ROOFar° E Associates, Inc. Roofing Laboratory Testing and Research Moisture and Up -Lift Testing Date: 4/19/96 Property address: 308 N.E. 99th. Street, Miami Shores, Fl Owner: Camesoma Contractor: Ace Roofing Permit #: 39156 City: Miami Shores Type of Tile: Altusa Product Control #: 94- 0914.01 Roof Slope: 3 -1/2 -12 Sq.ft. area: 3,500 sq.ft. approx. Testing Equipment: Chatillon - DFIS 100 - Calibrated 9/7/93 2524 W. 3rd. Avenue, Hialeah, Florida 33010 C954)433-1484 * (954 }437 -2332 * Fax (954)437-2296 tletra -Dude County Certification Na. 94- 0125.0E April 22, 1996 RE.: TEST TO DETERMINE ROOF TILES ARE SECURED TO DECK AFTER 72 HOURS INSTALLATION - ADHESIVE SET - SOUTH FLORIDA BLDG. CODE 3404.3 The purpose of this quality control test is to confirm that there exists sufficient bonding by the adhesive to the tile and underlayment in the tile system applied; it will be determined whether 75% of the tile bonds to be tested in three different roof areas, provides sufficient resistance to an arbitrary static uplift Toad applied on the tile. This procedure will satisfy the Building Code Compliance requirements set forth in Protocol PA 106 -95. Tiles have been tested on three different roof areas: field, perimeter and comer areas. Prior to testing, dimensions of these areas were determined and recorded according to Chapter 23 of South Florida Building Code. Tiles selected at random from the three different areas, were lifted by hand, in order to test for loose components. LOAD APPLICATION: An arbitrary Toad of 35 Ibf. has been applied to each tile, holding the load for 5 seconds. Test results are tabulated as follows: AREA # PULLS LOOSE TILES BROKEN/ CRACKED TILES ADHESIVE DELAMINATED FROM UNDERLAYMENT TILES DELAMINATED FROM ADHESIVE Field 37 none none none none Perimeter 36 none none none none Corners 32 none none none none Enclosed find a sketch of the test site roof, indicating field, perimeter and corner areas with dimensions, and also, location where pulls have been conducted. XX XX Truly yours, ETER L. ZA Lab. Director Encl. Sketch More than 75% of the tile bonds tested in each of the three areas, provided sufficient resistance to the arbitrary Toad applied. More than 25% of the tile bonds tested in each of the three areas, did not provide sufficient resistance to the arbitrary Toad applied. More than 10% of the components have been determined to be "loose" components. The static uplift quality control test for the property in question, complies with the Code requirements 3404.3 and Protocol PA 106 -95. ZARA AND ASSOCIATES, INC. RICARDO . CARLES, P.E. PROPERTY LOCATED AT 308 N.E. 99TH. ST., MIAMI SHORES, FL 55 ft 1 0 Fielt • Perimeter 0 Corners 22 ft • • 0 e ■ ■ . , • • • • • • • • • • • • • , 1 , . 1 1 , 1 N. 43 ft 22 ft co e • 28 ft e r - j <` is FRONT -4 ft- ® L 2 ft- , r 1 1 14 ft 2ft- 32 ft 0 • • • • • • 25 ft l e • • • • • • 7 • • • • • • . • • • • • 33 ft PERMIT APPLICATION FOR MIAMI SHORES VILLAGE J( Date ' S� /hob Address 3 0c /VC 77 St2, Tax Folio Legal Description Historically Designated: Yes No Owner/Lessee / Tenant A U1. Call /_ S/9/1/4 Master Permit # 3 ' i — Owner's Address /qS A /3 O v/, Contracting Co. / /o O F / /(VG CO / /V C. Address regS / S. W g 2 /_ celC , ,f A o o , Qualifier G O R 0 0A/ /}' R SS# , 'of- 6 s2 O State #RC 00 33 k(3T Municipal # 7'.3 S S3 -? Competency # /,2D2 Ins. Co.,&, L ht/ G TMM/ /4,s, C0 Architect/Engineer Address Bonding Company Address Mortgagor Address Permit Type (circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFING PAVING FENCE SIGN WORK DESCRIPTION Square Ft. Rea WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.) Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK. OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will . - ofie in complian cy with all applicable laws regulating construction and zoning. Furthermore, I authorize the above -named contractor to do . e ork stated. Signa e of owner and/or on o • resi . ent Date ` a 1C\ 1, 6 Notary as to Ome and/or Condo President My Commission Expires: 0,:'-. i i , ;r rtL N o ` �:'t ATE or: .i ..I:. -. ':..;i.;.): N '.:::: i FEES: PERMIT r (lf RADON APPROVED: Zoning Mechanical ,q 4o HP o v /f (4 y Estimated Cost (value) /8 0 0 0 f Building — t 9 (o Date g6 C.C.F. Phone N. as.tpceofi ctweEOCKilenwT1iliidSEAt. My C fission irk ^'''A P1 ��o�aTe .� Electrical Date NOTARY TOTAL DUE ZA1 Plumbing Engineering 2. Description of improvement* Notary Public 40 A93.. Print Notary's Name My Commission Expires: 123.01.112 1194 PAGE KAREN LYNN MOCILIA NOTARY PUBLIC STATE OF FLORIDA COMMISSION NO. CC418456 MY COMMISSION EXP. NOV. 2,1998 --Pc-aae—e1141-44-a-tea■,.-- Signature of Owner Print Owner's Name i � ,q r IL ('i p , N, s Sworn to and subscribed before me this ) day of ' 19 Qco STATE: OF Fica7 ;T , 1 HE'Ct:Y CSif�r% a D., J. cf he Ori3iuelfiI irr / r. ; r day of --- <` - 4 . 4 19 9l W.TNESS my h HA7IV£`t UV `s By F - eoP PERMIT NO. TAX FOLIO NO. STATE OF FLORIDA COUNTY OF DADE 3. Owner(s) name and address: / NOTICE OF COMMENCEMENT A RECORDED COPY MUST BE POSTED ON THE .SOB SITE AT TIME OF FIRST INSPECTION 968046 1 18 1996 FEB 01 12:55 THE UNDERSIGNED hereby gives notice that improvements wil be made to certain real property, and in accordance with Chapter 713, Florida Statutes, the following information is p ovided in this Notice of Commencement. 1. Legal description of property and street address* 3o QG� /v/z7 f p / 0 57t Interest in property: R Name and address of fee simple titleholder: A1/1 Mr5ANRS 4. Contractor's name and address* gcbr Roo, 74/ // '/C , 3B8c .s, ‘,33/z_ 5. Surety: (Payment bond required by owner from contractor, if i iny) Name and address* Amount of bond: $ 6. Lender's name and address 7. Persons within the State of Florida designated by Owner upoi i whom notices or other documents may be served as provided by Section 713.13(1)(a)7., Florida Statutes. Name and address* 8. In addition to himself, Owner designates the following person) s) to receive a copy of the Lienor's Notice as pro- vided in Section 713.13(1)(b), Florida Statutes. fk!^rne a address• 9. Expiration date of this Notice of Commencement (the expiratic n date is 1 year from the date of recording unless a different date in specified) Prepared by P• O `:-'N 1 4 ( ✓G ACC Roof/M6 /tvC Address: f `' 3Z r lkl? ZAcip Job Address: 3 Alb: cf 1 Sr/. Contractor: Underlayment (continued): Check all of the following which apply to the proposed underlayment for use wit the proposed tile system assembly: ASTM #30 asphalt saturated felt with: ❑ 19" overlap ❑ ' overlap • 4" overlap Manufacturer: F It( ❑ ASTM #15 asphalt saturated felt with: Man acturer: ❑ Other: Type: Manufacturer: ❑ Other: Type: Length: Manufacturer: Mineral Surfaced Roll Roofing with: Manufacturer: 4 Underlayment Fasteners (if applicable): " ❑ 19" overlap ❑ 6" overlap l3/" overlap ❑ 19" overlap ❑ 6" overlap overlap Check one of the following which apply to the proposed underlayment attachment: ❑ Minimum 12 ga. electro - galvanized roofing nail with minimum 32 ga. x 1' /," tin cap: Length: Manufacturer: n Po° Mortar or Adhesive Set Tile Systems Page - 3 Spacing (per tilt system assembly Product Control Approval): Field: /2 " o.c. Laps: �i " o.c. 5. Related Accessories: Edge Metal (refer to Section 3408.2 of the South Florida Building Code): Type: Dimensions: Gauge or Thickness: Finish: ❑ Cold Adhesive: 4 / 1 / c- (OProcess No. Type: Manufacturer: tAV6S /p 2x 2c Note: All edge metal shall be nailed on the flange and nailed or clipped at the face in compliance with the provisions set forth in Dade County Protocol PA 111, marked Appendix 'U' in the South Florida Building Code. Adhesives (check one of the following): Flashing Cement: Type: .8 /7 Manufacturer: /ft 2N 4 Job Address: � og 1kt r 9'9 Si Rid Height: � feet Contractor: ' 1 Too C c �• ° '!e∎oht: Roof Height 1A, / t BUILDING INFORMATION #1 Job Site Identification: Mortar or Adhesive Set Tile Systems Page - 6 Insert Building Ridge Height, Eave Height and Roof Mean Height. Also insert applicable information pertaining to the building below. ( See ASCE 7 -88 Fact Sheet Attached ) Exposurc Category: Classification Catcgory: AI l lurricancc Occanlinc?: Y N Basic Wind Speed at Building Location. 110 mph Building Condition based on % of openings: (See Table 9 oJASCE 7 -88) Ground Level Process No. Job Address: 30 g Af' Cm sin , Adhesives (continued): Note: Application of adhesives shall be in compliance with the Roofing Component Product Control Approval and the minimum requirements set forth in Subsection 3403.5(e)(4)(cc) of the South Florida Building Code. Ventilation System (check one or more of the following): The following information is required to confirm compliance with Subsection 3401.4(e) of the South Florida Building Code. ❑ Ridge: Type Soffit: Type Note: If underlayment is comprised of a self - adhered membrane, both soffit and ridge ventilation systems are required, unless a base sheet is applied as an anchor sheet below the self - adhered underlayment. Note: The Tile System Assembly shall be installed in strict compliance with the application instructions enumerated in the Product Control Approval. A permit shall be issued for application of the specified Tile System Assembly only. Any change to the specified Tile System Assembly shall require submission of a revised SECTION II with a copy of SECTION I, noting the permit number issued. Job Address: ',30? /V6 gel JtI. Ridge Venting: r vaPPfitoble ) Dcck: 1 type: r, Thickness: _ Underlayment: 4 30 f/= L Mortar or Adhesive Set Tile Systems Page - 4 Underlaym ent � �' /' Fastener: / / I H (h t X o o f . / 1 4. 5 3 � � / Roof Pitch 12" DETAIL #1 Job Site Identification: Contractor: 9c, /v o Mortar or Adhesive Set Tile Systems Page - 5 Additional Notes: C O. Process No. Contractor: / ?C/.' ( ?0 O k' a No. FILL IN APPLICABLE ROOFING COMPONENTS WIIICII MAKE UP TILE SYSTEM ASSEMBLY. INSERT ANY ADDITIONAL LEADERS INDICATING ADDITIONAL ROOFING COMPONENTS NOT SIIOWN ON THIS PAGE. ( Where Roofing Component not used in Tile System Assembly, fill in with "N /A ". ) Head Lap Dimension: (minimum 1' unless otherwise specified in the tile system assembly Product Control Approval) _/�IJ Mortar /Adhesive: �RF 't / / )( Tile: CAAy Tile Fastener: Edge Metal or Gutt r � Fastener: / • /L f Bird Stop: C 4 y (tf applicable ) Edge Metal 7 `e . 2 . or Gutter: )L if R Existing or Proposed , S /, Soffit Venting: ry (� d it/ 3G e+ -ro Lid`'CENTF Job Address: 9 Srel. Job Address: 2 °g IIV' cry . St - ft. Manufacturer: CT i 1 ❑ ASTM #15 asphalt saturated felt with: Manufacturer: l rim Mineral Surfaced Roll Roofing with: Manufacturer: ❑ Other: Type: Manufacturer: Underlayment Fasteners (if applicable): ❑ Other: Type: Length: Manufacturer: Rid f Height: �r /�L feet 11 O 19" overlap O 6" overlap 131" overlap O 19" overlap O 6" overlap 4" overlap Contractor: BUILDING INFORMATION #1 Job Site Identification: Underlayment (continued): Check all of the following which apply to the proposed underlayment for use with the proposed tile system assembly: Check one of the following which apply to the proposed underlayment attachment: ❑ Minimum 12 ga. electro- galvanized roofing nail with minimum 32 ga. x 1' / tin cap: Length: Manufacturer: T moo• -� '!e" ht: Roof M,qan Height et /0 Fri Mortar or Adhesive Set Tile Systcms Page - 6 Mortar or Adhesive Set Tile Systems Page - 3 Insert Building Ridge Height, Eave Height and Roof Mean Height. Also insert applicable information pertaining to the building below. ( See ASCE 7 -88 Fact Sheet Attached ) Exposure Category: Classification Category: At Ilurricancc Occanlinc ?: _ Y _ N Basic Wind Speed at Building Location• 110 moh Building Condition based on % of openings: (See Table 9 of ASCE 7 -88) Ground Level Process No. Contractor: /�'C -/� / ( J4 ,� Coprocess No. ASTM #30 asphalt saturated felt with: ❑ 19" overlap 0 'overlap 5. Related Accessories: • 4" overlap Spacing (per tile system assembly Product Control Approval): Field: 2 " o.c. Laps: " o.c. Edge Metal (refer to Section 3408.2 of the South Florida Building Code): Type: EA1//l: ,S 22'p Dimensions: 2 x Z Gauge or Thickness: 2 Finish: (141. 1/1 Note: All edge metal shall be nailed on the flange and nailed or clipped at the face in compliance with the provisions set forth in Dade County Protocol PA 111, marked Appendix 'U' in the South Florida Building Code. Adhesives (check one of the following): ❑ Cold Adhesive: Type: Manufacturer: Lit' Flashing Cement: Type: # /7 Manufacturer: / /11 /4.1 r4 (� Job Address: 30Y NF_ c ( Stn • Contractor: APPENDIX 'E' METRO -DADE UNIFORM BUILDING PERMIT SECTION II MORTAR OR ADHESIVE SET TILE SYSTEMS 1. General The information provided in this Section is required to confirm Product Control Approval of the proposed tile system assembly; confirm compliance with the wind load requirements of Chapter 23 of the South Florida Building Code (SFBC); and confirm compliance with Sections 3403.5 and 3404 of the South Florida Building Code. 2. Documentation The following documents are required for submission with the Uniform Building Permit application: ► Two (2) copies of the proposed tile system assembly's and associated roofing component's Product Control Approval(s). ► One (1) copy of the tile system assembly and/or roofing component(s) manufacturer's published application instructions and literature. ► All documents attached herein, filled out and completed in full. 3. Project Information Check one of the following: ❑ yew Construction Re -Roof Noje: Mortar or adhesive set tile systems are not acceptable as recover applications. l2aoi -158 Mortar or Adhesive Set Tile Systems Page -1 Pee Iao o Coo , Process No. Is the deck solid sheathed? (circle 'yes' or 'no') yes no Deck Type (check one of the following): ❑ Nominal %2" Plywood (for re -roof only) ❑ Nominal' /," Plywood ❑ Wood Plank / �! ❑ Other (fill in) f x G / -� - G Roof Pitch (fill ink: 3 Z ": 12" Note: Mortar or adhesive set tile systems shall not be installed at a pitch greater than 7V2 ":12 ". Mortar or adhesive set tile applied at a pitch greater than 5 ":12" and less than or equal to 7 ":12" shall have the first three courses of tile nailed with not less than one nail per tile. As an alternate, the first three courses of tile may be applied in mortar over a single layer of minimum 12 ga. wire mesh with square openings of not less than 3 /," which is mechanically attached to the sheathing with not less than one nail per 2 R Circle 'ves' or 'no' for each of the following: Have you attached two copies of the tile system manufacturer's Product Control Approval for the proposed tile system? no Have you attached a copy of the tile system assembly and/or roofing component(s) manufacturer's published, application instructions and o}}h�er literature l vet, no Is the proposed underlayment approved for use with this tile system assembly ? - no Job Address: 3Cg K6 ¶ 1 StA Contractor: The undersigned certifies that the Mortar or Adhesive Set Tile System Assembly is in compliance with the plans, specifications, and details submitted by the architect. STATE OF FLORIDA - COUNTY OF DADE Before me this day personally appeared who, being first duly sworn, deposes and says that all information submitted herein is true and correct. Licensed Contractor / Owner Signature Sworn to and subscribed before me this th day of 19 My commission expires: Notary Public State of Florida Mortar or Adhesive Set Tile Systems Page - 8 Process No. Job Address: 3 IY A: ( SfA. Contractor: The undersigned certifies that the Mortar or Adhesive Set Tile System Assembly is in compliance with the plans, specifications, and details submitted by the architect. STATE OF FLORIDA - COUNTY OF DADE Before me this day personally appeared who, being first duly sworn, deposes and says that all information submitted herein is true and correct. Licensed Contractor / Owner Signature Sworn to and subscribed before me this th day of 19 Job Address: 3e3f NF t sr 123.01 -158 My commission expires: Notary Public State of Florida APPENDIX 'E' METRO -DADE UNIFORM BUILDING PERMIT SECTION II MORTAR OR ADHESIVE SET TILE SYSTEMS 1. General 2. Documentation Contractor: The information provided in this Section is required to confirm Product Control Approval of the proposed tile system assembly; confirm compliance with the wind load requirements of Chapter 23 of the South Florida Building Code (SFBC); and confirm compliance with Sections 3403.5 and 3404 of the South Florida Building Code. The following documents are required for submission with the Uniform Building Permit application: ► Two (2) copies of the proposed tile system assembly's and associated roofing component's Product Control Approval(s). ► One (1) copy of the tile system assembly and/or roofing component(s) manufacturer's published application instructions and literature. ► All documents attached herein, filled out and completed in full. 3. Project Information Check one of the following: ❑ yew Construction M' Re -Roof Nole: Mortar or adhesive set tile systems are not acceptable as recover applications. Mortar or Adhesive Sct Tile Systems Page - 8 Mortar or Adhesive Sct Tile Systems Page -1 PeE %Z.o or I CO, Process No. Is the deck solid sheathed? (circle 'yes' or 'no') yes no Deck Type (check one of the following: ❑ Nominal '/2" Plywood (for re -roof only) ❑ Nominal' /," Plywood O Wood Plank " ❑ Other (fill in) /x G Roof Pitch (fill in): 3 Z ": 12" Note: Mortar or adhesive set tile systems shall not be installed at a pitch greater than 7Y2 ":12 ". Mortar or adhesive set tile applied at a pitch greater than 5 ":12" and less than or equal to 7 ":12" shall have the first three courses of tile nailed with not less than one nail per tile. As an alternate, the first three courses of tile may be applied in mortar over a single layer of minimum 12 ga. wire mesh with square openings of not less than ' 4" which is mechanically attached to the sheathing with not less than one nail per 2 ft'. Circle' yes' or 'no' for each of the following: Have you attached two copies of the tile system manufacturer's Product Control Approval for the proposed tile system? rves� no Have you attached a copy of the tile system assembly and/or roofing component(s) manufacturer's published, application instructions and o}her literature 1 vet, no Is the proposed underlayment approved for use with this tile system assembly? no Process No. Job Address: ,3 /V ! ? Stn. Contractor: Job Address: Project Information (continued): If the proposcd undcrlayment is self - adhered, have you complied with the venting requirements of Section 2913.3 (b), (c) and (d) of the South Florida Building Code? yes no Are all related accessories approved for use with this tile system assembly/ Are the proposed edge metal attachment fasteners in compliance with the requirements of the South Florida Building Code (minimum ye 12 ga. annular rinshank, corrossion reisistant nails)/ no 4. The Tile System Assembly: The following information is required to confirm compliance with Subsections 3403.5(a) and (c) and Section 3404 of the South Florida Building Code. Tile: Tile Name: Manufacturer: Tile Ma 'al: Clay ❑ Concrete ❑ Other: Product Control Approval Number: 9 / -0i V Mortar or Adhesive: no • SPRNf5k 5 (Ay mil- / G 7"(1S A �,� bg ,v, 97 st2 , /3 I' .y ' 33 S2 Contractor: t i �r /'oo Check one of the following which apply to the proposed tile securement for use with the proposed tile system assembly: Mortar or Adhesive Set Tile Systems Pagc - 2 Mortar or Adhesive Set Tile Systems Page - 7 Ly' Mortar: Manufacturer: e 1/TE ❑ Adhesive: Type: Manufacturer: Tile Fasteners (for first three courses if roof pitch exceeds 5 ":12" and is less than or equal to 7 ":12 "): Check one of the following which apply to the proposed tile fasteners (for the first three courses) for use with the proposed tile system assembly: ❑ Other: Type: Length: ❑ N/A Underlayment: 1141inimum 12 ga. galvanized roofing nail: Length: • BUILDING INFORMATION #2: Roof Plan with Perimeter and Corner Dimensions Job Site Identification: C . , Process No. Mixing Ratio: 4. 11 Note: All tiles shall be installed in compliance with the provisions set forth in the tile system assembly manufacturer's Product Control Approval and the minimum requirements set forth in Subsections 3403.5(c) and 3404.2 of the South Florida Building Code. Tile fasteners in the first three courses (if applicible) shall be of sufficient length to penetrate the sheathing a minimum of 1" or through the sheathing thickness a minimum of / ", whichever is less. The following information is required to confirm compliance with Section 3403.5(b) of the South Florida Building Code. J ' r e5'1;)rocess No. Sketch Roof Plan, indicating all dimensions, slopes and any roof top equipment. Also insert variable labeled "a" which represents perimeter and comer dimensions per Chapter 23 of the South Florida Building Code. (See ASCE 7 -88 Fact Sheet Attached ) Al;11S :1 Tile lC Alfareria del I urbio, S.A. • 13arquisimeto, Venezuela PRODUCT NO_ : ACCEPTANCE ,NO_: EXPIRES: Your application for Product Approval ofAltusa Tile Nail -0n, Mortar or Adhesive ,Set Clay "Altura S" Roofing Ti 5 under Chapter 8 of the Metropolitan Dade e -County Code governing the use of Alternate Materials.and Types of Construction, and completely described in the plans, specifications and calculations as submitted by Redland Technologies, The Center for Applied Engineering, and Testwell Craig Laboratories & Consultants, Inc has been recommended for acceptance by the Building Code Compliance Department to be used in Dade County, Florida under the specific and standard conditions set forth herein_ The approval shall be valid for a period of three years- The Building Code Compliance Department reserves the ri& t to secure a product or material at any time for a jobsite or manufacturer plant for quality control testing If product or material fail to perform in the approved manner, the Code Compliance Department may revoke, modify or suspend the use of such product or material immediately. The Building Code. Compliance Department reserves the right to require testing of this product or material should any amendments to the South Florida Building Code be enacted affecting this product or material_ The expense of such testing will be incurred by the Manufacturer. 4- 14.01 9 R9 FEB I q 1997 • 1 :: ) ; is i ! ; i I) . i) i , .. ; i i i '� , i ii( I1A; ;i ! I Ai ;I I it Ill 111 I AN( ; ( ( "t I,:.: +;I I1; l'Ait17.1! t., : .1;:,; ..., il;t)i':,I i! iin+;ii 1111111; M.111! ,11 I I OI111)A :1-113:1-1!;1,3 (:SIP,) :3/$ -?9O1 :A •: ( :30 :0 37_` 2 J013 Raul Rodriguez Product Control Division Supervisor - PLEASE NOTE - TIIIS IS THE COVERSIIEET. SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL CONDITIONS. BUILDING CODE COi\ti1ITTEE This applic :!ion for I'roducl Approval ha> bccn rcvic"'al by the r Ae i r(ltn)tit:in D :'dc County Building Code Coiiipli:ince :n n +cio ::nd :i.ppiovcii by the Building Lo('..: C.Ur11i11Ii;tC : I urcd +n D:1(1C Co n_y . Florid:: t1: d & r i ;11, ('ut :(li; ir •::'i fUr;;+ : :!';, -•i- /; ,// I/ i ., : i / , -: i ,l A \Itusa I de Alfareria del I uri)io. S.A. 13arquisinlcto• Venezuela 'Itt) ;,ut (:();\ 1.1“)1.!'\'()I I.l)t :1t c r.I•I \\t ;. l:()()r I:\r: S1..1! \I. Cateory: Prepared Roofing Sub ateaor� : Tile Nail -on /Mortar Set/Adhesive Set Sub -Tvoe: Clay °$vstem Description Contact: Carlos J. Fernandez General 1-lanaeer Altusa Tile, Almar (1JS. \). Ine. 66 - -15 Northwest 77th Avenue Miami_ i >> I66 ( I'toa7nCI (o:i ::01 No 9•: 091:1 01 -- Approval Date: Expiration Date: Alfareria del Turbio, S.A. ( Altusa), located in Barquisimeto, Venezuela, manufacturers clay roof tile for nail -dn, mortar set or adhesive set applications_ All tile is manufactured from natural Venezuelan clays. This Product Control Approval relates to Altusas "Altusa S" tile profile_ Refer to appropriate Product ontrol A • royals for other tile ore file The "Altusa S" tile profile is available in a variety of natural clay colors and has matching trim pieces used for rake hip, ridge hip, and valley terminations_ These accessories are manufactured for all profiles and form a part of this Product Control Approval_ Optional rubber or clay eave closures are also available. Altusa roof tiles have been tested in compliance with the South Florida Building Code requirements for clay, nail -on, mortar set or adhesive set tile applications_ The minimum roof slope for " Altusa S" nail -on tiles shall be 2 ":12 ". See thr "Profile Drawing" section in this approviti for the " Altusa S" profile drawing_ The "Altusa S" profile has been tested for both wind characteristics and static uplift performance, therefore, any consideration for installation shall be done as a 'Moment Based System'. Data for attachment calculations is noted in Tables 1 through 4 of this Approval_ Almar (USA). Inc., located in Miami, Florida, is the sole approved importer under contract for selling. and distributing_ Altusa products in the South Florida jurisdiction_ FEB 1 1 1991 1'1 od ;act A In r,a *S• v Roof Ti Trull Pieces (1j PIZ( )01:f (,)1;. 1. I) i:)' ;T. It \ I = varies w = varies varying thickness c•.t AS I C 1 if ASTM C 1167 ACCeSSOsy II clay root - pieces for use at hips, rakes, richzes and valley terminations. Manufactured for each the profile_ ip,11 i111;111)111: l jc k i:i , 011C- S NII:ipCd. clay roof file equipped with two nail holes and nIllC roll. l'or direct deck nail-on applications only. I'r udul'l =30 Mineral Surface Cap Sheet Lenzingtex -ZB 140 Underlavment Rainproof I1 Ice and Water Shield Moppintt Asphalt NIA .• Ceinciti k( 1;,;111) O 1111:1: !:: \ 59" x 164' roll 22 lbs/roll 30 "x75'roll 36" x 75' roll or 60" x 75' roll 36" x 75' roll • •∎'11(..(11(• : \ \ 1 1 :_ h 1) II t;43 Coated Base N/A ASIM 1) 2626 Saturated and coated Sheet organic base sheet for sinttic or double ply underlayment_ N/A AST,MI D 249 Mineral surfaced generic asphalt roll roofing for use as a top ply in a double ply underlayment system. PA 104 Single ply, nail -on Len zing underlayment_ Performance, Inc_ PCA '194- 0527.05 PA 104 PA 103 Self - adhering W.R. Grace Co_ underlayment for use PCA 492-1 1 16.01 as a top ply in a two ply underlayment system with approved #30 or 43 as the base laver. .?Sf.1 0312 type 11! or IV 1 ': o,4:.r( 1). . I•ri;nn :.: :maicd ur ^:+1):c: r. :1( io bi. uf:cd n•; a n:ulcd :nichor sheet. Single ply, nail -on underlayment with 2" self - adhering top edge_ Asphalt for bonding a mineral surface cap to a mech. attached base sheet in a double ply u nderl : S.Stem. genCnc I) - 5 ;ri (-ui f?' ; ;r':alt • :.1111 i .1.. ,., . gCllef;C Protect -O -Wrap, Inc. PCA 494- 0714.01 Roorrif, Naih: Tin Caps Wood Bat Tile Nails Tile Screws Roof Tile MOM'S t"TileTiterm") Roo: ;l k: :\!!!(:)..) 1•11 t 111111. 12 r:S. W1111 111...2.(1 min_ 32 ga. min_ 1 o_d_ max_ 2 o_d_ horizontal min_ I" x 4" for use with vertical bartens or min_ I" x 2" for use alone min_ 8d x T/2" or min_ iOt1Xi - min_ x TA or min. g10 x 2 PA 1 ri Append's 1] PA 114 Appendix E PA 114 Appendix E PA 114 Appendix E NIA PA 123 NSA 1),•..cr tio;t••■■ Co; ii it/ Annohr tint; siitlok. hot (Sipped, clecno or mechanically g:lv. rootil; nails (or use in under hiyncot attachment. Corrosion resistant circular disc for use in underlayment attachment vertical Wood Preservers Salt pressure treated generic thin_ 1" x 4" Instinite LP - 2 or decay resistant lumber battens Corrosion' resistant, screw, smooth or annular ring shank nails. Corrosion resistant, coated, coarse thread wood screxvs. Prepared mortar mix designed for mortar se: root applications. - 1 1) COtiti)ofIc:1; ** C. t',Clit:t generic generic generic Bermuda Roof Company, Inc. PCA ; -06 14.01 °ducts. I o e. ()!:() 01 Roorrig Nn Tin Caps Wood Battens Tile Nails Tile Screws Roof Tile Mortar C'TileTiter" !le A.dlicsive 1 wit ' he min_ 32 ga. min_ 1 o. d. max. r o_d_ vertical Wood Preservers Salt pressure treated generic min_ 1 institute LP - 2 or decay resistant lumber battens horizontal min 1" x 4" for use with vertical battens or min r x 2" for use alone min_ 8d x T/2" or inin_ iOd x min. #8 x 2%.. or min. :"--!10 x 2 PA 114 Appendix PA 114 Appendix E PA 114 Appendix E PA 114 Appendrx E NiA PA 123 See ■■.!to, 1),•.cs rio; ■•,ts !!!...irmi.!! Awitihr shank. hot dipped, cicctro or mechanically gait!. roofing nails for use in underlayment attachment. Corrosion resistant circular disc for use in underlayrnent attachment Corrosion resistant, screw, smooth or annular ring shank nails. Corrosion resistant, coated, coarse thread Wood screws. Prepared mortar m ix desilmed for mortar se; roof tile apnliC2tions. Iwo ctImpor!co; !.!!!!cth:!!!!.! I!!! •..: :;!.• generic generic 1.1, I" I °Crier Bermuda Roof Company, Inc. PCA ;:'J-1- 06 °doers, Inc O.:0 01 ( Valley Flashing Drip Edge 11 311u •s:-.1 *,(r.. ofi!I :mit. () 06(i' l'...r.tencr, mill. Sri x :-;•C.V.N11/,:d NICCi 1C.:1112CilinCni clips for supplcmcnuil rile ;Ii(acttmcnt. Clips arc installed with corrosion resistant rooting nails compatible with the clip. A hurricane clip is required on all cave tiles. min. 26 ga_ ASTM A 525 Galvanized steel _generic min. 16" width valley flashing min. 26 oa_ • PA 111 Galvanized steel drip generic min. 2" face flange ed.cle min. 2" deck flange i'■•■■!■,, 1).,c111,1:•••! .1: 1;•,1.: 11.1,111LIC11:1,1 R land-Technologic The Center for Applied Engineering. Inc. Idris idn It,: -0 Appendix 111 7161 A ppend ix 111 25-720 The Center for Applied 94-084 Static Uplift Testing May 1994 Engineering, Inc. PA 101 (Mortar Set) The Center for Applied 94-083 Static Uplift Testing April 1994 Engineering Inc. PA 101 (Adhesive Set) Dec_ 1991 Redland Technologies Letter Dated Aug_ I, 1994 Wind Tunnel Testing Aug 1994 . PA 108 (Nail-On) Aug. 1994 Redland Technolooies PO402 13. Resistance Sept. 1993 Testing of screw es. shank nails Oct. 1994 Redland Technologies 7161-03 - Wind Tunnel Testing Appendix II PA 108 (Nail-On) - Redland Technoloaies P0647-01 Wind Tunnel Testins! PA . 103 (Mortar Scz) The Center for Project No. 307025 Wind Driven Rain 1 Inc. Tes NIDC-78 l'A 100 ■•", x■iti I C . Lab t: 1 1. P-2 ri:e11 . Porcello r r. 10? Static Uplift 1 l'A 102(A) Static Uplift Testis PA 102 (Quite-Drive Screws, Battens) ''c:1 Propel:v 1167 I '• I ';.) Pee. 1991 Feb. 1995 Oci. 199.; .' \., t . i ( I - ,';: 1I,;:c,n: ,, \ew, :unti(,t:ctun: /.� • „,c::,i,-7 f,lvvr. >,:,f,r S 1'S (1- \1 1): iMMooar or Adhesive Set Apl>I:cU:On Slone I :In';c: 2 ":12" to 7” :12" Note: System I) is onlv acceptable in this slope range_ Undcrlavmcn (: Roofing Tile: Install choice of approved underlayment system, noted on Page 1 of Dade County Protocol PA 120, in compliance with Section 102 of PA 120. See System Limitation #7_ Install tile in compliance with PA 120 using one of the approved mortars or adhesives noted in this approval_ Mortar or adhesive shall be applied in compliance with the mortar or adhesive manufacturers Roofing Component Product Control Approval_ The mortar or adhesive attachment shall provide sufficient attachment resistance expressed as a moment to meet or exceed the required moment of resistance determined in compliance with PA 1 15 or PA 127_ The mortar and adhesive attachment data is noted in Table 4, attached. Comments: 1_ For re -roof applications, "4," plywood is an acceptable substrate_ 2_ For mortar set applications, the first three courses of tile shall be nailed with not less than one nail per tile_ As an alternate, the first three courses of tile shall be applied in mortar over a single layer of minimum 12 ga_ wire mesh with square openings of not less than '/," .which is mechanically attached to the deck with not less than one rooting nail every I ft For roof pitches from 6 " :12" to 7 " :12 ", every third tile of every fifth course, beginning at the eighth course, shall be nailed with not less than one nail per tile_ Altusa 'S' Tile Tile Profile Altusa 'S' Tile 3 ":12" or Tess Battens Direct Deck 4.47 5.35 4 ":12" Battens Direct Deck nts due to Gravity - M (ft-Ibf) 102 Testing 5 ":12" 1 6":12" Battens' Direct I Deck Battens 4.40 5.27 I 4.31 ! 5.16 I 4.20 Direct Deck 5.03 7 ":12" or greater Battens 4.08 Direct Deck N/A • Tile Profile Altusa 'S' Tile Tile Profile Table 1: Aerodynamic Multiplier - X (ft') from PA 108 Testing Table 2: Restoring Mome from PA 1)A TA I' )It ATI IEN r Cm,r tn,A rIo s Table 3: Attachment Resistance Expressed as a Moment - M (ft-lbf) from PA 102 and PA 102(A) Testing TILE APPROVED APPLICATION NAILS 1 nail + 2 nails Battens I N/A N/A Direct Deck 1 6.20 1 8.40 X (ft Batten Application Direct Deck Application 0.29 APPROVED SCREWS 1 screw 12 screws Product t :un:t i Nu APPROVED FIELD CLIP WITH: X (ft') 0.31 1 nail 1 2 nails 1 nail 1 2 nails N/A 1 26.80' N/A 1 N/A N/A 28.70 + 31.80 21.20 1 25.30 26.90 APPROVED EAVES CLIP WITH: N/A 34.90 Screws for tile installation over battens shall be #8 x 2W long. corrosion resistant. Quik -Drive screws installed in two manufactured holes located 1 and 1 from the head of the tile. Table 4: Attachment Resistance Expressed as a Moment - M (ft from PA 101 Testing L 1 Tile f Tile I Attachment I Profile � Application I Resistance I .- il(l:; 'S• Tile I Mor1'3r Set 1 24.50 I Sr:: 66 f50 A LT( ISA Clay Root riles 11 / DOVE TAIL LOCKS '1:1,1 i:,l ALTUSA 'S' TILE •1 0:1 11, N(111 t, QI 1( _571∎Nt);l1:1) f_f>_�`! phis approval Supersodcs approvals_ Last ,\pprov:il f'nlnlii•r 9 4-0106. IS Raul Rodrinucz Product Control Oivis:on Supervisor • r i i i i i(.1:1 11;i•It 111. :., r.a.t: ;:Ut I I: iGn;1 . .:c 1 I ).; ?!; I ; !, :I ? It liifii.t)GIC ::)': ;1 1 1 ).1 :1:11 :l1) -1;(i i (:IO%) ai5- : 1 rn . ( :11y; :175 -2.90s) 1 Extensions o1 Acceplancc may be considered after a new application has 1,, tiled and the supporting data, test reports no older than tcn (10) years, have been re-evaluated. All reports of re- tcstimz shall bear the seal, signature and date of an cn_in:cr registered in the State of Florida_ Any revision or change in the materials, use,. or manufacture of the product or process shall automatically . be cause for termination, unless prior approval is granted for revisions or change. 3_ . Any unsiitisfactory performance of this product or process or a chance in Code. provisions shalt be grounds for re- evaluation. This acceptance sita !1 net be used as an endorsement of any product for sales or advertising purposes. 5. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the • expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is displayed, then it shall be done in its entirety. 6. Product approval drawings_ where required for permit applications, shalt be provided to the applicant by the manufacturer or his distributors unless otherwise noted in the Notice of Acceptance. The prints need not be re- sealed by an eni.inecr_ Failure-to comply Nvith the Standard Conditions shall be cause for tennination of the Approval. • METRODADE Poly foam Products, inc. 2400 Spring - Stuebner Road Spring, Texas 77383 Your application for Product Approval of Poiyfoam P eduess "Po y rn AA„H -160" Ranf Tits_, dhesive under Chapter 8 of the Metropolitan Dade County Code governing the use of Alternate Materials and Types of Construction, and completely described in the plans, specifications and calculations as submitted by The Center for Applied Engineering, Inc. and Miles Laboratories Polymers Division has been recommended for acceptance by the Building Code Compliance Department to be used in Dade County, Florida under the specific and standard conditions set forth herein. The approval shall be valid for a period of three years. The Building Code Compliance Department reserves the right to secure a product or material at any time for a jobsite or manufacturer plant for quality control testing. If product or material fail to perform in the approved manner, the Code Compliance Department may revoke, modify or suspend the use of such product or material immediately. The Building Code Compliance Department reserves the right to require testing of this product or material should any amendments to the South Florida Building Code be enacted affecting this product or material. The expense of such testing will be incurred by the Manufacturer. PRODUCT NO. : ACCEPTANC>r`NO.: 25- 0314.10 ul Rodrigu APB 2 7 19 9 8 roduct Control Division EXPIRES: Supervisor - PLEASE NOTE - TIIIS IS THE COVERSNEET. SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL CONDITIONS. BUILDING CODE COMMITTEE This application for Product Approval has been reviewed by the Metropolitan Dade County Building Code Compliance Department and approved by the Building Code Committee to be used in Dade County, Florida under the conditions set forth above. APPROVED: 3 / � q METROPOLITAN COUNTY, FLORIDA DADE FLAGLER BUILDING moaucTsmmultimajmesssaarict AAfi 2 7 1995 BUILDING CODE COMPLIANCE DEPARTMENT SUITE 1603 METRO•DADE FLM LER BUILDING 140 WEST FLAMER STREET MIAMI. FLORIDA 33130 -1563 (305) 375.2901 FAX (305) 3754908 .E., D irector Building Code Compliance Department Metropolitan Dade County •r PRODUCT CONTROL NOTICE OF ACCEPTANCE ROOFING COMPONENT APPROVAL Applicant: Polyfoarn Products, Inc. Product Control No.: 95- 0314.10 2400 Spring - Stuebner Road Spring, Texas 77383 -1 132 Approval Date: APR 2 7 1995 Expiration Date: APR 2 7 1998 Categocv: Roofing Component Sub - Category; lygei Roof Tile Adhesive Sub : Type: Two Component Polyurethane System Description Polyfoam Products. Inc., produces two- component expanding polyurethane adhesive for the attachment of clay and concrete roof tile. Polypro® AH160 is specially designed for application of concrete and day roof tile over a variety of roof deck substrates and underlayment materials. Polypro® adhesive is applied with proprietary Foampro® RTFI000 dispensing equipment. Approval of this product is specific to the two component mix and Foampro® RTFI000 dispensing equipment. Alternative methods of dispensing will require a revision to this approval. Polypro® adhesive shall be applied only by 'Qualified Applicators', licensed by Poiyfoam Products, Inc. Certificates and identification cards are issued to applicators upon successful completion of a application training program. Approval of this adhesive system is contingent upon application by a 'Qualified Applicator. Contact: Pat Murray P.O. Box 1 132 Spring, Texas 77383 -1 132 (713)350 -8888 Fax: (713)288 -6450 1 Raul 'odri+g z TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT Raul \odriguez Product Control No.: 95- 0314.0 Test Product pro I Dimeusiona Specifications Description Polypro® AH 160 N/A PA 101 Two component polyurethane Foampro® RTF1000 N/A See Detail Attached Dispensing Equipment Product Control No.: 95- 0314.10 Product Underiayment Roof Tile TRADE NAMES OF PRODUCTS 1VMANUFACTURED BY OTHERS Test Criteria Product Description PA 120 All Dade County Component Approved products as detailed in Dade County Application Standard PA 120 PA 101 All Approved roof tile systems having tested in compliance with Dade County Protocol PA 101, as detailed in the systems section of this Component Approval 3 Manufacturer All Dade County Approved Products All Dade County Approved Products ' oul Rodriguez Test Agency Center for Applied Engineering Miles Laboratories Polymers Division Test Identifier #94 -060 NB- 589 -631 TEST REPORTS Test Name/Report Metro Dade Protocol PA 101 ASTM D 1623 TYPICAL PHYSICAL PROPERTIES Property Test Density ASTM D 1622 1.6 Ibsift.' Results Compressive ASTM D 1621 18 PSI Parallel to rise Strength 12 PSI Perpendicular to rise Tensile Strength ASTM D 1623 28 PSI Parallel to rise Water Absorption ASTM D 2127 0.08 Lbs./Ft Moisture Vapor ASTM E 96 3.1 Perm / Inch Transmission Dimensional Stability Closed Cell Content ASTM D 2126 ASTM D 2856 861/4 4 Ra411 3driguez Product Control No.: 95- 0314.10 Da 04/08/94 02/01/94 +0.07% Volume Change a -40° F.. 2 weeks +6.0% Volume Change @158°F., 100% Humidity, 2 weeks Note: The physical properties listed above are presented as typical average values as determined by accepted ASTM test methods and are subject to normal manufacturing variation. i SYSTEMS Deck Type: Wood, Non - insulated, New Construction/141 Deck Description: New construction " /,_" or greater plywood or wood plank. Re -roof "/„" or greater plywood SYSTEM A: Slope Range: Underlayment: Rooting Tile: Adhesive Set Application 2":1/" to 7 ":12" Product Control No • 95 -03J 4,10 Install choice of Approved underlayment system, noted on Page 1 of Dade County Protocol PA 120, in compliance with Section 3.02 of PA 120. Install Approved tile system in compliance with PA 120. Adhesive shall be applied in compliance with the Component Application section and the corresponding Placement Details of this Roofing Component Product Control Approval. The adhesive attachment shall provide sufficient attachment resistance expressed as a moment to meet or exceed the required moment of resistance determined in compliance with PA 115 or PA 127. The adhesive attachment data is noted in the tile Roof System Assembly Product Control Approval. Comments: 1. For re -roof applications, minimum ' /,_" plywood is an acceptable substrate. 2. All 'System Limitations' noted in the tile Roof System Assembly Product Control Approval shall apply. 5 Table 1: Adhesive Placement For Each Generic Tile Profile Tile Profile Placement Detail Two -Piece Barrel #1 'S'5�h p #2 Double Roll #3 Large Flat #4 Small Flat #5 1. Polypro® A14160 tile adhesive shall only be applied over an underlayment installed in compliance with application instructions detailed in its Component Approval.. Underlayment shall be any underlayments or underlayment systems listed as Approved in Dade County Protocol PA 120. 2. Adhesive application shall be in accordance with the instructions provided in this Component - Approval, the manufacturer may provide additional instructions subsequent to this approval date which shall prevail. Installation must be by a Factory Trained 'Qualified Applicator' approved and licensed by Polyfoam Products, Inc. 3. Calibration of the Foampro® dispensing equipment is required before application of any adhesive. The mix ratio between the "A" component and the "B" component shall be maintained between 1.0 -1.15 (A) ; 1.0 (B). The dispense timer shall be set to deliver 0.08 to 0.15 pounds per tile as determined at calibration. No other settings shall be approved without revision of this Component Approval. 4. Adhesive shall be dispensed in a 17 in to 23 in' pad at time of application. The cured pad shall be approximately 5" x 12 ". Foam placement shall be in accordance with the 'Placement Details' provided in this Component Approval. Each generic tile profile requires a specific placement, as noted in Table 1, below. A tile manufacturer may test a tile system in compliance with PA 101 and add an additional detail without incurring an additional revision cost. 5. Adhere tile directly in freshly applied adhesive. Tile must be set within 2 to 3 minutes after foam has been dispensed. 6. Adhesive shall be placed to create contact with minimum 2 tiles, as outlined in the 'Placement Detail' for each tile profile. COMPONENT APPLICATION 7 Raul Rodriguez Product Control No.: 95- 0314.10 SYSTEM LIMITATIONS Product Control No.! 955);14,10 1. Tile must be applied within 2 to 3 minutes of the application of Polypro® AH 160 adhesive. 2. Polypro® AH160 adhesive shall be installed only by 'Qualified Applicators' approved and licensed by Polyfoam Products, Inc. 3. - For adhesive set tile applications, a field static uplift test by a Dade County accredited testing agency, in compliance with Dade County Protocol PA 106, shall be required not less than 72 hours after application to confirm tile adhesion. The results of this testing shall be reported to the Building Official and the installer stating that the application has passed or failed PA 106 testing. If the application fails PA 106 testing, the report shall state which portion of the test was failed; Category 1 (examination for loose tile) or Category 2 (uplift testing of tile). Subsequent to testing, the installer may repair not more than 5% of field area tiles and 10% of perimeter area (i.e. ride /rake) the with approved tile adhesive. The installer shall place an identifiable marking on each repaired tile for future reference. Any PA 106 re -test shall not include any marked tile. Refer to application drawings published by the National Tile Manufacturers Association for penetrations and terminations, as well as the Placement Details' included with this Component Approval. 5. Refer to tile Roof System Assembly Product Control Approval for system Approvals with this Component. 6. Refer to the Prepared Roof System Assembly for fire rating, 7, Polyproe AH 160 shall not be exposed permanently to sunlight. 8. Polyproe AH I60 shall be applied with Foampro RTF 1000 dispensing equipment only. 9. Any amendments to these provisions shall be in compliance with Sections 203 and 204 of the South Florida Building Code. 8 Rau i' odriguez PLACEMENT DETAILS (CONTINUED) FASCIA BOARD (EPOS . PREFABRICATED ccosURE NAILED THROUGH rt.AsIte ROOF CEu OR INTO AP RO P AO KEPHCLE MAIL HOE l'ARCUG) FLAS11C ROCF CEMENT (WEN LO0I11CHM. HAIL. IS RECUIR.O BY cccE) ME!CIAP a;.RCE BOARD Sealant or P o l e AR 70 SURFACE Placement Detail #2: 'S' Shaped Tile Profile Product Control No.: 95- 0314.10 10 Raul ''. driguez METRO•DADE NMI ■ • This approval supersedes all previous approvals. METROPOLITAN DADE COUNTY. FLORIDA METRO -DADE FLAGLER BUILDING DU%LDING CODE COMPLIANCE DEPARTMENT SUITE 1003 METRO-DADE FLAMER DUILUINQ 140 WEST FLAGLER STREET MIAMI, FLORIDA 33130.1503 (305) 375-2901 FAX (305) 375 -2908 1. Extensions of Acceptance may be considered after a new application has been filed and the supporting data, test reports no older than ten (10) years, have been re- evaluated. All reports of re- testing shall bear the seal, signature and date of an engineer registered in the State of Florida. 2. Any revision or change in the materials, use, or manufacture of the product or process shall automatically be cause for termination, unless prior approval is granted for revisions or change. 3. Any unsatisfactory performance of this product or process or a change in Code provisions shall be grounds for re-evaluation. 4. This acceptance shall not be used as an endorsement of any product for sales or advertising purposes. 5. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is displayed, then it shall be done in its entirety. 6. Product approval drawings, where required for permit applications, shall be provided to the applicant by the manufacturer or his distributors unless otherwise noted in the Notice of Acceptance. The prints need not be re- sealed by an engineer. 7. Faiiure4o comply with the Standard Conditions shall be cause for termination of the Approval. Rau!' odrigucz Pr • • uct Control Division Supervisor C��