585 NE 93 St (9)ROOF REPORTERS, INC.
R044 eage&atf
(561) 434 -7555
TAS 106
Roof Tile Uplift Test Report
Test Date July 19, 2001
Project Address Jerry Moorehead
585 NE 93 St. Miami Shores, Fl
Contractor Pioneer Roofing
Permit Number 49249
Roof Pitch 3:12
Tile Installation Date 07/06/01
Adhesive Type Poly Foam
Tile Type Santa Fe S
All testing is in strict accordance with The Dade County version of The South Florida
Building Code, Section 3401.10 and PA 106 -95.
Each Test location was pulled using a Chatillon Force Gauge to a minimum of 35 lbs..
TEST SUMMARY
Roof Area Total # of Tests # of Tests Passed %Passed
Field & Ridge 25 25 100%
Corner 10 10 100%
Perimeter 11 11 100%
TEST RESULTS: PASSED
See Attached Sketch for Further Details
Al Macc`agli, RRC #116
Dade County Certified Testing Agency # 99 -0615.04
3281 Lake Worth RoadJ Suite EO Lake WorthOFlorida 33461
Roof Consulting & Testing OVisual Surveys & Evaluations Roof System Design O
Moisture Surveys
3:/
t
:Synergy Labs,` I nc
9831 E Evergreen St
FL =33157:
:888 :348 :2430
UNIT UNDER : TEST: CHATILLON DFIS 100'DIGITAL- FORCE::GUAGE
25282
:.25282
:�SYN156.
Mfr S/N:
Cust S/N
PROCEDURE NAME
"CALIBRATED":BY
NUMBER:
:SUBMITTED
•`BY
Eliu Lego
VERBAL
-ROOF REPORTERS
'3281 .LAKE .WORTH' ROAD
LAKE WORTH FL
CERTIFICATE NUMBER. 30445 :992524202
PERFORMED ON:
NEXT CAL DUE:: :
TEMPERATURE:
HUMIDITY
14Jun2001
14Se•2001
22.0 °C +1- 1 DEG
38% -- : + l -
•
Synergy Labs,'inc certifies that; An above listed instrvmert •meetsor exceeds all specifications as in the ieferesiced procedure at the points tested ( unless otherwise noted).
It has beers' cabbratcd' Measurement standarda" traceable to the Natrona Institute of Standards :and Technology (NIST), or to NIST accepted intrinsic standards of
measurement,' or derived by the ratio type of self- calibration tec3umique&T his cahbratiort complies with ISO Guide 17025 and ANSI/NCSL Z5 40 -1- 1994.' Calibration procedures
:::used providemeasnrement :uncertainty ratioa . of less than or equal to 4:1 of the specification of the unit under test,- with a coverage factor of 1m2 ai a "ccnf dense bvel of 95%
unless otherwise noted. Ala . report not be reproduced, accept ui'fiill;'unless permission for :the publication of an .approved abstract Is •obtained it writing fsom Synergy •
Lab; Inc: :
REMARKS thisunit was found to be in tolerance at the time of" calibration. No adjustments were necessary.
AMETEK WO-23 WEIGHT SET.::
ration 1 ecnniCian .
6 Jun 2001
• 6 Jun 2003
Standards Used
Tra ce No
REPORT -OF CALIBRATION for ': SERIAL NUMBER::. 25282
PRINTED ON: 14 Jun 2001
Synergy Labs assigned-ASSET NUMBER: •
•
30445
Page { .of
MIAMI SHORES VILLAGE
1 BUILDING INSPECTION DEPARTMENT
•
APPLICATION FOR BUILDING PERMIT
Application is hereby made for the approval of the detailed statement of the plans and specifications herewith submitted for the build-
ing or other structure herein described. This application is made in compliance and conformity with the Building Ordinance of Miami
Shores Village, Florida, and all provisions of the Laws of the State of Florida, all ordinances of Miami Shores Village and all rules and
regulations of the Building Division of Miami Shores Village shall be complied with, whether herein specified or not. A copy of approved
plans and specifications must be kept at building during progress of the work.
Owner's Name and Address
Harvey L. Carver
Date
November 29, 1950
,19
No 585 ILL Street 93rd Street
Registered Architect and /or Engineer
Name and address of licensed contractor Lang_Roofin$ & Tile Co., 430 N.W. 79th Street
Location and legal description of lot to be built on:
Lot Block Subdivision_ _____________
585 N.E. 93rd Street
Street and Number where work is to be done
State work to be done and purpose of building (by floors). 1-30 lb, felt, 1 lb. slate, White barrel tile
copper flashinge.
and for no other purpose.
New Building X Remodeling Addition Repairs No. of Stories
To be constructed of Kind of foundation_____ Roof Covering
Estimated Total cost of improvements $ 700,00 Amount of Permit $
Zone cubage required plan Cubage
Distance to next nearest building Size of Building Lot
Maximum live load to be borne by each floor
I hereby submit all the plans and specifications for said building. All notices with reference to the building and its construction may
be sent to
The undersigned applicant for this building permit does hereby certify that he understands and accepts his obligations as an employer
of labor under the Florida Workmen's Compensation Act, being Section 5966, Compiled General Laws of Florida, Permanent Supplement,
and has complied with the provisions thereof, and will require similar compliance from all contractors or sub - contractors employed by him
in the work to be performed under this permit; and will post or cause to be posted for inspection on the site of the work such public notice
or notices as are required by the Act. The undersigned agrees to employ only such subcontractors, on work to be performed under this
permit, as are licensed by Miami Shores Village. LANG ROOFING & TILE CO.
Remarks (Signed) By:
STATE OF FLORIDA,
COUNTY OF DADE. ss.
Before me, the undersigned authority, a notary public, duly authorized to administer oaths and take acknowledgments, personally ap-
peared
to me well known,
and who, being by me first duly sworn, upon oath deposes and says that he is the
of the above described construction, that he has carefully read the foregoing application, and that he did sign the same, and that all facts
therein by him stated are true.
Permit No Date Read, Sworn to and Subscribed before me.
Disapproved Date__ Notary Public, State of Florida
(Signed)
Building Inspector My Commission Expires
PLANNING BOARD DATE
Chairman Member
Member Member
Member Member
Council Approved Date Disapproved Date
NOTE: A charge of $1.00 will be made for making corrections or changes to this application after approval has been obtained from
the Planning Board.
A re- inspection fee of $1.00 will he charged when such re- inspection is made necessary by improper notice for inspection or faulty
materials and /or workmanship.
Legal Description
Date cf -'0, Job Address 5W /F E 6?.3 Tax Folio
D
APPROVED:
'PERMIT APPLICATION FOR MIAMI SHORES VILLAGE
Owner / Lessee / Tenant / »f 7 y /'mil oc d Master Permit #
5- /S/
Owner's Address 1 ! � /.— Phon ✓7 IO��b
T
AddressC st
Contracting Co.
Qualifier Air ef ss# Phone gos
State44 0 Municipal # Competency # Ins.Co.
Architect /Engineer N�'A
Bonding Company /1/(il
Si .�! r: •, o - ner and /or Condo President
otaryr s to Owner and/
My Commission Expires:
FL ,� C ��.,.., r h 6P - Y37- qq - o/
Zoning
AUDE C. FRANKS, HI
MY COMMISSION # CC 806735
EXPIRES: April 11, 2003
rs
Address
Address
Mortgagor /�1b -
Permit Type(circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFING PAVING FENCE SIGN
/4 5 � ' h ,c,1 L �_ -��� ! —901
WORK DESCRIPTION •1
6'E Cal&
Address
eg tete --
Square Ft. /.43 /t • FeAl. Estimated Cost(value)
WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO
SO MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR
NOTICE OF COMMENCEMENT).
Application is hereby made to obtain a permit to do work and installation as indicated above, and
on the attached addendum (if applicable). I certify that all work will be performed to meet the
standards of all laws regulating construction in this jurisdiction. I understand that separate
permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, RO` ING and MECHANICAL WORK.
OWNER'S AFFIDAVIT: I certify that all the foregoing informat
be done in compliance with all pplicable laws regulating c
authorize the above -named contr ctor to do the work s
n7 •
** * * * t * * * * *
FEES: PERMIT /g RADON C.C.F.
jiff
4.
u
Si tur: o j vn r-
D• t
s
15
0
ctor or Own = :uilder
ski
AUDE C. FRANKS, 11
MY COMMISSION # CC 806735
Notary
My C �}fn
NOTARY
Fire
i
Buildi 4 / l ' Electrical
s cc n
-�
e and hat all work will
c i F t rmore, I
i
• .L4/hi.irk/I ii
to Contra
', Expires: .
**
TOTAL DUE ?D0
Other
Mechanical Plumbing Engineering
06/1.8/ 2001 09:51 19549232677 PIONEER ROOFING PAGE 01/01
NOTICE OF CO
A RECORDED COPY MUST BE POSTED ON THE JOB SITE AT TIME OF FIRST INSPECTION
PERMIT NO. TAX FOLIO NO. /(--- r 3 ,2O e z/T -(0 3o
STATE OF FLORIDA:
COUNTY OF DADE: 01 R 311 194 2001. JUN 15 11:20
THE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with
Chapter 713, Florida Statutes, the following information is provided in this Notice of Commencement.
1. Legal description of property and street address: /// 107t.eS
~�S t/t ' 3 51-
3
2. Description of improvement:
( joke l
3. fawner s) name and address >°� /ci. �' �m >t? eRd ��-7j
11 73 /19• ,
Interest in property:
Name and address of fee simple titleholder:
FLORIDA, COUNTY OF DADE
•p p
ERTIFY that this 15 a true
4. Contractor's name and address:
5. Surety:(Payment bond re ired by owner from contractor, if 4119yE •
Name and address: !J 1 NERE
Amount of bond $ t igVe~
da�dornct: = �f
6. Lender's name and address: _ _ , MA J •,.'i���lc a y • ' °" �`;
7. Persons within the State of Florida designated by Owner upon whom notices or other documents may be served as provided
by Section 713.13(1)(a)7., lorida Statutes,
Name and address: N
8. In addition to-Mmself, Owner designates the following person(s) to receive a copy of the Lienor's Notice as provided in
Section 713.13(1)(b), Flor tatutes.
Name and address:
9. Expiration date of this Notice of Commencement: (the expiration date Is 1 year from the date of recording unless a
different date Is specified
' re of Owner
Notary Public
Print Notary's Name
My Commission Expires
OevnMvt--
Sig
print Owner's Name 1 14 6 6 0 2e7& 4 10
Sworn to and subscribed before me this day of , 20
FL. Dr. vx ' yie✓ 63o —437— 4q— o/ —p
AUDE C. F=RANKS, III
MY CAM ISSIO► : C 8087
EXPIRES; April 11, 2003
�, ElondadThru Navy Public Underwriters
Prepared b�
:ontractor's Name: 1) 1l
3 (Low Slope Application)
3 (Asphalt/Fiberglass Shingles)
F ca.4
Appendix "E"
UNIFORM ROOFING PERMIT APPLICATION
PROCESS No.
ROOF CATEGORY
❑ (Nail -On Tile)
L T L
Job Address: 7I ? 9\3
X adEr-Adhesive Set Tile)
❑ ( Metal Roofs\Wood Shingles & Shakes) ❑ (Other)
ROOF TYPE
❑ New Roof ❑ Re roofing ❑ Recovering ❑ Repair ❑ Maintenance
lat Roof Area (ft') Sloped Roof Area (ft') Total (ft') Master Permit No.
?xposure category (per ASCE 7 -88): Building Classification category (per ASCE 7 -88 table 1):
123.0 1.79 199
Ft.
v
A
v
Deck type: Al e
Fastener Type:
A TTACHMENt
SPACING
Field: Perimeter: Corner:
DETAIL 1 & 2
ROOF HEIGHT AND SYSTEM DETAILS
(Draw details as needed)
Page -1
Rid e Ventilation?
M CAN ItEICI(T
Deck type:
D E T A I L 3
Appendix "E"
UNIFORM ROOFING PERMIT APPLICATION
PROCESS No.
SLOPED SYSTEM DESCRIPTION
Underlarnent:
I,uulaUon:
43 i 0/1
Fastener type & sparing:
Cap Sheet:
Roof Covering:
/� TILE CALCULATIONS
(Pmax1: 1 ( j x X (Aerodynamic Multiplier): ti? I ) - M = M �, PCA: 6/7
(Pmax2. "9t J x a. (Acrodynarnic Multiplier): Y1 ) - M Z = M Z 2' � PCA: (t% 1 1
(Pmax3: !(% x a (Acrod 1ieMultiplia): ()97 ) - M .OZ = MrS' ' 2 21 PCA:
Page -2
Drip edge
4/4//
ATTACHMENTS REQUIRED
1) Fire Directory Listing Page
2) Dade County Product Control
Notice of Acceptance -Cover Sheet
a) Specific System Description
b) Specific System Limitation
c) General Limitations .
d) Applicable Detail Drawings
3) Municipal Permit Application
4) Other Component Approvals
06'/. ^6 /O1 • 08:17 FAX 5618320264
05/11/2001 14:46 3058880050
• MI'AMI•D'
EAST COAST SUPPLY -
SANTAFE TILE CORP
PRODUCT CONTROL NOTICE OF ACCEPTANCE
Santa Fe Tile Corporation
10302 N.W. South Rivet Drive, Bay #16
Medley ,FL 33178
Your application for Notice of Acceptance (t■IOA) of:
Spanish "S" Clay Tile
under Chapter 8 of the Code of M iami -Dade) County governing he use of Alternate Materials and Types of
Construction, and completely described herciin, has been recommended for acceptance by the Miami -Dade
County Building Code Compliance Office (BCCO) under the conditions specified herein.
This NOA shall not be valid after the expiration date stated bel
product or material at any time from a job ite or manufactur
product or material fails to perform in the ipploved manner,
use of such product or material immediately. BCCO resery e
determined by BCCO that this product or !material fails to n
Building Code,
The expense of such testing will be incurred iby the manufactur
ACCEPTANCE NO.: 00- 121106
EXPIRES: 02 /0 UZ006 I 6 Raul Rodriguez
Chief Product Control Division
THIS IS THE COVERSHEET, SEE ADDITIONAL PAG S FOR SPECIFIC AND GENERAL
CONDITIONS
BUILDING COPE krz PRODUCT REVIIEW COMMITTEE
This application for Product Approval has ibeen reviewed byf the BCCO and approved by the Building
Code and Product Review Committee to be`used in Miami-Da' e County, Florida under the conditions set
forth above.
a n. m /nl nOni
11s045000 t1pc200011cemptar acceptance cover pagedoc
•
lntrrnrr en.r.l srl.irrva• .rl.,,.
u"
)w. BCCO reserves the right to secure this
's plant for quality control testing. If this
CCO may revoke, modify, or suspend the
the right to revoke this approval, if it is
eet the requirements of the South Florida
MIAMI -DADE COUNTY, FLORIDA
METRO -DADE FLAGLER BUILDING
BUILDING CODE COMPLIANCE OFFICE
METRO -DADE FLAGLER BUILDING
140 WEST FLAGLER STRECT, SUITE 1603
N1IAi\tI. FLORIDA 33130 -1563
(305) 375 -2901 FAX (305) 375.2908
. s - " "-
CONTRACTOR LICENSING SECTION
(305) 375.2327 FAX (305)375
CONTRACTOR t',N FOR CEMENT DIVISION
(905) 375 - 2966 FAX (305)375-290a
PROW-ICI' CONTROL DIVISION
(305) 375.2902 1A.1 (305) 372 -6334
Francisco 3, Quintana, R.A.
Director
Miami -Dade County
1001
PAGE 01
r.rr
08/26/01 08:18 FAX 5618320264
05/11/2801 14:46 3059880050
SANTAFE TILE CORPORATION
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub- Categorv: 07320 Ro Tiles
Materials Clay RooflTiles
Deck Type: Wood 1
1. SCOPE
This renews a roofing system using Santa Fe "Santafe '
Santafe Tile Corporation described lin Section 2 of this
comply with the South Florida Building Code, 1994 Edi
locations where the design pressur requirements, as det
does not exceed the design pressor , obtain by cal
using the values listed in herein. TIe attachment calcul
system.
2. PRODUCT DESCRIPTION
Manufactured by
Applicant
Santafe `S' Clay
Roof Tile
Trim Pieces
Test
Dimensions Specifications
I-= 18"
w = 11.5"
%" thick
I = varies
w = varies
varying
thickness
EAST COAST SUPPLY .
SANTAFE TILE CORP
PA 112
PA 112
2.1 COMPONENTS OR PRODUCTS MANUFACT
est
Product Dimensions Spec ficationg
Tile Screws 8 x 2-Y2" long PI4 114
0.130" shank dia_ Ap . endix E
0.178 flute dia.
3. LIMITATIONS
3.1 Fire classification is not par of this acceptance.
3.2 For mortar or adhesive set ile applications, a st
accordance with RAS 106.
3.3 Applicant shall retain the ervices of a Mia
perform quarterly test in accordance with PA
submitted to the Building Code Compliance Of
2
On
equ
mo
Ac
hip
Ma
S
CCEPTANCE No. 00 1212.06
Approval Date: February 1, 2001
Expiration Date: February 1, 2006
" clay roofing tile, manufactured by
ice of Acceptance, designed to
Ion For Miami -Dade County. For
rrnined by applicable building code,
ulations in compliance with RAS 127
ions shall be done as a moment based
Prod uct
Description
piece high profile clay roof tile
ped with two nail holes. For nail -on,
ar set and adhesive set applications.
ssory trim. clay roof pieces for use at
rakes, ridges and valley terminations.
ufnetured for each tile profile.
RED BY OTHERS
Product
escri lion
inless Steel
Manufacturer
generic
e1002
PAGE 02
is field uplift test shall be performed in
- Dade County Certified Laboratory to
12 a, ..•..' _� ::. - i...,�...,,,::.•_ hall be
oaga, RRC
oofing Product Control Examiner
Table 3: Attachment Resltance Expresse as a Moment- Mf (ft-lbf)
Fbr Nall -On Syste
Tile Profile
Tile
Application
Two Nails
21.8
One Screw
29.15'
T Screws
38.28
One Screw
w/ Clip
57.31
Two Screws
w/ Clip
57.50
Santafe S
Direct Deck
Battens
. Mortar Set
Battens
23.6
j Adhesive Set
,
61.77
1 . Approved
screws as noted 'Product manufactured by others' 1
Direct
Deck
Table 2: Restorin•
Table 4: Attachment
for
Resistance Expresse
Mortar or Adhesive Set
Tile
Application
as a
ystems
Moment - M, (ft -lbf)
Attachment
Resistance
4 ":12"
Tile
Profile
6 ":12"
Santafe 'S'
or
Direct
Deck
Battens
. Mortar Set
Battens
23.6
j Adhesive Set
,
�___ 61.9
Table 2: Restorin•
Moments due to 1i. ravi - M. ft-lb
Tile
Profile
2
3 ":12"
4 ":12"
":12"
i
6 ":12"
7 ":12"
greater
Battens
or
Direct
Deck
Battens
Direct
beck
Battens
Direct!
Deck
Battens
Direct
Deck
B. is ns
1
Direct
Deck
Battens
Direct
Deck
Santafe 'S'
5.93
5.90
5.85
5.82
5.73
5.69
5. j6
5.53
5.32.
5.29
5.03
N/A
Table 1: Ae
od namic Multi • I ers— I.
ft
Tile
Profile
I I. (ft )
Batten A - - licat •
X. (ft )
Direct Deck
Santafe 'S'
0274 1
0.297
. 06/16/01. 08:18 FAX 5618320264 EAST COAST SUPPLY -
95/11/2001 14:46 3058880956
SANTAFE TILE CORPORATION
SANTAFE TILE CORP
CCEPTANCE No. : 00 1212.06
3.5 30/90 hot mopped underlayment applications ,-y be installed perpendicular to the roof
slope unless stated otherwise by the underla ent material manufacturers published
literature.
3.6 This acceptance is for world dcck applications. Minimum deck requirements shall be in
compliance with applicable building code.
4. INSTALLATION
4.1.1 Santafe 'S' azid its components shall be installed strict compliance with Miami Dade
County Roofing Applicatiol Standard RAS 118 S 119, and RAS 120,
4.1.2 Data For Attachment Calculations
0 003
PAGE 63
3
rank Zuloaga, RRC
RooFng Product Control Examiner
06/26/01 08:19 FAX 5618320264
05/11/2001 14:46 3058880050
• SANTAFE TILE CORPORATION
EAST COAST SUPPLY
5. LABELING
5.1 All tiles shall bear the imprint or identifiable m king of the manufacturer's name or logo,
or following statement: "Miami -Dade County Pr duct Control Approved ".
6. BOLDING PERMIT REQUIRE
6.1 Application for building petmit shall be accomp
6.1.1 This Notice of Acceptance.
6.1.2 Any other documents required by the Buildi
order to properly evalute the installation of
PROFILE DRAWIN
SANTA,)F•)~ " S" CLAY
SANTAFE TILE COPP
R ACCEPTANCE No. : 00- 1212.06
ed by copies of the following:
1004
PACE 04
g Official or applicable Building Code in
system.
OOF TILE
Frank Zuloaga, RRC
Roofing Product Control Examiner
06/26/01 '08:19 FAX 5618320264
05/11/2001 14:46 3058880050
EAST COAST SUPPLY .
SANTAFE TILE CARP
SANTAFE T11 CORPORATION
NOTICE OF ,ACC . PTANC • STANDA D CONDI
1 Renewal of this Acceptance (approval) s21a11 be considered after
original submitted documentation, lnclud test supporting da
eight (8) years.
2 Any and all approved products shall be p labeled wi
the following statement: "Miami -Dade dCaunty Product Control
specific conditions of this Acceptance.
5
ACCEPTANCE No.: 00 -12
ONS
repcwal application has been filed and thc
engineering documents, arc no older than
the manufacturer's name, city, stale, and
pproved ", or as specifically stated in the
3 Renewals of Acceptance will not be consklered if
a) There has been a change in the Snug Florida Building Co
and the product is not in compliant with the code changes
b) The product is no longer the same product (identical) as
c) If the Acceptance holder has not coittplied with all the req
correct installation of the product;
d) The engineer who originally prepar signed and sealed
submitted, is no longer practicing the engineering profes5i
4 Any revision or change in the materials, fuse, and/or manufactur
automatically be cause for termination oflthis Acceptance, un
(through the filing of a revision application with appropriate fee
5 Any of the following shall also be grounds for removal of this A
a) Unsatisfactory performance of thii product or process;
b) Misuse of this Acceptance as an endorsement of any pro
purposes. ■
6 The Notice of Acceptance number precedd by the words Miami Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If ann portion of the Notice of Acceptance is
displayed, then it shall be dope in its entitety.
affecting the evaluation of this product
one originally approved;
ernems of this acceptance, including the
required documentation initially
of the product or process shall
prior written approval has been requested
and granted by this office.
eptancc:
ct, for sales, advertising or any other
7 A Copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be
provided to the user by the manufacturer or its distributors and s l( be availablo for inspection at Use job
site at all times. The copies need not ba resealed by thc engin
8 Failure to comply with any section of this Acceptance shall be sv for termination and removal of
Acceptance.
9 This Acceptance contains pages 1 througft 5
END bF THIS ACCEPTA CE
005
PAGE 05
2.06
Frank Zuloaga, RRC
Roofing Product Control Examiner
ma y./ v1 Z £S 4. . Y►
MIAMI•D+ADE
£41. JJY J/Q 104L
rut.xruitm rnuuuui�, ttvt,.
PRODUCT CONTROL NOTICE OF ACCEPTANCE
Polyfo:lm Products, Inc.
2400 Spring- Stucbncr Road
Spring ,TX 77383 - 1132
Your application for Notice of Acceptance (NOA) of:
Two Component Polyurcthcne Foam Tile Adhesive
under Chapter 8 of the Code of Miami -Dade County governing the use of: \lternate Materials and Types of
Construction. and completely described herein, has been recommended for acceptance by the Miami -Dade
County Building Code Compliance Office (BCCO) under the conditions specified herein.
This NOA shall not be valid after the expiration date stated below. BCCO reserves the right to secure this
product or material at any time from a jobsite or manufacturer's plant for duality control testing. If this
product or material fails to perform in the approved manner, BCCO may revoke, modify, or suspend the
use or such product or material immediately. BCCO reserves the right to revoke this approval, it' it is
determined by I3CCO that this product or material fails to meet the requirements of the South Florida
Building Code.
The expense of such testing will be incurred by the manufacturer.
ACCEPTANCE, NO.: 01- 0404.01
EXPIRES: 02/04/2003
APPROVED: 05/10/2001
MIAMI -DADE COUNTY. FLORIDA
METRO -DADE FLAGLER BUILDING
BUILDING CODE COMPLIANCE OFFICE
Mr.TIt(- DA DI. FI.Ari1.1:It I1l1ILDING
140 WESTILAGLER STREI:r. SUI•rt: 1603
nn,ntin.
19.OI(l1)A 33130 -1563
(305) 375.2901 FAX (305) 375 -290 c
(0Ni'R. ('1'OK I.I( :E :NSIN(. til :trio
(305) 3 75 -2327 VAX (305)375 -255x
(:(n \TIt.■:I'rnt ENFORCEMENT DIVISION
(305) 375.2'16(, FAX (305)375-290X
r(touucr CONTILOI. I)('ISioN
(305) 375.2`102 FAX (305) 372.6339
I:au1 Rodriguez
Chic!' Product Control Division
TFIIS IS TIIE COVERSFIEET, SEF. ,ADD1TIOv:\1. PAGES FOR SPECIFIC AND GENERAL
CONDITIONS
BUILDING CODE & PRODUCT REVIF\V COMMITTEE
This application for Product Approval has been reviewed by the BCCO and approved by the Iuildint
Code and Product Review Committee to be used in Miami -Dade County, Florida under the conditions set
forth above.
Francisco J. Quinlan'. RA.
Director
r iiamni -D:(IQ County
Building Code Compliance ()Bice
'+ x0450001 '.,pc2000\ \cemplatestnocice acceptance cover page.doc
Interne( mail address: postmasterl7buildingeodeontine .c 41 , Iluntepagc: hltfi: /h1ww.builtlin);eodconline.com
uuz
•05:181'01 FRI 10:53 FAX 954 578 1042
Polyroam Products. Inc.
POLI'FOAM PRODUCrS.1NC.
ADHESIVE PLACEMENT DETAIL 2
SINGLE PATTY
Nail through plastic cement
Underlaymenl
1
Paddy (Beneath Tllel
6
ACCEPTANCE No.: 01- 0404.01
Frank Zuloaga, RRC
Product Control Examiner
Nall through plastic cement
Underlaymenl
1
Ere Caune
Paddy (gsnsalh Tgs)
Fascia
%phis
Eno Omura
Drip edge
uo:irscui tett It1:04 rAA VO4 010 1U4 ruLatuAlei
Polvfoam Products. Inc.
ADHESIVE PLACEMENT DETAIL 3
DOUBLE PATTY
Nall through plastic cement
3m.
t 13In.
Single paddy en
under.
leyment
Single paddy
on tap oI the
Single paddy
under the
Paddy
(between tile)
Piddy
(under tile)
4 In.
•
2 in.
Eave course
2In. X7 in. medium
size paddy eare
Fascia course only
Nall through plastic cement
3 In.
Single paddy
underlayrnent
4 In
Single paddy
under tile
S InIe paddy
on top of the
Eave Course
7
ACCEPTANCE No. : 01
Nail through plastic cement
Undedayment
Single
paddy en
under.
layment
4 In.
Single paddy
on top of the
Er01
Course
41"
Single paddy
between the
Eave Closure
2 a 71n. medium
site paddy eve course only
F3 scia
Single paddy under Illo
Single paddy between the
2 741. medium
she paddy ma
course only
Frank Zuloaga, RRC
Product Control Examincr
Fascia
Weegole
Eave closure
Orip edge
, FRI 10:54 FAX 954 578 1042
C • .
Polyfoam Products. Inc. ACCEPTANCE No. : 01- 0404.01
9. This Noticc of Acceptance consists of pages I through 8.
POLYFOAM PRODUCTS. INC. _ -
END OF THIS ACCEPTANCE
8
•
1. Renewal of this Acceptance (approval) shall be considered after a renewal appl�tation has been filed
and thc original submitted documcnts, including test- supporting data, cnginccnng documcnts, arc no
older than eight (8) years.
2. Any and all approvcd products shall be permanently labcicd with thc manufacturer's name, city, •
state, and the following statement: "Miami -Dadc County Product Control Approval ", or as
specifically stated in the spccific conditions of this Acceptance.
•
3. Renewals of Acceptance will not bc considered if:
a. There has been a change in the South Florida Building Code affecting thc evaluation of this
product and the product is not in compliance with the code changes.
b. Thc product is no longer the samc product (identical) as thc one originally approved.
c. If the Acceptance holder has not complied with all the requirements of this acceptance,
including the correct installation of the product.
d. The engineer who originally prepared, signed and scaled thc required documentation initially
submitted, is no longer practicing thc engineering profession.
4. Any revision or change in the materials, use, and/or manufacture of thc product or proccss shall
automatically be causc for termination of this Acceptance, unless prior written approval has been
rcquested (through the filing of a revision application with appropriatc fce) and granted by this
office.
5. Any of the following shall also be grounds for removal of this Acceptance:
a. Unsatisfactory performance of this product or proccss.
b. Misusc of this Acceptance as an cndorscmcnt of any product, for sales, advcrtising or any
other purposes.
6. Thc Notice of Acceptance number preceded by the words Miami -Dadc County, Florida, and followed
by the expiration date may be displaycd in advcrtising literature. If any portion of the Noticc of
Acccptancc is displaycd, then it shall bc done in its entirety.
7. A copy of this Acceptance as well as approvcd drawings and other documents, where it applics, shall
bc provided to the user by the manufacturer or its distributors and shall be available for inspection at
the job site at all time. Thc engineer need not reseal thc topics.
8. Failurc to comply with any scction of this Acccptancc shall bc causc for tcrmination and removal of
Acceptance.
Frank Zuloaga, RRC
Product Control Examiner