' HEX CAP SCREW 3581 -16 X 1 -314' HEX CAP SCREW TRIANGULAR MOUNTING BRACKET TRUSS °FIGURE 2 oz i j 0- 1 dv . ic B lc e . us ConEOCk cN]Vi4e 36Q3 EReee Or ��97PH. 8739i454 E4 8!6444 7257 ukw''ww.'vl08tp%W WM4�v7L91G w o < LL w 00 I 0 LLw Z Ct VJ O '-21 "11. P118USHED:04A19712 70255 PM THIS IS A SINGLE SHEETPLAN SHEET NAME: PERMIT SET DRAWN: SR CHECKED:AG SHEET NO: A.1.3 -10 COPY RIGHT & INTELLECTUAL PROPERTY NOTICE U 5g (scoPE OF WORK: NSTALLATION OF A SOLAR WATER HEATING YSTEM WITH A ROOF TOP COLLECTOR 1 DESIGNED PER: ASCE 7 -10 WIND LOAD: DESIGNED FOR 200 MPH I EXPOSURE CATEGORY D WIND: RISK CATEGORY I1 The LeverEdge DOMESTIC HOT WATER (DHW) INSTALLATION NOTES: GENERAL( THIS DRAWING AND THE SPECIFICATIONS HEREON ESTABUSH THE MINIMUM REQUIREMENTS FOR 011W EQUIPMENT ON BUILDINGS IN FLORIDA 60 FEET OR LESS IN HEIGHT AND AT ROOF ANGLES FROM FIAT UP T045 DEGREES. PER THIS PARTICULAR INSTALLATION DOCUMENT, TM 100001dge DHW SOLAR PANELS MAY BE INSTALLED PARALLEL TO THE ROOF PLANE WITH HOLD DOWNS FLUSH ON TOP OF THE UPPER SURFACE OF THE ROOF COVERING OR TILTED -UP TO ACHIEVE BETTER SOLAR COLLECTION. FLUSH -MOUNT SHALL REQUIRE 4- ANCHORS" (3/8 -INCH DIAMETER CRS, CORROSION RESISTANT STEEL) IN PZ -1 & PZ -2, EXPOSURES 0 ,C, DIN AU. WIND ZONES UP TO AND INCLUDING 200 MPH. 'ANCHORS CAN EITHER BE, AT CONTRACTORS' CHOICE, 4- ANCHORS FOR ASNGLE COLLECTOR OR 4-ANCHORS FOR TWO COLLECT0115111RU USE OF APPROVED RAOFNG TO TIE ME TWO COLLECTORS TOGETHER -SEE FIGURE 2 TILT -UP IS PERMITTED ONLY WITH THE FOLLOWING STIPULATIONS: A} NO INSTALLATIONS OUTSIDE OF PRESSURE ZONE 1; B) USE ONLY OEM HARDWARE- EXCEPT 814 TERS PER ARE 22• CI COLLECTOR LONG AXIS HORIZONTAL AND 30 DEGREES MAXIMUM TILT ANGLE D) WIND ZONE 140 MPH AND LESS REQUIRE 4- ANCHORS PER TILT -UP COLLECTOR 1) WIND ZONES GREATER THAN 140 MPH REQUIRE 6 ANCHORS PER TILT -UP COLLECTOR AND MINIMUM TBT POLE WALL THICKNESS OF 1/3TH -INCH. CONTRACTOR SHALL KEEP LAG BOLT LOADING TO UNDER 528 POUNDS OF UPLIFT. REFER TO WIND LOAD CALCULATIONS AT HTTPWAVWW. CAONCE .US /SW/NANDLOADCALCULATIONS.PDF WHEN LAG UMIT IS EXCEEDED CONTRACTOR SHALL USE MORE LAGS,1- BOLTS OR ALL - THREAD ROD. FOUR 1- 301150R ALL- THREAD RODS CAN HANDLE THE LOAD OF 2 -EACH, 405E SOLAR COLLECTORS IN ALL LOADING CASES ON THE CHART. WHEN STRAYING INTO 072, INCREASE ANCHORS 50%ON THE PORTION OF THE COLLECTOR IN PZ2. ABSOLUTELY NO INSTALLATIONS IN PM. TE51104, The LeverEdge DHW COLLECTORS HAVE PASSED MIAMITESTNG IARS WINO LOAD TESTING OF- 10205F PER ASTM 0 -330 (MR FILE NUMBER 95- 1249).THIS ENGINEER HAS EVALUATED THE INSTALLATION COMPONENTS AND HARDWARE CURRENTLY PROVIDED BY The LeverEdge AS OEM INSTALLATION KITS AND FOUND THEM TO MEET THE REQUIREMENTS OF THE FLORIDA BUILDING CODE CURRENT AS OF THE DATE OFTHILS PLAN. THERE 5HVR1 BE NO SUBSTITUTION OF OTHER VENDOR MATERIALS WITHOUT PRIOR APPROVAL OF THIS ENGINEER 71-MU The Levet-Edge. HARDWARE THIS ENGINEER HAS DETERMINED THAT THE HOLD -DOWN HARDWARE AND FASTENERS SUPPLIED BY The 1.003Wdge WILL WITHSTAND HURRICANE FORCE WINOS HP TO AND INCLUDING 200 MPH 3- SECOND GUSTS. THE ONLY REMAINING VARIABLE OF SIGNIFICANCE IS THE ATTACHMENT OF THE HOLD DOWNS TO THE UNDERLYING ROOF SYSTEM USING OEM HARDWARE. LAGGING OF TILE DHW COLLECTORS FOR FLUSH MOUNT INSTALLATION (PARALLEL WITH THE ROOF SURFACE AND AS CLOSE THERETO AS PERMITTED BY OEM HARDWARE) SHALL BE ALLOWED IN EXPOSURE CATEGORY a AND C AND IN BOTH P21 AND PZ2 AT MEAN ROOF HEIGHTS OF 60-FT OR LESS AND IN ALL WIND ZONES THRU 200 MPH SO LONG AS THE FOLLOWING CAUTIONARY RULES ARE OBSERVED. LAGS SHALL BE CORROSION RESISTANT STEEL, 3/B INCH DIAMETER MINIMUM OR BETTER LAGS SHALL ACHIEVE AT LEAST 3- INCHES OF THREAD EMBEDMENT IN RAFTER OR BLOCKING, MEASUREMENTS MUST BE CAREFULLY MADE AND PILOT HOLES SHALL BE DRILLED TO ENSURE HITTING UNDERLYING RAFTERS OR TRUSSES AND TO AVOID WOOD SAUTEING. 5PF0A, PROCEDURES TO USE WHEN, IN THE INSTALLER'S OPINION, HITTING THE CENTER OF TRUSS OR RAFTER WITH IAG CANNOT BE ASSURED. EITHER USE A 3/8INCH (MIN) "J' BOLT GRABBING THE TRUSS /RAFTER OR 3/B INCH DIAMETER (MIN) ALL THREAD ROD PLUS STANDARD FENDER & LOCK WASHERS AND NUT 'MU MINIMUM 4' BY 4' BY 3" BLOCKING ON THE UNDERAGE OF THE ROOF SHEETING. WHERE BLOCKING METHOD IS USED, INSTALLER SHALL APPLY A GENEROUS BEAD OF CONSTRUCTION ADHESIVE FOR MINIMUM OF I FT ALONG THE NEAR JOINTS OF THE ROOF TRUSS AND SHEETING ON EACH TRUSS ON 80TH SIDES OF THE BLOCKING -SEE FIGURE 2 ON THIS SHEET. PLUMBING SHALL BE PER FIGURE I. FLORIDA PLUMBING CODE SHALL BE ADHERED TO: PARTICULAR ATTENTION SHALL BE GIVEN TO PROTECTION AGAINST OVER - PRESSURE AND FREEZING -PER FLORIDA MECHANICAL CODE, CHAPTER 14, AND PER The LeverEdge INSTALLATION INSTRUCTIONS. MILS DRAWING SHOWS THE 13- VERSION PLUMBING. HOWEVER THERE ARE OTHER VARIANTS (PHOTO- VOLTAIC PUMP, INDIRECT, AND /OR DRAIN -BACKI WHICH, ALTHOUGH NOT SPECIFICALLY SHOWN HEREON, ARE COVERED BY THIS SEALED DRAWING 50 LONG AS INSTALLED PER The LeverEdge INSTALLATION INSTRUCTIONS. WATERPROOFING INSTALLER SHALL ADHERE TO REQMREMENTS OF FBC CHAPTER 15 (ROOFING) AND BEST PRACTICES OF THE NRCA ROOFING & WATERPROOFING MANUAL TO ENSURE THAT THE SOLAR INSTALLATION DOES NOT CAUSE ROOF LEAKS AT INITIAL INSTALLATION OR AS THE SYSTEM 'AGES'. QUESTIONS: INSTALLERS, AUTHORITIES HAVING JURISDICTION, OR OTHERS HAVING QUESTIONS OR DIFFERING CONDITIONS, MAY CONTACT THIS ENGINEER DIRECTLY -CELL( 813650 7246, E -MAIL• ALLEN@1GEZEIMANPE.COM NOTICE TO AHI,CONTRACCOR OWNER, &OTHER INTERESTED PARTIES )OIP):THISMAN PROVIDES ENGINEER - SEALED DETABS& SPECIFICATIONS FOR INSTALLATION OF BOTH AE& MORNING STAR CORPORATION (MSC) SOLAR DOMESTIC HOT WATER SYSTEMS AE & MSC ARE MADE IN THE SAME PIAM'BY 'ME SAME MANUFACTURER WHRETHEREARE SLIGHT PHYSICAL DIFFERENCES, THESE SYSTEMS ARE EQUWALENTSTRUCNRALLY, HYDRAUUCALIY, & THERMALLY. AE DETAILS ARE SHOWN ON THIS PLAN SHEET, BECAUSE AEISTHE VOLUME LEADER MSC DETAILS MAY BE VIEWED AT; http1 /www.aetRlar.mm/ ALL AFFIDAVITS, DESIGNS, OPINIONS, CALCULATIONS & OTHER ENGINEERING SERVICES PROVIDED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON ANY AND ALL PROJECTS ARE SUBJECT 10 THE PROVISIONS OF EJCDC C -700 (ENGINEERS JOINT CONSTRUCTION DOCUMENT COMMITTEE - STANDARD GENERAL CONDITIONS OF THE CONSTRUCTION CONTRACT) CURRENT AT THE TIME THOSE OBJECTING TO SAID EJCDC 0.700 OR PROVISIONS THEREOF ARE DIREUI M) NOT TO USE THE AFFIDAVIT, DESIGN, OPINION, CALCULATION OR OTHER ENGINEERING SERVICE OFFERED BY ALLEN GEZELMAN PE AND HIS ASSOCIATES ON THE PROJECT. EJCDC C-700 MAY BE VIEWED AT: HTTPAG IG70LMANPE .COFMREFERENCE/AGIC•700POF • DIRECT'D"SYYSSTEM ELM 0Aufw THIS DRAWING SHOWS The levarEdge DHW V" (DEMO) SYSTEM AND THIS PARTICULAR SYSIEM S PLUMBING. THEREARE OTHER, SUGHRYNFFEREN, The laverEdge DHW SYSTEM VARIANTS WHICH ARE AI50 COVERED BY IM SEALED DRAWING. THIS IS BECAUSE THE CRITICAL ELEMENT -THE COLLECTOR(S) AND ROOF MOUNTING DETAILS REMAIN THE SAME WHETHER The LsW r0dge. OH W SYSTEM BEING INSTALLED IS A DIRECT INDIRECT OR DRAIN -BACK MOOEISWHICH CAN BE CONFWUREDWITHEITHERANA /CDR PHOTO - VOLTAIC PUMP OR D/c CONTROLLED ELECTRIC PUMP 1 BACKUP ELECTRIC ELEMENT OIP TUBE STORAGE T FIGURE 1 SOLAR LOOP VEIN ISOLATION VALVE EXPANSION TANK DIFFERENTIAL CONTROL COLD WATER INLET SHUT OFF VALVE LEDGEND .LA ISOA1XXi VALVE (OPF(ONN1 TAN( SLEPLY SHUT OFF Gi7Tc SOLAR LOOP DRAIN (CPHONAL) '74 Fib Pfo1EC1i0N VALVE (OPTIONAL) "`•g • Taft:RATUREPSESSLRE RELEF VALVE PRESSUPE RMS.VALVE n AR VHVT(OPIIONAU 5.,.o MOTOFi® BALD. VALVE ELECTRIC PUMP ADO 0 EXPANSION TAM<(OPTIONAL) SOLAR SYSTEM COLLECTOR: 1 APPLICABLE CODE: MODEL: AE- 211AE- 24/AE- 261AE- 28IAE32JAE -00/ 5180211 MSC -321 MSC .0/SHC- 21/SHC.32/SHC-1D 2010 FLORIDA BUILDING CODE VOID WITHOUT RAISED OR ELECTRONIC SEAL, MAY NOT BE USED FOR PLANS ON FILE, EVERY PERMIT PULLED REQUIRES A SEALED ELECTRONIC PLAN OR SEALED ORIGINAL PAPER COPY OF THIS PLAN SOLAR UNIT (THERMAL OR PV) WIND FORCES SOWS UNITS INSTALLED AERIES PLAN SHALL NOT FORM PART OF THE GUIDING ENVELOPE UKE A WINDOW, DOOR SKYLIGHT, OR BIPV. SOLAR UNITS SHALL BE MOUNTED ABOVE ROOF SURFACE UKEAN AC CONDENSER. THEREFORE, SOLAR UNITS THUS INSTALLED 00 NOT REQUIRE A PRESSURE RATING AS 00 ENVELOPE COMPONENTS SUCH AS WINDOWS, DOORS, & SKY1GHTS. SOLAR UNITS SHALL BE MOUNTED VERY CLOSE TO THE ROOF SURFACE THIS PROVIDES PRESSURE EQUALIZATION BETWEEN THE ROOF SURFACE AND THE BACK OF THE 501AR UNITS. THIS RESULTS IN NO SIGNIFICANT CHANGE IN THE LOADS ON THE ROOF FRAMING FORA PARALLEL MOUNT AND MODEST CHANGES IF TILT UP. HOWEVER, THE INTERNAL AND EXTERNAL COMPONENTS OF WIND PRESSURE DEMURE, E.G. THE ROOF RESISTS THE INTERNAL W W D PRESSURES AND THE SOLAR UNITS RESIST THE EXTERNAL WIND PRESSURES. THE EXTERNAL WINO FORCES ARE THEN TRANSFERRED TO THE ROOF FRAMING THRU THE SOLAR ATTACHMENT HARDWARE. WIND CALCULATIONS LINK HERE H1TA.// WWW. GEZELMANPEC OM /GENERIC/2010FBC_WIND[ALCS.HTM GENRAL NOTE: ALL HOT WATER SOLAR COLLECTORS SOLD IN THIS STATE ARE REQUIRED TO HAVE BEEN TESTED BY THE FLORIDA SOLAR ENERGY CENTER AND BEAR ITS CERTIFICATION LABEL THE COLLECTORS LISTED ON THIS PLAN COMPLY WITH THOSE REQUIREMENTS FURTHER INFORMATION MAY BE ACCESSED ON LINE AT: HTTP: / /WWW.FSEC.UCF.EDUfEN/ INDUSTRY /TESTING /STCOLLECTORS /HOT WATER_RATINGS /INDEX.HTM COLLECTOR r I CERTIFY THAT THIS DESIGN & SPECIFICATIONS MEET THE REQUIREMENTS OF THE CURRENT FLORIDA BUILDING CODE ALLEN GEZELMAN 16502 HANNA RD. LW Z. FLORIDA 33549 PH. 813 650 7246 Ailen(g)GezaWan PE.COM www.GemImanPE.corn RAISED OR ELECTRONIC SEAL / `PE. FRONT ELEVATION = PRESSURE ZONE SECTION A = WIND ZONE m•Ai P.1AT 1LP J TWO COLLECTORS MAY BE MOUNTED ON 1.25' ALUM ANGLE ATTACHED TO BOTTOM FRAME WALL SPANNING BOTH COLLECTORS AND SINGLE SET OF OEM HARDWARE D 0GI N LAGGING I LAG OVER 3/8" LAG (HOOKS BOLT (HOOKS TRUSS) EXISTING ROOF TRUSS, TOP CHORD TYP. SHINGLE, MET, FLAT TILE DETAIL. SCALE. LVt =Td i'DIABPAE R, LENGTH ADJUST FLUSE W/TOP OF TIE EXIBTING MEMBRANE TILE ROOF: CUT OUT RECTANGLE FOR PITCH PAN, INSTALL AND FILL W/ 1 -PART POURABLE WATER PROOF CONSTRUCTION SEALANT ALTERNATE. TILE ROOF MOUNTING DETAIL SCALES' =,'A` ALUM. 1 WE FILL WI' -PART POURAE_E WATERPROOF CONSTRJCTION SEALANT ALUM 11180 PITCH 0143 ALL THREAD ROD. J BOLT OR LAG ()FIGURE 2 02 aF:VARIEB EXPLANATORY INFORMATION ENLARGED VIEWING & H001304KS: PRINT VERSION OF THIS PUN PROVIDES MINIMUM INFORMATION NEEDED BY USERS. ELECTRONIC VERSION (EN) PROVIDES MAGNIFIED VIEWING UP TO 6400%. EV ALSO PROVIDES HYPERUNK ACC'SS TO OEM MANUALS AND ABUNDANT OTHER SUPPLEMENTARY INFORMATION. EV MAY BE ACCESSED AT HTTP:/ IWWW. GEZELMANPECOM /GENEBICJASL3.WH- 10.PDF THERE ARE THREE PROPRIETARY RACE SYSTEMS APPROVED FOR USE WITH THIS PL/N. THESE MAYBE USED TO SUPPLEMENT OR TO REPLACE THE DETAILS SHOWN IN 1GURE 2. IN ALL CASES REFER TOOEM INSTRUCTIONS FOR DErAILS/.0STEM 8ENG USED. IN THE EVENT OF A CONFUCT BETWEEN OEM INSTRUCTIONS AND THIS PLAN, OEM INSTRUCTIONS SHALL PREVAIL OEM MANUALS MAY BE ACCESSED ELECTRONICALLY USING THE FOLLOWING HYPERUNKS: HTTPJj,W W.UN6RRUT.COM/ LITERATURE /INDEX.P3P?D0C N014&PG =1 HTTP:/( WWW. IRONRIDGECOM (FLLFS /XRS(IRONRIDGE_XRS_2 RAR_SYSTFM.POF HTTF:/ /W W W.UNIRAC.COM/POF/II227.POF STRUCTURAL LOADING: THIS PLAN WAS ENGINEERED FOR THE ENDRE STATE OF FLORIDA INCLUDING HYBL THE SOLAR EQUIPMENT REPRESENTED ON THIS PLAN IMPOSES A POSITIVE LOAD UPON THE ROOF STRUCTURE OF LESS THAN 4 -P5F. MY UPLIFT PRESSURE CALCULATIONS MAY BE VIEWED AT: HHTTPJ(W WW.GEZEUMNPE. CAM /GENERIC/2010F8C_WINOCALCS.HTM QUESTIONS REGARDING ROOF PRESSURE ZONES ARE REFERRED TO THE ASCE 10 DIAGRAM FOUND ON PAGE: AT THE ABOVE uNIRACHYPERLUN0, ()FIGURE 3 03 WHERE APPLICABLE FILL CAVITY UNDER TILE W/ EXPANSION CONST. FOAM EXISTING ROOF TRUSS, TOP CHORD TYP. BARREL TILE ROOF MOUNTING D SCALE WM. T-0' APPLY CONSTR ADHESIVE MEDIUM BEAD BOTH SIDES OF INTERFACE BETWEEN ROOF SHEETING AND TRUSS 1 FOOT IN EACH DIRECTION STARTING FROM 'SPANNER" TO WHICH COLLECTOR MOUNT FOOT -PAD IS SECURED BY ALL - THREAD ROD. NOTE -THERE SHAL TYP. MOUN SEALANT APPROVED RACKING SYSTEM W/ CHANNEL NUT 1' DIA. SPACER, LENGTH ADJUST FLUSH W/ TOP OF TILE 1 "DIA. SPACER / WATERPROOF SEALANT EXIST. BARREL TILE OEM HOLD DOWN: LAGGING (F OSRION OVER TRUSS 318" LAG BOLT OR J- SOLT (HOOKS TRUSS) N OVER TRUSS) O TTRUSSES) 30300 LNG LAR COLLECTOR ON A ROOF. MOUNTING BRACKETS SCALE NT.S. 3/8' -16 FINISHED HEX NUT 1 "z1 "30.072" ALUMINUM SQUARE TUBE T -LT KIT - DECK ANCHOR HINGE MOUNT CUP OEM FURNISHED FASTENER 1/4' -20 X 1/2' HEX CAP SCREW 3/8'- 16X4 "HEX CAP SCREW 3/6- -16 X 1 -3/4" HEX CAP SCREW TRIANGULAR MOUNTING BRACKET ()FIG()FIGURE 2 URE YAPoES Coate: EAdvice Iso 3603 E Rd4Nll'te Gr P1 813 9119 91554 EX. 866 694 7251 roAllgeAdvIcsAN k4.4•Is PUBLISHED:04/09 /12 7:02'50 PM THIS IS A SINGLE SHEET PLAN SHEET NAME: PERMIT SET DRAWN:513 CHECKED:AG SHEET NO: A.1.3 -10 IT #: ylArA -- Miami S cores Village FSEC # S9022 Approved Solar Ener DISTRIBUTOR DIY$ 041. i1P .IANCE WT11-1 ALL FEDERAL pC Date: December 91 STA. NU CN REGULATIONS Solar Hydronics Corp. 1423 Gunn Highway Odessa, Florida 33556 This system was evaluated by the Florida Solar Energy Center (FSEC) in accordance with the Florida Standards Program for Solar Domestic Water and Pool Heating Systems (FSEC Standard 104 -10) and was found to meet the minimum standards established by FSEC. SYSTEM pa' 6k OPV -80-40 North Central South The calculated Florida Eneru Factors for this system are: DESCRIPTION Collector Manufacturer FSEC Number ..,., ... _..1,.__/Alternate Energy Technologies 00090N A 0 C 1 2. Alternate Energy Technologies 00215N 0 1 3. Solar Hydronics Corp. 00333N � fl �� �" � 1 4. Alternate Energy Technologies 00081N AE -21 2 5. Alternate Energy Technologies 002131\ MSC -21 2 6. Solar Hydronics Corp. 004441\ SHC -21 2 Tank Manufacturer Type Capacity (gal) C lmerican Water Heater SE -62; 112- 80H -045S 80 2. Any Equivalent UL Listed Tank 80 3. P Manufacturer Model Number Power Draw (Watts) 1. arch 809 -BR- 12/24 48 2. Solar Hydronics Corp. SHC - 12'24 48 3. Controller Manufacturer Model Number Type Photovoltaic 1. Hoxan H -1 004 10 Watt 2. Solarex MSX -10 10 Watt (' iII AEE AE -010J 10 Watt 4. BP SX -310J 10 Watt Freeze Protection 1. Manual drain down 2. Freeze protection valve SUMMARY INFORMATION SHEET FLORIDA SOLAR ENERGY CENTER 1679 CLEARLAKE ROAD, COCOA, FLORIDA 32922 -5703 (321) 638 -1000 November 2002 FSEC # 00090N MANUFACTURER Alternate Energy Technologies, LLC 1057 N. Ellis Road, Unit 4 Jacksonville, Florida 32254 Collector Model AE -40 This solar collector was evaluated by the Florida Solar Energy Center (FSEC) in accordance with prescribed methods and was found to meet the minimum standards established by FSEC. This evaluation was based on solar collector tests performed at the Bodycote Materials Testing Canada Inc., Mississauga, Ontario, Canada. The purpose of the tests is to verify initial performance conditions and quality of construction only. The resulting certification is not a guarantee of long term performance or durability. DESCRIPTION Gross Length Gross Width Gross Depth Gross Area Transparent Frontal Area Volumetric Capacity Weight (empty) Recommended Flow Rate Test Pressure Number of Cover Plates Flow Pattern Number of Flow Tubes 3.080 meters 10.10 feet 1.200 meters 3.94 feet 0.079 meters 0.26 feet 3.697 square meters 39.79 square feet 3.482 square meters 37.48 square feet 6.1 liters 1.6 gallons 66.7 kilograms 147.0 pounds 76 ml /s 1.2 gpm 1103 kPag 160 psig One Parallel Forced Circulation Ten MATERIALS Enclosure Glazing Absorber Absorber Coating Insulation Aluminum frame, aluminum back Tempered low iron glass, 0.40 cm thick Copper tubes welded to copper fins Selective coating Foil faced polyisocyanurate, 3.2 cm thick THERMAL PERFORMANCE Tested per ASHRAE 93 -1986 Incident Angle Modifier Kra = 1.0 - 0.19 l I -1 cos() Efficiency Equations R = 72.0 - 501 (Ti -Ta) /I ri = 70.4 - 346 (Ti -Ta)/I • 1605 [(Ti- Ta) /I)2 Units of (Ti -Ta) /I are °C / Watt/m2 rl = 72.0 - 88 0= 70.4 - 61 (Ti -Ta) /I (Ti -Ta) /I - 50 [(Ti- Ta) /02 Units of (Ti -Ta) /I are °F / Btu /hr•ft2 RATING The collector has been rated for energy output on measured performance and an assumed standard day. Total solar energy available for the standard day is 5045 Watt - hours /m2 (1600 Btu/ftz) distributed over a 10 hour period. Output energy ratings for this collector based on the second -order efficiency curve are: Collector Temperature Low Temperature, 35 °C (95 °F) Intermediate Temperature, 50 °C (122 °F) High Temperature, 100 °C (212 °F) Energy Output 44,300 Kilojoules/day 36,300 Kilojoules /day 12,200 Kilojoules/day 42,000 Btu /day 34,400 Btu/day 11,600 Btu/day REFERENCE 00081N FSEC # S9022 F i_l )}:11 ' \ \R EN Fa C1: N 1 }.};. Approved Solar Energy System Approval Date: December 1991 Revision Date: July 2011 P One or Two Collector Ponels PV MODULE Solar Tank Cold Supply MARCH PU 1819 PICKWICK AVE., GLENVIEW, 1t. 60026.1306, U.S. PHONE: (847) 729 -5300. FAX: (847) 729 -7062 WWW.MARCHPUMP.COM DESCRIPTION: Your March hot water booster pump is a non -self priming unit built to handle ligjid transfer in heating and cooling operations. Applications include home heatng systems, solar heating systems, heat recovery systems and recirculating water in domestic and commercial hot water tanks. Contact the factory for applications other than those listed, and for liquids other than water. PS ILA + l i , ` 1 809 -BR 809 -PL Wine Housing ABBREVIATIONS: Pump Housing: BR is Bronze, PL is Potysuffone Plastic, SS is Stainless Steel, C is Center Inlet. INSTALLATIONS: The pump is assembled and ready for installatior. Tie pump should be mounted with the Electric Conduit Box on the bottom. The oil ports will then be on the top of the motor. The pump housing should be installed with tie arrow on our housing pointing in the direction of the water flow within the system 11 the arrow indicating water flow is not in the direction you require when the motor is in position, remove the four round housing screws (Item 1) holding the housing to the motor assembly and rotate the housing assembly as required. Replace the four screws and tighten. The pump is made up of two basics i sub - assemblies. They are the Wet End Assembly and the 809 -BR -C 809 -PL -C 809 -SS -C Center net Housing H E A G N F E E T Motor/Bracket/Drive Magnet Assembly To separate the 2 ; assemblies, simply remove the 4 round head screws (Item 1). The pump will then separate into the 2 sub - assemblies The water will still be contained within the Wet End assembly unless you loosen the screws on the rear of the ' Wet End Assembly. SPECIFICATIONS �-F_M LUBRICATION: The motor should be oiled at least once ; Max Flow soliz� a year at the start of the heating season with 4 or 5 drops of ' 50H2 Ye g SAE 20 weight non - detergent oil in each bearing. If the Max Heao 60Hz pump is used year around it should be oiled every six r'm."° months. Do not over oil. No oiling is required on the ball bearing motors. GENERAL SAFETY INFORMATION: Max internal essure Follow all local electrical and safety codes. and the Max id Liquid Occupational Safety and Health Act (OSHA). Make certain L Temperature that the power source confomts to the requirements of your PaL - -cked Weigh equipment. Always disconnect power source before performing any work on or near the electric motor. Caution Motor Type must be exercised to relieve any pressure in the system and in draining hot water from the pump or the system. `UL Recognition on pumps, file E80954, is for water only. 50Eit Motors are U.L. Yellow Card listed, impedance protected or thermal overload Protected. Complete pump under U L file E80954. Cattfomia Law, Bill #1953, states that any item. which provides water for human consumption. shall contain no . sCHZ more than 0.2% lead. March cannot recommend the 809 series out of bronze; instead use the plastic or stainless Electrical Connection steel housing. Overall PumOr H Dimensions ?' 809 "MAGNE- BOOST" HOT WATER PUTS L.P.M 60HZ 809 -8R-C 809-Pi .0 809 -5S-C 60H2 809.8R 809-PL 50H2 809 -BR.0 809 -PL -C 809•SS -C M E T E; R: 50HZ 809-8R 809 -PL GPM 9 01 a 10.3 10.3 1/7 MPT 1/2' MPT 117 MPT 1/7 MPT 50 3.4 250 121 3/4' MPT 1/7 MPT 3/8' FPT & 3/4' MPT 1/2' MPT 50 3.4 Phase Volts Watts Am• Kw 115 or 230 Air cooled 115 or 230 Air Cooled 115 or 230 Air Cooled 115 or 230 16.7 5.0 .92 4.3 1.86) 3/4' MPT 1/7 MPT 150 10 250 121 2.7/6 Air Cooled 115 or 230 1 0.5 ( 0.17 0.94 0.45 NOTES: All specifications & data are based on pumping water & are (Inches) ~L.. intended for use as a guideline only. Ratings & dimensions Dimensions! E---HW may ry depending on the current motor being used. (cm) e _ rlgth 1750 1750 Conduit Box 1750 1750 Conduit Box 018 1400 230 52 0.45 1/40 1750 13.5 13.0 8.4 , 8.4 13.5 13.5 10.7 10.7 8.5 . 8.5 10.4 10.4 16.7 ! 16.6 16.7 16.6 20.0 20.7 18.7 19.4 19.9 20 5 22 21 19 20 v ITEM DESCRIPTION REP UR PARTS MATERIAL I I re I O QTY ; PART # ' 00 4 0923- 0003 1000 f S J O 00 S cc W a S J O co S, co 0 w° 1 Screw 4l` -32 x 1° Long Steel 2 3 Screw#8 -32 x 1° Long Pump Housing Stainless 4 0809-0205 -1000 S 4 wlCenter Inlet Pump Housing Bronze 4 1 0809-0142 -0000 I S Online) Pump Housing Bronze 1 0809 - 0013-0000 F S 5 w/Center Inlet Polysulfone 1 0809-0179 -0100 S 6 Pump Housing (Inline) Polysulfone 1 0809 - 0079-0100 I S Housing w/Center Inlet Stainless 1 0809-0150 -0000 r S 8 Hex `0' Stainless 4 0991 -000410001 S 9 Ring .070 CS x 2.441 ID Silicone 1 0809-0165-1000 S S S 10 O" Ring 1/16' CS x 2 -3/8 ID Silicone 1 0809-0027-1400 5 S 1 1 Thrust Washer Teflon 1 0809 -0043 -1000 S S S S S 12 S h a f t Stainless 1 } 0809 -0161 -1000 S S S S S 13 Shaft (Left-Hand Thread)_(Old Style) Stainless 1 0809 -0008 -1000 0 14 Impeller (Z" Dia.) Ryton/Teflon/Glass 1 ! 0809-0005-0100 S ' S S S S 15 Rear Housing Stainless 1 0809-0012 -1000 S S S S S 16 Screw #8-32 x 3/8" Long_ Stainless 4 j 0135 - 0040 -1000 I S S S S 17 Sr:m #8 -32ix 1° Long Stainless 4 0809-0205 -1000 S 2 1 0125- 0083-0100 Stainless 4 0135-0040 -1000 S S S S S S 19 Screw x 3/8' Lon 9 S S S S 20 21 Washer Motor S t a i n l e s s 4 i 0858-0004-1000 S S S S Bracket Plastic y 1 0809 -0058 -1000 S S S S S S 22 Motor 115V 50/60Hz 1 0809 -0064 -1000 S S 22A Motor 230V 50/60Hz (Not Shown) 1 ° 0809-0065 -1000 S S 1 0135 -0109 -1000 S S S 23A Motor 230V 50/6011z Not Shown NOTE. Contact Factory for 1 0135 -0112 -1000 S= Standard. S O= S S Optitina! 1■ICACCCIL1aI other r iaterials and /or parts not listed. I Legend: V Akin DCAOQCUar v. —The motor can be removed from the Wet End assembly without having to drain the irqukt out of the system '— Remove four screws (Item 1) and slide the motor assembly away from the Wet End assembly. —If you must replace parts inside the wet end assembly, then first close off the valves that supply water to the heating system or to the hot water tank. /rain the system to relieve any pressure. --After the system is drained and cool enough to handle. then remove the four screws on :he rear of the housing. —The rear housing can now be removed. 11 may be snug fit into the pump housing and it may be necessary to pry evenly, under the four ears to loosen — Remaining pump parts can now be lifted out in sequence as shown on the exploded view. Replace any worn or damaged parts. Replace the '0' ring nytime the rear housing is removed. JMITED WARRANTY: torch pumps are guaranteed only against defects in workmanship or materials for a period of one year from date of manufacture pumping water. On all ther solutions, contact the factory for application assistance March Pump Application Worksheet 0750 - 0130 -1000 is available for additional warranty tformatiot. 0809-0053 -1000 R13 (Revised 1/5/11) Nimmilmonos Rated 150 Volt Sunlight- Resistant -20 °C to +60 °C 18 and 20 Gauge Copper Conductors TH EF:MO STAT WIRE A P P L I C A T I A N S Suitable for use as follows: if Thermostat Wire is a class 2 power - limited circuit cable for use in thermostat control applications STANDARDS & REFERENCES • 150 Voltage rating per NEC 1' Article 725 • ETL. listed to UL 13 • Meets UL 1581 Vertical Tray Flame Test (=T -1) • Type CL2 Southwire OEM Division _ Intertek C O N S T R U C T I O N • Solid copper conductors with 6 mils cf PVC insulat on • Conductors are covered with a brown PVC jacket • Ripcord green Spec' USA RoHSCompliar t ro UMBER CONDUCTOR COLORS N - dG G JACKET THICKNESS ' APPROX. OVERALL APPROX. NET WEISIIT NOM. (mils) CABLE DIAMETER (mils) j (Ibs/1'000ft) Red, White 14 132 16 Red. White, Green 14 140 22 18/4 Red, White, Sreen, Blue 14 154 28 18/5 Red, Wh te, Green, 17C 34 Ble u, Yellow 18/6 Red, Wh to Green, - - Blue, Yellow, Brown 18/7 Red, White, Green. Blue, 1 Yellow, Brown, Orange 18/8 Red, White. Green, Blue, Yellow, Brown, Orange, Black 18/9 Red, White, Green. Hlue, Yellow. Brown, Orange, Black, Pink 18/10 Red, White, Green. Blue, Yellow. Brow; Drange. Black, °ink, Gray 186 44 186 45 202 52 218 57 246 65 Red. 'White, Green, Blue, 18/12 Yellow. Brown, Orange, Black, Pink, Gray, Tan, Purple All Thermostat Wire is constructed with so Jd conductors, PVC insulation (6 mils), parili °_I conductors, PVC jacket. 25 of /ft capacitance between conductors @ 1 KHz, (norn.), and 6.32 Ohms/1000 toot DC resistance per conductor 20 ER DI CTORS' 20/2 CONDUCTOR COLORS Red. `Wh to 20/3 Red, White, Green 20/4 Red, White. Green, Blue Red, White, Green Blue ellow Red, White, Green, t 20,6 Blue, Yellow, Brown 2017 Red, White, Green, Blue, 15 Yellow, Brown, Orange 20/5 JACKET THICKNESS APPROX. OVERALL APPROX. NET WEIGHT NOM. (mils) CABLE DIAMETER (mils) (Ibs /1000 ft) 14 114 14 14 15 20/8 Red. White, Green. Blue, Yellow, Brown, Orange. Black Red. White. Green, Blue. Yellow. 20/9 Brown, Orange. Black. Pink Red, White, Green, Blue, 20/10 Yellow. Brown, Orange, Black, Pink. Gray 20/12 Red. White, Green, Blue, Yellow. Brown. Orange, Black, Pink, Gray, Tan, Purple 15 15 121 15 132 18 147 22 160 26 160 29 173 33 185 37 202 40 209 47 All Thermostat Wire is constructed with solid condt.c _ors, PVC insuiation (6 mas parallel conductors PVC Jacket 22 pPat capacitance between conductors s 1 KHz (norm), and 12.73 Ohm s /100'0 root DC res,stance per conductor © 20 °C or^ ). W 4 0 a CC AE -1 OST Circulation Modlule 10 W Circulation Module Power STC (peak) watts 10 Peak power voltage volts 17.9 Peak power current arnps 0.56 Open circuit voltage volts 21.8 Short circuit current arnps 0.61 Length inch (mrn) 25.6 (649.5) Width inch (mrn) 7.2 (182.5) Depth inch (mrn) ; (76) Tolerance +/ -10% 11__ 2±62,5_)11 _ 76 _ 800 - 777 -6609 www.aeesolar.com sales @aeesolar.corn • 707 - 923 -2277 • 707 - 923 -3009 fax 775 Fiero Lane • Suite 200 • San Luis Obispo, CA 93401 Al."5110611°. meric,:, W A T E R H E A T E R S ■ SE62 -801-1 -0455 SE62 -119R -0455 SOLAR STORAGE TANKS WITH ELECTRIC ELEMENT 6 -Year Tank Warranty 6-Year Parts Warranty • 2" Non -CFC Foam insulation Foam insulation saves fuel by retarding heat loss. • Fused Ceramic Shield Applied under pressure and fired at 1600 °F to completely cover the tank interior. This provides a tough interior surface for storage tanks and maximum prc tection against the wearing effects of high-volume and high - temperature hot water. • Anode Rod Promote longer tank life through even distribution, for protection against corrosion of tank interior. • Factory- Supplied Top Temperature and Pressure Relief Valve • Factory- Installed Dielectric Nipples • Pre -Wired Sensor Lead From storage sensor mounting stud to top of tank. Does not include sensor. • Water Connections Accessible from four factory- installed 3/4" dielectric nipples located on top of tank, • 4500 -Watt Heating Element and Automatic Thermostat Where a back -up system is desired. • UL Listed Model # SE62- 80H -045S Gal Capacity 80 Hght Wtr Conn. 60.25 acket Diameter 24 Hght Top of Tank 59.25 Hght Top T &P 59.25 pprox. Ship Wght 191 SE62- 119R -045S 119 62 28 61,5 61.5 278 Copyright© by American Water Heater Company 2005, All rights reserved. MADE IN USA 6 -Year Limited Tank Warranty Heavy gauge steel is automatically formed, rolled and welded to assure continuous seams for Fused Ceramic Shielc'r "' lining. Each tank is triple tested to ensure qual- ity. 6 -Year Parts Warranty Original factory parts warranted for 6 years. For complete warranty information consult the written warranty' of Americ it 'warer Hearer Company or (800) 999 -9515. No part oethen work may be reproduced or transmitted in any corm or by any means or mechanical, including photocopying and recordmq a t•ry information storage retrieval system. without permission m venting from American Water Herer 07,'05 L -SST -1.0a Crystal Clear"' Selective Coating t °.tai!_ ir.r ' ,,, ;.ar `,a.0 ..r • • ,.) re'; •. ,- r ,711y ( ,art. tnr ap•.uialyd Hinret. )16% nlir,y .I: -•.., o„rs (1,.;r.':- al!.r ...••■• . „ Li, •area ofrheabunbe, platy lot enax:rnun,•aa ; ;.n6.rt .. ,vs, ' r lr.tr "7, a•. t..- r. ...... .r ,.r ,,.q, ,ru,.,e 16,)"1 0 on!:nu ously with nunur.rl •1,1 da: ..)t its thermal • 'al( a• :e, .I :.• • . ;'F -,:.r. •1 .'.,,r�e�ih rht■ n rai nerfunr,a )nJn {t. 1hr r.n,.rrr��. „)n /I =,r,• ;r••an Ahu_,r,.1 611 yUf -. r 96 fZf roes■vrry of . THERMAFIN'' Absorbers -•f .- rq li! 1414Al .... nY,., t,.., , •ham nl .rn .ra7le, ra vn •.gar ,hrrn „j7 .• 7rnavr rru, r. e �r: l„I: nn .:• wr har.r crnplr,yrd 71,e t�. ^t hra: nL,•,fr•• r,,rihod /1 hxiay I70 - 1.1MAE IMs y, rm ye w•� pr) •rs..r.u,l rrulaely brn /1,11,, a• nr t ulmprovrdmy ion,/ Iasr,::yl; rr torrnairtr end ,I,,:.rh:!�iyv ;l, ;ir all r,w,n:l r7,r''■i'''st ilea! rr.r'rin. h .� ''''' _,lf, ! ..,t,�r.�, N.rldrrl l-nnt•,wd r.: ,t .�r.tL,•n eXp.rnd •■••I! nl,ar, ar,1 are h., xr :1' y,t Wr item le year [l, war t.• +• Electrostatically Painted C Channel Construction U0, nt .rr,r. idler tur Ira.nr'.eref I. e,n, rr. u , state .f thr a . manufai tunny !ar x.0 ,'. It, I {nnrin c tnitr•dmail.!,rhrtnunm, ex11uv01-0, nrth el rrinr.r.UUr ally appedbroi 1 hulye'.i rri.,nnt and •euuely fa•.t cord vnt 0, ■rre r eft gr,,de t:n. qr p ',vets Af Sprrse rdlrrtranarrburst 10 wrrhstond t fir mist dernandrng envuonmrnt•. ilk. sC1YCS Sklar t'oilc�'II I • \ IIItit h tut'eti hs• Aitt ;rnati Ettrt,,� 1't °c6inrh�,it ti (;\F f), 111' AE- Series "Flat Panel” Solar Thermal Collectors, manufactured in The United States of America by Alternate Energy Technologies (AET), are designed to meet the needs of any solar system. Our expert design team will assist in sizing any job to provide hot water, space heating, radiant floor heating or industrial process heat. AET is dedicated to building our AE- Series Collectors from the finest materials and with the highest standards of craftsmanship All AE- Series Col lectors Feature: •Wind load tested to allowable loads of yz PSF -Crystal Cleary' selective coatings •Extruded aluminum frame and battens •Thermax^• polyisocyanurate foam insulation •Aircraft aluminum pin grip rivets •30+ year design life •io year warranty •Proudly made in the U.S.A. •THERMAFIN n” absorber plates °Quick -lock mounting hardware Len.th In 85.187 97.187 77.187 85.187 97.187 121.187 WI•t In 35.187 35.187 47.187 47.187 47.187 47.187 Height In 3.137 3.137 ' 3.137 3.137 3.137 3.137 Gross Area (ft2) 20.8 23.7 25.3 27.9 31.8 39.7 Fluid Capacity (gals) 0.70 0.76 0.90 0.96 1.05 1.22 Dry Welght (lbs) _ 74 84 90 _� 99 113 153 ilk. sC1YCS Sklar t'oilc�'II I • \ IIItit h tut'eti hs• Aitt ;rnati Ettrt,,� 1't °c6inrh�,it ti (;\F f), 111' AE- Series "Flat Panel” Solar Thermal Collectors, manufactured in The United States of America by Alternate Energy Technologies (AET), are designed to meet the needs of any solar system. Our expert design team will assist in sizing any job to provide hot water, space heating, radiant floor heating or industrial process heat. AET is dedicated to building our AE- Series Collectors from the finest materials and with the highest standards of craftsmanship All AE- Series Col lectors Feature: •Wind load tested to allowable loads of yz PSF -Crystal Cleary' selective coatings •Extruded aluminum frame and battens •Thermax^• polyisocyanurate foam insulation •Aircraft aluminum pin grip rivets •30+ year design life •io year warranty •Proudly made in the U.S.A. •THERMAFIN n” absorber plates °Quick -lock mounting hardware of 5 1a k4