Adrian Hall and R Kirk Landon Student UnionDORMITORY AND COLLEGE UNION BUILDING NG FOR BARRY" COLLEGE MIAMI SHORES FLORI DA September 7, 1961 ELECTRICAL ADDENDUM NO.1 1. Article #31 7, First sentence of the third paragraph, change the word "executed" to "connected ". Sentence shal 1 read, "After lighting f ixtures and l ighti ng equipment are connected to the wiring system of the buil ding," etc. 2, Article # 319, Change 11 OV. 60 cycl e A, C. to 120'V. 60 cycle A. C. 3, All single phase equipment operating at 1 ine voltage shall be rated at 120 volts, 60 cycl e A. C. All systems shall also operate at the same voltage unl es otherwise shown on pl an or stated in the specifications. 4. Elevator motor M -2 shall be located in the penthouse in lieuol the bottom of the elevator shaft as shown. At the top of sheet E -1 the left station shall be known the sewage treatment plant. 6. In the sewage treatment add 2 -31-P motors to PF. #MDP -2 7. Change P. F. #N -9 to 3 #1/0 wire (RHW) in 2" cc ndudt fuse the feeder at 200/150 amps, E -1 ELECTRICAL ADDENDUM INTO, 2 DORMITORY AND COLLEGE UNION BLDG. BARRY COLLEGE, MIAMI SHORES F LORDI A The electrical contractor shall furnish and install 1- 500KVA 3 phase Askarel Immersed self cool transformer 4160 Delta high voltage 2087/120 low voltage transformer in lieu of 3 single phase transformers indicated on pole adjacent to the northesat corner of the "New Dormitory Bldg. " This unit to be mounted on a 4" reinforced concrete slab ..egegriele of 1000 lb. per square foot loading. Transformer is to have standard tops and accessories and is to be a: . a.nufaetured by Precision Transformer C • rpo, Sorgel Electric Company or Maloney Transformer Corp. September 22, 1963. This unit is to be provided with a low volt age air filled conduct entrance chamber and is to have high voltage cover mounted 5KV bushings. Contractor to provide pad and outdoor voult of approximately 10 ft. X 15 Ft. with the 15 feet running pee ne ' to the North wall of New Dormitory Bldg. The outdoor voult is to be constructed in accordance with Florida Power and Light Company specifications and similar to their drawing no SDA826. This voult is to be constructed in a manner Such t:nat it will comply with the 1959 National Electric ode Article 450 and with the Local Municipal and power Co's requirements. The transformer is to be protected by 200 .AMP fusible hook stick operated L V. disconnects as manufactured by S C Corp, Kearney- Hubbard Corp and are to be crossarm mounted on adjacent pole as shown on sheet E -1a Contractor is to also provide 5I01* Line type valve type arrestors as menu= lectured by G. Ea and Westinghouse on this same pole. The above specifications are also to apply to a 750 It:VA transformer to be fiarnntshed and set on a pad 12 X 15 feet on the south side of the center wing of the e.dsting "Dining Iiiafl re Dome Arts" bolding. This unit will require 17400 AMP-5KV disconnects on adjacent indicated pole instead of 200 AMP switch 9s as indicated above. ■ _lip EC ?JC,y• C ri I 11.i. Y OR m� tra:.a9 _ DORMITORY: AND COLLEGE UNION BLDG. BARRY COLLEGE MIAMI SHORES, FLORIDA PARAGRAPH NUMBER . ITEM 300 G�:nera1 Conditions 301 Work Required 302 Visiting the Site 303 Drawings 304 Sh Drawings 305 Standards for Material and Workmanship 306 Codes. Permits and Inspections 307 Temporary Light, Power and Scaffolding 308 Conduit Systems 309 Outlet Boxes 310 Wire and Cable 311 Splices and Connections 312 Fuses 313 Switches and Receptacles 314 Panelboards and Cabinets 315 Ernc-i gency -Exit Lighting 316 ; e Scle6 c 317 • if,IA. ;, ng Fixtures 318 w +z.J Wiring 319 •r C!t't jysteni (Dormitory and Student Union Bldg, ) a �. �w'c 3 -6_'. d h ?. -��f .., Ra #1 PARAGRAPH NUMBER 320 321 322 323 324 325 326 327 323 329 330 331 332 ELECT RICAL SP CITIC TIC ° UIDEX Electrical indlelt ITEM Fire Alarm System (Dormitory and Student Union Building) Into 1- System Public Address System a) Student Union Bldg. ((b) Dormitory Television. Antenna System ((Student Union Bldg - Conduit Only) Telephone System Service Entrance Street Lighting System Waterproofing Identification Balancing of Load Painting Teets and Adjustments Guarantee 300. GENERAL CONDITIONS This contractor shall read the general conditions which are a part of these specifications. 301. WORK REQUIRED The work to be done under these specifications shall include the furninhing of all labor and mateeial required to complete and leave ready for operation the installetion of the following items, in accordance with these specifications and the aecompanying drawings A. Electric Lighting System & Power System B. Fire Alarm System C. Ckock and Bell System (St/tient Union Bldg, ) D. Emergency-Exit Lighting E. Public Address System (Sludent Union Bldg.) F. Telephone System G. Clock & 3e11 System (Dorn i ory) H. Public Address System ; Doe niory) L Television Antenna Distributien System ((Student Union 131dg, ) J. Street Lighting System 302, VISITING THE SITE The bidder shall examine the site of the proposed work that he may fully understand the facilities, dirficulties, and restrictions attending the execution of the contract, T will be allowed no additional com- pensation for his failure to be informed. 303, DRAWINGS These specifications are ace)tripanied by floor plans of the buildings showing the log of t111 tAlete and switch control, the layout of branch circuit: and a seevt:e The drawings and e ap !eifieetions are complementary each to the other and what is celled int by one shell be ac, binding as if called for by both. 304, SHOP DRAWINGS ELECTRICAL SPECIFICATIONS FOR DORMITORY AND COLL:Et:14 ITSION BLDG. BARRY COLLEGE MIAMI SHORES, FLORIDA Ts2ject CIl-FLA-40 (DS) Shop drawings of all api» rElltS StAbLaiteC1 th. triplicate by tite contractor not more thee three veeeks after the contract is aigned. Work hall not pz.oceed unlesa the drawings have been approved.. Eel • . I 308. CONDUIT SYSTEMS E-2 :05„ STAND .DS FOR klATILIELL'et, 1T D WORKMANSHIP All materials shall be new and shall conform with the standard of the Underwriter's Laboratories, Inc, in every case where such standard has been established for the particular type of material in question. All work shall be executed in a workmanlike manner and shall present neat and meehan'.cal appearance when completed. 306. CODES, PERMITS AND INSPECTIONS The installation shall comply with laws ‘pplying to electrical installation in effect with the regulations f the National Electric Code where such regulations do not confl'el with the laws in effect. This contractor shall secure and pay for a.A necessary permits and certificates of inspection .tor all equipment *lecluded in this specifi- cation required by the various departments lf the tatt of Florida and the county and city having lawful jurisdicfon irrespective of any statenlents herein tO the contrary. 307, TEMPORARY LIGHT, POWER AND SCAFI'OLDING Temporary light and power will be provided by th General Contractor, However, this contractor is to provide an addition necessary wiring as may be required in the General Conditions or for 1: a own work. This contractor shall furnish and erect all scaffolding required to install the work required in this specification. All sett'iolding shall be removed upon completion of the contract. All wiring shall be concealed in conduit and all conduit shail be concealed unless otherwise indicated on the_plans. All exposed conduit anc] conduit for incenaing services, service- connections, feeders to power and light cabinets, and all conduil Vuried or concealed in outside walls and con.cealed in concrete floor slat • is to be Metallized Galvanized Rigid Steel conduit, as manufactured h,' the General Electric Co,, and shall meet in all respects *he Under writer's Laboratories, tee.. Stentlard for Rigid Steel Conduit, 1961 Edition, or any subserpent revlsien thereof. Electrical metallic tubing 6th ode;.n) may baud in all area outside of those stipulated abeve, Conduits shall be installed as shown on the pans and the riser ding in an approvkd manner, Joints shar be salt tight. reiareeere and fasten- ings shall be secure and of a type apnropriae in design and dimensions for the particular application, liures1 el he straight and true; elbows offsets and bends shell be uniZ.erre and symmetricaT. Lrnsallation workmanship shell be of the. brF.,sgf, Tinnitty and skill. 308. CONDUIT SYSTEMS (Con't.) Couplings, connectors and fittings shall be approved types specifically designed and manufactured for the purpose. They shall be installed expertly to provide a firm mechanical assembly and electrical conductivity. The conduit runs shall be installed in a neat and workmanlike manner and they shall be as nearly straight as practicable. Exposed conduits shall run parallel or at right angles to walls, beams, and floor unless shown otherwise on the drawings They shall be supported by clamps with clamp backs fastened to the wall, bearns or ceiling to provide a clearance of not less than 1/2 inch between the conduit and the wall. Each conduit bend shall have as long a radius as possible, and the radius shall not be less than that of he standard long - radius bend for that size of conduit No standard short- radius bends shall be used except as shown on the drawings The junction of conduit with any outlet box, panelboard box, or other receptacle provided with knock -outs, shall be made with a bushing inside and a lock nut outside of the box tightened to fasten the conduit rigidly to the box. The fittings for flexible conduit shall have a threaded portion for fastening the fittings to the box with a lock nut on the inside of the box. 309. OUTLET BOXES AU wall and ceiling outlets, junction and pull. box .s to be provided with galvanized steel knockout boxes suitable in design to the space which they occupy, and the purpose which they serve. Boxes to be of substantial construction, and entirely right and of make approved by the Engineer, In general, all outlet boxes to have threaded ears or lugs and open covers or bonnets for plaster grounds. Ali outlet boxes are to be set in walls, partitions or columns so as to be flush with the finished surface. Where they occur in plastered surfaces, both ceiling and rrais, boxes are to be accurately set and rigidly secured in position, the projecting edge being lined up with the grounds to which the plasterer will work, or the acoustic tile on ceilfikgse Plates or covers required for boxes in unplastered brick walls, or wall having special finish, to be made of brick or finish size or multiples thereof, erld be lined '41 with finish. 3090 OUTLET BOXES t Ceiling outlet boxes in solid concrete slabs to be of the two -piece removable back type. Boxes in concrete joints to be of the size and placed as directed. Boxes to be set on and fastened to forms so that when the forms are removed, no part of the holding nails will be left in the boxes. Provide boxes for fixture outlets with fixture supports of suitable design to carry weight of fixtures. A.nl. outlet bases td be clean and free from rust, concrete, plaster, and debris when delivered to the Owner 310. WIRE AND CABLE Furnish and install all wires and cables to serve all outlets as shown on the drawings or specified herein, Wire and cable shall comply to National Board of Fire Underwriters' type RHW and TW, The size and number of wires and cables are shown directly or typically on the drawings and refer to cross sectional area in circular mils of American Wire Gage (AWG). The minimum wire size shall be #12 AWG. The size of wires and cables for motor branch circuits shall conform with the requirements of the local inspection department but must not be smaller than the size indicated on the drawings. Conductors shall be soft drawn in accordance with the ASTM specifi- cation on B33.. Conductors Larger than #3 s AWG, shall be stranded, The rubber insulation shall be in accordance with IPCE1,; specification S49 -81 Appendices C (A) and K„ it shall be General Electric Versatol Geoprene SI - 58006,, or approved equal, On sizes # s AWG and smaller the insuk4 ion shall be covered with a protective braid otatttro; : flame and moisture resistant compound., On sizG9 #:110 AWG and . rger and on a. L runs„ the insuitatiorL shall', be protected ay a neoprene jacket in accordance with ASTM Dm752- 46T,. AA wire; sha !_ be in ae4 :Mane e with Underwriters Standards All branch cirayu .tE shall be color coded. The color of ihe inaal,arion or covering of the neutral or ground wire of all branch circuits No., 6 AWG and smaller shalt be white or natural gray color distinctly different from that of other wires 310 WIRE AND CAB! «Cori i., d In vertical conduit risers, the wires or cables must be supported within the conduit system in accordance with the National Electrical Code requirements., Runs of wires and cables to be continuous without joints to farthest outlet. Where connections are made and joints are necessary, they should be located only in outlet or junction boxes or cutout cabinets, All contact surfaces to be carefully finished, and fitted to have a bearing st every point . Contact surfaces to be not less than one square inch for every 200 amperes, 311. SPLICES AND CONNECTIONS Connections andsplicee shall be made in terminal and junction boxes only. Connections and splices for wires No, 6 AWG and smaller shall be made with Minnesota Mining and Meinnfacturing Company's pre- - insulated Scotchiok spring type connector, Use of these connectors shall be limited to the manufacturer's published wire size combinations; in general, Type Y (Yellow Jacket) for fixture connections; Type R Red Jacket) for 3 No, 12 and less, and Type B (Blue Jacket) for larger connections, up to 2 No. 6 stranded. Connections of larger wires or combinations shall be made with Burndy Servit Type KS, split bolt connector, for wires up to and including No. 1/0 AWAY and Bur. r+dy Oklip, Type KVS, for No, 2/0 AWG and larger, Connections and splices of wires made with 3M, pre - insulated S otchlok connecters do not require any taping or further insulating, Connection made with Burndy connectors shall be taped with 3M Scotch Fit and moulded into a smooth ball with all spaces filled. Over this surface apply three layers of half lapped Scotch No. 33 tape. Splices exposed to weather, bus connections to transformers, shall be made as above and then coated with Scotchkote electrical coating; apply two layers of half lapped friction tape over the entire splice extending approximately one inch beyond the No., 33 tape, then paint the entire splice with Scotchk.ote. Spli.Yes and connections made in ground cable and from cable to ground rcd shall be made by he Cadweici process. 312. FUSES Fuses 0 -30 Amperes 125 V All circuits not over 125 volts tr.; g, •ound and not over 30 ampere capacity shall be fustats, unless otherwis~c• .shown on plan and /or circuit breakers are specified.. .�, -5 Fuses O -600 Amperes Fuses shall be Fusetron dual - element fuses as manufactured by the Bussmann Manufacturing Company, or approved equal. Fuses shall have a minimum interrupting capacity of 100, 000 RMS amperes and carry 500% of rating for a minimum of ten seconds. Fuses of 600 amperes, 600 volts or less, shall be N. E. Ca dimensions. Fuses 650 Amperes and Above Fuses 650 amperes and above shall be BUSS Hi -Cap fuses having current characteristics to coordinate with Fusetron fuses. Fuses shall have a :minimum 100,. 000 RMS ampere short circuit capacity 1nterruptting capacity. Cendractor shall °supply to Owner spare fuses equal to one set for each i -e installed and a minaizrann of 10% of each size installed. 313. SWITCHES AND RECEPTACLES This contractor shall fucni.sh and instal lighting switches where shown on the drawings. All single pole switches shall be Hubbell Cat.; #1221 and #1223 or approved equal, All plates shall be chromium plated, except in the Equipmeoat or Boiler Room which will be brass., Duplex convenience receptacles shall be Hubbell Cat, #5252 or approved equal. All convenience outlets shall be mounted 1' -6" abaare floor unless otherwise noted on plan. All switches shall be !mounted I' -6' above floor unless otherwise noted on plan, . 3140 PANELBOARDS AND CABINETS This contractor shall furnish and install all panelboards as specified a the drawings. Branch circuit panelboards shall be the dead front »' cty type equipped with circuit breakers. Busbars &alll have lug connections for attaching feeders. and arranged for wire grains and 4:11 w rep b °,noes, unless otherwise noted on drawings.. The grounded side of each branch circuit shall be fed direct from the neutral busbar located at imp of panel: The circuit breaker shall control the ungrounded side, Breaker shall h :ve r i± . c vatic release secured through action of bi-metallic trip element engaging mechanism release latch. Breakers shall have taverse tiyne limit characteristics to prevent tripping on momentary overloads, but v.711 trip before high overloads are reached. Mechanism of breaker shall be trip free from handle so that contacts cannot be held closed against short circuit or abnormal overloads. Cabinets shall be of standard make and shall bear the manufacturer's name or :;tamp and the Ursdc! writ er°s' Laboratories inspection label. Lighting and powe' cabinets shatl Ipt i.rmtalled with tope 6' -6 above floor, All cabinet, shall be rigidly secured in place. AU cabinets shall have fronts straight and pi,.rrn.b0 • • 315., EMERGENC EXI'' :LIGHTING The electrical contractor shall furnish and install a complete emergency exit lighting system in each building as shown on plan and as herein specified, and shall conform to the National Electrical Code, 195 9 Edition, and all local codes governing and any subsequent revision thereafter. Emergency and exit lights are to be on separate circuits from the general lighting circuits and these circuits are to be in a separate conduit systesan. The emergency lighting panel shall be of plug Fuse type 8-20 ampere circuits. cuits, The conduit system for emergency and exit lights shall be entirely independent of all other conduit systems. 316. FIXTURE SCHEDIII.,T Fixtures shall be furnished and installed in accordance with the schedule shown on the drawings. 31 1. LIGHTING FIXTURES All lighting fixtures shown on the drawings are to be installed and furnished by this contractor complete with lamp. Fluorescent ballast shall be certified. This contractor shall furnish plaster rings for all recessed fixtures. Upon completion of the installation of the lighting fixtures and lighting equipment, they must be in firs class operating order and in perfect condition as to finish, etc. At the time of final inspection all fixtures and equipment must be complete with required glassware or reflectors which must be clean and free from defects. Any reflector or glassware broken prior to the time of final inspection must be replaced, After lighting lb: Lures and lighting eepipment are executed to the wiring system of the building, the wiring system and the fixtures or equipment must be test free from short Jrcuits and grounds must show an insulation resistance between conductors and between conductors and grounds based on minimum load not less than the requirements of the 1959 edition of the National Electric Code. 316. POWER WIRING This contractor shall furnish and install conduit, wiring and make all electrical connections, leaving all motor: s in operating condition including all controls and control wiring, unless otherwise noted. All disconnect switches shall be furnished and installed by this contractor. Motor starters shall be furnished by others: Final connections at starters anti disconnect switches and controls s;aall be made in conduit. Fin al connections fit motors shall be made with greenfield flexible conduit and .hinge. • CLO SYSTEM. 1.11 et STUDENT UNION BLI33.) This contractor shall furnish and install an extension to the existing Standard Electric Time Company Clock and Program System, The equipment furnished sheik include, but not be limited to the following and shall include all equipment necessary to make a complete operating system. The catalog numbers used are those of the Standard Electric Time Co Master Cloe. #3624-AR2 Tooketer olook ard c7;oeteor program controller to replace arid p'-•r n controller in the Administration BuDdinE, 114e :,up.ster prog,oanl ccntrnPer shall be Eli tegrai unit ciT.iven by a slogle heav: duty synchronous motor operating on 1 60 cycle, A. C It shall be provided with a spring powered mechaniera which shali automatically and ac:mrately operate the master clock and program mechanism during power interruptions of up toll' hours without the use of any eeternal power source, It .hall control the operation of minute impulse secondary clocks and shall auto.r.ai correct ail secondary clocks from errors of up to 25 minutes fat or slow. Power Li D\71.8-11 Power Lit to reploce the enisting power unit in the Admini stration Building Secondfily Clooke: FMT-12-AR2 1.2 -inch flush mounted cloeits, as shown on plans. DM 46-A1:t 2 side wall rriconted„ double faced clocks, Secondary lock movements shall Le of tioe minute irepolse, individually correc- tive type, manufactured to reepond to the corrective pulses tranernaitted by the ireiaseer clock. Secondary clocks shall be finished in satin aluminumn Program. Bells shalli be MA.,i• , 6 inch undordoirie vibrating type, manufactured to operate at 24 volts A, Ivls..nttfr,ci agent Rhal) be responsible. for supervising the final conrierra.cris t1:0,1 master 320, FIRE ALARM SYSTEM - EI.ORMITORY AND STUDENT TINION BLDG. Fu.rnish and inol_411 a.. iie ;n independent Fire Alarm System i. each huii.dg stern of a Fire Alarm Contro3.. Pane, Single 3.ti ak-glass Stad.ons,, Fire Alarm Signals, Thermaii. Deteclor, Wiri. OuzJet. Boxes, and all other material necessary to make a complete orating r-:;;?st.em. The system shall be a closed eircuit, double 9upervised, continuous ringing system, E-8 32Oa FIRE ALARM SYSTEM 13011MITORY UTD STUDENT UNION BLDG, 'Continued) Equipment furnished shall be as manufactured by The Standard Electric Time Company or approved equal. Equipment: Furnish and install, where shown on plans, a UAX 3 Fire Mai m Control Panel, The control panel shall cause all fire alarm signals to sound at the rate of 7 times per minute until the station from which the alarm was initiated has been reset, The control panel shall provide 3 signa . c °.nuts.. each with a capacity of 10 alarm signals. The control fan& and U system co,.npc: s; aUi be under double electrical S App,•. }'.. 7 in . the f_:: �';:; , : a cur. 1 8 ;, •f>and system, a trouble signal &IDAa so :1(3 ' ewl t i fain're of the supply to the primary suiwk-v o - -y s gral -0;Abie si n. al shall sound. Each trouble signal shal.i be prov;; P l$ = d with a silencing switch and trouble light, Terminal shale. be provided cn the cnaa.T.oX panel for connecting remote trouble signals, There shall be provided, as part of the control panel, the necessary relays, terminal s. etc, , for connection to the municipal fire alarm system, in accordance with pant ket # of the National Board of Fire Underwriters, . A switei shall Lie proaidied for the purpose of disconnecting supple mentary- circuits during fire drill or Earl. This "drill" switch shad -°;,u=se an audible 35gr:al to soz?and which cannot be reset until the return to normal and install ;-here shown on the plans!, ingle action breal. sEz s5 Fire Alarm Stations ?ire Aiarrn Statie4ls k hai=e. Yio - rojec bons which could cause a false alarm if a station ts Ezeciciemaly sty: tick or brushed against. Stations shall be operable s th or without Ehe breaicglass rod being installed.. Furnish and install.,, where shown on the plans: 4 - 350 - SP Semi flush grill type Alarm. Horns 4- 355-SF Double profecioc Ho: Horns shall be wound for 12 gip:; !t AC s ries operation Thermal Detectors 320, FIRE .t- IJAR -hi SYSTEM .wog mitory and Student Union ISidg Won't.) Furnish and install, where shown on the plans, #501 fixed temperature and rate -of -rise detectors, which operate at an ambient temperature of 136 degrees, or a rate -of -rise of 15 degrees per minute. Furnish and install where indicated on the plans, #502 fixed temperature and rate-of-rise detectors which operate at an ambient temperature of 190 degrees or a rate-of-rise of 15 degrees per minute, Fire Alarm Control P nets shall be so constructed that any number of :=fdctitiorxs91 st - nals and stations .nay he added without discarding 941: o i gli' - i i ane 7 She. Fire 1arre: : r'.c 7._ �,i . ss :a ' c.,srIT); :: with a:0 focal and state codes and Pha0.. tr:aaet 5r _,_equirpx of the National Board of Fire Underwriters where applicab.le., in general . the wiring shall consist of the followingo From the Control Panel_ 4 - #14 wires common to al:l fire alarm stations or detectors 2 #14 wires common to each circuit of fire alarm bells. - #12 wiz•ea to 120/240 VAC 60 cycle:, This power supply shall, be connected ahead of the main switch, through a two -pole, solid neutral, locked safety switch, painted red, cnd mark d "Fire Alarm Fuses ",. r i 1. , t'2E W :C l+ SYSTEM Dining, President's Dining, L3'd e1'`Ar Of i € ', etc.) The e ec .ric ?i and insta111 a complete intercom system as shown on lien and as herein specified:, The system shafl be a D Kaaie #1A540 system. There will be nine 4,9) phone locations, The Kitchen Office #J233 phone shall be a DuKane #7A2fft0 d sk type All other phones shall be D Kane #7A215,. Furnish and install ai a. conduit„, outlets, wires, etc„_. in accordance i h the manufacturer's wiring diagrams.. The system shall be eompie e and turned over to the Owner in first class working condition, 322. PUBLIC ADDRESS SYSTEM ;STUDENT UNION BLDG) General: This contractor shall furnish all equipment, materials and labor ne cessary for, or reasonably incidental. to, the complete operating installation of a public address system, all as indicated on the drawings and herein specified. All of this equipment shall be installed by the man.ufecturer's distributor in the conduit system provided by the electrical contractor Guarantee and Service AL equipine)e and wiring shell be guaranteed free from defect in ;material and workmenshie ;or period of otie year following date 01 final ae.ceptance„ Al. such defective work during the guarantee period, with Lhe exception of tubes, pilot lamps and fuses, shall be replaced or repaired without cost to the Owner. The contractor shall provide free service and adjustment for one full year following date of final acceptance, without cost to the Owner.. Emi4y3.2.e:o.t. Manufacturer Bid on this Eg y;:ct e .hall he based upon DuKane Corporation equipment and shall be inade eompatiele with the existing DuKane Equipment Etplinfl eat Cabinot requiredi The wall mounted ,ece.pifier equipment eabinet, shall be 194/2" wide, 20-3R6" high, wed 14-1/2 deep:. it shell provide 19-1/4." of panel mounting space !Or standard 19" panels, It shall be equipped with a hinged front doer with .;.ocking faciliLies and perforated panels to provide adequate ventilation. The entire assembly shall be constructed of 16 gauge steel and finished in baked, beige-gray enamel. PtLerarnpliAm !ler The Public Address amplifier shall be designed to deliver 30 watts of audio power with not more than 5% distortion and have not more than 2% distertion at 20 watts:, The frequency response shall be plus or minus I db from 20 to 20 cycles with the tone controls ir the fiat pion.. The senraii.er shall provide input facilities Ter three low ie..i.pecialtee etieee and two high impedance auxiliary ieneets,, it sha'A previde a ini eethle.o.e eere.ral for each input, separate has and treble ceyolee:' ri; 1 :3 P. AC power ewitcli and pilot light. tt Micr-ophune (1 required) The microphone shall be cardioid, dynamic type, with uniform frequency response from 60 to 13, 000 cps. The diaphragm shall be nonmetallic Acoustalloye Available impedances shall be 150 ohma The microphone line shall be balanced to ground on low impedance and phased. Speaker Assemblies The speaker shall be a DuKane Model 9935A -8. Its impedance shall be 8 ohms at 400 and it shall have frequency response rating of 30-15,000 cycles, A 25 volt line -to- speaker transformer shall be mounted on the speak r bracket bbav ±gig a secondary bnpedance of 8 ohms. It shall. have a tapped primary providing 1/2, 1 and 2 watts into its rated speaker load. It shall have an effective frequency response of 30 a 15, 000 cycles. Flush mounted grilles shall be DuKane 06L8. Individual room speakers and /or groupe of speakers (corridor) st.all be indiv.ddnally circuited and pulled back to the existing DuKane console in the Administration Building, This contractor shall add a DuXanie Model 9A57 switchbank to the existing console in order to accept the additional Loudspeaker circuits. Wiring 4 '. 7'' All Public At dress wiring shall, be DuKane #17602, PUBLIC' ADDF' SS SYSTEM tDORM1TORY Speaker Assemblies The speakers shall be a DuKame Model 9935A-8., Its impedance shall be 8 ohms at 400 and it shall have E: frequency response rating of 30 15, 000 cycles, A 25 Ton line -to- speaker transformer shall be mounted on the speaker bracket having a secondary impedance of 8 a tapped p rimal. providing 1/2, 1 and 2 watts into he A:atee! :taker iced. It shall have an effective frequency resi.yce se of 30 15, 000 cycles,. Flush mounted grilles ,hall be DuKane -12 322, PUBLIC ADDRESS SYSTEM - DORMITORY) (Con't„) Speaker Assemblies (con't.) An corridor speakers shall be individually circuited and pulled back to the existing Du Kane console in the existing Administration building. This contractor shall add a Du Kane Model 9A575 switch- bank to the existing console in order to accept the additional loudspeaker circuits Vffieing !i. Addre SF+ wm.ng e theicane #176-2. 323 i'Fi`,//SION S (Student Union Bid .) (Conduit .Only) The electrical contractor sea)i. fernish ad install conduit and outlets only for the Television Antenna Systeir. From the amplifier back box puJi RG59U cable to all teleeision outlels where indicated on the plans: From the amplifier back box run 3/4" cenduit up thru roof and cap: Wiring shall be left interminated and T. V outlets shall be covered with single gang blank plates. 324. TELEPHONE SYSTEM The electrical contractor shall furnish and install all conduit, out terminal cabinets, etc„ in eac building for the telephone system, as shown on plan and as hereie sviecified. From each building tertelnal box„ run an underground conduit i,size as recommended by ;the ioeat telephone cornpanyi the existing switchboard. In eac': beildiege run a xeaxineum of 4 telephone outlets per home run. The home run stall be I" eoncut, the remaining three outlets to have 314" •onduit coneiected to them: Rua i1 home runs to the telephone terminal cabinet -el:lere ho: on plan., All work shall. be don u .rdmce with the rules and regulations of the local telephone compa.n:e. 325, SERVICe.; ENTRANCE The ele4eL eontractor shark furnish and instaL all equipment necessary for the eec-trical. services to each bunding as shown on plan and as herein specified He sheit; futeilish all underground cable, underground conduit pose eer entrance equipment, etc. All poles shall be of the same as the existing. The existing is primary metered end khe e:ecendary i O /O8 Volt, 4 wire„ 3 phase. The eoeeractor shall coneeit With the FIeekcia Power and Jeeght Co. regarding their reeerelrereen:!.e., Hesh an imciude in his bid all excess service cha.eies 7:.ecAuirefl Fi.eri Power and Light Company. The street lighting system shall consist essentially of a concrete standard, incandescent luminaire, multiple lamp, and necessary cable and control. The concrete standard shall. be American Concrete design 705-13-21- IA prestressed standard with precast butt base. The bracket shall be 4 ft. long with 2" slip fitter:. It shall. be sand and gravel with honed finieh.. The da ;:- iir'itix:g i '. 21.'£ The inr_ des:: :en t S#1568229 type AK-6. The •distg ibut .. l.i '.LIES tyre II It shall be 1¢1/4" side cnount ^d with :.,1�= ?�a . > , r: = pt e and socket. It sheaf be hinged for 'c1- :r?: :l,' r; alr ; - r . e 'h Lin sham h.5 ; VileStiDerYotifft 91 `" 2500 luxuen rating with 3000 hour , average lire. J t' e contro?. < irr;-jit shake be 120 s = `:erhi;.ti shall be aetiva£ed by nizans of pushbutton kc'cate6 ='s'; a po... ";t fo . :o iverl.erit operatioii. \ilesling- h,ous.e #5.. 2 Ir station wi► :ha rini.xi airs a s on aet, surface mounting N &MAI„ The controk unit shall! be kCOC #4999 Muitiple relay 30 amp, single pole, type 1712 - T with load fuse, " j, caLi :;hash! lb Iiazasheath #6 single conductor solid 600 volt . .1. 1 1e. f . shalt/ be type RR for direct burial according .,0 the Aare .d shown on the plan. Ti-. e shall be no splices in the s tha . i:. buried: Fi' splices rirG ner. scary they shall be made ba,,t' of z:**te standard ?h'te: -e a 17.-.ui hoT„.e is located for this p eat:1! mils." be Eii :. {4 '," r .-, a<`r. • ;F..t 'ter single conductor solid type RH -RW . The safety switch be yips; .nghi :,F;flse #CAF .221 fusible safety switch 2 !,.so. e, 30 amp rat standard d? a:y Conduit wht?i'f' il.ecessa..'y 7 b..:5 be Standard Galvanized rigid 1 1" conduit. 327, WATERPROOFING Ali. of. th"+a' �° r i '�6� wF ;'.�'•� };•; " :. When p.pes pass through outis do al s. :air. Cosxtra shall remove ala loose uiateriai around pipe : - and drive oakum end lead wont tightly arcvIn i to or c•.oracini orti Leh 7. :;<! as welt h. as inaes'ior of the •,ara .' . -Fe z _ ? :E � . :?;' e ii?iaah off exterior wa3.1. with two waking for an absolute C entractcr backfills„ V 3 2 B. i 1 iz C.TLON All panels, cabinets, switches, circuits, etc, , shall be suitably marked in a permanent manner to indicate the use of each piece of equipment and the space served. Provide in the main lighting distribution board and in eoch branch circuit panel a permanent directory to indentify all circuits in these cabinets. 329, 13 ALANCING OF LOAD Thi con'',.eac OTD. , ation connecting a1i. circliits to panels and To the',..r wiTh 11C /7 on, disconnect and reconnect cirs.ss se elhat loa:i in tu wi not he greater than :3'Yr bei pha.s,t7ts The balancing or laod had b pF-- Ell, each panel, 330,. PAINTING The 'remits of panel face plates and other devices as hereinbeore specified shaU he finished as approved by the Architect. Ail other exposed work installed by this contractor shall be painted two coats of lead and oil; final coat as approved by the Architects. 331. TESTS AND ADJUSTMENTS This contractor shall test aU: equipment installed by him as necessary to show that it complies with arit esa.a.rements specified; testing shall be done in a m.anaer approvad by the Architect. ThIS oracior hIL 011:? in.stal,ation in operation, and make .7.:orirk..--!cti. 111161 it is shown to be in perfect werating 332, GUARANTEE This contractor sba! guarantee the en.tise, iastallaV.on and all.parts thereof against defects in materia1 ar:,1 worionauship for a period of one year frau the date of final sertificate and shall repa:x or replace any part which may 8how aigns of .failure in that thue, if such failure, in the opinion G7 the .Arelas.t„ is due to imperfection inaterial or to improper woak.manship.