Loading...
511 NE 94 St (7)s Miami Shores Village 10050 N.E. 2nd Avenue Miami Shores, Florida Att Frank Loubian €YflOLOG THINORD 'ARCHITECT E N G I N E E R PLANNERS 814 S.W. 27th Avenue Miami, Florida 33135 Phone (305) 642 -0341 June 20,1989 Re: 511 N.E. 94th Street Permit No. 29007 Dear Mr Loubian, Please find attached proctor compaction test preformed by All State Engineering and Testing Consultants, Inc. The 98% dry density requested by plans and specifications has been exceeded. The requested bearing capacity of 2000 PSF has been exceed by a 2500 PSF bearing capacity furnished, therefor soil bearing is acceptable to support above referenced structure. Sincerely . � William R. Bradford, '.E., R.A. 5- 22-89 TESTING LABORATORIES • ENGINEERS • INSPECTION SERVICES • CHEMISTS • DRILLING 3745 N. W. 501h STREET / MIAMI, FLORIDA 3314 PROCTOR COMPACTION TEST DATE: ORDER No 89 -1020 CLIENT: F.E. Builders ADDRESS 2222 Ponce Deleon Blvd., Suite 350 , Coral Gables, Fl. 33134 PROJECT:Single Family Residence ADDRESS: 511 N.E. 94 St., N. Miami, fl. SAMPLE LOCATION: homogeneous mixture from the bldg area SOIL DESCRIPTION: crushed limerock SAMPLED BY: REPORTED TO: W.Q. Laboratory Number: 5380 Sampled By: W.Q. Tested I3y: W•Q• Checked By: A.R. Jim Poppleton The following compaction test was conducted in accordance with 'the standard Methods for Moisture Density Relations of soil using a 10 Ib. hammer and 18" drop AASFITO designation T -180 —C % MOISTURE 4.1 5.4 7.5 10.2 7.5 Optimum Moisture 100% Maximum •Dry Density 130.2 98 %.Dry Density 95 %'•Dry Density GRADATION TEST Percent Passing 3/4" sieve 127.6 _ 123.7_ 69.8% TEST—RESULTS DRY DENSITY 121.4 127.0 130.2 125.9 136 134 132 130 128 126 124 122 120 P.O. BOX 66 / HIALEAH; FLORIDA 33010 / PHONE: (305) 838 - 6882-83' Sample Number: 1 ■■r1Im/a�1ra WW1ra.1■.. ■ ■w.ULL1lU C,a■CJNNCMwt■ ■ ■ ■ ■■■ 1111111111111111111111 11111111111111111111111111111111111J1 u■ ■.■1010u■10...ur.� n�iiiiiii■�iOiiiiiiii■ °ii ■.■■.•■.•.at■.■■o■■ ■■■■■■ee>, ■■10 ■ ■...■.■7■ ■ •■ •u■••••10 ■1010■ ` n■.■■..■.•■■.■....•■■■ ••u•• ■1010■■■■■ ■■■■■■■■■■■■■■■■ ■ ■■ •u 10■■1010.10.■.uu.0 ■u10.u10.•1010ri ■ ■■■■w■■■.M:..I■ ■■■w■■w■■■L4 � 1101010.10■wo.1.10■■.c. ■. ■■.■..ra ■ ■■.■w■■a■.■. ■10...10 ■■.■.■u ■■u ■■.■■w■.■■■■■•■.•■.■■ ■G ■■■■v iu.■u10u■■■■■■■.■■.1:1.■a■ ■10■rA■1010■.10•••••••10■■■10■.■eg 101010.■ ■ ■■■■ ■■■■■■■MMINI ■.M■■ C 10 =� ■..11.10■1010...1010 ■.10 ■..10.11. ■ /■....■■ ■ ■10■ ■.10.10■ ■1010 ■101011,1■ ■ ■.1010 ■10.10.10. ■■ ■.■.■.■■.10..10. MEMIMMEMOMMIOMMONEMMIUMMIMMINIM ■ii ■ ■■■■u■•■.•■u■ ■•.•••••uiai ■1 /■10. ■■■■ ■ ■.10 ■10.■■■. ■ ■ ■ ■.■ ■■ 1 1.1010..10.10. ■■10■ ■■■.■.■■10..10■■ IIMMUMMIMMUMMOMMEMMEMEMMEMMEM 101010■10■10.■.10.1010■10■ ■10.1010..1010■■ ■.10■.....uu10■.10. ■. ■10....10■ ■■ ■uuu..uwu10Yu.10■ ■■1010.10 ■.10■ IMMENIMMIMIIMOMMINEIMOMM 4 5 6 ' 7 ectf 1 10 11' Sub .'tted, crto Ramirez, ' E. ALL STATE ENGINEERING & TESTING CONSULTANTS, INC. c AS SUE.IMITTED REVISE AND RESUM`.411 FUM AS CORR:'.CTED SUBMIT SPECIFIED ITEI'vl El REJECTED Corrections or comments mode on shop drcv..igs duitle, this re- view do n.Dt from comijliance •vith N.2c.iuircrne:•:ts of th2. co Thif.; clie is only for re.vie.vi of ger, ro.! c with ancl gi.c.i ;h.: cor.trect 'pr: ;ontirrri:; t: •;; •ii dirtienflion::; st11:,:•-ting ta'crical-ion t otrlf,; o t of • ; p...r;o:mi:T. his work in a sa',e a •rj rnanr.er. WILLIAM R. BRADFCRD — ARCHITECT - ENGINEER DATE. -(( BY , D - 58744 D - 58745 D - 58746 D - 1 2 3 12" 12" 12" 127.9 128.0 126.2 5.6 5.1 4.9 98.2 98.3 96.9 95% 95% 95% 130.2 130.2 130.2 P - 5380 P - 5380 P - 5380 P - P - Lab No. D- 58744 LOCATION: Lab No. D- 58745 LOCATION: Lab No. D- 58746 LOCATION: Lab No. D- LOCATION: Lab No. D- LOCATION: SAMPLED BY: W.Q. C�ir�lieeeFfr� �� /� � o� �� G� a26 , L . TESTING LABORATORIES - ENGINEERS - INSPECTION SERVICES - CHEMISTS - DRILLING 3745 N. W. 50th STREET / MIAMI, FLORIDA 33142 FIELD DENSITY TESTS, OF COMPACTED SOILS CLIENT: F.E. Builders ORDER No. 89 -1020 ADDRESS: 2222 Ponce Deleon blvd, Suite 350, Coral Gables, Fl. DATE: 5 -22 -89 PROJECT: Single Family Residence ADDRESS: 511 N.E: 94 St., N. Miami, Fl. CONTRACTOR: F.E. Builders DESCRIPTION OF MATERIAL: crushed limerock (bldq pads) Laboratory No. Test Number: Depth (INCHES) Field Density (LB. /CU.FT.DRY BASIS) Moisture Content Maximum Density in the Field ( %) Compaction requirement by specs. % of Maximum Density 100% Maximum Density (lab) Optimum Moisture: 7.5 % Proctor T -180 A.A.S.H.T.O. Method C REMARKS: All of the above test result comply with job specification Reported By: W.Q. ' Checked By: A.R. REPORTED TO: COPY SENT TO: south center of the bldg pad N.W. corner of the bldg pad N.E. corner of the bldg pad Backfill ( ) Subgrade ( ) Grade TESTED BY: W.Q. FIELD DENSITY METHOD A.S.T.M. D- 2922 -81 Res ctf .l,- Sub • ted, ALL STATE ENGINEERING k TESTING CONSULTANTS. INC. As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and authorization for publication of statements, concrusions or extracts from our reports is reserved pending to clients written approval. P.O. BOX 66 / HIALEAH, FLORIDA 33010 / PHONE: (305) 638 - 5882 -83 re AS SUBMITTED ri REVISE AND RESUCl AS CORRECTED Ej SPI:.011:!ED E] REJECTED Corrections or comments mode on ship cii. tiwoing thi i re vie do not N.11,!ve cotra..tor from c.ompila!:ce cf do,:.umc;: This che...:1; onIy for re..•ied co.iformxicc cln).ign cancpt o h gener:.1 compliahco v,ith .e.7.;;Ar;7■ t docume; The co:.trator rei:ponle anc! correI:.tiog dirneasiom.; ... tIo.g prczesses and t. of co:ittruct.on: .g, 11::; tiit of all other tr;rdes; z.nd and satfactory manner. WILLIAM R. BRADFORD — ARCHITECT - ENGINg:R DATE 4-1(9-81 3y et)e.4.1— 4 MIAMI SHORES VILLA BUILDING INSPECTION DEPARTN, APPLICATION FOR BUILDINi Application is hereby made for the approval of the detniled stntemrnt of the plans and specifications I described. This npplicntion is made in compliance and conformity with the Building Ordinance of Miami Stnte of Florida. all ordinances of Miami Shores Vilinge and all rules and regulations of the Building Divii herein specified or not. A copy of approved plans and specificntions must be kept at building during prof Owner's Name and Address -- 'H _ F.E. Realty Financing, Inc. Registered Architect anchor Engineer William Reynolds Bradforsi Name and address of licensed contractor F.E. Builders, Inc. 2222 Ponce De Leon Blvd, Coral _Gables Florida 33134 Location and legal description of lot to be built. on: Lot 15 -f E 2 14 Block 55 Subdivision Mi Sh ores. S cj:I n 7 Street and Number where work is to he done 511 N o r t-h£ia -s t- 944- -3 t e e_ t_ State work to be done and purpose of building (by floors). state exterior colors (submit snmples) New Construct ion r o_ne (li _story, single family residence. and for no other purpose. N'v luilding XXXX Remodeling Addition Repairs No. of Stories To he constructed of CBS Kind of foundation CBS Roof Covering CLAY TILE Estimated Thud cost of improv s 917;q .1 0 Amount of Permit $ 9 .h71,110 1'Inn Cubn e 0 ` 1. ' ' f g " 14 Zone cubage required g .y 21.08' S ize of Building Lot 75.00'x 128.75' .9I6.g Uislnnce to next nearest building B Maximum live loud to be borne by each floor I hereby submit all plans and specifications for said building. All notices with reference to the building and its construction may be sent to F.E. Builders, Inc_ 2222 Pore_D 'Die undersigned applicant for this building permit dons hereby certify that he understnnds and accepts his obligatons as on employer of Labor under the Florida 1lbrkmeti s Compensation Act, being Section 5966. Compiled General Laws of Florida. Permanent Supplement, and has complied with the provisions thereof. and will require simil:n compliance from nil contractors or sub- conl.rnctors employed by him in the work to be performed under this permit: and will post or cause to o led for inspection on the site of the work such public notice or notices as are required by the Act. The undersigned agrees to mploy only such subcontracto , on .rk to be performed under this permit. as are licensed by Miami Shores Vilinge. Remarks Signed) • eat N STATE. OF' FLORIDA COUNTY OF DADE. Disapproved Date (Signed) Building Inspector - • PLANNING BOA RD DATE JIM POPPLETON F.E. BI ALDERS, ONC. 2222 PONCE DE LEON BLVD., SUITE 350 CORAL GABLES, FLORIDA 33134 TELEPHONE: (305) 442.0744 FAX 442-9848 REAL ESTATE INVESTMENTS- JOINTVENTURES- CONSULTINGBUILDERS Date May 4th, 19 89 N 2222 SLreet_fOnce —DP leon ' X350, Coral Gables,__EL 33134 } Ss. Before me. the undersigned authority. a notary public. duly authorized to administer oaths and take acknowledgments. personally appeared _._._.. to me well known. and who. being by me first duly sworn. upon oath deposes and says that he is the of the above described construction. that he has carefully read the foregoing application. and that he did sign the same. and that all facts therein by him stated are true. Permit No. Z1 1 Date 11 Read. Sworn to and Subscribed before me. Notary Public. State of Floridn My Commission Expires Chairman Member Member Member Member Member Council Approved Date Disapproved Date NOTE: A charge of '125. will he mark for making correct inns nr changes In this npplicntion niter npprnvnl has been nhtnined from the l'Innning Board. A re- inspection fee of $25.00 will hechnrfed when such re- inspection is made necessnry by Improper notice for inspection or fnulty materials and or workmanship KOPPEN, WATKINS, PARTNERS 8 ASSOCIATES A PROFESSIONAL ASSOCIATION ATTORNEYS AT LAW REPLY TO: 700 NORTHEAST 90T. STREET MIAMI, FLORIDA 33138 TELEPHONE (305) 754 - 5442 TELEFAX (305) 757 April 11, 1989 Mr. Frank Lubien Miami Shores Village 10050 N.E. Second Avenue Miami Shores, FL 33138 Dear Mr. Lubien: RAK /sh sa44.1, s`0 7 21 9y4 ANNEX BY APPOINTMENT ONLY 7251 NE 2N AVENUE MIAMI, FLORIDA 33138 TELEPHONE (305) 759 -1002 I own the following described parcel of real property, to -wit: Lot 13, and the West 25.00 feet of Lot 14, Block 55, MIAMI SHORES, SECTION 2, according to the Plat thereof, as recorded in Plat Book 10, at Page 37, of the Public Records of Dade County, Florida; I have been requested by the owner of the adjacent parcel, legally described as: Lots 14 and 15, Block 55, MIAMI SHORES, SECTION 2, according to the Plat thereof, as recorded in Plat Book 10, at Page 37, of the Public Records of Dade County, Florida, and except the West 25.00 feet of Lot 14. to consent to the installation of the condensing unit for the central air conditioning to be allowed to be placed on the West side of the said parcel. This letter will evidence my consent and approval. Very tr, yours, (10BERT A. KOPPEN ROBERT A. KOPPEN ATTORNEY AT LAW GENERAL PRACTICE COMMERCIAL LITIGATION TRIAL PRACTICE PROBATE GUARDIANSHIP TRUSTS REAL ESTATE PROJECT NAME AND ADDRESS: G F . ' a v t ,....-c, ms. 1 h , BUILDER: - k N •E. `z4 ='S'Tr PERMITTING OFFICE: A p SsppQC'S QtA CLIMATE 7 ❑ 8 9 NE: OWNER: . 15U %L V'Q-.S tl4 PERMIT NO.: I/ # t Grp JURISDICTION NO.: 2 3 I 4 6 S ek GLASS AREA AND TYPE NEW CONSTRUCTION ❑ ADDITION ❑ MULTIFAMILY ATTACHED ❑ SINGLE - FAMILY ETACHED FLOOR FLLOOR AREA Z ' 1 F UNITS BY THIS SUBMITTAL: SINGLE- PANE CLEAR TINT,FILM.SOLAR SINGLE- PANE SCREEN SAVE OVERHANG LENGTH FL 1 O. J FT. I I I J I S0. FT • REPRESENTS A WORS SUBMITTAL CASE CONDITION: LEENGTHwERHANG _ O PANES D PANE SO. FT 1 I I FT FT NET WALL AREA AND INSULATION MASONRY R = FRAME R = STEEL STUD R e LOG R I s 4 rl -----. n FT FT I I I I FT. CEILING AREA AND INSULATION FLOOR TYPE AND INSULATION UNDER ATTIC R = SGL ASSEMBLY R = SLAB PERIMETER R - RAISED WD C CON C R - I 2 I 4 7 1 1 1 IF7 ga FT 1 I2I3IZ1I FT FTT 1 1 1 I DUCTS UNCONDITIONED SPACE R COOLING SYSTEM at CENTRAL ROOM ❑ PACKAGE TERMINAL AIR CONDITIONER ❑ NONE SEERIEER • 1 1 1. _ HEATING ❑ ELECTRIC STRIP NATURAL GAS ❑ROOM UNIT OR PACKAGE TERMINAL HEAT PUMP SYSTEM fp HEAT PUMP ❑ OTHER FUELS NONE MAC CREDITS ❑ CEILING FANS ❑ CROSS VENTILATION ❑ WHOLE HOUSE FAN ❑ ATTIC RADIANT BARRIER ❑ MULTRONE HOT WATER SYSTEM 111 ELECTRIC In NATURAL GAS ❑ OTHER FUELS ❑ NONE NOT WATER CREDITS ❑ SOLAR ❑ HEAT RECOVERY ❑ DEDICATED HEAT PUMP y � • I4I. CONDITIONED \ SPACE `\ Z R • SF/EF • .I 1 1 EF • ,° _ BEDROO S = I 1 1 COPIAFUE • ^ ,I I I FORM 900 -A-88 REVISED: 1/87 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION SECTION 9 — RESIDENTIAL POINT SYSTEM METHOD DEPARTMENT OF COMMUNITY AFFAIRS CLIMATE ZONES SOUTH 7 8 9 This form may be used to demonstrate compliance with the Energy Code for new single-family detached or multifamily attached dwellings under Section 9. An alternative 10 this method for single- family detached dwellings, and mutifamily attached dwellings of three stories or less, Is provided in Section 10. MOW Amity attached dwellings greater than three stories must comply under Section 9 or 5. Additions to existing residential buildings must comply under Section 9 or 10. Additional information may be obtained from your local building department or. the Department of Community Affairs, Energy Code Program. 2571 Executive Center Circle East, Tallahassee, Florida 32399 " ILTRATION ITICE USED e'2 ❑ "3 El r 1 it 7. TOTALAS_BUILT POINTS TOTAL SASE POINTS CALCULATED ENERGY PERFORMANCE INDEX MUST NOT EXCEED 100 POINTS. BUILDING OFFICIAL: DATE: X 100 = A- 9_57 Revised 1/87 " CALCULATED E.P.I. ith Section 553.907 F.S., I hereby certify that the plans Review of the plans and specifications covered by this calculation indicates 1\ c6verbd by this calculation are in compliance with the compliance with the Florida Energy C ode. Before construction is compteted, this n 2- budding will be inspected f e• 4 . nce in accordance with Section 553.908 F.S. PST ,-Y itlff E AASURES (Must be met or exceeded by all residences.) C rg r A J0 /NT . REOUIREMENTS MAXIMUM OF 0.5 CFM PER LINEAR FOOT OF OPERABLE SASH CRACK. MAXIMUM OF 0.5 CFM PER SO. FT. OF DOOR AREA. INCLUDES SLIDING GLASS DOORS, SOLID CORE, D PANEL, IN_S TED, QR GLASS DWRS.?NLY, BE CAULKED, GASKETED, WEATHERSTRIPPED OR OTHERWISE SEALED. &T BEAR LABEL INDICATING COMPLIANCE WITH ASHRAE STANDARD 90 OR COMPLY WITH EFFICIENCY AND 'DBY LOSS REQUIREMENTS. SWITCH OR CLEARLY MARKED CIRCUIT BREAKER (ELECTRIC), OR CUT .OFF --K- 904 • JAST BE PROVIDED. AN EXTERNAL OR BUILT-IN HEAT TRAP MUST BE PROVIDED. `HEATED POOLS MUST HAVE COVERS (EXCEPT SOLAR HEATED). NONCOMMERCIAL POOLS MUST UMP TIMER. GAS SPA & POOL HEATERS MUST HAVE MINIMUM THERMAL EFFICIENCY OF 75%. HIS REOUIRED ONLY FOR RECIRCULATING SYSTEMS INCLUDING HEAT RECOVERY UNITS. IN SUCH CASES. PIPING HEAT LOSS ea TED TO 17.5 BTUMILINEAR FOOT OF PIPE Ct MOT BE RESTRICTED TO NO MORE THAN 3 QAL Q L$ PER MINUTE AT 20 TQ 8QL�G. P,44: IN ACCORDANCE WITH INDUSTRY STANDARDS & LOCAL MECHANICAL CODES. DUCTS IN PAQE MV�BE INSUF A D TO MINIMUM R. 4.2 & JOINTS _MSLBE --- Y AC E$SIBLE MANUAL QR AUTOMATIC THERMQ_STAT FOR EACH SYSTEM COMMON WALLS -FRAME R.11 OR CBS R -3 FRAME COMMON CEILINGS b FLOORS R -11 * CHECK PC 'YE •-fit ORIENT.I AREAS x SINGLE -PANE OR SUMMER POINT MOLT. DOUBLE -PANE SUMMER POINT MULT. x SUMMER OVERHANG = FACTOR (9B) 1 AS-BUILT GLASS SUM. PT'S/ 4.' y 4 C 64.5 TINT• • 65.2 CLEAR 60.2 TINT• • 54.9 N 1 NE 4, 94.5 88.0 78.2 E q 136. 133.9 127.0 109.5 1 1 Z 'L iv SE 146.2 X3. 1430 132.5 135.0 124.2 116.1 107.7 l t1.1. S q 0 SW 146 2 143.0 135. . 116.1 i W D 4 P 133.9 127.0 88.0 109.5 78.2 . 1 NW 94.8 94.5 H • 428.7 354,7 380.6 278.9 COMPONENT DESCRIPTION 1 AREA x IQqf SUMMER 1 POINT MULT. = (9C THRU 9G) 2.7 AS -BUILT SUMMER POINT 4155 (,.4 . -Icon. ADJACENT 1.0 COMPONENT DESCRIPTION AREA x �^ (1i + BASE SUMMER POINT MULT. 1.6 I BASE = SUMMER ;Ain_ Z 11VM I EXTERIOR ADJACENT 1.0 SUMMER CALCULATIONS GLASS BASE BASE AREA x SUMMER = SUMMER PT. MULT. POINTS 41;4'. k 60.2 88.0 N 7�- NE q S 9 Sw W 0 NW 127.0 135.0 124.2 135,0 88.0 124.2 H' 15 1 z' 127.0 1 COND. I TOTAL .15 x FLOOR + GLASS AREA A 1 1 ' ia'j "I a• BASE BASE ADJUSTED ADJUST. x GLA9S�SIJ.= GLASS FACTOR qa 7� 5 ` i3 $ E `T 2 i P 12.9 4.9 EXTERIOR ADJACENT to 8( -•1 1 UNDER ATTIC OR SINGLE ASSEMBLY 2Z '17 .8 8 14. .8 TOTAL COMPONENT BASE SUMMER POINTS 1r- BASE CEILING AREA EOUALS FLOOR AREA UNDER CEILING. AS -BUILT CEILING AREA EQUALS ACTUAL CEILING SOUARE FOOTAGE ID USE TOTAL FLOOR AREA OF CONDITIONED SPACE COOLING SYSTEM BASE COOLING 1 TOTAL BASE SYSTEM x SUMMER MULTIPLIER POINTS .43 1 41, I BASE COOLING 1 POINTS UM ER - 5/STEM NUMBER BASE BASE OF x HOT WATER = HOT WATER BEDROOMS MULTIPLIER , POINTS , 3319 1q •Cl 41. I TOTAL COMPONENT AS -BUILT SUMMER POINTS V 9 -58 2 47 CLIMATE ZONES 7 8 9 Revised 1/87 AS-BUILT GLASS SUBTOTA 12 01 1 1/ f So( , .ai •.,,mod la 1 2 I421.b p ¢ O SLAB RAISED - 20.0 - 2.16 V FOR SLAB -ON -GRADE USE PERIMETER LENGTH AROUND CONDITIONED FLOOR. FOR RAISED FLOORS USE AREA OVER UNCONDITIONED SPACE. V V I XA- SS°to TOTAL 1 AS-BUILT 1 AS-BUILT 1 AS-BUILT 1 AS -BUILT AS-BUILT x DM x . CSM x CCM = COOLING SUM. PTS. (9H) (9K) (9L) POINTS SG . 1 , 4 - . 3� .sl.>t.Qf .811 girt AS-BUILT HOT WATER SYSTEM DESC. NUMBER AS-BUILT 1 AS -BUILT AS-BUILT OF x HWM x HWCM = HOT WATER BEDROOMS (9M) (9N) POINTS 3 13lf' . L-z_ ?Al I.kr • H • Horizontal Glass (Skylights) •• For glass with known Shading Coefficient, we sec. 903.2(a) Tint Muhipliers may be used for glass with solar screens, film, or tint., . INFILTRATION PRACTICE (See Table 9P) SPM PRACTICE is 1 18.6 PRACTICE •' 2 14.7 PRACTICE • 3 _ 10.1 DOOR TYPE EXTERIOR ADJACENT WOOD 11.8 4.5 INSULATED 12.9 4.9 1 ■ 1 A813]13S OH RATIO ,0 -.11 .12 -.17 .18 -26 .27 -.35 ,36 -A6 .47 -,57 ,58 -,70 .71 -.83 ,84 -1.19 1.19 -1.72 1,73 -2.73 2.74+ N 1.0 .94 .91 .87 .84 .80 .77 .74' .70 .64 .58 .53 NE/NW 1.0 .95 .92 .86 .81 .76' .72 .68 .64 .56 .50 ,44 E/W 1.0 .95 .93 .87 .81 .75 • .70 .65 .59 .46 .41 .34 SE/SW 1.0 .95 .92 .85 .78 .70 .64 .58 .52 .42 .34 .28 S 1.0 .94 .91 .83 .75 .67 .60 .54 .48 .39 .33 .30 LENGTH • 0 tt. 1 ft. 114 ft. 2 Q. 3 ft. 3' ft. 41 ft. 51/2 ft. 61 ft. 914 ft, 14 ft. 20 ft.+ • To select by Overhang Lena no pan of glass shall be more than 6 It below the ovetnan. 9C WALL SUMMER POINT MULTIPLIERS (SPM) FRAME CONCRETE BLOC FACE BRIC LOG SPM INSULATION EXT. INSULATION R•VALUE • •D FR NORMAL WT. LT. WT. NOR. WT. LT. WT. if '�m 3.4.9 IN . . •∎• D r r AD R-VALU U!' AD EXT EXT EM' - 16.0 » � L . X � - • 9 =NM 1 • 1: 9 11111111111111=11111FINTEWIFINIIIIIIMIIMIll ' � 2.2 4.2 Wall . • 1 111111'5X' , 17 Mill 19 - .9 �- 1. '��' '1•11' �'' 11 1 1 �� MIME 1� �1' 1 _IIIIITall : '1111161111 ME' 111127M11105711 . EE}91111111MIIM'MIll MIIIIIIITCRIM,1111111111111111110111111 linfir5llir' MIIIIMI}!' 7 0 - - wirmi • 4.2 Mini 9E CEILING SUMMER POINT MULTIPLIERS (SPM) IMIIIMIIIIIIMMIIIIIIII 1117/1711111MMINITIII V111111111'11111111111 UNDER ATTIC SINGLE ASSEMBLY CONCRETE DECK R•VALUE $PM R -VALUE SPM CEILING TYPE 19 • 21.9 1.5 10 -10.9 4.0 R -VALUE DROPPED 4.1 EXPOSED 4.6 22.25.9 1.3 11 -12.9 3.6 10.13.9 26.29.9 1.0 13.18.9 3.3 14.20.9 2.9 3.1 30. 37.9 .8 l 19 - 25.9 2.5 21 8 Uo 1.9 2.0 38 &UP .6 26 &Up 1.6 r. s • • - . . , SLAB -ON -GRADE EDGE INSUL TION SPM RAISED CONCRETE R -VALUE SPM RAISED W000 (See 903.2(e)) R -VALUE SPM R -VALUE 0.2.9 -20.0 0.2.9 .8 0. 6.9 1.1 3 -4.9 -17,4 3.4.9 - .3 7.10.9 .1 5.6.9 -16.6 5 -6.9 - .4 11 - 18.9 • .0 7 &Up - 16.0 7 &Uo - .5 19 &UP .0 R-VALUE With Return Air Duct W/O Return Air Duct 4.2 - 4.9 1.14 1.10 5.0 - 6.6 1.12 1.08 6.7 & Up 1.09 1.06 DUCTS IN CONDITIONED SPACE 1.00 1.00 88 SUMMER OVERHANG FACTORS (SOF) For eIngle and double pane glass. OVERHANG RATIO o OH LENGTH OH HEIGHT 90 DOOR SUMMER POINT MULTIPLIERS (SPM) 9G INFILTRATION SUMMER POINT MULTIPLIERS (SPM) SUMMER POINT MULTIPLIERS (SPM) 9F FLOOR SUMMER POINT MULTIPLIERS (SPM) CLIMATE ZONES 7 8 9 -59 Revised 1/87 o T SINGLE-PANE DOUBLE-PANE GLASS x WINTER POINT MULT. OR WINTER POINT MULT. x WINTER 1 OVERHANG • FACTOR 9B) AS-BUILT GLASS WINN�,2:13� 41•f.3" AREA C I T" 3.7 EAR TINT" N 72 2.2 2.4 I• 03 NE E --- - ,7 2.9 1.4 1.8 - .6 - 2.5 .>1S 7�j -end' .2 - 1.1 - 3.3 1,1;,. - 2.0 9 0 ( -zdJ -1.8 -3.1 -2.a • 8 $ _S S_W - 2,1 -2.0 -3.3 -2.5 - W 1 .2 - 1.1 - .6 NW 2.9 2.9 1.4 1.8 H• -8.9 -7.8 -7,3 -5.7 w COMPONENT W AREA x P WINTER 1 A AS -BUILT c6 5 ua • -c,- 1 - 1 WINTER DESCRIPTION POINT MULT. POINTS EXTERIOR fg `4 .3 553 ADJACENT .5 „vM 1 6,* ltd. .... (o ' 3•b 470.4 EXTERIOR (.• 3 3.8 S 37- `f ADJACENT 2.5 Isaooa1 WINTER CALCULATIONS GLASS IBASE WINTER' BASE • AREA • POINT 1 WINTER o MULTIPLIER POINT) ��- 2.2 14w. _Si- NW H• 8 NE E 9 S go SW W N J 1.4 - 1.1 - 3.3 - 3.3 - 1.1 1.4 - 3.1 - 3.1 • - Znq L I COND. 1 TOTAL I BASE BASE 1 ADJUSTED .15 x FLOOR + GLASS = ADJUST • GLASS = GLASS AREA 1 AREA FACTOR SUBTOTAL BASE WP .15 1 2-2/1 1 ('11 t�.i l - t36. s I 17;1.7 d UNDER ATTIC OR SINGLE ASSEMBLY SAAB RAISED " 71 INFILTRATIQ 2. Z HEATING SYSTEM .1 - 2.1 427 1 - .28 l FOR SLAB -ON -GRADE USE PERIMETER LENGTH AROUND CONDITIONED FLOOR F US 4 BASE HEATING ' TOTAL BASE BASE SYSTEM • WINTER = HEATING MULTIPLIER POINTS POINTS 1.14 Z4.3 3f 4. 1.1 - 9 0 BASE BASE COOLING + HEATING POINTS POINTS (From P.21 �8( tq - 3► BASE TOTAL + HOT WATER = BASE POINTS POINTS (From P,2) (Enter on P,1) , q °(i 3)770 IMATE ZONES 7 A _ 9 AS-BUILT GLASS SUBS LIL -F0 ')0 rhso 2 21 Z BASE CEILING AREA EQUALS FLOOR AREA UNDER CEILING AS -BUILT CEILING AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE R RAISED FLOORS LISE AREA OVER UNCONDITIO SPACE. TOTAL I AS -BUILT 1 AS-BUILT AS-BUILT x DM x HSM WIN. PTS. (9H) (9t) 8ti, f 1.1'1 g cr • H - Horizontal Gress (Skvliohts) •• For glass with known Shading Coefficient as see. 903.2(a). Ttnt Multipliers may be used for glass with sorer screens, fitm, or tint. �. I.' /. 7 • 1 TOTAL FLOOR AREA OF CONDITIONED SPACE V L tO TAL COMPONENT BASE WINTER POINTS I Z 7 i s .3 TOTAL COMPONENT AS-BUILT WINTER POINTS 1 I V • AS-BUILT HCM (9J) re AS -BUILT HEATING POINTS 1 AS-BUILT COOLING POINTS (From P.2) PtIgif 1 AS -BUILT • HEATING POINTS 4&7.1 1 AS -BUILT • HOT WATER POINTS (From P.2) GI's ( TOTAL AS -BUILT POINTS • (Enter on P. Itt.z Revised 1/87 EXTERIOR (.• 3 3.8 S 37- `f ADJACENT 2.5 Isaooa1 WINTER CALCULATIONS GLASS IBASE WINTER' BASE • AREA • POINT 1 WINTER o MULTIPLIER POINT) ��- 2.2 14w. _Si- NW H• 8 NE E 9 S go SW W N J 1.4 - 1.1 - 3.3 - 3.3 - 1.1 1.4 - 3.1 - 3.1 • - Znq L I COND. 1 TOTAL I BASE BASE 1 ADJUSTED .15 x FLOOR + GLASS = ADJUST • GLASS = GLASS AREA 1 AREA FACTOR SUBTOTAL BASE WP .15 1 2-2/1 1 ('11 t�.i l - t36. s I 17;1.7 d UNDER ATTIC OR SINGLE ASSEMBLY SAAB RAISED " 71 INFILTRATIQ 2. Z HEATING SYSTEM .1 - 2.1 427 1 - .28 l FOR SLAB -ON -GRADE USE PERIMETER LENGTH AROUND CONDITIONED FLOOR F US 4 BASE HEATING ' TOTAL BASE BASE SYSTEM • WINTER = HEATING MULTIPLIER POINTS POINTS 1.14 Z4.3 3f 4. 1.1 - 9 0 BASE BASE COOLING + HEATING POINTS POINTS (From P.21 �8( tq - 3► BASE TOTAL + HOT WATER = BASE POINTS POINTS (From P,2) (Enter on P,1) , q °(i 3)770 IMATE ZONES 7 A _ 9 AS-BUILT GLASS SUBS LIL -F0 ')0 rhso 2 21 Z BASE CEILING AREA EQUALS FLOOR AREA UNDER CEILING AS -BUILT CEILING AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE R RAISED FLOORS LISE AREA OVER UNCONDITIO SPACE. TOTAL I AS -BUILT 1 AS-BUILT AS-BUILT x DM x HSM WIN. PTS. (9H) (9t) 8ti, f 1.1'1 g cr • H - Horizontal Gress (Skvliohts) •• For glass with known Shading Coefficient as see. 903.2(a). Ttnt Multipliers may be used for glass with sorer screens, fitm, or tint. �. I.' /. 7 • 1 TOTAL FLOOR AREA OF CONDITIONED SPACE V L tO TAL COMPONENT BASE WINTER POINTS I Z 7 i s .3 TOTAL COMPONENT AS-BUILT WINTER POINTS 1 I V • AS-BUILT HCM (9J) re AS -BUILT HEATING POINTS 1 AS-BUILT COOLING POINTS (From P.2) PtIgif 1 AS -BUILT • HEATING POINTS 4&7.1 1 AS -BUILT • HOT WATER POINTS (From P.2) GI's ( TOTAL AS -BUILT POINTS • (Enter on P. Itt.z Revised 1/87 WINTER CALCULATIONS GLASS IBASE WINTER' BASE • AREA • POINT 1 WINTER o MULTIPLIER POINT) ��- 2.2 14w. _Si- NW H• 8 NE E 9 S go SW W N J 1.4 - 1.1 - 3.3 - 3.3 - 1.1 1.4 - 3.1 - 3.1 • - Znq L I COND. 1 TOTAL I BASE BASE 1 ADJUSTED .15 x FLOOR + GLASS = ADJUST • GLASS = GLASS AREA 1 AREA FACTOR SUBTOTAL BASE WP .15 1 2-2/1 1 ('11 t�.i l - t36. s I 17;1.7 d UNDER ATTIC OR SINGLE ASSEMBLY SAAB RAISED " 71 INFILTRATIQ 2. Z HEATING SYSTEM .1 - 2.1 427 1 - .28 l FOR SLAB -ON -GRADE USE PERIMETER LENGTH AROUND CONDITIONED FLOOR F US 4 BASE HEATING ' TOTAL BASE BASE SYSTEM • WINTER = HEATING MULTIPLIER POINTS POINTS 1.14 Z4.3 3f 4. 1.1 - 9 0 BASE BASE COOLING + HEATING POINTS POINTS (From P.21 �8( tq - 3► BASE TOTAL + HOT WATER = BASE POINTS POINTS (From P,2) (Enter on P,1) , q °(i 3)770 IMATE ZONES 7 A _ 9 AS-BUILT GLASS SUBS LIL -F0 ')0 rhso 2 21 Z BASE CEILING AREA EQUALS FLOOR AREA UNDER CEILING AS -BUILT CEILING AREA EQUALS ACTUAL CEILING SQUARE FOOTAGE R RAISED FLOORS LISE AREA OVER UNCONDITIO SPACE. TOTAL I AS -BUILT 1 AS-BUILT AS-BUILT x DM x HSM WIN. PTS. (9H) (9t) 8ti, f 1.1'1 g cr • H - Horizontal Gress (Skvliohts) •• For glass with known Shading Coefficient as see. 903.2(a). Ttnt Multipliers may be used for glass with sorer screens, fitm, or tint. �. I.' /. 7 • 1 TOTAL FLOOR AREA OF CONDITIONED SPACE V L tO TAL COMPONENT BASE WINTER POINTS I Z 7 i s .3 TOTAL COMPONENT AS-BUILT WINTER POINTS 1 I V • AS-BUILT HCM (9J) re AS -BUILT HEATING POINTS 1 AS-BUILT COOLING POINTS (From P.2) PtIgif 1 AS -BUILT • HEATING POINTS 4&7.1 1 AS -BUILT • HOT WATER POINTS (From P.2) GI's ( TOTAL AS -BUILT POINTS • (Enter on P. Itt.z Revised 1/87 UNDER ATTIC 4 WPM SINGLE ASSEMBLY CONCRETE DECK_ROOF CEILING TYPE R R•VALUE WPM -VALUE 19 • 21.9 0. 2.9 10 -10.9 .6 R•VALUE DROPPED EXPOSED 1 •0 0 22 25. .3 11 • 12.9 13 • 18.9 5 ,5 10 • 13.9 . 0 • 26 • 29.9 .2 .2 14 • 20.9 .0 30 • 37.9 . 19 • 25.9 .. ,3_ 21 8 U . .0 38& .1 .1 INFILTRATION PRACTICE (See Table 9P) WPM PRACTICE 0 1 1.9 PRACTICE # 2 1.2 PRACTICE " 3 _ .6 DOOR TYPE EXTERIOR ADJACENT WOOD 3.5 2.3 INSULATED 3.8 2.5 - - -- SLAB -ON -GRADE EDGE INSULATION RAISED CONCRETE - RAISED WOOD (See ) -- R -VALUE WPM R •VALUE WP M R•VALMIE WPM _ 0. 2.9 - 2.1 0.2,9 1,0 0. 6.9 .8 3 - 4,9 - 2.6 • 3.4 9 ,3 7. 10.9 .2 5.6.9 - 2.7 • •5.6.9 .1 11.18.9 . 78UD - 2.7, . .7 & UD .0 198UD .1 911 DUCT MULTIPLIERS (UM) •• _ R•VALUE With Retum AIr Duet W/O Return AIr Dues__._ 1.10 4.2 • 4.9 1.14 5.0.6.6 1.12 1.08 6.7 8 Up 1.09 1.06 DUCTS IN CONDITIONED SPACE 1.00 1.00 9B WINTER OVERHANG FACTORS (WOF) 2 m W J N OVERHANG RATIO = OH LENGTH OH HEIGHT 9C WALL WINTER POINT MULTIPLIERS (WPM) OH RATIO N NE/NW ENV SE/SW S N NE/NW E/W SE /SW S ►0H LENGTH • 0 -.11 .12 -.17 0,6 0.3 WINTER POINT MULTIPLIERS (WPM) 18 -.26 27 -.35 90 DOOR WINTER POINT MULTIPLIERS (WPM) 9G INFILTRATION WINTER POINT MULTIPLIERS (WPM) .36 -.46 47 -.5T,r .58 -.70 SINGLE PANE GLASS DOUBLE PANE GLASS 1.0 1.03 1.05 1.08 1.10 1.12 1.14 71 -.83 .84 -1.18 1.17 1.18 ' To SEIe_! by Ove'''a 'a Lel7:'' no be of o;ass Via!' be Mn•e Thar E 11 betoyw the o.e'han9 PM MULTIPLIERS (WPM 9 -61 1.19 -1.72 1.24 • Revised 1/87 CLIMATE ZONES 7 8 9 1.73 -2.73 2.74+ 1.0 1.0 1.0 1.0 1.05 2.04 .91 .94 1.08 2.58 .87 .91 1.13 3.78 .76 79 1.17 5.04 .64 .65 1.09 1.21 6.54 .48 .47 1.11 1.24 7.92 .32 .28 1.27 9.43 15 .26 1.30 11.04 -.03 -.34 1.37 14.42 -.43 1.45 18.12 -.91 -1.68 1.29 1.26 1.51 22.04 - 1.46 -1.92 1.0 1.0 1.0 1.0 O ft. 1.08 85 .95 .96 1 ft. 1.12 .74 .92 .94 1'/ fi, 1.20 .55 .85 .87 2 tt. 1.26 .34 ,77 .78 3 ft. 1.32 1.37 .10 -.12 .67 .57 66 .54 3'% 11. 4 11 1.41 - .36 .45 .38 5111. 1.47 -.63 ,34 .15 6' ft. 1.57 -1,17 .08 -.34 9'/ ft. 1.69 -1.77 -.23 -.70 14 fl. 1.34 1.78 - 2.41 -.58 - .86 20 II.+ • maw 3 AD EXT 9 1 EXT NOM NMI 3 .2 0 0 • 2.9 EXT WOOD R -VALUE • EX 9 10 11 12 1 18. 9 1 25 STEEL R•VALIJE EXT 0. 6.9 7 10.9 11 • 12.9 13.18.9 FRAME 19 • 25.9 0.9 268UD 1 0.4 3.4 2.2 1.5 1.0 1.1 0.8 1.0 0.7 warm 4 •119 1111' 4 MI1161 CONCRETE BLOCK INTERIOR INSULATION NORMAL WT. LT. WT. ADJ EXT 7 15 5 NOR XT. INSULATION WT LT, WT. FACE R•VALUE 0. 6.9 7 10 9 BRICK WOOD FR 4 R -VALUE 3.6.9 7 LOG 6 INCH R -VALUE 3.6.9 7 &Up 8 INCH I SYSTEM TYPE HOT W TER CREDIT MULTPLIERS Heat Pump Solar Water Heater SF .1 .2 .3 .4 .5 6 .7 HSM 12.0. 1.0 HWCM .9 .8 .7 .6 .5 .4 SM .8 .9 .Szaa & Other Full PTHP & Room Units Heat Recovery Unit With A reconditioner HSM .3 .2 .1 .0 Neat Pump HWCM 42 Minimums: Central Units 2.7 COP. PTHP & Room Units 2.2 COP. COP means Coefficient of Performance. . Dedicated Heat Pump EF 2.0.2,49 2.5.2.99 -&6 3.0.3.49 3.5 & Uo HWCM ,44 .35 .29 .25 A HWM must be used in conjunction with all HWCM. See Table 9M. SF means Solar Fraction. EF means Energy Factor. I Form 900D.86 must be submitted to obtain credit for Heat Recovery Unil SY TEM TYP CODIINGCREW MULTITLTE - COOL HEATING SYSTEM MU TIPLIERS Heat Pump COP 7 2.5.2.69 2.7.2.89 2.9.3.09 3.1 - 3.29 3,3. 3.49 3.5. 3.69 3.7 - Up HSM 12.0. .53 .49 .46 .43 .40 9.4 9,9 _Electric Strip SM 11.4 .38 .36 1.0 .Szaa & Other Full PTHP & Room Units M CSM 1,0 (See Table 9J tor Credit Multipliers) HSM 40 HSM for COP 2.2.2.49 = 63,.$ee above for COP >-2.49. .36 Minimums: Central Units 2.7 COP. PTHP & Room Units 2.2 COP. COP means Coefficient of Performance. . SYSTEM TYP CODIINGCREW MULTITLTE - COOL NG SYST M MULTIPLIERS Multizone SEER 7 8.0- 8.5. 9.0- - 9.5• 10.0• 10.5 - 11.0. 11.5- 12.0. Central Units HCM 7.9 8.4 8.9 9.4 9,9 10.4 10.9 11.4 11.9 & Uo .58 CSM .44 ,43 40 .38 .36 .34 .32 PTAC & ROOM Unit CSM .31 .30 .28 CSM for EER 7.5.7.7 = .46. Fo EER's >7 7 use mul loliers above Minimums: Central Units 7.8 SEER. Room Units 7.5 EER. PTAC under 13,000 BTU /H 7.5 EER, and over 13,000 BTU /H 7.0 EER. SEER means Seasonal Energy Efficiency Ratio. EER means Energy Efficiency Ratio. SYSTEM TYPE CODIINGCREW MULTITLTE - Ceilina Fans .86 Multizone . 90 Cross Ventilation or Whole House Fan (Credit for only anal .90 Attic Radiant Barrier . .95 .95 Where more than one credit is claimed, multiply CCM's together. Enter product on page 2. SYSTEM TYPE HEATING SYSTEM MULTIPLIERS Attic Radiant Barrier HCM . 98 Multizone HCM .90 Natural AFUE .60 -.64 .65 -.69 .70 -.74 ,75•.79 .80 -.84 .85•.89 -UD HCM 41 .38 ,35 333 Celina .90 Other Fuels HCM .63 .58 .54 .51 .31 .48 .29 .27 .45 .42 Where more than one credit is claimed, multiply HCM's together. Enter product on page 4. AFUE means Annual Fuel Utilization Efficiency. 9P INFILTRATION REDUCTION PRACTICE COMPLIANCE CHECKLIST (See Section 903.2(1)) COMPONENTS PRACTICE •1 REQUIREMENTS FOR EACH PRACTICE COMPLY WITH ALL INFILTRATION PRESCRIPTIVES ON TABLE 9A. CHECK , PRACTICE •2 COMPLY WITH PRACTICE •1 AND THE FOLLOWING: Exterior Walls and Floors Too plate penetrations sealed, Infiltration barrier installed. Sole Dlatelfloor ioint caulked or sealed. _Exterior Walls & Ceilings Penetrations. joints and cracks on interior surface caulked. sealedr gasketed. Ductwork Ductwork in unconditioned space must be sealed. it DleCes EQuioped with ()aside combustion air. doors. and flue dampers. Equipped with dampers. Combustion devices see 903.2(1). Exhaust FanS PRACTICE •3 COMPLY WITH PRACTICES '1 AND '2 AND THE FOLLOWING: Infiltration barrier installed, . Too plate Denel ipn gamed or ioints & cracks on interior walls caulked. sealedpr gasketed. Celina Interior Walls Recessed Lights Ductwork Sealjrom conditioned space & insulated from ventilated attic spaces. All ductwork totaled in conditioned sDaca• Be in unconditioned space (except direct vent). Draw air from unconditioned space. Exhaust by- products outdoors Stoves see 903 2(11 Combustion Appliances 91 HEATING SYSTEM MULTIPLIERS (HSM) 9.1 HEATING CREDIT MULTIPLIERS (HCM) 9K COOLING SYSTEM MULTIPLIERS (CSM) 9L COOLING CREDIT MULTIPLIERS (CCM) 9M HOT WATER MULTIPLIERS (HWM) 2 Water heaters must comply with prescriptive measures of Table 9A. EF means Energy Factor. 184 1 1329 MEM Electric Resistance Natural Gae Other Fuels P 1495 12 9N HOT WATER CREDIT MULTIPLIERS (HWCM) CLIMATE ZON Revised 1/87 24 _1.x'1 -- N 18 g -32 -9 4.2 /7.5 . - 5. '124.34 , -31 24. - S a _ /'Ii _ . S 4 _500 _ E &ST t kLL Goo a /\Q EAt s 21.11 5 f 44 . S )( 49 r k at 6,f 4( x q 3V7 aiami cfhores91llage F L OR ID A PLANNING BOARD AGENDA OF tip' *b, ),9 ITEM NO. 3 Name of Owner /Applicant th•A• «4.0 Phone No.1►_Qtf Address of Property, and /or Legal Description Ott 1'16: T li`r. Nature of Request 1000VON- 70 4 iPCt gott "n"6 . WAWA Present Zoning ik° 11 Area of Present Building Area with Proposed Addition Parking Spaces Provided Parking Spaces Required with Addition Setbacks as per Code Setbacks Provided Variances /Exceptions /Zoning Change ottc NM. 1 f?ttoVAte o- ."$t$ t.O'r WAos NIA coitrit40,41* T '0%1' t,SCAY •utt -PING tit ttAfittitni, N & M isultip 1 tm Council Action Required Date of Applicant Notification " Planning Board Action" R/. tA/ ' Council Action Director of Building and Zoning COO V R NcEIQ April 13, 1990 Miami Shores Village Miami Shores Planning & Zoning Board Miami Shores, FL 33138 Dear Members of the Board: [IMSMAMCIE ROMMOE, CO.m.pOO mzTnOO m I am the owner of a new residence located at 511 N4gil 294 Street in Miami Shores. I have first completed construction at this location. I have a small concrete building located on the rear North West corner of my lot. I wish to retain this building as a storage facility. The building poses no problem to the neighbors or neighborhood. There are several buildings at the rear of the lots on the block this residence is in. I respectfully request your permission to retain this building and to approve a variance according to Article VII, Section 702 of the Shores Code of Ordinances. As a condition of your approval, I agree to re -roof the building with the same tile roof as the residence, and to repaint the building the same color as the new residence. Thank you for your consideration in this matter. Very tr ly yours, 6e A.A. Grillo e'4// /ri, kF oft AL 2222 Ponce de Leon Blvd., Suite 350 Coral Gables, Florida 33134 ^ Phone: (305) 442 -0744 / Fax: 442 -9848 r MIAMI SHORES VILLAGE A regular meeting of the Miami Shores Village Planning & Zoning Board was held on October 23, 1986, at the Miami Shores Village Hall. The meeting was called to order by Chairman Stobs at 7:30 P.M., with the following Members present: J. Robert Stobs, II, Chairman Patrick L. Duffy Thomas Laubenthal Larry T. McClure Robert J. Rossi Also present: Frank LuBien, Director of Building & Zoning 1. MINUTES PLANNING & ZONING BOARD MEETING OCTOBER 23, 1986 There were two corrections to the minutes of the September 25th meeting. In the first paragraph Thomas Laubenthal made the motion to approve the minutes of Sept. 11, 1986. In the last paragraph Mr. Laubenthal recommend- ed Mr. Rossi moved to approve the minutes of September 25, 1986, as corrected, seconded by Mr. Laubenthal and passed unanimously. 2. REQUEST FOR APPROVAL OF DIVISION OF LAND WITHOUT PLAT ROBERT A. KOPPEN Lots 13, 14, & 15 Blk 55, Miami Shores Sec 2 Mr. LuBien presented a set of plans for the Board's review, he described and explained the changes to be made. A portion of the existing structure will have to be removed to abide by (within 3/10 of a ft.) the set back requirement. Christine M. Moreno, Atty. was present to represent Robert Koppen, and to answer questions. She stated that the entire one story addition will be removed, and the new windows and wall will be in place. Discussion followed concerning the legality of the property line, any interior alterations to the house, the purpose of the one story CBS accessory building in the rear. The changes, subject to meeting the same harmonious architectural standards of Miami Shores and the existing house will be upheld. Mr. Laubenthal moved to approve the request for division of land without plat as submitted, subject to harmony standards being upheld. Motion was seconded by Mr. Rossi. Mr. McClure requested that the motion be more clearly defined. Mr. Laubenthal then restated the motion: To accept the division of land without plat into two 75' wide lots, including the commitment to remove the single story addition as well as the patio, allowing the house line to retreat to within .3' encroachment of the 10' side yard set back, and parallel to the existing structure. Further that the CBS single story accessory structure on the otherwise vacant second lot be allowed to remain at this time. The motion carried unanimously. Ms. Morino was advised that this request will be considered by Council at their meeting on November 4th. SURVEYING, INC. 25.00' LOT 0-. Z 25.00' 14 ,0.0 T.3' • /0.0 21 • ' r-- 22.2' 10.1' 3701tir C..& 7.5• LOW FUR C.P. wOJr DRIVE 8' ASP.. ALLEY 75.QQ' 14.7' C.B.S. _SHED a t • /4.7' # 51/ Id 411 9 r GQNC, s -a* -' ' • J DDRIV N. E. g4th 75' R/W LOT 15 CO v. GoNC. • 9 0.5' C.B.S. WALL Q• • 5' CONC WALK STREET ,EDGE PAVEMEN CERTIFICATE OF OCCUPANCY MIAMI SHORES VILLAGE, FLORIDA BUILDING DIVISION N° 1974 �� �e t ��o Miami Shores Village, Florida, Owner, Age t or Tenant of Bui d' g Y 1b1 4 J 't4C Lot Y6 Block Subdivision M Lk \ ,6 S C Street Address . 61 `_ r 67 �/ �•� Approved � us � e by occupancy °�1�o1` 1 1''[ � ) G Ci- Remarks %' [� This Certificate of Occupancy is issued to the above namec for building at above named location only upon the express provision that the applicant will abide by and comply with all conditions of Ordinances Nos. 92, 93, 94 and 97, known as the Zoning, Electrical, Plumbing and Building Ordinances of Miami Shores Village pertaining to the erection, construction, alteration or remodeling of build s r r str ytures. buildin BUILDING DIVISION