Loading...
437 NE 102 St (4)1 1 1 LG ENGINEERING SERVICES, INC. Consulting Engineers North Office: 7370 N.W. 36th Street Suite 374 Miami, Florida 33166 Tel: (305) 994 -8128 Fax: (305) 994 -8135 Mike Wilson Roofing 870 Northeast 122 Street Miami, Florida Project: ' Dear Sirs; South Office: 13380 S.W. 131 Street Suite 120 Miami, Florida 33186 T1LE UTLIFT TEST Lartein Residence 437 Northeast 102 Street Miami Shores, Florida Information provided by client: Permit Number: 44963 Date Completion: July 31, 1999 Roofing Contractor: Mike Wilson Roofing LG Engineering Services, Inc. Project Number: LG99 - 0966 (Testing Laboratory Certificate #99- 0609.01) Based on our test results', we conclude that : the installation of the roof the at the a project meets the'test requirement outlined'in the above mentioned p rotocol Aua a copy of our test report for your review ove re August 3, 1999 In accordance with your request and authorization, a representative of LG Engineering Services, Inc. completed the Roof Tile Uplift Test at the above referenced project. This testing was performed in general accordance with Roofing Application Standard RAS No.106 -- Standard procedure for field verification of the bonding of mortar or adhesive set tile system and mechanically attached, rigid, discontinuous roof systems. The total of the tested roof surface area was less than 5000 square feet, and the mean height of the roof is less than 20 feet above ground surface. The type of tile used for this project was reported to be Bermuda Roof Tile. This tile was reported to have been foamed in place. At the time of this testing, one test for every corner, one test for every 100 square feet of roof tile in the perimeter area and one test for every 200 square feet of roof tile in the field area were tested. Initially the entire area of the roof was examine for loose tile. More than 10% of the roof tile located in the field area and more than 20% of the roof tile at the roof perimeter and corner were physically examined. erence leasefind LG Engineering Services, Inc. appreciates the opportunity of assisting you in this project. If you have any questions or if we may be of further assistance, please do not hesitate to contact the undersigned. Respectfully submitted; LG Engineering Services, Inc. M•hama� onny.Salleh Project Manager TJLE_UP.LI r_TEST Laricin Residence 437 Northeast 102 Street Miami Shores, Florida Report of TILE UPLIFT TEST for Laricin Residence 437 Northeast 102 Street Miami Shores, Florida Project Number: LG99-0966 est Number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Test Load Obfl 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 '..eStStatUS Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass LG Engineering Services, Inc. -- Tile Uplift Test Result -- Project Number: LG99-0966, Page 1 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass LG Engineering Services, Inc. -- Tile Uplift Test Result — Project Number: LG99 -0966, Page 2 —North- 5 5 36, 3 4o 3g I cf3 32. t I IQ 11 —! — — i 35 LG Engineering Services, Inc. -- Tile Uplift Test Result -- Project Number: LG99 -0966, Page 3 FEES: PERMIT A 3 RADON PERMIT APPLICATION FOR MIAMI SHORES VILLAGE Job Address 7 iVE • Tax Folio Da Legal Description ee Owner/Lessee / Tenant H&.. 1 ,, /2S. L Owner's Address X3 7 NE; /0a A S /%0€7 Contracting Co. / • CCA/j0 • Qualifier MI& - 1— •up: state # C 6G op (.176 Competency # Architect/Engineer Address Address Bonding Company Mortgagor Address Permit Type (circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL OOFING AVING FENCE SIGN WORK DESCRIPTION /� � C r �514z l 6 � , / ,-4D /l.edha e C 4_,)4 ( Q / e w i r - : /e i7 (es 6 /r 7: 7/e99)-rz) • Square Ft. /0 V / S a/vi o s) - Estimated Cost (value) Ol iPeD ' 6 --t- - 2 1 1. • WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.) Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK. OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. Furthermore, I authorize the above -named c • 'tractor to do the work stated. L 'a e-A-Zz . 2 - beaii.& El i' f f' Signature r and/or iCgond' ppaa �yy-�•,fi st vS¢�s�'i� VYi 1. �J trilifH%r'IM M1 01 5icr Exp. p vol nr4By Seein ,://6(99 r anent Date Notary My Comrm ssi hxpues: $ ate APPROVED: Zoning Building Mechanical Plumbing C.C.F. r---- NOTARY " O BOND 3 co TOTAL DUE 34.a . b� 1 No Master • Permit # t 9 1 / 96 3 Phon ,(2.S / "7.5 % cJ a / 56 . /e /s- GV. /�s / /t- � Ii.4a - Ins. Co. • • i s g illif : e' p e.i .' otox rm`ilDik ' !/, •Alder .rig. 4 ! . j Ci: s r, 4 • M � N` En,,I 'sGLs LVAt'"t' a u r r t i:3::: Y •. Z0 tail i ` d Kr! v1 ;k: r4oPf on Notary My Commission Expires: Electrical 6 rervaier-BerifErdra Date Engineering A RECORDED COPY MUST BE POSTED ON THE JOB SITE AT TIME OF FIRST INSPECTION . PERMIT NO. TAX FOLIO NO. STATE OF FLORIDA: COUNTY OF DADE: THE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with Chapter 713, Florida Statutes, the following information is provided in this Notice of Commencement. is 1. Legal description of property and street address: Y /37 Al.' ET• , 03duel �• / A/1 ; S / -ieVe 33 /". . - 2. scription of improvement: 7/4 6 � � �� 777 /Gccre 3. Owner(s) name and address: j1 4 S ( - 0 0 1 - & - A / Interest in property: 44/e/272 Name and address of fee simple titleholder: 4. Contractor's name and address: / 2 ,4-//d ; ,197.)7 ioaa/ s ed. /s1 /L ;4 Ft 3 1t 6 5. Surety:(Payment bond required •y owner from contractor, if an Name and address: j/ 4- • `� C1 Amount of bond $ 6. Lender's name and address: 7. Persons within the State of Florida designated by Owner upon whom notices or other documents may by Section 713.13(1)(a)7., Florida Statue's, N/ Name and address: 8. In addition to himself, Owner designates the following person(s) to receive a copy of the Lienor's Notice as provided in Section 713.13(1)(b), Florida Statutes. Name and address: 9. Expiration date of this Notice of Commencement: (the expiration date is 1 year from the date of recording unless a different date is specified) S&gnawre of Owner Print Owners Name c2 A,Q OL At.. ki >v /, Sworn to and subscribed before me this X day of TV• Notary Public Print Notary's Name My Commission Expires: ti)twita* t)o'tt2rt $ ;LIZ M hi: rl. WILSON Comm Exp. =VW NOW 3 ` 0 ,1999 . 99R314839 1999 JUN 17 11.06 E OF FLORIDA, COUNTY OF DADE i ;,:43ESvea11:vt::(st afru') orh:nalfJi f in 45 is olaco on c l kl W MESS my h "n and f ▪ %i HARVEY RUVIN py of tho day of A u 31 Soal. o Circuit and County Courts e served as provided Prepared by /eV (1 -- ) i /$011 • 870 Ai- - 6 : /a2 s Address: At/0 W / 4-4. * 4e--7; a 3 /6l 5726 12301.52 2/93 APPENDIX "F" REQUIRED O\YNERS NOTIFICATION FOR ROOFING CONSIDERATIONS As it pertains to his Appendix F ", it is the responsibility u: tiiC rooting contractor to provide the o'. t:2r with th required roofing permit, to provide the owner with this appendix and to explain to the owner the content of this form. The provisions of Chapter 34 of the South Florida Building Codc (SEBC) govern all the minimum requirements and standards of the industry for roofing system installations. Additionally the following items should be addressed as part of the agreement between the owner and the contractor. The owner's initial in the adjacent box indicates that the item has been explained. ' 1. Aesthetics- \Vorkmanship: The workmanship provisions of Chapter 34 are for the purpose of providing that the roofing system meets the wind resistance and water intrusion perform:met standards. Aesthetics (appearance) issues are not a consideration with respect to workmanship provisions. Aesthetic issues such as color or architectural appearance, that are not part of a zoning cod_, should be addressed as part of the agreement between the owner and the contractor. 0 2. Renalling Wood D'ccks: When replacing roofing. thc existing wood roof deck may have to be renailed in accordance with the current provisions of Chapter 29 of the SFBC. (The roof deck is usually concealed_ prior to removing the existing roof system) _-� 3. Common Roofs: Common root's are those which have no visible deliner.tion between neighborinn units (i.e. townhouses, condominiutns, etc In buildings with common roofs. the roofing contractor and /or «•ner should notify the occupants of adjacent units of roofing work to be performed. • 4. Exposed ceilings: Exposed. open beam ceilings are �vttere the underside of the roof deckin_u can bc . sewed from below. The owner may wish to ntaintain the architectural appearance. therefore, roofing, nail penetrations of the underside of the decking may not bc acceptable. The SFBC provides the option of maintaining this appearance. V \ S. Pending Water: The current roof system and!c'r deck of die buildinu may not drain well 'and may cause water to pond (accumulate) in low-lying areas of the roof. Pending can be an indication of structural distress and may require thc review of a profes�:on::I structural cn_nteer. Poading may shorten the life expectancy and performance of the new roofing system. Po :[dime coaziitions may not be evident until the oneinal r fing system is removed. Ponding conditions should be corrected. �' 6. Ovcrflolt' Scuppers (wall outlets): It is required that raimv'ater flog': off so that the roof is not overloaded from a build up of water. Perimeter /cd:c walls or other roof extensions may block this discharge if overflow scuppers (wall outlets) are not provided. It may b_ necessary to install overflow scuppers in accordance with Chapter 23 of the SFBC. - 7. Ventilation: Most roof structures should have some ability to vent natural airflow through the interior of the structural assembly (the building itself). The existing amount of attic ventilation shall trot be reduced. It n ay be beneficial to consider additional ventinz which can result in extcndin�u the service life of the roof. t S. The owner may contact the Miami County Consumer Services Department for further information re_t rding the above. z� `l6z 6/l il Signature Date Ong ncr's!Aecn Contractor's Signature I Contractor's Name: 1 .1.4. __J_,. ROOF CATEGORY U (Low Slope Application) ❑ (Nail -On Tile) (Mo I ❑ (Asphalt%Fibergiass Shingles) L7 ( Metal RoofslWood Shingles & Shakes) ( (Other) ,�� ROOF TYPE t� Re- roofing ❑ Recovering 0 Repair u Mainienan N ce Flat Roof Area (ft') ���• Roof Area o e Slopd G s,' /�� _._ ,42• . ►� pie r Sloped - (••) s vial (ft) 2_ ��. 44.1 Master Permit No. Exposure category (p ASCE 7__8a : G � Building Classification category (per • •--� 7-88): .�uuu,,,� �iassu,caiion category (per ASCE 7 -88 table 1): = O New Roof a F Ft. Deck type: l V. 6 ti( 34 Fastener Type: Field: Perimeter: Corner: DETAIL 1 & 2 Appendix "E" UNIFORM ROOFING PERMIT APPLICATION PROCESS No. d er ATTACH ME NJ SPACING job Address: ROOF HEIGHT AND SYSTEM DETAILS (Draw details as needed) Deck type:I mi.as sctcttT # � 2 - Z nOOP SLOP[ D K T A I L -V- 3 z� (Pmaxl: X X (Aerodynamic Multiplier): ) - (PMOX2: x X (Aerodynamic Multiplier): (Pmaxi: 1 � " 3 . 1 ? (Aerodynamic Multiplier): 2 C Appendix "E" UNIFORM ROOFING PERMIT APPLICATION PROCESS No. o 4-s Insulation: [ ,. //A - SLOPED SYSTEM DESCRIPTION Fastener type & spacing: Cap Shed: Roof Covering: Drip edge: TILE CALCULATIONS Zo / Ie �� mg:- - M U . 2 - PCA: m - 2 M rZ • : 7 PCA: II 8•5o - M 6.2 0 = M I� :1 PCA: // � It .S• / 2 ' 4- L / e0 /04 vm►rgo ? ) • Nz >! ' 4-4/Ac S.1K- std ' - - d. ATTACHMENTS REQUIRED 1) Fire Directory Listing Page 2) Dade County Product Control Notice of Acceptance -Cover Sheet a) Specific System Description b) Specific System Limitation c) General Limitations d) Applicable Detail Drawings 3) Municipal Permit Application 4) Other Component Approvals /) (-21 01/13/99 12:08 MEDITERRANEAN ROOF TILE -) 3058999490 561 338 5391 03/09/98 NON 16:07 FAX 591 338 5391 LIFETILE METROPOLITAN DAOE COUNTY. FLORIDA METRO -DADE FLAGLER BUILDING BUILDING CODE COMPLIANCE OFFICE METRO.OADE FLAGLER BUILDING 140 WEST FLAGLER STREET. SUITE 1903 MIAMI, FLORIDA 33130 -1563 (305) 375.2901 FAX (30S) 375.2908 NOT PRODUCT CONTROL ICE O ACCEPT PRODUCT CONTROL, D S 2902 Monier Roof Tile FAX (305) 372 -6339 135 N.W. 20 St. Boca Raton, FL 33431 Your application for Product Approval of: Bermuda Flat Tile under Chapter 8 of the Metropolitan Dade County Code governing the use of Alternate Materials and Types of Construction, and completely described in the plans, specifications and calculations as submitted by: Redland Technologies, The Center for Applied Engineering, Ise.. and Professional Service Industries, Inc.. -.- has been recommended for acceptance by the Building Code Compliance Office to be used in Dade County, Florida under the specific conditions set forth on pages 2.12 and the standard conditions on page 13. This approval shall not be valid after the expiration date stated below. The Building Code Compliance Office reserves the right to secure this product or material at any time from a jobsite or manufacturer's plant for quality control testing. If this product or material fails to perform in the approved manner, the Building Code Compliance Office may revoke, modify, or suspend the use of such product or material immediately. The Building Code Compliance Office reserves the right to revoke this approval, if it is determined by the Building Code Compliance Office that this product or material fails to meet the requirements of the South Florida Building Code. The expense of such testing will be incurred by the manufacturer. ACCEPTANCE NO.: 96- 0528.06 Renews No.:24. 1221.08 EXPIRES: 01/08101 Raul Rodriguez Product Control Supervisor THIS IS THE COVERSHEET, SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL CONDITIONS !WILDING CODE C This application for Product Approval has been reviewed by the Metropolitan Dade County Building Code Compliance Office and approved by the Building Code Committee to be used in t .c County, Florida under the conditions set forth above. a‘ Charles Danger, P.E. Director Building Code Compliance. Dept. APPROVED: 01/08/98 l Metropolitan Dade County NO.209 901 Internet mail address: D0stmaster asuildingcodeonline.com iNomepege:'httpar wrw.buildingeodeontine.eom l� 00 1 . 03/09/98 NON 16:08 FAX 581 338 5391 • 0 I 1 licant: Monier Roof Tile 135 NW 20 St. Boca Raton, FL 33431 PRODUCT CONTROL NOTICE OF ACCEPTANCE ROOFING SYSTEM APPROVAL Category: Prepared Roofing Sub- Cgeeory: Tile Tie: Mortar Set/Adhesive Set §up -Tune: Concrete JEAN ROOF TILE -, 3058999490 MONIER LIFEPILE System Description Contact Reese H. Moody Technical Service Accessories Manager 135 N.W. 20 St. Boca Raton, FL 33431 (407)338-8200 Page 2 of 13 Product Control No.: 96- 0528.06 Product Control No.: • 96. 0528.86 Approval Date: January 8 Expiration Date: Jauuart► 8.2001 Monier Roof Tile is a member of the Redland Group, a world wide producer of primary building products and roof tile. Monier manufacturers concrete roof tile for nail -on, mortar set or adhesive set applications in plants throughout the United States ranging from Washington State to Florida. All tile is manufactured from extruded concrete consisting of Portland Cement, plasticizer, iron and metallic oxides, and blended aggregates. This Product Control Approval relates to Mo nier s "Bermuda Flat" tile profile. Refer to a ,• at Product Control A u• • als • ether tile • files. Monier sells tile systems through local distribution and directly to consumers. All profiles have matching trim pieces used for rake hip, ridge hip, and valley terminations. Tile system accessories such as underlayment, ventilation systems and flashing systems are also available. These accessories are manufactured for all profiles and form a part of this Product Control Approval. Monier's "Bermuda Flat" roof tile has been tested in compliance with the South Florida Building Code requirements for concrete, mortar or adhesive set tile applications. The minimum roof slope for Monier's "Bermuda Flat" mortar or adhesive set tiles shall be 2 ":1 See the "Profile Drawing" section in this approval for the "Bermuda Flat" profile drawing. The Monier "Bermuda Flat" tile profile has been tested for both wind characteristics and static uplift performance, therefore, any consideration for installation shall be done as a 'Moment Based System'. Data for attachment calculations is noted in Tables 1 through 3 of this approval. Frank Zuloaga Roofing Product Control Examiner NO. 209 D02 0002 �. . u • rr.cr ix MUUr I 1 Lt -+ 3r73$99Y4` U NO. 209 P03 03/09/98 NON 18:09 FAX 581 338 5391 MONIER LIFETIIE ®003 TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT Page 3 of 13 Product Control No_: 96- 0528.06 • Test Product Product Dimensions Specification: Description Bermuda Flat Flat 1 r< 15" PA 112 Flat, interlocking, extruded Tile w = 10 3 /g" concrete roof tile equipped with Ph" thick two nails holes. For mortar set or adhesive set applications. Trim Pieces . 1= varies PA 112 Accessory trim, concrete roof w = varies pieces for use at hips, rakes. ridges varying and valley terminations. thickness Manufactured for each tile profile_ Frank Zuloaga Roofing Product Control Examiner U1 13:‘JV IJ:by MEDITERRANEAN ROOF TILE i 3058999490 03/09/98 MON 18:09 FA% 581 338 8391 MONIER LIFETILE la 004 130 Felt Product #43 Coated Base Sheet Mineral Surface Cap Sheet Rainproof 11 Ice and Water Shield TRADE NAMES OF PRODUCTS MANUFACTURED OTHERS Dimensions N/A N/A N/A Lenzingtex -ZB 140 59" x 164' roll Underlayment 221bs/rolt 30" x 75 roll 36" x 75' roll or 60 "x75'roll 36" x 75' roll Test Specifications ASTM 0 226 type ll ASTM D 2626 ASTM D 249 PA 104 PA 104 PA 103 Page 4 of l3 Product Control No.: 96- 0528.06 Product Description Saturated organic felt to be used as a nailed anchor sheet. Saturated and coated organic base sheet for single or double ply underlayment. Mineral surfaced asphalt roll roofing for use as a top ply in a double ply undertayment system. Single ply. nail -on underlayment. Single ply, nail -on underlayment with 2" self- adhering top edge. Self- adhering underlayment for use as atop ply in a two ply underlayment system with approved 130 or 043 as the base layer. Manufacturer generic generic . generic Lcrating Performance, Inc. PCA 194- 0S27.05 Protect -O -Wrap, inc. PCA 194 -0714.01 W.R. Grace Co. PCA 192-1116.01 Frank Zulongs Roofing Product Control Examiner NO.209 904 e 1 % 1,5 12:10 MEDITERRANEAN ROOF TILE 4 3056999490 NO. 2 ©9 005 03/09/08 MON 18:09 FAX 561 338 5391 1IONIER LIFETILE Product Mopping Asphalt Flashing Cement Asphalt Primer Roofing Nails Tin Caps Tile Nails Dimensions N/A N/A N/A min. 12 ga. with 3 /g" head min. 32 ga. min. 1 o.d. max. 2" o.d. min. 8d x 2W' or min. 10d x3" Test Specifications ASTM 0 312 type jlt or IV ASTM D 4586 ASTM D 41 PA 114 Appendix E PA114 Appendix E PA 114 Appendix E Page 5 of 13 Product Control No.: 96- 0528.06 Product Description Manufacturer Asphalt for bonding generic a mineral surface cap to a mech. attached base sheet in a double ply underlayment system. Cut back asphalt based, asbestos free, fiber reinforced, trowel grade cement for repair and flashing applications. Cut back, asphalt based coating used to facilitate bonding of dissimilar materials. Annular ring shank, hot dipped. clectro or mechanically galv. roofing nails for use in underlayment attachment. Corrosion resistant circular disc for use in underlayment attachment Corrosion resistant, screw or smooth shank nails for additional tile attachment at eave tile courses. generic generic generic generic generic Crank Zuloaga Roofing Product Control Examiner cos 01/13/99 12:10 MEDITERRANEAN ROOF TILE -* 3058999490 03/09/98 LION 18:10 FAX 581 338 5391 MONIER LIFETILE Product Roof Tile Mortar ("Ti1eTiteT" ") Roof Tile Mortar ( "Quikrcte® Roof Tile Mortar #1140") Roof Tile Mortar ( "BONSAI -8 Roof Tile Mortar Mix ") Roof Tile Adhesive (POlypro® AH 160) Valley Flashing Drip Edge Dimensions N/A N/A N/A N/A min. 26 ga. min. 16" width min. 26 ga. min_ 2" face flange min. 2" deck flange Test Specifications PA 123 PA 123 PA 123 PA 110 Product Description Prepared mortar mix designed for mortar set roof tile applications. Prepared mortar mix designed for mortar set roof tile applications. Prepared mortar mix designed for mortar set roof tile applications. Adhesive designed for use in roof tile applicuions. ASTM A 525 Galvanized steel valley flashing PA I11 Page 6 of 13 Product Control No.: 96- 0528.06 Galvanized steel drip edge Manufacturer Bermuda Roof Company, Inc. PCA #94- 0614.01 Quikrete Construction Products PCA #94. 0808.01 W.R. Bonsai Co. PCA #94- 0628.03 Polyfoam Products, Inc. PCA/! 94- 0401.01 generic generic Frank Zuloaga Roofing Product Control Examiner NO.209 P06 ll 008 01/13/99 12:10 MEDITERRANEAN ROOF TILE -0 3058999490 03/09/98 MON 19 :10 FAX 501 338 5391 MONIER LIFETItE Test Agency The Center for Applied Engineering. Inc. The Center for Applied Enigneering, Inc. Redland Technologies Professional Service Industries, Inc. TEST REPORTS Tat Identifier 94 -084 94 -060A P0631 -01 224 -47099 Page 7 of t3 Product Control No.: 96- 0528.06 Test Name/Report Static Uplift Testing PA 101 (Mortar Set) Static Uplift Testing PA 101 (Adhesive Set) Date May 1994 March, 1994 Wind Tunnel Testing July 1994 PA 108 (Mortar Set) Physical Properties Sept, 1994 PA 112 Frank Zuloaga Roofing Product Control Examiner NO. 209 007 ® 007 ul 1.Y 77 1G• lei t iCLI I tKKHrVtHN KUUF I ILE 4 3058999490 03/09/96 MON :10 FAX 581 338 5391 MIONIER LIFETILE Deck Type: Deck Description: SYSTEM D: Slope Range: Underioyment: Roofing Tile: Comments: SYSTEMS Wood, Non - insulated New construction 19 /32" or greater plywood or wood plank. Mortar or Adhesive Set Application Page 8 of 13 Product Control No.: 96 0528.06 2 ":12" to 7 ":12" Note: System D is only acceptable in this slope range. Install choice of approved underlayteent system. noted on Page 1 of Dade County Protocol PA 120, in compliance with Section 3.02 of PA 120. Sec System Limitation 86. Install tile in compliance with PA 120 using one of the approved mortars or adhesives noted in this approval. Mortar or adhesive shall be `applied in compliance with the mortar manufacturer's Roofing Component Product Control Approval. The mortar or adhesive attachment shall provide sufficient attachment resistance expressed as a moment to meet or exceed the required moment of resistance determined in compliance with PA 115 or PA 127. The mortar and adhesive attachment data is noted in Table 3, attached. 1. For re -roof applications, 15 /32" plywood is an acceptable substrate. 2. For mortar set applications, the first three courses of tile shall be nailed with not less than one nail per tile. As an alternate, the first three courses of tile shall be applied in mortar over a single layer of minimum 12 ga. wire mesh with square openings of not less than 3 /8" which is mechanically attached to the deck with not less than one roofing nail every 1 ft For roof pitches from 6 ":12" to 7 ":12 ", every third tile of every fifth course. beginning at the eighth course, shalt be nailed with not less than one nail per tile.. Frank Zuloaga Roofing Product Control Examiner N0.209 008 e008 CU/ i.�/ 1::-• 1 • 1 ICL 1 1 CRRMI'IC1"V'1 RUUr 1 1 Lt - r SU7t377747U NU. eU7 VrJ7 03/09/98 NON 18:11 FAX 581 338 5391 MONIER LIFETILE ® 009 SYSTEM LIMITATIONS Page 9 of 13 Product Control No.: 96.0528.06 1. The standard minimum roof pitch for Monier "Bermuda Flat" mortar set or adhesive set tile applications is 2" rise in 12" run (2":12"). The maximum roof pitch for mortar set or adhesive set file applications is 7" rise in 12" run (7 " :12 "). 2. Monier's "Bermuda Flat" tile profile has not been tested for nail -on applications, therefore, System A (Counter - Batten Nail -On Application). System B (Direct Deck Nail - On Application) and System C (Horizontal Batten Nail-On Application) do not form pan. of this approval. • 3. System installation shall be in compliance with the system specifications outlined in this Product Control Approval. Mortar set or adhesive set tile shall be attached using an approved mortar or tile adhesive noted in this approval, the data of which is noted in 'fable 3 of this Approval. The method of attachment utilized shall provide sufficient attachment resistance expressed as a moment to meet or exceed the required moment of resistance determined in compliance with Dade County Protocol PA 115 or PA 127. 4. For mortar set applications, the first three courses of the shall be nailed with not less than one nail per tile. As an alternate, the first three courses of tile shall be applied in mortar or adhesive over a single layer of minimum 12 ga. wire mesh with square openings of not less than 3 /8" which is mechanically attached to the deck with not less than one roofing nail every 1 ft For roof pitches from 6 ":12' to 7 ":1 ", every third tile of every fifth course, beginning at the eighth course, shall be nailed with not less than one nail per tile. 5. For mortar set or adhesive set tile applications, a field static uplift test by a Dade County accredited testing agency, in compliance with Dade County Protocol PA 106, shall be required not less than 30 days after application to confirm tile adhesion. The results of this testing shall be reported to the Building Official and the installer stating that the application has passed or failed PA 106 testing. lithe application fails PA 106 testing, the report shall state which portion of the test was failed; Category i (examination for loose tile) or Category 2 (uplift testing of tile). Subsequent to testing. the installer may repair not more than 5% of field area tiles and 10% of perimeter area (i.e. ridgelrake) tilt with approved tile adhesive. The installer shall place an identifiable marking on each repaired tile for future reference. Any PA 106 re -test shall not include any marked tile. 6. For mortar or adhesive Set tile applications, 30/90 hot mopped underlayment applications may be installed perpendicular to the roof pitch prior to June 1, 1995 unless stated otherwise by the material manufacturer. Thereafter, 30190 underlayment systems shall be installed parallel to the roof pitch in compliance with Appendix 'A' of Dade County Protocol PA 120. 7. All tiles shall bear the imprint or identifiable marking of the manufacturers name or logo for identification in the field. ' 8. The Monier "Bermuda Flat" tile profile hes been tested for both wind characteristics and static uplift performance, therefore, attachment calculations for installation in compliance with Dade County Protocol PA 115 or PA 127 shall be done as a 'Moment Based System' uloaga Roofng Product Control Examiner ..., i a , J J a • a cL 1 crCrCFY 1C - w1 KUUr 11 Lt -; 3FMtriJJ4W NU. 209 D 10 03/09/98 MON 18:12 FAX 561 338 5391 MONIER LIFETILE ®olo r Page 10 of 13 Product Control No.: 96- 0528.06 SYSTEM LIMITATIONS (CONTINUED) 9. Applications for roofing permits shall include a completed Section II of the Uniform Building Permit, a copy of Monier Roof Tile's current specifications and details. a copy of this Product Control Approval and a copy of the Product Control Approval of any Roofing Component used in the proposed tile application. Reference shall be made to appropriate data for the required fire rating. 10. The applicant shall retain the services of a Dade County certified testing laboratory to maintain quality control In compliance with the South Florida Building Code and related protocols. Samples taken shalt be, in compliance with Dade County Protocol PA 112, Appendix 'A'. 11. Any amendments to these provisions shall be in compliance with Sections 203 and 204 of the South Florida Building Code. Frank Zuloaga Rooting Product Control Examiner 03/09/98 KON 18:12 FAX 581 338 5391 nUUr 1 1 LC -' ..X.1,-)0777.47V MONIER LIFETILE ® 011 DATA FOR ATTACHMENT CALCULATIONS Page I I of 13 Product Control No.: 96- 0528.06 Table 1: Aerodynamic Multipliers - >` (ft') from PA 108 Testing Tile X (ft') ). (ft') Profile Batten Application Direct Deck Application Bermuda Flat Flat Tile N/A 0.24 Table 2: Restoring Moments due to Gravity - M (ft•lbf) from PA 101 Testing ", 5 " :12" Tile Profile Monier Bermuda 'The e 3 :1 or less 5.20 5.12 5.01 6 ":12" 4.89 7" :12" Or greater N/A Table 4: Attachment Resistance Expressed as a Moment • M (ft -Ibf) . from PA 101 Testing Tile Profile Monier Bermuda Flat Flat Tile Tile Application Mortar Set Adhesive Set Attachment Resistance Voniml 39.00 118.90 rank Zuloaga Roofing Product Control Examiner E 4U. Gr77 W 1 1 JU 03/09/98 NON 18:12 FAX 581 338 S391 MONIER LIFETILE PROFILE DRAWING BERMUDA FLAT FLAT TILE Page 12 of 13 Product Control No.: 96.0528.06 Frank Zuloaga Roofing Product Control Examiner NU. U7 1, 012 11- -' JU:70777'6 03/09/98 ION 16:13 FAX 561 338 5391 DMONIER LIFETILE 9 This Acceptance contains pages 1 through 13. END OF THIS ACCEPTANCE Page 13 of 13 Product Control No.: 96- 052$46 Monier Roof Tile ACCEPTANCE NO.: 96- 0528.06 135 N.W. 20th St APPROVED : January 8,1998 Boca Raton, FL. 33431 EXPIRES : January 8, 2001 NOTICE OF ACCEPT CE STANDARA CONDITIOItS 1 Renewal of this Acceptance (approval) shall be considered after a renewal application has been filed and the original submitted documentation, including test supporting data. engineering documents, are no older than eight (8) years. 2 Any and all approved products shall be permanently labeled with the manufacturer's name, city. state. and the following statement: "Metro -Dade County Product Control Approved ". or as specifically stated in the specific conditions of this Acceptance. 3 Renewals of Acceptance will not be considered if a) There has been a change in the South Florida Building Code affecting the evaluation of this product and thrproduct is not in compliance with the code changes•. b) The product is no longer the same product (identical) as the one originally approved; c) Tithe Acceptance holder has not complied with all the requirements of this acceptance, including the correct installation of the product; d) The engineer who originally prepared, signed and sealed the required documentation initially submitted, is no longer practicing the engineering profession. 4 Any revision or change in the materials, use, and/or manufacture of the product or process shall automatically be cause for termination of this Acceptance. unless prior written approval has been requested (through the filing of a revision application with appropriate fee) and granted by this office. 5 Any of the following shall also be grounds for removal of this Acceptance: a) Unsatisfactory performance of this product or process; b) Misuse of this Acceptance as an endorsement of any product, for sales, advertising or any other purposes. 6 The Notice of Acceptance number preceded by the words Metro-Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is displayed, then it shalt be done in its entirety. 7 A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at all times. The copies need not be resealed by the engineer. 8 Failure to comply with any section of this Acceptance shall be cause for termination and removal of Acceptance. uloaga Roofing Product Control Examiner NU. X77 W 1 S ® 013 / \tit '3(1• r)rz fiR 04:10P ii,l_yr.)gtm Pr•.)g1.a 1.c T.ic-. PRODUCT CONTROL NOTICE OF ACCEPTANCE Polyfoam Products, Inc. 2400 Spring - Stuebner Road Spring, TX. 77383 Your application for Product Approval of: Polyfoam Ploducts "Tolvpro All -160" Roof Tile Adhesive under Chapter 8 of the Miami -Dade County Code governing the use of Alternate Materials and Types of Construction, and completely described in the plans, specifications and calculations as submitted by: The Center for Applied Engineering, Inc. and Miles Laboratories Polymers Division has been recommended for acceptance by the Building Code Compliance Office to be used in Dade County, Florida under the specific conditions set forth on pages 2 -14 and the standard conditions on page 15. This approval shall not be valid after the expiration date stated below. The Building Codc Compliance Office reserves the right to secure this product or material at any time from a jobsite or manufacturer's plant for quality control testing. If this product or material fails to perform in the approved manner, thc Building Code Compliance Office may revoke, modify, or suspend the use of such product or material immediately. The Building Code Compliance Office reserves the right to revoke this approval, if it is determined by the Building Code Compliance Office that this product or material fails to meet the requirements of the South Florida Building Code. The expense of such testing will be incurrcd by the manufacturer. ACCEPTANCE NO.: 98- 0303.02 Renews: 96- 0402.02 EXPIRES: 04/16/01 THIS IS THE COVERSHEET, SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL CONDITIONS BUILDING CODE COMMITTEE This application for Product Approval has been reviewed by the Miami -Dade County Building Codc Compliance Office and approved by thc Building Code Committee to be uscd in Dade County, Florida under the conditions set forth above. APPROVED: 04/16/98 Internet mail address: postmaster @buildingcodeonllne.com 954 47F3- 14617 P.02 METROPOLITAN DADE COUNTY, FLORIDA METRO -DADE FLAGLER BUILDING BUILDING CODE COMPLIANCE OFFICE METRO -DADE FLAGLER BUILDING 140 WEST FLAGLER STREET, SUITE 1603 MIAMI, FLORIDA 33130 -1563 (305) 375-2901 FAX (305) 375 -2908 PRODUCT CONTROL DIVISION (305) 375-2902 FAX (305) 372 -6339 aul Rodriguez Product Control Supervisor L ar ei c.„/ Charles Danger, P.E. Director Building Code Compliance Dept. Miami -Dade County Homepage: http : //www.bulldingcodeonllne.com Apr- 30- 98 Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. Applicant: Polyfoam Products, Inc. 2400 Spring - Stuebner Road Spring, Texas 77383 -1132 PRODUCT CONTROL NOTICE OF ACCEPTANCE ROOFING COMPONENT APPROVAL Contact: Pat Murray P.O. Box 1 132 Spring, Texas 77383-1132 Phone: (713)350 -8888 Fax: (713)288 -6450 Page 2 of 15 954 475 -1462 P.03 Product Control No.: 98-0303,02 Product Control No.: 98- 0303.02 Approval Date: April 16, 1998 Expiration Date: April 16, 2001 Category: Roofing Component Sub - Category: Fastening/Adhesive Type" Roof Tile Adhesive Sub -Type: Two Component Polyurethane System Description Polyfoam Products, Inc., produces two - component expanding polyurethane adhesive for the attachment of clay and concrete roof tile. Polypro® AH160 is specially designed for application of concrete and clay roof tile over a variety of roof deck substrates and underlayment materials. Polypro® adhesive is applied with proprietary Foamproe RTF1000 dispensing equipment. Approval of this product is specific to the two component mix and Foampro® RTF1000 dispensing equipment. Alternative methods of dispensing will require a revision to this approval. Polypro® adhesive shall be applied only by 'Qualified Applicators, licensed by Polyfoam Products, Inc. Certificates and identification cards are issued to applicators upon successful completion of a application training program. Approval of this adhesive system is contingent upon application by a 'Qualified Applicator. Frank Zuloaga, RRC Roofing Product Control Examiner Apr -30 -98 04:11P Polyfoam Products Inc. • 954 475 -1462 P.04 • POLYFOAM PRODUCTS, INC. Product Control No.: 98- 0303.02 TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT Product Dimensions Polypro® AH 160 N/A Foampro® RTF 1000 N/A Page 3 of 15 Test Product Specifications Description PA 101 Two component polyurethane See Detail Attached Dispensing Equipment Frank Zuloaga, RRC Roofing Product Control Examiner Apr -5O -98 014:1,1P Polyfoam Products Inc. • POLYFOAM PRODUCTS, INC. Product Underlayment Roof Tile TRADE NAMES OF PRODUCTS MANUFACTURED BY OTHERS Test Criteria Product Description PA 120 All Dade County Component Approved products as detailed in Dade County Application Standard I'A 120 PA 101 All Approved roof tile systems having tested in compliance with Dade County Protocol PA 101, as detailed in the systems section of this Component Approval Page 4 of 15 954 475 -1462 P.05 Product Control No.: 98- 0303.02 Manufacturer All Dade County Approved Products All Dade County Approved Products Frank Zutoaga, RRC Roofing Product Control Examiner Apr -30 -98 04:11P Polyfoam Products Inc. ' POLYFOAM PRODUCTS, INC. TEST REPORT'S Test Agency Test Identifier Test Name/Report Date Center for Applied 1/94 -060 Miami Dade Protocol 04/08/94 Engineering PA 101 Ccnter for Applied 257818 -1PA Miami Dade Protocol 12/16/96 Engineering PA 101 Center for Applied 25- 7438 -3 SSTD 11-93 10/25/95 Engineering Center for Applied 25- 7438 -4 SSTD 11-93 10/25/95 Engineering Center for Applied 25- 7438 -7 SSTD 11 -93 11/02/95 Engineering Center for Applied 25 -7492 SSTD 11 -93 12/12/95 Engineering Miles Laboratories NB -589 -631 ASTM D 1623 02/01/94 Polymers Division Ramtech Laboratories, 9637 -92 ASTM E 108 04/30/93 Inc. Southwest Research 01- 6743 -011 ASTM E 108 11/16/94 institute Southwest Research 0I - 6739 -062b[ I ] ASTM E 84 01/16/95 Institute Trinity Engineering 7050.02.96 -1 PA 114 03/14/96 Page 5 of 15 954 475 -1462 P.06 Product Control No.: 98- 0303.02 Frank Zuloaga, RRC Roofing Product Control Examiner Apr .04:1.1P Polyfoam Products Inc. • POLYFOAM PRODUCTS, INC. Product Control No.: 98- 0303.02 Dimensional ASTM D 2126 +0.07% Volume Change @ -40 F., 2 Stability weeks +6.0% Volume Change @158°F., 100% Humidity, 2 weeks TYPICAL PHYSICAL PROPERTIES Property Test Density ASTM D 1622 1.6 lbs. /ft.' Compressive ASTM D 1621 18 PSI Parallel to rise Strength 12 PSI Perpendicular to rise Tensile Strength ASTM D 1623 28 PSI Parallel to rise Water Absorption ASTM D 2127 0.08 Lbs. /Ft Moisture Vapor ASTM G 96 3.1 Perm / Inch Transmission Closed CeII Content ASTM D 2856 86% 954 475 - 1462 P.07 Page 6 of 15 Results Note: The physical properties listed above are presented as typical average values as determined by accepted ASTM test methods and are subject to normal manufacturing variation. Frank Zuloaga, RRC Roofing Product Control F.xarniner Apr-30-98 Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. SYSTEMS Deck Type: Wood, Non - insulated, New Construction /Reroof Dcck Description: 15 /32" or greater, plywood or wood plank. SYSTEM A: Adhesive Set Application Slope Range: 2 ": 12" to 7 ":12" 954 475 -1462 P.08 Product Control No.: 98- 0303,02 Underlayment: Shall comply with Miami -Dade Roofing Application Standard PA 120 Roofing Tile: Comments: Any roof tile assembly having a current shall be applied in compliance with the Component Application section and the corresponding Placement Details of this Notice of Acceptance. The adhesive attachment shall provide sufficient attachment resistance expressed as a moment to meet or exceed the required moment of resistance determined in compliance with Miami -Dade County Roofing Application Standards PA 115 or PA 127. The adhesive attachment data is noted in the roof tile assembly NOA. 1. All 'System Limitations' noted in the tile Roof System Assembly Product Control Approval shall apply. Page 7 of 15 Frank Zuloaga, RRC Roofing Product Control Examiner Apr- 30- 98,04:12P Polyfoam Products Inc. • POLYFOAM PRODUCTS, INC. Comments: Page 8 of 15 954 475 -1462 P.09 Product Control No.: 98- 0303.02 SYSTEMS (CONTIN UED) Deck Type: Concrete, New Construction /Reroof Deck Description: New construction SYSTEM B: Adhesive Set Application Slope Range: 2 ":12" to 7 ":12" Underlaymcnt / Install Approved underlaymcnt system of one of the following: Waterproofing: Underlayment: (30/90 Hot Mop) fully adhered in a full mopping of ASTM D 312 type IV asphalt applied within the EVT range. Back nailing and laps shall be in compliance with Roofing Application Standard PA 120. Any liquid applied roofing system having a current NOA for its use as a tile undcrlayment system. Roofing Tile: Any roof tile assembly having a current shall be applied in compliance with the Component Application section and the corresponding Placement Details of this Notice of Acceptance. The adhesive attachment shall provide sufficient attachment resistance expressed as a moment to meet or exceed the required moment of resistance determined in compliance with Miami -Dade County Roofing Application Standards PA 115 or PA 127. The adhesive attachment data is noted in the roof tile assembly NOA. 1. All 'System Limitations' noted in the tile Roof System Assembly Product Control Approval or waterproofing component Roofing Component Product Control Approval shall apply, as applicable. Frank Zuloaga, RRC Roofing Product Control Examiner Table 1: Adhesive Placement For Each Generic Tile Profile Tile Profile Placement Detail Two -Piece Barrel #1 'S' Shaped #2 Double Roll #3 Flat #4 Apr - 30 - 98 04:13P Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. Product Control No.: 98- 0303.02 COMPONENT APPLICATION 954 475 - 1462 P.10 1. Polypro® A1-1160 tile adhesive shall only be applied over an underlayment installed in compliance with application instructions detailed in its NOA.. Underlayment may be any undcrlayments or underlayment systems listed Miami -Dade County Roofing Application Standard 1'A 120. 2. Adhesive application shall be in accordance. with the instructions provided herein. Tthe manufacturer may provide additional instructions subsequent to this approval date which may prevail. Installation must be by a Factory Trained 'Qualified Applicator' approved and licensed by Polyfoam Products, Inc. 3. Calibration of the Foampro® dispensing equipment is required before application of any adhesive. The mix ratio between the "A" component and the "B" component shall be maintained between 1.0- 1.15 (A) : 1.0 (13). The dispense timer shall be set to deliver 0.08 to 0.15 pounds per tile as determined at calibration. No other settings shall be approved without revision of NOA. 4. Adhesive shall be dispensed in a 17 in' to 23 in' pad at time of application. The cured pad shall be approximately 5" x 12 ". Foam placement shall be in accordance with the 'Placement Details' herein. Each generic tile profile requires a specific placement, as noted in Table 1, below 5. Adhere tile directly in freshly applied adhesive. Tile must be set within 2 to 3 minutes after foam has been dispensed_ Page 9 of 15 Frank Zuloaga, RRC Roofing Product Control Examiner .Apr- 30- 98,04:t3P Polyfoam Products Inc. 954 475 -1462 P.11 POLYFOAM PRODUCTS, INC. Product Control No.: 98- 0303.02 SYSTEM LIMITATIONS 2. Polypro® AH160 adhesive shall be installed only by 'Qualified Applicators' approved and licensed by Polyfoam Products, Inc. 3. For adhesive set tilt applications, a field static uplift test by a Miami-Dade County accredited testing agency, in compliance with Miami -Dade County Roofing Application Standard PA 106, shall be required not less than 72 hours after application to confirm tile adhesion. 4. Refer to application drawings published by the National Tile Manufacturers Association for penetrations and terminations, as well as the 'Placement Details' included with NOA. 5. Refer to tile Roof Tile Assembly Product Control NOA for system acceptance with this Component. 6. Refer to the Prepared Roof Tile Assembly for fire rating. 7. Polypro® AH160 shall not be exposed permanently to sunlight. 8. Polypro® AH160 shall be applied with Foantpro RTF1000 dispensing equipment only. 9. Polyfoam Products Inc. shall supply Building Official with a list of 'Qualified Applicators' approved and licensed by Polyfoam Products, Inc. Page 10 of 15 Frank Zuloaga, RRC Roofing Product Control Examiner Apr -30 -98 04:14P Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. Underlay/n..4 2) Torn cove~ ep•ld• down. Place Adh.olvo 112' to 1 boon the eel.td. .dit. M Canoe tile. Than !noted 111.. 1)►Iee..n..yh .dh..l fo to rehires 1 to 29 eq. Inches In contort with Ow pen 111.. Re new. tee poelle• M the twee a..a.. Sta. Abut to second oaar,e d pen 1115.. tamer. wove and of pan taw' cover 111.e we fleets at new. tine. ear. Glow, (mortar shown) PLACEMENT DETAILS we.plol. Page 11 of 15 Sell 1bn:web plastic cement (wt.w. required by cod.) Opt1..1d mat's (oe Steep pltel. applications. ?...l. Sward Placement Detail #1: Two-Picce Barrel Profile 954 475 -1462 P.12 Product Control No.: 98- 0303.02 Opllo•d P.11-Up r.rtar .. L.eyltadlasl .dyne .t tile. She.TMn. Frank Zuloaga, RRC Roofing Product Control Examiner Apr -30 -98 04:14P Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. 11.11 through pIwtlo ...root (wh.n r.polr.d pY ce u.e..t.y.r.nt PLACEMENT DETAILS (CONTINUED) Appel .n..eh .dh.. W. to oghl.v. 17 to 22 ■qwr. boohoo I....too1 with tir t11.. E.Y. clo..r. Fogel. S..rd Placement Detail #2: 'S' Shaped Tile Profile Page 12 of 15 954 475 - 1462 P.13 Product Control No.: 98- 0303.02 Drip Edge Frank Zuloaga, RRC Roofing Product Control Examiner Apr -30 -98 04:15P Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. Paull through ploollc c....nt (whom rewired ►y pod.) — Uwd.rby.,...t [.►. Cameo PLACEMENT DETAILS (CONTINUED) 4 fra ewe Clout.» e env. cw.. •.tr. k—p odhr1 . Approuhw.tloy r up rrrru w oophdr. _ Apply .w.ugM .dM.ly. to .cld.00 11.23 .qu.r. loch.* 1. ..wt..t with (M Placement Detail 03: Double Roll Profile Pagc 1 3 of 15 954 475 - 1462 P.14 Product Control No.: 98- 0303.02 A Frank Zuloaga, RRC Roofing Product Control Examiner f, • '. , I• rr Apr -30 -98 04:15P Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. Kell 1M.tgh plastic cem.nl (whim requited by cede) u el. Cave Closure PLACEMENT DETAILS (CONTINUED) lave Cones lave come only. Keep adheolve .pp r up Fowl weep►plwh Placcmcnt Detail #4: Flat Profile Page 14 of 15 954 475 -1462 P.15 Product Control No.: 98- 0303.02 Apply etweph adhesive to achieve 17.23 square lactate M eostaot with the Ale. uloaga, RRC Roofing Product Control Examiner Apr-30-98_04:15P Polyfoam Products Inc. POLYFOAM PRODUCTS, INC. Product Control No.: 98- 0303.02 Polyfoam Products, Inc. 2400 Spring - Stucbner Road Spring, TX 77383 NOTICE OF ACCEPTANCE STANDARD CONDITIONS 954 475 - 1462 P.16 ACCEPTANCE NO: 98- 0303.02 APPROVED : April 16, 1998 EXPIRES : April 16, 2001 1 Renewal of this Acceptance (approval) shall be considered after a renewal application has been filed and the original submitted documentation, including test supporting data, engineering documents, are no older than eight (8) years. 2 Any and all approved products shall be permanently labeled with the manufacturers name, city, state, and the following statement: "Miami -Dade County Product Control Approved ", or as specifically stated in the specific conditions of this Acceptance. 3 Renewals of Acceptance will not be considered if: a) There has been a change in the South Florida Building Code affecting the evaluation of this product and the product is not in compliance with the code changes: b) The product is no longer the same product (identical) as the one originally approved; c) if the Acceptance holder has not complied with all the requirements of this acceptance, including the correct installation of the product; d) The engineer who originally prepared, signed and scaled the required documentation initially submitted, is no longer practicing the engineering profession. 4 Any revision or change in the materials, use, and/or tnanufacture of the product or process shall automatically be cause for termination of this Acceptance, unless prior written approval has been requested (through the filing of a revision application with appropriate fee) and granted by this office. 5 Any of the following shall also be grounds for removal of this Acceptance: a) Unsatisfactory performance of this product or process; b) Misuse of this Acceptance as an endorsement of any product, for sales, advertising or any other purposes. 6 The Notice of Acceptance number preceded by the words Miami -Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is displayed, then it shall be done in its entirety. 7 A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at all times. The copies need not be resealed by the engineer. 8 Failure to comply with any section of this Acceptance shall be cause for termination and removal of Acceptance. 9 This Acceptance contains pages I Through 15. END OF THIS ACCEPTANCE Page 15 of 15 Frank Zuloaga, RRC Roofing Product Control Examiner PERMIT APPLICATION FOR MIAMI SHORES VILLAGE /- ,(7•47eS E 7 �5, � � - // Date Job Address � Tax Polio�� � 20(O - 6/7- Did G Legal Description Lessee Owner's Address Contracting Co. Square Ft. Zoning / Tenant rl R- c 1 /z L.44'e--teiV L/37 /07//), /G--0 Address Qualifier CG L � ex / �� Phon 3fsS)e65 79 7O .GC State # Municipal # Competency # Ins.Co : r l G , Architect /Engineer Address Bonding Company Address Mortgagor Address // ;it) 0 C A.tA/.e. Q. ( .4/L -= Signat a o' •weer and /or Condo President Date: / MICHAEL WILSON NOTARY MY COMM EXP. 1.28 -9A. a PUBLIC BONDED BY SERVICE INS =CG NC'. CC 176804 Notary a Owner and /or Condo President My Commission Expires: /-14 ** * * * * * * FEES: PERMIT " RADON APPROVED: Mechanical * * C.C.F. Fire Buildin Master ermit 4� 3 �� ( 40-5) Phone 75 (/,- r j X' - /A Permit Type(circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFIN PAVING FENCE SIGN WORK DE p I PT I ON �L � / IV, L6 ' wiz¢• / 3 / _ f � � Estimated Cost(value)X 2 D • 4 " D WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT). Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if. applicable). I certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK. OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. Furthermore, I authorize the above -named contractor to do the work stat / Signature of Contractor or Owner - Builder Date: Plumbing Engineering_ C 1 2 76 1 1/ /--/9-9r Notary as to Contractor or Owner-Builder My Consaios (lY P V OFFICIAL NOTARY SSA 6' l ei SANDRA M MON/EL �iw� COMMISSION WEISER 4 L 1•-, * CC4g1261 * " 3' COMMISSION .EXP. .r 0 G, 1, • Other * * * Electrical GAFGLAS® Specifications N -B -3 -C Specifications General Apiipcaliu n'C6er;unciit!adurts doge() un pages 17.20 shall apply In addition to the Iplluwtng recommend inlets and speciticaduns. AppttcBUUn or flouting Membrane Ovor entire surface. lay coo ply of sheathing paper where applicable. Lap each sheet 2 inches over preceding street. (Jail sufficiently to bold In place. 2. Startdrg at tilt tow point of the roof, lay ono ply ul GArGL1S o;se Street, hpphhg tact► slat 2 filches at edges and hot loss than 6 inches at end Lips. WI along lap of base ply at Intervals nut to exceed 9 incites arid stagger-101 down center of sheet in two rocs vriUi nails spaced al 18 itch i ucn;ls b1 oauih row. Use fasteners with integral rlteU heads at !cast 1 inch In diameter or square that are recommended by GAF cr the deck rnanulac• tunirr Gee 'Special InshucliuIIs' bcicm, - - - '3. Slanting at the toe: paint of the roof; mop t,o plies of GAFGLAS Ply shingle ,Isaul:, lapping oach sheet 19 Iht;les -a1'rr the preceding sheet: solidly mopping ` to the underlying base sheet to provide three plies over the entire roof area. `FS;diait flequIrenlcuts . :Ictapy moppings of GAF nouflrig ilsptiart must be applied in a continuous film _a`hd ;;hall consist of approximatciy pounds per 100 spuare feet of roof area w„IQI atolerance not to exceed 20: pL-Cr minus. The appropriate asphalt for tho kiopcs Involve) C1051 be used.. - - - • p e per loot ' .. '7..7 Asphalt Type .. • 1 Ujr'o 3' - - Steep ASTM Type III ; 6'. • • • NT•Stecp ASI M Type IV - On scope, up to 2,iricf ;or loot, Frac,cs Type II may be used 'except Ir1 rlorida,.T, xas -New Mexico, Ari ;una, and California. `'Surfacing ` Ovcr`Ihe entire sulfate, apply a unpurtl canting. Gr undy liberal Aluminum Coating. GAr WEArtic(i CUAT ernOs1 r or GAF Special flooring Bitumen may , ird■oed for suh�a.Iriq.- Ssc'Coalirrs for Smooth Surl a,cd flout Systems,' iMpo SnrAla1 Inshucllons , 1. SrLF.ccolnntcnaaliurrs for use v urn decks on page 8. 2 Acccptatac GArGt.AS Base Shoots Include. GArGLnS SIRATAVEur' (Vent for N43ilabto Decks (requited for fresl�y poured gypsum decks), GAFGLAS . 'OS GATGIAS' PLY 6', aitd GAUGL1S Ply 3. For sruod decks. and 'sbuclural wood fiber decks it GATGCAS 4 or GAFGLAS PLY 615 used as a : Case sleet, sheathing paper Is railuired. - '3` Sdo'Nailing of Baso Sheet, paQ5S1'B-19. • VI Tool slopes of 1 Inch per fodt9rmcre, all plies must be back - nailed 4 • incnIs in from the tell edge. Sea'mstaitatton on Steep Roots,' page 9. UL Classification UL Chart key 1. Surtacing GWCE • GAF Mettle' Coat Emulsion GFAC • Grundy Fibcrod Aluminum Coating GSRB • GAF Special Roofing Bitumen 2. Substrate C . Combustible and Noncombustible Combustible - Wood planks. boards, etc., pVvood (min. 3 /11 inch thickness), oriented strand board (min. Y Inch thickness). NC . Noncombustible only Noncombustible . Stool, poured 0: precast structural concrete, liUlltwolght I!SUIaling CCI1C1ete, gypsum, structural wood fiber, etc. 3. Slope Maximum Slope allowed, In inches per foot. I 2 1 1r agst Sheathing 1'epor, In requlrodl .•,t. ; 2" 61111 lop • circus Gale sheet (uo below) 1 c r . OAP IIVACA.0 Y M 4N lpN OAF •• - nooIIn7 Arphul . _aurbu Cooling South and West Zones Only Nallable docks up to 6 Metros per fool slope. Wood, plywood, poured gypsum, precast gypsum planks, other acceptable precast naitable decks (not Including I1ght.rcight Insulaling concrete), htatnrleia �?•• t Approximate Weight Per Square Sheathing paper (1 ply, II rcidlroe) . �. • _ . GAi•GLAS Rase Street GAI:GLIS Ply (2 plies) GAF Roofing Asphalt;,, ',. :Surface Coating ':. • : ' GAr Special R, uofing Biilimo,i''` Grundy Fibered Alurnlnuni Coating GAFWEAI'IIEfl COAT Emulsion r. ,. SLhoclllcallon N 8 3 C. . • .. Guorenle ea Available' ":' Libert Gueranioes 10,.5 +5, 5 yr, 11.69 lbs. 22 lbs. : 50 tbs. 1. 201bs.' :' 1Z lbs. 21 lbs. Total 136-194 lbs. 43 Job Address: 3� A> .elo'zs GENERAL: Type of Roof System Assembly to be Applied: Manufacturer of Roof System Assembly: Product Control Approval Number: System Number from Product Control Approval: 'IWO COPIES (Attach of.i of the Roof System Assembly Product Control Approval and the Manufacturer's System Guide Specification. ) ( Note: If a minimum roof system is to be applied, describe all components within the system and list the manufacturer of each component. DO NOT complete this section if system is Product Control Approved. ) ¥ ' 3 L6 ova s'a- S Base Sheet: Mi./Le &y/. Contractor Process No. APPENDIX 'E' METRO -DADE UNIFORM BUILDING PERMIT SECTION 11 BUILT -UP APPLICATIONS AND MODIFIED BITUMEN SYSTEMS Fasteners: 77 N e blialoee 4) -le,d e Ply Sheet(s): 3 p /c( Fi hv°i F . Cap Sheet: Asphalt: ( Note: No insulation system is acceptable under the minimum roof category. ) Complete the following for all Roof System Assemblies: Built -Up Applications and Modified Bitumen Systems • Page -1 Job Address: Contractor Process No. ( Check one of the following ) Recover Re-roof: l7 New Construction If a recover, is the existing Roof System Assembly to be used as a bonding substrate ?: If YES, has an ASTM E907 test been carried out to confirm adhesion of the existing membrane to the substrate ?: Y N (If 'yes', attach ASTM E907 test report. ) Proposed Fastener: (Attach withdrawal resistance test report. ) Has the deck been examined for moisture ?: (Provide data confirming compliance with Section 3401.9(c) . ) THE SYSTEM: All Roof System Assemblies in the Product Approval have a variety of options. Briefly describe the Roofing Components to be used in the Roof System Assembly and attach a copy of the manufacturer's published specification: Deck: (Briefly describe ) Insulation: ( Type, size and method of attachment, if applicable ) Base Sheet or Ply: ( Type and method of attachment ) 3/ `` pl G {2 `,�, if 443 66 I/ Y Y N Ply Sheet(s): ( Type and method of attachment ) Built -Up Applications and Modified Bitumen Systems • Page -2 Job Address: Contractor Process No. Top Ply: ( Type and method of attachment ) Surfacing: (Type, if applicable ) Flashing Materials: ( Type and method of attachment ) 3x gac r ( 9az. Built -Up Applications and Modified Bitumen Systems Page -3 Job Address: T inches inches T inches FILL IN APPLICABLE ROOFING COMPONENTS WHICH MAKE UP ROOF SYSTEM ASSEMBLY AND THICKNESS OF DECK AND INSULATION LAYER(S). (Where Roofing Component not used in Roof System Assembly, fill in with "N /A ".) �\ Top Ply: Ply Sheet(s): Base Sheet: r Surfacing: / ( aepl is bls) Bonding Material: Bonding Material: Fastener: (if bare sheet mech. attached) Bonding Material: (ifbase sheet bonded) Fastener: (if top insulation layer mech. attached) Top Insulation Layer. (if applicable ) Bonding Material: ( i/rop insulation layer bonded ) Fastener: (rf insulation mech. attached) Insulation: Primer. (if applicable) Bonding Material: (rf insulation bonded ) Vapor Retarder. (if applicable ) DECK: Type: Gage or Thickness: Density, if concrete deck: Contractor Built -Up Applications and Modified Bitumen Systems Page -4 Process No. Job Address: Contractor PERIMETER DETAIL #1: Parapet Wall Detail Process No. Coping Cap Gage: Fastener - Spacing: _ o.c. Clip Type: Clip Gage: Ve/0' Deck Type: Sketch Roofing Components which make up Roof System Assembly at Perimeter Parapet Walls. Insert leaders indicating Roofing Component names, dimensions, thicknesses, etc. Include fastener type and spacing used for wood - blocking attachment. Deck Type: Sketch Roofing Components which make up Roof System Assembly at Perimeter Areas to be Flashed. Insert leaders indicating Roofing Component names, dimensions, thicknesses, etc. Include fastener type and spacing used for wood - blocking attachment. PERIMETER DETAIL #2: Flashing Detail Built -Up Applications and Modified Bitumen Systems Page -5 Job Address: Contractor PERIMETER DETAIL #3: Gravel Stop or Drip Edge Process No. Sketch Roofing Components which make up Roof System Assembly at Perimeter Edge with Gravel Stop or Drip Edge. Insert leaders indicating Roofing Components names, dimensions, thicknesses, etc. Include fastener type and spacing used for wood - blocking attachment. Gravel Stop/Drip Edge Gage: Fastener Spacing: o.c. Clip Type: Clip Gage: / I I LT I Deck Type: Sketch Roofing Components which make up Roof System Assembly at Perimeter Edge with Gutters. Insert leaders indicating Roofing Component names, dimensions, thicknesses, etc. Include fastener type and spacing used for wood - blocking attachment. Gutter Type: Gutter Gage: Fastener Spacing: Deck Type: PERIMETER DETAIL #4: Gutter Detail Built -Up Applications and Modified Bitumen Systems Page -6 Job Address: Contractor PERIMETER DETAIL #5: 'Other' Detail Process No. Sketch Roofing Components which make up Roof System Assembly at any 'other' Perimeter Condition which may exisit. Insert leaders indicating Roofing Component names, dimensions, thickesses, etc. Include fastener type and spacing used for wood- blocking attachment Sketch Roofing Components which make up Roof System Assembly at any 'other' Perimeter Condition which may exisit Insert leaders indicating Roofing Component names, dimensions, thickesses, etc. Include fastener type and spacing used for wood - blocking attachment. PERIMETER DETAIL #6: 'Other' Detail Built -Up Applications and Modified Bitumen Systems Page -7 Job Address: Contractor Process No. Insert Building and Parapet Heights. (1/ no Parapet exists, insert "N/A") Also insert applicable information pertaining to the building below. (See ASCE 7 -88 Fact Sheet Attached) Exposure Category: Classification Category: At Hurricane Oceanline ?: Y N Basic Wind Speed at Building Location: 110 mph Building Condition based on % of Openings: GROUND LEVEL T feet feet BUILDING INFORMATION #1 Built -Up Applications and Modified Bitumen Systems Page -8 Job Address: Contractor Process No. Sketch Roof Plan indicating all dimensions, any slopes, roof drains, crickets, or roof top equipment. Also insert variable labeled "a" which indicates perimeter and corner dimensions per Chapter 23 of the South Florida Building Code. ( See ASCE 7 -88 Fact Sheet Attached ) 6 m2 9 i r 14 ' r ' T /-4-'1 j4- ?.. e ,.4- . l �CPu eS E e, ue^ fu, dal: fi 1,g BUILDING INFORMATION #2: Roof Plan with Perimeter and Corner Dimensions Built -Up Applications and Modified Bitumen Systems Page -9 Job Address: Contractor Process No. -- FOR PLAN EXAMINER USE ONLY -- Roof System Assembly Product Control Approved: Y N If NO, note any deficiencies: Design Pressure Requirements: Field: psf Perimeter Areas: psf Corner Areas: psf Note any limitations: Reviewed Details ?: Notes: Built -Up Applications and Modified Bitumen Systems Page -10 Y N Job Address: Contractor Process No. Reviewed Field Test Data ?: Y N Notes: Additional Notes: Built -Up Applications and Modified Bitumen Systems Page -11 Plan Examiner APPLICATION FOR BUILDING PERMIT Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build- ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida. and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. Date...r..._..._>7 ' _ 9 ,19. . 7. Owner's Name and Address �� zIte" r/ .... _. No A. STATE OF FLORIDA, COUNTY OF DADE. ss Before me, th peared Registered Architect and /or Engineer ,, ,,, , ,,,,,,,,, ,,,, ,,,,, „,,,,,.,,,.., ....... /m /;, t o I c , Cad.? G y��n t .5' E /l.., , <. Name and address of licensed contractor _ ... ..t_...._ 3:30 - a Location / an le al/d` iption of lot to be but Lot 1... /.Lt Block 1.. State work to be done and purpose of building (by floors) felts and art. ersigned authority, a not Building Inspector gs6,5 MIAMI SHORES VILLAGE BUILDING INSPECTION DEPARTMENT Subdivision LiL /7 O72 Street and Number where work is to be done �3 A/ / G a Residence Reroof flat roof with fiberglas and for no other purpose. New Building Remodeling Addition IRCiP To be constructed of Kind of foundation 10 .. _ Rood Covering Estimated Total cost of improvements $ 1, 700 Amount of Permit L. Zone cubage required plan Cubage Distance to next nearest building.. Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to The undersigned applicant for this building permit does hereby certify that he understands an. accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled Gener i aws of Florida, Permanent Snp p leent, and has complied with the provisions thereof, and will require similar compliance from all con ors or u. contrac . s emp ed iu by him in the work to be performed under this permit; and will post or cause to be posted for i ecti h• of the sucl blic notice or notices as arc required by the Act. The undersigned agrees to employ only such su ntract under this permit, as are licensed by Miami Shores Village. Remarks No. of Stories authorizyto administer oaths and take acknowledgments, personally ap- to me well known, and who, being by me first duly sworn, upon oath deposes and says that he is the. / of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true. Permit No.._. ‘ Date 4 P1 Read, Swo �, Disapproved t� . -.. / - Date ••• My ' VI �t w , Not. Public, Std'i8 ' 'Pdr'db% - n � ..... 7777------- ;� Ofl ISStoll EX' i. av C ommission Ex ires.... .. Y P� { i0Li1ED.. L4P .11.ccrC�Js before e . PLANNING BOARD DATE Chairman Member Member Member Member ...... Member �.._.._ Council Approved Date Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has hero obtained from the Planning Board. A rc -in' pcction fee of $1.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty materials and /or workmanship. MIAMI SHORES VILLAGE BUILDING INSPECTION DEPARTMENT APPLICATION FOR BUILDING PERMIT Application is hereby mode for the approval of the detailed statement or me plans and specifications herewith submitted for the build • in or other structure herein described. This application Is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida. and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the i3uil. ling Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. Owner's Name and Address .K.. .. ...... Registered Architect and /or Engineer .. ,.l,.... + ^ • ... Name and address of licensed contractor : ±:Q.0 . .. 1 .. /rye G - -• �••'• a•+,Fr Location and icgal description of lot to be built on: Lot Block Subdivision Street and Number where work is to be done State work to be done and purpose of building (by floors) STATE OF FLORIDA, COUNTY OF DADE. peared s Permit No.._.. - - - Z- 1-:.3 Z Disapproved. Date (Signed) Date Building Inspector NOTE: A charge of $1.00 will be made for the I'Lmnir. Board. A re- inspection fee of $1.00 will be charged materials and /or workmanship. Chairman Mcrr,bcr Member ... — .....__....._..._. sass_ Council Approved Date • Slop _. ..........._...__....._..._.. _.— roof and for no other purpose. New Building Remodeling Addition Repairs No. oo stories To be constructed of Kind of f undation Roof Covering ....is.. Estimated Total cost of improvements $ 0 a' 0 Amount of Permit 0.A.._7 Zone cubage required .._...Plan Cubage Distance .to next nearest building.. Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to. The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the 'Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Su , ement, and has complied with the provisions thereof, and will require similar complia e • n all contractor or sub - contractors emplo ' by him in the work to be performed under this permit; and will post or cause to be pasted fo inspection • . e site •f•the wo t` it tice or notices as arc required by the Act. The undersigned agrees to employ only s s • •ntractor , wo • be pennit, as are licensed by Miami Shores Village. Remarks (Signe Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- and who, being by me first duly sworn, upon oath deposes and says that he is the. of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true.. Read, Sworn to and Subscribed before me. Notary Public, State of Florida My Commission Expires PLANNING BOARD DATE Member biembcr Member —_.._ — .. -sass. Disapproved Date to me well known, making corrections or changes to this application after approval has been obtained from when such re- inspection is made necessary by Improper notice for inspection at faulty Owner's Name and Address Mrs • Larkin MIAMI SHORES VILLAGE BUILDING INSPECTION DEPARTMENT APPLICATION FOR BUILDING PERMIT Application is hereby mode for the approval of the detailed statement ur me plans and specifications herewith submitted for the build inc or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida. and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Divisinn of Miami Shores Village shall bc complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. 8 squares ... No..437 Street • E. 102nd St. Registered Architect and /or Engineer ,.,. ,.•••n.• ernnwre Name and address of licensed contactor Lang Roofing &Tile Co. , Inc. 573 N, W, 71st, Miami,_ Florida 33150 Location and legal description of lot to •be built on: Lot Block Subdivision - .••••• •••■••■••• Street and Number where work is to be done 437 N. E. 102ndStreet State work to be done and u ose of building (by floors .'_ artiq. zero.. O.i.... f1, ra: b... S�s2f .:...._.t.P_ar.._o- f.f_.. .e.cl stin Pm g( Y )••• gr tin cap 1-30# felt to sheathing mop2 -15;# felts with hot asphalt and apply pea gravel embedded into hot asphalt. and for no other purpose. New Building Remodeling Addition Repairs No. of Stories • To be constructed of Kind of foundation Roof Covering ... 41.- .p.ly....Gra.ve1..__ Estimated Total cost of improvements $ 1, 250.00 Amount of Permit S.. 15.00 Zone cubage required Plan Cubage Distance .to next nearest building Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of Libor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement, and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him in the work to bc performed under this permit; and will post or cause to be posted for inspection on the of the work such public notice or noticcs as arc required by the Act. The undersigned agrees to employ only such subco ors, to be performed under this pcnnit, as are licensed by Miami Shores Village. r Remarks..._ (Signe STATE OF FLORIDA, COUNTY OF DADE. s Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared and who, being by me first duly 'sworn, upon oath deposes and says that he is the. of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated e true. Permit No. ' 4 Date. . k) Read, Sworn to and Subscribed before me. Disapproved ... ' Date (Signed) Building Inspector Notary Public, State of Florida My Commiuion Expires _. — to me well known, PLANNING BOARD DATE Ciiairnan Mcmbcr Member Member Member..... _.....__....._..._. ....._ Member ...._ __.._._...— -- Council Approved Date Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained frrnn the I'i,innir.g )lo.rrd. A rc- inspection Ice of 51.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty materials anti /or workmanship. MIAMI SHORES VILLAGE BUILDING INSPECTION DEPARTMENT APPLICATION FOR BUILDING PERMIT Application is hereby made for the approval of the detailed statement or ore plans and specifications herewith submitted for the build • ing or other structure herein described. This apphcation Is made in compliance and corfformity -with the Building Ordinance of Miami Shores Village, Florida. and all provisions,nf the Laws of the State of Florida, all ordinances Miami Shores Village and all rules and regulations of the Building Division of —Miami Shores Village- shall -be complied with; whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. 4 squares Date _Nay 25.th, .19..29. Os.-ncr's Name and Address ..... . No. ../ Street.N d Street Registered Architect and /or 1?,ngineer . „,.. ,,. ,, ,., . ........ .. . . . Name and address of licensed contactor , Roofing &Tile Co,, m Location and legal description of lot to be built on: Lot Block Subdivision Street and Number where work is to be done.../ State work to be done and purpose of building (by floors)..i r.Q Qf ..graYe1...r.00 r f...in...ea�:.. ten roofing down to sheathi tin cap 1 -30# felt mop 2 -15# felts with hot asphalt and apply pea gravel embedded into hot asphalt _.._. and for no other purpose. New Building Reniodeling Addition Repairs..Fart......1/R No. of Stories To be constructed of Kind of foundation Roof Covering . 4- ply Estimated Total cost of improvements $ 995...00 Amount of Permit s15...O1) Zone cubage required .Plan Cubage Distance to next nearest building Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to.. The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida. Permanent Sup ienrent, and has complied ssith the provisions thereof, and will require similar compliance from all contractors or su.- contractors employed by him in the work to be performed under this permit; and will post or cause to be posted for inspection on th f the work such public notice or notices as arc required by the Act. The undersigned agrees to employ only such subcontr _ ors to be performed under this pennit, as are licensed by Miami Shores Village. � rs/ Remarks (Signed) STATE OF FLORIDA, COUNTY OF DADE. i ss. Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared and who, being by me first duly sworn, upon oath deposes and says that he is the. of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true. Permit No Date Read, Sworn to and Subscribed before me. Disapproved Date (Signed) Notary Public, State of Florida to me well known, Building Inspector My Commission Expires PLANNING BOARD DATE Chairman Member \Iccr,ber Member Member .. .. Member _ .._..... Council Approved Date Disapproved Date NOTE: A cl,.,rge of $1.00 will he made for making corrections or changes to this application after approval has hero obtained from the P1.tnnir.;; Board. A re in.pc•ction fee of $1.00 will be charged when such re- inspection is made necessary by Improper notice for inspection or faulty materials and /or workmanship. Owner's Name and Address Registered Architect and /or Engineer Name and address of licensed contractor Location and legal description of lot to be built on: Lot Block Subdivision State work to be done and purpose of building (by floors) WAR/ill] SHORES V1LLASE BUILDING INSPECTION DEPARTMENT AP2LOCATDON FOG. ELDuLEDGNO PERMOT Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build- ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. CiKev. yf leoofrfc. Street and Number where work is to be done _. 1 137 Alt PA- 7 NEw troop ON «0df7(fiV — .__ —30 2 -L * /Iva, and for no other purpose. New Building Remodeling Addition l Repairs No. of Stories l To be constructed of Kind of foundation Roof Covering Aef1 vFr: Estimated Total cost of improvements $ 160 ' 00 Amount of Permit $ 3'. 00 Zone cubage required .Plan Cubage Distance to next nearest building Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement, and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such ublic notice or notices as are required by the Act. The undersigned agrees to employ only such bcontrac s, on work to be p- . • . •. • this permit, as are licensed by Miami Shores Village. Remarks (Signed). STATE OF FLORIDA, COUNTY OF DADE. j ss. Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared to me well known, and who, being by me first duly sworn, upon oath deposes and says that he is the of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true. 1 Permit No 13 (Da 5' Date 10 " 22-. 3 / Read, Sworn to and Subscribed before me. Disapproved i� ,, [4 ) Date (Signed) ' Q h L � Notary Public, State of Florida l/�J , j � �r,_S�IL h -!�" Buil g Inspecto - My Commission Expires Date No Y37 Street. NE /0 ST- AC 01 /Uhl 21 ST f /Y(m PLANNING BOARD DATE Chainnan Member Member Member Member Member Council Approved Date Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from the Planning Board. A re inspection fee of 51.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty materials and /or workmanship. Owner's Name and Address R. Paul Weber MIAMI SHORES VILLAGE BIJ ..DING INSPECTION DEPARTMENT APPLIEVTION FOR BUILDING PERMIT Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build- ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. Date No 437 Location and legal description of lot to be built on: 7357 N • UI • Miami C t . Lot Block Subdivision August 4 Registered Architect and /or Engineer Name and address of licensed contractor O b e n o u r Roofing, Sheet Metal & Supply Co. Street and Number where work is to be done 437 N. E. 102nd St. State work to be done and purpose of building (by floors) Remove L T a V e l roof' O n with 1 -30 lb. felt, 2 -1 lb. felts, gab/. fials hing;a____ _and ___graval. and for no other purpose. New Building Remodeling Addition Repairs X No. of Stories To be constructed of Kind of foundation Roof Covering 3 s q s • Estimated Total cost of improvements $ 381.0 0 Amount of Permit $ Zone cubage required plan Cubage Distance to next nearest building__. ______Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Pennanent Supplement, and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors emplo ed by him in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work suc blic notice or notices as are required by the Act. The undersigned agrees to employ only such subcontr agtors, on work to . •e o. • under this permit, as are licensed by Miami Shores Village. Remarks (Signed) _ .a/77 .C� STATE OF FLORIDA, COUNTY OF DADE. j ss. Disapproved (Signed) D Date. I- ✓ 7g 5.00 garage Read, Sworn to and Subscribed before me. /Or/ ,19 StreetN. E. 102nd St. only and replace Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared to me well known, and who, being by me first duly sworn, upon oath deposes and says that he is the of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true. Permit No /1 Notary Public, State of Florida Bu ' ding Inspector My Commission Expires PLANNING BOARD__ .__... DATE Chainnan Member Member Member Member _. _ _ Member Council Approved _Date Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from the Planning Board. A re- inspection fee of $1.00 will be charged when such re- inspection is made necessary by improper notice for inspe, tion or faulty materials and /or workmanship. ,� 4 , ei e Z \ Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build- ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building dui progress of the work. / � Date - -- � , 19 G 7 !J Owner's Nam dress__�__ No.2 7 � Street_ __ eft Registered Architect and /or Engineer // Name and address of licensed contractor fL� Location and legal description of lot to be built on: Lot Block 1137 Subdivision Street and Number where work is to be done �, e !` p State work to be done and purpose of building (by floors) __21.., "f and for no other purpose. Building Inspec Disapproved D (Signed) MIAMI SHORES VILLAGE BUILDING INSPECTION DEPARTMENT APPLICATION FOR BUILDING PERMIT `� • -- ;r■ New Building Remodeling Addition Repairs No. ofStor ies- Q /� To be constructed of Kind of foundation Roof Covering_ _1_�.L_'�'`� _ ago Estimated Total cost of improvements $_,Z,27_ tS Zone cubage required _Plan Cubage Distance to next nearest building Maximum live load to be borne by each floor % I hereby submit all the Tans and § pecifications for said building. Allltices with reference to the building,arrthits construction may Amount of Permit $__t1 e _Size of Building Lot be sent to_ � � � f� . x_ f_ .3. 7742. //a The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement, and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such public notice or notices as are required by the Act. The undersigned agrees to employ only such subcontr ors, on work to be .erformed under this permit, as are licensed by Miami Shores Village. Remarks_ � 9 2 (Signed) STATE OF FLORIDA, COUNTY OF DADE. ss. Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared to me well known, and who, being by me first duly sworn, upon oath deposes and says that he is the of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true. Permit No qi t ''' 9 Date ' 4— C' Read, Sworn to and Subscribed before me. Notary Public, State of Florida My Commission Expires PLANNING BOARD DATE Chairman Member Member Member Member Member Council Approved Date Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from the Planning Board. A re- inspection fee of $1.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty materials and /or workmanship. BUILDING ELECTRICAL PLUMBING ROOFING Owner of Building Architect Contracto ` f /!► or Buildetf� Legal Description. Address of Building Lot 3t/ CONTRACTOR OR BUILDER MIAMI SHORES VILLAGE, FLORIDA PERMIT iN° 12277 Work to be performed under this Permit 0 'II BL / This permit is granted to the contractor or builder named above to const herefor in strict compliance with all ordinances pertaining thereto and ith t drawings, statements or specifications that may have been submitted to time if the work is not done in compliance with such ordinances or if the granted is the understanding that the contractor or builder named abov pertaining to the work covered hereby whether shown on .the•`ptana or done by his agents, servants or employees. Sign rawi Subdi- vision Value of oject $ t the building or to install the equipment or device described in the app understand' - that the work will be performed in compliance with any p d ap oved by th.per municipal authorities. This Permit may be revoked at any plans are changed .ut uthorization. A further condition upon which this permit is assumes the respo •ility thorough kn.• ledge of the ordinances and regulations tements ifica .. t he assumes responsibility for work BY DATF. Contractor's License No BY Amt. of Permit INSPECTOR In consideration of the issuance to me of this pe it gree to perform the work covered hereunder in compliance with all or pertaining thereto and in strict conformity with the plans, rawings, statements or specifications submitted to the proper authorities o In accepting this permit I assume responsibility for all work done by either, myself, my agent, servant or employee...„ 'C.04.04.4 AUTHORIIT 195 on and regulations Mian " Shores Vil, : ge. 1 4) Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build- ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances �f Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. Owner's Name and Address Z u Registered Architect and /or Engineer _ Name and address of licensed contractor Location and legal description of lot to be built on: Lot Block Subdivision_ Street and Number where work is to be done State work to be done and purpose of building . (by floors)___ r and for no other purpose. New Building Remodeling Addition Repairs No. of Stories To be constructed of Kind of foundation Roof Covering L I * t Estimated Total cost of improvements $ ,% ` _Amount of Permit $ Zone cubage required _Plan Cubage Distance to next nearest building _______Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement, and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such public notice or notices as are required by the Act. The undersigned agrees to employ only such subcontractors, on work to -:ke performed under this permit, as are Miami Shores p t, licensed by M Sh Village. Remarks ( Signed) __ STATE OF FLORIDA, COUNTY OF DADE. j ss. Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared and who, being by me first duly sworn, upon oath deposes and says that he is the of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by hitn tatRd e true. Permit �Jo Disapproved d .BUILDING INSPECTION DEPARTMENT APPLICATION FOR BUILDING PERMIT ui : Ins MIAMI SHORES VILLAGE 7 Date_ Date A \kNli 6\0 v. , ) Chairman Member Member Council Approved Date Date � /19 No Street__ / i f to me well known, `r"' Sworn to and Subscribed before me. Notary Public, State of Florida My Commission Expires PLANNING B • RD L_____________ DATE Member Member - Member — — - -- Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from the Planning Board. A re- inspection fee of $1.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty materials and /or workmanship.