ROOFar° E Associates, Inc.
Roofing Laboratory
Testing and Research
Moisture and Up -Lift Testing
Date: 4/19/96
Property address: 308 N.E. 99th. Street, Miami Shores, Fl
Owner: Camesoma
Contractor: Ace Roofing
Permit #: 39156
City: Miami Shores
Type of Tile: Altusa
Product Control #: 94- 0914.01
Roof Slope: 3 -1/2 -12
Sq.ft. area: 3,500 sq.ft. approx.
Testing Equipment: Chatillon - DFIS 100 - Calibrated 9/7/93
2524 W. 3rd. Avenue, Hialeah, Florida 33010
C954)433-1484 * (954 }437 -2332 * Fax (954)437-2296
tletra -Dude County Certification Na. 94- 0125.0E
April 22, 1996
RE.: TEST TO DETERMINE ROOF TILES ARE SECURED TO DECK AFTER 72
HOURS INSTALLATION - ADHESIVE SET - SOUTH FLORIDA BLDG. CODE
3404.3
The purpose of this quality control test is to confirm that there exists sufficient
bonding by the adhesive to the tile and underlayment in the tile system applied; it will be
determined whether 75% of the tile bonds to be tested in three different roof areas, provides
sufficient resistance to an arbitrary static uplift Toad applied on the tile. This procedure will
satisfy the Building Code Compliance requirements set forth in Protocol PA 106 -95.
Tiles have been tested on three different roof areas: field, perimeter and comer
areas. Prior to testing, dimensions of these areas were determined and recorded according
to Chapter 23 of South Florida Building Code.
Tiles selected at random from the three different areas, were lifted by hand, in order
to test for loose components.
LOAD APPLICATION: An arbitrary Toad of 35 Ibf. has been applied to each tile, holding
the load for 5 seconds. Test results are tabulated as follows:
AREA
#
PULLS
LOOSE
TILES
BROKEN/
CRACKED
TILES
ADHESIVE
DELAMINATED
FROM
UNDERLAYMENT
TILES
DELAMINATED
FROM
ADHESIVE
Field
37
none
none
none
none
Perimeter
36
none
none
none
none
Corners
32
none
none
none
none
Enclosed find a sketch of the test site roof, indicating field, perimeter and corner
areas with dimensions, and also, location where pulls have been conducted.
XX
XX
Truly yours,
ETER L. ZA
Lab. Director
Encl. Sketch
More than 75% of the tile bonds tested in each of the three areas, provided
sufficient resistance to the arbitrary Toad applied.
More than 25% of the tile bonds tested in each of the three areas, did not
provide sufficient resistance to the arbitrary Toad applied.
More than 10% of the components have been determined to be "loose"
components.
The static uplift quality control test for the property in question, complies with
the Code requirements 3404.3 and Protocol PA 106 -95.
ZARA AND ASSOCIATES, INC.
RICARDO . CARLES, P.E.
PROPERTY LOCATED AT 308 N.E. 99TH. ST., MIAMI SHORES, FL
55 ft
1
0 Fielt
• Perimeter
0 Corners
22 ft
•
•
0
e
■
■ .
,
•
•
•
•
•
•
•
•
•
•
•
•
•
,
1
,
. 1
1
,
1
N.
43 ft
22 ft
co e
•
28 ft
e r
- j
<`
is
FRONT
-4 ft-
® L 2 ft-
, r
1 1
14 ft
2ft-
32 ft
0
•
•
•
•
•
•
25 ft
l e
•
•
•
•
•
•
7
•
•
•
•
•
•
.
•
•
•
•
•
33 ft
PERMIT APPLICATION FOR MIAMI SHORES VILLAGE
J(
Date ' S� /hob Address 3 0c /VC 77 St2, Tax Folio
Legal Description Historically Designated: Yes No
Owner/Lessee / Tenant A U1. Call /_ S/9/1/4 Master Permit # 3 ' i —
Owner's Address /qS A /3 O v/,
Contracting Co. / /o O F / /(VG CO / /V C. Address regS / S. W g 2 /_ celC , ,f A o o ,
Qualifier G O R 0 0A/ /}' R SS# , 'of- 6 s2 O
State #RC 00 33 k(3T Municipal # 7'.3 S S3 -? Competency # /,2D2 Ins. Co.,&, L ht/ G TMM/ /4,s, C0
Architect/Engineer Address
Bonding Company Address
Mortgagor Address
Permit Type (circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFING PAVING FENCE SIGN
WORK DESCRIPTION
Square Ft.
Rea
WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING,
CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.)
Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I
certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate
permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK.
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will . - ofie in complian cy with all applicable
laws regulating construction and zoning. Furthermore, I authorize the above -named contractor to do . e ork stated.
Signa e of owner and/or on o • resi . ent Date
` a 1C\ 1, 6 Notary as to Ome and/or Condo President
My Commission Expires:
0,:'-. i i , ;r rtL
N o ` �:'t ATE or: .i ..I:. -.
':..;i.;.): N '.:::: i
FEES: PERMIT r (lf RADON
APPROVED:
Zoning
Mechanical
,q 4o HP o v /f (4
y
Estimated Cost (value) /8 0 0 0 f
Building
— t 9 (o
Date
g6
C.C.F.
Phone
N. as.tpceofi ctweEOCKilenwT1iliidSEAt.
My C fission irk ^'''A P1 ��o�aTe .�
Electrical
Date
NOTARY TOTAL DUE ZA1
Plumbing Engineering
2. Description of improvement*
Notary Public 40 A93..
Print Notary's Name
My Commission Expires:
123.01.112 1194 PAGE
KAREN LYNN MOCILIA
NOTARY PUBLIC STATE OF FLORIDA
COMMISSION NO. CC418456
MY COMMISSION EXP. NOV. 2,1998
--Pc-aae—e1141-44-a-tea■,.--
Signature of Owner
Print Owner's Name i � ,q r IL ('i p , N, s
Sworn to and subscribed before me this ) day of ' 19 Qco
STATE: OF Fica7 ;T ,
1 HE'Ct:Y CSif�r% a D., J. cf he
Ori3iuelfiI irr / r. ; r
day of
--- <` - 4 . 4 19 9l
W.TNESS my h
HA7IV£`t UV `s
By
F - eoP
PERMIT NO. TAX FOLIO NO.
STATE OF FLORIDA
COUNTY OF DADE
3. Owner(s) name and address: /
NOTICE OF COMMENCEMENT
A RECORDED COPY MUST BE POSTED ON THE .SOB SITE AT TIME OF FIRST INSPECTION
968046 1 18 1996 FEB 01 12:55
THE UNDERSIGNED hereby gives notice that improvements wil be made to certain real property, and in accordance
with Chapter 713, Florida Statutes, the following information is p ovided in this Notice of Commencement.
1. Legal description of property and street address*
3o QG� /v/z7 f p / 0 57t
Interest in property: R
Name and address of fee simple titleholder:
A1/1 Mr5ANRS
4. Contractor's name and address* gcbr Roo, 74/ // '/C ,
3B8c .s, ‘,33/z_
5. Surety: (Payment bond required by owner from contractor, if i iny)
Name and address*
Amount of bond: $
6. Lender's name and address
7. Persons within the State of Florida designated by Owner upoi i whom notices or other documents may be served
as provided by Section 713.13(1)(a)7., Florida Statutes.
Name and address*
8. In addition to himself, Owner designates the following person) s) to receive a copy of the Lienor's Notice as pro-
vided in Section 713.13(1)(b), Florida Statutes.
fk!^rne a address•
9. Expiration date of this Notice of Commencement (the expiratic n date is 1 year from the date of recording unless
a different date in specified)
Prepared by P• O `:-'N 1 4 ( ✓G
ACC Roof/M6 /tvC
Address: f `' 3Z r lkl?
ZAcip
Job Address: 3 Alb: cf 1 Sr/. Contractor:
Underlayment (continued):
Check all of the following which apply to the proposed underlayment
for use wit the proposed tile system assembly:
ASTM #30 asphalt saturated felt with: ❑ 19" overlap
❑ ' overlap
• 4" overlap
Manufacturer: F It(
❑ ASTM #15 asphalt saturated felt with:
Man acturer:
❑ Other:
Type:
Manufacturer:
❑ Other:
Type:
Length:
Manufacturer:
Mineral Surfaced Roll Roofing with:
Manufacturer: 4
Underlayment Fasteners (if applicable):
"
❑ 19" overlap
❑ 6" overlap
l3/" overlap
❑ 19" overlap
❑ 6" overlap
overlap
Check one of the following which apply to the proposed
underlayment attachment:
❑ Minimum 12 ga. electro - galvanized roofing nail with
minimum 32 ga. x 1' /," tin cap:
Length:
Manufacturer:
n Po°
Mortar or Adhesive Set Tile Systems
Page - 3
Spacing (per tilt system assembly Product Control Approval):
Field: /2 " o.c.
Laps: �i " o.c.
5. Related Accessories:
Edge Metal (refer to Section 3408.2 of the South Florida Building
Code):
Type:
Dimensions:
Gauge or Thickness:
Finish:
❑ Cold Adhesive:
4 / 1 / c- (OProcess No.
Type:
Manufacturer:
tAV6S /p
2x
2c
Note: All edge metal shall be nailed on the flange and nailed or clipped
at the face in compliance with the provisions set forth in Dade
County Protocol PA 111, marked Appendix 'U' in the South
Florida Building Code.
Adhesives (check one of the following):
Flashing Cement:
Type: .8 /7
Manufacturer: /ft 2N 4
Job Address: � og 1kt r 9'9 Si
Rid Height:
� feet
Contractor: ' 1 Too C
c �• ° '!e∎oht: Roof Height
1A, / t
BUILDING INFORMATION #1
Job Site Identification:
Mortar or Adhesive Set Tile Systems
Page - 6
Insert Building Ridge Height, Eave Height and Roof Mean Height.
Also insert applicable information pertaining to the building below.
( See ASCE 7 -88 Fact Sheet Attached )
Exposurc Category:
Classification Catcgory:
AI l lurricancc Occanlinc?: Y N
Basic Wind Speed at
Building Location. 110 mph
Building Condition based on
% of openings:
(See Table 9 oJASCE 7 -88)
Ground Level
Process No.
Job Address: 30 g Af' Cm sin ,
Adhesives (continued):
Note: Application of adhesives shall be in compliance with the Roofing
Component Product Control Approval and the minimum
requirements set forth in Subsection 3403.5(e)(4)(cc) of the South
Florida Building Code.
Ventilation System (check one or more of the following):
The following information is required to confirm compliance with
Subsection 3401.4(e) of the South Florida Building Code.
❑ Ridge: Type
Soffit: Type
Note: If underlayment is comprised of a self - adhered membrane, both soffit
and ridge ventilation systems are required, unless a base sheet is
applied as an anchor sheet below the self - adhered underlayment.
Note: The Tile System Assembly shall be installed in strict compliance
with the application instructions enumerated in the Product
Control Approval. A permit shall be issued for application of the
specified Tile System Assembly only. Any change to the specified
Tile System Assembly shall require submission of a revised
SECTION II with a copy of SECTION I, noting the permit
number issued.
Job Address: ',30? /V6 gel JtI.
Ridge Venting:
r vaPPfitoble )
Dcck: 1
type:
r,
Thickness: _
Underlayment: 4 30 f/= L
Mortar or Adhesive Set Tile Systems
Page - 4
Underlaym ent � �' /'
Fastener: / / I H (h t X o o f . / 1 4. 5
3 � �
/ Roof Pitch
12"
DETAIL #1
Job Site Identification:
Contractor: 9c, /v o
Mortar or Adhesive Set Tile Systems
Page - 5
Additional Notes:
C O. Process No.
Contractor: / ?C/.' ( ?0 O k' a No.
FILL IN APPLICABLE ROOFING COMPONENTS WIIICII MAKE UP
TILE SYSTEM ASSEMBLY. INSERT ANY ADDITIONAL LEADERS
INDICATING ADDITIONAL ROOFING COMPONENTS NOT SIIOWN
ON THIS PAGE. ( Where Roofing Component not used in Tile System
Assembly, fill in with "N /A ". )
Head Lap Dimension:
(minimum 1' unless otherwise specified
in the tile system assembly Product Control
Approval) _/�IJ
Mortar /Adhesive: �RF 't / / )(
Tile:
CAAy
Tile Fastener:
Edge Metal or Gutt r �
Fastener: / • /L f
Bird Stop: C 4 y
(tf applicable )
Edge Metal 7 `e . 2 .
or Gutter: )L
if R
Existing or Proposed , S /,
Soffit Venting: ry (�
d it/ 3G e+ -ro Lid`'CENTF
Job Address:
9 Srel.
Job Address: 2 °g IIV' cry . St - ft.
Manufacturer: CT i 1
❑ ASTM #15 asphalt saturated felt with:
Manufacturer: l rim
Mineral Surfaced Roll Roofing with:
Manufacturer:
❑ Other:
Type:
Manufacturer:
Underlayment Fasteners (if applicable):
❑ Other:
Type:
Length:
Manufacturer:
Rid f Height:
�r /�L feet
11
O 19" overlap
O 6" overlap
131" overlap
O 19" overlap
O 6" overlap
4" overlap
Contractor:
BUILDING INFORMATION #1
Job Site Identification:
Underlayment (continued):
Check all of the following which apply to the proposed underlayment
for use with the proposed tile system assembly:
Check one of the following which apply to the proposed
underlayment attachment:
❑ Minimum 12 ga. electro- galvanized roofing nail with
minimum 32 ga. x 1' / tin cap:
Length:
Manufacturer:
T
moo• -� '!e" ht: Roof M,qan Height
et
/0 Fri
Mortar or Adhesive Set Tile Systcms
Page - 6
Mortar or Adhesive Set Tile Systems
Page - 3
Insert Building Ridge Height, Eave Height and Roof Mean Height.
Also insert applicable information pertaining to the building below.
( See ASCE 7 -88 Fact Sheet Attached )
Exposure Category:
Classification Category:
At Ilurricancc Occanlinc ?: _ Y _ N
Basic Wind Speed at
Building Location• 110 moh
Building Condition based on
% of openings:
(See Table 9 of ASCE 7 -88)
Ground Level
Process No.
Contractor: /�'C -/� / ( J4 ,� Coprocess No.
ASTM #30 asphalt saturated felt with: ❑ 19" overlap
0 'overlap 5. Related Accessories:
• 4" overlap
Spacing (per tile system assembly Product Control Approval):
Field: 2 " o.c.
Laps: " o.c.
Edge Metal (refer to Section 3408.2 of the South Florida Building
Code):
Type: EA1//l: ,S 22'p
Dimensions: 2 x Z
Gauge or Thickness: 2
Finish: (141. 1/1
Note: All edge metal shall be nailed on the flange and nailed or clipped
at the face in compliance with the provisions set forth in Dade
County Protocol PA 111, marked Appendix 'U' in the South
Florida Building Code.
Adhesives (check one of the following):
❑ Cold Adhesive:
Type:
Manufacturer:
Lit' Flashing Cement:
Type: # /7
Manufacturer: / /11 /4.1 r4 (�
Job Address: 30Y NF_ c ( Stn • Contractor:
APPENDIX 'E'
METRO -DADE UNIFORM BUILDING PERMIT
SECTION II
MORTAR OR ADHESIVE SET TILE SYSTEMS
1. General
The information provided in this Section is required to confirm
Product Control Approval of the proposed tile system assembly;
confirm compliance with the wind load requirements of Chapter 23
of the South Florida Building Code (SFBC); and confirm compliance
with Sections 3403.5 and 3404 of the South Florida Building Code.
2. Documentation
The following documents are required for submission with the
Uniform Building Permit application:
► Two (2) copies of the proposed tile system assembly's and
associated roofing component's Product Control
Approval(s).
► One (1) copy of the tile system assembly and/or roofing
component(s) manufacturer's published application
instructions and literature.
► All documents attached herein, filled out and completed in
full.
3. Project Information
Check one of the following:
❑ yew Construction
Re -Roof
Noje: Mortar or adhesive set tile systems are not acceptable as recover
applications.
l2aoi -158
Mortar or Adhesive Set Tile Systems
Page -1
Pee Iao o Coo , Process No.
Is the deck solid sheathed? (circle 'yes' or 'no')
yes no
Deck Type (check one of the following):
❑ Nominal %2" Plywood (for re -roof only)
❑ Nominal' /," Plywood
❑ Wood Plank / �!
❑ Other (fill in) f x G / -� - G
Roof Pitch (fill ink:
3 Z ": 12"
Note: Mortar or adhesive set tile systems shall not be installed at a pitch
greater than 7V2 ":12 ". Mortar or adhesive set tile applied at a
pitch greater than 5 ":12" and less than or equal to 7 ":12" shall
have the first three courses of tile nailed with not less than one
nail per tile. As an alternate, the first three courses of tile may be
applied in mortar over a single layer of minimum 12 ga. wire
mesh with square openings of not less than 3 /," which is
mechanically attached to the sheathing with not less than one nail
per 2 R
Circle 'ves' or 'no' for each of the following:
Have you attached two copies of the tile system manufacturer's
Product Control Approval for the proposed tile system?
no
Have you attached a copy of the tile system assembly and/or
roofing component(s) manufacturer's published, application
instructions and o}}h�er literature
l vet, no
Is the proposed underlayment approved for use with this tile
system assembly ? -
no
Job Address: 3Cg K6 ¶ 1 StA
Contractor:
The undersigned certifies that the Mortar or Adhesive Set Tile System
Assembly is in compliance with the plans, specifications, and details
submitted by the architect.
STATE OF FLORIDA - COUNTY OF DADE
Before me this day personally appeared
who, being first duly sworn, deposes and says that all information submitted
herein is true and correct.
Licensed Contractor / Owner
Signature
Sworn to and subscribed before me this th day of
19
My commission expires:
Notary Public
State of Florida
Mortar or Adhesive Set Tile Systems
Page - 8
Process No.
Job Address: 3 IY A: ( SfA. Contractor:
The undersigned certifies that the Mortar or Adhesive Set Tile System
Assembly is in compliance with the plans, specifications, and details
submitted by the architect.
STATE OF FLORIDA - COUNTY OF DADE
Before me this day personally appeared
who, being first duly sworn, deposes and says that all information submitted
herein is true and correct.
Licensed Contractor / Owner
Signature
Sworn to and subscribed before me this th day of
19
Job Address: 3e3f NF t sr
123.01 -158
My commission expires:
Notary Public
State of Florida
APPENDIX 'E'
METRO -DADE UNIFORM BUILDING PERMIT
SECTION II
MORTAR OR ADHESIVE SET TILE SYSTEMS
1. General
2. Documentation
Contractor:
The information provided in this Section is required to confirm
Product Control Approval of the proposed tile system assembly;
confirm compliance with the wind load requirements of Chapter 23
of the South Florida Building Code (SFBC); and confirm compliance
with Sections 3403.5 and 3404 of the South Florida Building Code.
The following documents are required for submission with the
Uniform Building Permit application:
► Two (2) copies of the proposed tile system assembly's and
associated roofing component's Product Control
Approval(s).
► One (1) copy of the tile system assembly and/or roofing
component(s) manufacturer's published application
instructions and literature.
► All documents attached herein, filled out and completed in
full.
3. Project Information
Check one of the following:
❑ yew Construction
M' Re -Roof
Nole: Mortar or adhesive set tile systems are not acceptable as recover
applications.
Mortar or Adhesive Sct Tile Systems
Page - 8
Mortar or Adhesive Sct Tile Systems
Page -1
PeE %Z.o or I CO, Process No.
Is the deck solid sheathed? (circle 'yes' or 'no')
yes no
Deck Type (check one of the following:
❑ Nominal '/2" Plywood (for re -roof only)
❑ Nominal' /," Plywood
O Wood Plank "
❑ Other (fill in) /x G
Roof Pitch (fill in):
3 Z ": 12"
Note: Mortar or adhesive set tile systems shall not be installed at a pitch
greater than 7Y2 ":12 ". Mortar or adhesive set tile applied at a
pitch greater than 5 ":12" and less than or equal to 7 ":12" shall
have the first three courses of tile nailed with not less than one
nail per tile. As an alternate, the first three courses of tile may be
applied in mortar over a single layer of minimum 12 ga. wire
mesh with square openings of not less than ' 4" which is
mechanically attached to the sheathing with not less than one nail
per 2 ft'.
Circle' yes' or 'no' for each of the following:
Have you attached two copies of the tile system manufacturer's
Product Control Approval for the proposed tile system?
rves� no
Have you attached a copy of the tile system assembly and/or
roofing component(s) manufacturer's published, application
instructions and o}her literature
1 vet, no
Is the proposed underlayment approved for use with this tile
system assembly?
no
Process No.
Job Address: ,3 /V ! ? Stn. Contractor:
Job Address:
Project Information (continued):
If the proposcd undcrlayment is self - adhered, have you complied
with the venting requirements of Section 2913.3 (b), (c) and (d) of
the South Florida Building Code?
yes no
Are all related accessories approved for use with this tile system
assembly/
Are the proposed edge metal attachment fasteners in compliance
with the requirements of the South Florida Building Code (minimum
ye
12 ga. annular rinshank, corrossion reisistant nails)/
no
4. The Tile System Assembly:
The following information is required to confirm compliance with
Subsections 3403.5(a) and (c) and Section 3404 of the South Florida
Building Code.
Tile:
Tile Name:
Manufacturer:
Tile Ma 'al:
Clay
❑ Concrete
❑ Other:
Product Control Approval Number: 9 / -0i V
Mortar or Adhesive:
no
• SPRNf5k 5 (Ay mil-
/ G 7"(1S A �,�
bg ,v, 97 st2 ,
/3
I' .y '
33 S2
Contractor:
t
i
�r /'oo
Check one of the following which apply to the proposed tile
securement for use with the proposed tile system assembly:
Mortar or Adhesive Set Tile Systems
Pagc - 2
Mortar or Adhesive Set Tile Systems
Page - 7
Ly' Mortar: Manufacturer: e 1/TE
❑ Adhesive: Type:
Manufacturer:
Tile Fasteners (for first three courses if roof pitch exceeds 5 ":12"
and is less than or equal to 7 ":12 "):
Check one of the following which apply to the proposed tile
fasteners (for the first three courses) for use with the proposed tile
system assembly:
❑ Other: Type:
Length:
❑ N/A
Underlayment:
1141inimum 12 ga. galvanized roofing nail:
Length:
•
BUILDING INFORMATION #2: Roof Plan with Perimeter and Corner Dimensions
Job Site Identification:
C . , Process No.
Mixing Ratio:
4.
11
Note: All tiles shall be installed in compliance with the provisions set
forth in the tile system assembly manufacturer's Product Control
Approval and the minimum requirements set forth in Subsections
3403.5(c) and 3404.2 of the South Florida Building Code. Tile
fasteners in the first three courses (if applicible) shall be of
sufficient length to penetrate the sheathing a minimum of 1" or
through the sheathing thickness a minimum of / ", whichever is
less.
The following information is required to confirm compliance with
Section 3403.5(b) of the South Florida Building Code.
J '
r e5'1;)rocess No.
Sketch Roof Plan, indicating all dimensions, slopes and any roof top equipment.
Also insert variable labeled "a" which represents perimeter and comer dimensions
per Chapter 23 of the South Florida Building Code.
(See ASCE 7 -88 Fact Sheet Attached )
Al;11S :1 Tile
lC
Alfareria del I urbio, S.A.
• 13arquisimeto, Venezuela
PRODUCT NO_ :
ACCEPTANCE ,NO_:
EXPIRES:
Your application for Product Approval ofAltusa Tile Nail -0n, Mortar or Adhesive ,Set Clay "Altura S" Roofing
Ti 5 under Chapter 8 of the Metropolitan Dade e -County Code governing the use of Alternate Materials.and Types of
Construction, and completely described in the plans, specifications and calculations as submitted by Redland
Technologies, The Center for Applied Engineering, and Testwell Craig Laboratories & Consultants, Inc
has been recommended for acceptance by the Building Code Compliance Department to be used in Dade County,
Florida under the specific and standard conditions set forth herein_
The approval shall be valid for a period of three years- The Building Code Compliance Department reserves the
ri& t to secure a product or material at any time for a jobsite or manufacturer plant for quality control testing If
product or material fail to perform in the approved manner, the Code Compliance Department may revoke, modify
or suspend the use of such product or material immediately. The Building Code. Compliance Department reserves
the right to require testing of this product or material should any amendments to the South Florida Building Code be
enacted affecting this product or material_
The expense of such testing will be incurred by the Manufacturer.
4- 14.01
9 R9
FEB I q 1997
• 1 :: ) ; is i ! ; i I) . i) i , .. ; i i i '� , i
ii( I1A; ;i ! I Ai ;I I it Ill 111 I AN( ;
( ( "t I,:.: +;I I1; l'Ait17.1! t.,
: .1;:,;
..., il;t)i':,I i! iin+;ii 1111111;
M.111! ,11 I I OI111)A :1-113:1-1!;1,3
(:SIP,) :3/$ -?9O1
:A •: ( :30 :0 37_` 2 J013
Raul Rodriguez
Product Control Division
Supervisor
- PLEASE NOTE -
TIIIS IS THE COVERSIIEET. SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL
CONDITIONS.
BUILDING CODE COi\ti1ITTEE
This applic :!ion for I'roducl Approval ha> bccn rcvic"'al by the r Ae i r(ltn)tit:in D :'dc County Building Code
Coiiipli:ince :n n +cio ::nd :i.ppiovcii by the Building Lo('..: C.Ur11i11Ii;tC : I urcd +n D:1(1C Co n_y . Florid:: t1: d & r
i
;11, ('ut :(li; ir •::'i fUr;;+ : :!';, -•i- /; ,// I/ i
., : i / , -:
i ,l
A \Itusa I de
Alfareria del I uri)io. S.A.
13arquisinlcto• Venezuela
'Itt) ;,ut (:();\ 1.1“)1.!'\'()I I.l)t :1t c r.I•I \\t ;.
l:()()r I:\r: S1..1! \I.
Cateory: Prepared Roofing
Sub ateaor� : Tile
Nail -on /Mortar Set/Adhesive Set
Sub -Tvoe: Clay
°$vstem Description
Contact:
Carlos J. Fernandez
General 1-lanaeer
Altusa Tile, Almar (1JS. \). Ine.
66 - -15 Northwest 77th Avenue
Miami_ i >> I66
(
I'toa7nCI (o:i ::01 No 9•: 091:1 01 --
Approval Date:
Expiration Date:
Alfareria del Turbio, S.A. ( Altusa), located in Barquisimeto, Venezuela, manufacturers clay roof
tile for nail -dn, mortar set or adhesive set applications_ All tile is manufactured from natural Venezuelan
clays. This Product Control Approval relates to Altusas "Altusa S" tile profile_ Refer to appropriate
Product ontrol A • royals for other tile ore file
The "Altusa S" tile profile is available in a variety of natural clay colors and has matching trim
pieces used for rake hip, ridge hip, and valley terminations_ These accessories are manufactured for all
profiles and form a part of this Product Control Approval_ Optional rubber or clay eave closures are also
available.
Altusa roof tiles have been tested in compliance with the South Florida Building Code
requirements for clay, nail -on, mortar set or adhesive set tile applications_ The minimum roof slope for
" Altusa S" nail -on tiles shall be 2 ":12 ". See thr "Profile Drawing" section in this approviti for the
" Altusa S" profile drawing_ The "Altusa S" profile has been tested for both wind characteristics and
static uplift performance, therefore, any consideration for installation shall be done as a 'Moment Based
System'. Data for attachment calculations is noted in Tables 1 through 4 of this Approval_
Almar (USA). Inc., located in Miami, Florida, is the sole approved importer under contract for
selling. and distributing_ Altusa products in the South Florida jurisdiction_
FEB 1 1 1991
1'1 od ;act
A In r,a *S• v Roof
Ti
Trull Pieces
(1j PIZ( )01:f (,)1;.
1. I) i:)' ;T. It \
I = varies
w = varies
varying thickness
c•.t
AS I C 1 if
ASTM C 1167
ACCeSSOsy II clay root - pieces for
use at hips, rakes, richzes and valley
terminations. Manufactured for each
the profile_
ip,11
i111;111)111: l jc k i:i , 011C-
S NII:ipCd. clay roof file equipped with
two nail holes and nIllC roll. l'or
direct deck nail-on applications only.
I'r udul'l
=30
Mineral Surface Cap
Sheet
Lenzingtex -ZB 140
Underlavment
Rainproof I1
Ice and Water Shield
Moppintt Asphalt NIA
.• Ceinciti
k( 1;,;111) O 1111:1:
!:: \
59" x 164' roll
22 lbs/roll
30 "x75'roll
36" x 75' roll
or
60" x 75' roll
36" x 75' roll
• •∎'11(..(11(•
: \ \ 1 1 :_ h
1) II
t;43 Coated Base N/A ASIM 1) 2626 Saturated and coated
Sheet organic base sheet for
sinttic or double ply
underlayment_
N/A
AST,MI D 249 Mineral surfaced generic
asphalt roll roofing
for use as a top ply in
a double ply
underlayment system.
PA 104 Single ply, nail -on Len zing
underlayment_ Performance, Inc_
PCA '194- 0527.05
PA 104
PA 103 Self - adhering W.R. Grace Co_
underlayment for use PCA 492-1 1 16.01
as a top ply in a two
ply underlayment
system with approved
#30 or 43 as the base
laver.
.?Sf.1 0312
type 11! or IV
1 ': o,4:.r(
1). . I•ri;nn
:.: :maicd ur ^:+1):c: r. :1(
io bi. uf:cd n•; a n:ulcd
:nichor sheet.
Single ply, nail -on
underlayment with 2"
self - adhering top
edge_
Asphalt for bonding a
mineral surface cap to
a mech. attached base
sheet in a double ply
u nderl : S.Stem.
genCnc
I) - 5 ;ri (-ui f?' ; ;r':alt • :.1111 i
.1.. ,., .
gCllef;C
Protect -O -Wrap, Inc.
PCA 494- 0714.01
Roorrif, Naih:
Tin Caps
Wood Bat
Tile Nails
Tile Screws
Roof Tile MOM'S
t"TileTiterm")
Roo: ;l k:
:\!!!(:)..)
1•11 t
111111. 12 r:S. W1111
111...2.(1
min_ 32 ga.
min_ 1 o_d_
max_ 2 o_d_
horizontal
min_ I" x 4" for use
with vertical bartens
or
min_ I" x 2" for use
alone
min_ 8d x T/2" or
min_ iOt1Xi -
min_ x TA or
min. g10 x 2
PA 1 ri
Append's 1]
PA 114
Appendix E
PA 114
Appendix E
PA 114
Appendix E
NIA PA 123
NSA
1),•..cr tio;t••■■
Co;
ii it/
Annohr tint; siitlok.
hot (Sipped, clecno or
mechanically g:lv.
rootil; nails (or use
in under hiyncot
attachment.
Corrosion resistant
circular disc for use in
underlayment
attachment
vertical Wood Preservers Salt pressure treated generic
thin_ 1" x 4" Instinite LP - 2 or decay resistant
lumber battens
Corrosion' resistant,
screw, smooth or
annular ring shank
nails.
Corrosion resistant,
coated, coarse thread
wood screxvs.
Prepared mortar mix
designed for mortar
se: root
applications.
- 1 1) COtiti)ofIc:1;
** C.
t',Clit:t
generic
generic
generic
Bermuda Roof
Company, Inc.
PCA ; -06 14.01
°ducts.
I o e.
()!:() 01
Roorrig Nn
Tin Caps
Wood Battens
Tile Nails
Tile Screws
Roof Tile Mortar
C'TileTiter"
!le A.dlicsive
1 wit
' he
min_ 32 ga.
min_ 1 o. d.
max. r o_d_
vertical Wood Preservers Salt pressure treated generic
min_ 1 institute LP - 2 or decay resistant
lumber battens
horizontal
min 1" x 4" for use
with vertical battens
or
min r x 2" for use
alone
min_ 8d x T/2" or
inin_ iOd x
min. #8 x 2%.. or
min. :"--!10 x 2
PA 114
Appendix
PA 114
Appendix E
PA 114
Appendix E
PA 114
Appendrx E
NiA PA 123
See
■■.!to,
1),•.cs rio; ■•,ts
!!!...irmi.!!
Awitihr shank.
hot dipped, cicctro or
mechanically gait!.
roofing nails for use
in underlayment
attachment.
Corrosion resistant
circular disc for use in
underlayrnent
attachment
Corrosion resistant,
screw, smooth or
annular ring shank
nails.
Corrosion resistant,
coated, coarse thread
Wood screws.
Prepared mortar m ix
desilmed for mortar
se; roof tile
apnliC2tions.
Iwo ctImpor!co;
!.!!!!cth:!!!!.!
I!!!
•..: :;!.•
generic
generic
1.1, I" I
°Crier
Bermuda Roof
Company, Inc.
PCA ;:'J-1- 06
°doers,
Inc
O.:0 01
(
Valley Flashing
Drip Edge
11 311u •s:-.1 *,(r..
ofi!I
:mit. () 06(i'
l'...r.tencr,
mill. Sri x
:-;•C.V.N11/,:d NICCi
1C.:1112CilinCni
clips for supplcmcnuil
rile ;Ii(acttmcnt. Clips
arc installed with
corrosion resistant
rooting nails
compatible with the
clip. A hurricane clip
is required on all cave
tiles.
min. 26 ga_ ASTM A 525 Galvanized steel _generic
min. 16" width valley flashing
min. 26 oa_ • PA 111 Galvanized steel drip generic
min. 2" face flange ed.cle
min. 2" deck flange
i'■•■■!■,,
1).,c111,1:•••!
.1: 1;•,1.:
11.1,111LIC11:1,1
R land-Technologic
The Center for Applied
Engineering. Inc.
Idris idn
It,: -0
Appendix 111
7161
A ppend ix 111
25-720
The Center for Applied 94-084 Static Uplift Testing May 1994
Engineering, Inc. PA 101
(Mortar Set)
The Center for Applied 94-083 Static Uplift Testing April 1994
Engineering Inc. PA 101
(Adhesive Set)
Dec_ 1991
Redland Technologies Letter Dated Aug_ I, 1994 Wind Tunnel Testing Aug 1994 .
PA 108
(Nail-On)
Aug. 1994
Redland Technolooies PO402 13. Resistance Sept. 1993
Testing of screw es.
shank nails
Oct. 1994
Redland Technologies 7161-03 - Wind Tunnel Testing
Appendix II PA 108
(Nail-On) -
Redland Technoloaies P0647-01 Wind Tunnel Testins!
PA . 103
(Mortar Scz)
The Center for Project No. 307025 Wind Driven Rain
1 Inc. Tes NIDC-78 l'A 100
■•", x■iti I
C .
Lab t: 1 1. P-2
ri:e11 . Porcello
r
r.
10?
Static Uplift 1
l'A 102(A)
Static Uplift Testis
PA 102
(Quite-Drive Screws, Battens)
''c:1 Propel:v
1167
I '• I ';.)
Pee. 1991
Feb. 1995
Oci. 199.;
.' \.,
t .
i (
I - ,';: 1I,;:c,n: ,, \ew, :unti(,t:ctun: /.� • „,c::,i,-7 f,lvvr. >,:,f,r
S 1'S (1- \1 1): iMMooar or Adhesive Set Apl>I:cU:On
Slone I :In';c: 2 ":12" to 7” :12"
Note: System I) is onlv acceptable in this slope range_
Undcrlavmcn (:
Roofing Tile:
Install choice of approved underlayment system, noted on Page 1 of Dade
County Protocol PA 120, in compliance with Section 102 of PA 120. See
System Limitation #7_
Install tile in compliance with PA 120 using one of the approved mortars or
adhesives noted in this approval_ Mortar or adhesive shall be applied in
compliance with the mortar or adhesive manufacturers Roofing Component
Product Control Approval_ The mortar or adhesive attachment shall provide
sufficient attachment resistance expressed as a moment to meet or exceed the
required moment of resistance determined in compliance with PA 1 15 or PA
127_ The mortar and adhesive attachment data is noted in Table 4, attached.
Comments: 1_ For re -roof applications, "4," plywood is an acceptable substrate_
2_ For mortar set applications, the first three courses of tile shall be nailed with
not less than one nail per tile_ As an alternate, the first three courses of tile
shall be applied in mortar over a single layer of minimum 12 ga_ wire mesh
with square openings of not less than '/," .which is mechanically attached to the
deck with not less than one rooting nail every I ft For roof pitches from
6 " :12" to 7 " :12 ", every third tile of every fifth course, beginning at the eighth
course, shall be nailed with not less than one nail per tile_
Altusa 'S' Tile
Tile
Profile
Altusa 'S' Tile
3 ":12"
or Tess
Battens Direct
Deck
4.47 5.35
4 ":12"
Battens Direct
Deck
nts due to Gravity - M (ft-Ibf)
102 Testing
5 ":12" 1 6":12"
Battens' Direct
I Deck
Battens
4.40 5.27 I 4.31 ! 5.16 I 4.20
Direct
Deck
5.03
7 ":12" or
greater
Battens
4.08
Direct
Deck
N/A •
Tile
Profile
Altusa 'S' Tile
Tile
Profile
Table 1: Aerodynamic Multiplier - X (ft')
from PA 108 Testing
Table 2: Restoring Mome
from PA
1)A TA I' )It ATI IEN r
Cm,r tn,A rIo s
Table 3: Attachment Resistance Expressed as a Moment - M (ft-lbf)
from PA 102 and PA 102(A) Testing
TILE APPROVED
APPLICATION NAILS
1 nail + 2 nails
Battens I N/A N/A
Direct Deck 1 6.20 1 8.40
X (ft
Batten Application Direct Deck Application
0.29
APPROVED
SCREWS
1 screw 12 screws
Product t :un:t i Nu
APPROVED
FIELD CLIP
WITH:
X (ft')
0.31
1 nail 1 2 nails 1 nail 1 2 nails
N/A 1 26.80' N/A 1 N/A N/A
28.70 + 31.80 21.20 1 25.30 26.90
APPROVED
EAVES CLIP
WITH:
N/A
34.90
Screws for tile installation over battens shall be #8 x 2W long. corrosion resistant. Quik -Drive screws installed
in two manufactured holes located 1 and 1 from the head of the tile.
Table 4: Attachment Resistance Expressed as a Moment - M (ft
from PA 101 Testing
L
1 Tile f Tile I Attachment
I Profile � Application I Resistance
I
.- il(l:; 'S• Tile I Mor1'3r Set 1 24.50
I Sr:: 66 f50
A LT( ISA
Clay Root riles
11 /
DOVE TAIL LOCKS
'1:1,1 i:,l
ALTUSA 'S' TILE
•1 0:1 11,
N(111 t, QI 1( _571∎Nt);l1:1) f_f>_�`!
phis approval Supersodcs approvals_
Last ,\pprov:il f'nlnlii•r 9 4-0106. IS
Raul Rodrinucz
Product Control Oivis:on
Supervisor
• r i i i i i(.1:1 11;i•It
111. :., r.a.t:
;:Ut I I: iGn;1
. .:c 1 I ).; ?!; I ; !, :I ? It liifii.t)GIC
::)': ;1 1
1 ).1 :1:11 :l1) -1;(i i
(:IO%) ai5- : 1
rn . ( :11y; :175 -2.90s)
1 Extensions o1 Acceplancc may be considered after a new application has 1,, tiled and the supporting
data, test reports no older than tcn (10) years, have been re-evaluated.
All reports of re- tcstimz shall bear the seal, signature and date of an cn_in:cr registered in the State of
Florida_
Any revision or change in the materials, use,. or manufacture of the product or process shall automatically
. be cause for termination, unless prior approval is granted for revisions or change.
3_ . Any unsiitisfactory performance of this product or process or a chance in Code. provisions shalt be grounds
for re- evaluation.
This acceptance sita !1 net be used as an endorsement of any product for sales or advertising purposes.
5. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the
• expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is
displayed, then it shall be done in its entirety.
6. Product approval drawings_ where required for permit applications, shalt be provided to the applicant by
the manufacturer or his distributors unless otherwise noted in the Notice of Acceptance. The prints need
not be re- sealed by an eni.inecr_
Failure-to comply Nvith the Standard Conditions shall be cause for tennination of the Approval.
•
METRODADE
Poly foam Products, inc.
2400 Spring - Stuebner Road
Spring, Texas 77383
Your application for Product Approval of Poiyfoam P eduess "Po y rn AA„H -160" Ranf Tits_, dhesive under
Chapter 8 of the Metropolitan Dade County Code governing the use of Alternate Materials and Types of
Construction, and completely described in the plans, specifications and calculations as submitted by The Center for
Applied Engineering, Inc. and Miles Laboratories Polymers Division has been recommended for acceptance by
the Building Code Compliance Department to be used in Dade County, Florida under the specific and standard
conditions set forth herein.
The approval shall be valid for a period of three years. The Building Code Compliance Department reserves the
right to secure a product or material at any time for a jobsite or manufacturer plant for quality control testing. If
product or material fail to perform in the approved manner, the Code Compliance Department may revoke, modify
or suspend the use of such product or material immediately. The Building Code Compliance Department reserves
the right to require testing of this product or material should any amendments to the South Florida Building Code be
enacted affecting this product or material.
The expense of such testing will be incurred by the Manufacturer.
PRODUCT NO. :
ACCEPTANC>r`NO.: 25- 0314.10 ul Rodrigu
APB 2 7 19 9 8 roduct Control Division
EXPIRES: Supervisor
- PLEASE NOTE -
TIIIS IS THE COVERSNEET. SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL
CONDITIONS.
BUILDING CODE COMMITTEE
This application for Product Approval has been reviewed by the Metropolitan Dade County Building Code
Compliance Department and approved by the Building Code Committee to be used in Dade County, Florida under
the conditions set forth above.
APPROVED:
3 / � q METROPOLITAN COUNTY,
FLORIDA
DADE FLAGLER BUILDING
moaucTsmmultimajmesssaarict
AAfi 2 7 1995
BUILDING CODE COMPLIANCE DEPARTMENT
SUITE 1603
METRO•DADE FLM LER BUILDING
140 WEST FLAMER STREET
MIAMI. FLORIDA 33130 -1563
(305) 375.2901
FAX (305) 3754908
.E., D irector
Building Code Compliance Department
Metropolitan Dade County
•r
PRODUCT CONTROL NOTICE OF ACCEPTANCE
ROOFING COMPONENT APPROVAL
Applicant:
Polyfoarn Products, Inc. Product Control No.: 95- 0314.10
2400 Spring - Stuebner Road
Spring, Texas 77383 -1 132 Approval Date: APR 2 7 1995
Expiration Date: APR 2 7 1998
Categocv: Roofing Component
Sub - Category; lygei Roof Tile Adhesive
Sub : Type: Two Component Polyurethane
System Description
Polyfoam Products. Inc., produces two- component expanding polyurethane adhesive for the attachment
of clay and concrete roof tile. Polypro® AH160 is specially designed for application of concrete and
day roof tile over a variety of roof deck substrates and underlayment materials.
Polypro® adhesive is applied with proprietary Foampro® RTFI000 dispensing equipment. Approval of
this product is specific to the two component mix and Foampro® RTFI000 dispensing equipment.
Alternative methods of dispensing will require a revision to this approval.
Polypro® adhesive shall be applied only by 'Qualified Applicators', licensed by Poiyfoam Products, Inc.
Certificates and identification cards are issued to applicators upon successful completion of a application
training program. Approval of this adhesive system is contingent upon application by a 'Qualified
Applicator.
Contact:
Pat Murray
P.O. Box 1 132
Spring, Texas 77383 -1 132
(713)350 -8888 Fax: (713)288 -6450
1
Raul 'odri+g z
TRADE NAMES OF PRODUCTS MANUFACTURED OR
LABELED BY APPLICANT
Raul
\odriguez
Product Control No.: 95- 0314.0
Test Product
pro I Dimeusiona Specifications Description
Polypro® AH 160 N/A PA 101 Two component
polyurethane
Foampro® RTF1000 N/A See Detail Attached Dispensing Equipment
Product Control No.: 95- 0314.10
Product
Underiayment
Roof Tile
TRADE NAMES OF PRODUCTS 1VMANUFACTURED BY OTHERS
Test Criteria
Product Description
PA 120 All Dade County Component Approved
products as detailed in Dade County
Application Standard PA 120
PA 101 All Approved roof tile systems having
tested in compliance with Dade County
Protocol PA 101, as detailed in the systems
section of this Component Approval
3
Manufacturer
All Dade
County
Approved
Products
All Dade
County
Approved
Products
' oul Rodriguez
Test Agency
Center for Applied
Engineering
Miles Laboratories
Polymers Division
Test Identifier
#94 -060
NB- 589 -631
TEST REPORTS
Test Name/Report
Metro Dade Protocol
PA 101
ASTM D 1623
TYPICAL PHYSICAL PROPERTIES
Property Test
Density ASTM D 1622 1.6 Ibsift.'
Results
Compressive ASTM D 1621 18 PSI Parallel to rise
Strength 12 PSI Perpendicular to rise
Tensile Strength ASTM D 1623 28 PSI Parallel to rise
Water Absorption ASTM D 2127 0.08 Lbs./Ft
Moisture Vapor ASTM E 96 3.1 Perm / Inch
Transmission
Dimensional
Stability
Closed Cell
Content
ASTM D 2126
ASTM D 2856 861/4
4
Ra411 3driguez
Product Control No.: 95- 0314.10
Da
04/08/94
02/01/94
+0.07% Volume Change a -40° F.. 2
weeks
+6.0% Volume Change @158°F., 100%
Humidity, 2 weeks
Note: The physical properties listed above are presented as typical average values as determined
by accepted ASTM test methods and are subject to normal manufacturing variation.
i
SYSTEMS
Deck Type: Wood, Non - insulated, New Construction/141
Deck Description: New construction " /,_" or greater plywood or wood plank.
Re -roof "/„" or greater plywood
SYSTEM A:
Slope Range:
Underlayment:
Rooting Tile:
Adhesive Set Application
2":1/" to 7 ":12"
Product Control No • 95 -03J 4,10
Install choice of Approved underlayment system, noted on Page 1 of Dade
County Protocol PA 120, in compliance with Section 3.02 of PA 120.
Install Approved tile system in compliance with PA 120. Adhesive shall be
applied in compliance with the Component Application section and the
corresponding Placement Details of this Roofing Component Product Control
Approval. The adhesive attachment shall provide sufficient attachment
resistance expressed as a moment to meet or exceed the required moment of
resistance determined in compliance with PA 115 or PA 127. The adhesive
attachment data is noted in the tile Roof System Assembly Product Control
Approval.
Comments: 1. For re -roof applications, minimum ' /,_" plywood is an acceptable substrate.
2. All 'System Limitations' noted in the tile Roof System Assembly Product
Control Approval shall apply.
5
Table 1: Adhesive Placement For Each Generic Tile Profile
Tile
Profile
Placement
Detail
Two -Piece Barrel
#1
'S'5�h p
#2
Double Roll
#3
Large Flat
#4
Small Flat
#5
1. Polypro® A14160 tile adhesive shall only be applied over an underlayment installed in compliance
with application instructions detailed in its Component Approval.. Underlayment shall be any
underlayments or underlayment systems listed as Approved in Dade County Protocol PA 120.
2. Adhesive application shall be in accordance with the instructions provided in this Component
- Approval, the manufacturer may provide additional instructions subsequent to this approval date
which shall prevail. Installation must be by a Factory Trained 'Qualified Applicator' approved and
licensed by Polyfoam Products, Inc.
3. Calibration of the Foampro® dispensing equipment is required before application of any adhesive.
The mix ratio between the "A" component and the "B" component shall be maintained between
1.0 -1.15 (A) ; 1.0 (B). The dispense timer shall be set to deliver 0.08 to 0.15 pounds per tile as
determined at calibration. No other settings shall be approved without revision of this Component
Approval.
4. Adhesive shall be dispensed in a 17 in to 23 in' pad at time of application. The cured pad shall be
approximately 5" x 12 ". Foam placement shall be in accordance with the 'Placement Details'
provided in this Component Approval. Each generic tile profile requires a specific placement, as
noted in Table 1, below. A tile manufacturer may test a tile system in compliance with PA 101 and
add an additional detail without incurring an additional revision cost.
5. Adhere tile directly in freshly applied adhesive. Tile must be set within 2 to 3 minutes after foam
has been dispensed.
6. Adhesive shall be placed to create contact with minimum 2 tiles, as outlined in the 'Placement
Detail' for each tile profile.
COMPONENT APPLICATION
7
Raul Rodriguez
Product Control No.: 95- 0314.10
SYSTEM LIMITATIONS
Product Control No.! 955);14,10
1. Tile must be applied within 2 to 3 minutes of the application of Polypro® AH 160 adhesive.
2. Polypro® AH160 adhesive shall be installed only by 'Qualified Applicators' approved and licensed
by Polyfoam Products, Inc.
3. - For adhesive set tile applications, a field static uplift test by a Dade County accredited testing
agency, in compliance with Dade County Protocol PA 106, shall be required not less than 72 hours
after application to confirm tile adhesion. The results of this testing shall be reported to the
Building Official and the installer stating that the application has passed or failed PA 106 testing. If
the application fails PA 106 testing, the report shall state which portion of the test was failed;
Category 1 (examination for loose tile) or Category 2 (uplift testing of tile). Subsequent to testing,
the installer may repair not more than 5% of field area tiles and 10% of perimeter area (i.e.
ride /rake) the with approved tile adhesive. The installer shall place an identifiable marking on
each repaired tile for future reference. Any PA 106 re -test shall not include any marked tile.
Refer to application drawings published by the National Tile Manufacturers Association for
penetrations and terminations, as well as the Placement Details' included with this Component
Approval.
5. Refer to tile Roof System Assembly Product Control Approval for system Approvals with this
Component.
6. Refer to the Prepared Roof System Assembly for fire rating,
7, Polyproe AH 160 shall not be exposed permanently to sunlight.
8. Polyproe AH I60 shall be applied with Foampro RTF 1000 dispensing equipment only.
9. Any amendments to these provisions shall be in compliance with Sections 203 and 204 of the South
Florida Building Code.
8
Rau i' odriguez
PLACEMENT DETAILS
(CONTINUED)
FASCIA
BOARD
(EPOS . PREFABRICATED
ccosURE NAILED THROUGH
rt.AsIte ROOF CEu OR
INTO AP RO P AO
KEPHCLE
MAIL HOE l'ARCUG)
FLAS11C ROCF CEMENT
(WEN LO0I11CHM. HAIL.
IS RECUIR.O BY cccE)
ME!CIAP
a;.RCE BOARD
Sealant
or
P o l e AR 70
SURFACE
Placement Detail #2: 'S' Shaped Tile Profile
Product Control No.: 95- 0314.10
10
Raul ''. driguez
METRO•DADE
NMI
■ •
This approval supersedes all previous approvals.
METROPOLITAN DADE COUNTY. FLORIDA
METRO -DADE FLAGLER BUILDING
DU%LDING CODE COMPLIANCE DEPARTMENT
SUITE 1003
METRO-DADE FLAMER DUILUINQ
140 WEST FLAGLER STREET
MIAMI, FLORIDA 33130.1503
(305) 375-2901
FAX (305) 375 -2908
1. Extensions of Acceptance may be considered after a new application has been filed and the supporting
data, test reports no older than ten (10) years, have been re- evaluated.
All reports of re- testing shall bear the seal, signature and date of an engineer registered in the State of
Florida.
2. Any revision or change in the materials, use, or manufacture of the product or process shall automatically
be cause for termination, unless prior approval is granted for revisions or change.
3. Any unsatisfactory performance of this product or process or a change in Code provisions shall be grounds
for re-evaluation.
4. This acceptance shall not be used as an endorsement of any product for sales or advertising purposes.
5. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is
displayed, then it shall be done in its entirety.
6. Product approval drawings, where required for permit applications, shall be provided to the applicant by
the manufacturer or his distributors unless otherwise noted in the Notice of Acceptance. The prints need
not be re- sealed by an engineer.
7. Faiiure4o comply with the Standard Conditions shall be cause for termination of the Approval.
Rau!' odrigucz
Pr • • uct Control Division
Supervisor