Loading...
MC-11-22061 1 - 1 0 3 Inspection Worksheet Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, FL Phone: (305)795 -2204 Fax: (305)756 -8972 Inspection Number: INSP- 167125 Permit Number: MC -11 -11 -2206 Scheduled Inspection Date: June 27, 2012 Inspector: Perez, JanPierre Owner: , SHORES SQUARE INVESTMENTS Job Address: 9025 BISCAYNE Boulevard Miami Shores, FL 33138 -0000 Project: <NONE> Contractor: RESULTS AIR CONDITIONING CO Permit Type: Mechanical - Commercial Inspection Type: Final Work Classification: New Phone Number Parcel Number 1132060110051 -25 Phone: 305 -886 -2534 Building Department Comments INSTALL CARRIER SPLIT A/C SYSTEMS ALL WITH 8KW HEAT, DUCTWORK AND BATHROOMS EXHAUST FANS q-Ig Passed Failed Correction Needed Re- Inspection Fee No Additional Inspections can be scheduled until re- inspection fee is paid. Inspector Comments p2 (51_‘„ ale June 26, 2012 For Inspections please call: (305)762 -4949 Page 6 of 36 Balance Certification Rep NATIONAL BALANCING COUNCIL- 6/25/2012 PROJECT PROJECT NAME Fit 4 Life ADDRESS 9025 Biscayne Blvd. Miami, FL 33138 CUSTOMER Results A/C Fit 4 Life SYSTEM All Systems READINGS BY Sergio Aguirre JOB NUMBER The data presented in this report is an exact record of system performance and was obtained in accordance with the NBC Standard Procedures. Any variances from design quantities which exceed NBC tolerances are noted throughout this report. The air distribution systems and water distribution systems if applicable, have been tested and balance and final adjustments have been made in accordance with NBC "Procedural Standards for Testing, Adjusting, Balancing of Environmental Systems" and the project specifications. NBC TAB FIRM: Mechanical Systems & Controls Inc. TAB SUPERVISOR: Luis Prats REG NUMBER: 0177 CERTIFICATION EXPIRATION DATE: July -17 -2014 COMMENTS: TB -12 -25 Luis U Prate Mechanical Systems & Controls Inc, #1177 Expires 07/17/2014 NA;IONAL BALANCING COUNCIL 1 of 18 NATIONAL BALANCING COUNCIL'TM NBC Air and Hydronic Balancing Certification The National Balancing Council is committed to providing and maintaining a comprehensive set of values, standards, practices, and procedures governing the field of testing, balancing, and adjusting commercial environmental systems. Our members pledge to faithfully uphold the highest standards of integrity and professionalism in the industry as a requisite to certification. NBC stands fully dedicated to the advancement of the testing and balancing field, and the support of its membership through training, communication, and leading -edge methodology. NBC Philosophy The distinguishing characteristic of an NBC certified technician is the ability to prescribe solutions to the endless field conditions that prohibit an HVAC system from achieving balance and maximum field performance. Nearly all NBC technicians have extensive field experience in HVAC system repair, installation or service and possess skills required to troubleshoot the most difficult field conditions that can be revealed by their testing. These technicians test, diagnose and maximize the performance of over 200,000 HVAC systems per year. Practical Standards Each certified technician prescribes to National Balancing Council Practical Standards and Procedures. These cover a full range of testing, balancing, adjusting, and diagnostic practices backed up by NBC reporting forms. CSERTM and HSERTM In addition to traditional independent test reports, NBC Technicians can provide an efficiency rating of the installed system. These ratings can be compared to the manufacturer's equipment efficiency ratings to offer a new view of system performance that is not offered anywhere else in the HVAC industry. CSERTM represents Cooling System Efficiency Rating and HSERTM is Heating System Efficiency Rating. Technical Support and Backup NBC provides its certified technicians with toll free technical support. New field conditions affecting HVAC system performance are uncovered daily. Experienced support is available as a benefit of certification. Architects, engineers, and building maintenance staff are welcome to contact us with their questions and comments as well at 800- 633 -7058. 2 of 14 CEI3'I'IFIE1D, Luis U Prats Mechanical Systems & Controls Inc. #0177 Expires 07/17/2014 NATIONAL BALANCING COUNCIL) Why MSC Experienced Staff Over 5 years of Service Quick dotes NBC Certified Easy to read Reports Serving 111 of Sontli Florida Responsive Service Advanced Instruments Large or Sn�lall Projects PII. 786- 228 -8925 FAX 786- 228 -8348 STAFF Luis Prats Vice - President Luis brings to your projects over balancing experience. He has been a controls Contractor for over 5 years and a Mechanical Engineer for over 17 years. He holds an NBC air and hydronic balancing certification with an emphasis in engineered solutions through diagnostics for HVAC systems. Luis is also a LEED AP and an expert in duct renovation, reaching beyond the typical air balancing limits, delivering complete system solutions and creating measured system performance. Victor Gomez President Victor has design & implemented controls strategies for over 200 commercial and industrial HVAC systems over the past 12 years. He specializes in performance controls, and system evaluations. He holds an Mechanical & Electrical Contractor's License and has been an Electrical Engineer for the last 12 years with an emphasis in engineered solutions through diagnostics for HVAC systems. Victor is also a LEED AP and an expert in duct renovation, reaching beyond the typical air balancing limits, delivering complete system solutions and creating measured system performance. Victor Holds an NBC air and hydronic balancing certification. 3of14 CERTIFIEDD Luis U Prats Mechanical Systems & Controls Inc. #0177 Expires 07/17/2014 NATIONAL BALANCING COUNCIL I Schedule of Tools and rlest Instruments NATIONAL BALANCING COUNCIL' Instrument Manufacturer \1ndel Air Capture Hood Air Multimeter Pitot Tubes Electrical Meter Tachometer Thermocouples Theatrical Fog Hydronic Meter TSI Testo Dwyer AEMC Testo Testo NCI Alnor 8371 435-4 160 502 Model 460 Various SP -2 HM680 Serial 70915122 1658950/903 None 25358JACT 38807427/104 Various 71002014 Calibrated Jul -11 Jul -11 N/A Jul -11 Jul -11 N/A N/A Jul -11 Description Hood Velocity /Pressure/Temperature /Humidity 18 ", and 24" Amp/Volt/Temperature /Ohms 1- 10,000 RPM. Non - Contact Multiple Ranges and applications Smoke Stick Hydronic Differential Gauge 4of14 CFM Cubic Feet per Minute Diameter Supply Return Exhaust Direction of Airflow T Thermostat/control D Damper Volume Damper OBD Opposed Blade Damper BD Backdraft Damper Unit Location CR Ceiling Retum Retum Duct Supply Duct OSA Outside Air Equipment Designation SP Static Pressure SWS Sidewall Supply SWR Sidewall Retum CS Ceiling Supply HP Horsepower V Volts FLA Full Load Amps SF Service Factor BHP Brake Horsepower CU Condensing Unit DNA Data Not Available CC Cooling Coil AH Air Handler L Louver DNL Data Not Listed NA NT NATIONAL BALANCING COUNCIL" DATE 6/25/2012 PROJECT Fit 4 Life SYSTEM All Systems READINGS BY Sergio Aguirre JOB NUMBER TB -12 -25 ots co 2 W V Z J J 0 a� (1) Z z Q 0 W 2 00 CO N N to 00 ti co LL 10 N 0? Oo m 00 ti 0) 0 Not Accessible Not Taken - no valid location ERTIFIE Luis U Prats Mechanical Systems & Controls Inc. #0177 Expires 07/17/2014 ATIONAL BALANCING COUNC 5of14 UNIT DATA DESIGN ACTUAL COMMENT Unit Designation (TAG) AHU -1 AHU -1 DATE Unit Manufacturer Carrier Carrier Unit Model Number FY4ANF060T00 FB4CNF048 6/25/2012 Unit Serial Number 4711A83440 PROJECT FAN /AIRFLOW DATA DESIGN ACTUAL COMMENT Fit 4 Life Supply Air Flow (cfm) 1600 N/A No Valid Traverse Could Be Taken SYSTEM Outside Air Flow (cfm) 402 390 Retum Air Flow (cfm) 1198 940 All Systems Total Outlet Airflow (cfm) 1330 READINGS BY External Static Pressure 0.4 0.49 Sergio Aguirre Fan Speed HIGH JOB NUMBER MOTOR DATA DESIGN ACTUAL COMMENT TB -12 -25 Motor HP (or Kw) 3/4 3/4 RPM N/A Motor Volts (V) 208 208 Motor Amps (A) 2.03 Phase (PH) 1 1 Operating Frequency (Hz) 60 60 Motor Service Factor N/A Heater Size (Kw) 10 N/A Units Were Set To High Speed Luis U Prats Mechanical Systems & Controls Inc. e 0177 Expires 07/17/2014 N- TIONAL BALANCING COUNCII 6 of 14 SYSTEM TO BE BALANCED TO SYSTEM DESIGNATION (TAG) SYSTEM TOTAL DESIGN AIRFLOW 10 % AHU -1 1600 Number 1 2 3 4 5 6 7 8 Area Served Corridor Nurse Station Waiting Area Waiting Area Waiting Area Waiting Area Reception Reception Grille Type CS CS CS CS CS CS CS CS Size 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 Design CFM 100 200 220 220 220 220 220 220 AK Factor Test 1 186 171 151 160 151 150 143 218 Final CFM 84 163 182 180 179 184 183 181 % of Design DATE 6/25/2012 PROJECT Fit 4 Life SYSTEM All Systems READINGS BY JOB NUMBER TB -12 -25 ets Cl) G W Iv Z c co J J 0 0 '- Z 0 C) s c) W 2 Grilles Were Proportionally Balanced Luis U Prats Mechanical Systems & Controls Inc. #0177 Expires 07/17/2014 ATIONAL BALANCING COUN 7of14 sir w viii UNIT DATA DESIGN ACTUAL COMMENT Unit Designation (TAG) AHU -2 AHU -2 DATE Unit Manufacturer Carrier Carrier Unit Model Number FY4ANF060T00 FB4CNF048 6/25/2012 Unit Serial Number 4911A82993 PROJECT FAN /AIRFLOW DATA DESIGN ACTUAL COMMENT Fit 4 Life Supply Air Flow (cfm) 1600 N/A No Valid Traverse Could Be Taken SYSTEM Outside Air Flow (cfm) 394 415 Retum Air Flow (cfm) 1206 972 All Systems Total Outlet Airflow (cfm) 1387 READINGS BY External Static S.P (inwc) 0.4 0.4 Sergio Aguirre Fan Speed HIGH JOB NUMBER MOTOR DATA DESIGN ACTUAL COMMENT TB -12 -25 Motor HP (or Kw) 3/4 3/4 RPM NA/ Motor Volts (V) 208 208 Motor Amps (A) 2.06 Phase (PH) 1 1 Operating Frequency (Hz) 60 60 Motor Service Factor N/A Heater Size (Kw) 10 N/A Units Were Set To High Speed *V T LoL° co C M 2 t000 W • V �� N I— Z — LL CO .1 0 u..in are •g Q I-- c °° — o� Z0 .cN Q V CO 0) h ♦_ v N v W rte• 2 o0 iV Luis U Prats Mechanical Systems & Controls Inc. #1177 Expires 07/17/2014 NAZIONAL BALANCING COUNCIL 8of 14 SYSTEM TO BE BALANCED TO SYSTEM DESIGNATION (TAG) SYSTEM TOTAL DESIGN AIRFLOW 10% AHU -2 1600 Number 1 2 3 4 5 6 7 8 Area Served Corridor Waiting Area Waiting Area Waiting Area Waiting Area Corridor Reception Reception Grille Type CS CS CS CS CS CS CS CS Size 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 Design CFM 110 230 230 230 230 110 230 230 AK Factor Test 1 161 194 184 183 156 157 127 195 Final CFM 98 206 209 210 191 91 189 193 % of Design 91% 91% DATE 6/25/2012 PROJECT Fit 4 Life SYSTEM All Systems READINGS BY JOB NUMBER TB -12 -25 otS co 2 w (j co >- _1 O vH — Z ZO Q ♦_ V w 2 ERTIFIE REMARKS Grilles Were Proportionally Balanced Luis U Prats r'< Mechanical Systems & Controls Inc, 0177 Expires 07/17/2014 IONAL BALANCING COUNCI 9of14 UNIT DATA DESIGN ACTUAL COMMENT Unit Designation (TAG) AHU -3 AHU -3 DATE Unit Manufacturer Carrier Carrier Unit Model Number FY4ANF060T00 FB4CNF060 6/25/2012 Unit Serial Number 4911A83608 PROJECT FAN /AIRFLOW DATA DESIGN ACTUAL COMMENT Fit 4 Life Supply Air Flow (cfm) 2000 N/A No Valid Traverse Could Be Taken SYSTEM Outside Air Flow (cfm) 295 284 Retum Air Flow (cfm) 1705 1066 All Systems Total Outlet Airflow (cfm) 1350 READINGS BY Extemal Static S.P (inwc) 0.4 0.41 Sergio Aguirre Fan Speed HIGH JOB NUMBER MOTOR DATA DESIGN ACTUAL COMMENT TB-1 2 -25 Motor HP (or Kw) 3/4 3/4 RPM N/A Motor Volts (V) 208 208 Motor Amps (A) 2.31 Phase (PH) 1 1 Operating Frequency (Hz) 60 60 Motor Service Factor N/A Heater Size (Kw) 10 N/A Units Were Set To High Speed 06 co 2 LV 0 cn Z cn J J0 a re v Z z 0 a� s w d M 00 co N N t0 O LL N 00 o N o 0 t w v 0 E R T I F I E D Luis U Prats Mechanical Systems & Controls Inc. 0177 Expires 07/17/2014 NATIONAL BALANCING COUNCL. 10of14 SYSTEM TO BE BALANCED TO SYSTEM DESIGNATION (TAG) SYSTEM TOTAL DESIGN AIRFLOW 10% AHU -3 2000 Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Area Served Office #4 Exam Room #7 Exam Room #8 Exam Room #5 Exam Room #6 File Area Lab Area Corridor X -Ray Restroom Pharmacy Storage Restroom Exam Room #4 Exam Room #3 Exam Room #2 Exam Room #1 Grille Type CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS Size 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 Design CFM 140 130 130 130 130 120 170 50 170 40 140 90 40 130 130 130 130 AK Factor Test 1 105 129 118 107 133 122 Final CFM 112 105 101 103 102 96 Does Not Exist 79 106 43 127 79 74 142 106 116 41 131 33 111 73 34 105 100 103 Does Not Exist % of Design DATE 6/25/2012 PROJECT Fit 4 Life SYSTEM All Systems • READINGS BY JOB NUMBER TB -12 -25 co 2 W () cn Z c J 0 ,Q = Z z0 a� 0 W 2 to MA M CO .0 to O LI 0 c.) 0) (0 ti co N REMARKS Grilles Were Proportionally Balanced ERTgFIE Luis U Prats Mechanical Systems & Controls Inc. #0177 Expires 07/17/2014 NATIONAL BALANCING COU 11 of 14 UNIT DATA DESIGN ACTUAL COMMENT Unit Designation (TAG) AHU-4 AHU-4 DATE Unit Manufacturer Carrier Carrier Unit Model Number FY4ANF060T00 FB4CNF060 6/25/2012 Unit Serial Number 4911A83659 PROJECT FAN /AIRFLOW DATA DESIGN ACTUAL COMMENT Fit 4 Life Supply Air Flow (cfm) 2000 N/A No Valid Traverse Could Be Taken SYSTEM Outside Air Flow (cfm) 393 400 Retum Air Flow (cfm) 1607 1009 All Systems Total Outlet Airflow (cfm) 1409 READINGS BY External Discharge S.P (inwc) 0.4 0.5 External Static S.P (inwc) 0.009 Sergio Aguirre HIGH JOB NUMBER MOTOR DATA DESIGN ACTUAL COMMENT TB -12 -25 Motor HP (or Kw) 3/4 3/4 RPM N/A Motor Volts (V) 208 208 Motor Amps (A) 2.21 Phase (PH) 1 1 Operating Frequency (Hz) 60 60 Motor Service Factor N/A Heater Size (Kw) 10 N/A Units Were Set To High Speed oes U) W V z M 00 co N N (0 0 1•■• I0 N Q) o N N to 00 v 0 Luis U Prats Mechanical Systems & Controls Inc. x0177 Expires 07/17/2014 N rIOMAL BALANCING COUNCIL 12 of 14 SYSTEM TO BE BALANCED TO SYSTEM DESIGNATION (TAG) SYSTEM TOTAL DESIGN AIRFLOW 10% AHU-4 2000 Number 1 2 3 4 5 6 7 8 9 10 11 12 13 Area Served Weight Rm #1 Weight Rm #2 Weight Rm #3 Weight Rm #4 Weight Rm #5 Weight Rm #6 Office #1 Private Restrm Corridor Office #2 I.T. Room Office #3 Lounge Grille Type CS CS CS CS CS CS CS CS CS CS CS CS CS Size 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 24 x 24 Design CFM 150 150 150 150 150 150 210 40 60 210 160 210 210 AK Factor Test 1 154 135 103 129 130 Final CFM 115 116 114 117 115 Does Not Exist 150 130 80 146 81 152 121 157 33 49 156 124 159 154 % of Design DATE 6/25/2012 PROJECT Fit 4 Life SYSTEM All Systems READINGS BY JOB NUMBER TB -12 -25 2 WL(,) co Z cn V 1— Z Z 0 V W 2 co d' M CO 0 N CO ti CO LL to N 0) 00 co N CO C d t) O ERTIFIE REMARKS Grilles Were Proportionally Balanced Luis LI Prats Mechanical Systems & Controls Inc. 0177 Expires 07/17/2014 IONAL BALANCING COUNCI 13of 14 UNIT DATA FAN NUMBER FAN NUMBER FAN NUMBER Unit Designation (TAG) EF -1 A EF -2 B EF -3 C DATE Type Of Service Bathroom Bathroom Bathroom Manufacturer Broan Broan Broan 6/25/2012 Model Number S5OU 1 S5OU S5OU PROJECT TEST DATA 1 DESIGN AC N I ACTUAL DESIGN Total Airflow (CFM) 50 60 50 ACTUAL 1 DESIGN ACTUAL Fit 4 Life 51 1 50 55 SYSTEM All Systems READINGS BY JOB NUMBER TB -12 -25 LiJ CO Z LL ti • CO i ii ; (/) J _11 0 � M) I-- 0 0D U <0 �m Q 0 �03 0 N W ti o E 2 o N c ERT IFIE Luis U Prats Mechanical Systems & Controls Inc. #0177 Expires 07/17/2014 NATIONAL BALANCING COUNC L� 14 of 14 t 1 Njj BUILDING PERMIT APPLICATION FBC 20 Miami Shores Village Building Department 10050 N.B.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795.2204 Fa= (305) 756.8972 INSPECTION'S PHONE NUMBER (305) 762.4949 Permit Type: MECHANICAL 1ii NOV 2 9 2A11 BY: Permit No. WC> 1 aaat) Master Permit No 11-1693 OWNER: Name (Fee Single Tittehotder):Shores Square Investments Address9017 Riseaynp R117td City: Mi amt ShnrA Tenant/Lessee Name: Edmundo R. Tamayo . M.D. Email :tama157 @bellsouth.net Phoned: 3 05 - 7 7 9 - 8 04 8 State: FT. Zip: 33138 P:305- 835 -6322 JOB ADDRESS: ,9 02 5 >3 i_seayn T31_vd _ City: Miami Shores Folio/Parcel#: 1132060110051 -25 Is the Building Historically Designated: Yes County: Miami Dade Zip: 33138 NO Flood Zone: CONTRACTOR. Company Name: e.5.(1/7:3- dfr oty-It P 1144 Address: 'Y % -61 / City: i State: t g ;6') Qualifier Name: (} State Certification or Registration d: Contact Phoned: DESIGNER A rnhiteet/Engineer: Phone#: hp: 66 Phone#: 30. ?eff- ', 61C Certificate of Competency t: Email Address: re V /�1'arrIA0 6,4eket,04 • "tef Phoned: Value of Work for this Permit: $ 3 CriNQ Sguare/Linear Footage of Work 5 , 000 SF Type of Work: °Address °Alteration Description of Work: �i1s G.l� (c ) CLtrrter r »f- 4A fy e ,4// f.M7k f /0w ✓` x ivel 4° 7 i/ t zxda.eau4 d' •► s CINew tlltepairlRepiace Qllentolition o,c. *+ Submits Fee $ Ponnit Fee $ \ D .`� "�CCF $ coicc $ Scanning Fee $ Radon Fee $ Notary $ Training/Education Fee $ Tediumtlogy Fee $ Double Fee $ _ Structural Review $ DBPR $ Bond $ t \o�.cp :WDUE$ it Vb\\l2 qd) Bonding Company's Name (if applicable) N/A Bonding Company's Address N/A City State �p Mortgage Lender's Name (if applicable) Mortgage Lender's Address N/A City State Zip N/A Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has connnenced prior to the issuance of a permit and that all work will be performed to >neet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit mum be secured for ELECTRICAL WORK, PLUMBING, SIGNS, WELLS, POOLS, FURNACES, BOILERS, MINTERS, TANKS and AIR CONDITIONERS, ETC— OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating consttemicat and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: Asa conditicm to the issuance of a building permit with an estimated value exceeding $25(7tt. the applicant muss promise in good faith that a copy of the notice of rrmtmencement and construction lien lays= brochure will be delivered to the person whose property is subject to anadtment. Also, a certified copy of the recorded Ralice of conunencentent must be posted at the jab site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of suit pasted notice. the inspection wilt not be approved and e t einspectlon fee will be charged Signature Owner or Agent The foregoing instrument was aciotowledged before me this day of , 20 _, by who is personally known to me or who has produced As identification and who did take an oath. NOTARY PUBLIC: Sign: Print My Commission Expires: Contractor The fling instrument was acknowledged before me this !"6.- day of 40ovArr►.4 ev-, 20 _t, by who is personally kmmo to me or who has produced as identitieattn NOTARY PUBLIC: Structural Review (Revised 07110107)Qtevi®ed 05110P�) Revised 3/15109) Sign: Print: My Conomissio did take:ati bdtlgODRIGUEZ # DD804481 July 08, 2012 -GryService.com MAO. #D'.`rEr: -;;' IRES July 08, 2012 4b m7)388-0153 FloridallotaryService.com Zoning Clerk Miami Shores Village Building Department 10050 ALE2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 Fax: (305) 756.8972. AIR CONDITIONING REPLACEMENT DATA PERMIT NUMBER: MC This form must accompany ALL air conditioning replacement permit applications. Each unit change-out must be on its own data sheet. Multiple units on single sheets are not acceptable. Job Address (where the work is being done): City: Miami Shores Village County: Miami Dade Zip Code: ALL CONDENSING UNITS MUST BE ON A 4 INCH SOLID CONCRETE SLAB ALL UNITS MUST COMPLY WITH F.E.M.A MINIMUM FLOOD ELEVATION A COPY OF THE CONTRACT IS REQUIRED WITH ALL SUBMITALS Aid (AHRI) DATA SHEET REQUIRED Change Disconnecting means: YES ❑ NO ❑ ARHI Sheet Attached: YES ❑ NO ❑ Contract Attached: YES ❑ UNIT BEING REPLACED DATA NEW UNIT MANUFACTURER AHU or PKG. UNIT MODEL # COND. UNIT MODEL # KW HEAT NOM TONS AHU CU PKG 1) M.CA AHU CU PKG AHU CU PKG 2) M.O.P AHU CU PKG AHU CU PKG 3) VOLTS AHU CU PKG PKG UNIT 1 I PKG UNIT 1 1 EER/SER YES NO REPLACING DUCTS YES NO YES NO REPLACING THERMOSTAT YES NO YES NO NEW eCONCRETE SLAB YES NO YES NO NEW ROOF STAND YES NO YES NO NEW RETURN PLENUM BOX YES NO 1. Minimum Circuit Ampacity (tire Size):. 2. Maxhnum Overcurrent Protection (Fuse/Breaker Size): 3. Voltage of Circuit (208<24W480): 4. Size Disconnecting Means: Contractor's Company Nam= Rao Can t< try? (0, phone: 30," tir -,) 63 State Certificate or Re bstion N. C Q- 0-6:? 60 Certikete of Cropetency N. Signature (a3us8Refs signature only) Date: /! /,S /,�O// 11 -1693 P ID: ILGU 1 CERTIFICATE OF LIABILITY INSURANCE DAT01111112 THIS CERTIFICATE IS ISSUED AS A MATTER OF INFORMATION ONLY AND CONFERS NO RIGHTS UPON THE CERTIFICATE HOLDER. THIS CERTIFICATE DOES NOT AFFIRMATIVELY OR NEGATIVELY AMEND, EXTEND OR ALTER 'THE COVERAGE AFFORDED BY THE POLICIES BELOW. THIS CERTIFICATE OF INSURANCE DOES NOT CONSTITUTE A CONTRACT BETWEEN THE ISSUING INSURER(S), AUht1R12ED' REPRESENTATIVE OR PRODUCER, AND THE CERTIFICATE HOLDER. IMPORTANT: If the certificate holder Is an ADDITIONAL. INSURED, the pollcy(les) (must be endorsed. If SUBROGATION IS WAIVED, snbjert to the terms and conditions of the policy, Certain policies may require an endorsement, A statement on this cortliic¢ite does not confer rights to the certificate holder In lieu of Stich endorse= s PRODUCER 305 462 -5244 All Safe Insurance 7171 Coral W 7884884244 Miami, FL 38158 #208 Jorge Pena, PIAM �^ -imTAGT + } ire, No[: A�AIt = " R USIOMENIOIe ESULI INSURER(S)AFFORDS *COVERAGE NAICB INSURED Results AirCondlontloning Company 7451 Nw 72 Ave Miami, FL 33166 iNsuRERA :WESTERN WORLD OCCUR INsurom a : BRIDGEFIRLD 10701 awsuRta c :COMMERCE AND INDUSTRIES 10/R8112 nusURER a • $ 1,000,000 INSURER 9 • OAMABET d RiATED S tE a ecnate ne[ INSURER F : 1] COVERAGES CERTIFICATE NUMBER: REVISION NUMBER: THIS IS TO CERTIFY THAT THE POUOIES OF INSURANCE LISTED BELOW HAVE REEN,ISSUED TO THE INSURED NAMED ABOVE FOR THE POLICY PERIOD INDICATED. NOTWITHSTANDING ANY REQUIREMENT, TERM OR CONDITION OF ANY CONTRACT OR OTHER DOCUMENT WITH RESPECT TO WHICH THIS CERTIFICATE MAY SE ISSUED OR MAY PERTAIN, THE INSURANCE AFFORDED BY THE POLICIES DESCRIBED HEREIN IS SUBJECT TO ALL THE TERMS, EXCLUSIONS AND CONDITIONS OF SUCH POLICIES. LIMITS SHOWN MAY HAVE BEEN REDUCED BY PAID CLAIMS waft LIR TYPE OF INSURANCE )N R WW POLICY NUMBER iMaIO ppLYY1 10/28111 �p Mme. A SALLUABPJ1Y COMMERAA GENERALUAeiL1TY —1 CLAIM$43ADE BIIPDED DEO $260 OCCUR NPP132277 10/R8112 EACH OCCURRENCE $ 1,000,000 X OAMABET d RiATED S tE a ecnate ne[ S � �,000 1] • MED EXP {Ater orin Qermn) $ 5,0011 X PERSONAL a ADV INJURY S 1,000,000 GENERAL AQC TE $ 2,000,000 Gan. AGERESATE LIMIT I POLIOY 1 4. APPLIES PER: PRODIIGTS • COMP/OP A00 9 2,000,000 X I I LOC $ AUTOMOBILE LIABILITY ANY AU1t1� HIRED AUTOS NON•0M4EDAUTOS COMBINED SINGLE UMrr $ — BODILYINJURY(Farecddent) $ _ PROPERTY DAMAGE $ — $ O X uMBI1E11A 1,1313 EXCESS LIAB X Ott CLAIMS -MADE Ef3U015273340 11109111 10129112 EACH OCCURRENCE 9 1,000,000 AGGREGATE $ 1,000,000 DE UOTBBLE RETENTION $ $ $ B AND EMPLOYERS' S LIA p.rffy PROPRIETOWPART pyaeene,tlatory N N DEsc ON OF GPERATIaNS NIA 0830.3567 01/26/11 01/28/12 YVC: b A .X p� MRS UTn+9Y• E.L EACH ACCIDENNT 5 600,000 E.L. DISEASE- EA EMPLOYEE $ 500,000 below EL DISEASE . POLICY LIMIT $ 500,000 Maw= OF DPFRATJONS I LOCA710N9 J VEHICLES (Arendr ACbRD 101, Ammons Remeri%Sdrdauls, If mom egmao IS regffbed) VILMIAM VILLAGE OF MIAMI SHORES 10090 NE a AVE MIAMI SHORES, FL 33138 I . �...- -__...... -•• . SHOULD ANY OF THE ABOVE DESCRIBED POUCIES BE CANCEU.Eb BEFORE THE EXPIRATION DATE THEREOF, NOTICE WILL BE DELIVERED IN ACCORDANCE WITH THE POLICY PROVISIONS. AUTHORIZED REPRE, ACORD 25 (2008109) �? 9988.2009 ACORD CORPORATION. All lights reserved. The ACORD name and Togo are registered marks of ACORD