ROOFING3731 SW. 47th Avenue, Suite #401, Davie, Florida 33314 Ph: (954) 584 -4475 Fax: (954) 584 -3887
W • i ' «• -
n
•
- . • o.., x. .
1 ,
NG
• SOl • ASB
Client: Arguelles & Arguelles
9455 S. W. 78th Street
Miami, Florida 33173
Att. Mr. Daniel Arguelles
Test Procedure
TOS •
• ASP
CERTIFICATE OF TEST AND ANALYSIS
Date: 5/4/99
Lab #: ABM -86
Tech. R. Binns
Project: 1298 N.E. 95th Street
Miami Shores, Florida
Permit #: 44008
Tile /Manufacturer: Artezanos, Barrel
Test Required: South Florida Building Code Protocol PA 106 -95
Project Description
Approximately 41 squares of roof tile had beemn installed on the pitched roof
areas of the above listed structure.
Tile Description
The tiles were a mortar set, hand -made, clay, barrel, roof tile manufactured
by Artezanos Ltd., product control approval # 98- 0408.02.
The roof was first examined for loose tile by hand lifting one hundred forty
one (141) field tiles and one hundred thirty one (131) corner and perimeter
tiles. Forty eight (48) single tiles, were randomly selected and tested.
Twenty eight (28) tests were conducted in the field area, ten (10) in the
perimeter area, and ten (10) in the corner areas. The single tiles were
subjected to a concentrated uplift force measured with a manually operated,
Chatillon mechanical dial push /pull gauge, series DPPH. The gauge was
connected to a steel "L" shaped angle that was inserted under the nose of the
tile and gradually pulled upward until reaching the required test pressure of
35 lbs. +/- 5 lbs.
As the load was applied, observations for failure of the component and the
attachment, if any, were recorded. Tests were performed in respective order
as illustrated on the attached sketch.
..ALL STATE ENGINEERING & TESTING CONSULTANTS, INC.
Client: Arguelles & Arguelles
Project: 1298 N.E. 95th Street
Miami Shores, Florida
Permit #: 44008
Completion Date: > 30 days as per client
Required Testing Force: 35.0 ± 5 lbf.
Date: 5/4/99
Tech. R. Binns
Lab #: ABM -86
Comments: The above listed test meets the South Florida Building Code,
Protocol PA 106 -95 static uplift test criteria. The Protocol PA 106 -95 test
reported in report No. ABM -86 has been performed in full accordance to the
requirements of Dade County, with no deviations.
Rahimuddin Rahimi, P.E.
Reg. State of Florida # 51484
Field
Field
Field
Perimeter
Corner
1.
pass
19.
pass
1.
pass
1.
pass
2.
pass
20.
pass
2.
pass
2.
pass
3.
pass
21.
pass
3.
pass
3.
pass
4.
pass
22.
pass
4.
pass
4.
pass
5.
pass
22.
pass
5.
pass
5.
pass
6.
pass
23.
pass
6.
pass
6.
pass
7.
pass
24.
pass
7.
pass
7.
pass
8.
pass
25.
pass
8.
pass
8.
pass
9.
pass
26.
pass
9.
pass
9.
pass
10.
pass
27.
pass
10.
pass
10.
pass
11.
pass
28.
pass
12.
pass
13.
pass
14.
pass
15.
pass
16.
pass
17.
pass
18.
pass
..ALL STATE ENGINEERING & TESTING CONSULTANTS, INC.
Client: Arguelles & Arguelles
Project: 1298 N.E. 95th Street
Miami Shores, Florida
Permit #: 44008
Completion Date: > 30 days as per client
Required Testing Force: 35.0 ± 5 lbf.
Date: 5/4/99
Tech. R. Binns
Lab #: ABM -86
Comments: The above listed test meets the South Florida Building Code,
Protocol PA 106 -95 static uplift test criteria. The Protocol PA 106 -95 test
reported in report No. ABM -86 has been performed in full accordance to the
requirements of Dade County, with no deviations.
Rahimuddin Rahimi, P.E.
Reg. State of Florida # 51484
, 'ALL STATE ENGINEERING & TESTING CONSULTANTS, INC.
Client: Arguelles & Arguelles Date: 5/4/99
Project: 1298 N.E. 95th Street
Miami Shores, Florida
Permit #: 44008
Tech. R. Binns
Lab #: ABM -86
" PERMIT APPLICATION FOR MIAMI SHORES VILLAGE
Date 12 Job Address 1 L T6 15' 5 ' Tax Folio
Legal Description Historically Designated: Yes No
t i CO?
Owner/Lessee / Tenant 2 e ley P 4n �12't !14 44 7h ✓ I
Owner's Address 23S j i iP - Phone
Master Permit #
Contracting Co. A'0. ((11 AvLk I ' Alt (UL 1(L Address 94-C S Sic.), 181-A
Qualifier Ag., u. l/t,. t (L') ss# - Phone 51s - 4 f '�-
State # Municipal # Competency # Inc. 7/ — 6
Architect/Engineer Address
Bonding Company Address
Mortgagor Address
Permit Type (circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFING PAVING FENCE SIGN
WORK DESCRIPTION 30 ('O las , c A A9')' 074 Jl2
C A- 0- 0\29 - nai, 0 Safi c - 2j camm C66 r` -1-14-2v 51 ' 544
v
Square Ft. l) Estimated Cost (value) X5 60 eup,
a
WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING,
CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.)
Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I
certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate
permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK.
7Y'V 6)
owner and/or
O R'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable
laws gul= g construction and zoning. Furthermore, I authorize the above -named contractor to do the work stated.
Signpre • SC ndo President Date
/ • f //
o tary as to Own' : • • ( • • • • 'resi • ent Date
My Commission Exp es: OFG� TA ,
NOTARY PUBLICSI'ATE OF FLOC
COMMISSION ION NO. CC714103
MY COMMISSION FXP. MAR.1
FEES: PERMIT / / RADON
Signature ontractor or
wner- Builder
ctor
ary as to ontr
My Commission xpires:
NOTARY SEAL
GLADYS J VILLAR
NCIFARY PUBLIC STATE OF FLORIDA
COMMISSION NO. CC714103
!Y COMMISSION EXP. MAR. 1
i z -3 i.98
"bate
NO-)61C 7 tl
/— -
ate
C.C.F. /6 NOTARY S- TOTAL DUE Z i 3
360 0300
APPROVED:
Zoning Buildin Electrical
Mechanical Plumbing Engineering
NOTICE OF COMMENCEMENT
PERMIT NO. TAX FOLIO NO.
STATE OF FLORIDA:
, OUNTY OF DADE: 99x00 1343 1999 JAN 04 14:52
1'HE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with
:Maple(' 713, Florida Statutes, the following information is provided in this Notice of Commencement.
Legal description of properly and street address: I Z9'43 k-u-
?. Description of improvement:
3. Owner(s) name and address:
L- L-5 -- f \10fi.'f fi„ f
, nterest in property: OW �Lfl
Vame and address of tee simple titleholder:
4. Contractor's name and address: �v� -1 ny(.e vtas 7 ¢� f )t✓ . • ?& ��
,- 414 it , r Lrtt td
5. Surery:(Payment bond required by owner from contractor, if any)
Vame and address:
4mount of bond $
3. Lender's name and address:
7. Persons within the State of Florida designated by Owner upon whom notices or other documents may be served as provided
)y Section 713.13(1)(a)7., Fiorida Statutes.
Vame and address:
3. In addition to himself, Owner designates the following person(s) to receive a copy of the Lienor's Notice as provided in
Section 713.13(1)(b), Florida Statutes.
Vame and address: rJ J b>
3. Expiration date of this Notice oi_Commenceme (the xoiration date -is_1 year from the date of recording unless a
jifferent date is pecifiedy
Signature of Oweer
Print Owners Name
Sworn to and subscr
Votary Public
in. Notary's Name
vfy Commission expires:
LE E' A/DR%7f U!° ,j/3i—.21— 97 —5 4 / Pre p ared by: � ► 4 � aa.vz-L�-. J
d before me this 9Y day of / 19 Y p .
w
_ J
GLADYS J V1LLAR /
NOTARY PUBUC STATEOF>mR1DA
Crn Amisstnnt NO. CC:714103
STATE OF FLORIDA, COUNTY OF DADE
i HERE + V CERTIFY That this Is a tqu9fcopy of fho
origin !!Mod in fhts office on
MY COMM SSION EXP. MAR 1,2002
• A 0 i9
Ol%Iclal Seal.
of c . d Coun fy Courts
O.C.
Address: 1 44 - S S ./1//.
fLA f d4A I / / -r� � t' 1>
Appendix "E"
UNIFORM ROOFING PERMIT APPLICATION
PROCESS No.
Contractor's Name: Aft .61/_L C�\ � 11 6 10 Job Address: / 2 9 S M€ a 9 S ' .S t
ROOF CATEGORY �,�
❑ (Low Slope Application) ❑ (Nail -On Tile) LI (Mortar- Adhesive Set Tile)
❑ (Asphalt/Fiberglass Shingles) ❑ ( Metal Roofs \Wood Shingles & Shakes) ❑ (Other)
ROOF TYPE
❑ New Roof E J Re- roofing ❑ Recovering ❑ Repair ❑ Maintenance
Flat Roof Area (ft Sloped Roof Area (ft 32360 Total (ft 38 O 0 Master Permit No.
Exposure category (per ASCE 7 -88): Building Classification category (per ASCE 7 -88 table 1):
Ft.
Ft.
V
A
Deck type:
ATTACHMENT
Fastener Type:
Field:
SPACING
Perimeter: Corner:
DETAIL 1 & 2
ROOF HEIGHT AND SYSTEM DETAILS
(Draw details as needed)
r
r
r
r
r
ROOF PLAN
i 9 L 1 d° J�
/` —A-6 —Y
123.01 -78 9/96
Page -1
Appendix "E"
UNIFORM ROOFING PERMIT APPLICATION
PROCESS No.
Ridge Ventilation?
MEAN HEIGHT
Deck type:
Underlayment:
Insulation:
12"
ROOF SLOPE
D ET A I L 3
SLOPED SYSTEM DESCRIPTION
A V
Fastener type & spacing:
Cap Sheet:
Roof - overing:
s
Drip edge:
s
ATTACHMENTS REQUIRED
1) Fire Directory Listing Page
2) Dade County Product Control
Notice of Acceptance -Cover Sheet
a) Specific System Description
b) Specific System Limitation
c) General Limitations
d) Applicable Detail Drawings
3) Municipal Permit Application
4) Other Component Approvals
(Pmaxl: x X (Aerodynamic Multiplier):
X a, (Aerodynamic Multiplier):
A TILE CALCULATIONS
) --
(Pmax2: X a, (Aerodynamic Multiplier): ) - = M PCA:
(Pmax3:
M
= M PCA:
= M
PCA:
Page -2
AO'
'
inmaimmosiono
I IMMETtl
111111111111111111111 • w
• ...• ,
z ,..-----\
..-.
2 0 ..
...,.
i • , ".......____„...
-
..
,
.
...
: ..i..
. ' ../
AO'
'
inmaimmosiono
I IMMETtl
111111111111111111111 • w
mErRoD METROPOLITAN DADE COUNTY, FLORIDA
METRO -DADE FLAGLER BUILDING
BUILDING CODE COMPLIANCE OFFICE
METRO -DADE FLAGLER BUILDING
140 WEST FLAGLER STREET, SUITE 1603
MIAMI, FLORIDA 33130 -1563
PRODUCT CONTROL NOTICE OF ACCEPTANCE (305) 375 -2901
Artesanos, Ltda.
FAX (305) 375 - 2908
Avenia 0 No. 8A - PRODUCT CONTROL DIVISION
El Salado, Colombia (305) 375 -2902
FAX (305) 372 -6339
Your application for Product Approval of:
Artesanos, Ltda., Mortar Set, Clay "2 Piece Handmade Tapered Mission Barred Tile" Roofing
Tile,
under Chapter 8 of the Miami -Dade County Code governing the use of Alternate Materials and Types
of Construction, and completely described in the plans, specifications and calculations as submitted by:
Testwell Craig Laboratories & Consultants, Inc.
has been recommended for acceptance by the Building Code Compliance Office to be used in Dade
County, Florida under the specific conditions set forth on pages 2 -9 and the standard conditions on
page 10.
This approval shall not be valid after the expiration date stated below. The Building Code Compliance
Office reserves the right to secure this product or material at any time from a jobsite or manufacturer's
plant for quality control testing. If this product or material fails to perform in the approved manner, the
Building Code Compliance Office may revoke, modify, or suspend the use of such product or material
immediately. The Building Code Compliance Office reserves the right to revoke this approval, if it is
determined by the Building Code Compliance Office that this product or material fails to meet the
requirements of the South Florida Building Code.
The expense of such testing will be incurred by the manufacturer.
ACCEPTANCE NO.: 98- 0408.02 Renews: 95- 0317.11
EXPIRES: 05/14/01
Internet mall address: postmaster @buildingcodeonline.com
aul Rodri:uez
Product Control Supervisor
THIS IS THE COVERSHEET, SEE ADDITIONAL PAGES FOR SPECIFIC AND GENERAL
CONDITIONS
BUILDING CODE COMMITTEE
This application for Product Approval has been reviewed by the Miami -Dade County Building Code
Compliance Office and approved by the Building Code Committee to be used in Dade County, Florida
under the conditions set forth above.
Charles Danger, P.E.
Director
Building Code Compliance Dept.
APPROVED: 05/14/98 1 Miami -Dade County
Homepage: http : / /www.buildingcodeonline.com
ARTESANOS, LTDA. Product Control No.: 98- 0402.02
Applicant: ,
Artezanos, Ltda. Product Control No.: 98 0408.02.
Avenia 0 No. 8A -22 Approval Date: May 14, 1998
El Salado, Colombia Expiration Date: May 14, 2001
Category: Prepared Roofing
Sub - Category: Tile
Type: Mortar Set/Uplift based
Sub -Type: Clay
PRODUCT CONTROL NOTICE OF ACCEPTANCE
ROOFING SYSTEM APPROVAL
Page 2 of 10
Fran Zuloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA.
TRADE NAMES OF PRODUCTS MANUFACTURED OR
LABELED BY APPLICANT
Product
2 Piecce Handmade
Tapered Mission
Barrel Tile
Trim Pieces
Dimensions
1 =17"
w = 7"
%" thick
1= varies
w = varies
varying thickness
Test Product
Specifications Description
ASTM C 1167 High profile, two piece, barrel, clay
roof tile. For direct deck mortar set
applications.
ASTM C 1167
Page 3 of 10
Product Control No.: 98- 0402.02
Accessory trim, clay roof pieces for
use at hips, rakes, ridges and valley
terminations.
Frank Zuloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA. Product Control No.: 98- 0402.02
Product
Roof Tile Mortar
( "TileTiteTM ")
TRADE NAMES OF PRODUCTS MANUFACTURED OTHERS
Dimensions
N/A
Test
Specifications
PA 123
Page 4 of 10
Product
Description
Prepared mortar
mix designed for
mortar set roof tile
applications.
Manufacturer
Bermuda Roof
Company, Inc. with
current PCA
ran Zuloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA. Product Control No.: 98- 0402.02
Test Aeencv
Testwell Craig Laboratories
& Consultants, Inc.
Testwell Craig Laboratories
& Consultants, Inc.
EVIDENCE SUBMITTED
Test Identifier
Lab #ABM -4
Lab #ABM -1
Page 5 of 10
Test Name/Report Date
Static Uplift Testing January 1995
PA 101 (Mortar Set)
Physical Properties
ASTM C 1167
November 1994
ran uloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA.
Deck Type:
Deck Description:
SYSTEM D:
Slope Range:
Underlayment:
Roofing Tile:
Comments:
SYSTEMS
Page 6 of 10
Product Control No.: 98- 0402.02
Wood, Non - insulated
New Construction 19/32 " or greater plywood or wood plank.
Mortar Set Application
2 ":12" to 7 ":12"
Note: System D is only acceptable in this slope range.
Install choice of Approved underlayment system, noted on Page 1 of Miami -
Dade County Protocol PA 120, In compliance with Secton 3.02 of PA 120. See
System Limitation #6.
Install tile in compliance with PA 120 using one of the Approved mortars
noted in this Approval. Mortar shall be applied in compliance with the mortar
manufacturer's Roofing Component Product Control Approval. The mortar
attachment shall provided sufficient attachment resistance expressed as a
moment to meet or exceed the required moment of resistance determined in
compliance with PA 115 or PA 127. The mortar attachment data is noted in
Table 2, attached.
1. For re -roof applications, 15 /32" plywood is an acceptable substrate
2. For mortar set applications, the first three courses of tile shall be nailed
with not less than one nail per tile. As an alternate, the first three courses
of tile shall be applied in mortar over a single layer of minimum 12 ga.
Wire mesh with square openings of not less than 3/8" which is
mechanically attached to the deck with not less than one roofing nail every
1 ft . For roof pitches from 6 ":12" to 7 ":12 ", every third tile of every
fifth course, beginning at the eighth course, shall be nailed with not less
than one nail per tile..
Frank Zuloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA. Product Control No.: 98- 0402.02
SYSTEM' LIMITATIONS
1. The standard minimum roof pitch for Artesanos, Ltda. "2 Piece Handmade Tappered Mission Barrel
Tile" shall comply with Dade County Application Standards PA 120, depending on the method of
installation.
2. For nail - on applications, fasteners for mechanical attachment of tiles shall have a head diameter
larger than that of the preformed holes in the tile.
3. System installation shall be in compliance with the system specifications outlined in this Product
Control Approval. The method of attachment utilized shall provide sufficient attachment resistance
to meet or exceed the required resistance determined in compliance with Dade County Protocol PA
115 or PA 127. Artesanos, Ltda. "2 Piece Handmade Tappered Mission Barrel Tile" profile has
been tested for static uplift performance, therefore, attachment calculations for installation in
compliance with PA 115 or PA 127 shall be done as a Uplift Based System'.
4. For mortar /adhesive set tile applications, a field static uplift test by a Dade County accredited
testing agency, in compliance with Dade County Protocol PA 106, shall be performed.
5. For tile applications, 30/90 hot mopped underlayment applications may be installed perpendicular
to the roof pitch unless stated otherwise by the underlayment material manufacturer's published
literature.
6 All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo for
identification in the field.
7. Applications for roofing permits shall include a completed Section II of the Uniform Building
Permit, a copy of Monier Lifetile's current specifications and details, a copy of this Product Control
Approval and a copy of the Product Control Approval of any Roofing Component used in the
proposed tile application. Reference shall be made to appropriate data for the required fire rating.
8. The applicant shall retain the services of a Dade County certified testing laboratory to maintain
quality control in compliance with the South Florida Building Code and related protocols. Samples
taken shall be in compliance with Dade County Protocol PA 112, Appendix 'A'.
Page 7 of 10
Frank Zuloaga, RRC
Roofing Product Control Examiner
Table 2: Minimum Characteristic Resistnce Load — F' (Ibf)
From PA 101 testing
TileProfile
Tile Profile
Tile Application
Attachment Resistance
2 Piece Handmade Tapered
Mission Barrel Tile
Mortar Set
1.42
78.90
Table 1: Average Weight (W) and Demensions (I x w )
From PA 101 Testing
TileProfile
Weight -W (Ibf)
Length-1 (ft)
Width -w (ft)
2 Piece Handmade
Tapered Mission Barrel
Tile
4.90
1.42
0.58
ARTESANOS, LTDA.
DATA FOR ATTACHMENT
CALCULATIONS
Product Control No.: 98- 0402.02
Page 8 of 10
Frank Zuloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA.
PROFILE DRAWINGS
ARTESANOS, LTDA. " 2 PIECE HANDMADE TAPERED MISSION BARREL TILE
3° L
The Tiles Shall be Identified by This Stamp
ARTEZANO'S WORLD CLASS
ARTEZANO'S INC.
(305) 595-9352
Made in El Salado, Colombia.
Page 9 of 10
18"
Product Control No.: 98- 0402.02
7 "
Fran Zuloaga, RRC
Roofing Product Control Examiner
ARTESANOS, LTDA.
Artesanos, Ltda.
Avenia 0 No. 8A -22
El Salado, Colombia
END OF THIS APPROVAL
Page 10 of 10
Product Control No.: 98- 0402.02
ACCEPTANCE NO.: 98- 0408.02
APPROVED : May 14, 1998
EXPIRES : May 14, 2001
NOTICE OF ACCEPTANCE STANDARD CONDITIONS
1. Renewal of this Acceptance (approval) shall be considered after a renewal application has been filed and the
original submitted documentation, including test supporting data, engineering documents, are no older than eight (8)
years.
2. Any and all approved products shall be permanently labeled with the manufacturer's name, city, state, and the
following statement: "Dade County Product Control Approved ", or as specifically stated in the specific conditions
of this Acceptance.
3. Renewals of Acceptance will not be considered if: a) There has been a change in the South Florida Building
Code affecting the evaluation of this product and the product is not in compliance with the code changes; b) The
product is no longer the same product (identical) as the one originally approved;c) If the Acceptance holder has not
complied with all the requirements of this acceptance, including the correct installation of the product; d) The
engineer who originally prepared, signed and sealed the required documentation initially submitted , is no longer
practicing the engineering profession.
4. Any revision or change in the materials, use, and/or manufacture of the product or process shall automatically
be cause for termination of this Acceptance, unless prior written approval has been requested (through the filing of a
revision application with appropriate fee) and granted by this office.
5. Any of the following shall also be grounds for removal of this Acceptance: a) Unsatisfactory performance of
this product or process; b) Misuse of this Acceptance as an endorsement of any product, for sales, advertising or any
other purposes.
6. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the expiration
date may be displayed in advertising literature. If any portion of the Notice of Acceptance is displayed, then it shall
be done in its entirety..
7. A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be
provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at all
times. The copies need not be resealed by the engineer..
8. Failure to comply with any section of this Acceptance shall be cause for termination and removal of
Acceptance.
9. This Acceptance contains pages 1, through 10 this last page.
Frank Zuloaga, RRC
Roofing Product Control Examiner
APPLICATION FOR BUILDING PERMIT
Application is hereby mode for the approval of the detailed statement ur me plans and specifications herewith submitted for the build •
ing or other structure herein described. This application Is made in compliance and conformity with the Building Ordinance of Miami
Shores Village, Florida. and nII provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and
regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved
plats and specifications must be kept at building during progress of the work.
r . Date..._..._ .._.__...__.. ,19.x/._
Owner's Name and Address G�iLI -o /� .... ...... ._ No........... ..... Street._..
Registered Architect and /or lyngincer........ l� ?...- ... sr,,• •,,... , ^,„„„. w-„
Name and address of licensed contractor . ... . / ._.•44' -6- _
Location and legal description of lot to be built on:
Lot / 4- - Block ri Subdivision.. /,'Z *r: ...�sP� � ..��!�SC�.tti:�.. X.- —
Ste N ' 4s �- 4° os?mf
Street an d Number where work is t o be done /a
_.. ... _.. .. ._.._ . .... _.._ . -� y ...
State work to be done and purpose of building (by floors). - a04-
..
and for no other purpose.
Addition Repairs No. of Stories / _
•
To constructed of
o f foundation Roof vering
Estimated Total cost of improvements $ • ...I Amount of Permit L. .1Ib
New Building �emodcling
' G : i t Ki nd o
Zone cubage required .Plan Cubage
Distance .to next nearest building Size of Building Lot f` .�. 2P >r
liaximum live load to be borne by each floor
I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may
be sent to
The undersigned applicant for this building permit dots hereby certify that he understands and accepts his obligations as an employer
of Labor under the 'Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement,
and has complied .eith the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him
in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such public notice
or notices as are required by the Act. The undersigned agrees to employ only such subcontractors, on work to be performed under this
pcnnit, as are licensed by Miami Shores Village.
Remarks (Signed) "4...
STATE OF FLORIDA,
COUNTY OF DADE. ss.
Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap-
peared -. — . --
and who, being by me first duly sworn, upon oath deposes and says that he is the.
of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts
therein by him stated ar e.
Permit No. Date (Oh ........_._._ Read, Sworn to and Subscribed before me.
Disapproved
(Signed)
Building Inspector
v
ate
Chainnan
Member
Member .. ...
Council Approved Date
NOTE: A charge of $1.00 will be made for
the P1. nnir.g Board.
A re- inspection fee of SI.00 will be charged
materials anti /or workmanship.
MIAMI SHORES VILLAGE
BUILDING INSPECTION DEPARTMENT
PLANNING BOARD DATE
to me well known,
Notary Public, State of Florida
My Commission Expires _..._......_ . — _
Member
Member
Member ...._ _.._.....
Disapproved Date
making corrections or changes to this application after approval has hero obtained from
when such re- inspection is made necessary by improper notice for inspection or faulty
APPLICATION FOR BUILDING PERMIT
Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build-
ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami
Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and
regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved
plans and specifications must be kept at building during progress of the work.
Date . anus ry L 1 , 19
Owner's Name and Address. __ Mr.. _. H..__B.._ _A tkIRa_4n _________.___ __. No 1298._. ___ street__ NE 95th Street
RegiRered Architect and /or E n g i n e e r
Name and address of licensed contractor_._Nys.tr8 .L�.9�5�___�_Q7'�? __. 230 5 -- -17th Avenue Miami, F la .
Location and legal description of lot to be built on:
Lot__ Block
Street and Number where work is to be done
State work to be done and purpose of building (by floc
_Remov_e___axi_s_ting .00ver_ing. _ ..
T_er_r_a__- _0_Qt ti .Le__._ L� _
New Building Remodeling
To be constructed of Kind of foundation__
Estimated Total cost of improvements $___&Q0..0_Q
Zone cubage required
Distance to next nearest building__
Maximum live load to be borne by each floor
STATE OF FLORIDA,
COUNTY OF DADE. ss.
peared
Disapproved D
(Signed)
Building Inspe or
MIAMI SHORES VILLAGE
BUILDING INSPECTION DEPARTMENT
Subdivision
L2.98 NE___95 th.__Street
floor __Reronfing.__par_t of_ roof deck.
a_pp 1, .y. 3Q# 2 e).t, 90# s la to and new
and for no other purpose.
Addition Repairs / �' No. of Stories /
Roof Covering./CIA °
Amount of Permit $_6_._00
plan Cubage_
Size of Building Lot
I hereby submit all the plans and specifications fot said building. All notices with reference to the building and its construction may
be sent to___._ Nye trand. L L.Qyd Corp_ -230 SW .17th- Avenue - Miami, Fla .
The undersigned applicant for this building permit doc hereby certify that he understands and accepts his obligations as an employer
of labor under the Florida Workmen s Compensation Act. being Section 5966, Compiled General Laws of Florida, Permanent Supplement,
and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him
in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such public notice
or notices as are required by the Act. The undersigned agrees to employ only suclYsebcontractors, on work to be performed under this
permit, as are licensed by Miami Shores Village.
Remarks ( Signed
Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap-
to me well known,
and who, being by me first duly sworn, upon oath deposes and says that he is the
of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts
therein by him stated are true.
Permit No /
1cs" (-4- .._ Date ___I ` (Y-7. . ___ Read, Sworn to and Subscribed before me.
Notary Public, State of Florida
My Commission Expires__
P ' ANNING BOARD__ __ . DATE
Chat'nnan - . Member
Member Member
Member _ Member . _._....
Council Approved . _Date Disapproved
643 -5200
Date
NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from
the Planning Board.
A re- inspection fee of $1.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty
materials and /or workmanship.
Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the building or other structure herein
described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida, and all provisions of the Laws of the
State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether
herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work.
APPLICATION FOR BUILDING PERMIT
Owner's Name and Address 7h ® r / 2 To n/
Permit No.
Disapproved
(Signed)
Z16,5
New Building Remodeling
MIAMI SHORES VILLAGE
BUILDING INSPECTION DEPARTMENT
Remarks (Signe
Date J
Date
PLANNING BOARD
No
Date
Registered Architect and/or Engineer
3 /6,
L / c '/v, / °Y / 2 ✓ ? a� r ;
Name and address of licensed contractor � 6.6 � .� 0 0 / � / 3 ; do/v
Location and legal description of lot to be built on:
Lot Block J Subdivision
Street and Number where work is to be done /12' 37e u
State work to be done and purpose of building (by floors), state exterior colors (submit samples) j7/ �c /� �
f r
and for no / other purpose.
Addition Repairs `' No. of Stories
To be constructed of Kind of foundation Roof Covering / /?J L
Estimated Total cost of improvements S ,,„S' � Amount of Permit S !a
Zone cubage required Plan Cubage
Distance to next nearest building Size of Building Lot
Maximum live load to be borne by each floor
I hereby submit all plans and specifications for said building. All notices with reference to the building and its construction may be sent to .C.JI'J 'f)l / S -
or/ivy / 971✓ / 29.S' 7 , "erg; P.479, 3,7/4
The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligatons as an employer of Labor under the Florida Workmen's
Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement. and has complied with the provisions thereof, and will require similar
compliance from all contractors or sub - contractors employed by him in the work to be performed under this permit: and will post or cause to be posted for inspection
on the site of the work such public notice or notices as are required by the Act. The undersigned agrees to employ only such subcontractors. on work to be performed
under this permit, as are licensed by Miami Shores Village.
STATE OF FLORIDA
COUNTY OF DADE. } ss.
Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally appeared
to me well known.
and who. being by me first duly sworn, upon oath deposes and says that he is the
of the above described construction, that he has carefully read the foregoing application. and that he did sign the same. and that all facts therein by him stated are true.
Read, Sworn to and Subscribed before me.
S - < 19?
Street / e: 7/ E
Notary Public, State of Florida
Building Inspector My Commission Expires
DATE
Chairman Member
Member Member
Member Member
Council Approved Date Disapproved Date
NOTE: A charge of $25.00 will be made for making corrections or changes to this application after approval has been obtained from the Planning Board.
A re- inspection fee of $25.00 will be charged when such re- inspection is made necessary by improper notice for inspection or faulty materials and/or workmanship.