585 NE 93 St (9)ROOF REPORTERS, INC. R044 eage&atf (561) 434 -7555 TAS 106 Roof Tile Uplift Test Report Test Date July 19, 2001 Project Address Jerry Moorehead 585 NE 93 St. Miami Shores, Fl Contractor Pioneer Roofing Permit Number 49249 Roof Pitch 3:12 Tile Installation Date 07/06/01 Adhesive Type Poly Foam Tile Type Santa Fe S All testing is in strict accordance with The Dade County version of The South Florida Building Code, Section 3401.10 and PA 106 -95. Each Test location was pulled using a Chatillon Force Gauge to a minimum of 35 lbs.. TEST SUMMARY Roof Area Total # of Tests # of Tests Passed %Passed Field & Ridge 25 25 100% Corner 10 10 100% Perimeter 11 11 100% TEST RESULTS: PASSED See Attached Sketch for Further Details Al Macc`agli, RRC #116 Dade County Certified Testing Agency # 99 -0615.04 3281 Lake Worth RoadJ Suite EO Lake WorthOFlorida 33461 Roof Consulting & Testing OVisual Surveys & Evaluations Roof System Design O Moisture Surveys 3:/ t :Synergy Labs,` I nc 9831 E Evergreen St FL =33157: :888 :348 :2430 UNIT UNDER : TEST: CHATILLON DFIS 100'DIGITAL- FORCE::GUAGE 25282 :.25282 :�SYN156. Mfr S/N: Cust S/N PROCEDURE NAME "CALIBRATED":BY NUMBER: :SUBMITTED •`BY Eliu Lego VERBAL -ROOF REPORTERS '3281 .LAKE .WORTH' ROAD LAKE WORTH FL CERTIFICATE NUMBER. 30445 :992524202 PERFORMED ON: NEXT CAL DUE:: : TEMPERATURE: HUMIDITY 14Jun2001 14Se•2001 22.0 °C +1- 1 DEG 38% -- : + l - • Synergy Labs,'inc certifies that; An above listed instrvmert •meetsor exceeds all specifications as in the ieferesiced procedure at the points tested ( unless otherwise noted). It has beers' cabbratcd' Measurement standarda" traceable to the Natrona Institute of Standards :and Technology (NIST), or to NIST accepted intrinsic standards of measurement,' or derived by the ratio type of self- calibration tec3umique&T his cahbratiort complies with ISO Guide 17025 and ANSI/NCSL Z5 40 -1- 1994.' Calibration procedures :::used providemeasnrement :uncertainty ratioa . of less than or equal to 4:1 of the specification of the unit under test,- with a coverage factor of 1m2 ai a "ccnf dense bvel of 95% unless otherwise noted. Ala . report not be reproduced, accept ui'fiill;'unless permission for :the publication of an .approved abstract Is •obtained it writing fsom Synergy • Lab; Inc: : REMARKS thisunit was found to be in tolerance at the time of" calibration. No adjustments were necessary. AMETEK WO-23 WEIGHT SET.:: ration 1 ecnniCian . 6 Jun 2001 • 6 Jun 2003 Standards Used Tra ce No REPORT -OF CALIBRATION for ': SERIAL NUMBER::. 25282 PRINTED ON: 14 Jun 2001 Synergy Labs assigned-ASSET NUMBER: • • 30445 Page { .of MIAMI SHORES VILLAGE 1 BUILDING INSPECTION DEPARTMENT • APPLICATION FOR BUILDING PERMIT Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build- ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved plans and specifications must be kept at building during progress of the work. Owner's Name and Address Harvey L. Carver Date November 29, 1950 ,19 No 585 ILL Street 93rd Street Registered Architect and /or Engineer Name and address of licensed contractor Lang_Roofin$ & Tile Co., 430 N.W. 79th Street Location and legal description of lot to be built on: Lot Block Subdivision_ _____________ 585 N.E. 93rd Street Street and Number where work is to be done State work to be done and purpose of building (by floors). 1-30 lb, felt, 1 lb. slate, White barrel tile copper flashinge. and for no other purpose. New Building X Remodeling Addition Repairs No. of Stories To be constructed of Kind of foundation_____ Roof Covering Estimated Total cost of improvements $ 700,00 Amount of Permit $ Zone cubage required plan Cubage Distance to next nearest building Size of Building Lot Maximum live load to be borne by each floor I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may be sent to The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement, and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such public notice or notices as are required by the Act. The undersigned agrees to employ only such subcontractors, on work to be performed under this permit, as are licensed by Miami Shores Village. LANG ROOFING & TILE CO. Remarks (Signed) By: STATE OF FLORIDA, COUNTY OF DADE. ss. Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap- peared to me well known, and who, being by me first duly sworn, upon oath deposes and says that he is the of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts therein by him stated are true. Permit No Date Read, Sworn to and Subscribed before me. Disapproved Date__ Notary Public, State of Florida (Signed) Building Inspector My Commission Expires PLANNING BOARD DATE Chairman Member Member Member Member Member Council Approved Date Disapproved Date NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from the Planning Board. A re- inspection fee of $1.00 will he charged when such re- inspection is made necessary by improper notice for inspection or faulty materials and /or workmanship. Legal Description Date cf -'0, Job Address 5W /F E 6?.3 Tax Folio D APPROVED: 'PERMIT APPLICATION FOR MIAMI SHORES VILLAGE Owner / Lessee / Tenant / »f 7 y /'mil oc d Master Permit # 5- /S/ Owner's Address 1 ! � /.— Phon ✓7 IO��b T AddressC st Contracting Co. Qualifier Air ef ss# Phone gos State44 0 Municipal # Competency # Ins.Co. Architect /Engineer N�'A Bonding Company /1/(il Si .�! r: •, o - ner and /or Condo President otaryr s to Owner and/ My Commission Expires: FL ,� C ��.,.., r h 6P - Y37- qq - o/ Zoning AUDE C. FRANKS, HI MY COMMISSION # CC 806735 EXPIRES: April 11, 2003 rs Address Address Mortgagor /�1b - Permit Type(circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFING PAVING FENCE SIGN /4 5 � ' h ,c,1 L �_ -��� ! —901 WORK DESCRIPTION •1 6'E Cal& Address eg tete -- Square Ft. /.43 /t • FeAl. Estimated Cost(value) WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT). Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, RO` ING and MECHANICAL WORK. OWNER'S AFFIDAVIT: I certify that all the foregoing informat be done in compliance with all pplicable laws regulating c authorize the above -named contr ctor to do the work s n7 • ** * * * t * * * * * FEES: PERMIT /g RADON C.C.F. jiff 4. u Si tur: o j vn r- D• t s 15 0 ctor or Own = :uilder ski AUDE C. FRANKS, 11 MY COMMISSION # CC 806735 Notary My C �}fn NOTARY Fire i Buildi 4 / l ' Electrical s cc n -� e and hat all work will c i F t rmore, I i • .L4/hi.irk/I ii to Contra ', Expires: . ** TOTAL DUE ?D0 Other Mechanical Plumbing Engineering 06/1.8/ 2001 09:51 19549232677 PIONEER ROOFING PAGE 01/01 NOTICE OF CO A RECORDED COPY MUST BE POSTED ON THE JOB SITE AT TIME OF FIRST INSPECTION PERMIT NO. TAX FOLIO NO. /(--- r 3 ,2O e z/T -(0 3o STATE OF FLORIDA: COUNTY OF DADE: 01 R 311 194 2001. JUN 15 11:20 THE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with Chapter 713, Florida Statutes, the following information is provided in this Notice of Commencement. 1. Legal description of property and street address: /// 107t.eS ~�S t/t ' 3 51- 3 2. Description of improvement: ( joke l 3. fawner s) name and address >°� /ci. �' �m >t? eRd ��-7j 11 73 /19• , Interest in property: Name and address of fee simple titleholder: FLORIDA, COUNTY OF DADE •p p ERTIFY that this 15 a true 4. Contractor's name and address: 5. Surety:(Payment bond re ired by owner from contractor, if 4119yE • Name and address: !J 1 NERE Amount of bond $ t igVe~ da�dornct: = �f 6. Lender's name and address: _ _ , MA J •,.'i���lc a y • ' °" �`; 7. Persons within the State of Florida designated by Owner upon whom notices or other documents may be served as provided by Section 713.13(1)(a)7., lorida Statutes, Name and address: N 8. In addition to-Mmself, Owner designates the following person(s) to receive a copy of the Lienor's Notice as provided in Section 713.13(1)(b), Flor tatutes. Name and address: 9. Expiration date of this Notice of Commencement: (the expiration date Is 1 year from the date of recording unless a different date Is specified ' re of Owner Notary Public Print Notary's Name My Commission Expires OevnMvt-- Sig print Owner's Name 1 14 6 6 0 2e7& 4 10 Sworn to and subscribed before me this day of , 20 FL. Dr. vx ' yie✓ 63o —437— 4q— o/ —p AUDE C. F=RANKS, III MY CAM ISSIO► : C 8087 EXPIRES; April 11, 2003 �, ElondadThru Navy Public Underwriters Prepared b� :ontractor's Name: 1) 1l 3 (Low Slope Application) 3 (Asphalt/Fiberglass Shingles) F ca.4 Appendix "E" UNIFORM ROOFING PERMIT APPLICATION PROCESS No. ROOF CATEGORY ❑ (Nail -On Tile) L T L Job Address: 7I ? 9\3 X adEr-Adhesive Set Tile) ❑ ( Metal Roofs\Wood Shingles & Shakes) ❑ (Other) ROOF TYPE ❑ New Roof ❑ Re roofing ❑ Recovering ❑ Repair ❑ Maintenance lat Roof Area (ft') Sloped Roof Area (ft') Total (ft') Master Permit No. ?xposure category (per ASCE 7 -88): Building Classification category (per ASCE 7 -88 table 1): 123.0 1.79 199 Ft. v A v Deck type: Al e Fastener Type: A TTACHMENt SPACING Field: Perimeter: Corner: DETAIL 1 & 2 ROOF HEIGHT AND SYSTEM DETAILS (Draw details as needed) Page -1 Rid e Ventilation? M CAN ItEICI(T Deck type: D E T A I L 3 Appendix "E" UNIFORM ROOFING PERMIT APPLICATION PROCESS No. SLOPED SYSTEM DESCRIPTION Underlarnent: I,uulaUon: 43 i 0/1 Fastener type & sparing: Cap Sheet: Roof Covering: /� TILE CALCULATIONS (Pmax1: 1 ( j x X (Aerodynamic Multiplier): ti? I ) - M = M �, PCA: 6/7 (Pmax2. "9t J x a. (Acrodynarnic Multiplier): Y1 ) - M Z = M Z 2' � PCA: (t% 1 1 (Pmax3: !(% x a (Acrod 1ieMultiplia): ()97 ) - M .OZ = MrS' ' 2 21 PCA: Page -2 Drip edge 4/4// ATTACHMENTS REQUIRED 1) Fire Directory Listing Page 2) Dade County Product Control Notice of Acceptance -Cover Sheet a) Specific System Description b) Specific System Limitation c) General Limitations . d) Applicable Detail Drawings 3) Municipal Permit Application 4) Other Component Approvals 06'/. ^6 /O1 • 08:17 FAX 5618320264 05/11/2001 14:46 3058880050 • MI'AMI•D' EAST COAST SUPPLY - SANTAFE TILE CORP PRODUCT CONTROL NOTICE OF ACCEPTANCE Santa Fe Tile Corporation 10302 N.W. South Rivet Drive, Bay #16 Medley ,FL 33178 Your application for Notice of Acceptance (t■IOA) of: Spanish "S" Clay Tile under Chapter 8 of the Code of M iami -Dade) County governing he use of Alternate Materials and Types of Construction, and completely described herciin, has been recommended for acceptance by the Miami -Dade County Building Code Compliance Office (BCCO) under the conditions specified herein. This NOA shall not be valid after the expiration date stated bel product or material at any time from a job ite or manufactur product or material fails to perform in the ipploved manner, use of such product or material immediately. BCCO resery e determined by BCCO that this product or !material fails to n Building Code, The expense of such testing will be incurred iby the manufactur ACCEPTANCE NO.: 00- 121106 EXPIRES: 02 /0 UZ006 I 6 Raul Rodriguez Chief Product Control Division THIS IS THE COVERSHEET, SEE ADDITIONAL PAG S FOR SPECIFIC AND GENERAL CONDITIONS BUILDING COPE krz PRODUCT REVIIEW COMMITTEE This application for Product Approval has ibeen reviewed byf the BCCO and approved by the Building Code and Product Review Committee to be`used in Miami-Da' e County, Florida under the conditions set forth above. a n. m /nl nOni 11s045000 t1pc200011cemptar acceptance cover pagedoc • lntrrnrr en.r.l srl.irrva• .rl.,,. u" )w. BCCO reserves the right to secure this 's plant for quality control testing. If this CCO may revoke, modify, or suspend the the right to revoke this approval, if it is eet the requirements of the South Florida MIAMI -DADE COUNTY, FLORIDA METRO -DADE FLAGLER BUILDING BUILDING CODE COMPLIANCE OFFICE METRO -DADE FLAGLER BUILDING 140 WEST FLAGLER STRECT, SUITE 1603 N1IAi\tI. FLORIDA 33130 -1563 (305) 375 -2901 FAX (305) 375.2908 . s - " "- CONTRACTOR LICENSING SECTION (305) 375.2327 FAX (305)375 CONTRACTOR t',N FOR CEMENT DIVISION (905) 375 - 2966 FAX (305)375-290a PROW-ICI' CONTROL DIVISION (305) 375.2902 1A.1 (305) 372 -6334 Francisco 3, Quintana, R.A. Director Miami -Dade County 1001 PAGE 01 r.rr 08/26/01 08:18 FAX 5618320264 05/11/2801 14:46 3059880050 SANTAFE TILE CORPORATION ROOFING ASSEMBLY APPROVAL Category: Roofing Sub- Categorv: 07320 Ro Tiles Materials Clay RooflTiles Deck Type: Wood 1 1. SCOPE This renews a roofing system using Santa Fe "Santafe ' Santafe Tile Corporation described lin Section 2 of this comply with the South Florida Building Code, 1994 Edi locations where the design pressur requirements, as det does not exceed the design pressor , obtain by cal using the values listed in herein. TIe attachment calcul system. 2. PRODUCT DESCRIPTION Manufactured by Applicant Santafe `S' Clay Roof Tile Trim Pieces Test Dimensions Specifications I-= 18" w = 11.5" %" thick I = varies w = varies varying thickness EAST COAST SUPPLY . SANTAFE TILE CORP PA 112 PA 112 2.1 COMPONENTS OR PRODUCTS MANUFACT est Product Dimensions Spec ficationg Tile Screws 8 x 2-Y2" long PI4 114 0.130" shank dia_ Ap . endix E 0.178 flute dia. 3. LIMITATIONS 3.1 Fire classification is not par of this acceptance. 3.2 For mortar or adhesive set ile applications, a st accordance with RAS 106. 3.3 Applicant shall retain the ervices of a Mia perform quarterly test in accordance with PA submitted to the Building Code Compliance Of 2 On equ mo Ac hip Ma S CCEPTANCE No. 00 1212.06 Approval Date: February 1, 2001 Expiration Date: February 1, 2006 " clay roofing tile, manufactured by ice of Acceptance, designed to Ion For Miami -Dade County. For rrnined by applicable building code, ulations in compliance with RAS 127 ions shall be done as a moment based Prod uct Description piece high profile clay roof tile ped with two nail holes. For nail -on, ar set and adhesive set applications. ssory trim. clay roof pieces for use at rakes, ridges and valley terminations. ufnetured for each tile profile. RED BY OTHERS Product escri lion inless Steel Manufacturer generic e1002 PAGE 02 is field uplift test shall be performed in - Dade County Certified Laboratory to 12 a, ..•..' _� ::. - i...,�...,,,::.•_ hall be oaga, RRC oofing Product Control Examiner Table 3: Attachment Resltance Expresse as a Moment- Mf (ft-lbf) Fbr Nall -On Syste Tile Profile Tile Application Two Nails 21.8 One Screw 29.15' T Screws 38.28 One Screw w/ Clip 57.31 Two Screws w/ Clip 57.50 Santafe S Direct Deck Battens . Mortar Set Battens 23.6 j Adhesive Set , 61.77 1 . Approved screws as noted 'Product manufactured by others' 1 Direct Deck Table 2: Restorin• Table 4: Attachment for Resistance Expresse Mortar or Adhesive Set Tile Application as a ystems Moment - M, (ft -lbf) Attachment Resistance 4 ":12" Tile Profile 6 ":12" Santafe 'S' or Direct Deck Battens . Mortar Set Battens 23.6 j Adhesive Set , �___ 61.9 Table 2: Restorin• Moments due to 1i. ravi - M. ft-lb Tile Profile 2 3 ":12" 4 ":12" ":12" i 6 ":12" 7 ":12" greater Battens or Direct Deck Battens Direct beck Battens Direct! Deck Battens Direct Deck B. is ns 1 Direct Deck Battens Direct Deck Santafe 'S' 5.93 5.90 5.85 5.82 5.73 5.69 5. j6 5.53 5.32. 5.29 5.03 N/A Table 1: Ae od namic Multi • I ers— I. ft Tile Profile I I. (ft ) Batten A - - licat • X. (ft ) Direct Deck Santafe 'S' 0274 1 0.297 . 06/16/01. 08:18 FAX 5618320264 EAST COAST SUPPLY - 95/11/2001 14:46 3058880956 SANTAFE TILE CORPORATION SANTAFE TILE CORP CCEPTANCE No. : 00 1212.06 3.5 30/90 hot mopped underlayment applications ,-y be installed perpendicular to the roof slope unless stated otherwise by the underla ent material manufacturers published literature. 3.6 This acceptance is for world dcck applications. Minimum deck requirements shall be in compliance with applicable building code. 4. INSTALLATION 4.1.1 Santafe 'S' azid its components shall be installed strict compliance with Miami Dade County Roofing Applicatiol Standard RAS 118 S 119, and RAS 120, 4.1.2 Data For Attachment Calculations 0 003 PAGE 63 3 rank Zuloaga, RRC RooFng Product Control Examiner 06/26/01 08:19 FAX 5618320264 05/11/2001 14:46 3058880050 • SANTAFE TILE CORPORATION EAST COAST SUPPLY 5. LABELING 5.1 All tiles shall bear the imprint or identifiable m king of the manufacturer's name or logo, or following statement: "Miami -Dade County Pr duct Control Approved ". 6. BOLDING PERMIT REQUIRE 6.1 Application for building petmit shall be accomp 6.1.1 This Notice of Acceptance. 6.1.2 Any other documents required by the Buildi order to properly evalute the installation of PROFILE DRAWIN SANTA,)F•)~ " S" CLAY SANTAFE TILE COPP R ACCEPTANCE No. : 00- 1212.06 ed by copies of the following: 1004 PACE 04 g Official or applicable Building Code in system. OOF TILE Frank Zuloaga, RRC Roofing Product Control Examiner 06/26/01 '08:19 FAX 5618320264 05/11/2001 14:46 3058880050 EAST COAST SUPPLY . SANTAFE TILE CARP SANTAFE T11 CORPORATION NOTICE OF ,ACC . PTANC • STANDA D CONDI 1 Renewal of this Acceptance (approval) s21a11 be considered after original submitted documentation, lnclud test supporting da eight (8) years. 2 Any and all approved products shall be p labeled wi the following statement: "Miami -Dade dCaunty Product Control specific conditions of this Acceptance. 5 ACCEPTANCE No.: 00 -12 ONS repcwal application has been filed and thc engineering documents, arc no older than the manufacturer's name, city, stale, and pproved ", or as specifically stated in the 3 Renewals of Acceptance will not be consklered if a) There has been a change in the Snug Florida Building Co and the product is not in compliant with the code changes b) The product is no longer the same product (identical) as c) If the Acceptance holder has not coittplied with all the req correct installation of the product; d) The engineer who originally prepar signed and sealed submitted, is no longer practicing the engineering profes5i 4 Any revision or change in the materials, fuse, and/or manufactur automatically be cause for termination oflthis Acceptance, un (through the filing of a revision application with appropriate fee 5 Any of the following shall also be grounds for removal of this A a) Unsatisfactory performance of thii product or process; b) Misuse of this Acceptance as an endorsement of any pro purposes. ■ 6 The Notice of Acceptance number precedd by the words Miami Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If ann portion of the Notice of Acceptance is displayed, then it shall be dope in its entitety. affecting the evaluation of this product one originally approved; ernems of this acceptance, including the required documentation initially of the product or process shall prior written approval has been requested and granted by this office. eptancc: ct, for sales, advertising or any other 7 A Copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be provided to the user by the manufacturer or its distributors and s l( be availablo for inspection at Use job site at all times. The copies need not ba resealed by thc engin 8 Failure to comply with any section of this Acceptance shall be sv for termination and removal of Acceptance. 9 This Acceptance contains pages 1 througft 5 END bF THIS ACCEPTA CE 005 PAGE 05 2.06 Frank Zuloaga, RRC Roofing Product Control Examiner ma y./ v1 Z £S 4. . Y► MIAMI•D+ADE £41. JJY J/Q 104L rut.xruitm rnuuuui�, ttvt,. PRODUCT CONTROL NOTICE OF ACCEPTANCE Polyfo:lm Products, Inc. 2400 Spring- Stucbncr Road Spring ,TX 77383 - 1132 Your application for Notice of Acceptance (NOA) of: Two Component Polyurcthcne Foam Tile Adhesive under Chapter 8 of the Code of Miami -Dade County governing the use of: \lternate Materials and Types of Construction. and completely described herein, has been recommended for acceptance by the Miami -Dade County Building Code Compliance Office (BCCO) under the conditions specified herein. This NOA shall not be valid after the expiration date stated below. BCCO reserves the right to secure this product or material at any time from a jobsite or manufacturer's plant for duality control testing. If this product or material fails to perform in the approved manner, BCCO may revoke, modify, or suspend the use or such product or material immediately. BCCO reserves the right to revoke this approval, it' it is determined by I3CCO that this product or material fails to meet the requirements of the South Florida Building Code. The expense of such testing will be incurred by the manufacturer. ACCEPTANCE, NO.: 01- 0404.01 EXPIRES: 02/04/2003 APPROVED: 05/10/2001 MIAMI -DADE COUNTY. FLORIDA METRO -DADE FLAGLER BUILDING BUILDING CODE COMPLIANCE OFFICE Mr.TIt(- DA DI. FI.Ari1.1:It I1l1ILDING 140 WESTILAGLER STREI:r. SUI•rt: 1603 nn,ntin. 19.OI(l1)A 33130 -1563 (305) 375.2901 FAX (305) 375 -290 c (0Ni'R. ('1'OK I.I( :E :NSIN(. til :trio (305) 3 75 -2327 VAX (305)375 -255x (:(n \TIt.■:I'rnt ENFORCEMENT DIVISION (305) 375.2'16(, FAX (305)375-290X r(touucr CONTILOI. I)('ISioN (305) 375.2`102 FAX (305) 372.6339 I:au1 Rodriguez Chic!' Product Control Division TFIIS IS TIIE COVERSFIEET, SEF. ,ADD1TIOv:\1. PAGES FOR SPECIFIC AND GENERAL CONDITIONS BUILDING CODE & PRODUCT REVIF\V COMMITTEE This application for Product Approval has been reviewed by the BCCO and approved by the Iuildint Code and Product Review Committee to be used in Miami -Dade County, Florida under the conditions set forth above. Francisco J. Quinlan'. RA. Director r iiamni -D:(IQ County Building Code Compliance ()Bice '+ x0450001 '.,pc2000\ \cemplatestnocice acceptance cover page.doc Interne( mail address: postmasterl7buildingeodeontine .c 41 , Iluntepagc: hltfi: /h1ww.builtlin);eodconline.com uuz •05:181'01 FRI 10:53 FAX 954 578 1042 Polyroam Products. Inc. POLI'FOAM PRODUCrS.1NC. ADHESIVE PLACEMENT DETAIL 2 SINGLE PATTY Nail through plastic cement Underlaymenl 1 Paddy (Beneath Tllel 6 ACCEPTANCE No.: 01- 0404.01 Frank Zuloaga, RRC Product Control Examiner Nall through plastic cement Underlaymenl 1 Ere Caune Paddy (gsnsalh Tgs) Fascia %phis Eno Omura Drip edge uo:irscui tett It1:04 rAA VO4 010 1U4 ruLatuAlei Polvfoam Products. Inc. ADHESIVE PLACEMENT DETAIL 3 DOUBLE PATTY Nall through plastic cement 3m. t 13In. Single paddy en under. leyment Single paddy on tap oI the Single paddy under the Paddy (between tile) Piddy (under tile) 4 In. • 2 in. Eave course 2In. X7 in. medium size paddy eare Fascia course only Nall through plastic cement 3 In. Single paddy underlayrnent 4 In Single paddy under tile S InIe paddy on top of the Eave Course 7 ACCEPTANCE No. : 01 Nail through plastic cement Undedayment Single paddy en under. layment 4 In. Single paddy on top of the Er01 Course 41" Single paddy between the Eave Closure 2 a 71n. medium site paddy eve course only F3 scia Single paddy under Illo Single paddy between the 2 741. medium she paddy ma course only Frank Zuloaga, RRC Product Control Examincr Fascia Weegole Eave closure Orip edge , FRI 10:54 FAX 954 578 1042 C • . Polyfoam Products. Inc. ACCEPTANCE No. : 01- 0404.01 9. This Noticc of Acceptance consists of pages I through 8. POLYFOAM PRODUCTS. INC. _ - END OF THIS ACCEPTANCE 8 • 1. Renewal of this Acceptance (approval) shall be considered after a renewal appl�tation has been filed and thc original submitted documcnts, including test- supporting data, cnginccnng documcnts, arc no older than eight (8) years. 2. Any and all approvcd products shall be permanently labcicd with thc manufacturer's name, city, • state, and the following statement: "Miami -Dadc County Product Control Approval ", or as specifically stated in the spccific conditions of this Acceptance. • 3. Renewals of Acceptance will not bc considered if: a. There has been a change in the South Florida Building Code affecting thc evaluation of this product and the product is not in compliance with the code changes. b. Thc product is no longer the samc product (identical) as thc one originally approved. c. If the Acceptance holder has not complied with all the requirements of this acceptance, including the correct installation of the product. d. The engineer who originally prepared, signed and scaled thc required documentation initially submitted, is no longer practicing thc engineering profession. 4. Any revision or change in the materials, use, and/or manufacture of thc product or proccss shall automatically be causc for termination of this Acceptance, unless prior written approval has been rcquested (through the filing of a revision application with appropriatc fce) and granted by this office. 5. Any of the following shall also be grounds for removal of this Acceptance: a. Unsatisfactory performance of this product or proccss. b. Misusc of this Acceptance as an cndorscmcnt of any product, for sales, advcrtising or any other purposes. 6. Thc Notice of Acceptance number preceded by the words Miami -Dadc County, Florida, and followed by the expiration date may be displaycd in advcrtising literature. If any portion of the Noticc of Acccptancc is displaycd, then it shall bc done in its entirety. 7. A copy of this Acceptance as well as approvcd drawings and other documents, where it applics, shall bc provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at all time. Thc engineer need not reseal thc topics. 8. Failurc to comply with any scction of this Acccptancc shall bc causc for tcrmination and removal of Acceptance. Frank Zuloaga, RRC Product Control Examiner