MC-12-1561Inspection Worksheet
Miami Shores Village
10050 N.E. 2nd Avenue Miami Shores, FL
Phone: (305)795 -2204 Fax: (305)756 -8972
Inspection Number: INSP - 177493 Permit Number: MC -8 -12 -1561
Scheduled Inspection Date: September 05, 2012
Inspector: Perez, JanPierre
Owner: , BARRY UNIVERSITY
Job Address: 11300 NE 2 Avenue Browne Hall
Miami Shores, FL 33138 -0000
Project: BARRY UNIVERSITY
Contractor: HILL YORK SERVICE CORP
Permit Type: Mechanical - Commercial
Inspection Type: Final
Work Classification: A/C Replacement
Phone Number
Parcel Number 1121360010160 -14
Phone: (305)756 -6501
Building Department Comments
INSTALL 3 UNITS 1.5 TON EACH
l
Inspector Comments
Passed
Failed
Correction
Needed
Re- Inspection
Fee
No Additional Inspections can be scheduled until
re- inspection fee is paid.
September 04, 2012
For Inspections please call: (305)762 -4949
Page 17 of 33
•
Miami Shores Village
Building Department
10050 N.E.2nd Avenue, Miami Shores, Florida 33138
Tel: (305) 795.2204 Fax: (305) 756.8972
INSPECTION'S PHONE NUMBER: (305) 762.4949
BUILDING
PERMIT APPLICATION
Permit Type: MECHANICAL
/L/ o� �� , ��
JOB ADDRESS: N CJ Z' e A I6
City: Miami Shores County:
Folio/Parcel #:
Is the Building Historically Designated: Yes NO Flood Zone:
FBC �,r� n
Permit No. ► 1 C 12 -1 Sk 1
Master Permit No.
ograi, Miami Dade Zip: 33'CK,
OWNER: Name (Fee Simple Titleholder): l.,Y n lV.LV?3I.� "f (0 Phone #:
Address: I I � X J) 14 2nd i-
City: i) pm a Shur) '
State: �4
Zip: 3�I(9
Tenant/Lessee Name: Phone #:
Email:
CONTRACTOR: Company Name: /4-i I I Y1)rlL
Address: (9, a5 5 , -r d rJIL)S Ai.-Q-
City: 1-J ktui'/ G�Q &� state: ,��
Qualifier Name: � OWL, k'i
0 c�a0
Phone #:
Zip:IL
Phone#:
State Certification or Registration #: pl "I lJJ //nn Certificate oof Competency #: OEM � 3- 3q (U,"1
Contact Phone #: Email Address: NW2 eh l 1'k'QOL .
DESIGNER: Architect/Engineer: / Phone #:
Value of Work for this Permit: $ !) Square/Linear Footage of Work:
Type of Work: ]Address ]Alteration New [ Repair/Replace ]Demolition
Description of Work: flOV IO 4 4 t, kilo& J r-47JAIftlircAril f&
******** * *** * ** ********** ** ** * *** ****** es+x �x�x�x+ x*: xx��x**** �x* �x�x+ x *�x�x*** *** * *x:�x *+x:x�x *x�***
Submittal Fee $ �, n„ _',/M.. Permit Fee $ CCF $ CO /CC $
Scanning Fee $ Radon Fee $ DBPR $ Bond $
Notary $ Training/Education Fee $ Technology Fee $
Double Fee $ Structural Review $
TOTAL FEE NOW DUE $ �-
r
4
• Bonding Company's Name (if applicable)
Bonding Company's Address
City State Zip
Mortgage Lender's Name (if applicable)
Mortgage Lender's Address
City State Zip
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRICAL WORK, PLUMBING, SIGNS,
WELLS, POOLS, FURNACES, BOB .FRS, HEATERS, TANKS and AIR CONDITIONERS, ETC
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF
COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR
IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN
FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE
RECORDING YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved and a reinspection fee will be charged.
Signature
Owner or Agent
The foregoing instrument was acknowledged before me this 1
day of kAUA , 20 It; by atitA (( `e it I o ,
who is personally known to a or who has produced
As identification and who did take an oath.
Sign:
Print:
My Commission Expir
***** ** * * * * * * ********* **** * * ** * * * * ** ****
APPROVED BY
Signature
� yr
Contractor Mart, y ��
The foregoing instrument was acknowledged before me this i 9-N h
day of L ,,� , 20 I� , by it ,
who is personally known to me or who has produced
as identification and who did take an oath.
NOTARY PUBLIC:
Plans Examiner
Structural Review
Revised 3 /12/2012)(Revised 07 /10 /07)(Revised 06 /10 /2009)(Revised 3/15/09)
Sign:
Print: CASTRO
My Commis , stilY COMMISSION # EE109306
• EXPIRES August 07, 2015
•¢i ' ` eNorary$ervicesmat
(407) 398-0153
Zoning
Clerk
Ammi
RUUD Design Star Load Calculation
Results are intended for use with Ruud heating and cooling systems only
Customer Information
Location:
Street Address 11300 NE 2nd Ave, MIAMI-DADE, FL 33161
Latitude, Longitude 25.7791°, -80.1978°
House Square Footage: 572 sq. ft.
Name: Barry U - Browne Hall Rms 25/26
Phone: 123-123-1234
Email: example@maiLcom
Desi n Conditions
Outdoor Heating Cooling
Dry bulb (°F) 54 92
Daily range
L
Relative humidity 50%
Moisture difference
Indoor
Indoor temperature (°F)
Design temperature difference(°F)
58
Heating Cooling
68 74
14 18
Hea]i��
'' Loads
Area Btuh % of load
Wall 7480 45
Floor
8453 50.9
Ceiling �' 424 2.6
Windows 252 1.5
/
Infiltration 0 0
---------------------`-------^-~--`
System Efficiency Loss 0 0
--_._--'_------------'_'-_-_-_-_---__-_-_
Total: I66I0
Floor
Heati ng Loads
16 .610 eTuyh,
Infiltration
System Efficiency Loss
Windows
Ceiling
Wall
Coolin. Loads
Area
Wall
Ceiling
Windows
Sensible Infiltration
................... ............ ...............................
Latent Infiltration
Btuh % of load
.......... ...............................
59.5
9617
546 3.4
2008 12.4
948 5.9
1888 11.7
System Efficiency Gain 0
Internal 642
Sensible People Load
Latent People Load 263
Total:
Sensible load
Latent load
SHR
Capacity at .87 SHR
Cooling Loads
16,175 BTU /hr
r System Efficiency Gain
Sensible People Load
I 1 � —Ltent People Load
111
�eiling
Internal
/ — Sensible Infiltration
Latent Infiltration
Wall
3000
2000
�
�
1000
o
AED Graph
8am ovm zoam zzvm ovm lpm 2pm 3pm
[
Manual "^~ ^~"x°'
System equipment selection will be made using the following Manual derived values.
Summer Outdoor
92°F
Summer Wet BuIb 77°F
Summer Indoor
74°F
Summer Design Grains 50%
Winter Outdoor
54°F
Winter Indoor - 68°F
Sensible Cooling 14,023 Btuh
_-_'--_-_--_-__---_'-__--_----___--__----_ __
Latent Cooling 2,151 Btuh
Required Cooling Airflow 637 CFM
Sensible Heating 16,610 Btuh
Required Heaing Airflow 216 CFM
An calculations are based upon approved hvac industry standards and procedures, and comply with all local,
state and federal code requirements. fII computed results are Estimates, Product provided by Energy Design
Systems and Idea Tree
iiu RUUD DesignStar Load Calculation
Results are intended for use with Ruud heating and cooling systems only
Customer Information
Street Address
Latitude, Longitude
House Square Footage:
Name:
Email:
Location:
11300 NE 2nd Ave, MIAMI -DADE, FL 33161
25.7791 °, - 80.1978°
572 sq. ft.
Barry U - Browne Hall Rms 31/32
123 -123 -1234
example @mail.com
Desi• n Conditions
Dry bulb (°F)
Daily range
Relative humidity
Moisture difference
Outdoor
Cooling
L
Indoor
Indoor temperature ( °F)
58
Heating Cooling
Design temperature difference( °F)
14
18
Heatin• Loads
Wall
Floor
Ceiling
Windows
Area
Infiltration
Btuh % of load
7480 45
8453 50.9
424 2.6
252 1.5
System Efficiency Loss 0
Total
Floor
0
Heating Loads
16,610 BTUThr
Infiltration
System Efficiency Loss
Windows
Ceiling
Wall
Coolin• Loads:
Area
Wall
Ceiling
Windows
Sensible Infiltration
Btuh % of load
9617 59.5
546
3.4
2008 12.4
948
5.9
Latent Infiltration 1888 11.7
System Efficiency Gain
Internal
Sensible People Load
Latent People Load
Total:
Sensib
Latent Load
SHR
load
2151
0.87
Capacity at .87 SHR 1.34 Tons
Cooling Loads
16175 BTU /hr
System Efficiency Gain
Sensible People Load
ad Lo
/Ceiling
Internal
��� Sensible Infiltration
Latent Infiltration
Wall
Windows
q
3000
2000
1000
0
1 i(:r vie ItiIY11 II Y
AED Graph
Sam 9am 10am llam 12pm 1pm
ACCA Manual S
2pm
3pm
— Hourly Loads — Average
4pm 5pm 6pm 7pm 8pm
System equipment selection will be made using the following Manual S derived values.
Summer Outdoor
Summer Wet BuIb
Summer Indoor
Summer Design Grains
92 °F
Winter Outdoor
Winter Indoor
Sensible Cooling
Latent Cooling
Required Cooling Airflow
Sensible Heating
Required Heaing Airflow
74 °F
54 °F
14,023 Btuh
637 CFM
216 CFM
A;I calculations are based upon approved hvac industry standards and procedures, and comply with all local,
state and federal code requirements. All computed results are Estimates.. Product provided by Energy Design
Systems and Idea Tree
- RUUD Design Star Load Calculation
,L,IIP•mmoM11111F Results are intended for use with Ruud heating and cooling systems only
Customer Information
Location:
Street Address 11300 NE 2nd Ave, MIAMI-DADE, FL 33161
Latitude, Longitude 25.7791°, -80.1978°
House Square Footage: 572 sq. ft.
Name: Barry U - Browne Hall Rms 17/18
Phone: 123-123-1234
Email: example@mail.com
Desi n Conditions
Outdoor Heating Cooling
Dry bulb (°F) 54 92
Daily range
L
Relative humidity 50%
Moisture difference
58
Indoor Heating Cooling
Indoor temperature (°F) 68 74
Design temperature difference(°F)
14 18
Heatin. ~ad~a.`�' ;�'
Area Btuh % of load
Wall 7480 45
Floor
8453 50.9
Ceiling
Windows 252 1.5
Infiltration 0 0
System Efficiency Loss 0 0
Total: 16610
Floor -
Heating Loads
e,610 oru/x,
Infiltration
System Efficiency Loss
Windows
Ceiling
Wall
Coo lino Loads
Area
Wall
Ceiling
Btuh % of load
9617 59.5
546 3.4
Windows 2008 12.4
Sensible Infiltration 948 5.9
Latent Infiltration 1888 11,7
System Efficiency Gain 0 0
Internal 642 4
Sensible People Load 263 1.6
Latent People Load 263 1.6
Total: 16175
Sensible load 14023
Latent load 2151
SHR 0.87
Capacity at .87 SHR 1.34 Tons
Cooling Loads
16,175 BTUThr
Wall -----
1-- System Efficiency Gain
Sensible People Load
r-------np"----- Latent People Load
/ r"-------___:Ceiling
Internal
:, ',-: r"-------- Sensible Infiltration
44 ,.:.,
Latent Infiltration
Windows
�����0�� � Diversit
~�+
'._~~ -.~~__~_.. •_._, � ~-,~~. ~.~
• AEOGraph
3000
-0
0
�
2000
1000
0
— Hourly Loads — Average
..~~~~.. Manual S ' ~
System equipment selection will be made using the following Manual 5 derived values,
Summer Outdoor
Summer Wet BuIb
Summer Indoor
Summer Design Grains
Winter Outdoor
Winter Indoor
Sensible Cooling
Latent Cooling
--------------'—'---'----'
Required Cooling Airflow
92°F
77°F
74°F
50%
54°F
<58°F
14'033 Btuh
2,151 Btuh
637 CFM
Sensible Heating 16,610 Btuh
Required Heaing Airflow 216 CFM
All calculations are based upon approved hvac industry standards and procedures, and comply with all local,
state and federal code requirements. AV computed results are Estimates, Product provided by Energy Design
Systems and Idea Tree