Loading...
ELC-11-54 (2)GENERAL ELECTRICAL NOTES 1, THE ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), AND THE LATEST EDITIONS OF ALL LOCAL CODES, RULES AND ORDINANCES HAVING JURISDICTION. 2. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR TYPE OF EQUIPMENT AND INTENDED USE, OF THE FOLLOWING: a. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). b. ILLUMINATING ENGINEERS SOCIETY (IES), c. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM). d, NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA). NOTE: THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY U.L. 3. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES, 4, THE CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK, 5. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM DATE OF ACCEPTANCE, U.O.N.. 6. IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECI- FICATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 7, THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING TO ORIGINAL CONDITIONS, ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, ETC. CAUSED DURING THE PERFORMANCE OF WORK. 8. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE OR DELAYS AND SHALL INCLUDE REPLACE- MENT OR REPAIR OF' ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 9. THE CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN OR NOTED ON THE DRAWINGS, PRIOR TO SUBMITTING BID. 10, THE CONTRACTOR SHALL NOT SCALE THE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE, 11, IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE PLANS, 12. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCE ORDERING OF LONG LEAD ITEMS, AS TO NOT INTEFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. THE CONTRACTOR SHALL NOT ORDER ANY ITEMS UNTIL APPROVED SHOP DRAWINGS ARE RETURNED TO HIM, 13. THE CONTRACTOR SHALL KEEP ALL AREAS WHERE WORK IS BEING PERFORMED FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EACH WORKING DAY. 14, ALL CONDUCTORS SHALL BE COPPER, TYPE THHN/THWN EXCEPT WHERE OTHERWISE REQUIRED BY U.L. OR CODES. MINIMUM WIRE SIZE SHALL BE #12 AWG. EXCLUDING CONTROL WIRING. 15. ALUMINUM CONDUCTORS ARE NOT PERMITTED ANYWHERE. 16. ALL CONDUCTORS SHALL BE IN 3/4" MIN, CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID STEEL (GRS) EXCEPT THAT: (a) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED ELBOWS AND RISERS ARE GRS, WHERE SUBJECT TO PHYSICAL DAMAGE (b) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR CORROSIVE CONDITIONS. (c) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED. (d) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS ONLY. ALL CONDUITS IN HAZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. 17, ALL CONDUIT RUNS ARE SHOWN DIAGRAMATICALLY. THE EXACT ROUTING SHALL BE DETERMINED IN THE FIELD. UNLESS NOTED OTHER- WISE. 18. WHERE CORE DRILLING OF FLOORS /WALLS IS REQUIRED, THE CON- TRACTOR SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE - BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER THAT IS CLEAN AND FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE CONDUIT. 19. PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENE- TRATIONS, WALLS AND STRUCTURAL SLABS. IT SHALL BE THE RE- SPONSIBIUTY OF THE ELECTRICAL CONTRACTOR TO VERIFY PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE RATED PART- ITIONS, WALLS, AND STRUCTURAL SLABS. 20. UNLESS NOTED AS EXISTING. ALL EQUIPMENT, WIRING. DEVICES. ETC. SHALL BE NEW. 21. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMODATE EQUIPMENT SERVED, INCLUDING REQUIRED FUSES U.O.N. SWITCHES SHALL BE HORSEPOWER RATED FOR MAX. HORSEPOWER, HEAVY DUTY TYPE. 22. THE CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATINGS FOR EQUIPMENT PRIOR TO INSTALLATION. 23. ALL FUSES SHALL BE CURRENT UMITING, PER U.L., RATED 600V. OR 250V, AS REQUIRED, WITH: (o) NON TIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. (b) TIME DELAY FUSES FOR MOTOR AND HVAC CIRCUITS. 24. WIREWAYS SHALL BE SIZED AS REQUIRED, PER NEC, U.O.N. 25. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL - MAGNETIC). TWO AND THREE POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. TIE HANDLES ARE NOT PERMITTED. 26. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R) WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE UQUIDTIGHT. 27. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED FOR OTHER CLASSIFIED AREAS. U.O.N.. 28. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH U.L. APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE, THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM AS PER NEC 250 -50. 29. THE CONTRACTOR SHALL SUBMIT 6 COPIES OF EQUIPMENT SHOP DRAWINGS FOR ELECTRICAL EQUIPMENT TO THE ENGINEER FOR REVIEW, PRIOR TO ORDERING SUCH EQUIPMENT, 30. PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PLASTER RINGS SHALL BE A MAXIMUM OF 1/8" FROM THE FINISHED SURFACE OF THE DRYWALL AFTER THE DRYWALL IS INSTALLED. PROPER COORDINATION BETWEEN THE ELECTRICAL CONTRACTOR AND THE GENERAL CONTRACTOR FOR RING INSTALLATION IS RE- QUIRED. NO "GOOF" RINGS WILL BE ALLOWED. ALL OUTLET BOXES SHALL BE SECURELY FASTENED. ANY AND ALL IMPROPERLY INSTALLED PLASTER RINGS OR OUTLET BOXES SHALL BE REMOVED AND A NEW RING OR OUTLET INSTALLED AT THE CONTRACTOR'S EXPENSE. SYMBOL 0 3 ELECTRICAL SYMBOL LEGEND DESCRIPTION CEIUNG OUTLET BOX AND DUPLEX RECEPTACLE 20A, 125V. JUNCTION BOX, MOUNTING AS SHOWN ELECTRICAL BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED. (SEE PANEL SCHEDULE FOR DETAILS) CONDUIT WITH WIRES CONDUIT TURNING UP CONDUIT TURNING DOWN CONDUIT STUB CONDUIT CONTINUED fluszemaxemzumessimp LOW VOLTAGE GENERAL NOTE 1. DATA CABLES SHALL NOT RUN MORE TI-IN 300FT FROM ETHERNET HUBS TO ANY FINAL POINT OF LED CONTROLLER CONNECTION. ADDITIONAL EQUIPMENT SHALL BE INSTALLED TO ALLOW MORE THAN 300FT DATA CABLE RUNS. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT FOR ADDITIONAL EQUIPMENT TO BE INSTALLED. ELECTRICAL INDEX DRAWING E -001 ELECTRICAL INDEX, SYMBOL LEGEND AND NOTES. 2 E -101 ELECTRICAL. SITE PLAN 3 E -201 KOLASA/GARNER/ ANDREA AND LIBRARY (1ST FL) ELECTRICAL FLOOR PLAN 4 E -202 POWER /ADRIAN AND WEIGAND ELECTRICAL FLOOR PLAN 5 E -203 UBRARY (GROUND AND 3RD FL) /FINE ARTS ELECTRICAL FLOOR PLAN 6 E -301 PANEL SCHEDULES SHOP DRAWING REQUIREMENTS 1, CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3. SUBSTITUTIONS SHALL BE UNITED TO ONE OF THE ALTERNATES USTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR LT SHALL BE REJECTED. 6. CIRCUMSTANCES, NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND ,DELNERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION MID /OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. /35THWIEn AA JAN 1 1 2011 BY: Miami Shores Village APPROVED BY DATE ZONING DEPT BLDG DEPT 5,y2.- Il SUBJECT TO COMPLIANCE WITH ALL FEDERAL STATE AND COUNTY RULES AND REGULATIONS Manuel Synalovski Associates, LLC 1800 Eger Drive, Suite 500 Fort Lauderdale, R 33316 Telephone . 954.9616806 Facsimile 954.961.6€07 V W V W.S)R18lOMSki.com ItifEEMMESSEUIZEIEANSEMISSINSZSZISSMOO z t7) ism= 22 re: � of „teton w z z N w z 8 M CLIENT: BARRY UNIVERSITY REY DATE DESCRIPTION DESIGN DELIVERABLE: ISSUE TYPE ISSUE DATE: 10-14:2010 PROJECT NUMBER: DRAWN BY: DS CHECKED BY: MV SHEET TITLE: ELECTRICAL INDEX, SYMBOL LEGEND AND NOTES SHEET NUMBER -001 N.W J 1 1 51-h ST. KEY NOTES O APPROXIMATELY LOCATION OF MASS NOTIFICATION SYSTEM SPEAKER ARRAY. (2 APPROXIMATELY LOCATION OF MASS NOTIFICATION SYSTEM ULTRAVOICE CONTROLLER DEVICE IN 3rd FL. MECHANICAL ROOM BELOW. REFER TO DRAWING 2 IN SHEET E -203 FOR ADDITIONAL INFORMATION. N �- . _ _ ter"T, ,-.� -E-E ��T T • f e WA Q r UMW N111 Mr *Alt CAA LLBRARY • D Ll HMAN S UILL rip ,/ L GRASS SOCCER FIa.D u w z w 13 c N U 0 L J c n v r 1 r -1E-) 1. J L GRASS SOCCER FIELD 0 DUNSPLUGH ROUST L J PNI95611 inn N. E. 1 1 1 t h STREET OVERALL SITE KEY PLAN SCALE: NOT TO SCALE Manuel Syt'1a1ovski Associates, LLC 1800 Eller Drive, Site 500 Fort Lauderdale, FL 33316 TelephOrne 954.9616806 Facskile 9549616807 WWW�tynalovsk6.com 0 z P tin '4< ,woo 11300 NE 2ND AVENUE MIAMI SHORES, FLORIDA 33161 -6695 CLIENT: BARRY UNIVERSITY DATE DESCRIPTION DESIGN DELIVERABLE: ISSUE TYPE ISSUE DATE: 10 -15 -2010 PROJECT NUMBER: DRAWN BY: DS CHECKED BY: MV SHEET TITLE: ELECTRICAL SITE PLAN SHEET NUMBER E -101 PANEL "2EM" LOCATED IN CLOSET IN KITCHEN AREA SECOND FLOOR NEW 300W UPS. FIELD COORDINATE FINAL LOCATION. Manuel Synakovski Associates, LLC 1800 Eller Drive, Suite 500 Fort Lauderdale, FL 33316 RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. CORD WITH PLUG Telephone 95449616806 Facsimile 954.961.6807 wWw.synaQovski.com LED CONTROLLER MOUNTED ABOVE CEILING 1/2 "C WITH 2 #12, 1 #12 GND. — TO LED RECEPTACLE. FIELD COORDINATE FINAL CONDUIT RUN. RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. L -20 (THRU 500W UPS IN MECHANICAL ROOM) DATA CABLE TO ETHERNET HUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. 1/2 "C TO LED RECEPTACLE BELOW, FIELD COORDINATE FINAL CONDUIT RUN, ELECTRICAL ROOM ALTERNATE PANEL "GLR" WITH SPACE ON CIRCUIT 25 1/2 "C WITH BRANCH CIRCUIT TO MECHANICAL ROOM IN THIS FLOOR. REF R TO DRAWING 4 IN SHEET E -203 FOR -5 ADDITIONAL INFORMATION. —� DATA CABLE TO ETHERNET HUB IN MECHANICAL ROOM THIS FLOOR. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. 3/4 "C FOR LED DATA CABLE FROM 1ST FLOOR CEILING TO GROUND FLOOR STRUCTURAL CEILING. FIELD COORDINATE FINAL CONDUIT RUN. ELECTRICAL ROOM PANEL "LP1" NEW 300W UPS MOUNTED ON WALL WITH SUPPORT BRACKETS. 1/2 "C WITH 2 #12, 1#12 GND. TO LED RECEPTACLE. FIELD COORDINATE FINAL CONDUIT RUN, LED CONTROLLER MOUNTED ABOVE CEILING Z 21 11300 NE 2ND AVENUE MIAMI SHORES, FLORIDA 33161 -6695 > z NEW 300W UPS MOUNTED ON WALL WITH SUPPORT BRACKETS. FIELD COORDINATE FINAL LOCATION. RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. PANEL "T2" CORD WITH PLUG 1/2 "C WITH 2 #12, 1 02 GND. Ls TO LED RECEPTACLE. FIELD COORDINATE FINAL CONDUIT RUN CORD WITH PLUG ELECTRICAL ROOM REV DATE DESCRIPTION RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. DATA CABLE TO ETHERNET HUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. • DATA CABLE TO ETHERNET HUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. DESIGN DELIVERABLE: ISSUE TYPE ISSUE DATE: 10 -15 -2010 PROJECT NUMBER: DRAWN BY: DS CHECKED BY: MV SHEET TITLE: KOLASA/GARNER/ ANDREA AND LIBRARY (1ST FL) ELECTRICAL FLOOR PLAN LED CONTROLLER MOUNTED ABOVE CEILING SHEET NUMBER GARNER = UILDING ENLARGED FLOOR PLAN KALE: 1 /a' • 11-0' E -201 PANEL "AC" CONFERENCE ROOM 113 CORD WITH PLUG NEW 3.OKVA 277V-120V TRANSFORMER 1/2 "C WITH 2 #12, 1 #12 GND. TO LED RECEPTACLE. FIELD COORDINATE FINAL CONDUIT RUN. NEW 300W UPS. FIELD COORDINATE FINAL LOCATION. RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. CHEM. L , B RDDM 1 *3 ELECTRICAL ROOM C -EN. LAB R -IIM 103 RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. DATA CABLE TO ETHERNET HUB IN 1::. BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. S DEPARTMENT. LED CONTROLLER MOUNTED ABOVE CEILING DATA CABLE TO ETHERNET HUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. LED CONTROLLER MODUNTED ABOVE CEILING PANEL "G" 1 /2 "C WITH 2 #12, 1 #12 GND. TO LED RECEPTACLE. FIELD COORDINATE FINAL CONDUIT RUN. CORD WITH PLUG MAIN ELEC. ROOM ON GROUND FLOOR NEW 300W UPS MOUNTED WITH SUPPORT BRACKETS ON EXTERIOR WALL OF ELECTRICAL ROOM. FIELD COORDINATE ANAL LOCATION. bni•111141111j I 1D47IP .— ALTERNATE PANEL "NL1 —A" WITH SPACE ON CIRCUIT 10. NO TRANSFORMER REQUIRED IF BRANCH CIRCUIT IS TAKEN FROM THIS PANEL. HOWEVER, RUNNING THE CIRCUIT CONDUIT THRU BUILDING STRUCTURE COULD BE CUMBERSOME. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO BID. UPS CAN BE LOCATED INSIDE ROOM MOUNTED ON WALL WITH SUPPORT BRACKETS. ALTERNATE PANEL A. WITH SPACE ON CIRCUIT 35. NO TRANSFORMER REQUIRED IF BRANCH CIRCUIT IS TAKEN FROM THIS PANEL. HOWEVER, RUNNING THE CIRCUIT CONDUIT THRU BUILDING STRUCTURE COULD BE CUMBERSOME. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO BID. LOCATION OF UPS SHALL ALSO NEED TO BE COORDINATED IN A MORE SECURE ROOM. ELECTRIC L CLOSET KEY PLAN 3CAlLE: LT.3. ADRIAN HALL /NHSB BUILDING ENLARGED FLOOR PLAN SCA�e •.✓8', : r -0 ItUturLAN TIE TO WEST LED SIGN RECEPTACLE CIRCUIT RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. °— ---- RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. RECEPTACLE ABOVE -- ---'�" CEILING FOR LED AND CONTROLLER POWER, DATA CABLE TO ETHERNET HUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. PANEL DATA CABLE TO ETHERNET HIUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY LT. DEPARTMENT. LED CONTROLLER MOUNTED ABOVE CEILING 1/2"C WITH 2#12, 1#12 GND. TO LED's RECEPTACLES (WEST & EAST). FIELD COORDINATE FINAL CONDUIT RUN. CORD WITH PLUG ELECTRICAL ROOM 161 LED CONTROLLER MOUNTED ABOVE CEILING NEW 500W UPS MOUNTED ON WALL WITH SUPPORT BRACKETS. DESIGN DELIVERABLE: ISSUE TYPE ISSUE DATE: 10 -15 -2010 PROJECT NUMBER: DRAWN BY: DS CHECKED BY: MV POWER/ADRIAN AND WEIGAND ELECTRICAL FLOOR PLAN . ENLARGED FLOOR PLAN - EAST VESTIBULE POW SCALE. V$ • ER-0 S BUILDING Y POWERS BUILDING ENLARGED FLOOR PLAN - WEST VESTIBULE SCALE: 1/11' ' Y-A" 1/2"C WITH 2 #12, 1#12 GND. PANEL. "L„ NEW 3.OKVA 277V -120V TRANSFORMER NEW 500W UPS MOUNTED ON WALL WITH SUPPORT BRACKETS. CORD WITH PLUG 1/2 "C WITH 2 #12, 1 #12 GND. TO LED's RECEPTACLES LIBRARY ENLARGED FLOOR PLAN 1Al.IE;` 1/8" a 9'-®" I.T. SERVER AND ETHERNET HUB. 3/4 "C FOR DATA CABLES FOR 2 LED's, FIELD VERIFY FINAL CONDUIT RUN. REFER TO DRAWING 3 IN SHEET E -201 AND DRAWING 1 THIS SHEET FOR ADDITIONAL INFORMATION. FILL WALL SPACES AROUND CONDUIT WITH 2—HOUR FIRE RATED MATERIAL. PROVIDE INSULATING BUSHING AFTER CONDUIT WALL PENETRATION. RUN DATA CABLE ON 1ST FLOOR CEILING TO NEW LED CONTROLLERS. FIRST FLOOR MASS NOTIFICATION EQUIPMENT: ULTRAVOICE WITH AMPLIFIER, MODEL UV400, AND BACK UP BATTERIES. PANEL "N" t J. I.T. SERVER AND ETHERNET HUB. NEW 3.OKVA 277V -120V TRANSFORMER 1/2"C WITH 2 #12, 1#12 GND, N -2 3/4 "C FOR DATA CABLE. FIELD VERIFY FINAL CONDUIT RUN. RUN APPROXIMATELY 150' OF 1" PVC SCH. 40 CONDUIT FOR SPEAKER ARRAY MODEL DSA. SPEAKERS MOUNTED ON ROOF ABOVE. REFER TO SITE PLAN SHEET E -101 FOR ADDITIONAL INFORMATION. LIBRARY ENLARGED FLOOR PLAN - THIRD FLO $GALE: 1/8" s Y-G" FINE ARTS SCALE; t/! T-o" A -5B (THRU 300W UPS IN ELECTRICAL ROOM) RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. DATA CABLE TO ETHERNET HUB IN BUILDING DATA ROOM. COORDINATE WITH BARRY UNIVERSITY I.T. DEPARTMENT. LED CONTROLLER MOUNTED ABOVE CEILING DISTRIBUTION PANEL "DP" NEW 300W UPS MOUNTED ON WALL WITH SUPPORT BRACKETS. CORD WITH PLUG ......... .... QUADRANGLE ENLARGED FLOOR PLAN - ROOM 122 RECEPTACLE ABOVE CEILING FOR LED AND CONTROLLER POWER. 1/2"C GND. FIELD COND — ELECTRICAL CLOSET LOCATION WITH 2 #12, 1 #12 TO LED I�ECEPTACLE. COORDINATE FINAL IT RUN. LED CONTROLLER MOUNTED ABOVE CEILING LED 1/2 "C TO LED RECEPTACLE CIRCUIT ABOVE. FIELD COORDINATE FINAL CONDUIT RUN. DATA CABLE —� CONDUIT SLEEVE IN GROUND FLOOR STRUCTURAL CEILING. FIELD COORDINATE FINAL LOCATION. NEW LED -p; CLOSET EL "A" Manuel Synalovski Associates, LLC 1800 Eller Drive, Suite 500 Fort Lauderdale, FL 33316 Telephone 95061.6806 Facsimile 954.961.6807 w v sralovskitvm KEY t&T PLAN SC.$. RY ENLARGED FLOOR PLAN - GROUND FLOOR z 0 uni Pi ce ig>ticj 68"Lsi M M t Z Q 4 vlZ � 01 I4J Z VI r r CLIENT: BARRY UNIVERSITY REV DATE DESCRIPTION DESIGN DELIVERABLE: ISSUE TYPE ISSUE DATE: 10 -15 -2010 PROJECT NUMBER: DRAWN BY: DS CHECKED BY: MV SLEET TITLE: LIBRARY (GROUND AND 3RD FL) /FINE ARTS ELECTRICAL FLOOR PLAN SHEET NUMBER: E-203 Manuel Synalovski Associates, LLC 1800 Eller Drive, Suite 500 Fort Lauderdale, FL 33316 Telephone 954.9616806 Facsimile 954.9616807 YVWw.synal ?VSkl.com ..•U11111/•, .o" IL kLIVAI Z P o Z cin .A4x �C sn CLIENT: BARRY UNIVERSITY DATE ISCRIPTNN DESIGN DELIVERABLE: ISSUE TYPE ISSUE DATE: 10 -15 -2010 PROJECT NUMBER: DRAWN BY: DS CHECKED BY: MV SHEET TITLE: PANEL SCHEDULES SHEET NUMBER E-301 LOCATION: POWERS BLDG. ELEC. RM. 161 a s s CKT, lints LJ P.G.► LOAD DESCRIPTION WIRE GRD, COND. POLE/ TRIP KVA KVA KVA A PHASE B PHASE C PHASE POLE/ TRIP COND. GRD. WIRE LOAD DESCRIPTION CKT. COND. a L•AD 111111111M:lIIIIIIIIIIPz•T47[•37 20 EX 1.0 MrM VW 0.9 1.0 W4 ► a IA s EX EX EX. L•AD , 20 EX EX EX EX _ EX. LOAD 4 3 EX. LOAD . WEN EX EX 5 7 9 - EX EX ( 111 12 EX EX Kral 20 EX 20 EX 20 i ''"0 AV 0.9 1 0 yW6''F/�'/M1�1 0 � . 0.7 1.0 0.9 1.0 20 EX EX EX EX EX EX. LOAD 6 EX. LOAD EX. LOAD MASS NOTIF. LED SIGN s .E EX i',h i W/ %r,,, 20 EX EX EX EX 20 EX 20 EX EX. LOAD 8 20 EX EX EX EX EX EX. LOAD 10 1 SPACE /11/183111 a - -18:11111 1&M i / y 1.rg - - 1.0 20 EX EX EX EX 2 EX. LOAD 12 W lffi MASS NORF. LED SIGN - - - i j 1.0 SPACE 14 13 EX EX - -11111:11 - - fWA '4f,j0 ' - - - - - SPACE 16 15 13 SPACE 17 1" - • IIII '� _1111=1-I111C1111 - .(lur -- ,.III . - -11� . - 111:1111111111211101; 11:X111111:11111111811111,d/aff. 111:X111111:111111118111111121111 - - ar a I, '� �K%�� / 11:1111 - TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE U EQPT. GRD. 0 ISOL. GRD. - -^ SPACE SPACE 18 � i / BRANCH BREAKERS= EX KAIC BRACING = EX KAIC ls'.� .- - - - - - SPACE 20 - - - - 30 SPACE SPACE 22 24 1 IEWRAIIIIIM11.11111111111111111111C115 23 .',//aff. ' i .1111CIII f '/VAIN - K i 105.3 102.4 I 102.4 CIRCUIT TYPE : 0 ARC FAULT 0 TIME SWITCH CONTROL - - SPACE _ SPACE 26 25 TRIP -. - - - SPACE 28 2.7 FEEDER SIZE IS MICABLE = SEE R 1 S E R 0 BUSWAY ' _ " �� �/,W/MilIC:11 TO 20 21 SPACE ENCLOSURE : NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) - - SPACE - CIRCUIT TYPE : ® ARC FAULT ®TIME SWITCH CONTROL SHUNT TRIP ® GROUND FAULT i° DEDICATED ®ISOLATED GRD. ` ALL FEEDER CALCULATIONS ARE BASED ON;THHN/fHWN CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY - TOTAL KVA IS 10.3 KVA TOTAL AMPERES IS 29 AMPS d - ESTIMATED DEMAND LOAD= - AMPS - POLE TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE MI EQPT. GRD. 0 ISOL GRD, MAINS: ®M.L.0. O BREAKER : - -- vgI . TI - - FEEDER SIZE 1S: El CABLE = SEE RISER ❑ BUSWAY BRANCH POLES: 30 BRANCH BREAKERS= EX KAIC MOUNTING: MISURFACE D FLUSH D FREE STANDING 0 KEYED DOOR BUS RATING 225 BRACING = EX KAIC NEUTRAL BUS IS DHALF SIZE 111FULL SIZE D K RATED (1.9 0 K RATED (2.0) GROUND BAR: MI EQUIPMENT 0 ISOLATED 0 BOTH ENCLOSURE ; IINDAA 1 D NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: ❑ TOP MI BOTTOM D FEED THRU PANEL TYPE :f ❑FUSED 0 CB PLUG N = CB BOLT IN FED FROM ®NORMAL D EMERGENCY 0 UNINTERRUPTABLE 'NOTE: LOCATION; ANDREAS BLDG KITCHEN ELECT. CLOSET (2ND FL) PANEL "2 E hit" SCHEDULE �rv,cT.ur it A,CW SPEC: EX. COPPER BUS 0 ALUMINUM BUS CKT. LOAD DESCRIPTION ' WIRE GRD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GRD. WIRE LOAD DESCRIPTION CKT. IA EX. LOAD EX EX EX , 0 a it %' - gf * a _ _1 _ _ EX. LOAD EX. LOAD a i ► 28 4A 3 EX. LOAD , %;/ %.. 20 EX ? `� �, 20 EX , it , ��a��s. EX EX EX 20 EX � L ' 1.2 1 2 ? �,.,%4% 20 EX EX EX EX EX 1 2 EX. LOAD 4 5 7 EX. LOAD DC LOAD EX EX EX EX EX EX EX 20 EX 20 EX i /` '% / ,(, 1.2 20 EX EX EX EX EX EX. LOAD 6 1.2 1.2 Wr , , , , 404'# a a a EX EX LOAD 8 - - - - 0.4 41? 20 2 2 12 EX EX MASS NORF. LED SIGN 10 9 SPACE i j 1.0 - 11 SPACE EX EX - - - - fWA '4f,j0 ' - - - - - ALL FEEDER CALCULATIONS ARE BASED ON:1TfN/TINWSI CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY SPACE 1 13 SPACE TOTAL KVA is KVA - - - - - /�9i. s-r TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE U EQPT. GRD. 0 ISOL. GRD. MAINS: MI M.L.O. D BREAKER : ^'- SPACE 4 17 17 SPACE SPACE BRANCH BREAKERS= EX KAIC BRACING = EX KAIC - - - - - - - - CO- PANEL TYPE : DFUSED O CB PLUG IN NI CB BOLT IN FED FROM: ENCRMAL CD EMERGENCY CI UNINTERRUPTABLE iNCITE: 30 %"f %7Aii .; ,,0:.,,'/ 23 8 23.8 23.8 218 / , ",r% sy,.7,4 29 16 , , , r 'y� /: � ALL FEEDER CALCULATIONS ARE BASED CXEDI N/TI N CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY SUBTOTAL 105.3 102.4 I 102.4 CIRCUIT TYPE : 0 ARC FAULT 0 TIME SWITCH CONTROL TOTAL "A IS 310.1 KVA ® GROUND FAULT ® DEDICATED © ISOLATED GRD. TOTAL AMPERES IS 373 AMPS ® SHUNT TRIP SPACE _ 18 19 SPACE TRIP - - - 3 '/I / "' C.B. FEEDER SIZE IS MICABLE = SEE R 1 S E R 0 BUSWAY BRANCH POLES: 32 BRANCH BREAKERS= EX KAK: MOUNTING: =SURFACE ❑ FLUSH 0 FREE STANDING 0 KEYED DOOR SPACE 20 21 SPACE ENCLOSURE : NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) - - - - �� - - ' - - 'I..y'ii�y; (��� - 1 d - ' - 23 SPACE 22 24 - - - - vgI . TI - - - - - - / 9 'ilif ,, SPACE 24 25 SPACE - - - - - - ��" ;r ' . .20 EX - - - - SPACE 26 27 SPACE - - - - - - �� 20 EX - - - - SPACE 28 - - -%. - - - - - - SPACE SPACE 30 29 SPACE - - SUBTOTAL 4,8 2.8 ,4 CIRCUIT TYPE : ® ARC FAULT 0 TIME SWITCH CONTROL ® SHUNT TRIP ® GROUND FAULT ® DEDICATED ® ISOLATED GRD. ALL FEEDER CALCULATIONS ARE BASED ON:DE N/THWN CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY TOTAL KVA IS ►. • VA TOTAL AMPERES IS 28 AMPS SPACE ESTIMATED DEMAND LOAD= - AMPS ALL FEEDER CALCULATIONS BASED �. NOT MORE THAN 4 CONDUCTORS N A RACEWAY POLE TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS • 3 PHASE 4. WIRE MI EQPT. GRD. O ISOL. GRO. MAINS: MI M.L.O. 0 BREAKER : -- -- ESTIMATED DEMAND LOAD= - AMPS FEEDER SIZE IS MICABLE = SEE RI SR O BUSWAY BRANCH POLES: 30 BRANCH BREAKERS= EX KAIC MOUNTING: MI SURFACE 0 FLUSH 0 FREE STANDING 0 KEYED DOOR BUS RATING: 225 I BRACING = EX KAIC NEUTRAL BUS IS: C (HALF SIZE MI FULL SIZE 0 K RATED (1.5) ❑ K RATED (2,0) GROUND BAR: Ea EQUIPMENT 0 ISOLATED 0 BOTH ENCLOSURE : MI NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: ❑TOP MI BOTTOM O FEED THRU PANEL TYPE : DFUSED ❑ CB PLUG IN 811 CB BOLT IN FED FROM: =NORMAL 0 EMERGENCY 0 UNINTERRUPTABLE MOUNTING: ®SURFACE O FLUSH D FREE STANDING 0 KEYED DOOR NOTE: • LOCATION: FINE ARTS ELEC. CLOSET PANEL "A" SCHEDULE SPEC: EX. COPPER BUS 0 ALUMINUM BUS CKT. LOAD DESCRIPTION `)e IMRE GRD. COND. POLE/ TRIP KVA A PHASE KVA 8 PHASE j KVA C PHASE POLE/ TRIP COND. GRD. WIRE tip` LOAD DESCRIPTION CKT. IA SPARE EX EX EX EX 70 EX - 0.8 /gi,"/i / '�� /�f/� � �� „ „''; 20 EX EX EX EX EX EX EX EX EX EX EX EX. LOAD EX. LOAD 2A 28 4A 0.8 4 /9/ iA 6, / ��,r - 0,8 , %;/ %.. 20 EX ? `� �, 20 EX , it , ��a��s. 16 EX. LOAD 3A 4B - 5A EX. LOAD MASS MOTIF. LED SIGN 2.5 20 EX � -0 l�'i r ",� 2.5 EX 12 EX 12 EX 1 2 20 EX� 20 EX %fir %/' ' /// v rj4",f% "WPM,. 0 8 0.8 20 EX EX EX EX - EX. LOAD 8A 68 0.4 5B 7A EX. LOAD SPARE EX EX EX EX EX EX EX 20 EX 20 EX 0.8 0 . 8 10 EX EX EX 13 1 S EX. LOAD 8A 8B %' iffier, ri; N 7B 9A EX. LOAD 16 EX EX EX EX EX EX 20 EX 100 4 / ,/ 1.0 0.8 / i,r1'i.A !/�, r�% % y v . .7 T� y'4r� i j 1.0 0.8 20 EX 20 EX EX EX EX EX EX EX EX. LOAD EX. LOAD 10A 108 12A 9B EX. LOAD 11A 113 ALL FEEDER CALCULATIONS ARE BASED ON:1TfN/TINWSI CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY SUBTOTAL 3.2 2.6 3 8 CIRCUIT TYPE : ® ARC FAULT ® TIME SWITCH CONTROL SHUNT TRIP ® GROUND FAULT ® DEDICATED © ISOLATED GRD. TOTAL KVA is KVA 27 TOTAL AMPERES IS 27 AMPS 23 ESTIMATED DEMAND LOAD= - AMPS - POLE TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE U EQPT. GRD. 0 ISOL. GRD. MAINS: MI M.L.O. D BREAKER : ^'- - - FEEDER SZE IS CABLE = SEE RI SER CI BUSWAY BRANCH POLES: 11/22 BUS RATING: 60 BRANCH BREAKERS= EX KAIC BRACING = EX KAIC MOUNTING: MI SURFACE 0 FLUSH 0 FREE STANDING ❑ KEYED DOOR NEUTRAL BUS IS: DHALF SIZE SIFOLL SIZE 0 K RATED 1.5) 0 K RATED (2.0) GROUND BAR: M EQUIPMENT 0 ISOLATED 0 B0111 ENCLOSURE : =RENA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: DTCP a BOTTOM Q FEED THRU PANEL TYPE : DFUSED O CB PLUG IN NI CB BOLT IN FED FROM: ENCRMAL CD EMERGENCY CI UNINTERRUPTABLE iNCITE: 30 LOCATION: ADRIAN BLDG. COIF. ROOM 113 "AC" SCHEDULE asspEassassmsa SPEC: EX. ®COPPER BUS 0 ALUMINUM BUS CKT. LOAD DESCRIPTION WIRE GRD. COND. POLE/ TRIP KVA A PHASE KV B PHASE KVA 0 PHASE POLE/ TRIP COND. GRD. WIRE LOAD DESCRIPTION CKT, 1 EX. LOAD EX EX EX EX EX EX EX 20 EX 20 EX 2.5 .y 'r 0.4 , 4 ' /1/';',.' // ' 2.5 2.5 ' ,;, 0 EX EX EX EX O MASS NOTIF. LED SIGN EX. LOAD 2 4 3 EX. LOAD 5 EX. LOAD <W'J 1.2 , ,P.„ ' EX EX EX EX X EX EX EX 20 EX 20 EX 30 EX 2.5 20 EX � -0 l�'i r ",� 2.5 EX EX EX LCD MONITOR RM. 143 EX. LOAD 6 2.5 2 5 � ',--/fir/ 20 EX EX EX EX - EX. LOAD 8 7 EX. LOAD ` ,, 5 8 ��� 30 EX ,�% ' 5,6 5.6 EX EX EX EX EX EX. LOAD 12 9 EX. LOAD 10 j- -T4 58 58 ;;,T,.%/ a'. 13 1 S 40 EX -' „ >J �� 7.2 0 -, 40 EX , i //,4/,,1/• 7.2 7.2 EX EX EX y;� ?' EX. LOAD 16 EX. LOAD 20 a EX EX 18 17 20 72 72 0 /,-' / :% i, ;r ; 19 21 EX. LOAD - EX EX EX 125 E�,.�6, / X47,/ r 23.8 %,ie f %' / - „r (/'/Y , ' /,l,xup% 23 8 - - - - - - - - SPACE 22 SPACE 24 26 23 23.8 / //1-f %/ P oy` ' - I - - - 14 SPACE 25 27 EX. LOAD - EX EX EX 125 a % ;° 218 23.8 l''' , t " 25 y EX EX EX SPACE EX. LOAD 28 30 %"f %7Aii .; ,,0:.,,'/ 23 8 23.8 23.8 218 / , ",r% sy,.7,4 29 22 31 ALL FEEDER CALCULATIONS ARE BASED CXEDI N/TI N CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY SUBTOTAL 105.3 102.4 I 102.4 CIRCUIT TYPE : 0 ARC FAULT 0 TIME SWITCH CONTROL TOTAL "A IS 310.1 KVA ® GROUND FAULT ® DEDICATED © ISOLATED GRD. TOTAL AMPERES IS 373 AMPS ® SHUNT TRIP - ESTIMATED DEMAND LOAD= - AMPS SPACE POLE TRIP TYPE RATED VOLTAGE= 277/480 VOLTS 3 PHASE 4 WIRE a EQPT. GRD. 0 ISOL. GRD. MAINS: OM.LO. CI BREAKER : 3 400 C.B. FEEDER SIZE IS MICABLE = SEE R 1 S E R 0 BUSWAY BRANCH POLES: 32 BRANCH BREAKERS= EX KAK: MOUNTING: =SURFACE ❑ FLUSH 0 FREE STANDING 0 KEYED DOOR BUS RATING: 800 BRACING - EX RAC NEUTRAL BUS IS: DHALF SIZE MI FULL SIZE 0 K RAZED (1.5) 0 K RATED (2.0) GROUND BAR: MI EQUIPMENT 0 ISOLATED 0 BOTH ENCLOSURE : NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: Q TOP El BOTTOM D FEED THRU PANEL TYPE : DFUSED 0 C8 PLUG iN GB BOLT IN FED FROM: MINORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE 'NOTE; Q REPLACE EXISTING 20AMP C.B. WITH NEW 15 AMP C.B. LOCATION: %REGAND BLDG. MAIN ELECTRICAL ROOM (GROUND FL - CKT. LOAD DESCRIPTION \ WIRE GRD. COND. POLE/ TRIP KVA KVA A PHASE B PHASE KVA C PHASE POLE/ TRIP COND. GRD. WIRE 1/ LOAD DESCRIPTION CKT. 1 AUDIOVISUAL EQ, RM. 143 EX. LOAD EX EX EX 20 EX 0.2 I /,°'//i ,,r"6,�'rc'�4 / ' - - - - EX SPACE 2 3 LCD MONITOR 4t SURG. UGHT RM. 143 3 EX EX EX 20 EX <W'J 1.2 , ,P.„ ' - - - - 20 EX SPACE 4 5 LCD MONITOR RM. 143 EX. LOAD EX EX EX 20 EX / /'i /74 - 1 3 - - - - - , %�' / SPACE 8 7 MASS MOTIF. LED SIGN EX EX 12 12 1/2 20 EX 0.4 /1�,�, ,�r�c6s�f''ryr��,. FFY cif%/ - '0.. s'/ ' - - - - - - - - SPACE SPACE 8 10 9 SPARE y;� ?' - - - 20 11 SPARE EX. LOAD - - - 206 ' / ' ,r, - - - - - - rfir ., 1.0 1.0 SPACE 12 13 SPARE EX - - - 20 - 0 ,,;/"."„',, ,fg,; - - - - 1.0 1 .0 ; .,, , etr #' ., SPACE 14 15 SPARE EX - - - 20i/',,'i/ - J �i.Gr��frdir - - - - "//%'" ' : /''.' : 10 1 0 %%/ iii!1",/,4 SPACE 16 17 SPACE EX - - - - 1i3O/07%.I''' `,f ). - - - - /, /' 71; / ; 1.0 1.0 1.0 1.0 ' "#„, /<. frit i %�/�' SPACE 18 19 SPACE EX - - - - 2 • �r /�fr0 -, - - - - EX SPACE 20 21 SPACE mm - - - - 'I..y'ii�y; (��� - 1 d - - - - - 22 24 SPACE 22 23 SPACE EX - - - - / 9 'ilif ,, EX - - - - EX. LOAD SPACE 24 25 SPACE .20 EX - - - - - ', 4, 4,%�`' /--X ' - - - - EX. LOAD SPACE 26 27 SPACE 20 EX - - - - /i ,r'/ / - - l''� //yA - - - - EX SPACE 28 29 SPACE - - - - // i ; ''r. ;.. ���%,, , d//%���� - - - - - 20 EX SPACE 30 ALL FEEDER CALCULATIONS BASED �. NOT MORE THAN 4 CONDUCTORS N A RACEWAY SUBTOTAL 0. I 1.2 1,3 CIRCUIT TYPE : ® ARC FAULT ® TIME SNITCH CONTROL ® SHUNT TRIP ® GROUND FAULT ® DEDICATED © ISOLATED GRD. TOTAL KVA IS 3.1 KVA TOTAL AMPERES IS 9 AMPS ESTIMATED DEMAND LOAD= - AMPS EX POLE TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE MI EQPT. GRD. 0 ISOL GRD. MAINS: MI M.L.O. 0 BREAKER : -- EX. LOAD FEEDER SIZE IS: MI CABLE = SEE RISER O BUSWAY BRANCH POLES: 30 BRANCH BREAKERS= 10 KAIC MOUNTING: ®SURFACE O FLUSH D FREE STANDING 0 KEYED DOOR BUS RATING: 250 BRACING - 1 0 KAIC NEUTRAL BUS I5: DHALF SIZE ® FULL SIZE 0 K RATED (15) 0 K RATED (20) GROUND BAR: MI EQUIPMENT 0 ISOLATED 0 BOTH ENCLOSURE : El NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: In TOP Q BOTTOM Q FEED THRU PANEL TYPE : DFUSED 0 IS PLUG IN MI CB BOLT IN FED FROM: NORMAL C] EMERGENCY Q UNINTERRUPTABLE I NOTE: LOCATION: LIBRARY 3rd FL. MECH. RM NI EXISTING 0 NEW PANEL "N" SCHEDULE SPEC: EX. ®COPPER BUS 0 ALUMINUM BUS CKT. 3 5 7 9 11 13 15 17 LOAD DESCRIPTION i4` GRD. COND. EX EX EX "% %! EX EX EX a • ► y s EX. LOAD EX. LOAD SPACE SPACE SPACE SPACE POLE/ KVA A PHASE TRIP 0 EX 20 EX 20 EX ALL FEEDER CALCULATIONS ARE BASED 0N:TiiHN/H I CU. SUBT•TAL NOT YORE THAN 4 CONDUCTORS N A RACEWAY TOTAL KVA IE TOTAL AMPERES IS KVA KVA POLE/ B PHASE C PHASE TRIP ;POW- - ate, ,7)2 A MI MAO 4.► 2.5 .5 9.0 KV 11 AMPS COND, GRD. WIRE ,1/440 LOAD DESCRIPTION SPACE SPACE SPACE SPACE SPACE SPACE - - - - SPACE pAr *^ •'r CKT. 4 6T 8 1' 18 - - - - SPACE 1 CIRCUIT TYPE : ® ARC FAULT ®. TIME SWITCH CONTROL 0 SHUNT TRIP ® GROUND FAULT DEDICATED 4 ISOLATED OR ESTIMATED DEMAND LOAD= - AMPS POLE TRIP rtpti RATED VOLTAGE= 277/480 VOLTS 3 PHASE 4 WIRE ® EQPT. GRD. 0 ISOL. GRD. FEEDER SIZE IS: MI CABLE - S IE E RISER O BUSWAY MAINS: BRANCH POLES; M,L,O. 0 BREAKER : 18 BRANCH BREAKERS= EX KAIC MOUNTING: MI SURFACE 0 FLUSH 0 FREE STANDING 0 KEYED DOOR BUS RATING: 100 BRACING = EX KAIC NEUTRAL BUS IS: ❑HALF SIZE II FULL SIZE 0 K RATED (1.5) 0 K RATED (20) GROUND BAR: I® EQUIPMENT 0 ISOLATED 0 BOTH ENCLOSURE : NEMA 1 0 NEMA 3R O NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: 0 TOP BOTTOM D FEED THRU PANEL TYPE : ©FUSED 0 CB PLUG IN MI CB BOLT IN FED FROM: NORMAL 0 EMERGENCY 0 UNINTERRUPTAB I NOTE: LOCATION; LIBRARY 1st FL MECH. RM. EXISTING D NEW PANEL "L" SCHEDULE SPEC: EX. COPPER BUS 0 ALUMINUM BUS CKT. 1 3 5 11 13 15 LOAD DESCRIPTION EX. LOAD EX. LOAD EX. LOAD EX. LOAD EX. LOAD EX. LOAD EX. LOAD EX. LOAD 17 EX. LOAD 19 MAIN 21 23 WIRE GRD. COND. EX EX EX EX EX EX EX EX EX EX EX EX EX EX EX EX EX POLE/ KVA KVA KVA POLE/ TRIP A PHASE B PHASE I C PHASE TRIP COND. 20 EX 2 17 ,� :. " //, gr 20 EX EX 20 EX °'/GG�%'�/ al 2.0 2.0 "/#11/4 20 EX EX ! �. ,��ji',, 'i / , , 2.0 2.0 20 EX EX 20 EX 20 EX 2.0 2.0 if '�/;1,,f 20 EX / "j! , 2.0 2.0 !"ill, 20 EX / /#'4 2.0 20 Ex 2 2 0 '� i� % % -4'7i 20 EX ° it g;//'' 2.0 2.0 r.GS/1,., EX 20 EX ' 20 EX EX 20 EX EX 2.0 20 EX EX 4 20 EX EX y���,� 2.0) 2.0 20 EX EX EX 100 - �.7_,�''i7;.% '7/;'° < 15 1 2 �' 1 .4 GRD. WIRE 4/ LOAD DESCRIPTION ALL FEEDER CALCULATIONS ARE BASED O*114IN/1MNIN CU. SUBTOTAL NOT MORE THAN 4 CONDUCTORS Si A RACEWAY TOTAL KVA IS TOTAL AMPERES IS 12. 12. 38.4 KVA 44 AMPS EX EX EX EX EX EX EX EX EX EX EX EX EX 12 12 EX. LOAD EX. LOAD EX. LOAD EX. LOAD EX. LOAD EX. LOAD CKT. 2T 4T 6T 8T 10 12 EX. LOAD 14 EX. LOAD 16 EX. LOAD 18 MASS NOTIF. LED SIGN'a 20 - - - SPACE 2 - - - SPACE . 2 12.0 CIRCUIT TYPE : ® ARC FAULT ® TIME SWITCH CONTROL 0 SHUNT TRIP ® GROUND FAULT ts DEDICATED 0 ISOLATED GR ESTIMATED DEMAND LOAD= - AMPS POLE TRIP RATED VOLTAGE= 277 /480 VOLTS 3 PHASE 4 WIRE =I EQPT. GRD. 0 ISOL. GRO. MAINS: ❑M.L.O. M BREAKER : 100 C.B. FEEDER SIZE IS: ® CABLE = SEE RISER O BUSWAY BRANCH POLES: 24 BRANCH BREAKERS= EX KAIC MOUNTING: ® SURFACE D FLUSH 0 FREE STANDING 0 KEYED DOOR BUS RATING: 100 BRACING - EX KAIC NEUTRAL BUS IS: O HALF SZE FULL SIZE ENCLOSURE : NEMA 1 D NEMA 3R D K RATED (1,5) D K RATED (20) D NEMA 4X CLASS ( ) DIV PANEL TYPE : DFUSED ❑ CB PLUG IN MI CB BOLT IN NOTE: GROUND BAR: EQUIPMENT 0 ISOLATED 0 BOTH FEED LOCATION: 0 TOP M BOTTOM 11 FEED THRU FED FROM: Ei NORMAL 0 EMERGENCY D UNINTERRUPTABLII LOCATION; KDLASA BLDG. ELECTRIC ROM PANEL `T2" SCHEDULE SPEC: EX. =COPPER BUS 0 ALUMINUM BUS CKT. 1 LOAD DESCRIP104 WIRE GRD. COND. POLE/ TRIP KVA A PHASE KVA 3 PHASE KVA C PHASE POLE / TRIP COND. GRD. WIRE 4° LOAD DESCRIPTION I CKT. EX. LOAD EX. LOAD EX EX EX , 20 EX 1.0 1.0 r it , e. `% %yam. 20 EX EX EX EX EX. LOAD EX. LOAD 2 3 EX. LOAD 12 EX EX EX 20 EX .,., o' 1.0 1.0 ',v ' -4 20 EX EX EX EX EX EX EX. LOAD 47 20 EX EX EX. LOAD EX EX £teas EX EX a' EX 20 EX 20 EX re, I .[► 1.0 , %�' / to 1.0 A/,/- ,' ,/ t a 20 EX a EX EX EX EX EX EX. LOAD EX EX. LOAD 8 7 EX. LOAD 9 O( LOAD EX EX EX 20 EX y;� ?' 10 1 0 OA 20 EX EX EX EX 20 EX EX. LOAD 1 d 11 EX. LOAD EX. LOAD EX EX EX 20 EX ; :9; '!4' rfir ., 1.0 1.0 20 EX EX EX EX EX D(. LOAD 12 13 EX. LOAD 14 EX EX EX 20 EX 1.0 1 .0 ; .,, , etr #' ., 2b EX DC EX EX EX EX. LOAD 14 15 EX. LOAD EX EX EX 20 EX "//%'" ' : /''.' : 10 1 0 %%/ iii!1",/,4 20 EX EX EX EX EX EX. LOAD 1. 17 EX. LOAD 18 EX EX EX 20 EX /, /' 71; / ; 1.0 1.0 1.0 1.0 ' "#„, /<. frit i %�/�' 20 EX 20 EX EX EX EX EX EX EX. LOAD 10 2• EX EX 2 • EX. LOAD 19 EX. LOAD EX EX EX EX 20 EX 21 EX. LOAD mm EX EX EX 20 EX %' ,/r QI ` 10 j 1 0 „ r" /i i %if,' 20 EX EX EX EX FAULT EX. LOAD 22 24 23 EX. LOAD TOTAL KVA IS 28.1 KVA EX EX EX 20 EX %�/r� o /r 06'/' 10 1 0 20 EX EX EX EX - EX. LOAD 25 EX. LOAD BRANCH POLES: 24 EX EX EX .20 EX 1 0 1 0 F/, ,% ,ONW,/ ,04 20 EX EX EX EX FED FROM: =NORMAL 0 EMERGENCY 0 UNINTERRUPTABLIi D( LOAD 26 27 EX. LOAD EX EX EX 20 EX y 7,-/F , 1.0 1.0 w ,/ ,//-4 % %,, '' ' 4, 4. 1.0 1.0 20 EX 20 EX EX EX EX EX. LOAD 28 30 EX EX EX OEX L`OAAD 29 EX. LOAD EX EX EX 20 EX 31 EX. LOAD EX EX EX 20 EX 1.0 1.0 %%,#i it ;s f,,ry's /s / 20 EX EX EX EX EX. LOAD 32 34 33 EX. LOAD EX EX EX '20 EX f ff 10 1.0 AA 20 EX EX EX EX EX. LOAD 35 EX. LOAD EX EX EX 20 EX /�7/l '//, �.. 1,0 1.0 20 EX EX EX EX EX. LOAD 36 37 EX. LOAD EX EX EX 20 EX 1 0 1.0 �'�!ir •, � /�°, 0 f /l4 20 EX EX EX EX EX. LOAD 38 39 SPACE - - - - �;1'47 - 1.0 "0/7 " 44 20 EX EX EX EX EX. LOAD 40 41 SPACE - - - - / / /. /f/iY„' ,7/' '1. - 0.4 20 1/2 12 12 MASS NOTIF. LED SIGN 42 AU. FEEDER CALCULATIONS ARE BASED ON THHN/TFIWN CU. NOT MORE THAN 4 CONDUCTORS N A RACEWAY SUBTOTAL 14.0 13.0 12.4 CIRCUIT TYPE : ® ARC FAULT ® TIME SWITCH CONTROL 0 SHUNT TRIP ® GROUND FAULT 17? DEDICATED © ISOLATED GRD, TOTAL KVA IS 39.4 KVA TOTAL AMPERES IS 109 AMPS ESTIMATED DEMAND LOAD= - AMPS POLE TRIP TYP RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE MI EQPT. GRD. 0 ISOL GRD. MAINS: OM.L.O. MI BREAKER : 3 200 C.B. FEEDER SIZE IS: MICABLE = SEE RISER D BUSWAY BRANCH POLES: 42 BRANCH BREAKERS= EX KAIC MOUNTING: U SURFACE 0 FLUSH D FREE STANDNG 0 KEYED DOOR BUS RATING: 200 BRACING = EX KA C T NEUTRAL BUS IS: DHALF SIZE a FULL SIZE ❑ K RAZED (1,5) 0 K RAZED (20) GROUND BAR: MI EQUIPMENT 0 ISOLATED 0 BOTH ENCLOSURE : CINEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: O TOP al BOTTOM 0 FEED THRU PANEL TYPE : DFUSED D C8 PLUG IN M CB BOLT IN FED FROM; NORMAL 0 EMERGENCY 0 UNINTERRUPTABL NOTE: LOCATION: GARNER BLDG. ELECTRICAL RML MI EXISTING ❑ NEW PANEL "LP1" SCHEDULE SPEC: EX. IBBCOPPER BUS ❑ ALUMINUM BUS CKT. LOAD DESCRIPTION "cam` WIRE GRD. COND. POLE/ TRIP KVA A PHASE KVA 8 PHASE KVA C PHASE POLE/ TRIP COND. GRD. WIRE 4119 LOAD DESCRIPTION CKT. 1 EX. LOAD EX EX EX EX EX EX 20 EX 20 EX 1.1 Effil , ii' rr' -4 20 EX EX a. EX. LOAD 2 re ,; /:- 1.1 0.4 y / ,%4 20 EX 1 12 12 MASS NOTIF. LED SIGN 4;. 3 EX. LOAD 5 EX. LOAD EX EX EX EX EX EX 20 EX 20 EX , :,, At/ ArfPg 1.1 1.1 11 1.1 r ��' %i%d" iy/ %:20 20 EX EX EX EX EX EX EX EX EX. LOAD 8T EX. LOAD 8, 7 EX. LOAD 9 EX. LOAD EX EX EX 20 EX '07;,/,,Aft 1./1 1,1 , «�',, ! , 20 EX EX EX EX EX. LOAD 10 11 EX. LOAD EX EX EX 20 EX 3/2/.16„ 1.1 1.1 20 EX EX EX EX EX. LOAD 12 13 EX. LOAD EX EX EX 20 EX 1.1 1.1 iii ,; `/J/) 20 EX EX EX EX EX. LOAD 14 15 EX. LOAD EX EX EX 20 EX ;P , , 1.1 1.1 / /y' ' /./; 20 EX EX EX EX EX. LOAD 17 EX. LOAD EX EX EX 30 EX ! /i ' , /A . 2.1 1.1 20 EX EX EX EX EX. LOAD 18 19 EX. LOAD EX EX EX 30 EX 21 0.7 V; < 20 EX EX EX EX EX. LOAD 2 • 21 EX. LOAD EX EX EX SUBTOTAL 20 EX.. 15 1,1 •>•a =a :■ mm a a. • :• 2 'i2 4,4e; is kim, 1.5 1.1 9.4 8.5 10,2 20 EX CIRCUIT ® SHUNT EX TYPE TRIP EX : ® ARC ® GROUND EX FAULT FAULT EX. LOAD ® TIME SWITCH CONTROL S:2 DEDICATED © ISOLATED 2. GRD t 23 ALL FEEDER CALCULATIONS ARE BASED Ott 1HUN/THWN CU NOT MORE THAN 4 CONDUCTORS N A RACEWAY TOTAL KVA IS 28.1 KVA TOTAL AMPERES IS 78 AMPS ESTIMATED DEMAND LOAD- - AMPS POLE TRIP TYPO RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE M EQPT. GRD. 0 ISOL, GRD. MAINS: ®M,LO. 0 BREAKER : - - FEEDER SIZE 15: El CABLE = SEE RISER ❑ BUSWAY BRANCH POLES: 24 BRANCH BREAKERS =� EX KAIC MOUNTING: M SURFACE ❑ FLUSH D FREE STANDNG ❑ KEYED DOOR BUS RATING: 100 BRACING - EX KAIC NEUTRAL BUS IS: ❑HALF SIZE MI FULL SIZE O K RATED (1.5) O K RATED (20) GROUND BAR: El EQUIPMENT 0 ISOLATED ❑ BOTH ENCLOSURE : El NEMA 1 0 NEMA 3R 0 NEMA 4X CLASS ( ) DIV ( ) FEED LOCATION: 0 TOP MI BOTTOM 0 FEED THRU PANEL TYPE : ZFUSED D CB PLUG N MI CB BOLT IN FED FROM: =NORMAL 0 EMERGENCY 0 UNINTERRUPTABLIi NOTE: 1