867 NE 91 Terr (8)ETS
ENVIRONMENTAL TESTING
SERVICES, INCORPORATED
December 1, 1999
Mr. John Cherry
Roofs By Cherry, Inc.
3901 S.W. 40th Avenue
Pembroke Park, Florida 33023
RE: TILE UPLIFT TEST
Residence
877 N.E. 91 Terrace
Miami Shores, Florida
Mr. Cherry:
Report # FL99- 456RUT
Pursuant to your request, ETS ENVIRONMENTAL TESTING SERVICES
INC. in association with ROOF REPORTERS, INC. has performed uplift
test on the tile roof at the above referenced address. The
following report includes the results of the uplift test.
The uplift test consisted of placing a load test devise
manufactured by Chatillon (model DFIS), over the tile with an
adjustable connector placed under the front lip of the tile, and
gradually increasing the pressure. The gauge readings are indicated
in pounds. Pressure was exerted on the tile until a reading of
thirty -five (35) pounds was obtained. The tests were conducted,
and the results have been reported in accordance with Dade County
Protocol, PA -106.
ETS ENVIRONMENTAL TESTING SERVICES INC. greatly appreciates the
opportunity to work with you, Should you have any questions or
comments, please feel free to call.
Respectfully submitted,
ETS ENVIRONMENTAL TESTING SERVICES INC.
van J merson I.H.
Director of Environmental Service
7779 Miramar Pkwy. * Miramar, FI. 33023
(954) 270 -0436
Test Date
Project Address
Contractor
Permit Number
Roof Pitch
Adhesive Type
Tile Type
TEST SUMMARY
TEST RESULTS: PASSED
See Attached Sketch for Further Details
ROOF REPORTERS, INC.
4,4ez 9
PA 106 -95
Roof Tile Uplift Test Report
November 30, 1999
877 NE 91 Terr. Miami Shores, FL
Cherry Roofing
45698
3:12
Tile Installation Date November 22, 1999
Polyfoam
(561) 434 -7555
SanTa - CK.-, /ar,1 /TV /Sok
All testing is in strict accordance with The Dade County version of The South Florida
Building Code, Section 3401.10 and PA 106 -95.
Each Test location was pulled using a Chatillon Force Gauge to a minimum of 35 lbs..
Roof Area Total # of Tests # of Tests Passed %Passed
Field & Ridge 25 25 100%
Corner 10 10 100%
Perimeter 10 10 100%
accagli, RRC #116
Dade County Certified Testing Agency # 94 -0916 -11
3281 Lake Worth Roadr Suite Ell Lake WorthOFlorida 33461
Roof Consulting & Testing D Visual Surveys & Evaluations ORoof System Design O
Moisture Surveys
ttull
Moccogli
CONSULTANTS Nn+
T
-Tr
T.
r
r
r
1 N E 91 - - E RAA Gt
M M S t- o R?€S 1 Fort A
ur1.1/1117 v7:: r Jnja i I'�Jbd
SYNERGY
Labs, Inc
Calibration Date Sep 15. 1999
Calibration Due: Sep 15, 2000
Reference Standards Used
Manufacturer
CONSOLIDATED
SYNERGY
Model
Number
t000PF
12'
SVI•CP(;V LABS INC
Certificate of Calibration
Manufacturer CMATI LION
Model Number DFIS 200
Serial Number' 25220
Customer SN. 25220
Description DIGITAL FORCE GAUGE
Customer: ROOF REPORTERS. INCORPORATED
Cantleate Number 81503
Environmental Conditions: Temp: 21 dog C Relative humidity: 45%
This certifies that the above equipment was calibrated in compliance with the requlroments of ANSUNCSL -Z540-
1994. ISO Gutde 25. and ISO 10012 using applicable procedures.
At planned intervals. Synergy Labs, Inc measurement standards are calibrated by comWr13On to Or measurement
against national standards. natural physueal constants, consensus standards. or by rotlo type measurements using
sell-calibrating techniques.
National standards are administered by NISI (National Institute of Standards and Technology) or other recognized
national standards taboretones.
Supporting documentation relative to traceability is on file and Is available for examination upon request.
Ltmtta: NONE
Remarks: UNIT RECEIVED IN TOLERANCE - NO ADJUSTMENTS REQUIRED
Swat True
Number Number Cat Due Date
•
_
775 69652 Jan 06. 2000
388 19257 8116/2000
Synergy Labs. Inc 8211 NW 64 ST 113 Miami. FL 33188 Ph (305) -477 -5
PAGE 04
r
8.1.4 The nose of the tile deflects vertically in excess of 2 inches in mechanically
attached systems.
9 Acceptance Criteria:
9.1.1 75% or more of the static up lift tests shall be required to pass the testing criteria.
10 Report
10.1 The final test report shall include the following:
10.1.1 A sketch of the test site roof which indicates I ) the field, perimeter and corner
areas, with dimensions; and, 2) the location of all components on which a static
uplift test is conducted. Indicate those attachments which were initially tested
and, if applicable, those attachments which were tested in the extended testing.
10.1.2 A tabulated set of test results, signed by a Professional Engineer or a Registered
Roof Consultant.
10.1.3
-END OF RAS 106-
106
-' PERMIT APPLICATION FOR MIAMI SHORES VILLAGE
Date 6 f r Job Address `is I N E 4 1 l e f t Tax Folio I L" fl CQ — 00
Legal Description G ,tdo Historically Designated: Yes No
‘X,2 3 0/
Owner/Lessee / Tenant la_ rc tee- W e- -Is r -e, Master Permit #
Owner's Address 1 !J ell t �r
Notary as to 0
My Commissi
Square Ft. d
Signature of owner and/or Condo President Date
s: MARIETTA RODRIGUEZ -NOVO
MY COMMISSION 0 CC 713506
EXPIRES: February 4, 2002
f3 Bonded Thu Notary Public Undery l$ era
FEES: PERMIT 1 6/ RADON
APPROVED:
Zoning Building
Mechanical Plumbing
C.C.F.
Phone
.) s g - s444-
Contracting Co. N.16 v o I b ) PJ g 6 v p pt> 7K` Address (..S? q O CQ vr� ar � 5
Qualifier {-} (Q- X4n►oJtr I t SS# - ( Phone LP
Competency # Ins. Co.
Address
Address
State # Municipal #
Architect/Engineer
Bonding Company
Mortgagor Address
Permit Type (circle one): BUILDING ELECTRICAL PLUMBING MECHANIC ROOFING PA ING FENCE SIGN
M
I0 N rtr Co Or 1 n
WORK DESCRIPTION 2 h, - f - �QJ �( �-�- fi I r't 651 Ve
Estimated Cost (value) r--- ' 7 d O
WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING,
CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.)
Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I
certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate
permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK.
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable
laws regulating construction and zoning. Furthermore, I authorize the above -named contractor to do the work stated.
Signature of Corii or Owner- Builder
Notary s tContractor or er- Builder Date
My Commission Expires:
ej
O
NOTARY
;; :Py MARIETTA RODRIGUEZ -NOVO
r■ ti MY COMMISSION 0 CC 713506
�L� EXPIRES: February 4, 2002
1. ";t y n;;' Bonded Pau Notary Pubic Underwriters
Electrical
Date
-�� ' /c4,3y
O
BOND 3c
TOTAL DUE 3 '49y
Engineering
A RECORDED COPY MUST BE POSTED ON THE JOB SITE AT TIME OF FIR I. I S CT
PERMIT NO. TAX FOLIO NO. 1 — c7Co - 5 - dag c:-/F;:, STATE OF FLORIDA:
tai f'
COUNTY OF DADE:
. NOTICE OF COMMENCEMENT
THE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with
Chapter 713, Florida Statutes, the following information is provided in this Notice of Commencement.
1. Legal description of property and street address:
2. Description of improvement: 4<Q�
3. Owner(s) name and address: 0.�� (a _a_ Y Tr r4- re
Interest in property: ,—
Name and address of fee simple titleholder:
4. Contractor's name and address: `I \► d - 00 r
C.a 60 �0.✓vto r, ►J ��
5. Surety:(Payment bond required by owner from contractor, if any)
Name and address:
Amount of bond $
6. Lender's name and address:
7. Persons within the State of Florida designated by Owner upon whom notices or other documents may be served as provided
by Section 713.13(1)(a)7., Florida Statutes,
Name and address:
Signature of Owner e
Notary Public
Print Notary's Name
My Commission Expires:
8. In addition to himself, Owner designates the following person(s) to receive a copy of the Lienor's Notice as provided in
Section 713.13(1)(b), Florida Statutes.
Name and address:
9. Expiration date of this Notice of Commencement: (the expiration date is 1 year from the date of recording unless a
different date is specified)
a,z4_
Print Owners Name iea L Cf
Sworn to and subscribed before me this 6
day of ,JP ' / , 19 9 .
MARIETTA RODRIGLI.EZ -NOVO
°g ;; Bonded Tin Notary Public Underwtf e
re
X4,1 f..) ' Tm•
98R 16412
m 5 hore_S 33138
6opp� t �
C_-12),(24,7t4 " (4 (D
Prepared by: N\1 -.et. (w i■.,)p.r o
Address: 6' oc,
- Go4d./ (,G6,
123.01.52 2/93
'3= I _bMDA, COUNTY OF Or"\c7
f:.c `.
Appendix "E"
UNIFORM ROOFING PERMIT APPLICATION
PROCESS No.
Contractor's Name: CAf • R s „ L • . fp(y Job Address: (-.: 1 ?•) G (; t < <' r-
ROOF CATEGORY
❑ (Low Slope Application) ❑ (Nail -On Tile) 1r(Mortar- Adhesive Se t e)
❑ (Asphalt/Fiberglass Shingles) ❑ ( Metal Roofs\Wood Shingles & Shakes) ❑ (Other)
ROOF TYPE
❑ New Roof 21e- roofing ❑ Recovering ❑ Repair ❑ Maintenance
Flat Roof Area (ft Sloped Roof Area (ft Total (ft ) -> Master Permit No.
Exposure category (per ASCE 7-88): i2_ Building Classification category (per ASCE 7-88 table 1):
Ft.
A
v
Ft.
A
v
Deck type:
ATTACHMENT
Fastener Type:
SPACING
Field: Perimeter: Corner:
a
DETAIL 1 & 2
ROOF HEIGHT AND SYSTEM DETAILS
(Draw details as needed)
1
r
r
r
r
r
r
ROOF PLAN
31
Appendix "E"
UNIFORM ROOFING PERMIT APPLICATION
PROCESS No.
Ridge Vea on7
I 44 (t
MEANRSIQIf
7 et)
1 ft)
Deck type:
Insulation:
0 , 4
tr �
ROOF SLIM
D E T A I L 3
6
1VV
SLOPED SYSTEM DESCRIPTION
y
IA-104=d_
Underlayment: * A 5777 oaa 6 - r3 p
7T
t
Fastener type & spaehq:
Cap Sheet:
tc ma Al"
Roof Covering:
t.
5. lc) G" of
Drip edce:3X3 al� G4. G&Iv•
ATTACHMENTS REQUIRED
1) Fire Directory Listing Page
2) Dade County Product Control
Notice of Acceptance-Cover Sheet
a) Specific System Description
b) Specific System Limitation
c) General Limitations
d) Applicable Detail Drawings
3) Municipal Permit Application
4) Other Component Approvals
(Pmazil a 3 x ? (Aerodynamic Multiplier): • w> ) -
( P m a x 2 : / X (Aerodynamic Multiplier):. c ) ` 1 )
(Pmax3: i 5x X (Aerodynamic Multiplier): o) `f- ) -
TILE CALCULATIONS
M SaO = Mr i4 PCA: / / g -`j o
M c = Mr 1 9 PCA: o
M = M - PCA: 1 / 9 ..
a lh , s(ye,
Page -2
PRODUCT CONTROL IOTX E OF ACCEPTANCE
Monier Roof Tile
135 N.W. 20 Si
Boca Raton, FL 33431
ACCEP rANCE NO.: 96- 0528.06 Renews No._94- I22L08
EXPIRES: 0-1
THIS j
CO
CONDT p
BUILDING CODE COMMI'IZEF
mot mail address: postmasterebuildingeodven tiga.eom
EH ' 'S8 10:27
LP FOR
INTROMLIYAN DADE COUNTY, FLORIDA
METRO -DADE FLAGLER BUILDING
BUILDING CODE COMPUANCE OFFICE
METRO -DADE FLAGLER BUILDING
140 WEST FLAGLER STREET, SUfTE 1603
MIAMI, FLORIDA 33130 -1553
(305) 375 -2901
FAX (305) 375 -2908
Raul Rod guez
Product Control Supervisor
PRODUCT CONTROL OMSION
(305) 375-2902
FAX (905) 372 -6335
Your application for Product Approval of
Bermuda Fiat Tile
under Chapter 8 of the Metropolitan Dade County Code governing the use of Alternate Materials and
Types of Construction, and completely described in the plans, specifications and calculations as
submitted by
Redland Technologies, The Center for Applied Engineering, Inc. and Professional Service
Industries, Inc_
has been - _Jmmennded for acceptance by the Building Code Compliance Office to be used in Dadc
County, ' ,orida under the specific conditions set forth on pages 2 -12 and the standard conditions on
page 13_
This approval shall not be valid after the expiration date stated below. The Building Code Compliance
Office :serves the right to secure this product or material at any time from a jobsite or manufacturer's
plant fc quality control testing. If this product or material fails to perform in the approved manner, the
Building Code Compliance Office may revoke, modify, or suspend the .use of such product or material
immediately. The Building Code Compliance Office reserves the right to revoke this approval, if it is
determined by the Building Code Compliance Office that this product or material fails to meet the
requirc.nents of the South Florida Building Code.
The expen. of such testing will be incurred by the manufacturer.
.Ir.�d.
1 1 �1��
This appliic::rion.for Product Approval has been reviewed by the Metropolitan Dade County Building
Code Corsi. .lane Office and approved by the Building Code Committee to be used in » c County,
Floe • . ui . the conditions set forth above,
Charles Danger, P.B.
Director
Building Code Compliance Dept.
APPROVED: 01/0V98 1 Metropolitan Dade County
HomePago:
non c.nn. ,.,.
03. 16. 98 .2:12 PM ^P01�
Category: Prepared Roofing
Sut.Categorv: Tile
Type: Mortar Set/Adhesive Set
S4I Concrete
=E3 12 '98 10:28
rtylignaleScriPtion
Page 2 of 13
PRODUCT CONTROL NOTICE OF ACCEPTANCE
ROOFING SYSTEM APPROVAL
Expiration Date:
Contact:
Reese H. Moody
Technical Service Accessories Manager
I35 N.W. 20 St.
Boca Raton, FL 33431
(407)338 -8200
unouw atlnml iQ}00
Product Control No.: 96- 01$,06
AovlicanZ:
Monier Roof Tile Product Control No.: • 96-0528.06
135NW20St.
Boca Raton, FL 3343 I Approval Date: Javan 8. 1994
lama ce1202
Monier Roof Tile is a member of the Redland Group, a world wide producer of primary building
products and roof tile. Monier manufacturers concrete roof tile for nail -on, mortar set or adhesive set
application_ a plants throughout the United States ranging from Washington State to Florida. All tile is
manufar.:.acd from extruded concrete consisting of Portland Cement, plasticizer, iron and metallic
oxides, and blended aggregates. This Prod xpntral Approval relates to Monier's "Bermnfla Flat" tile
profile. f o r to 1 vals for th the fil .
Monier sells tile systems through local distribution and directly to consumers. All profiles have
match:: g trim pieces used for rake hip, ridge hip, and valley terminations. Tile system accessories such
as underiayment, ventilation systems and flashing systems are also available. 'These accessories are
mansfactured for all profiles and form a part of this Product Control Approval.
M• .,nier's "Bermuda Flat" roof tile has been tested in compliance with the South Florida Building
Code req' •.:moms for concrete, mortar or adhesive set tile applications. The minimum roof slope for
Monier's •' ■.nuda Flat" mortar or adhesive set tiles shall be 2 ":12 ". Sec the "Profile Drawing" section
in this 4,z oval for the "Bermuda Flat" profile drawing. The Monier "Bermuda Flat" tile profile has
been tested for both wind characteristics and static uplift performance, therefore, any consideration for
installation shall be done as a 'Moment Based System'. Data for attachment calculations is noted in
Tables 1 through 3 of this approval.
rank Zuloaga
Roofing Product Control Examiner
SRI rill S'Zc 1 nor= CAP
03. 16. 92 12:12 FM 202
Product
E3 12 '88 18:28
1111191101 It! LACTURED OR
Bermuda Flat Flat 1 =15"
Tole w 10 3 /8°
Ph" thick
Trim Pieces , I = varies.
w varies
varying
thickness
LABELED BY APPLICANT
Test
Dimensions Specifications
PA 112
PA 112
Page 3 of 13
Product
Description
Flat, interlocking, extruded
concrete roof tilt equipped with
two nails holes For mortar set or
adhesive set applications.
Accessory trim, concrete roof
pieces for use at hips, rakes, ridges
and valley terminations.
Manufactured for each tile profile.
1
Franc; Zuloaga
Roofing Product Control Examiner
rid 1 '7'30 c ^,c non
03. 16. 9° 12:_12 PM P03
:itz /yo lnu 1u:43 tile JO1 J341f 53UI
1130 Felt
1Produc4
#43 Coated Base
Sheet
Mineral Surface
Cap Sheet
Lenzingtex -LB 140 59" x I64' roll
Under;ayment 22 Ibs/roll
Rainproof 11
Ice and Water
Shield
:93 12 'SS 10:29
MONIER L[FETILE ••-• BRADCO MIAMI ®004
Product Control No.: 96- 0528.06
TRADE NAMES OF PRODUCTS MANUFACTURED OTHERS
Test
Dimensions § c tionrs
30" x 75' roll
36" x 75' roll
or
60" x 75' roll
36" x 75' roll
N/A
N/A
N/A
ASTM D 226
type II
ASTM D 2626
ASTM D 249
PA 104
PA 104
PA 103
Page 4 of I3
Product
Description
Saturated organic
felt to be used as a
nailed anchor sheet.
Saturated and
coated organic base
sheet for single or
double ply
underlayment.
Mineral surfaced
asphalt roll roofing
for use as a top ply
in a double ply
underlayment
system.
Single ply, nail -on
underlayment.
Single ply, nail -on
underlayment with
2" self- adhering top
edge.
Self - adhering
underlayment for
use as a top ply in a
two ply
underlayment
system with
approved #30 or
#43 as the base
layer.
Manufacturer
generic
generic
generic
Lenzing
Performance, Enc.
PCA 1494- 052705
Protect -O -Wrap,
Inc.
PCA #94- 0714.01
W.R. Grace Co.
PCA #92- 1116.01
Frank Zuloaga
Roofing Product Control Examiner
n;. 16. 98 12 :12 FM PO4
Tin Caps
Tile Na::::
Product Dimensions
Mopping Asphalt N/A
Plashing Cement
Asphalt Primer
N/A
N/A
Roofing Nails rein. 12 ga. with PA 114
3 /g" head Appendix E
min. 32 ga.
min. 1 /g" o.d.
max.. 2" o.d.
min. 8d x 2%:" or
min. 10dx3"
cs:
Specifications
ASTM D 312
type III or IV
ASTM D 4586
ASTM D 41
PA 114
Appendix E
PA 114
Appendix E
Page 5 of 13
roc uct
Description
Manufacturer
Asphalt for bonding generic
a mineral surface
cap to a meth.
attached base sheet
in a double ply
underlayment
system.
Cut back, asphalt
based, asbestos
free, fiber
reinforced, trowel
grade cement for
repair and flashing
applications.
Cut back, asphalt
based coating used
to facilitate bonding
of dissim liar
materials.
Annular ring shank,
hot dipped, electro
or mechanically
ga1v. roofing nails
for use in
underlayment
attachment.
Corrosion resi
screw or smooth
shank nails for
additional tile
attachment at cave
tilt courses.
generic
generic
generic
Corrosion resistant generic
circular disc for use
in
underlayrnent
attachment
generic
Frank Zuloaga
Rooting Product Control Examiner
FEB 12 'S8 1C:2S 561 338 5391 PAGE.005
03. 16. 98 12:12 PM P05
Roof Tile Mortar
('Ti1eTite'TM")
Roof Tile Mortar
( "Quikrete® Roof
Tile Mortar #1140")
Roof Ti.: Mortar
("BONSAI.® Roof
Tile Me• gar Mix ")
Roof Tire Adhesive
(Polypro® AH 160)
Valley FI•snirsg
Drip Edge
EB 12 'SS 1e ;30
r
NIA
N/A
NIA
N/A
min. 26 ga.
min. 16" width
min..26 ga.
min. 2" face flange
min. 2" deck flange
Test
PA 123
PA 123
PA !23
ASTM A 525 Galvanized steel
valley flashing
PA 111 Galvanized steel
drip edge
Page 6 of I3
Product
L!S CJPLkU
Prepared mortar
mix designed for
mortar set roof tile
applications.
Prepared mortar
mix designed for
mortar set roof tile
applications.
Prepared mortar
mix designed for
mortar set roof tile
applications.
Manufacturer
Bermuda Roof
Company, Inc.
PCA H94- 0614.01
Quikrcte
Construction
Products
PCA #94- 0808.01
W.R. Bonsai Co.
?CA #940628.03
PA 110 Adhesive4 ...?olyfoam Products,
for use in roof tilt Inc.
applications. PCA%94- 0401.0I
generic
generic
Frank Zuloaga
Roofing Product Control Examiner
S
03. 16. 98 12:12 PM ^�P06�
Test money
The Center for Applied
Engineering, Inc.
The Center for Applied
Enigneering, Inc.
Redland Technologies
Professional Service
Industries, Inc.
IN 28 •S8 Ie:=8
TEST REPORTS
Test Identifier
9 4 -084
94 -060A
P063I -01
224 -47099
Page 7 of 13
Product Control No.: 96- 0528.06
Test Name/Report
Static Uplift Testing
PA 101
(Mortar Set)
Static Uplift Testing
PA 101
(Adhesive Set)
Wind Tunnel Testing
PA 108
(Mortar Set)
Physical Properties
PA 112
Frank Z1110 age
Rooting Product Control Examiner
03. 16. 98
Date
May 1994
March, 1994
July 1994
Sept, 1994
1 ?:12 PM P07
Deck Type:
Deck Description:
SYSTEM D:
Slope Range-.
Lh*dcriayment:
Roofing Tile:
CommecU:
3 12 '98 10:31
SYSTEMS
Page 8 of 13
Product Control No.: 96. 0528.06
Wood, Non - insulated
New construction 19/32" or greater plywood or wood plank.
Mortar or Adhesive Set Application
2 ":12" to 7 ":12"
Note: System D is only acceptable in Mb slope rang
Install choice of approved undertayment system, noted on Page 1 of Dade
County Protocol PA 120, in compliance with Section 3.02 of PA 120. See
Syster1 Limitation #6.
Install tile in compliance with PA 120 using one of the approved mortars or
- adhesives noted in this approval Mortar or adhesive shall be applied in
compl - iance with the mortar manufacturer's Roofing Component Product
Control Approval. The mortar or adhesive attachment shall provide sufficient. -
attacbment resistance expressed as a moment to meet or exceed the required
moment of resistance determined in compliance with PA 115 or PA 127. The
mortar and adhesive attachment data is noted in Table 3, attached.
1. For re-roof applications, 15 /32" plywood is an acceptable substrate.
2. For mortar set applications, the first three courses of tile shall be nailed with
not less than one nail per tile.. As an alternate, the first three courses of tile
shall be applied in mortar over a single layer of minimum 12 ga. wire mesh
with square openings of not Tess than 3 /8" which is mechanically attached to
the deck with not less than one roofing nail eve 1 ft For roof pitches from
6 ":12" to 7 " :12 ", every third tile of every fifth course, beginning at the eighth
course, shall be nailed with not less than one nail per tile.
Frank Zufoaga
Roofing Product Control Examiner
03. 16. 98 12:12 PM P08
.r• vv• �uu iv..ru CAA ..Vl JJO 0441
1 - The standard minimum roof pitch for Monier "Bermuda Flat" mortar set or adhesive set tile
applications is 2" rise in 12" run (2 ":12"). The maximum roof pitch for mortar set or adhesive set
tile applications is 7" rise in 12" run (7 " ;121.
2. Monier's "Bermuda Flat" tile profile has not been tested for tutu -on applications, therefore,
System A (Counter - Batten Nail-On Application), System 8 (Direct Deck Nail -On Application) and
System C (Horizontal Batten Nail -On Application) do not form part of this approval.
3. System installation shall be in compliance with the system specifications outlined in this Product
Conte -. Approval. Mortar set or adhesive set tile shall be attached using an approved mortar or
tile ,..rnesive noted in this approval, the data of which is noted in Table 3 of this Approval. The
method of attachment utilized shall provide sufficient attachment resistance expressed as a moment
to tweet or exceed the required moment of resistance determined in compliance with Dade County
Protocol PA 115 or PA 127.
i3 12 'S8 10:32
eufvitt( Llrrlrl'1Lk
SYSTEM LIMITATIONS
4. For mortar set applications, the first three courses of tile shall be nailed with not less than one nail
per tile. As an alternate, the first three courses of tile shall be applied in mortar or adhesive over -
single layer of minimum 12 ga. wire mesh with square openings of not less than 3 /g" which is
mechanically attached to the deck with not less than one roofing nail every 1 ft For roof pitches
from 6 ":12" to 7":12", every third tile of every fifth course, beginning at the eighth course, shall be
nailea with not less than one nail per tile.
5. For mortar set or adhesive set tile applications, a field static uplift test by a Dade County
accredited testing agency, in compliance with Dade County Protocol PA 106, shall be required not
Tess than 30 days after application to confirm tile adhesion. The results of this testing shall be
reported to the Building Official and the installer stating that the application has passed or failed PA
• 06 testing. If the application fails PA 106 testing, the report shall state which portion of the test
was failed; Category f (examination for loose tile) or Category 2 (uplift testing of tile). Subsequent
to icsting, the installer may repair not more than 5% of field area tiles and 10% of perimeter area
(.:. ridgehake) tile with approved tile adhesive. The installer shall place an identifiable marking on
each repaired tile for future reference. My PA 106 re -test shall not include any marked tile.
6. For mortar or adhesive set the applications, 30/90 hot mopped underlayment applications may be
instilled perpendicular to the roof pitch prior to June 1, 1995 unless stated otherwise by the material
auz: ufacturer. '!hereafter, 30/90 underlayment systems shall be installed parallel to the roof pitch in
compliance with Appendix 'A' of Dade County Protocol PA 120.
7. All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo for
;' '•'tification in the field. •
8. The Monier "Bermuda Flat" tile profile has been tested for both wind characteristics and static uplift
performance, therefore, attachment calculations for installation in compliance with Dade County
=rotocol PA 115 or PA 127 shall be done as a 'Moment Based System'
Page 9 of 13
BRADCO MIAMI e1009
Product Control No.: 96- 0528.06
uloaga
Roofing Product Control Examiner
SC s '7 70 S•7c T onrr
03. 16. 98 12:12 PM P09
SYSTEM LIMITATIONS
(Corrrrnv )
9. Applications for roofing permits shall include a completed Section 11 of the Uniform Building
Permit, a copy of Monier RoofTile's current specifications and details. a copy of this Product
Control Approval and a copy of the Product Control Approval of any Roofing Component used in
the proposed tik application. Reference shall be made to appropriate data for the required fire
rating.
10. The applicant shall retain the services of* Dade County certified testing laboratory to maintain
quality control in compliance with the South Florida Building Code and related protocols. Samples
taken shall be in compliance with Dade County Protocol PA 112, Appendix 'A'.
11. Any amendments to these provisions shall be in compliance with Sections 203 and 204 of the South
Florida Building Code.
=EB 12 '98 10 :3?
Page 10 of 13
Product Control No.: 96- 0528.06
Frank Zutoaga
Roofing Product Control Examiner
c r nnr. a e.
03. 16. 98 12:12 PM � P10
Table 2: Restoring Moments due to Gravity - U. (ft --1bf)
from PA 101 Tasting
Tile
Profile
3 ":12" or
less
4 ":12"
5":1x'
6":12"
7" :12" or
greater
. N/A
Monier
Bermuda
Flat Ti.a
5.20
5.12
5.01
4.89
Tile
Profile _
X (ft3) z
Batten Application
. (ft')
Direct Deck Application
Bermuda Flat Fiat Tile
NIA
0.24
Table 1: Aerodynamic Multipliers - (fe)
Tile
Profile
Monier Bermuda Flat Flat Tile
Tile
Application
Mortar Set
Adhesive Set
Attachment
Resistance
39.00
118.90
FE3 12 '88 10:33
Table 4: Attachment Resistance Expressed as a Moment - M (ft-lbf)
from PA 101 Testln
DATA FOR ATTACEIMENT
CALCULATIONS
from PA 108 Testln
Page 11 of 13
rank Zuioaga
Roofing Product Control Examiner
5S1 338 5351 PRt,F 211
03. 16. 98 1 '::^ PM P11
:=15 1:' • 0 0 . f7 . 77
PROF= DRAWING
Product Control No.: .96- 0528.06
BERMUDA FLAT FLAT TILE
Page 12 of 13
Frank Zuloaga
Roofing Product Control Examiner
03. 16. 98 12:12 P11 P12
Monier Roof Tile
135 N.W. 20th St.
Boca Raton. FL. 33431
NOTICE OF ACCEPTANCE STANDARD CONDITIONS
1 Renewal of this Acceptance (approval) shall be considered after a renewal application has been
filed and the original submitted documentation, including test supporting data, engineering
documents, are no older than eight (8) years.
2 An :nd all approved products shall be permanently labeled with the manufacturer's name, city,
state. and the following statement: 'Metro -Dade County Product Control Approved ", or as
specifically stated in the specific conditions of this Acceptance.
3 Renewals of Acceptance will not be considered iE
a) There has been a change in the South Florida Building Code affecting the evaluation of this
product and the product is not in compliance with the code changes;
b) The product is no longer the same product (identical) as the one originally approved;
c) • f the Acceptance holder has not complied with all the requirements of this acceptance,
; ncluding ttre cortrct1 taifation'of the product • " • —
d) The engineer who originally prepared, signed and sealed the required documentation Initially
submitted, is no longer practicing the engineering profession.
4 Any re•fision or change in the materials, use, and/or manufacture of the product or process shall
auton....:ally be cause for termination of this Acceptance. unless prior written approval has been
requ. sc-d (through the filing ofa revision application with appropriate fee) and granted by this
offIc• i.
5 Any of the following shall also be grounds for removal of this Acceptance:
a) Unsatisfactory performance of this product or process;
;‘) Misuse of this Acceptance as an endorsement of any product, for sates, advertising or any
,ther purposes.
6 The Notice of Acceptance number preceded by the words Metro-Dade County. Florida, and
follgwed by the expiration date may be displayed in advertising literature. If any portion of the
N.: ice of Acceptance is displayed, then it shall be done in its entirety.
7 A .op • :this Acceptance as well u approved drawings and other documents, where it applies,
sha• be provided to the user by the manufacturer or its distributors and shall be available for
inspe:tion at the job site at all times. The copies need not be resealed by the engineer:
8 Failure to comply with any section of this Acceptance shall be cause for termination and removal
or cceptance•
9 This Acceptance contains pages 1 through 13.
END OF THIS ACCEPTANCE
rrn ,-s ,nn ..+•
Page 13 of 13
Product Control No.: 96- 0528.06
ACCEPTANCE NO.: Qtt $.06
APPROVED : January 3. 1p9S
EXPIRES . Jannary S. 2Q91
Roofing Product Control Examiner
4(dvLJ
03. 16. 1 :1 PM''P13
'1-eTTFIO DADE
ISO
Polvloani PrOOU: s. !nc.
2.100 Spring Stuebner Roao
Spt tng, texas- .
IAETnOPOLifAN DAOE CZ;UNry,
METRO.OAOC PLAGLER BUIL;-
outLOtNG COOS COuvuAt.ic_ NEp^p•ry
SUR c
uE r n0.0AoE i U,GLER OIJ&
:40 vW€ T FLAGLER ST;
FLOR1t PC151
CONTltt)1. OF kCCFPTa Fnz
Your application for I'roduc: Appro'al of PolYfaam Products "Polvnrn AH -I60" Roof 'r•t_ • cih• -ivt • mac
C:laotcr 3 of the `.letropot.ta:t Dade County Code governing the use of Alternate Materials and Tr p.e
Construction. and completely described in the plans. specifications and calculations is submitted by The Cato '
Applied Engineering. Inc. and stiles Labor iories Polymers Olvision has been recommended for a:et:pun=
Me Building Code Compliance Department to be used tit Dade County, Horida under the specific and saute_
conditions set fortn itretn.
Th approval 01•1 be valid for a period of three years. The Building Code Compliance Departrnatt rr_erves
ri;nt 'o secure a product or material at any time for a jobsite or manufacturer plant for quality control testi.^.g..
pr oduct or matet ;al fail to perform in the approved manner. the Code Compliance De- r aruneat may revoke, rtoa:.
ur su•pcnd he us- of such product or material immediately. The Building Code Ccmpli anca 0 , tmatt r>rcr r
tltc r ight to require testing of this product or material should any uncidments to the south Florida Buiiding Cane
mot. u d affecting this product or material
experts-. of su =h testing will be incurred by the Manufacturer.
: :OOUCT NO. :
ACCEPTANCE NO.: 95-03[4:10
AP R 2 7 1998
EXPIRES:
l Rodripoi v
rodutx Control Division
Supervisor
- PLEASE NOTE -
TiiIS IS TILE COVERSHEET. SEE ADDITIONAL PACES FOR SPEC:F1C AND Gu`IERAL
CONDITIONS.
BUILDING CODE COMMITTEE
This applicatic'n for I' :o�u..t /•pproval 1•.2s been tev•et --d b-; :hi Moto, *�1' D.:de Curl; Building Cx
Compliance Oep;.rtt.l, a•id a«ro•ieJ Cy the 0utldin6 Cc,dc Committee to be used in Ozde County. Florida un:t
the conditions sct fonit above.
APPROVED:
APB 2 1995
V
Sundial; Ca•M C: same :ace Departma e
Meuopaiitrr C-xs C„-unry
.- >nolicant;
Polyfonn► Products. Inc.
2300 Spring - Stuebncr Road
Sprin„ Texas 77333 -1132
Cate ?ors•• Roofing Component
Sub- Catc;:orv Fastening Adhesive
Tyne Roof Tile Adhesive
Sib -Tvpe• Two Component Polyurethane
L K V 1)1.JI. V,• I..VL At../ 1 . — • • ••
ROOFING COMPONENT APPROVAL
System Description
Polyfoam Products, Inc., produces two- component expanding polyurethane adhesive for the attachment
of clay and concrete roof tile. Polypro® AH I60 is specially designed for application of concrete and
clay roo.` ::I: over a ••^ii -ty of roof deck substrates and underlayment materials.
Polypro® adhesivc is applied with proprietary Foampro® RTF1000 dispensing equipment. Approval of
this pro'luc! is specific to the two component mix and Foampro® RTF1000 dispensing equipment.
1- :ternative methods of dispensing will require a revision to this approval.
Polypro® adhesiv.: shz.l: be applied only by 'Qualified Applicators', licensed by Polyfoam Products. Inc.
C - rtific: tea and identification cards are issued w applicators upon successful completion of a application
training N.igram. Approval of this adhesive system is contingent upon application by a 'Qualified
Applicator.
Contact:
Pat Murray
P.O. Box 1 132
Spring. Texas 77383-1132
(713)350 - 3838 Fax: (713)288 -6
1
p- - --
R��I Rkounguez
Product Control No.. 95 -0114 to
.Approval Date: APR 7 7 1905
Expiratid?i Date: APR 7 7 egg
Test Product
Product Dimensions Specifications Description
Polyoro® .AH 160 VIA PA 101 Two component
polyurethane
Foarnpro® RTF
TRADE NAMES OF PRODUCTS t`IANUFAL L./Rt.') vi<
LABELED BY APPLICANT
VIA See Detail Attaciicd Dispensing Equipme^t
2
Product
Underlayment
Root' Tile
l l��"\ ✓ L \ 1• 1 1— —7 V a l \L/ 1 1 J 1• -• • • "'
Test Criteria
PA 120
Product Description
All Dade County Component Approved
products as detailed in Dade County
.Application Standard PA 120
3
R- • di tZorrtgur
PA 101 All .Approved roof tile systems having
tested in compliance .vith Dade County
Protocol PA 101. as detailed in the systems
section of this Component Approval
Manufacturer
All Dade
County
Approved
Products
All Dade
County
A pproved
P roducts
Test ,Aacncv Test Identifier Test Name/Renort
Center for Applied a 94 -J60 Metro Dade Protocol
Engineering PA 101
Miles Laboratories - '�C N6- 559.631
Polymers Division
ASTN1 D (623
TYPICAL PHYSICAL PROPERTIES
rroperry Tcst
Density ASTN1 D 1622 1.6 lbs. /1t.
Results
Compressive ASTM D 1621 18 PSI Parallel to rise
Strength 12 PSI Perpendicular to rise
Tensile Strength ASTM D 1623 28 PSI Parallel to rise
\`/ %ter Absorption ASTM D 2127 0.03 Lbs. /Ft
Plcisture Vapor ASTM E 96 3.1 Perm / Inch
Transmission
Dimensional
Stability
Closed Cell
Content
ASTM D 2126
ASTM D 2856 86%
+0.07% Volume Change @ -40' F.. 2
weeks
+6.0% Volunte. @ 1 SS'F.. 100%
Humidity. 2 weeks
at
0
02:01/94
Note: The physical properties listed above arc presented as typical average values as determined
by accepted ASTM test methods and arc subject to normal manufacturing variation.
4
1
Rail :tc,d1
. Deck Type: Wood. `:on- insulated. New ConstructioniRereof
Deck Description: New construction /,:" or greater plywood or %vood plank.
Re -roof ':,:" or greater plywood
Adhesive Srt ,Application
SYSTEM .A:
Slope :Ling.::
Lndcrlavmcnt:
Roofing Tilc:
Install choice of Approved underlayment system, noted on ?ag. o f D
County Protocol PA 120, in compliance %vith Section 3.02 of PA !
Install :approved tile system in compliance with PA 120. Adhesive shall be
applied in compliance with the Component Application section and the
corresponding Placement Details of this Rooting Component Product Control
Approval. The adhesive attachment shall provide sufficient attachment
resistance expressed as a moment to meet or exceed the required moment of
resistance determined in compliance with PA 115 or PA 127. The adhesive
attachment data is noted in the tile Roof System Assembly Product Control
Approval.
Cuttir.t:nt�:
I. For re - roof applications. minimum " /,:" plywood is an acceptable substrate.
2. All 'System Limitations' noted in the tile Roof System Assembly Product
Control Approval shall apply.
Rau(Rodriguez
Y5 1
(CONTINUED)
Deck Type: Concrete. New Constr'.iction /Reroof
Deck Description: New construction
SYSTEM 0: . Adhesive Set Application
Slope Range: I to
Undcrlaymcnt / Install .Approved underlayment system of one of the following:
Waterproofing:
Roofing Ti:c:
Undedaymcnt System 4. (30/90 Hot Mop) noted on Page 1 of Dade Count./
Protocol PA 120. installed in compliance with Section 3.02(A) of PA 120
or
Any .Approved urethane or asphalt based concrete waterproofing component
installed in compliance with the waterproofing component manufacturer's
Roofing Component Product Control Approval.
Strips of reinforcing fabric shall be installed at all concrete deck joints.
Install Approved tile system in compliance %with ('A 120. Adhesive shall be
applied in compliance with the Component Application section and the
corresponding Placement Details of this Roofing Component Product Control
Approval. The adhesive attachment shall provide sufficient attachment
resistance expressed as a moment to meet or exceed the required moment of
resistance determined in compliance'ith PA 115 or PA 127. The adhesive
attachment data is noted in the tile Roof System Assembly Product Control
Approval.
Comments: I. For re -roof applications, minimunt " /,;' plywood is an acceptable substrate.
2. All 'System Limitations' noted in the tile Roof System Assembly Product
Control Approval or waterproofing component Roofing Component Product
Control Approval shall apply. as applicable.
Ra��l • odrigucz
r ble 1: Adhesive Placement For Each Generic Tile Profile
Tile
Profile
Placement
Detail
Two-Piece Barrel .
# I
'S' Shaped
tl2
Double Roll
03
Large Flat
ad
Small Flat
a
ir(J,.t.'s, 1 1t "YL�t.� •�,.
Polvoro® Al (de adhesive shall only be applied over an underlayment installed in compliance
%vith application instructions detailed in its Component Approval.. Under!ayment shall be any
underlarniettts or underlayment systems listed as Approved in Dade County Protocol PA 120.
Adl'�esiv,� ACstion shall to in accordance with the instructions provided in this Component
Approval. fie manufacturer may provide additional instructions subsequent to this approval date
which shall prevail Installation must be by a Factory Trained 'Qualified Applicator' approved and
licensed by Poi:. (. am Produc :s. inc
3. Calibration of the Foamprc0 dispensing equipment is required before application of any adhesive.
The mix ratio 5etwcen the "A" component and the "8" component shall be maintained between
1.0 -1.15 (.A) : 1.0 3). The dispense timer shall be set to deliver 0.08 to 0.15 pounds per the as
determined at calibration No other settings shall be approved without revision of this Component
Approval.
4. Adhesive shall be dispensed in a 17 in' to 23 in' pad at time of application. The cured pad shall be
approximately 5" x 12 ". Foam placement shall be in accordance with the 'Placement Details'
provided in this Component .Approval. Each generic tile profile requires a specific placement, as
noted in Table 1, b :!o■v. A tile manufacturer may test a tile system in compliance with PA 101 and
add ,n : dditic'uual detail without incurring an additional revision cost.
Aah -re rile directly in freshly applied adhesive. Tile must be set within 2 to 3 minutes after foam
has Leen dispe.sed.
F Adhesive shall be placed w create contact with minimum 2 tiles. as outlined in the ' Placement
Detail' 'or ea�ct tile profile.
711_ .?y
Raul Rodrieuez
I DETAILS
• AH
(--• u0R'AR 9C1
roq COKR ttLC
COVER
\ uCTAL C!r ORIP
=cute'
•I, clo•uc=
cCtional tASC1A OOARO
point-up uoc_ac
x 10 - • roar Pad
then appllad
2X4 ON (OCC
• - N(SI poi M. ;E
(*WA ACO1fOV
NAVNC 1S RECLIAZO
IT COOC)
2' % 10- "o ?cd
Than applied
NJUI COK.t NCR(
• (0401 RC:VIRCO)
?I.lcc.nci Cu.uI NI: T.v -riccc 3arrcl ['-odic
Raul I 'odrigucz
•
i ASQA /
ECARO —
101 uINEFIAL SU °FACS
Ac_F'•HO FELT
Z - 10'
Tor. Pad
i:he:l eppLIed
(EPOu). PREFABRJCATEO
CLOSURE NAILED THROUGH
PLASTIC ROOF C£UCI4T OR
INTO APPROKO AOHCSIVE
It LAN 1 lwUC.
YtEEPHOLE
Placement Dctail #2: 'S' Shaped Tilc Profile
10 '
Raul driguez
NAIL XCPC :44ACL;C)
PLASTIC RCCT CLUEJ+t
(WEN A001 i1CYAL xaIU!
IS RECUtRE0 8Y CCCE)
"*.C. CLAP
c„nC� SOAAO
SCCURE .M
CCRRO 1ON
RC
HA..S
Sealant
or
POC1T -UP I,Ir14 : CLORLO
uoRTAR TO uATC4 T1.0
SURFACE
ROLLED RAKE "Lt
(SPANISH 'S' CU:S,
Test Location
Uplift Pull
Test (P or F)
Test Location
Uplift Pull
Test (P or F)
Test Location
Uplift Pull
Test (P or F)
1
)
26
-
51
2
27
52
3
28
53
4
29
54
5
30
55
6
31
56
7
32
57
8
33
58
9
34
59
10
35
60
11
36
61
12
37
62
13
38
63
14
39
64
15
40
65
16
41
66
17
42
67
18
43
68
19
44
69
20
45
v
70
21
46
71
22
47
72
23
48
73
24
49
74
25
V
50
75
Owner's Name:
Job Address'
Du Quesne & Associates, Inc.
Consulting Engineers Environmental • Civil • Structural
Testin Laborator Buildin Inspection Services
ON -SITE CONCENTRATED UPUFT LOAD TESTING OF ROOF TILE
IN ACCORDANCE WITH METRO-DADE BUILDING CODE COMPLIANCE
PROTOCOL PA 106
SITE SPECIFIC INFORMATION
1JbJ7 elte0 a . / C. ..rNITTR € Permit #. 35c28 6/
8107 Old . 9 / Terr-. /A . SHr) tFF.s
A) O \JO °R • I iv.Q O
Type of Tile: V ...../.. NIP -. • LA Date Installed* ��
Approximate Roof Height /T feet Roof Pitch 3 [!a
Type of Access to Roof: Scaffolds ✓ Ladder Other
Approximate Square Footage of Roof* 2 ft 2
Required Testing Force: 35 lbs. Testing Equipment: Chatillion DFIS 100
Date Tested* /8/98
Roofing Contractor
Du Quesne, P.E
ngineer
P. 4513
Du •uesne & Associates, Inc.
E.B. License #0005245
Lab Certification #94-0318.01
TEST RESULTS
P = PASS, F = FAIL
SKETCH OF ROOF IN BACK
IN ACCORDANCE WITH THE CRITERIA OF PROTOCOL PA 106, THIS ROOF ASSEMBLY HAS PASSED THE STATIC UPLIFT
QUALITY CONTROL TEST.
7821 S.W. 24th Street • Suite 104 • Miami, Florida 33155 • Telephone (305) 264 -1425 • Fax (305) 264 -1426
UTR 14309
THIS PA 106 TEST HAS BEEN PERFORMED IN FULL ACCORDANCE TO THE
REQUIREMENTS OF DADE COUNTY, WITH NO DEVIATIONS.
Please Note: This form is not valid unless
Company logo appears in
color (burgundy)
KETCH OF ROOF
JOB
SHEET NO OF
CALCULATED BY
CHECKED BY DATE
SCALE
DATE
AC;
NOTES'
•
KETCH OF ROOF
,OB 8'67 /v. E. 7/ rir • , A4 b4-41/ 5//o, ss
SHEET NO Z OF 2
CALCULATED BY 7- ` .D DATE C •- le -9,
CHECKED BY DATE
SCALE
‘reo
33
\IN
NOTES.
❑ PERMIT N? 15159
BUILDING
ELECTRICAL
PLUMBING
ROOFING
Owner of
Building
Er Work to be performed under this Permit
Architect
Contractor .., "" .%
or Builder ‘... -' ''
Legal Lot II
BI.
Description
Address of
Building f, ‘ k... .
CONTRACTOR OR BUILDER
MIAMI SHORES VILLAGE, FLORIDA
Subdi-
vision
Value of
Project $
;;• f
DATE -- 195 a ,
Contractor's
License No
Amt. of
Permit
$
This permit is granted to the contractor or builder named above to construct the building or to install the equipment or device described in the application
herefor in strict compliance with all ordinances pertaining thereto and with the understanding that the work will be performed in compliance with any plans,
drawings, statements or specifications that may have been submitted to and approved by the proper municipal authorities. This Permit may be revoked at any
time if the work is not done in compliance with such ordinances or if the plans are changed without authorization. A further condition upon which this permit is
granted is the understanding that the contractor or builder named above assumes the responsibility for a thorough knowledge of the ordinances and regulations
pertaining to the work covered hereby whether shown on the plans or drawings or in the statements or specifications and that he assumes responsibility for work
done by his agents, servants or employees.
Signed: y . .• _, BY
INSPECTOR
• n consideration of the issuance to me of this permit I agree to perform the work covered hereunder in compliance with all ordinances and regulations
-to and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores Village.
is permit I assume responsibility for all work done by either, myself, my agent, servant or employee.
BY AUTHORITY
STATE OF FLORIDA,
COUNTY OF DADE. ss.
MIAMI SHORES VILLAGE
BUILDIN7, INSPECTION DEPARTMENT
APPLICATION FOR BUILDING PERMIT
Application is hereby made for the approval of th' det,iled statemen of the plans and specifica-ions herewith submitted for the build-
ing or o h, -ructure her 1 described This 1 licatic is made in compliance and cow° m ty w.th the Building Ordinance of Mia
Shores Villaee, or da, and all pro isions of the Laws f the Stat& cf 1.1..rid. all o d nances if Mi - ni Shores Village and all rules and
regu a ion. of the Building Div . i of -lam Sho. illage 1- '1 ,e -0, ipl.ed with, whether herein specified or not. A copy of approved
plans and specificati .ns must be kei• at bui.ding durin, progress of tl.e wcrk.
Date 8/31/53 , 19
Owner' Name and Address.__RallSea. No 867 street_ NE 91 Teri-,
Registered Architect and/or Engineer. Dick Besola.
Name nd address of licen.,ed contractor. Lang Roofing and Tile Co 430 N. W. 79th St.,
Location and legal description of lot to be built on:
Lot Block. Subdivision
Street and Number where work is to be done. 867 B..__B.s___9lat Tarr—, Miami Shores.
State work to be done and purpose of building (by floors)
_ and for no other purpose.
New Building. X Rernodeling Addition_ .... ___ ..... __ _ Repairs. _ . . No. of Stories
To be constructed of ___ _ _ Kind of foundation ___ Roof Cov ling__ Shingle Tile_
Estimated 7 - ,tal cost of improvements $__ 650.00 Amount c Permit $._ 5.00
Zone ^ubage required __. __Plan Cubage
Distance to next nearest building__ _ _ Size of Building Lot
Maximum live load to be borne by each floor _ . ..... ___
hereby submit all the plans and specitic.ations for said building. All notices with reference to the building and its construction may
be sent to
The unde signed appli ant for tit's building permit does hereby certify Clat he understands and accepts his Aligations as an employer
of 1 bor under he Florida Workmen's Compensation.Act being S. -tion 5966 Coi p led Gen al Laws of Florida P r anen Sipple 'tent,
and h s compl ed w'th he provions thereof, and will require s.milar comp lance from all contractors or sub-contractors emplo .ed by him
in the wo k to be p rt med under th s pern it and ill post or cause to be posted for inspection on the site of the work su :h public not' e
cr •otit.es as are requir d by the Act. The u. d. r ign .d agrees to employ only such_ abcon. ctors. on wo6c (to he narforn, d der this
permit as are licensed by M am. Shores ge. Lang Roofing and kiie
Remarks. _ (Signed) C •
Before me, the undersigned authority, a notary public, duly authorized to administer oaths ..nd take acknowledgments, personally op-
.
pearecl _
to me well known,
and who, being by me first d. ly sworn, upon oath deposes and says that he is the
of th abov de & ibed • istruction t h has careially read the foregoing application, and that he did sign the same, and that all facts
therein by him stated are tr ie.
Permit No / _ Date__ Read, Sworn to and Subscribed before me.
Disapproved Date_
A !"\
R Notary Public State of Florida
(Signed)
Chairman
Member
Member _
Council A proved
C Building Inspector
PLANNING BOARD DATE
Member
Member
Member
Date Disapproved
My Commission Expires.
Date
. .
Ne E: A charge of $1.00 will be made for making corrections or 21ianges to this application Ifter approval h is hecn obtained from
the ant- ng Board
A re-Inspection fee of $1.00 will be charged when such re-inspection is m. le necessary by improper notice for inspe..t-or or fa. Ity
iaterials and workmanship.