RF-07-2126May 23, 2008
To: Miami Shores Village
Building Department
10050 NE 2nd Avenue
Miami Shores, FL 33138
€BB
Engineering & Testing Co.
7450 Griffin Road, Suite 140, Davie, FL 33314
Phone: (954)581 -7115, Fax: (954)581 -2415
www.cebb.net
Roof Tile Uplift Test Report
Test Date:
May 22, 2008
Permit #:
RF -10-07 -2126
Address:
Longman Residence
844 NE 98th Street, Miami Shores, FL.
Contractor:
Reliant Roofing Systems, Inc.
Roof Pitch:
3:12
Attachment method:
Two Component Polyurethane Foam Adhesive — PolyPro AH 160 (NOA 06- 0201.02)
Tile Type:
Altusa Roof Tile (NOA 06- 0706.09)
Device Used:
"IMADA" DPS 110 force gauge (Serial # 199579E)
Total Sloped Roof Area:
15.00 squares
All Testing is in strict accordance with the Florida Building Code, 2004 Edition, High Velocity Hurricane Zone —
Testing Application Standard (TAS) 106.
Roof Area 15.00 squares
Total Number of Tests
Number of tests Passed
% Passed
Field Area (1): 8.00 squares
8
8
100%
Perimeter Area (2): 7.00 squares
7
7
100%
No. of Corner Areas (3): 6
6
6
100%
Ridge/Hip Areas: 112 pcs
6
6
100%
Based upon the field tests, I certify that 100% of the static up -lift tests 'PASSED" the testing criteria of 35.0 lbf loads,
and meet the attachment resistance for adhesive Set Systems, as specified in the NOA.
Should you have any questions regarding the above, or if require additional information, please do not hesitate to
contact this office.
Sincerely,
CeBB Engineering & Testing Co.
(NOA 07 -1002. a ses NOA 06- 0320.14)
MAY 2 `R 2008 4(
uard`C. Bad. ,
Fla. Reg. No: 5'99
.E.
Cc: Reliant Roofing Systems, Inc
Enc. Location Sketch
Calibration Certificate
PGT Industries, Inc.
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
C. CALCULATIONS
1. Anchor Calculations and structural analysis, complying with FBC -2004, prepared by
PGT Engineering, dated 10/26/06, signed and sealed by Robert L. Clark, P.E.
Complies with ASTM E1300 -98 and 02
D. QUALITY ASSURANCE
1. Miami Dade Building Code Compliance Office (BCCO).
E. MATERIAL CERTIFICATIONS
1. Notice of Acceptance No. 05- 1208.02 issued to E.I. DuPont DeNemours for "DuPont
Butacite PVB Interlayer" dated 01/05/2006, expiring on 12/11/2010.
2. Notice of Acceptance No. 03- 0421.01 issued to Solutia Inc. for their "Saflex HP a
polyvinyl butryal interlayer for lamination of glass" dated 05/22/2003, expiring on
04/14/2008.
F. STATEMENTS
1. Statement letter of compliance, and no financial interest, dated 08/10/2007, signed and
sealed by Robert L. Clark, P.E.
2. Laboratory compliance letter for Test Report No. FTL- 5330, issued by Fenestration
Testing Laboratory, Inc., dated 07/18/2007, signed and sealed by Carlos S. Rionda,
P.E.
2. Laboratory compliance letter for Test Reports No.'s FTL- 4858 and Fria- 4859,
issued by Fenestration Testing Laboratory, Inc., dated 03/08/2006, signed and sealed
by Edmundo Largaespada, P.E.
(Submitted under NOA# 06- 0405.06)
G. OTHER
1. Notice of Acceptance No. 06- 0405.09, issued to PGT Industries, Inc. for their Series
"Alum. Horizontal Roller Window, Impact ", approved on 12/21/2006 and expiring on
12/21/2011.
J
Manuel Perez,
Product Control Era
NOA No 07- 0815.09
Expiration Date: December 21, 2011
Approval Date: January 03, 2008
II .3