RAFAEL E. DROZ-SEDA, P.E.
CIVIL ENGINEER 4 5TRUCTURAL IN5PECTOR
OF THRESHOLD BUILDINGS
FL. PE No. 35228 t 843
5130 CRE5CENT DRIVE, TURTLE BAY
MIRAMAR, FLORIDA 33025
PHONE:(305) 562-1452
ADDITION LEGALIZATION
TO RESIDENCE
941 NE 91st Terrace
Miami Shores, FL 33138
Owner: Elise Fable
TABLE OF CONTENT
Description
01-07 Foundations Design
08-12 Beams Design
13-14 Wood Rafter Design
15-18 C.M.U. Wall Design
19-20 Wind Load Analysis as per ASCE 7-10
�'6 N-/5319
FEMArDO G90W=Z-PKk PE
CCNMLTM e+oRAM
FL. P.E. No 14710 (CIVIL)
250 CATALONIA AVE. #404
CORAL GABLES, FL. 33134
TEL (305) 461-2188
FAX. (305) 461-2238
JOB b- EL-/
ADDRESS
PROJECT No SHEET No OF
CALCULATED BY DATE
CHECKED BY DATE
i
'eo0 --'T \-20
(v0 0
27s
_
<L
�_.330..
•:
ROO,� }(.=i0 /Fi�J.v?.��-'`�' �_(�'�"_� s.)--
_�.20 _
330
'.
QW
a c
ZOi iE '4 —
,ZONc F
(0.6)
- 3, 2
- /D
-2 Z.
-. ..
01
Title :
Dsgnr:
Description
Scope:
Job #
Date: 10:OOPM, 4 MAY 14
Kev: bwuuu Page 1
User. KW-0605358, Ver5.8.0, 1-Dec2003 General Footing Analysis & Design
(c)1883-2003 ENERCALC Engineering Software ELISE_FABLE-ADDITION.ECW:Fooungs
Description WF-16 (qs'=2.0 ksf)
General Information
Code Ref: ACI 318-02, 1997 UBC, 2003 IBC, 2003 NFPA 5000
Allowable Soil Bearing
2,000.0 psf
Dimensions...
Short Term Increase
1.330
Width along X-X Axis
1.333 ft
Seismic Zone
0
Length along Y-Y Axis
1.000 ft
Biaxial Applied Loads
Footing Thickness
12.00 in
Live & Short Term Combined
Cal Dim. Along X-X Axis
8.00 in
fc
3,000.0 psi
Col Dim. Along Y-Y Axis
12.00 in
Fy
60,000.0 psi
Base Pedestal Height
0.000 in
Concrete Weight
150.00 pcf
e
Min Steel /0
0.0014
Overburden Weight
g
100.00 psf
p
Rebar Center To Edge Distance
3.50 in
Loads
Applied Vertical Load...
Dead Load
1.600 k
...ecc along X-X Axis
0.000 in
Live Load
0.700 k
...ecc along Y-Y Axis
0.000 in
Short Term Load
k
Creates Rotation about Y-Y Axis
Applied Moments...
(pressures @ left & right)
Dead Load
k-ft
Live Load
k-ft
Short Term
k-ft
Creates Rotation about Y-Y Axis
Applied Shears...
(pressures @ left & right)
Dead Load
k
Live Load
k
Short Term
k
Creates Rotation about X-X Axis
(pressures @ top & bot)
k-ft
k-ft
k-ft
Creates Rotation about X-X Axis
(pressures @ top & bot)
k
k
k
Footing Design OK
1.33ft x 1.00ft Footing,
12.Oin Thick, w/ Column Support 8.00 x 12.00in x O.Oin high
1.33ft x 1.00ft Footing,
12.Oin Thick, w/ Column Suppo
DL+LL
DL+LL+ST
Actual
Allowable
Max Soil Pressure
1,925.4
1,925.4 psf
Max Mu
0.139 k-ft
per ft
Allowable
2.000.0
2,660.0 psf
Required Steel Area
0.259 in2 per ft
"X Ecc, of Resultant
0.000 in
0.000 in
Shear Stresses....
Vu
Vn * Phi
"Y Ecc, of Resultant
0.000 in
0.000 in
1-Way
0.000
93.113 psi
X-X Min. Stability Ratio No Overturning
1.500 :1
2-Way
0.000
186.226 psi
Y-Y Min. Stability Ratio No Overturning
Shear Forces
ACI C-1
ACI C-2
ACI C-3
Vn * Phi
Two -Way Shear
0.00 psi
0.00 psi
0.00 psi
186.23 psi
One -Way Shears...
Vu @ Left
0.00 psi
0.00 psi
0.00 psi
93.11 psi
Vu @ Right
0.00 psi
0.00 psi
0.00 psi
93.11 psi
Vu @ Top
0.00 psi
0.00 psi
0.00 psi
93.11 psi
Vu @ Bottom
0.00 psi
0.00 psi
0.00 psi
93.11 psi
Moments
ACI C-1
ACI C-2
ACI C-3
Ru / Phi
As Rea'd
Mu @ Left
0.14 k-ft
0.10 k-ft
0.06 k-ft
2.1 psi
0.26 in2
per ft
Mu @ Right
0.14 k-ft
0.10 k-ft
0.06 k-ft
2.1 psi
0.26 in2
per ft
Mu @ Top
0.00 k-ft
0.00 k-ft
0.00 k-ft
0.0 psi
0.02 in2
per ft
Mu @ Bottom
0.00 k-ft
0.00 k-ft
0.00 k-ft
0.0 psi
0.02 in2
per ft
02
Title : Job #
Dsgnr: Date: 10:0012M, 4 MAY 14
Description
Scope :
Rev.580000 Page 2
User: KW-W05358, Ver 5.8.0, 1-Deo-2003 General Footing Analysis & Design
(c)1983-2003 ENERCALC Engineering Software ELISE_FABLE ADDITION.ECW:FooSngs
Description WFA6 (qs'=2.0 ksfl
Soil Pressure Summary
Service Load Soil Pressures
Bottom- Top -Rig
Bottom-
Top-Lef
DL + LL
1,925.42 1,925.42
1,925.42
1,925.42 psf
DL + LL + ST
1,925.42 1,925.42
1,925.42
1,925.42 psf
Factored Load Soil Pressures
ACI Eq. C-1
2,853.13 2,853.13
2,853.13
2,853.13 psf
ACI Eq. C-2
2,139.84 2,139.84
2,139.84
2,139.84 psf
ACI Eq. C-3
1,260.26 1,260.26
1,260.26
1,260.26 psf
ACI Factors (per ACI 318-02, applied internally to entered loads)
ACI C-1 & C-2 DL
1.400 ACI C-2 Group Factor
0.750 Add"I "1.4" Factor for Seismic 1.400
ACI C-1 & C-2 LL
1.700 ACI C-3 Dead Load Factor
0.900 Add"I "0.9"
Factor for Seismic 0.900
ACI C-1 & C-2 ST
1.700 ACI C-3 Short Term Factor
1.300
....seismic = ST " :
1 A 00 Used in ACI C-2 & C-3
03
a
Title:
Dsgnr:
Description
Scope:
Job #
Date: 10:04PM, 4 MAY 14
User. KW-0605358, Ver 5.8.0, 1-Dec-2003 Square Footing Design
ig
Pa e
(c)1983-2003 ENERCALC Engineering Software �7 ELISE_FABLEADDITION.ECW:Fooiings
Description F-3x3x12 (12-4)
General Information
Code Ref: ACI 318-02, 1997 UBC, 2003 IBC, 2003 NFPA 5000
Dead Load
12.000 k
Footing Dimension
3.000 ft
Live Load
4.500 k
Thickness
12.00 in
Short Term Load
0.000 k
# of Bars
4
Seismic Zone
0
Bar Size
5
Overburden Weight
0.000 psf
Rebar Cover
3.250
Concrete Weight
150.00 pcf
Pc
3,000.0 psi
LL & ST Loads Combine
Fy
60,000.0 psi
Load Duration Factor
1.330
Column Dimension
0.00 in
Allowable Sail Bearing
2,000.00 psf
Note: Load factoring supports 2003 IBC and 2003 NFPA 5000 by virtue of their references to ACI 318-02 for concrete design.
Factoring of entered loads to ultimate loads within this program is according to ACI 318-02 C.2
Reinforcing
Rebar Requirement
Actual Rebar "d" depth used
8.438 in
As to USE per foot of Width
0.259 in2
200/Fy
0.0033
Total As Req'd
0.778 in2
As Req'd by Analysis
0.0009 in2
Min Allow % Reinf
0.0014
Min. Reinf % to Req'd
0.0014 %
Summary
Footing OK
3.00ft square x 12.Oin thick
with 4- #5 bars
Max. Static Soil Pressure
1,983.33 psf
Vu : Actual One -Way
23.03 psi
Allow Static Soil Pressure
2,000.00 psf
Vn*Phi : Allow One -Way
93.11 psi
Max. Short Term Soil Pressure
1,983.33 psf
Vu : Actual Two -Way
87.42 psi
Allow Short Term Soil Pressure
2,660.00 psf
Vn*Phi : Allow Two -Way
186.23 psi
Alternate Rebar Selections...
Mu :Actual
3.29 k-ft / ft
4 # 4's 3 # 5's
2 # 6's
Mn * Phi: Capacity
14.94 k-ft / ft
2 # 7's 1 # 8's
1 # 9's 1 # 10's
04
Title :
Dsgnr:
Description
Scope:
Job #
Date: 10:06PM, 4 MAY 14
Rev: 580000 Page 1
User KW-=5358, ver 5.8.0,1-0ee-2003 Square Footing Design ELISE FABLE_ADDI nON.ECw'Beams
i9 n _
(c)1983-2003 ENERCALC Engineering Software
Description F-3x3x12 (8-8)
General Information
Code Ref: ACI 318-02, 1997 UBC, 2003 IBC, 2003 NFPA 5000
_ . ..
Dead Load
8.500 k
_ .... ._ ..... ...
Footing Dimension
- -=--.
3.000 ft
Live Load
8.000 k
Thickness
12.00 in
Short Term Load
0.000 k
# of Bars
4
Seismic Zone
0
Bar Size
5
Overburden Weight
0.000 psf
Rebar Cover
3.250
Concrete Weight
150.00 pcf
Pc
3,000.0 psi
LL & ST Loads Combine
Fy
60,000.0 psi
Load Duration Factor
1.330
Column Dimension
0.00 in
Allowable Soil Bearing
2,000.00 psf
Note: Load factoring supports 2003 IBC and 2003 NFPA 5000 by virtue of their references to ACI 318-02 for concrete design.
Factoring of entered loads to ultimate loads within this program Is according to ACI 318-02 C.2
Reinforcing
Rebar Requirement
Actual Rebar "d" depth used
8.438 in
As to USE per foot of Width
0.259 in2
200/Fy
0.0033
Total As Req'd
0.778 in2
As Req'd by Analysis
0.0009 1n2
Min Allow % Reinf
0.0014
Min. Reinf % to Req'd
0.0014 %
3.00ft square x 12.Oin thick with 4- #5 bars
Max. Static Soil Pressure
1,983.33 psf
Allow Static Soil Pressure
2,000.00 psf
Max. Short Term Soil Pressure
1,983.33 psf
Allow Short Term Soil Pressure
2,660.00 psf
Mu :Actual
3.42 k-ft / it
Mn * Phi: Capacity
14.94 k-ft / ft
p
Vu : Actual One -Way
Vn*Phi : Allow One -Way
Vu : Actual Two -Way
Vn*Phi : Allow Two -Way
Alternate Rebar Selections...
4 # 4's 3 # 5's
2 # 7's 1 # 8's
Footing OK
23.95 psi
93.11 psi
90.90 psi
186.23 psi
2 # 6's
1 # 9's 1 # 10's
05
Rev: 580000
User KW-0605358.
(c)1683-2003 EHER
Description
1-Dec-2003
ineering Software
F-4x4x2 (25-4)
Title :
Dsgnr:
Description
Scope:
Square Footing Design
Job #
Date: 10:08PM, 4 MAY 14
Page 1
General Information
Code Ref: ACI 318-02, 1997 UBC, 2003 IBC, 2003 NFPA 5000
Dead Load
25.000 k
Footing Dimension
4.000 ft
Live Load
4.000 k
Thickness
12.00 in
Short Term Load
0.000 k
# of Bars
6
Seismic Zone
0
Bar Size
6
Overburden Weight
0.000 psf
Rebar Cover
3.250
Concrete Weight
150.00 pcf
fc
3,000.0 psi
LL & ST Loads Combine
Fy
60,000.0 psi
Load Duration Factor
1.330
Column Dimension
0.00 in
Allowable Soil Bearing
2,000.00 psf
Note: Load factoring supports 2003 IBC and 2003 NFPA 5000 by virtue of their references to ACI 318-02 for concrete design.
Factoring of entered loads to ultimate loads within this program is according to ACI 318-02 C.2
Reinforcing
Rebar Requirement
Actual Rebar "d" depth used
8.375 in
As to USE per foot of Width
0.259 in2
200/Fy
0.0033
Total As Req'd
1.037 in2
As Req'd by Analysis
0.0015 in2
Min Allow % Reinf
0.0014
Min. Reinf % to Req'd
0.0020 %
4.00ft square x 12.Oin thick with 6- #6 bars
Max. Static Soil Pressure
1,962.50 psf
Allow Static Soil Pressure
2,000.00 psf
Max. Short Term Soil Pressure
1,962.50 psf
Allow Short Term Soil Pressure
2,660.00 psf
Mu :Actual
5.64 k-ft / It
Mn * Phi: Capacity
22.95 k-ft / ft
Vu : Actual One -Way
Vn*Phi : Allow One -Way
Vu : Actual Two -Way
Vn*Phi : Allow Two -Way
Alternate Rebar Selections...
6 # 4's 4 # 5's
2 # 7's 2 # 8's
Footing OK
36.57 psi
93.11 psi
156.06 psi
186.23 psi
3 # 6's
2 # 9's 1 # 10's
Title : .lob #
Dsgnr: Date: 10:10PM, 4 MAY 14
Description
Scope:
Rev: 580000User. KW-0605356, Ver 5.8.0, 1-Dec-2003Designg
Square Footing Pa e 1
(c)1983-2003 ENERCALC Engineering Software "� 9ELISE FABLE ADDITION.EMBeams
Description F-442 (17-12)
General Information
Code Ref: ACI 318-02, 1997 UBC, 2003 IBC, 2003 NFPA 5000
Dead Load
17.500 k
Footing Dimension
4.000 ft
Live Load
12.000 k
Thickness
12.00 in
ShortTerm Load
0.000 k
# of Bars
6
Seismic Zone
0
Bar Size
6
Overburden Weight
0.000 psf
Rebar Cover
3.250
Concrete Weight
150.00 pcf
fc
3,000.0 psi
LL & ST Loads Combine
Fy
60,000.0 psi
Load Duration Factor
1.330
Column Dimension
0.00 in
Allowable Soil Bearing
2,000.00 psf
Note: Load factoring supports 2003 IBC and 2003 NFPA 5000 by virtue of their references to ACI 318-02 for concrete design.
Factoring of entered loads to ultimate loads within this program Is according to ACI 318-02 C.2
Reinforcing
Rebar Requirement
Actual Rebar "d" depth used
8.375 in
As to USE per foot of Width
0.259 in2
200/Fy
0.0033
Total As Req'd
1.037 in2
As Req'd by Analysis
0.0016 in2
Min Allow % Reinf
0.0014
Min. Reinf % to Req'd
0.0022 %
4.00ft square x 12.Oin thick with 6- #6 bars
Max. Static Soil Pressure
1,993.75 psf
Allow Static Soil Pressure
2,000.00 psf
Max. Short Term Soil Pressure
1,993.75 psf
Allow Short Temp Soil Pressure
2,660.00 psf
Mu :Actual
6.03 k-ft / ft
Mn * Phi: Capacity
22.95 k-ft / ft
Vu : Actual One -Way
Vn*Phi : Allow One -Way
Vu : Actual Two -Way
Vn*Phi : Allow Two -Way
Alternate Rebar Selections...
6 # 4's 4 # 5's
2 # 7's 2 # 8's
Footing OK
39.08 psi
93.11 psi
166.78 psi
186.23 psi
3 # 6's
2 # 9's 1 # 10's
MA
�MANDO GOMEZ-FNA., PE
OONBtIL1N�# Fa
FL. P.E. No 14710 (CIVIL)
250 CATALONIA AVE. #404
CORAL GABLES, FL. 33134
TEL (305) 461-2188
FAX. (305) 461-2238
JOB
ADDRESS
PROJECT No
CALCULATED BY
CHECKED BY
SHEET No OF
DATE
DATE
......... _._........ - .---- - ----- ---_. _w _ _.._ ---..... ................ _. _ w.---_ _.._.._ _._..... --- ....-.
_..............._......»..._w._..,..,...---..._.,_..._...,...........,,..,........-....i....,_....._,.........Ir,lip....-----._..........«.......... ...,....................... _............ ........._._.....��__._..;..._..__...�..__......._.__........ -... ...... ............. .......... ._........ _... ...... .__.. _.......... ».... .._.
,
, !
._w»
' '
_...._..._:...__.._ w._..:..__._---:.._...•„y.-. .._:._.»_._._;__......_..:__.__.w,;•_._-__i••_w._.._.r.._._..i..___._.i...__..__.:—._.. ___ ._._ _._. ._. _ ._.._ .-.. .. _.___ ......w ,...___..._._.. _._
:
.... _._._ _ _._ _._ __ _ __ __.. _ _. _ .__ .......__ _
;
_.........._..._.»..._......._..-._,......:- �.... .«_......... _..... _......._.. __....._.. .«_._ ......... �_....._._.i ..... .....,....�..............:—.....-....... ,... .........i
... ._ a - ....
i
/ 44
' ' ._-. s -
i
i
; ;
._._.- �.
i ( ; i y
i
+
,
;
46
;
s
'
o-e o V. mot: T"je
- I i
i E
r
i
f i
s , , ,
}
i
e i .
F
,
i
I .............., ......-..-..-:_........j.,........_.:... ...... .... y...... ....... ;.w.. ; - .-.... __.... ........... .......... ........ ......,. ....... —............. ...... « ..... ... _...... �....... ........
i»-_........ ...... . .......... �- _—. . ....... _.. __.. « - _._ _...__ __ . _... _._._. _._...... ' - __
i
f.. ........ ..-... . i ... .......... .....-._ i.............._._......;....._..__i........«._.i..._.....__i. .._.........._... ._.. i._.__.....i._ ..... _ _.._.. ..... _. — _.__ ...—.......... — .......__........-........... _..._.—�._..._.ti...___.....«.... «.. .._w...i i �
•
Title : Job #
Dsgnr: Date: 2:11AM, 3 MAY 14
Description
• Scope:
Rev- 580002 �A Page 1
User. KW40605358, Ver5.8.0, 1-Dec2003 Multi -Span Steel Beam
(c)1383-2003 ENERCALC Engineering Software ELISE FABLE_ADDITION.EMBeam
Description W12x22 Steel Beam (1-Spans)
General Information
Code Ref: RISC 9th ASD, 1997 UBC, 2003 IBC, 2003 NFPA 5000
Fy - Yield Stress
36.00 ksi
Load Duration Factor
1.00
Spans Considered Continuous Over Supports
Span information
Description
s-1
Span ft
16.00
Steel Section
w12x22
End Fixity
Pin -Pin
Unbraced Length ft
4.00
Loads
Live Load Used This Span?
Yes
Dead Load k/ft
0.376
Live Load k/ft
0.330
Results
Mmax @ Cntr k-ft
22.59
@ X = ft
8.00
Max @ Left End k-ft
0.00
Max @ Right End k-ft
0.00
fb : Actual psi
10,696.4
Fb : Allowable psi
23,760.0
Bending OK
fv : Actual psi
1,764.7
Fv : Allowable psi
14,400.0
Shear OK
Reactions & Deflections
Shear @ Left k
5.65
Shear @ Right k
5.65
Reactions...
DL @ Left k
3.01
LL @ Left k
2.64
Total @ Left k
5.65
DL @ Right k
3.01
LL @ Right k
2.64
Total @ Right k
5.65
Max. Deflection in
-0.230
@ X = ft
8.00
Span/Deflection Ratio
834.4
Query Values
Location ft
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Shear k
5.65
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Moment k-ft
-0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Max. Deflection In
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Title :
Dsgnr:
Description
Scope
Rev: 580002
User: KW-=5358, Ver 5.8.0, 1-Dec-2003 Multi -Span Steel Beam
(c)1983-2003 ENERCALC Engineering Software
Description W12x22 Steel Beam (2-Spans)
.lob #
Date: 2:21AM, 3 MAY 14
Page 1
General Information Code Ref: AISC 9th ASD, 1997 UBC, 2003 IBC, 2003 NFPA 5000
Fy - Yield Stress 36.00 ksi Load Duration Factor 1.00
Spans Considered Continuous Over Supports
Span Information
Description
s-1
s-2
Span
ft
12.00
12.00
Steel Section
w12x22
ws2x22
End Fixity
Pin -Pin
Pin -Pin
Unbraced Length
ft
4.00
4.00
Loads
Live Load Used This Span ?
Yes
Yes
Dead Load
k/ft
0.600
0.600
Live Load
k/ft
0.720
0.720
Point #1 DL
k
3.010
LL
k
2.640
@ X
ft
4.000
Results
Mmax @ Cntr
k-ft
26.59
11.55
@ X =
ft
4.00
7.84
Max @ Left End
k-ft
0.00
-28.78
Max @ Right End
k-ft
-28.78
0.00
fb : Actual
psi
13,627.3
13,627.3
Fb : Allowable
psi
23,760.0
23,760.0
Bending OK
Bending OK
fv : Actual
psi
3,812.4
3,223.9
Fv : Allowable
psi
14,400.0
14,400.0
Shear OK
Shear OK
Reactions & Deflections
Shear @ Left
k
9.29
10.32
Shear @ Right
k
12.20
5.52
Reactions...
DL @ Left
k
4.48
10.45
LL @ Left
k
4.80
12.07
Total @ Left
k
9.29
22.52
DL @ Right
k
10.45
2.48
LL @ Right
k
12.07
3.04
Total @ Right
k
22.52
5.52
Max. Deflection
in
-0.107
-0.041
@ X =
ft
5.04
7.36
Span/Deflection Ratio
1,344.9
3,509.4
Query Values
Location
ft
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Shear
k
9.29
10.32
0.00
0.00
0.00
0.00
0.00
0.00
Moment
k-ft
0.00
-28.78
0.00
0.00
0.00
0.00
0.00
0.00
Max. Deflection
in
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
10
Title :
Dsgnr:
Description
Scope:
Job #
Date: 10:18PM, 4 MAY 14
Rev: bUWUU Page 1
User:KW-0605358.Ver5.8.0.1-Dec-2oo3 Multi -Shan Concrete Beam
(c)1983-2003 ENERCALC Engineering Software �" ELISE_FABLE ADDITION.EMBeams
Description TB (8"x12") Conc. Beam
General Information Code Ref: ACI 318-02, 1997 UBC, 20031BC, 2003 NFPA 6000
Fy 60,000.0 psi Spans Considered Continuous Over Supports ACI Dead Load Factor 1.40
fc 3,000.0 psi Stirrup Fy 60,000.0 psi ACI Live Load Factor 1.70
Concrete Member Information
Description
S-1
Span
ft
12.00
Beam Width
in
8.00
Beam Depth
in
12.00
End Fixity
Pin -Pin
Reinforcing Center
Area
0.62in2
Bar Depth
9.75in
Left
Area
0.62€n2
Bar Depth
2.25in
R€ght
Awl
0.62€n2
Bar Depth
2.25€n
Loads
Us€ng L€ve Load This Span ??
Yes
Dead Load
k/ft
0.451
Live Load
k/ft
0.330
Results
Beam OK
Mmax @ Cntr
k-ft
21.46
@ X =
ft
6.00
Mn * Phi
k-ft
24.66
Max @ Left End
k-ft
0.00
Mn * Phi
k-ft
24.66
I
Max @ Right End
k-ft
0.00
Mn * Phi
k-ft
24.66
Bending OK
Shear @ Left
k
7.15
Shear @ Right
k
7.15
Reactions & Deflections
DL @ Left
k
2.71
LL @ Left
k
1.98
Total @ Left
k
4.69
DL @ Right
k
2.71
LL @ Right
k
1.98
Total @ Right
k
4.69
Max. Deflection
in
-0.279
@ X =
ft
6.00
Inertia: Effective
in4
417.71
Shear Stirrups
Stirrup Rebar Area
in2
0.220
Spacing @ Left
in
4.88
Spacing @ .2*L
in
4.88
Spacing @ .4*L
in
Not Req'd
Spacing @ .6*L
in
Not Req'd
Spacing @ .8*L
in
4.88
Spacing @ Right
in
4.88
11
Title : Job #
Dsgnr. Date: 10:18PM, 4 MAY 14
Description
Scope:
Rev:580000 Page 2
User KW-0605358•Ver5.8.0,,-Deo-2003 Multi -Span Concrete Beam
(c)M3-2003 ENERCALC Engineering Software ELISE FABLE_ADDITION.EMBeams
Description TB (8" A T) Conc. Beam
Location
it
0.00
Moment
k-ft
-0.0
Shear
k
7.2
Deflection
in
0.0000
12
Title :
Dsgnr:
Description
Scope:
nor. :ivww
User KW-06os358.ver5.a.0,1-3ec-2003 Multi -Span Timber Beam
(c)19W-2003 ENERCALC Engineering Software
Description Joist 2"x12" @ 12" o.c. (Gravity-16' Span)
Job #
Date: 11:31 PM, 4 MAY 14
Page 1
tads & ,foists
General Information Code Ref: 2001 NDS, 2003 IBC, 2003 NFPA 5000. Base allowables are user defined
_.
Southern Pine, No.2 2 -4 Thick, 10 Wid Fb : Basic Allow 1,050.0 psi Elastic Modulus 1,600.0 ksi
Spans Considered Continuous Over Support Fv : Basic Allow 175.0 psi Load Duration Factor 1.000
Note: Repetitive Member Stress Increase of 1.15 being used for all members under 4" wide
Timber Member Information
Description
5-1
Span ft
16.00
Timber Section
2x12
Beam Width in
1.500
Beam Depth in
11.250
End Fixity
Pin - Pin
Le: Unbraced Length ft
8.00
Member Type
Sawn
Loads
Live Load Used This Span ?
Yes
Dead Load #fft
25.00
Live Load #/ft
30.00
Results
@x=
Max @ Left End
Max @ Right End
fb : Actual
Fb : Allowable
Shear @ Left
Shear @ Right
fv : Actual
Fv : Allowable
ftj 8.00
in-k 0.0
in-k 0.0
psi 667.5
psi 693.7
Bending OK
k 0.44
k 0."
psi 34.9
psi 175.0
Shear OK
Reactions & Deflection
LL @ Left k
0.24
Total @ Left k
0.44
DL @ Right k
0.20
LL @ Right k
0.24
Total @ Right k
0."
Max. Deflection in
-0.285
@ X = ft
8.00
.uery Values
Moment in-k 0.0
Shear k 0.4
Deflection in 1 0.0000
13
Title : Job #
Dsgnr: Date: 11:34PM, 4 MAY 14
Description
Scope:
Row.580000 Page 1
User KW-06053s8.ver5•a•a1-Dec.2003 Timber Ledger Design
(c)1383-2003 ENERCALC Engineering Software 9EUSE_FABLE_ADDITION.ECKStuds & ,foists
Description 2-211x10" Wood Ledger Design
General Information
Code Ref: 2001 NDS, 2003 IBC, 2003 NFPA 5000. Base allowables are user defined.
Ledger Width
...
3.000 in
Uniform Load...
Point Load...
Ledger Depth
9.250 in
Dead Load
360.00 #fft Dead Load
0.00 lbs
Live Load
300.00 #fft Live Load
0.00 lbs
Bolt Diameter
314"
Spacing
0.00 It
Bolt Spacing
12.000 in
Horizontal Shear
0.00 #tft Offset
0.00 in
Load Duration Factors... Southern Pine, No.2 2 -4 Thick, 8 Wide
Live Load 1.250 Fb Allowable 1,200.0 psi
Short Term 1.330 Fv Allowable 175.0 psi
Ledger Stresses
Load Combination:
DL + LL
DL + ST
DL + LL + ST
Maximum Moment
660.00 in-#
360.00 In-#
660.00 in-#
Bending Stress
15.43 psi
8.41 psi
15.43 psi
Stress Ratio
0.010
0.005
0.010
MaximumShear
431.41 lbs
235.31 lbs
431.41 lbs
Shear Stress
15.55 psi
8.48 psi
15.55 psi
Stress Ratio
0.071
0.036
0.067
Bolt Loading Note: Bolt Design Value from NDS 8.21 UBC 23
Using :Southern Pine
Stress Summary
DL + LL
Max. Vertical Load
660.00 lbs
Allow Vertical Load
3,687.50 lbs
Max. Horizontal Load
0.00 lbs
Allow Horizontal Load
7,687.50 lbs
Angle of Resultant
90.0 degrees
Diagonal Component
660.00 lbs
Allow Diagonal Force
933.83 lbs
Final Stress Ratio
0.707 : 1.00
Summary
Stress Summary
DL + LL
Wood Bending Stress Ratio
0.010 :1.00
Wood Shear Stress Ratio
0.071 :1.00
Bolt Stress Ratio
0.707 :1.00
DL + ST
DL+L_+ST
360.00 lbs
660.00 lbs
3,923.50 lbs
3,923.50 lbs
0.00 lbs
0.00 lbs
8,179.50 lbs
8,179.50 lbs
90.0 degrees
90.0 degrees
360.00 lbs
660.00 lbs
979.18 lbs
979.18 lbs
0.368 : 1.00
0.674 :1.00
Wood Stress & Bolts OK
DL + ST DL+LL+ST
0.005 :1.00 0.010 :1.00
0.036 :1.00 0.067 :1.00
0.368 :1.00 0.674 :1.00
14
Title:
Dsgnr:
Description
Scope:
Job #
Date: 9:54PM, 4 MAY 14
Rev. 580000 Page 1
User. KIAI-0605358. Ver 5.8.0, 1-Deo-2003 Masonry Wall Design
(c)1883-2003 ENERCALC Engineering Software ELISE FABLE ADDITION.ECW:CMU
Description 8" Reinf. C.M.U. Wall Design (Zone-4)
General Information Code Ref: ACI 530-02 N
Wall Height 12.00 ft
Seismic Factor
0.0000
fm 1,500.0 psi
Parapet Height 0.00 ft
Calc of Ern = fm *
900.00
Fs 24,000.0 psi
Duration Factor
1.330
Special Inspection
Thickness 8.0 in
Wall Wt Mult.
1.000
Grout @ Rebar Only
Rebar Size 5
Medium Weight Block
Rebar Spacing 48 In
Equivalent
Depth to Rebar 3.810 In @
Center
Solid Thickness 4.600 in
Loads
Uniform Load
Concentric Axial Load
Wind Load 39.400 psf
Dead Load 600.000 #/ft
Dead Load
0.000 #/ft
Live Load 720.000 #/ft
Live Load
0.000 #/ft
Load Eccentricity 0.000 in
Roof Load
Roof Load
Design Values
E 1,350,000 psi
Rebar Area
0.078 in2
np 0.03641 j 0.92137
n : Es / Em 21.481
Radius of Gyration
2.535 in
k 0.23590 21 kj 9.20187
Wall Weight 49.000 psf
Moment of Inertia
354.810 in4
Max Allow Axial Stress = 0.25 fm (1-(h/140r)^2)' Spinsp
313.28 psi
Allow Masonry Bending Stress = 0.33 fm " Spinsp =
495.00 psi
Allow Steel Bending Stress =
24,000.00 psi
Load Combination & Stress Details Summary
Axial
Bending Stresses
Axial
Moment
Load
steel Masonry
Compression
Top of Wall in-#
Ibs
psi psi psi
DL + LL 0.0
1,320.0
0.0
0.0 23.91
DL + LL + Wind 0.0
600.0
0.0
0.0 10.87
DL + LL + Seismic 0.0
600.0
0.0
0.0 10.87
Between Base & Top of Wall
DL + LL
DL + LL + Wind
DL + LL + Seismic
11 Summary M
0.0 1,614.0 0.0 0.0 29.24
8,510.4 894.0 31,281.7 449.6 16.20
0.0 894.0 0.0 0.0 16.20
12.00ft high wall with 0.00ft parapet, Med Wt Block w/ 8.00in wall w/ #5 bars at 48.00ino.c. at center
Max. Bending Compressive Stress ......... 465.76 OK
Allowable .................... 658.35 OK
Max. Axial Only Compressive Stress ......... 29.24 psi
Allowable .......... 313.28 OK
Max Steel Bending Stress .............. 31,281.68 psi
Allowable .......... 31,920.00 OK
15
Title : Job #
Dsgnr. Date: 9:54PM, 4 MAY 14
Description
Scope:
Rev: SSWOO Page 2
User. KW-0605358, Ver5.8.0,1-oeo.2003 Masonry Wall Design
(c)1983-2003 ENERCALC Engineering Software 9 ELISE_FABLE_ADDITION.EMCK
Description 8" Reinf. C.M.U. Wall Design (Zone-4)
Final Loads & Moments
Wall Weight moment @ Mid Ht 294.00 lbs
Wind Moment @ Mid Ht
8,510.40 in-#
Seismic Moment @ Mid Ht
0.00 in-#
Dead Load Moment @ Top of Wall
0.00 in-#
Dead Load Moment @ Mid Ht
0.00 in-#
Total Dead Lead
600.00 lbs
Total Live Load
720.00 lbs
Live Load Moment @ Top of Wall
0.00 in-#
LiveLoad Moment @ Mid Ht
0.00 in-#
Maximum Allow Moment for Applied Axial Load =
6,529.37 in-#
Maximum Allow Axial Load for Applied Moment =
17,292.92 lbs
16
Title : Job #
Dsgnr: Date: 9:58PM, 4 MAY 14
Description
Scope
Rev:580000 Page 1
User Kw-0605358, vex 5.8.0, 14)ec-2003 Masonry Wall Design
(01983-2003 ENERCALC Engineering Software ELISE�FABLE ADDITION.ECW:CMI
Description 8" Reinf. C.M.U. Wall Design (Zone-5)
General Information Code Ref: ACI 530-02
Wail Height 12.00 It
Seismic Factor
0.0000
fm 1,500.0 psi
Parapet Height 0.00 It
Calc of Em = I'm "
900.00
Fs 24,000.0 psi
Duration Factor
1.330
Special Inspection
Thickness 8.0 in
Wall Wt Mult.
1.000
Grout @ Rebar Only
Rebar Size 5
Medium Weight Block
Rebar Spacing 40 in
Equivalent
Depth to Rebar 3.810 in @
Center
Solid Thickness 4.700 in
Loads
Uniform Load
Concentric Axial Load
Wind Load 45.500 psf
Dead Load 600.000 Nit
Dead Load
0.000 #/ft
Live Load 720.000 #Ift
Live Load
0.000 Nit
Load Eccentricity 0.000 in
Roof Load
Roof Load
Design Values
E 1,350,000 psi
Rebar Area
0.093 IQ
np 0.04370 j 0.91495
n : Es / Em 21.481
Radius of Gyration
2.521 In
k 0.25514 2 / kj 8.56756
Wall Weight 53.000 psf
Moment of inertia
358.350 in4
Max Allow Axial Stress = 0.25 I'm (1 -(h/1 40r)"2) ` Spinsp
312.56 psi
Allow Masonry Bending Stress = 0.33 I'm * Spinsp =
495.00 psi
Allow Steel Bending Stress =
24,000.00 psi
Load Combination & Stress Details Summary
Axial
Bending Stresses
Axial
Moment
Load
steel Masonry Compression
Top of Wall in-#
lbs
psi psi psi
DL + LL 0.0
1,320.0
0.0
0.0 23.40
DL + LL + Wind 0.0
600.0
0.0
0.0 10.64
DL + LL + Seismic 0.0
600.0
0.0
0.0 10.64
Between Base & Top of Wall
DL + LL 0.0 1,638.0 0.0 0.0 29.04
DL + LL + Wind 9,828.0 918.0 30,315.0 483.4 16.28
DL + LL + Seismic 0.0 918.0 0.0 0.0 16.28
12.00ft high wall with 0.00ft parapet, Med Wt Block w/ 8.00in wall w/ #5 bars at 40.00ino.c. at center
Max. Bending Compressive Stress ......... 499.66 OK
Allowable .................... 658.35 OK
Max. Axial Only Compressive Stress ......... 29.04 psi
Allowable .......... 312.56 OK
Max Steel Bending Stress .............. 30,315.01 psi
Allowable .......... 31,920.00 OK
Title : Job #
Dsgnr: Date: 9:58PM, 4 MAY 14
Description
Scope
Rev: 580000
User. KW-0805358, Ver5.8.0, 1-Dec2003 Masonry Wall Design Page 2
(c)1983-2003 ENERCALC Engineering Software ELISE_FABLE—ADDITION.ECW:CMU
Description 8" Reinf. C.M.U. Wall Design (Zone-5)
Final Loads & Moments
Wall Weight moment @ Mid Ht 318.00 Ibs
Wind Moment @ Mid Ht
9,828.00 in-#
Seismic Moment @ Mid Ht
0.00 ink
Dead Load Moment @ Top of Wall
0.00 in-#
Dead Load Moment @ Mid Ht
0.00 in-#
Total Dead Load
600.00 Ibs
Total Live Load
720.00 Ibs
Live Load Moment @ Top of Wail
0.00 in-#
LiveLoad Moment @ Mid Ht
0.00 ink
Maximum Allow Moment for Applied Axial Load =
7,780.70 in-#
Maximum Allow Axial Load for Applied Moment =
17,628.31 Ibs
18
. J08
� GOMEZ-PNIA, PF.
0ON9«iN0 9 OWEER ADDRESS
® FL.. P.E. No 14770 (CIVIL)
PROJECT No SHEET No
OF________
250 CATALONIA AVE. #404
CORAL GABLES, FL. 33134 CALCULATED BY DATE
' TEL (305) 461-2188
FAX. (305) 461-2238 CHECKED BY DATE
_... _'........ _..._. ...... ........ ....__ .............. ._._.. -... _».... » .._ ...--...« __.. __.. ._... ....... ....... - - ._..
: :
i Vc�%•��� o �sy-ems d .�. `Y: 5 T A3 O0
. _....... ._ _....w.__x.._... _....._ .: - _ .... . _._-._...._.....x . _ __._..._ -
: . ... ... ... ...............
....... ... ....... ........
, :
� : i � r : •
!
i i
......_..._�_........» ....»...._..d».......... .»,._.....«.j......_.....:_._«wi»..«............_-...._5.........w. ' .......«...»..._._.._. ...._» .....«..._.._. _ _ ... .... ...i..._......._.l.. ....... i i............... r
3a D
i»
L..x.«...-+---------- _-------;._..:.......... _le
!
i
:
e
FT F
i 4
£
:
i.......,.....<.......,.....:., ......: _.......J.............:.....-.......:.«...........i............. ...... .....- ........... F........ ...... ...... ...........t... .__............. .7.... .......... :.-»... .- ........ ..... .». _. ....._ ._.... .......... -... ,..
i ! i' . t
33 j3o
.»..._.............._....._..t. _........:
t y'
_
( % All
J/ {` i i
.»...» .._... .._.. ....... -__.. .......... .»..... .. ...... ...._ «._...../+1.r«.1x1.••...._..i...«_r».»rL...x..._._x.,..». x..wL. ..«..�_... .». .x.... ...._ .x..... ..M..........._... -»»_ .»..... ..!_......._....tw._..... .. .......
_......._.......... ........ ........
_....._._..«..._._._.,......_..i............ :.._........ _........_ «'.---...... ..a. ........ y�:_
x.._._---...._.i............. ..... _... ..... _.».. _ .__ -•_-_.r..--'--- ...._. _ --_•..........._ _•_•_ w_ _ •_ _ _.._ ._..... _. ._. «_._.
i
` !
....... .....i....«.».»...i«_........,..:»._._......a.,....».__.L.........».._....... ...... :............. a........... _...».w__.:........ .....:...,....... _..._ .__. _..... _ .......... ....................... ........... ._.»........ _. _....« _...».
t
_._, ....... _..,
...«_ ._..- ....... __.
{ ,
.__.._»..a.__.».»..`.__......i_..._._._.i.....w...:.'—w»._a....w__._:..._...__...:.�.....�._...._... £.._._..«__.__»._ :__.»...._.-...._.__ .-.w. _.. ..... -------- ....««..-...__.i_.__._..:_ .._.._ ._....- .__.. _ ..._._ .w __...............
+
• i ! i ! r 2
- , t t i
.................. .. .. __.. .. .. w. : ............ .. _. ! ...
i i i i i i ..,.._ ..p...» ,
t
+ - - i e ..........__.._._i i e
._..._— ...._. .......
; i
3
i
i i
i
+ i
! k ! !
].......... ................. ........ ..... ,...........................»;........ .... ............ i..x...._._..y_..__w.............. .... ............... •i»....»._...x............«........... ........... «._«.»............. ..j---- ------ i_...... ...... ,............... p.---------- . ............ ..._._..r._._._._....
: i ! :
. !
1 i
.w_................. ........
i
+ !
i.......-..-......... ..... .. _« _y... _._..... . _..__{...».w»»: _ _—_ ;_._.._wy.._._.._ _ — — _ — _._ . _ _...... _ _. _ — _...._
,,
:........_...............:....._._..-.£__._......'..........._:._......... '.........._._i .........._.'. ...._. ......n ..... .._... ..........................:.._.-.........:...._..»»»..._...-«:.._..._..r._....._...'..».......»..w......................uw...._.. ....... ...... ........._..._...,.
1 • y a ... ....... ....�,._ ......... ...... 1 F r ...,...
t
+
:.. ........... .......... . Y.... ....... . .._.__....{..».........:l.... ._._...�_..........q - t... ___.._............... .; _.-.... ....__.1..... ......... ........ a. - ..._....-..._._ ....w. _ ... ... ....._..h._._......., ....... ........... � _._.....
:
= •..
— ._._._
....... .«. .. ........ .......
.... �.. « ...i....
_ ........ ... .w_.
.. .............. . ........ w_ ........ ....... ..... ....... ........ _... .._... ........... .»..... .—._. ....... ........ ...._ ...... ...... ._w.
............... ....... ....... ...•••3 ••
j
e
• � i
+ : e :
..... .......».
i
i
19
4
5/4/2014
WIND10 v3-20
Detailed Wind Load Design (Method 2) per ASCE 7-10
Description: Elise Fable Addition Company Name: F.G.P.
Analysis by: O.G.
Calculated Parameters
Type of Structure
Height/Least Horizontal Dim
0.24
Flexible Structure
No
Calculated Parameters
Hurricane Prone Region (V>100 mph)
Table 6-2 Values
Alpha
1 9.500
Z9 =
1 900.000
At =
0.105
Bt =
1.000
Bm =
0.650
Cc =
0.200
I =
500.00
ft
Epsilon =
0.200
min =
15.00
ft
Gust Factor Category 1: Rigid Structures - Simplified Method
Gust1 For rigid structures Nat Freq > 1 Hz) use 0.85 1 0.85
GustfactorCategoryII:` Rigid Structures -. Com fete Analysis
Zm
Zmin
15.00
ft
Izm
Cc * 33/z ^0.167
0.2281
Lzm
1* zm/33 "Epsilon
427.06
ft
Q
1/1+0.63* Min B,L +Ht /Lzm "0.63 ^0.5
0.9143
Gust2
0.925* 1+1.7*Izm*3.4*Q / 1+1.7*3.4*Izm
0.8799
Gust Factor Summary
G
ISince this is not a flexible structure the lessor of Gust1 or Gust2 are used
I0.85
Fin 6-5 Internal Pressure Coefficients for Buildings, Gcol
Condition
Gc i
Max +
Max -
Open Buildings
Partially Enclosed Buildings
Enclosed Buildings
0.00
0.55
0.18
0.00
-0.55
-0.18
Enclosed Buildings
0.18
-0.18
Developed by Meca Enterprises, Inc, Copyright 2010 F.G.P. Page No. 1 of 5
20
5/4/2014
WIND10 v3-20
Detailed Wind Load Design (Method 2) per ASCE 7-10
6.5.12.2.1 Desian Wind Pressure - Buildings of All Heights
Elev
ft
Kz
Kzt
qz
Ib/ftA2
Pressure Ib/ft^2
Windward Wall*
Leeward Wall
Total
Shear
Moment
+GCpi
-GCpi
+GCpi -GCpi
+/-Gcpi
(Kip)
(Kip-ft)
16
0.86
1.00
57.34
28.81
49.18
-34.22 -13.86
63.04
5.29
2.65
15
0.85
1.00
1 56.57
1 28.28
48.65
-34.22 -13.86
1 62.51
r_8_4_._0_6r
675.4311
Note: 1) rositive torces act toward the Tate ana Negative torces act away trom the tace.
Figure 6-6 - External Pressure Coefficients, CR
Loads on Main Wind -Force Resistina Svstems,4M,stthod 2)
L
Variable
Formula
Value
Units,:.-'
Kh
2.01 *(1 5/Z" 2/AI ha
0.85
Kht
Topographic factor(Fig 6-4
1.00
Oh
.00256* V "2*Kh*Kht*Kd
56.57
psf
Khcc
Comp & Clad: Table 6-3 Case 1
0.85
Qhcc
.00256*V"2*Khcc*Kht*Kd
56.57
sf
Wall Pressure Coefficients Cp
Surface C
Windward Wall See Figure 6.5.12.2.1 for PressuresL 1 0.8
Roof Pressure Coefficients, Cp
toof Areas . ft.)-
teduction Factor 1.00
.0alculations for Wind Normal to 84 ft Face
Cp
Pressure (psf)
;ddifional Rwns may be req'd for other wind directions,
+GCpi , ;` .
-GCpi
-eeward Walls (Wind Dir Normal to 84 ft wall)
-0.50
-34.22
-13.86
-eeward Walls (Wind Dir Normal to 54 ft wall)
-0.39
-28.88
-8.52
aide Walls
-0.70
-43.84
-23.46
Roof - Wind Normal to Ridge (Theta>=10) - for Wind Normal to 84 ft face
Vindward - Min Cp
-0.36
-27.69
-7.32
Vindward - Max Cp
0.14
-3.64
16.72
-eeward Normal to Ridge
-0.57
-37.49
-17.12
)verhang Top (Windward)
-0.36
-17.50
-17.5C
)verhang Top (Leeward)
-0.57
-27.31
-27.31
Developed by Meca Enterprises, Inc. Copyright 2010 F.G.P. Page No. 2 of 5
21
5/4/2014
WIND1O v3-20
Detailed Wind Load Design (Method 2) per ASCE 7-10
Overhang Bottom (Applicable on Windward only)
0.80
38.47
38.4
Roof - Wind Parallel to Ride All Theta - for Wind Normal to 54 ft face
Dist from Windward Edge: 0 ft to 26 ft - Max Cp
-0.18
-18.84
1.5
Dist from Windward Edge: 0 ft to 6.5 ft - Min Cp
-0.90
-53.46
-33.0
Dist from Windward Edge: 6.5 ft to 13 ft - Min Cp
-0.90
-53.46
-33.0
Dist from Windward Edge: 13 ft to 26 ft - Min Cp
-0.50
-34.22
-13.8
Dist from Windward Edge: > 26 ft
-0.30
-24.61
-4.2
* Horizontal distance from windward edge
Fiaure 6-10 - External Pressure Coefficients, GCuf
Loads on Main Wind -Force Resisting Systems w/ Ht <= 60 ft
Kh =
2.01 *(15/zg)^(2/Alpha)
= 0.85
Kht =
Topographic factor (Fig 6-2)
= 1.00
Qh =
0.00256*(V)^2*Kh*Kht*Kd
= 56.57
Theta =
Angle of Roof
= 18.4 Deg
Transveme Direction Longitudinal Direction
Torsional Load Cases
Wind Pressures
on
Main Wind Force Resisting
System
Surface
GCpf
+GCpi
-GCpi
qh
s
Min P
s
Max P
s
1
0.52
0.18
-0.18
56.57
19.01
39.38
2
-0.69
0.18
-0.18
56.57
-49.22
-28.85
3
-0.47
0.18
-0.18
56.57
-36.67
-16.31
4
-0.42
0.18
-0.18
56.57
-33.66
-13.30
5
-0.45
0.18
-0.18
56.57
-35.64
-15.27
6
-0.45
0.18
-0.18
56.57
-35.64
-15.27
1 E
0.78
0.18
-0.18
56.57
33.93
54.29
2E
-1.07
0.18
-0.18
56.57
-70.71
-50.35
3E
-0.67
0.18
-0.18
56.57
-48.25
-27.89
4E
-0.62
0.18
-0.18
56.57
-45.12
-24.75
* p = qh * (GCpf - GCpi)
Developed by Meca Enterprises, Inc. Copyright 2010 F.G.P. Page No. 3 of 5
22
5/4/2014
a
WIND10 0-20
Detailed Wind Load Design (Method 2) per ASCE 7-10
Figure 6-11 - External Pressure Coefficients, GCa
Loads on Components and Cladding for Buildings w/ Ht <= 60 ft
it
a�ablcd <ThtRoof 45
a = 5.2 =_> 5.20 ft
r1l;nL nn mnv rhfo onfni lino fn rcnaiva a holn Rrnaan
Component
Width ^
(ft)
Span
(ft)
Area
(ft"2)
Zone
GCp
Nind Press
lb/ft"
Max
Min
Max
Min
A
4.42
5
22.10
4
0.94
-1.04
63.31
-68.97
A
4.42
5
22.10
5
0.94
-1.28
63.31
-82.50
B
4.42
4.17
18.43
4
0.95
-1.05
64.10
-69.76
B
4.42
4.17
18.43
5
0.95
-1.31
64.10
-84.07
C
4.42
3.17
14.01
4
0.97
-1.07
65.29
-70.95
C
4.42
3.17
14.01
5
0.97
-1.35
65.29
-86.45
D
3.08
5.25
16.17
4
0.96 i
-1.06
64.67
-70.32
D
3.08
5.25
16.17
5
0.96
-1.33
64.67
-85.21
E, E1, F
3.08
4.17
12.84
4
0.98
-1.08
65.67
-71.32
E, E1, F
3.08
4.17
12.84
5
0.98
-1.36
65.67
-87.21
G
3.08
3.17
9.76
4
1.00
-1.10
66.75
-72.41
G
3.08
3.17
9.76
5
1.00
-1.40
66.75
-89.38
H
1.58
3.17
5.01
4
1.00
-1.10
66.75
-72.41
H
1.58
3.17
5.01
5
1.00
-1.40
66.75
-89.38
1
1
3.17
3.35
4
1.00
-1.10
66.75
-72.41
1
1
3.17
3.35
5
1.00
-1.40
66.75
-89.38
D-1 & 2
3
6.67
20.01
4
0.95
-1.05
63.74
-69.40
D-1 & 2
3
6.67
20.01
5
0.95
-1.29
63.74
-83.36
D-3
8
7
56.00
5
0.87
-1.14
59.28
-74.43
2 SL
2.17
6.67
14.83
4
0.97
1 -1.07
65.04
-70.70
2 SL
2.17
1 6.67
14.83
5
0.97
I -1.34
65.04
-85.96
0.00
T-1, J-1
2
18
108.00
1
0.30
j -0.80
27.15
-55.44
T-1, J-1
2
18
108.00
2
0.30
-1.20
27.15
-78.07
OR
2
2
4.00
1 H
0.50
-0.90
28.28
-50.91
OH.
2
2
4.00
2H
0.50
-2.20
28.28
-124.45
01-1.
2
2
4.00
3H
1 0.50
1 -3.70
1 28.28
-209.31
Developed by Meca Enterprises, Inc. Copyright 2010 F.G.P. Page No. 4 of 5
23
5/4/2014
WI N D10 v3-20
Detailed Wind Load Design (Method 2) per ASCE 7-10
0.00
Wall
1
12
48.00
4
0.88 -0.98
1
59.95
-65.60
Wail
1
1 12
48.00
5
0.88 -1.16
59.95
-75.77
Note: ' Enter Zone 1 through 5, or 1 H through 3H for overhangs.
Developed by Meca Enterprises, Inc. Copyright 2010 F.G.P. Page No. 5 of 5
24
FORM 405-10
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Addition Legalization and Interior Renovation
Builder Name:
Street: 941 NE 91st Terrace
Permit Office:
City, State, Zip: Miami Shores, Ft,
Permit Number:
Owner: Mrs Elise Fable
Jurisdiction: 232600
Design Location: FL, Miami
1. New construction or existing Existing (Projecte
9. Wall Types (967.5 sqft.)
Insulation Area
2. Single family or multiple family Single-family
a. Concrete Block - Int Insul, Exterior
R=4.1 967.50 ftz
b. NIA
R= ftz
3. Number of units, if multiple family 1
c. NIA
R= ftz
4. Number of Bedrooms 1
d. NIA
R= ftz
10. Ceiling Types (981.0 sqft.)
Insulation Area
5. Is this a worst case? No
a. Under Attic (Vented)
R=30.0 981.00 ftz
6. Conditioned floor area above grade (ftz) 981
b. NIA
R= ftz
Conditioned floor area below grade (ftz) 0
c. NIA
R= ftz
11. Ducts
R ftz
7. Windows(279.3 sqft.) Description Area
a. Sup: Attic, Ret: Space 2, AH: Space 2
6 196.2
a. U-Factor: Sgl, U=0.62 279.35 ftz
SHGC: SHGC=0.50
b. U-Factor: NIA ftz
12. Cooling systems
kBtu/hr Efficiency
SHGC:
a. Central Unit
29.8 SEER:16.00
c. U-Factor: NIA ftz
SHGC:
13. Heating systems
kBtu/hr Efficiency
d. U-Factor: NIA ftz
a. Electric Strip Heat
17.0 COP:1.00
SHGC:
Area Weighted Average Overhang Depth: 1.250 ft.
Area Weighted Average SHGC: 0.500
14. Hot water systems
a. Natural Gas Tankless
Cap: 1 gallons
8. Floor Types (981.0 sqft.) Insulation Area
EF: 0.891
a. Slab -On -Grade Edge Insulation R=0.0 981.00 ftz
b. Conservation features
b. N/A R= ftz
None
c. NIA R= ftz
15. Credits
Pstat
Total Proposed Modified Loads: 27.26
Glass/Floor Area: 0.285
PASS
Total Standard Reference Loads: 34.42
1 hereby certify that the plans and specifications covered by
Review of the plans and
-THE S3r�g?,.
this calculation are in compliance with the Florida Energy
specifications covered by this
ti+0 = g- F0*6
Code.
calculation indicates compliance
with the Florida Energy Code.{rr,
. �-,; •- ,ti
PREPARED BY:
Before construction is completed
DATE:
this building will be inspected for
Section 553.908
c7
compliance with
I hereby certify that this building, as designed, is in compliance
Florida Statutes.
S
cflD
with the Florida Energy Code.
WE
OWNER/AGENT:
BUILDING OFFICIAL:
_
DATE:
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with 403.2.2.1.1.
- Compliance requires completion of a Florida Air Barrier and Insulation Inspection Checklist
- Compliance requires an air distribution system test report, by a Florida Class 1 Rater, confirming system
leakage to outdoors tested at 26 pascals pressure difference in accordance with 403.2.2.1. is not greater than
(29 cfm:Duct#1)
a
•,, 5/1/2014 8:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 1 of 5
PROJECT
Title:
Building Type:
Owner:
# of Units:
Builder Name:
Permit Office:
Jurisdiction:
Family Type:
New/Existing:
Comment:
Addition Legalization and Inter Bedrooms: 1
User Conditioned Area: 981
Mrs Elise Fable Total Stories: 1
1 Worst Case: No
Rotate Angle: 0
Cross Ventilation:
232600 Whole House Fan:
Single-family
Existing (Projected)
Address Type:
Lot #
Block/SubDivision:
PlatBook:
Street:
County:
City, State, Zip:
Street Address
941 NE 91 st Terrace
Dade
Miami Shores,
FI ,
CLIMATE
Design Location
F__�_
IECC Design Temp
TMY Site Zone 97.5 % 2.5 %
Int Design Temp Heating Design Daily Temp
Winter Summer Degree Days Moisture Range
FL, Miami FL_MIAMI_INTL_AP 1 51 90
70
75 149.5
56 Low
BLOCKS
Name
Area Volume
VNumber
Block1
981 8829
SPACES
r
Name
Area Volume Kitchen Occupants
Bedrooms
lnfilID Finished Cooled Heated
1
Space 2
981 8829 Yes 2
1
1 Yes
Yes Yes
FLOORS
#
Floor Type
Space Perimeter R-Value
Area
Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio Space 2 108 ft 0
981 ft2
0 0 1
ROOF
#
Type
Roof Gable Roof
Materials Area Area Color
Solar
Absor.
SA Emitt
Tested
Emitt Deck Pitch
Tested Insul. (deg)
1
Hip
Barrel tile 1097 ft2 0 ft2 White
0.21
No 0.9
No 0 26.6
ATTIC
v #
Type
Ventilation Vent Ratio (1 in)
Area
RBS IRCC
1
Full attic
Vented 150
981 ft2
N N
M,
CEILING
#
Ceiling Type
Space R-Value Area
Framing Frac
Truss Type
1
Under Attic (Vented)
Space 2 30 981 ft2
0.11
Wood
5/1/2014 8:52 AM EnergyGaugeO USA - FlaRes2010 Section 405.4.1 Compliant Software Page 2 of 5
'V
F
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
#-_Ornt__To--�IVaU�ype Spate R�Wue Ft In F"n Area __-R alue-Eraction---Absor. Grade%-
1 N Exterior Concrete Block - Int Insul Space 2 4.1 35 0 9 0 315 ft' 0 0 0.47 0
2 E Exterior Concrete Block - Int Insul Space 2 4.1 32 0 9 0 288 ft2 0 0 0.47 0
3 W Exterior Concrete Block - Int Insul Space 2 4.1 40.5 0 9 0 364.5 ft2 0 0 0.47 0
WINDOWS
Orientation shown is the entered, Proposed orientation.
Wall
V # Omt ID Frame Panes
Overhang
NFRC U-Factor SHGC Area Depth Separation
Int Shade
Screening
1 N 1 Metal Single (Clear)
2 E 2 Metal Single (Clear)
3 E 2 Metal Single (Clear)
4 W 3 Metal Single (Clear)
5 W 3 Metal Single (Clear)
Yes 0.62 0.5 66.69999 1.25 ft 0 i 1.25 ft 0 i
Yes 0.62 0.5 24 ft2 1.25 ft 0 i 1.25 ft 0 i
Yes 0.62 0.5 66.69999 1.25 ft 0 i 1.25 ft 0 i
Yes 0.62 0.5 55.25 ft2 1.25 ft 0 i 1.25 ft 0 i
Yes 0.62 0.5 66.69999 1.25 ft 0 i 1.25 ft 0 i
Drapes/blinds
Drapes/blinds
Drapes/blinds
Drapes/blinds
Drapes/blinds
None
None
None
None
None
INFILTRATION
# Scope Method
SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Best Guess 0.000300 771.95 42.379 79.700 0.2070 5.2460
HEATING SYSTEM
# System Type
Subtype Efficiency Capacity
Block
Ducts
1 Electric Strip Heat
None COP: 1 17 kBtu/hr
1
sys#1
COOLING SYSTEM
# System Type
Subtype Efficiency Capacity Air Flow
SHR Block
Ducts
1 Central Unit
Split SEER: 16 29.8 kBtu/hr 894 cfm
0.72 1
sys#1
HOT WATER SYSTEM
# System Type SubTpe
Location EF Cap Use SetPnt
Conservation
1 Natural Gas Tankless
Space 2 0.82 1 gal 40 gal 120 deg
None
ry
SOLAR HOT WATER SYSTEM
FSEC
Cert # Company Name
Collector
System Model # Collector Model # Area
Storage
Volume FEF
None None
ft2
5/1/2014 8:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 3 of 5
DUCTS
---- Supply ----
---- Return ----
Air
Percent
HVAC #
# Location R-Value Area
Location
Area
Leakage
Type
Handler
CFM 25
Leakage QN
RLF
Heat Cool
1
FCooling
Attic
6 196.2 ft
Space 2
0 ft2
Prop. Leak Free
Space 2
29.4 cfm
3.29
% 0.03
0.00
1 1
TEMPERATURES
amable Thermostat: Y
Ceiling Fans:
Jan
Jan
Feb
Feb
Mar
Mar
A r
Apr
Ma
May
X Jun
l
X Jul
Jul
X Au
X Se
Sep
Oct
Nov
X�
Dec
enng Jan
Feb
X Mar
L Jun
Aug
Oct
Nov
Dec
Thermostat Schedule:
HERS 2006 Reference
Hours
Schedule Type
1
2
3
4
5
6
7
8
9
10
11
12
Cooling (WD)
AM
78
78
78
78
78
78
78
78
80
80
80
80
PM
80
80
78
78
78
78
78
78
78
78
78
78
Cooling (WEH)
AM
78
78
78
78
78
78
78
78
78
78
78
78
PM
78
78
78
78
78
78
78
78
78
78
78
78
Heating (WD)
AM
66
66
66
66
66
68
68
68
68
68
68
68
PM
68
68
68
68
68
68
68
68
68
68
66
66
Heating (WEH)
AM
66
66
66
66
66
68
68
68
68
68
68
68
PM
68
68
68
68
68
68
68
68
68
68
66
66
5/1/2014 8:52 AM EnergyGaugeO USA - FlaRes2010 Section 405.4.1 Compliant Spftware Page 4 of 5
10
FORM 405-10
Florida Code Compliance Checklist
Florida Department of Business and Professional Regulations
Residential Whole Building Performance Method
ADDRESS: 941 NE 91st Terrace PERMIT #:
Miami Shores, FI,
MANDATORY REQUIREMENTS SUMMARY - See individual code sections for full details.
COMPONENT
SECTION SUMMARY OF REQUIREMENT(S)
CHECK
Air leakage
402.4
To be caulked, gasketed, weatherstripped or otherwise sealed.
Recessed lighting IC -rated as meeting ASTM E 283. Windows and
doors = 0.30 cfm/sq.ft. Testing or visual inspection required.
Fireplaces: gasketed doors & outdoor combustion air. Must complete
t
envelope leakage report or visually verify Table 402.4.2.
i
Thermostat &
403.1
At least one thermostat shall be provided for each separate heating
controls
and cooling system. Where forced -air furnace is primary system,
programmable thermostat is required. Heat pumps with supplemental
electric heat must prevent supplemental heat when compressor can
meet the load.
Ducts
403.2.2
All ducts, air handlers, filter boxes and building cavities which form the
primary air containment passageways for air distribution systems shall
be considered ducts or plenum chambers, shall be constructed and
sealed in accordance with Section 503.2.7.2 of this code.
403.3.3
Building framing cavities shall not be used as supply ducts.
Water heaters
403.4
Heat trap required for vertical pipe risers. Comply with efficiencies in
Table 403.4.3.2. Provide switch or clearly marked circuit breaker
(electric) or shutoff (gas). Circulating system pipes insulated to =
R-2 + accessible manual OFF switch.
Mechanical
403.5
Homes designed to operate at positive pressure or with mechanical
ventilation
4 ventilation systems shall not exceed the minimum ASHRAE 62 level.
No make-up air from attics, crawispaces, garages or outdoors adjacent
to pools or spas.
i
Swimming Pools
403.9 Pool pumps and pool pump motors with a total horsepower (HP) of = 1
& Spas
HP shall have the capability of operating at two or more speeds. Spas
and heated pools must have vapor -retardant covers or a liquid cover or
other means proven to reduce heat loss except if 70% of heat from
site -recovered energy. Off/timer switch required. Gas heaters minimum
thermal efficiency=78% (82% after 4/16/13). Heat pump pool heaters
minimum COP= 4.0.
Cooling/heating
403.6
Sizing calculation performed & attached. Minimum efficiencies per
Tables 503.2.3. Equipment efficiency verification required. Special
equipment
occasion cooling or heating capacity requires separate system or
variable capacity system. Electric heat >10kW must be divided into two
or more stages.
Ceilings/knee walls
405.2.1 R-19 space permitting.
5/1/2014 8:52 AM EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software Page 5 of 5
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 79
The lower the EnergyPerformance Index, the more efficient the home.
941 NE 91 st Terrace, Miami Shores, FI,
1. New construction or existing
Existing (Projecte
9. Wall Types
Insulation
Area
a. Concrete Block - Int Insul, Exterior
R=4.1
967.50 ft2
2. Single family or multiple family
Single-family
b. NIA
R=
ft
3. Number of units, if multiple family
1
c. NIA
R=
ft2
4. Number of Bedrooms
1
d. NIA
R=
ft2
10. Ceiling Types
Insulation
Area
5. Is this a worst case?
No
a. Under Attic (Vented)
R=30.0
981.00 ft2
6. Conditioned floor area (ft2)
981
b. N/A
R=
ft2
c. NIA
R=
ft 2
7. Windows" Description
Area
11. Ducts
R ft2
a. U-Factor: Sgl, U=0.62
279.35 ft2
a. Sup: Attic, Ret: Space 2, AH: Space 2
6 196.2
SHGC: SHGC=0.50
b. U-Factor: NIA
ft2
SHGC:
12. Cooling systems
kBtu/hr
Efficiency
c. U-Factor: NIA
ft2
a. Central Unit
29.8 SEER:16.00
SHGC:
d. U-Factor: NIA
ft2
13. Heating systems
kBtu/hr
Efficiency
SHGC:
a. Electric Strip Heat
17.0
COP:1.00
Area Weighted Average Overhang Depth:
1.250 ft.
Area Weighted Average SHGC:
0.500
8. Floor Types
Insulation
Area
14. Hot water systems
Ca
1 gallons
p'
a. Slab -On -Grade Edge Insulation
R=0.0
981.00 ft2
a. Natural Gas
EF: 0.82
b. N/A
R=
ft2
b. Conservation features
c. N/A
R=
ft2
None
15. Credits
Pstat
I certify that this home has complied with the Florida Energy Efficiency Code for Building
Construction through the above energy saving features which will be installed (or exceeded)
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature:
Address of New Home:
Date:
City/FL Zip:
,�•oITxE S7-CO
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's
support staff.
**Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at (321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's
support staff.
**Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
EnergyGauge® USA - FlaRes2010 Section 405.4.1 Compliant Software
si
RAFAEL E. DROZ SEDA P. E.
STRUCTURAL AND THRESHOLD INSPECTIONS
LICENCES 39228 & SPECIAL INSPECTOR # 843
9130 CRESCENT DRIVE
MIRAMAR FL. 33025 - 2426
March 11, 2015
To whom it's May Concern
Miami Florida
Dear Sirs
AS BUILT INSPECTION
941 N.E.91 Terrace
Miami Shore Village,
Florida
Permit RC-7-14-1531
This report was issued in response to a request from
Building Contractor to perform a Building Inspection at the above address of the
House Repaired work.
A visual inspection was performed of all structural components that were repaired
and in accordance with the approved structural Plans
To performed the structural inspection a NDT James Instrument Inc. Rebar
Locator C700, and James Rebar Data Scan C -4974.
1. Foundations The Contractor excavated next to the footing to determine size
4'-0" x 4'-0" x12" 5# 5 each way T. & B. and also 2 # 5 continuous bar.
2. The 4" Slab in thickness with 6x6-10/10wire mesh.
3. The Columns 8" x 12" with 4 #6 bars and #3 ties, 8" X 24" with 6 # 6 with
# 3 ties reinforcing steel .
4. Roof framing were detected by ceilings openings 2" x12" wood joists @ 12"
on center and prefab wood trusses @ 24" and fastened with NVSTA- 22
straps also R-30 insulation.
5. The Tie downs were placed with # 5 @ 40" on center.
6. The 5/8" plywood was fastened with 8d nails @ 4"o/c at edge and 6" at
field.
7. New windows were installed and fastened'/a" tap cons embedded 11 /4" on
the wall and wood buck around the perimeter.
I certify to the best of my knowledge and belief after the inspections that the all
work was done in accordance with the 2010Florida Building Specifications, and is
structurally sound and safe for the specific usage.
The Inspectors certify that there are no financial or business interests on the above
property nor has ever been a contractor employee.
If additional information is required please contact me at (305) 962-7452.
Sincerely,
RAFAEL E. DROZ
HVAC Load Calculations
for
Mrs Elise• Fable
941 NE 91 st Terrace
Miami Shores, Florida
RH'%,IAC RzsiDHNwnAL
HVAC LOADS
Prepared By:
Thursday, May 01, 2014
r Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhirac �'i��id�ntial,>�#»i htCoMmetCta�„HVAC Loatls ;'' � , '� � Mite Softwawe De�elopment,anc.:
i t 2 f., 4( tlk� ti;i ii }f it jF f -Er
System 2 AC-2 Summary Loads
J
t. �l . 1:[i li lii i ::E' i i' ;!. t :1: r y}• } r if EI €'i E
Com a i yen i;]i .'.Yt t i E
{
1
f i i. i.
E E - "
Total
.' :l i:: ✓LIt�I •! .i 3 f L
S 1
} Descmpt�+on r <' ,: _Quart,
Loss Gain ° tinG•ain ,
_�'
Clear: Glazing -Storm Window 2, ground reflectance =
281.8
4,019
0 14,608 14,608
0.23, u-value 0.62, SHGC 0.5
13A-4ocs: Wall -Block, board insulation only, R-4 board
685.8
2,255
0 2,187 2,187
insulation, open core, siding finish
16A-30: Roof/Ceiling-Under Attic with Insulation on Attic
981
722
0 2,417 2,417
a Floor (also use for Knee Walls and Partition
Ceilings), Unvented Attic, No Radiant Barrier, Any
Roofing Material, Any Roof Color, R-30 insulation
22A-pl: Floor -Slab on grade, No edge insulation, no
108
2,457
0 0 0
insulation below floor, any floor cover, passive, light
dry soil
Subtotals for structure:
9,453
0
19,212
19,212
People:
`
2
400
460
860
T
Equipment:
0
200
200
Lighting:
200
682
682
Ductwork:
3,952
694
2,029
2,723
Infiltration: Winter CFM: 90, Summer CFM: 47
2,270
1,947
932
2,879
Ventilation: Winter CFM: 0, Summer CFM: 0
0
0
0
_0
System 1 AC-1 Load Totals:
15,675
3,041
23,515
26,556
;,.;: ,:... s3
`7, bia,CkMl;i1
i 1 s
Supply CFM: 1,069 CFM Per Square ft.: 1.090
Square ft. of Room Area: 981 Square ft. Per Ton: 443
Volume (f?) of Cond. Space: 8,829
v' �.. ✓� ....., F..� .. t,t i X,...g:rt'•...:...) •, ;': E:f;. .,ES. "X.* f i .t "�:-E' E .t.. ti: 1:: f:l
e i t
' y , ,z.zo; sAq •r E tt z t sl t!i }...,. -. i :f} EFit.fEE •t, 1,t:s fp .f i,, i i z„i . tr , € : ,t.. !. t
:t�QCt1EEL..r�sf! s jj u z
i �•'Sa<tt.. E,.t1: J, �5�,¢E,
Total Heating Required Including Ventilation Air: 15,675 Btuh 15.675 MBH
Total Sensible Gain: 23,515 Btuh 89 %
Total Latent Gain: 3,041 Btuh 11 %
Total Cooling Required Including Ventilation Air: 26,556 Btuh 2.21 Tons (Based On Sensible +
Latent)
►, S���f� ;it . ..�?�ia�}..��?r•-:� Utz ...a. << ..,117ryi� .z_ ....,f_ -. lt�t?,.y,,. < , . iNf3.a , 1., .. _ _.. .. ..L:z; �.:}; a.._ , i.iit.t ,ir , .. �.:� ` _.: f i
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data
at your design conditions.
C:1Program FileslElitelRhvacwlProjectslELISE FABLE RESIDENCE.rhv Thursday, May 01, 2014, 8:56 AM
JW L11111K;;U
1C11111LG VV 111 MIL 1
W01K
VI Mi
954 971-7201
( )
561 734-6373 • FAX 951 971-
( ) ( )
2 2
7 0
DATEI/8/2015
Mrs. Fable
SELLER/PROPERTY OWNER/AJTFIORIZEC AGENT
941 NE 91St Terrace, Miami Shores, FL
STREET ADDRESS OF PROPERTY
305-972-6413
PHONE NUMBER / EMAIL / FAX
BUYERS NAME
STREET ADDRESS
PHONE NUMBER/ EMAIL/ FAX
The COMPANYis authorized to treat premises herein described for the control of:
DRYWOOD TERMITES
POWDER POST BEETLES
Treatment is based on our inspection which reveals:
a () LIVE INFESTATION
(X) CONTROL OF EXISTING INFESTATION
(X) PREVENTION OF INFESTATION
(X) SUBTERRANEAN TERMITES *See Note Below
( ) FORMOSAN TERMITES "See Note Below
* Note: Structure must be free and clear, and stay free and
clear of any and all water intrusion, Such as (but not limited to):
Hoof Leaks, Foundation Leaks, Plumbing Leaks, Siding Leaks,
F_tc. Customer must make any such repairs immediately.
A) TYPE OF TREATMENT TO BE DONE:
( ) Pre -treat (X ) Sub -slab injection ( ) Liquid/Foam Treatment () Spot Treatment () Fumigation
B) STRUCTURE TYPE: CBS C) CHEMICAL. TO BE USED: Termidor
C) AREA TO BE TREATED: Entire perimeter
D) SPECIFIC STRUCTURES ON PROPERTY TO BE INCLUDED IN THIS WARRANTY: House
E) RE -INSPECTIONS ARE INCLUDED FREE OF CHARGE AT CUSTOMER REQUEST WHILE HOME IS UNDER CURRENT
WARRANTY
F) NOTICE OF TREATMENT STICKER WILL BE PLACED AT ONE OF THE FOLLOWING AREAS: ATTIC ENTRY, CRAWL SPACE,
WATER HEATER, ELECTRIC PANEL, A/C UNIT, OR ANY OTHER READILY AVAILABLE AREA OF PROPERTY.
A) Cost of Treatment
B) Cost of Sub Slab
C) Wood Repair
1) Sub total
2) Sales Tax
3) Discount
4) Balance Due
Acceptance is regvired within 30 days of proposal dF-te. Cancellation of job must be received by 9:00 am of the day
prior to scheduled date of job. Fee for cancellation without required notice is 25% of the service agreement price.
Payment in full is due at the time of service.
Type of Warranty:
( X) Limited Warranty
( ) Non -Renewable Limited Wa: ranty (F(-: r Spot Treatments)
REFER TO REVERSE SIDE FOR LIMITED WARRANTY, DISCLAIMERS, LIMITATIONS, CONDITIONS OR
EXCLUSIONS TO REPAIR AND/OR RE TREATMENT. LIMITED WARRANTY IS FOR RE -TREATMENT ONLY.
THIS LIMITED WARRANTY ON THE ABOVE NAMED PROPERTY WILL BE RENEWED IN an 2016 UPON
PAYMENT OF THE INITIAL rREATMENT COST, .AND ANNUALLY THEREAFTER IN Jan, UPON PAYMENT OF
S188.00 BEGINNING IN 2016 . THE LIMITED WARRANTY WILL BE 1N EFFECT FOR AN INITIAL PERIOD OF 12
MONTHS AND THEREAFTER SO LONG AS PAYMENTS ARE MADE IN ACCORDANCEWITH THE TERMS AND
CONDITIONS OF THE CONTRACT.
Wi i Alaulirli (SiIZ1rorrrre all fr1e)
COMPANY REPRESENTAj iVE
SELLERIPROPERTY OWNER/AUTHORIZED AGENT
2195 N. ANDREWS AVE., SUITE #11 POMPANO, FLORIDA 33069
(as required by Florida Building Code (FBC) 104.2.6)
Command Pest Control, Inc.
954-943-0008 561-734-6373
Address of Treatment
941 NE 91 Terrace, Miami Shores FI
Date Time
1-12-2015 2pm
Product Used Chemical
(active ingredient)
Termidor Fipronil
Applicator
Steven Little
Number of Gallons
108
Percent of Area Treated (sq Ft)Linear Feet Treated
Concentration
.06% 270 Linear Feet
Stage of Treatment (Horizontal, Vertical, Adjoining Slab, Re -treat of disturbed area
As per 104.2.6- If soil chemical barrier method for termite prevention is used, final exterior treatment shall
be completed prior to final building approval.
If this notice is for the final exterior treatment (final grade), Initial and Date this line: S L 1- I Z-2 i715
BUILDING HAS RECEIVED A COMPLETE TREATMENT IN THE SPECIFIED AREA FOR THE PREVENTION OF
SUBTERANEAN TERMITES, TREATMENT IS IN ACCORDANCE WITH THE RULES ESTABLISHED BY THE
DEPARTMENT OF AGRICULTURE AND CONSUMER AFFAIRS.
Payment for the initial treatment includes a one year limited warranty as specified herein. Normal renewal anniversary date shall be considered to be
tite la.4t day of the calendar month proceeding flee i+ctuad treatment date. At your option and for your further protection, the limited warranty may be
renewed annually for lour additional years after the first year. After receipt of payment for each annual limited warranty renewal, the COMPANY
will make an inspection of the premises, within a reasonable time period following request. After four limited warranty renewal years, the FEE and
the renewal period may be adjusted by the COMPANY.
The LIMITED WARRANTY is personal to the property and as such is transferred from owner to owner during the course ofthis agreement, and
by advising the COMB' \NY in writing of the narne and billing address of the new owner.
GENERAL TERMS AND CONDITIONS
I. If during the L1Ml i' U WARRANTY pe; iod. additions and/or alterations at-,: made which affect the treated structure(s) by creating new insect
hazards or interference with the chemical barriar. the COMPANY may terminate the LIMITED WARRANTY unless the COMPANY receives
prior written notification. reinspects the structure(s). contracts for additional treatment and/or adjusts the LIMITED WARRANTY renewal fee.
2. The COMPANY'S liability under this L mi,rED WARRANTY shall terminate when access to the premises for the purpose of carrying out
the terms and conditions of this contract is ref:ised the COMPANY or its agent.
3. The CO MPAN Y" will exercise reasonable care in its treatment procedures, but will not accept responsibility for broken roof tiles. gutters, solar
- heaters, satellite dishes, landscape foliage, broken or damaged pipes or any other inadvertent damage occasioned by properly performed
procedures.
.4. Certain conditions heyond the t_'()N1PAN*%"S control may allcet its ability to commence or to complete treatment. Such conditions include but
are not limited to strong or heavy ,%inds..e:nlper.w!re b6ow 60 degrees f.. acts cif war. acts of government authorities. civil disturbances or
refusal by the occupant to allow the COMPANY access to all or any part of the structure(s). No liability shall accrue to the COMPANY if. at its
discretion in any of these conditions, it becomes necessary for ill- COMPANY to postpone treatment.
5. This contract may he assigned to a � HOI,VSALF FUMIGATiON COMPANY. If so assigned, then from the date of assignment and
throughout the one (1) year period following file (late of initial treatment as stated on the LiMITED WARRANTY to be issued to you, the
WHOLESALE COMPANY shall held itself primarily liable to you and the Florida State Department of Agriculture for a full performance of all
fumigation work performed in the above premises, and the WHOLESALE COMPANY shall hold itself primarily liable for the full performance
ofall the terms and conditions of this fumigation contract for the treatment of the above premises as same may be required by Chapter 482 of
the Florida Statutes.
6. In the event it becomes necessary to retain 1-!gal counsel or collection agents. in order to collect payment as agreed in the contract, the
COMPANY shall be entitled to reasonable attorneys or collection agencies fees and costs of collection through final appeal.
7. This contract, the attached Graph &Specifications and the Release of Company Liability comprise the entire agreement between the parties
hereto. and the C'O,X1fANY and the CLIENT:,re hound by the stipulation of these terms and conditions and not by any other representations,
oral or otherwise. unless such are: in w•riti112 and signed by an ofTicer of the COMPANY.
8. If moisture and/orstructural conditions. which are (conductive to Subterranran'lermites, are subsequently found to exist without ground
contact, then the Comptuty shall b; relieved r,t'amv and all liability.
9. Structural or mechanical defects, which result in water leakage in interior areas or through the roof or exterior walls of the premises, may
destroy the eftcctiveness of the C0;\-1I -,\NY'ti ircrtrrtent. thereby permitting infestation to continue after file date of the initial treatment. It'such
a condition is din:xovere,,.L it is agreed that the; customer will be responsible for making such repairs as necessary to correct the structural or
mechanical detect and the COMPANY will, upon completion of said repairs, provide additional treatment to control the infestation in the area.
10. Ifthis contract covers treatrnen; for the prevention of'Subterranean termites for new construction, then should Subterranean termite infestation
occur to the su•ucture treated durina warranty period, additional treatment will bQ performed to control the infestation.
If. The company will not accept liability fist any they or vandalism during. a tent fumigation. If you are concerned we recommend that you
obtain the service% of a security guard company.
CONSUNIER'S RIGHT Or. CANCELLATIONS
You may cancel this contract w ithcut tm per,a;!y or oE►. ation prior to midnight of the third business day following acceptance of this service
agreement. Il' you dance; this contract for t;ta r;,tson, the seller, Command Pest Control, inc., may keep only a portion of the contract price, not to
exceed 50or W.00 whichever is i:sser.
You may cancel this, contract it' the �ervicc ccttsc; to be offered as stated in the contract. You may notify the Seller of your intent to cancel by
written notice to Coma;and 1',at Control. Inc.
PAVNIENT TER.NIS
Payment shall be rendered ;it time ot'sorvice. 'Nov account which fins an unpaid balance; at the end of said term will be charged interest on the
unpaid portion. the rate of one and one hall' perccnt (1 1 /2%) interest per month until such time as the account has been paid in full.
Notwithstanding that the serviced property i,, the subject of a real estate transfer. refinance etc., payment for services rendered shall be made
within the stated time. and if not, the ('0\, ANY shall hold CLIENT fully responsible for all payments due hereunder to include total amount of
invoice and any and all Reasonable .'lttornev !-es and Court costs that may arise if collection becomes necessary.
_ US South
Engineering & Testing Laboratory, Inc.
14345 Commerce VA/ay, Miami. FL 33016
Phone: 305.568.2888 1 Fax: 306.362.4669
Tested by: Larry
DATE: 11.07.2014
Project: #14-9074
REPORT OF FIELD DENSITY TEST (SOIL COMPACTION)
CLIENT: SRncoast Building & Roofing PROJECT: Residential Home Addition
1040 SW 1st Street #1205 941 NE 91st Terrace
Miami, FL 33130 Miami Shores, FL
PROCTOR DATA
PROCTOR
NUMBER
SOIL DESCRIPTION
PROCTOR VALUE
Max. Dry Density (pct)
Optimum Moisture (%)
- 14681
LIME SAND WITH SOME ROCK
114.6
10.4
FIELD DENSITY TEST ACCORDING TO ASTM METHOD D-2922-71
TEST No.
TEST LOCATION
PROC. No.
LIFT
DRY
DENSITY
M%
°
COMP.
RESULT
1
CENTER OF R. HOME ROOM ADDITION
14681
FINAL
113.5
10.0
99.0
PASS
TEST DEPTH (IN)
12"
REQUIRED PERCENTAGE OF COMPACTION
95%
P= PASS F=FAIL FT=FOOTING SG=SUB-GRADE BC=BASE COURSE MH=MAN HOLE
Respectfully suS;,;ned, _
�5 —
:.hasem Khavanin.,
Florida RegistratioO=#, 41955
COUNTY
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
BUILDING AND NEIGHBORHOOD COMPLIANCE DEPARTMENT (BNC) 11805 SW 26 Sbw% Room 208
BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474
T (786) 315.2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.mlamidfide,uoy/buildl"g/
Entegra Roof Tile, Inc.
1289 NE 9'" Ave.
Okeechobee, FL. 34972
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials.
The documentation submitted has been reviewed and accepted by Miami -Dade County BNC - Product Control
Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction
(AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control
Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right
to have this product or material tested for quality assurance purposes. If this product or material fails to
perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may
immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. BNC
reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control
Section that this product or material fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Bermuda Concrete Flat Roof Tile
LABELING: Each unit shall beat a permanent label with the manufacturer's name or logo, city, state and
following statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no
change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any
product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply
with any section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by
the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall
be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors
and shall be available for inspection at the job site at the request of the Building Official.
This renews NOA # 10-0518.01 and consists of pages I through 6.
The submitted documentation was reviewed by Alex Tigera.
NOA No.11-0414.09
Expiration Date: 06/07/16
Approval Date: 05/26/11
Page 1 of 6
RooFiNG ASSEMBLY APPRovAL
Category: Roofing -
Sub Category: Roofing Tiles
Material: Concrete
1. SCOPE
This revises a roofing system using Entegra Flat Concrete Roof Tile, as manufactured Entegra
Roof Tile Corporation in Okeechobee, FL. as described in Section 2 of this Notice of Acceptance,
designed to comply with the Florida Building Code for High Velocity Hurricane Zone. For the
locations where the pressure requirements, as determined by applicable Building Code, does not
exceed the design pressure values obtain by calculations in compliance with RAS 127 using the
values listed in section 4 herein. The attachment calculations shall be done as a moment based
system.
2. PRODUCT DEsCI wnoN
Manufactured by
Test
Product
- A nlicant
Dime�asionnj amiB�cations
Descries
Entegra Flat Tile
1=16" TAS 112
Flat profile, interlocking, high pressure
a
w =10"
extruded concrete roof file equipped with
two nail holes. For mechanical, mortar or
adhesive set applications.
Trim Pieces
1= varies - TAS 112
Accessory trim, concrete roof pieces for use
w = varies
at hips, rakes, ridges and valley
varying thickness
terminations. Manufactured for each file
profile.
2.1 AZANUFACTURING LOCATION
2.1.1. Okeechobee, FL.
2.2 EVIDENCE Suslhwrw
Teat ,A►gw-gy
- .�
Test Iden�tfiter
�.,,_._..._
lest N, �eJRe= MEL
Redland Technologies
7161-03
Static Uplift Testing Dec. 1991
Appendix III
PA IO2 & PA 102(A)
The Center for Applied
94-084
Static Uplift Testing May 1994
- Engineering, Inc.
PA 101 (Mortar Set)
The Center for Applied
94-060A
Static Uplift Testing March,1994
Engineering, Inc.
PA 101(Adhesive Set)
The Center for Applied
25-7094-2
Static Uplift Testing Oct. 1 "4
Engineering, Inc.
PA 102
(4" Headlap, Nails, Direct Deck, New
Construction)
NOA No.11-0414.09
Fxpirntfon Date: 06/07/16
Approval Date: 05 26/11
Page 2 of 6
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
The Center for Applied
Engineering, Inc.
Redland Technologies
Redland Technologies
Redland Technologies
Redland Technologies
The Center for Applied
Engineering, Inc.
Atlanta Testing &
Engineering, lnc.
Professional Service
Industries, Inc.
Celotex Corporation
Testing Service
Celotex Corporation
Testing Service .
Walker Engineering, Inc.
Walker Engineering, inc.
Walker Engineering, Inc.
Walker Engineering, Inc.
Walker Engineering, Inc.
Walker Engineering, Inc.
Walker Engineering, Inc.
Nutting Engineers
25-7094-8
25-7094-5
25-7183-6
25-7183-5
25-7214-1
25-7214-5
7161-03
Appendix 11
Letter Dated Aug. 1,
1994
P0631-01
P0402
Project No. 307025
Test #MDC-77
R1.894
R2.894
R3.894
395-40011-1
520109-1
520111-4
520191-1
Calculations
Evaluation Calculations
Evaluation Calculations
Evaluation Calculations
Evaluation Calculations
Evaluation Calculations
Calculations
13343.1
Static Uplift Testing
PA 102
(4" Headlap, Nails, Battens)
Static Uplift Testing
PA 102
(4" Headlap, Nails, Direct Deck,
Recover/Reroof)
Static Uplift Testing
PA 102
(2 Quik Drive Screws, Direct Deck)
Static Uplift Testing
PA 102
(2 Quik Drive Screws, Battens)
Static Uplift Testing
PA 102
(1 Quik-Drive Screw, Direct Deck)
Static Uplift Testing
PA 102
(1 Quik Drive Screw, Battens)
Wind Tunnel Testing
PA 108 (Nail -On)
Wind Tunnel Testing
PA 108 (Nail -On)
Wind Tunnel Testing
PA 109 (Mortar Set)
Withdrawal Resistance Testing of
screw vs. smooth shank nails
Wind Driven Rain
PA 100
Physical Properties
PA 112
Physical Properties
PA 112
Static Uplift Testing
PA 101
Static Uplift Testing
PA 101
Aerodynamic Multiplier
25-7094
25-7496
25-7584
25-7804b-8
25-7804-4 & 5
25-7848-6
25-7183
Restoring Moment, Ma
Two Patty Adhesive Set System
TAS 112
Oct. 1994
Oct. 1994
Feb. 1995
Feb. 1995
March,1995
March, 1995
Dec. 1991
Aug. 1994
July 1994
Sept.1993
Oct. 1994
Aug. 1994
Feb 2004
Dec.1998
March 1999
March 2004
Feb 1996
April 1996
December
1996
March 1995
March 2004
April 1999
05/06/08
NOA No.11-0414.09
Expiration Date: 06/07/16
Approval Date: 0146/11
Page 3 of 6
3. LnvnTATIONS:
3.1 Fire classification is not part of this acceptance.
3.2 For mortar or adhesive set tile applications, a static field uplift test in accordance with TAS
106 may required, refer to applicable building code.
3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform
quarterly test in accordance with TAS 112, appendix `A'. Such testing shall be submitted to
the Building and Neighborhood Compliance Department — Product Control Section for review.
3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications
Standards listed section 4.1 herein.
3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope
unless stated otherwise by the underlayment material manufacturers published literature.
3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in
compliance with applicable building code.
4. INSTALLATION
4.1 Entegra `Flat' Concrete Roof Tile and its components shall be installed in strict compliance
with Miami Dade County Roofing Application Standard RAS 119, RAS 119, and RAS 120.
4.2 Data For Attachment Calculations.
Table 1: Average Weight (W) and Dimensions (I x w )
Tile Profile
Weight-W (lbf)
Length -I (ft)
Width-w (ft)
Ente ra Fiat Tile
9.7
1.33
.833
Table 2: Aerodynamic AAuiti tiers -
Tile
Profile
x ( )
Batten Application
x ( )
Direct Deck Application
,Entegra Flat Tile
0.189
.0.205
Table 3:
ring Moments
due to Gran
- lbl ft4
Tile
Profile
311:12"
4":12"
681Ar
611:12"
Greater than
7"Si r
Entegra Fiat
Tile
Battens
Direct
Deck
Battens
Direct
Deck
Battens
Direct
Deck
Battens
I
Direct
Deck
1
Battens
I
Direct
Deck
[-6.53
6.97
6.43
6.86
6.29
6.71
1 6.14
6.54
1 5.97
6.35
NOA No.11-0414.09
Expiration Date: 06WI16
Approval Date: O 26/11
Page 4 of 6
Table 4: Attachment Resistance Expressed as a Moment - Mt (ft4bf)
for NalWn 3vatems
Tile
Profile
Fastener Type
Direct Deck
(min 15132" plywood)
Direct Deck
(min.1913211 plywood)
Battens
Entegra
Flat -tile
•
2-10d Ring Shank Nails
30.9
38.1
17.2
1-10d Smooth or Scow
Shank Nail
7.3
9.8
4.9
2-10d Smooth or Screw
Shank Nails
14.0
18.8
7.4'
1 #8 Screw
30.8
30.8
18.2
2 #8 Screw
51.7
61.7
24.4
1-10d Smooth or Screw
Shank Nail (Field -Clip)
24.3
24.3
24.2
1-14d Smooth or Screw
Shank Nail Eave Clip)
19.0
19.0
22.1
2-10d Smooth or Screw
Shank Nabs Field Clip)
36.6
36.6
34.8
2-10d Smooth or Screw
Shank Nails Eave CUP)
31.9
31.9
32.2
�2-40-dftgShank Nails 50.3 65.6 48.3
1 Installation with a 4" Ile headlep and fasteners are located a min. of 2W from head of tile.
Table 6: Attachment Resistance Expressed as a Moment Mr (ft4bf)
for Two Patty Adhesive Set we
Tile
Profile
Tile Application
Minimum Attachment Resistance
Ent ra Flat Tile
Adhesive
31.3
2 See manufactures component approval for Installation requIrements.
3 Flexible Products Company TileBond Average weight per patty 13.9 grams.
Pclylbarn ProdugL Inc. Average weight RE patty8 gmrns.
Table 6: Attachment Resistance Expressed as a Mornent - Mt (ft-ibf)
for Single Eft Adhesive Set System
Tile
Profile
Tile Application
Minimum Attachment
Resistance
Entegra Fiat
Tile
Po Proms"
118.
P*PrOTM
40.4
4 Lame PaddyPlacement
of 45 ararns of PoWrOTU.
S Medium paddyplacement
of 24 arems of Po roTM.
NOA No.11-0414.09
Expiration Date: 06/07/16
Approval Date: 05/26/11
Page 5 of 6
5. LABELING:
All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo (See
Detail Below), or following statement: "Miami -Dade County Product Control Approved".
ENTEGRA FLAT TILE LABEL (LOCATED ON UNDERSIDE OF TILE)
6. BUILDING PERMIT REQUIREMENTS:
6.1 Application for building permit shall be accompanied by copies of the following:
6.1.1 This Notice of Acceptance.
6.1.2 Any other documents required by Building Official or Applicable building code in
order to properly evaluate the installation of this system.
PROFILE DRAWING
ENTEGRA "FLAT" CONCRETE ROOF TILE
16'
10'
FIELD TILE
16' =j
THICK BUTT TILE
END OF THIS ACCEPTANCE
NOA No.11-0414.09
Expiration Date: 06/07/16
Approval Date: 05a6/11
Page 6 of 6
MI®•
DEPARTMENT OF PERMITTING, ENVIRONMENT, AND REGULATORY
AFFAIRS (PERA)
BOARD AND CODE ADMINISTRATION DIVISION
OF ACCEPTANCE I
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
Mlam4 Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
www.miamidede,aov/pers/
1055 East 29"' Street
Hialeah, Florida 33013
SCOPE: This NOA is being issued under the applicable rules and regulations governing the use of
construction materials. The documentation submitted has been reviewed and accepted by Miami -Dade
County PERA -Product Control Section to be used in Miami Dade County and other areas where allowed by
the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control
Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right
to have this product or material tested for quality assurance purposes. If this product or material fails to
perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may
immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. PERA
reserves the right to revoke this acceptance, if it is determined by Miami -Dade County Product Control
Section that this product or material fails to meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building
Code, including the High Velocity Hurricane Zone.
DESCRIPTION: Series NVSNP, NV/NVTH, NVHC, NVSTA and NVHTA Steel Wood Connectors.
APPROVAL DOCUMENT: Drawing No. NU-5, titled "Skewed Nail Plate, NV359 & NV458 with Double
NVTH Straps, NVTH/NVTHS Anchors & NVHC Hurricane Clips and NVSTA & NVHTA Heavy Duty
Anchors with Seat", sheets 1 through 4 of 4, dated 04/15/2004, with last revision dated 01/25/2012, prepared
by Nu-Vue Industries, Inc., signed and sealed by Vipin N. Tolat, P.E., bearing the Miami -Dade County
Product Control revision stamp with the Notice of Acceptance number and expiration date by the Miami -
Dade County Product Control Section.
MISSILE IMPACT RATING: None
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state,
model/series, and following statement: "Miami -Dade County Product Control Approved", unless otherwise
noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been
no change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change
in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of
any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to
comply with any section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed
by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then
it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its
distributors and shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA N 09-0721.05 and consists of this page I and evidence page E-1, as well as approval
document mentioned above.
The submitted documentation was reviewed by Carlos M. Utrera, P.E.
NOA No. 12-0130.35
Z Expiration Date: December 23, 2014
1S'0
Approval Date: April 12, 2012
#5101 Page 1
� Nu -Vie Induatx.
NPMQ OF A►CCEFTANCE: EVIDENCE aPEWTTED
A. DRAWINGS
1. Drawing No. NU-5, titled "Skewed Nail Plate, NV358 & NV458 with Double NVTH
Straps, NVTJE•1/NVTHS Anchors & NVHC Hurricane Clips and NVSTA & NVHTA
Heavy Duty Anchors with SeaC. sheets 1 through 4 of 4, dated 04/15/2004, with last
revision dated 01/2512012, prepared by Nu-Vue Industries, Inc., signed and sealed by
Vipin N. Tolat, P.E.
B. TESTS "Submitted under NOA # 04-OSIOL03"
Test reports on wood connectors per ASTM
D1761 by Product Testing, Inc., signed
and sealed by C. R. Caudel, P.E.
BE ort . Wood Connector
•r.irwir�rw�w.��• �
Direct�io�n
Date
��-
1.
PT # 03-4482 NVSNP3
Downward
09/15/03
- 2.
PT # 03-4625 NVHCIJR
Up& Sideways
01/21/04
3.
PT # 04-4641 NVSTA•24H
Up& Sideways
03/17/04
4.
PT # 04-4698 NVTH24
Up& Sideways
04/15/04
5.
PT # 03-4590 NVTH26/NV458
Sideways
12/31 /03
6.
PT # 04-4642 NVHTA-24H
Up& Sideways
03/22/04
7.
PT # 03-4543 NVTH2O/NV358
Up& Sideways
12/19/03
C. CALCULATIONS "Submitted under NOA # 09-0721.05"
1. Report of Design Capacities, dated 06/30/2009, sheets 1 through 12 of 12, prepared,
signed and sealed by Vipin N. Tolat, P.E.
"SubmiNed under NOA # 04-0S10.03"
2. Report of Design Capacities dated 04/27/2004, sheet 1 through 12, prepared,
signed and sealed by Vipin N. Tolat, P.E.
D. QUALITY ASSURANCE
1. Miami Dade Department of Permitting, Environment, and Regulatory Affairs (PERA)
E. MATERIAL CERTIFICATIONS
1. None.
F. STATEMENT "Submitted raider NOA # 09-0721.05"
1. -Statement letter of code conformance, no financial interest and no change of product,
dated 07/08/2009, issued, signed and sealed by Vipin N. Tolat, P.E.
Carlos K Utren4 P.B.
Product Control Examiner
NOA No. U4130.35
Expiration Date: December 23, 2014
Approval Date: April 129 2012
E -1
• • N
y4.
0 0
0 o c
• a nji; 3%-
• 1 o 0
. " z W his
�W
v7i , �M
• one' Ir ur 4fe" •
We pattern Is Hdes ;" d&L �
m�Owdto d F
supperw
a
W a,w.
NVSNP3
TABLE 1
Installation
SKEWED NAIL PLATE
Product
Steel
Fastener
Allowable Loads (lbs)
Code
Gauge
Each Ead
Grovtty
li fR
NVSHPs
18
(8) 8d x Or
594
.594
For Uplift, use two NVSNP3. one at top chord and
one at bottom chord of the supporting and supported
Trusses In compliance with section 2321.7 of the F$C.
Notes:
1. Use . 6 nail holes In each flange.
2. Do not bend nail plate more then once.
•3. Supporting member shall be In the acute angle side with other flange behind the
end of supported member (see sketch.)
Ggneral Notes•
1. Steel shall conform to ASTM A653, structural grade .33 (Min. yield
33 kst) and a minimum galvanized coating of G 60 per ASTM A525.
2. Allowable loads are based on Latest Editions of National Desing
specifications (NDS) for wood construction and ' Florida Building Code
(FBC). ic. N I>s 2 aaS cxv.,dl Fe c 2 o I'm .
3. Design loads are for Southern Pine species with a specific gravity
of 0.55. Allowable loads for other species shall be adjusted
accordingly.
4. Common wire nail values are based on NDS and have been
Zam rum reduced for Penetration Qepth factor.
��bdottom
5. Allowable loads for wind uplift have been Increased by a duration
factor of 1.6 for anchors into wood only. Load values shown are,
without 33% steel stress increase.
6. Allowable loads for more than a single connection cannot be
added together. A design load which is divided into components In
the direction given must be evaluated as follows:
Actual Uplift'
Allowable Uplift + owa e Ll+Allowable - <i
7. Allowable loads are based on Ur thick wood members unless
otherwise noted.
8. All tie beams and grouted concrete masonry shall comply with '
FBC. Concrete for tie beams and grout and mortar for concrete
masonry shall be a minimum of 2500 psi. Concrete masonry shall
comply with ASTM C90.
9. All tests have been conducted In accordance with ASTM D-1761.
�taot8."a'xBVeseD VIM X. TOI AT, PE (CIM)
�,lak ItiEloeii 16 tom. 0 1W C
1� 181&9 I,ANT�RN CBBEK LAA1S
+J� 801i3YnN. TX 77088
.r o Qr Nu ..... Y u a lad .moo.
TABLE 2: NV358 - 14G Double NVTH Straps with 2 ply IBIS seat
Assembly
Product
Code
140 Strap
Product
Code
Dimension
H
(inches)
Total No.
of Fasteners
In 2 Straps
10d x 3'
Total No.
of Fastenero
In Seat
10d x 3'
Allowable Loads ([be)
uplift
L1
L2
NV3se-12
NV1Nte
12-
a
e
2245
1981
1e39
NV358-14
NValta
14
to
a
2525
2206
2088
NV355-19
NVIH20
is
12
a
2M
2452
229111
NV3511-20
NVTH24
2D
14
a
3086
26e7
25M
NV358-22
NVM25
22
16
a
338]
2tM2
2758
NV3511-24
NVTM
24
Ntla Ob '
p der. deelade.
plate an the gpoe6e eke.
NV !Zfl
IlImiao
26
NV359-32
NV"
32
NV359-44
NVM4a
44
Notes
1.e WwMNm aal
2. Neils as n
3. ass Note
roude
4 WasM9h
hto
In soaps
8 (S 1) for
(Shoe
dtaon Mail
oaaele 4'.
and eat to ad
ambboo.
net force IN Ws
ur
M trolPT 15GIB41
L2m.
ise�N x w Trues stole reaaVed
1 71 N b bell. clad b
TABLE 3: NV458 - 14G Double NVTH Strap:
Assembly
Product
Coda
140 Strop
Product
Code
I Dimension
H
(Inches)
Total No.
of Fast""
In 2 Straps
10d x 3'
Total
of Fast
In Se
10d x
NV45s-12
NV11116
12
6
9
HV4W-14
NVIRI8
14
10
a
W458-16
NVM20
to
12
e
NV458-20
NVN124
20
14
8
NV4W-22
NVTHM
22
18
8
NV456-24
NVIN28
24
NW58-20
NVI430
26
NV45a-32
NVM38
32
NV4611 4"
NVM46
44 Holm Diane"
r NV3se
Fiscou REVOW
eleengliiftwisenalift
Iri' NV488
�1W "11,954
1m,
W Holes D4
Lsti'NV356
tirmie3e
vim N. TOUT. PE (CM)
n. UG. / I N147
51ae.3�9
15128 1ANT6RH CHI )AN
HOU&M. T% 77068
with 3 ply 18G seat
1.
tors Allowable Loads ([be)
I. uplift L1 I t2
2245 2781 1D7B
25t5 3/31 23]a
xe06 x7e 25e7
30116 1 3827 1 2857
3W7 1 MIS 1 3117
]stall
NV358 and NV458 emcucr aevlsn
Tie Ban.
an lamretl sllh
filled Masonry.
561 a)
7
N u- V u e Induetrle., taa.
fOa3-,iQTA EON 29 5
..-'•-Idakeh: Fladtltl'J30
Phelan,(305) 694-M
For: (3W) 694-0
NV85B ! NV458 WITH DOIIHB NVTR SM
DEG /:
NU-5
sheet:
9 of 4
Data:
4 ta, to et
Hwviviane:
July S. woo
t
''`+ '�'1'.
PmpmTnearrgnrw�`�s�
TABLE
4
to
�tottm abed
•�L2
Truss Anchors NVTH
and
Riveted Truss Anchors with Seat NVTHS
OdAmmm
H
Length
Product
G�
Gauge
o. 0 en
in op
Maxirnurn ANowdMe
Load a
y
(ink
Cc&
strop
10d x�5•
Uplift
L1
L2
y ice r
12
NVM-16
NVTHS 212
18
14
a
1032
560
525
6
1222
671
630
R4N.
Paoli
1CN. EMB. to W=
14
NV114-18
NVTHS 214
18
14
7
1275
783
735
NVTHS NVtH
C+onvaie%110 Boom
or off•fW
16
UM-20
NVFHS 216
18
14
8
1329
783
735
TABLE 5
18
NViM-22
NMS 218
18
14
9
1383
783
735
HURRICANE CUPS
10
1437
783
735
Product
Description iPtiOf1
Gauge
Fasiorr n 10d
ROWW
x IF
ddat
!
ugm
to
Lx
NV WR
FWRRiCW CUP — RIGHT
18
8
6
80
253
333
K%m
HLOWAK CUP — LEFT
18
6
a
Ig
233
333
20 NVTH-24 NVINS 220 18 14 11 1480 783 735
22 NVtH-26 NVTHS 222 18 14 12 1544 783 735
For gift. use two ciIps. one on each
24
NVTH--28
WINS 224
18
14
13
1698 I
783
730
side to comply with section 2321.7 of
the FBC
26
NViH-30
NV7HS 228
18
14
32
NV114-38
WTHS 232
18
14
toter
44
NViHH-48
NVTHS 244
18
14
o
A
d V
0
•
.
11rtt� �e r
Hot" Ilia �'
o
t7C
to
WW IL Yma, PS (CWQ
�4hWWW'�'
M88 I1N1'M cum LAWN
NVTH. NVTHS
HOUB�N. TX TMO
t,Z
N C L
Nu — ue . Imo.
M.�. Awas
;
mtom=iomm
i�
war
doff I
09
�gqwll
ifwove••
ROWMm"Emlift:2
$,
hVM / XV= s K= RUMAM CUM
m IP.
1hee1;:
Date!
Ravidom
NU-5
3 of 4
Aess. !d. DM
;UV 6, SM
TABLE 6
NVSTA—Heavy Duty Anchors with 14G NVTH Straps and 1 ply 20G seat
Assembly 14G Strap Olmension Total No. Total No. of
Product Product H of Fasteners Fasteners In Allowable Loads (lbs)
Code Code (inches) In Strap 20 GA. Seat
10d x IV 10d x IX* uplin a LI a L2 e
NVSTA-121 NVTH16 12 5 8 Mae 700 MIS
a 8 1428 no 1144
NYSTA-1H NVTHIB 14
7 6 I045 an 1239
NVSTA-15H NVTH20 18 8 5 faA4 887 1335
NVSTA-20H NVTH24 20 e a I 950 1430
NVSTA-22H NVTIMS 22 h
• o
NMA-24H NVM29 24 • T
'- A 1
NVSTA-26H NVM30 M li
NVSTA-32H NVITM 32
Mtlaa DM '
NVSTA-44H NVM41 44
NVSTA
12H throght 44H
at 4' Nh
Ca
Fnisanmt 1bt 1$' PN 'E
UPLIFT
I
T.. repxree m belay
cats ottom Mad
uplM b
Top k betlmn
TABLE 7
NVHTA—Heavy Duty Anchors with 14G Double NVTH Straps and 1 ply 20G seat
Assembly
Product
Code
14G Strap
Product
Cade
Dimension
H
Inches
(Inches)
Total No.
of Fasteners
In two Straps
10d x Uf
Total No. of
Fasteners In
20 GA. Sect
tad x 1PC
Allowable Loads (Iba)
e
Uplift
a
UPRft
•
L1
a
NWTA-12H
NVMIa
12
to
6
M2
2070
1050
1450
12
a
1694
2335
flat
1631
NVMA-14H
NVM18
14
14
6
=5
28gs
1312
11112
NWTA-IW
NVTH20
18
16
6
2437
2558
14"
to"
NWTA-20H
NVTH24
20
18
6
2658
31t]
1 1573
Z75
Notes:
1. Naas, we necessary In straps and mat to achieve, desing load&
2. See note 8, sheet 1 for combined leading.
3. Nees through chord, shall not force the tram plate&
4• For general notes, em sheet 1.
5. For higher uplift loode6 concrete shall be 3000 psi.
S. Based on min. 25W pal concrete.
irl
",
NWTA-22H
NVTH26
22
NW7A-24H
NVM28
24
NWTA-26H
NVDIM
26
NWTA-32H
NVMW
32
NWTA-4414
NM48
44
s�wwm IYVs,swift ~� (�I�
A4haFr IS �I
M1a1ra
NYHTA
I Uroglht 44H Onsoll
nLgm=14
�iNIAb P1alY Side
V1PIN N. TOIAT, PE (CIVIL) Yls&
4i FL. MG. t 1s"? 20 OA. Seat
A'0�°4aN 16128 T21TP6tN CREEK LWE tyLAyly
AOU@I014, 17I 77088
N.
Nu—Vue industries. tea.
1061-IM ZWL M ff"A
Pia raylrad to banarw r ®dash. Floats Mols
fo Bottom A,aa Phoee: (am) 014-WVr
I ry�d� Pan (ON) Bg -W"
g nfasea txnsrw � I O NV"A k NVATA tRAVY DUTY tl CHIMIS "M SEAT
as beam UK 2p5 1{
Tap a bottom DWO 0: Sheet: Date: R ".=
NU-15 4 of 4 4Pm. la, 1004 July 5, 20M
Florida Building Code Online
Page 1 of 5
floodaD2p9!, BUS Home Log In UserRegistrabon Hot Topics
Busines/cLaQrLl Product Approval
Prof essi V na l 4USEa' Ptoli: User
Regulation
Submit Surcharge Scats a Facts Publications FK Staff BUS Site Map Links Search
Product Approval Menu> Prowa or AppbGBon
Sear,>Applicaton List> Application Hboorv>Appllrwnona 11
n. W_ :- FL #
FL13285-RO
Application Type
New
Code version
2007
Application Status
Approved
Comments
Archived
Product Manufacturer
USP Structural Connectors, a MiTek Company
Address/Phone/Emall
14305 Southcress Drive
Suite 200
Burnsville, MN 55306
(952) 898-8602
jmlllns®mll.mm
Authorized Signature
Technical Representative
Addmm/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory
Compliance Method
Evaluation Entity
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
Jim Collins P.E.
jmllins@mll.com
Todd Grevlous, PE
14305 Southcross Drive
Burnsville, MN 55306
(952) 898-8651
tgrevious@gibraltarl.com
Bryan Phelps
14305 Southcross Drive
Burnsville, MN 55306
(952) 898-8648
bphelps@gibraltarl.mm
Structural Components
Wood Connectors
Evaluation Report from a Product Evaluation Entity
ICC Evaluation Service, LLC
PFS Corporation
12/3l/2012
Terrence E. Wolfe P.E
Validation Checklist - Hardoi Received
FL13285 RO C01 FL
Standard
AFBPA N.D.S.
AISI/COS/NASPEC
ASTM D1761
Year
2005
2001
2000
https://www.floridabuilciing.org/pr/pr app_ tl.aspx?pamm=wGEVXQwtDgvRk6bsvZ66... 10/25/2014
Florida Building Code Online
Page 2 of 5
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
Date Revised
Summary of Products
Go to Page = a
Method 1 Option C
12/14/2009
05/18/2010
06/11/2010
08/10/2010
02/22/2012
0 0 Page 1/400
FL #
j Model, Number or Name
Description
13285.1
BRN Bridging
BRN812, BRN816, BRN3012, BRN3016, BRN1024, BRN1212,
BRN1216, BRN1224, BRN1412, BRN1416, BRN1424,
BRN1616,BRN1624
Limits of Use
Instal4tion Instructions
Approved for use In HVHZ: Yes
FL13285 RO 11 FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use in
HVHZ.
13285.2
EPCM Post Caps
EPCM4416, EPCM4516, EPCM4616, EPCM4716, EPCM4816,
EPCM5416, EPCM5516, EPCM6416, EPCM6616, EPCM6816,
EPCM8416, EPCM8616, EPCM8816, EPCM44, EPCM46,
EPCM48, EPCM64, EPCM66, EPCM68, EPCM75, EPCM77,
EPCM84, EPCM86, EPCM88
Limits of use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO II FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined in report ESR-1781.
13285.3
G Bridging
G812, G816, G824, G1024, G1212, G1216, G1224, G1416,
G3424, G1616, G1624
Limits or Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure. N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use in
HVHZ.
13285.4
HD Face Mount Hanger
HD26, HD24-2, HD34, HD44
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO II FL R2 11 ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Otherr Subject to loads and installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use in
HVHZ.
13285.5
HD Face Mount Hanger
HD28, HD210, HD212, H0214, HD216, HD26-2, HD28-2,
HD210-2, HD212-2, HD214-2, HD216-2, HD26-3, HD28-3,
HD210-3, HD212-3, HD214-3, HD216.3, HD210-4, HD36,
HD38, HD310, HD312, HD314, HD316, HD38-2
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO II FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 Rn AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781.
13285.6
HD Face Mount Hanger
HD310-2, HD312-2, HD46, HD48, HD410, HD412, HD414,
HD416, HD418, HD66, HD68, HD610, HD612, HD61,
https://www.floridabuil(ling.org/pr/pr_app_dtl.aspx?param--vGEVXQwtDgvRk6bsvZ66... 10/25/2014
Florida Building Code Online
Page 3 of 5
HD616, HD86, HD88, 1-0830, HD812, HD814, HD816,
HD3770, HD17925, HD17112
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO 11 FL R2 II ESR-1761.odf
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Verified By: ICC Evaluation Service, LLC
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined in report ESR-1781.
13285.7
HD Face Mount Hanger
HD3714, HD27925, H1327112, HD2714, HD32305, HD3212,
HD5112, HD51135, HD5210, HD5212, HD5214, HD5216,
HD62117, HD71117, HD7100, HD7120, H137140, HD7160,
H137180, HD77117, HD83117, HD95117
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO 11 FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.Ddf
outlined in report ESR-1781.
13285.8
HDO Top Mount Hanger
HDO24, H0034, HDO24-2, HDO44,
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 11 ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
EL13285 RO AE FL R2 AE ESR-1781.odf
outlined in report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use In
HVHZ.
13285.9
HDO Top Mount Hanger
HDO26, HDO28, HDO210, HDO212, H13O214, HDO216,
HDO36, HDO38, HDO310, HDO312, H13O314, HDO316,
HDO26-2, HDO28.2, HDO210-2, HDO212-2, HDO214-2,
HDO216-2, HDO46, HDO48, HDO410, HDO412
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO II FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.Ddf
outlined In report ESR-1781.
13285.10
HDO Top Mount Hanger
HOO414, HDO416, HDO210-3, HDO212-3, HDO214-3,
HDO216-3, HDO66, H13068, HDO610, HDO612, HDO614,
HD0616
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO 11 FL R2 11 ESR-1781.pdf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: WA
Evaluation Reports
Other: Subject to loads and Installation instructions
FL13285 RO AE FL R2 AE ESR-1781.odF
outlined in report ESR-1781.
13285.11
HHDO Top Mount Hanger
HHDO26-2, HHDO28-2, HHDO210-2, HHDO212-2,
HHDO214-2, HHDO216-2, HHDO210-3, HHDO212-3,
HHDO214-3, HHDO216-3, HHDO46, HHD048, HHDO410,
HH13O412, HHDO414, HHDO416, HHD066
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 11 ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781 odf
outlined In report ESR-1781.
13285.12
HHDO Top Mount Hanger
HHDO68, HHDO610, HH13O612, HHDO614, HHDO616,
HHDO312512, HHDO512512, HHDO512516
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO II FL R2 li ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Parry:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation instructions
FL13285 RO AE FL R2 AE ESR-1781.od
outlined in report ESR-1781.
https://www.floridabuilding.org/pr/pr_app_ tl.aspx?param=wGEVXQwtDgvRk6bsvZ66... 10/25/2014
Florida Building Code Online
Page 4 of 5
X
13285.13 ]A Joist Angle
JAI, JA3, ]A5, ]A7
Limits of Use
Installs on atructlons
Approved for use In HVHZ: Yes
FL13285 RO It FL R2 11 ESR-1781 odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluatlon Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odF
outlined In report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use In
HVHZ.
13285.14
]A loist Angie
JA9
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL13285 RO 11 FL R2 Lf ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined in report ESR-1781.
13285.15
IL Joist Hangers
31-24, JL26
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO I1 FL R2 it ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use In
HVHZ.
13285.16
It. Joist Hangers
31-28, JL210
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781.
13285.17
JR Joist Hangers
JRSSS, JRSS
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO 11 FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined in report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use In
HVHZ.
13285.18
]R joist Hangers
JRS, JRSX
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 It ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined in report ESR-1781.
13285.19
LSSH Ught Slopeable/Skewable
LSSH210, LSSH179, LSSH2O, LSSH23, LSSH25, LSSH26,
Hangers
LSSH3I,LSSH35
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 II ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
outlined In report ESR-1781.
13285.20
LSTA Strap Tle
LSTA9
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL13285 RO II FL R2 If ESR-1781.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL13285 RO AE FL R2 AE ESR-1781.odf
https://www.floridabuilding.org/pr/pr_app_dd.aspx?param--wGEVXQwtDgvRk6bsvZ66... 10/25/2014
Florida Building Code Online
Page 5 of 5
outlined In report ESR-1781. Requires supplementary
connection to provide minimum of 700# uplift for use In
HVHZ.
Go to Page 0 0 Page 1/ 4 0 0
Back Ncrt
cdnlact us :: Iw North Monme 4hreat Tallahassee FL 323N Phone: 850-187-1824
The State 0 F rlda k an WeE0 empbyer. Couvdoht 2007-2013 Sale of nodda.:: PrIvacv Statennem :: Accessibility Statement:: Refunds Statement
Under Fbddb taw, email addresses are public ncord5. If yew do not want your e-nnall address released in raspnme to a Wblk-nlcorts recuest, do rwt send
electronic mall b this sentry. Instead, contact the mice by phone or by "moral map. It you have any questions, please contact 850.487.INS. *"um, to
SeRbn 455.275(1), Fiords StaWbes, aRertive October 1, 2012, licensees lamed under chapter 455, F.S. must provide the Depamnem whh an small address 8
they have one. The smalls provided my be used for ot8clal communication w8h the licensee. However email addresses are public record. If you do not wish to
supply a personal address, please provide the DeamreM with an email address which can be made available ro the public. To deals" I e If you are a licensee under
Chapter 455, F.S., please di& h=.
PmduR Approval Accepts,
® ® El
xcuritvu, nur�
NEW
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvRk6bsvZ66... 10/25/2014
ICC-ES Evaluation Report ESR-1781
Issued January 1, 2009
This report is subject to re-examination in two years.
www.icc-es.ora 1 (800) 423-6587 1 (562) 699-0543 A Subsidiary of the Intemational Code Council'
DIVISION: 06—WOOD AND PLASTICS
Section: 06090—Wood and Plastic Fastenings
REPORT HOLDER:
UNITED STEEL PRODUCTS COMPANY
14306 SOUTHCROSS DRIVE, SUITE 200
BURNSVILLE, MINNESOTA 66306
(962) 89"772
www.uspeonnectors.com
infoCa usoconnectors.com
EVALUATION SUBJECT:
USP STRUCTURAL CONNECTORS
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2006 International Building Code® (IBC)
■ 2006 International Residential Code® (IRC)
■ Other Codes (see Section 8.0)
Property evaluated:
Structural
2.0 USES
The USP structural connectors described in this report (see
Table 1 for a complete listing) are used for connecting wood
framing members in accordance with Section 2304.9.3 of the
IBC. They may also be used in structures regulated underthe
IRC when an engineered design is submitted in accordance
with IRC Section R301.1.3.
3.0 DESCRIPTION
3.1 THE Face Mount Hanger:
The THE Face Mount Hanger is designed to provide lateral
top chord support for 1-joist-to-header applications. The THE
Face Mount Hanger is cold -formed from either No. 18 gage,
No. 16 gage, or No. 12 gage steel; and is prepunched for 10d
common nails into the header, and either 1 Od common or 10d-
by-11/2-inch nails into the joist. See Figure 1 and Table 2 for
product dimensions, fastener schedule, allowable loads, and
a typical installation detail.
3.2 THO Top Mount Hanger:
The THO Top Mount Hanger is designed to provide lateral top
chord support for 1-joist-to-header applications. The THO Top
Mount Hanger is cold -formed from either No. 18 gage, No. 16
gage, or No. 12 gage steel; and is prepunched for either 16d
common or 10d common nails into the header, and either 10d
common or 10d-by-V/2-inch nails into the joist. See Figure 2
and Table 3 for product dimensions, fastener schedule,
allowable loads, and a typical installation detail.
3.3 HD Face Mount Hanger:
The HD Face Mount Hanger is designed to support headers,
joists and trusses. The HD Face Mount Hanger is cold -formed
from No. 14 gage steel; and is prepunched for 16d common
nails into the supporting member, and either 10d common or
I0d-by-1'/2 inch nails into the supported member. See Figure
3 and Table 4 for product dimensions, fastener schedule,
allowable loads, and typical installation details.
3.4 HHDO Top Mount Hanger:
The HHDO Top Mount Hanger is designed to support
headers, joists and trusses. The HHDO Top Mount Hanger is
cold -formed from No. 12 gage steel and prepunched for
installation with NA20d nails. See Figure 4 and Table 5 for
product dimensions, fastener schedule, allowable loads, and
typical installation details.
3.6 HDO Top Mount Hanger.
The HDO Top Mount Hanger is designed to support wood
headers over door or window openings. The HDO Top Mount
Hanger is cold -formed from No. 12 gage steel; and is
prepunched for either 16d common, 10d common, or 10d-by-
1'/,-inch nails. See Figure 5 and Table 6 for product
dimensions, fastener schedule, allowable loads, and typical
installation details.
3.6 The THD Face Mount Hanger:
The THD Face Mount Hanger is designed to support LVL. LSL
and PSL beams. The THD Face Mount Hanger is cold -formed
from either No. 12 gage, No. 14 gage, or No. 16 gage steel;
and is prepunched for 16d common nails into the header, and
either 10d common or 10d-by-11/2-inch nails into the joist. See
Figure 6 and Table 7 for product dimensions, required
fastener schedule, allowable loads, and a typical installation
detail.
3.7 SKH Skewed 45' Hanger.
The SKH Skewed 45' Hanger is designed as a face mount
hanger that supports wood joists skewed either right or left at
an angle of 45 degrees from perpendicular. The connector is
cold -formed from either No. 14 gage or No. 16 gage steel; and
is prepunched for either 16d common, 10d common, or 10d-
by-1'/, inch nails. See Figure 7 and Table 8 for product
dimensions, fastener schedule, allowable loads, and a typical
installation detail.
3.8 TMP Rafter -to -Plate Connector:
The TMP Rafter -to -Plate Connector is designed to make
rafter -to -plate connections in lieu of notching. The connector
has a seat that can be field -adjusted to slopes ranging from
1:12 to 6:12 (5 to 27 degrees). The TMP Rafter -to -Plate
ICC-FS&o1.non Reports are nol to be.1reed as represerrling aesthetics or any other attributes not,,N tfic lly addressed nor are they to be.1med
man endorsement r flhe.sub/ecl ofthe report or mcmm endaflon for hs mse. There u w trarmmy by ICC /iVa1wum Service, bm., express or implied ms
to anyfrnding or other matter in this report, or as to arty product emered by the report.
Copynght 0 2009 Page 1 of 36
ESR-1781 I Most Widely Accepted and Trusted
Page 2 of 36
Connector is cold -fanned from No. 18 gage steel; and is
prepunched far 10d common nails into the plate and 10d-by-
11/,-inch nails into the rafter. See Figure 8 and Table 9 for
product dimensions, fastener schedule, allowable loads, and
a typical installation detail.
3.9 JL and JR Standard Joist Hangers:
The JL and JR Standard Joist Hangers are designed as face
mount hangers for connecting nominal dimension lumber to
headers, beams or girders. The JL hangers are cold -farmed
from No. 20 gage steel, and the JR hangers are cold -fanned
from No. 18 gage steel. The hangers are prepunchad for 16d
common or 10d common nails into the header, and 10d-by-
1V,4nch nails into the joist. See Figure 9 and Table 10 for
product dimensions, fastener schedule, allowable loads, and
a typical installation detail.
3.10 N and O Bridging:
The N series bridging is designed to span between two
nominally dimensioned wood joists to provide lateral bridging
and bracing meeting the requirements of IBC Section 2308.8.5
and IRC Section R502.7.1. The bridging is cold -formed from
No. 20 gage steel or No. 22 gage steel. The O series bridging
is designed to span across three joists in an over -and -under
configuration to provide lateral bridging and bracing meeting
the requirements of IBC Section 2308.8.5 and IRC Section
R502.7.1. The O series bridging is cold -formed from No. 22
gage steel. The ends of both the N and O series bridging are
prepunched for 8d-by-l'/2-inch nails, and the O series is also
partially punched in the middle to allow prongs to be pressed
into the middle joist. See Figure 10 and Table 11 for product
dimensions, fastener schedule, allowable loads, and a typical
installation detail.
3.11 BRN, G, MB1Sand MBG Bridging:
The BRN, G, MB16, and MBG series bridging is designed to
span between two nominally dimensioned wood joists to
provide lateral bridging and bracing meeting the requirements
of IBC Section 2308.8.5 and IRC Section R502.7.1. The BRN
series is cold -formed from No. 16 gage steel and is
prepunched for Bd-by-l'/,-inch nails. The G series is cold -
formed from No. 18 gage steel and is prepunched for 8d-by-
1'/,4nch nails. The MB16 and MBG series are cold -formed
from No. 22 gage steel. The MB16 series is designed to be
installed without the use of nails, and the MBG series is to be
installed with 8d-by-11/Z inch nails in a similar manner as the
G series. See Figure 11 and Table 12 for product dimensions,
fastener schedule, allowable loads, and a typical installation
detail.
3.12 MP MuIB-Purpose Framing Angle:
The MP Multi -Purpose Framing Angle is designed to provide
two-way and three-way lumber connections at various angles
and configurations. The MP Multi -Purpose Framing Angle is
cold -formed from No. 18 gage steel and prepunched for 8d-
by-11/i inch nails. See Figure 12 and Table 13 for product
dimensions, fastener schedule, allowable loads, and a typical
installation detail.
3.13 MPH Masonry Hanger:
The MPH Masonry Hanger is designed as a top flange hanger
to support nominally dimensioned wood joists, I -joists or
glued -laminated beams on concrete block walls. The hanger
is fabricated from No. 12 gage hot -rolled steel plate; and is
prepunched for 16d double -headed nails to be embedded into
the grouted cells of the masonry wall, and either 10d common
nails or 10d-by-1Y; inch nails driven into the joist. The U-
shaped saddle is factory -welded to the flange. See Figure 13
and Table 14 for product dimensions, fastener schedule,
allowable loads, and a typical installation detail.
3.14 S and WB Wall Bracing:
The S and WB series wall bracing is designed as alternatives
to the code -prescribed bracing method as noted in IBC
Section 2308.9.3(1) and IRC Section R602.10.3(1). The S
series bracing is cold -formed from either No. 16 gage or No.
20 gage steel in both a flat profile and a 'T' profile, and is
prepunched for 8d common nails. The WB series bracing is
cold -formed from No. 16 gage steel, and is prepunched for 8d
common nails into each stud and 16d common nails into the
top plate and sill plate. See Figure 14 and Table 15 for product
dimensions, fastener schedule, allowable loads, and typical
installation details.
3.16 IRS, PBES and PBS Post Caps:
The PB, PBES and PBS Post Caps are designed to provide
a post -to -beam connection of nominally dimensioned or rough
sawn lumber. The PBES and PBS are required to be used in
pairs (one on each side of the connection) at each connection
location. See Figure 15 and Table 16 for product dimensions,
fastener schedule, allowable loads, and typical installation
details.
3.16 PCM and EPCM Post Caps:
The PCM and EPCM Post Caps are designed to provide a
positive connection for post -to -beam applications. The post
caps are cold -formed from either No. 12 gage or No. 16 gage
steel, and are prepunched for 16d common nails. The PCM is
configured for a beam that is continuous over the post, and
the EPCM is configured for applications at the end of a beam.
See Figure 16 and Table 17 for product dimensions, fastener
schedule, allowable loads, and a typical installation detail.
3.17 JA Joist Angle:
The JA Joist Angle is designed to support wood joists where
stirrup -style hangers cannot be installed, or for reinforcement
of 90-degree wood connections. The angles are cold -formed
from either No. 14 gage or No. 16 gage steel, and are
prepunched for either 16d common or 10d-by-l'/,-inch nails.
See Figure 17 and Table 18 for product dimensions, fastener
schedule, allowable loads, and typical installation details.
3.18 SOt Hold -Down Framing Anchor:
The S01 Hold -Down Framing Anchor is designed to anchor
wall studs to wood sill plates. The framing anchor is cold -
formed from No. 18 gage steel and is prepunched for either 8d
common or 8d-by-1'/z inch nails. See Figure 18 and Table 19
for product dimensions, fastener schedule, allowable loads,
and typical installation details.
3.19 LSTA and MSTA Strap Ties:
The LSTA and MSTA Strap Ties are designed as strap ties for
various applications to transfer tension loads between wood
members. The LSTA series is cold -formed from either No. 18
gage or No. 20 gage steel, and the MSTA series is cold -
formed from either No. 16 gage or No. 18 gage steel. LSTA
and MSTA Strap Ties are prepunchad for 1 Od common or 10-
by-l'/, inch nails. See Figure 19 and Table 20 for product
dimensions, fastener schedule, allowable loads, and typical
installation details.
3.20 LSSH Light Slopeable/Skewable Hanger.
The LSSH Light Slopeable/Skewable Hanger is designed to
conned rafters to ridge beams in vaulted roof structures. The
hanger is field -adjustable to meet a variety of skew and/or
slope applications. The hanger may be field -adjusted for any
slope angle up to 45 degrees up or down from horizontal, and
for skew angles up to 45 degrees left or right from
perpendicular. The hanger is cold -formed from either No. 16
gage or No. 18 gage steel, and is prepunched for 16d
common, 10d common or 10d-by-1'/,-inch nails. See Figure
ESR-1781 I Most Widely Accepted and Trusted
Page 3 of 36
20 and Table 21 for product dimensions, fastener schedule,
allowable loads, and typical installation details.
3.21 Materials:
3.21.1 Steel: The specific types of steel and corrosion
protection for each product are described In Table 22 of this
report. Minimum steel base -metal thicknesses for the different
gages are shown in the following table:
GAGE NO.
MINIMUM BASE -METAL
THICKNESS (inch)
22
0.029
20
0.033
18
0.044
16
0.055
14
0.070
12
0.099
For Sh 1 Inch = 25.4 mm.
3.21.2 Wood: Wood members must be sawn lumber or
structural glued laminated timber with a minimum specific
gravity of 0.50, or approved structural engineered lumber
(structural composite lumber, alternative strand lumber, or
prefabricated wood (joists) with a minimum equivalent specific
gravity of 0.50, unless otherwise noted in the applicable table
within this report. Wood members must have a moisture
content not exceeding 19 percent (16 percent for structural
engineered lumber), except as noted in Section 4.1. For
connectors installed with nails, the thickness of each wood
member must be sufficient such that the specified fasteners
do not protrude through the opposite side of the member,
unless otherwise permitted in the applicable table within this
report. Wood members that are structural engineered lumber
must be recognized In, and used in accordance with, a current
evaluation report. Refer to Section 3.21.4 for issues related to
treated wood.
3.21.3 Fasteners: Required fastener types and sizes for use
with the USP structural connectors described in this report are
specified in this section and Tables 2 through 21. Nails used
for connectors described in this report must comply with
material requirements, physical properties, tolerances,
workmanship, protective coating and finishes, and packaging
and package marking requirements specified in ASTM F 1667;
and must have lengths, diameters and bending yield strengths
as shown in the following table:
FASTENER
DESIGNATION
FASTENER
LENGTH
(inches)
SHANK
DIAMETER
(Inch)
MINIMUM
REQUIRED
F (IhNln)
8d x 11/2
1.5
0.131
100,000
8d common
2.5
0.131
100,000
10d x 11/2
1.5
0.148
90,000
10d common
3.0
0.148
90,000
16d common
3.5
0.162
90,000
16d double-
headed
3.01
0.162
90,000
NA20d
2.5
0.192
80,000
For 81: 1 Inch = 25.4 mm, 1 psi 3 6.89 kPa.
' Indicates the length of the shank, not Including the length between
the two heads.
3.21 A Use In Treated Wood: Connectors and fasteners used
in contact with preservative -treated or fire -retardant -treated
wood must comply with IBC Section 2304.9.5 or IRC Section
R319.3. The lumber treater or the report holder (United Steel
Products Company), or both, should be contacted for
recommendations on the appropriate level of corrosion
resistance to specify for the connectors and fasteners as well
as the connection capacities of the fasteners used with the
specific proprietary preservative treated or fire -retardant -
treated lumber.
3.21.E Concrete and Masonry Construction: Materials and
quality of concrete and masonry construction must comply
with the applicable provisions of Chapter 19 and 21 of the I BC.
The compressive strength of the concrete and masonry
construction must be in accordance with the approved design
and applicable provisions of the building code.
4.0 DESIGN AND INSTALLATION
4.1 Design:
The allowable load capacities in Tables 2 through 21 are
based on allowable stress design. The use of the allowable
load values for the products listed in Table 1 of this report
must comply with all applicable requirements and conditions
specified in this report Tabulated allowable loads are for
normal duration and/or short duration, based on load duration
factors, Co, in accordance with Section 10.3.2 of the NDS, as
Indicated in Tables 2 through 21 of this report No further
increases are permitted for load durations other than those
specified. Tabulated allowable loads are for connections in
wood seasoned to a maximum moisture content of 19 percent
(16 percent forengineered wood products) or less, used under
continuously dry conditions and where sustained temperatures
are limited to 100OF (37.8°C) or less. When connectors are
installed in wood having a moisture content greater than 19
percent (16 percent for engineered wood products), or where
the in-service moisture content is expected to exceed this
value, the applicable wet service factor, CM, must be applied.
Unless otherwise noted in the tables of this report, the
applicable wet service factor, Cm, is as specified in the NDS
for lateral loading of dowel -type fasteners. When connectors
are installed in wood that will experience sustained exposure
to temperatures exceeding 100OF (37.8°C), the allowable
loads in this evaluation report must be adjusted by the
temperature factor, Cr, specified in Section 10.3.4 of the NDS.
The group action factor, C , has been accounted for, In
accordance with Section 10.�3.6 of the NDS, in the tabulated
allowable loads, where applicable. Connected wood members
must be checked for load -carrying capacity at the connection
in accordance with NDS Section 10.1.2.
4.2 Installation:
Installation of the connectors must be In accordance with this
evaluation report and the manufacturer's published installation
instructions.
4.3 Special Inspection:
4.3.1 IBC: Periodic special inspection is required for
installation of connectors described in this report that are
designated as components of the seismic-foroe-resisting
system for structures in Seismic Design Category C, D, E or
F in accordance with IBC Section 1707.3 or 1707.4, with the
exception of those structures that qualify underthe Exceptions
to Section 1704.1.
4.3.2 IRC: Special inspections are not required for
connectors used In structures regulated under the IRC.
5.0 CONDITIONS OF USE
The USP Structural Connectors described in this report
comply with, or are suitable alternatives to what is specified in,
those codes listed in Section 1.0 of this report, subject to the
following conditions:
ESR4781 I Most Widely Accepted and Trusted
Page 4 of 36
6.1 The connectors must be manufactured, idenfified and
installed in accordance with this report and the
manufacturer's published installation instructions. A copy
of the manufacturer's published installation instructions
must be available at the jobsite at all times during
installation. In the event of a conflict between this report
and the manufacturer's published installation
instructions, this report governs.
6.2 Calculations showing compliance with this report must
be submitted to the code official. The calculations must
be prepared by a registered design professional where
required by the statutes of the jurisdiction in which the
project is to be constructed.
6.3 Connected wood members and fasteners must comply
with Sections 3.21.2 and 3.21.3, respectively.
6A Adjustment factors, noted in Section 4.1 of this report
and the applicable codes, must be considered where
applicable.
5.5 Use of connectors and fasteners with preservative -
treated or fire -retardant- treated lumber must be in
accordance with Section 3.21.4.
6.6 The design of the anchorage to, and bearing upon,
concrete or masonry construction, inclusive of cast -in -
place and post -installed anchors, used to attach the
connectors described in this report to concrete or
masonry construction, is outside of the scope of this
report.
6.7 Connectors identified in Table 1 as being manufactured
under a quality control program with third -party
inspections are manufactured atthe designated facilities
under quality control program with inspections by PFS
Corporation (AA-652).
6.0 EVIDENCE SUBMITTED
Data in accordance with the ICC-ES Acceptance Criteria for
Joist Hangers and Similar Devices (AC13), dated October
2006 (corrected March 2007; editorially revised April 2008).
7.0 IDENTIFICATION
Each connector described in this report is identified by the
product model (stock) number, the number of the ICC-ES
index evaluation report for United Steel Products Company
ESR-2685 , and by one ormore of the following designations:
USP, or United Steel Products Company. Labels on
connectors identified in Table 1 as being manufactured under
a quality control program with third -party Inspections, also
bear the name of the third -party inspection agency (PFS
Corporation).
8.0 OTHER CODES
In addition to the codes referenced in Section 1.0, the
products recognized in this report were evaluated for
compliance with the requirements of the following codes:
■ 2003 International Building Code®
■ 2003 International Residential Code®
The USP structural connectors described in this report comply
with, or are suitable a@ematives to what is specified in, the
codes listed above, subject to the provisions of Sections 2.0
through 7.0.
ESR4781 I Most Kidely Accepted and Trusted
Page 32 of 36
TABLE 1"A JOIST ANGLE ALLOWABLE LOADS 1• r•'' 4'
STOCK NO.
STEEL
OIBE 711 On.)
FASTENER
SCHFJ)la.E
ALLOWABLE
LOADS(
Fbader
Joist
F
F
GAGE
W
Lcav
TV00
QtV
T
.0
=1.16
.26
-1b
.8R495
JA1
16
1 /
1 /
2
10d x i /
2
10d x 1 /
225
255
255
255
345
JAY--
14
2 /
3
4
16d
4
10d x 1 /
455
525
570
590
535
JA5
14
271
5
6
18 1
6
10d x 1 /
685
7115
855
950
1015JA7
14
2 /
7
8
16d
8
10dx1 /
910
1050
1140
1460
1625
14
2 /
9
10
led
10
10dx1/
1140
1310
1425
1825
16/5
For SI: 1 inch = 25.4 mm, 1 Ibf = 4.45 N.
'Allowable loads have been adjusted for load duration factors, Co, as shown, in accordance with the NDS. The allowable loads do not apply
to loads of other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 4.2 for additional design and
installation requirements.
' See Section 3.21.3 for required fastener dimensions and mechanical properties.
'Allowable loads shown are for Installations in wood members complying with Section 3.21.2.
4 Refer to drawings below for illustrations of each load direction. The "F1"load direction is that which results in lateral loading of all nails. The
"F2" load direction is that which results In the wood joist bearing on one leg of the angle, and lateral loading on the header nails. The "F3"
load direction is that which results in a withdrawal load on either the joist nails or the header nails.
' Tabulated allowable loads are for a single connector. When using a single angle, the joist must be constrained to provide fixity against
rotation.
w
I
1
JA
JAI
f3
Typical JA
installation
FIGURE 17—JA JOIST ANGLE
TYPICAL JA I
IN5TALLATION
Florida Building Code Online
Page 1 of 3
sin
KIS Home l In User Reglstrabon Hot Topics Submit Surcharge Stats&FaG Pubiimtons FSC Staff &CIS Site Map Un" Seamh
Business y���� Product Approval
Professional �i {�, tiSeR: Public User
Regulation i
crodua Aoorpval Menu > Proi or Aooncabon 5,Mh I Aeohcatmn U,t Application oaten
FL # FL16294
— - -- Application Type New
Code Version 2010
Application Status Approved
Comments
Archived
Product Manufacturer Nu-Vue Industries Inc.
Address/Phone/Emall 1055 E 29th street
Hialeah, FL 33013
(305) 694-0397
vtolat@sbcglobal.net
Authorized Signature Maria Guardado
vtolatesbcgiobal.net
Technlcal Representative
Address/Phone/Email
Quality Assurance Representative
Address/Phone/Email
Category Structural Components
Subcategory Wood Connectors
Compliance Method Evaluation Report from a Florida Registered Architect or a Umnsed
Florlda Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed
Vipin N. Tolat
the Evaluation Report
Florida License
PE-12847
Quality Assurance Entity
National Accreditation & Management Institute
Quality Assurance Contract Expiration Date
12/31/2014
Validated By
Jesus Gonzalez, P.E.
Validation Checklist - Hardcopy Received
Certificate of independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method
FL16294 RO COI Scan0205.odf
Standard Yee[
AISI 5100 2007
ASIM D1761-88 2000
NOS 2005
Method 1 Option D
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgsNc735fllbM... 10/25/2014
Florida Building Code Online
Page 2 of 3
Date Submitted 04/18/2013
Date Validated 04/2Z/2013
Date Pending FBC Approval 04/28/2013
Date Approved 06/11/2013
Summry of Products
FL a
Model, Number or Name
Description
16294.1
ASS, A87, NVHC 37, Tables 16 and
18 gage angle Clips and 5 way grip clip
17
Limits of Use
Inatallatlon Instructions
Approved for use in HVHZ: Yes
FL16294 RO II scan02O4.gdf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Party: Yes
16294.2
NVBH 24 and NVUH 26, Tables 2
Joist hangers
and 3
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL16294 RO II scanQ204.odf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design pressure: N/A
Evaluation Repots
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Party: Yes
16294.3
NVHCR, NVHCL, NVSTA, NVHTA
18 gage Hurricane clips and 14 gage single and double
Tables 9,10,11
straps
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL16294 RO II scan0204.odf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant. WA
Created by Independent Third Party: Yes
Design Pressuro: WA
Evaluation Reports
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Party: Yes
16294.4
NVJH, NVSO Tables 12 and 13
18 Gage and 16 Gage Joist hangers
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL16294 RO II scan02O4.ndf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12047
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scan0204.pd
Created by Independent Third Party: Yes
16294.5
NVRT, Table 4
14 Gage Flat and twisted rafter ties.
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL16294 RO II scan0204.odf
Approved for use outside HVHZ: Yes
Verified By; Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scanO204.udf
Created by Independent Third Party: Yes
16294.6
NVSNP3, NV 358, NV 458, Tables
Skewed Nall Plate and 14 Gage double straps.
6,7,8
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL16294 RO II scan0204.odf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scanO204 odf
Created by Independent Third Party: Yes
16294.7
NVSTA, NVHTA Tables 20 and 21
14 Gage Single and Double Straps
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
Approved for use outside HVHZ: Yes
FL16294 RO II scan0204.odf
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure N/A
Evaluation Reports
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Party: Yes
https://www.floridabiiilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgsNc735fObM... 10/25/2014
Florida Building Code Online
Page 3 of 3
16294.8
NV'A, AS, NVIH, NViHS,
14 Gage Truss anchors wood to concrete
Tables i and 5
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL16294 RO It scanD204.odf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Parry: Yes
16294.9
NVTH] and IKE, Tables 18 and 19
12 Gage Truss and Hip & lack Hangers and 20 gage Stud
Plate ties.
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL16294 RO ii scan02O4.odF
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Parry: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Party: Yes
16294.10
NVTP, NVTPH, NVHC Tables 14 and
20 gage Top Plate anchors and 18 gage Hurricane Clips
15
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL16294 RO tI scan0204,gdf
Approved for use outside HVHZ: Yes
Verified By: Vipin N. Tolat, P.E. PE 12847
Impact Resistant: N/A
Created by Independent Third Party: Yes
Design Pressure: N/A
Evaluation Reports
Other:
FL16294 RO AE scan0204.odf
Created by Independent Third Party: Yes
Baca nest
ar.Tagnaa•_:ht�'GLiISRT:•ii:1.:.^.iarllFl�]�Yk[. ]�d�&Y'LlS6PY
are public remNs. If you & not want your e-mail address released in response to a W Gk-remNs request, do not
rommunlOess wtbn wltll the Ikens e, However mull addresses are public record. n you do not wish to
m an eall addrhich can be made available to the public. To determine If you am a Ika nam undo
Chapter 455, F.S., please dick nere .
Product Approval Accepts:
re A E
https://www.floridabuilding.org/pr/pr_app_dfl.aspx?param=wGEVXQwtDgsNc735i0bM... 10/25/2014
LAT,
/� V1PIN N. W enp P.E.
// 15123 Lantern CreeeLane,
Houston, TX, 77068-3831
TEL: 281444-9183
Fax: 281444-9184
Email: vtolat®sbeglobaLnet
Page 1
ENGINEER'S EVALUATION REPORT # NU0413
CATEGORY: Structural Components
SUB CATEGORY: Metal Connectors
REPORT HOLDER:
NuVue Industries Inc;
1055 E. 29's Street,
Hialeah, FL. 33013
www.nu-vueindustries.com
nuvueaa bellsouth.net
Phone:305-694-0397
Fax: 305-694-0398
1.0 EVALUATION SCOPE:
Compliance with 2010 Florida Building Code- Building and Residential
2.0 PRODUCT DESCRIPTION:
Refer to tables 1 through 21 of this report for Product name, size, size and number of
fasteners, fastening details shown in the diagrams and the allowable loads.
3.0 STRUCTURAL SPECIFICATIONS:
1. Steel shall conform to ASTM A653, SS grade 33, min. yield 33 ksi, min. tensile
strength 45 ksi and min. galvanized coating of G 60 per A§TM A653.
2. Allowable loads and fasteners are based on NDS 2005.
3. Design loads are for S. Pine, specific gravity 0.55. Design loads for other species
shall be adjusted per NDS 2005.
4. Allowable uplift loads have been adjusted for load duration factor CD of 1.6.
Allowable gravity loads have been adjusted for CD values of 1.0, 1.15 and 1.25 per
table 2.3.2 of NDS 2005. Design loads do not include 33% increase for steel and
concrete.
5. Concrete in Tie beams shall be min. of 2500 psi. Concrete Masonry, Grout and
mortar in concrete masonry shall be min. of 1500 psi. Concrete masonry shall
comply with ASTM C90.
6. Combined load of Uplift, Ll and L2 shall satisfy the following equation.
Actual Uplift + Actual Ll + Actual L2 <=1.0
Allowable Uplift Allowable Ll Allowable L2
Page 2
4.0 INSTALLATION
Installation shall be in accordance with this report and the latest edition of
Nu-Vue Industries Catalog. The information in this report supercedes any
conflicting information in the catalog.
5.0 EVIDENCE SUBMITTED:
Test reports submitted by Product testing Inc, (PT) Atec Associates Inc(Atec)
and PSI Inc and signed and sealed calculations in conformance with FBC
2010 by Vipin N. Tolat, P.E.
• Product Test #/Test lab
tested
NVTA/NVTAS
02-3938/PT
NVTA/NVTAS
024073/PT
• NVTA/NVTAS
02-4074/PT
NVTA/NVTAS
02-4075/PT
NVTA/NVTAS
31.22456.0002/ATEC
NVBH 24
02-4096/PT
NVUH 26
02-4095/PT
NVRT
03-4177/PT
NVRT
03-4202/PT
i NVRT
03/4270,4271 /PT
NVTH/NVTHS
O44698/PT
NVSNP3
03-4482/PT
NV358
03/4543/PT
NV458
03-4590/PT
NVHCL/R
03-4625/PT
NVSTA/NVHTA
044641,4642/PT
NVJH24,26,28
034385,86,87/PT
NVS0236
03-4349,57,58/PT
NVTP4
03-4303,44/PT
NVTP4H
03-4345,43/PT
NVHC43,43/2
70-02-94-00381 /ATEC
AB5
05-5195.95A/PT
A137
05-5196,96A/PT
• NVHC37
03697.0001/ATEC
IKE 1
05-5612/PT
IKE2
06-5622/PT
NVTHJ26
04-4995/PT &138-96013-01/PSI
NVTHJ28
044996/PT& 138-96013-05/PSI
Date
Tested
8/6/02
11 /6/02
11 /6/02
11 /6/02
7/6/02
12/3/02
1 / 17/03
2/3/03
2/19/03
3/27/03
4/ 15/04
9/15/03
12/ 19/03
12/31 /03
1 /21 /04
3/17&3/22/04
5/30/03
5/ 13,5/ 19,5/20/03
4/21, 5/l/03
5/2, 5/5/03
11 /27/95
2/15/08
2/15/08
11 /27/96
3/20/06
5/l /06
1 /31 /05&2/7/89
1 /3 I /05& 12/2/89
Page 3
6.0 DESIGN:
1 Maximum allowable loads shall not exceed the allowable loads listed in this
report. Allowable loads are based on allowable stress design per NDS.
2. Capacity of wood members is not covered by this report. Allowable loads shall
not exceed the capacity of wood members. Capacity of wood members shall be
checked by Engineer/Architect of record.
3. Wood members with which the connectors are used must be nominal dimension
lumber or approved structural composite lumber.
7.0 CODITIONS OF USE:
1. NuVue Industries metal structural connectors described in this report comply
with or are suitable alternative to what is specified in section 1.0 of this report.
2. Design loads must be less than the allowable loads shown in all the tables of
this report.
3. The connectors must be manufactured, identified and installed in accordance
with this report and the manufacturer's instructions.
4. Products covered by this report are manufactured by NuVue industries Inc in
Hialeah, Florida under a quality control program with inspections by NAMI
Inc having State of Florida license # QUA 1789.
Vipin N. Tolat, P.E.
Florida P.E. # 12847
4/15/2013
vnt/nu0413
• �GENS �••• ':
No. 12847
w ••
•
:'�•. STATE OF • w
.w.
.'�
'• 0•0
•:c O R O ?�
S/ONA���••
''���rf111lltt��
Page 4
TABLE 1
Truss Anchors NVTA and Riveted Truss Anchors with Seat NVTAS
14 G Straps, 20 G Seats
1"
H
Length
(in)
Product
Code
t6
NVTA-16
NVTAS 212
18
NVTA-18
NVTAS 214
20
NVTA-20
N VTAS 216
22
NVTA-22
NVTAS 218
24
NVTA-24
NVTAS 220
26
NVTA-26
NVTAS 222
28
NVTA-28
WAS 224
30
NVTA— 30
WAS 226
36
NVTA-36
NVTAS 232
48
NVTA-48
NVTAS 244
1 �N
H
MIN. 4"
EMB. Parallel L1
to wall
NVTAS 1"
1"
NVTA
No. of
Fasteners
each strap
10d
Maximum Allowable Load
Ibs
Uplift
Single
Strap
Uplift
Double
Straps
L1 Single
& Double
Straps
L2 Single
& Double
Straps
5
757
1514
250
500
6
805
1610
250
500
7
854
1708
250
500
8
902
*1804
250
500
9
951
*1902
250
500
10
999
*1998
250
500
11
1048
*2096
250
500
12
1096
*2192
250
500
13
1145
*2290
250
500
14
1193
$2290
250
500
*Note: For 8 or more nails per strap, use double
truss for double straps.
For all Loads Cp=1.6
J 4"
EMB.
1"
Perpendicular
to wall
L2
Concrete Tie Beam
or Tie Beam formed
with concrete filled
masonry
�N
0 1„
H 2j„ O
O 2j"
0
Holes Die. All
NVTA, NVTAS
No. of
Fasteners
each strop
10d x 1.5"
Maximum Allowable Load
Ibs
Uplift
Single
Strap
Uplift
Double
Straps
L1 Single
& Double
Straps
L2 Single
& Double
Straps
5
1032
2236
250
500
6
1127
2254
385
565
7
1136
2272
520
630
8
1144
*2288
520
630
9
1153
$2306
520
630
10
1161
02322
520
630
11
1170
02340
520
630
12
1178
02356
520
630
13
1187
$2374
520
630
Page 5
TABLE 2
NVBH 24 BUTTERFLY HANGER
N
Ow
00
v
Q
FASTENER
SCHEDULE
ALLOWABLE
LOADS (Ibs.)
DOWNWARD
2
N
0
o
LA
GRAVITY
Wind
Q ago
000
LOADS
Uplift Load
_
-'
Co=1.0
C0=1.6
2x4
NVBH24
18
12
6
1113
364
Notes:
1. Values are based on 1 j" header and Joist
thickness.
2. Can only be used in Nan—HVHZ.
UPLIFT LOAD
2j"
TABLE 3
NVUH 26 JOIST HANGER
N
CAd
U W
no
U
�
D
FASTENER
SCHEDULE
ALLOWABLE
LOADS (Ibs.)
�_
DOWNWARD
WIND
0
Qmo
N x
GRAVITY
UPLIFT
LOADS
LOAD
i
C0=1.0
Cp=1.6
2x6
NVUH26
14
20
10
2233
1213
Notes:
1. Values are based on 3" header thickness and
11" Joist thickness.
UPLIFT LOAD
DOWNWARD LOAD
5J"
Page 6
TABLE 4
NVRT — Flat and Twisted Rafter Ties 1"x14 G
NVRT Wood to Wood
Length
(in)
Product
Code
Gauge
12
NVRT-12
14
16
NVRT-16
14
18
NVRT-18
14
20
NVRT-20
14
22
NVRT-22
14
24
NVRT-24
14
30
NVRT— 30
14
36
NVRT-36
14
48
NVRT-48
14
Notes:
1. Specify "F" for Flat and "T" for Twisted when
ordering.
2. Fastener values are based on a minimum T
thick wood members.
3. • Indicates no. of nails in each connected
wood member.
16d Fasteners
Maximum Uplift Load (Ibs)
TOTAL
Temg;^.
Flat Ties
Twisted Ties
6
3
s
588
s
588
8
4
725
724
10
5
861
860
12
6
1 998
996
14
7
1135
1132
NVRT Wood to Concrete
No. of 16d nails
to Wood Framing
No. of }" diameter
Tapcons to Concrete
Maximum Uplift
Load (Ibs)
3
3
a
588
4
4
722
5
4
856
6
1 5
1 991
7
5
1125
4. ITW topcons shall be embedded a minimum of
1j" into concrete tiebeam or tiebeam formed
with concrete filled masonry. ITW topcons shall
have a min. edge distance of 21" and minimum
staggered spacing of -" as shown.
5. Use only in Non—HVHZ.
6. For Uplift loads CD=1.6
}• Do not
Use circled
II II holes 16d
0 1.
0 }"Tapcons
o
11- o
0 Z o jr
K o 7(
O 1�. o a 11S" 11�
a
NVRT Anchor
Holes dia. all
I IPI IGT
•••• Al
L • LENGTH _I
r 7
FLAT
HALF HALF
Connected Connected
to truss Il0 WOII
• • a
I_ LENGTH _I
TWISTED
concrete Poled musonary or
concrete tie beam
0,tooco
I;
nce
Florida Building Code Online
Page i of 4
etvvlvv uvAvrnwgr pc
_ ALrlpnc_c R _Prafe6 jinni Rey t aft0tt..=
?Wl 1 tt
MIS Home LW In User Regist-mon Hot Tapia Submit Surcharge Stots & Facts Publications FaC Staff 3C1S Site Map Links Search
Busines / Product Approval
Professignall �a,k
Regulation
Product Aomoval menu > Product or Application Search > Aoollcaban LIST > AVWlotlan aab11
Fl- # FL821-R3
Application Type Revision
Code Version 2010
Application Status Approved
Comments
Archived
Product Manufacturer USP Structural Connectors, a MITek Company
Address/Phona/Emall 14305 Southcross Drive
Suite 200
Burnsville, MN 55306
(952) 898-8602
)collins@mii.com
Authorized Signature
Technical Representative
Address/Phone/Emall
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory
Compliance Method
Evaluation Entity
Quality Assurance Entity
Quality Assurance Contract Expiration Date
Validated By
Certificate of Independence
Referenced Standard and Year (of Standard)
Equivalence of Product Standards
Certified By
Sections from the Code
31m Collins P.E.
Jcolilnsomii.com
Todd Grevicus, PE
14305 Southcross Drive
Burnsville, MN 55306
(952) 898-8651
tgrevlous@glbraltarl.com
Chad Becker
703 Rogers Drive
Montgomery, MN 56069
(507) 364-7333
checker@mli.com
Structural Components
Wood Connectors
Evaluation Report from a Product Evaluation Entity
ICC Evaluation Service, LLC
PFS Corporation
12/31/2015
Terrence E. Wolfe RE
J Validation Checklist - Hardcopy Received
Fl-821 R3 COI ICC Indeoendence.cert.odf
Standard
AF&PA National Design Specification
ASTM D1761
ASTM D7147
Year
2005
2000
2005
h4s://www.flori&building.orglprlpr app_4tl.aspx7param=wGEVXQwtDgti7enhn9An9... 10/25/2014
Florida Building Code Online
Page 2 of 4
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
Summary of Products
Go to Page = a
Method 1 Option C
02/22/2012
04/25/2012
04/30/2012
06/11/2012
i'J O Page t/50 42
FL #
Model, Number or Name
Description
821.21
HUS24-3
Slant Nall Joist Hanger
Limits of Usa
Installation Instructions
Approved for use In HVHZ: No
FL821 R3 II esr1881.Ddf
Approved for use outside HVHZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Product Deleted.
FL821 R3 AE esr1881.Ddf
821.22
i HUS26, HUS26-2
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 11 AE esr1881.Ddf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other. Subject to loads and Installation Instructions
FL821 R3 AE AE esr1881.Ddf
outlined In report ESR-1881.
821.23
HUS26-3
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVHZ: No
FL821 R3 II esrl881.odf
Approved for use outside HVHZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Product Deleted.
FL821 R3 AE esrl881.Ddf
821.24
HU528, HUS28-2
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II esr1881.Ddf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL821 R3 AE esr1881.Ddf
outlined In report ESR-1881.
821.25
HUS28-3
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVHZ: No
FL821 R3 11 esrl881.Ddf
Approved for use outside HVMZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Parry:
Design Pressure: N/A
Evaluation Reports
Other: Product Deleted.
FL821 R3 AE esrl881.Ddf
821.26
HUS410
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
Approved for use outside HVHZ: Yes
FL821 R3 11 esr1881.oil
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL821 R3 AE esr1881.odf
outlined in report ESR-1881.
821.27
HUS412
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVMZ: Yes
FL821 R3 11 esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL821 R3 AE esr1881.Ddf
outlined In report ESR-1881.
621.28
HUS414
Slant Nall Joist Hanger
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgti7enlm9An9... 10/25/2014
Florida Building Code Online
Page 3 of 4
Limits of Use
Installation Instructions
Approved for use In HVHZ: No
Approved for use outside HVHZ: No
FL821 R3 II esr1881.odF
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Othen Product Deleted.
FL821 R3 AE esr1881.odf
821.29
i HUS44
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: No
FL821 R3 11 esr1881.odf
Approved for use outside HVHZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other. Product Deleted.
FL821 R3 AE esr1881.odf
821.30
HUS46
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II e5r1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL821 R3 AE esrI881.odf
outlined In report ESR-1881.
821.31
li HUS48
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II esrIS81.odf
Approved for use outside HVHZr Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL821 R3 AE esr188I.ydf
outlined In report ESR-1881.
821.32
JUS210
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation instructions
outlined in report ESR-1881.
FL821 R3 AE esr1881.odf
821.33
i JUS210-2
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FU21 R3 11 esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation instructions
FL821 R3 AE esr1881.odf
outlined In report ESR-1881.
821.34
JUS210-3
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 It esr1881 odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Intlependent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
F_L821 R3 AF e5r1881 odf
outlined in report ESR-1881.
821.35
JUS212-2
Slant Nall Joist Hanger
Limits of Use
Installation InstruWons
Approved for use in HVHZ: No
FL821 R3 11 esr1881. odf
Approved for use outside HVHZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Product Deleted.
FL821 R3 AE esr1881 odf
821.36
JUS212-3
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 11 esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation instructions
FL821 R3 AE esr1881.odf
outlined In report ESR-1881.
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param--vGEVXQwtDgti7enlm9An9... 10/25/2014
Florida Building Code Online
Page 4 of 4
821.37 JUS214-2
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 11 esr1B81.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Product Deleted.
FL821 R3 AE esr1881.odf
821.38
JUS214-3
Slant Nail Joist Hanger
Limits of Use
Inatsllation Instructions
Approved for use In HVHZ: No
FL821 R3 11 esr1881.Ddf
Approved for use outside HVHZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Repots
Other: Product Deleted.
FL821 R3 AE esr1881.odf
821.39
JUS24
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL821 R3 11 esr1881.Ddf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Parry:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL821 R3 AE esr1881. Do
outlined In report ESR-1881. Requires supplementary
connection to provide minimum of 700# uplift for use in
HVHZ.
821.40
3US24-2
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL821 R3 I1 esri881.Ddf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL821 R3 AE esr1881.odf
outlined in report ESR-1881. Requires supplementary
connection to provide minimum of 700# uplift for use In
HVHZ.
Go to Page = 40
Back Nezl
O 0 Page 2 / 5 0 0
The sum a F1arWa a an AA/EED employer. Cownaht 2007-2013 Stites of nanoa.:: Pnvary Statement :: 4,v+c.i U11i�snornou :: RafuM S3lemenf
Under Flarda ew, email addresses are oublk records. If you do not waM your a mall address reeasea In response W a pubik-records reeuest, do not sent
de conk mail W M15 entry. Instuad, ondad the ofeae by phone or by tradMoml mall. If you have any auesdom, please woud 950.4e7.1395.'Purswnt W
Sedbn 455.275(1), Rama SnWtas, effia vm October 1, 2012, Ikensees Ikem under Chapter 455, F.S. must prowo. the Department with an email adtlrbs r
May have cam. The emaiis pronWed may be used for oMoal communication wIM one Ilcamae. tbwever emell addnssas art publk remM. If you on not wish W
supply a personal address, plmse provide the Department with an email address which an be made avallade W the publk. To dettrmlm If you are a Iloensee uMar
Chapter 455, F.S., please dhk obit.
Product Approval
m proval Apbt
® 10 1
CreditSAFE
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgti7enlm9An9... 10/25/2014
Florida Building Code Online
Page 2 of 4
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
Summary of Products
Go to Page
Method 1 Option C
02/22/2012
04/25/2012
04/30/2012
06/11/2012
0 0 Page3/50 0
FL ff
Model, Number or Name
Description
822.41
JUS24-3
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in I4VHZ: No
FL821 R3 11 esr1881.odf
Approved for use outside HVHZ: No
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Product Deleted.
F1.821 R3 AE esr1881.odf
821.42
i JUS26
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL821 R3 II esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation instructions
FL821 R3 AE esr1881.odf
outlined In report ESR-1881.
821.43
3US26-2
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation instructions
FL821 R3 AE esr1881.Ddf
outlined in report ESR-1881.
821.44
1 3US26-3
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 :i esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other. Subject to loads and Installation instructions
FL821 R3 AE esr1881.odf
outlined in report ESR-1881.
821.45
13US28
Slant Nail Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II esr1881.odF
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and Installation Instructions
FL821 R3 AE esr1881.odf
outlined in report ESR-1881.
821.46
3US28-2, JUS28-3
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use in HVHZ: Yes
FL821 R3 II esr1881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other. Subject to loads and Installation Instructions
FL821 R3 AE esr1881.odf
outlined in report ESR-1881.
821.47
JUS36, JUS38, JUS310
Slant Nall Joist Hanger
Limits of Use
Installation Instructions
Approved for use In HVHZ: Yes
FL821 R3 it esrl881.odf
Approved for use outside HVHZ: Yes
Verified By: ICC Evaluation Service, LLC
Impact Resistant: N/A
Created by Independent Third Party:
Design Pressure: N/A
Evaluation Reports
Other: Subject to loads and installation Instructions
FL821 R3 AE esr1881.odf
outlined in report ESR-1881.
821.48
13US410
Slant Neil Joist Hanger
h4s://www.floridabuilding.org/pr/pr_app_dfl.aspx?pamm--vGEVXQwtDgt17enlm9An9... 10/25/2014
ICC-ES Evaluation Report ESR-1881
Reissued May 1, 2011
This report is up for renewal January 1, 2013.
www.icc-es.org j (800) 423.6687 j (662) 699-0543 A Subsidiary of the International Code Council®
DIVISION: 06 00 00—WOOD, PLASTICS AND
COMPOSITES
Section: 06 OS 23—Wood, Plastic, and Composite
Fastenings
REPORT HOLDER:
UNITED STEEL PRODUCTS COMPANY
14305 SOUTHCROSS DRIVE, SUITE 200
BURNSVILLE, MINNESOTA 66306
(952)898-8772
www.uspconnectors.com
i n fo(cD u s o c o n n e cto rs. c o m
EVALUATION SUBJECT:
USP STRUCTURAL CONNECTORS
1.0 EVALUATION SCOPE
Compliance with the following codes:
■ 2009 and 2006 International Building Code® (IBC)
■ 2009 and 2006 Intemational Residential Codee (IRC)
Property evaluated:
Structural
2.0 USES
The USP structural connectors described in this report
(see Table 1 for a complete listing) are used for connecting
wood framing members in accordance with Section
2304.9.3 of the IBC. They may also be used in structures
regulated under the IRC when an engineered design is
submitted in accordance with IRC Section R301.1.3.
3.0 DESCRIPTION
3.1 CLPBF Butterfly Hanger:
The CLPBF Butterfly Hanger is a face -mount hanger with
triangular header flanges having prepunched nail holes for
joist -to -header or truss -to -truss connections. The CLPBF
Butterfly Hanger is cold -formed from No. 18 gage steel and
is prepunched for 10d common nails into the header and
tOd-by-1112-inch nails into the joist. See Figure 1 and Table
2 for product dimensions, fastener schedule, allowable
loads, and a typical installation detail.
3.2 CMST Coil Strap:
The CMST Coil Strap is designed for resisting tension
loads for a variety of wood framing applications. The
CMST Coil Strap is cold -formed from either No. 12 or
No. 14 gage steel in lengths of 40 and 52'/2 feet (12.2 and
16.0 m), respectively. The CMST Coil Strap is prepunched
for either 10d common or 16d common nails. See Figure 2
and Table 3 for product dimensions, fastener schedule,
allowable loads, and a typical installation detail,
3.3 HCPRS Hurricane/Seismic Anchor:
The HCPRS Hurricane/Seismic Anchor is designed to
tie trusses and rafters or nominally dimensioned 2-by
wall studs to bottom plates for the purpose of resisting
uplift, lateral and transverse loads. The HCPRS
Hurricane/Seismic Anchor is cold -formed from No. 18
gage steel and is prepunched for 8d common or 8d-by-
1'/cinch nails. See Figure 3 and Table 4 for product
dimensions, fastener schedule, allowable loads, and a
typical installation detail.
3.4 HUS Slant Nail Joist Hanger:
The HUS Slant Nail Joist Hanger is designed to provide
double shear nailing for joistttruss-to-beam connections.
The HUS Slant Nail Joist Hanger is cold -formed from No.
14 gage or No. 16 gage steel and is prepunched for 16d
common nails into both the joist and the header. See
Figure 4 and Table 5 for product dimensions, fastener
schedule, allowable loads, and typical installation details.
3.5 JUS Slant Nail Joist Hanger.
The JUS Slant Nail Joist Hanger is designed for face -
mount applications to provide double shear nailing for
joist/truss-to-beam connections. The JUS Slant Nail Joist
Hanger is cold -formed from No. 18 gage steel and is
prepunched for either 10d common or 16d common nails
into both the joist and the header. See Figure 5 and Table
6 for product dimensions, fastener schedule, allowable
loads, and a typical installation detail.
3.6 MP F Multi -Lateral Plate Tie:
The MP_F Mufti -Lateral Plate Tie is designed to transfer
lateral loads in top plate -to -rim joist applications or for
blocking applications. The MP F Multi -Lateral Plate Tie is
cold -formed from No. 20 gage steel and Is prepunched for
either Bd common or Bd-by-l'/2-inch nails. See Figure 6
and Table 7 for product dimensions, fastener schedule,
allowable loads, and a typical installation detail.
3.7 PAU Post Anchor.
The PAU Post Anchor is designed to secure wood posts to
concrete or masonry members. The PAU Post Anchor is
comprised of three components: an anchor base, a stand-
off plate, and a washer. The anchor base is cold -formed
from No. 10 gage or No. 12 gage steel. The stand-off plate
is cold -formed from either No. 12 gage or No. 16 gage
steel. The washer is cut from No. 3 gage or No. 10 gage
steel. The PAU Post Anchor is fastened to the post with
either 16d common nails or '/2-inch-diameter (12.7 mm)
ICC-F.:S liwluarion Reports arc It. be rorulrued as orany other wr burea not apee0rally addressed nor. they ro be eonsiruM
as an endorsemeno erohe subject ofthe neporl or a recommendation for lm use. There a no warranty by ICC n aluollon 8erelce, LLC, exprus or Implied, M
o, any jindong or other maaeNn this Moon,, or. m any product m,ared by the reparr. '4= e„—„_
Copyright O 2011 Page 1 of 14
ESR4881 I Most Widely Accepted and Trusted Page 2 of 14
bolts. The PAU Post Anchor is fastened to the concrete or
masonry foundation utilizing s!e-Inch- diameter (15.9 mm)
anchor bolts, expansion anchors or threaded rod, which
must be designed separately. See Figure 7 and Table 8 for
product dimensions, required fastener schedule, allowable
loads, and a typical installation detail.
3.8 RSPT Stud Plate Tie:
The RSPT Stud Plate Tie is designed to connect wall studs
to single- or double -top plates or sill plates. The RSPT
Stud Plate Tie Is cold -formed from No. 18 gage or No. 20
gage steel, and prepunched for either 10d common, 10d-
by-1'/24nch, 8d common, or 8d-by-1 1/2-inch nails. See
Figure 8 and Table 9 for product dimensions, fastener
schedule, allowable loads, and typical installation details.
3.9 SPT and SPTH Stud Plate Ties:
SPT and SPTH Stud Plate Ties are designed to connect
wall studs to single- or double -top plates. SPT and SPTH
Stud Plate Ties are cold -formed from No. 20 gage and No.
18 gage steel, respectively, and are prepunched for 10d-
by-1 %-Inch nails. See Figure 9 and Table 10 for product
dimensions, fastener schedule, allowable loads, and a
typical installation detail.
3.10 THOH Face Mount Hanger.
The THDH Face Mount Hanger is designed as a hanger
for metal -plate -connected wood trusses. The THDH Face
Mount Hanger is cold formed from No. 12 gage steel and
is prepunched for 16d common nails. See Figure 10 and
Table 11 for product dimensions, fastener schedule,
allowable loads, and a typical installation detail.
3.11 Materials:
3.11.1 Steel: The specific types of steel and corrosion
protection for each product are described in Table 12 of
this report. Minimum steel base -metal thicknesses for the
different gages are shown in the following table:
GAGE NO.
MINIMUM BASE -METAL
THICKNESS (inch)
20
0.033
18
0.044
16
0.055
14
0.070
12
0.099
10
0.129
3
0.240
For Si: 1 inch a 25.4 mm.
3.11.2 Wood: Wood members must be sawn lumber or
structural glued laminated timber with a minimum specific
gravity of 0.50, or apprgved structural engineered lumber
(structural composite lumber, alternative strand lumber, or
prefabricated wood Igoists) with a minimum equivalent
specific gravity of 0.50, unless otherwise noted in the
applicable table within this report Wood members must
have a moisture content not exceeding 19 percent
(16 percent for structural engineered lumber), except as
noted in Section 4.1. For connectors installed with nails,
the thickness of each wood member must be sufficient
such that the specified fasteners do not protrude through
the opposite side of the member, unless otherwise
permitted in the applicable table within this report. Wood
members that are structural engineered lumber must be
recognized in, and used In accordance with, a current
evaluation report. Refer to Section 3.11.4 for issues related
to treated wood.
3.11.3 Fasteners: Required fastener types and sizes
for use with the USP structural connectors described in
this report are specified in this section and Tables 2
through 12.
3.11.3.1 Bolts: At a minimum, bolts must comply with
ASTM A 36 or ASTM A 307, and must have a minimum
bending yield strength of 45,000 ibf/in2 (310 MPa). Bolt
diameters must be as specified in the applicable tables of
this report.
3.11.3.2 Nails: Nails used for connectors described in this
report must comply with material requirements, physical
properties, tolerances, workmanship, protective coating
and finishes, and packaging and package marking
requirements specified In ASTM F 1667; and must have
lengths, diameters and bending yield strengths as shown
in Table 12 of this report
FASTENER
DESIGNATION
FASTENER
LENGTH
(inches)
SHANK
DIAMETER
(inch)
MINIMUM
REQUIRED
Fyb (00n)
8d x 02
1.5
0.131
100,000
8d common
2.5
0.131
100,000
10d x 02
1.5
0.148
90,000
10d common
3.0
0.148
90,000
16d common
3.5
0.162
90,000
'12' dia. bolt
Varies
0.500
45,000
64a- dia. bolt
Varies
0.625
45,000
For SI:1 inch = 25A mm,1 psi = 6.89 kPa.
3.11.4 Use in Treated Wood: Connectors and fasteners
used in contact with preservative -treated or fire -retardant -
treated wood must comply with IBC Section 2304.9.6 or
IRC Section R319.3. The lumber treater or the report
holder (United Steel Products Company), or both, should
be contacted for recommendations on the appropriate level
of corrosion resistance to specify for the connectors and
fasteners as well as the connection capacities of the
fasteners used with the specific proprietary preservative -
treated or fire -retardant -treated lumber.
3.11.5 Concrete and Masonry Construction: Materials
and quality of concrete and masonry construction must
comply with the applicable provisions of Chapters 19 and
21 of the IBC. The compressive strength of the concrete
and masonry construction must be in accordance with the
approved design and with applicable provisions of the
building code.
4.0 DESIGN AND INSTALLATION
4.1 Design:
The allowable load capacities in Tables 2 through 12 are
based on allowable stress design. The use of the allowable
load values for the products listed in Table 1 of this report
must comply with all applicable requirements and
conditions specified in this report Tabulated allowable
loads are for normal duration andfor short duration, based
on load duration factors, Co, in accordance with Section
10.3.2 of the NDS, as indicated In Tables 2 through 12 of
this report. No further increases are permitted for load
durations other than those specified. Tabulated allowable
loads are for connections in wood seasoned to a maximum
moisture content of 19 percent (16 percent for engineered
wood products) or less, used under continuously dry
conditions and where sustained temperatures are limited to
100°F (37.8°C) or less. When connectors are installed in
wood having a moisture content greater than 19 percent
(16 percent for engineered wood products), or where the
ESR-1881 I Most Widely Accepted and Trusted Page 3 of 14
In-service moisture content is expected to exceed this
value, the applicable wet service factor, Ca, must be
applied. Unless otherwise noted in the tables of this report,
the applicable wet service factor, CM, is as specified in the
NDS for lateral loading of dowel -type fasteners. When
connectors are installed in wood that will experience
sustained exposure to temperatures exceeding 100°F
(37.81C), the allowable loads in this evaluation report must
be adjusted by the temperature factor, C1, specified In
Section 10.3.4 of the NDS. The group action factor, Co,
has been accounted for, in accordance with Section 10.3.6
of the NDS, in the tabulated allowable loads, where
applicable. For connectors installed with bolts, minimum
edge distances and end distances within the wood
members must be met, such that the geometry factor, C,,
is 1.0, in accordance with NDS Section 11.5.1. Connected
wood members must be checked for load -carrying capacity
at the connection in accordance with NDS Section 10.1.2.
For connectors with anchors intended to transmit loads
into concrete or masonry, adequate embedment length
and anchorage details, including edge and end distances,
must be determined by a registered design professional in
accordance with Chapter 19 or 21 of the ISC, as
applicable, for design of anchorage to concrete and
masonry structural members.
Where design load combinations include earthquake
loads or effects, the design strength of anchorage to
concrete for the PAU Post Anchor (Table 8) must be
determined In accordance with Section 1912 of the IBC,
except for detached one- and two-family dwellings
assigned to Seismic Design Category A, B or C, or located
where the mapped short -period spectral response
acceleration, Se, is less than 0.4g.
4.2 Installation:
Installation of the connectors must be in accordance with
this evaluation report and the manufacturer's published
installation instructions. Botts must be installed in
accordance with NOS Section 11.1.2.
4.3 Special Inspection:
4.3.1 IBC: Periodic special inspection is required for
installation of connectors described in this report that are
designated as components of the seismio4orce-resisting
system for structures in Seismic Design Category C, D, E
or F in accordance with IBC Section 1707.3 or 1707.4, with
the exception of those structures that qualify under the
Exceptions to Section 1704.1.
4.3.2 IRC: Special inspections are not required for
connectors used in structures regulated under the IRC.
6.0 CONDITIONS OF USE
The USP Structural Connectors described in this report
comply with, or are suitable alternatives to what is
specified in, those codes listed in Section 1.0 of this report,
subject to the following conditions:
6.1 The connectors must be manufactured, identified and
installed in accordance with this report and the
manufacturer's published installation instructions. A
copy of the manufacturer's published installation
instructions must be available at the jobsite at all
times during installation. In the event of a conflict
between this report and the manufacturer's published
installation instructions, this report governs.
5.2 Calculations showing compliance with this report must
be submitted to the code official. The calculations
must be prepared by a registered design professional
where required by the statutes of the jurisdiction in
which the project is to be constructed.
6.3 Connected wood members and fasteners must
comply with Sections 3.11.2 and 3.11.3, respectively.
6.4 Adjustment factors, noted in Section 4.1 of this report
and the applicable codes, must be considered where
applicable.
6.6 Use of connectors and fasteners with preservative -
treated or fire -retardant- treated lumber must be in
accordance with Section 3.11.4.
5.6 The design of the anchorage to, and bearing upon,
concrete or masonry construction, inclusive of cast -in -
place and post -installed anchors, used to attach the
connectors described in this report to concrete or
masonry construction, is outside of the scope of this
report.
6.0 EVIDENCE SUBMITTED
Data in accordance with the [CC -ES Acceptance Criteria
for Joist Hangers and Similar Devices (AC13), dated
October 2010.
7.0 IDENTIFICATION
Each connector described in this report is identified by the
product model (stock) number, the number of the ICC-ES
index evaluation report for United Steel Products Company
(E5R-2685), and by one or more of the following
designations: USP, or United Steel Products Company.
ESR-1881 I Most Widely Accepted and Trusted Page 4 of 14
TABLE 1—CROSS-REFERENCE OF PRODUCT NAMES WITH APPLICABLE
REPORT SECTIONS, TABLES AND FIGURES
PRODUCT NAME
SECTION
TABLE NO.
FIGURE NO.
CLPBF Butterfly Hanger
3.1
2
1
CMST Coil Strap
3.2
3
2
HCPRS Hurricane/Seismic Anchor
3.3
4
3
HUS Slant Nail Joist Hanger
3.4
5
4
JUS Slant Nail Joist Hanger
3.5
6
5
MP_F Mufti -Lateral Plate Tie
3.6
7
6
PAU Post Anchor
3.7
8
7
RSPT Stud Plate Tie
3.8
9
8
SPT and SPTH Stud Plate Ties
3.9
10
9
THDH Face Mount Hanger
3.10
11
10
TABLE 2—CLPBF BUTTERFLY HANGER ALLOWABLE LOADS''2'3'4
JOIST
DIMENSIONS
FASTENER SCHEDULE
ALLOWABL LOADS (lbs)
Header
Joist
Download
Uplift
STOCK
NO.
WIDTH
STEEL
GA.
(in.)
W
H
D
Qty
Type
Qty
Type
co=1.0
coa1.15
coa1.25
cD=1.60
CLPBF
11/2
18
19/18
2'/2
2%
12
10d Common
6
10dx 1'/2
815
815
815
215
For SI:1 inch = 25.4 mm,1 lb. = 4.45 N.
'Allowable toads have been adjusted for load duration factors, Co, as shown, in accordance with the NDS. The allowable loads do not apply to
loads of other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 4.2 for additional design and
installation requirements.
2See Section 3.11.3 for required fastener dimensions and mechanical properties.
'Allowable loads shown are for Installations In wood members complying with Section 3.11.2. Wood members must also have a reference
compression perpendicular to grain design value, FQ„ of 626 psi (4.31 MPa) or greater.
4CLPBF hangers provide torsional resistance up to a maximum joist depth of 3.5 inches (88.9 mm), where torsional resistance is defined as a
moment not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with
respect to the vertical position of the joist Is 0.125 Inch (3.2 mm).
h
'
W
D
CLPBF
`7
j
TYPICAL CLPBF
INSTALLATION
FIGURE 1--CLPBF BUTTERFLY HANGER
ESR4881 I Most Widely Accepted and Trusted Page 5 of 14
TABLE 3--CMST COIL STRAP ALLOWABLE LOADS'".4
DIMENSIONS RIM JOIST INSTALLATION FASTENER SCHEDULE ALLOWABLE
STOCK STEEL CollEndMin. Nall TENSION
NO. GAGE (in.)
Length Cut Length Length Qty. Type Spacing Ibs
feet O.C. rro s 1.6
Installed In weed with a sneclflc aravitw of 0.80 or areatar
CMST12
12
3
40
Clear Span + 74"
37"
82
16d Common
13/a-
9320
Clear Span + 168"
84"
96
10d Common
31/2.
Clear Span + 332"
166"
7"
CMST14
14
3
52'/2
Clear Span + 58"
29"
64
16d Common
13/4•
6630
Clear Span + 130"
65"
74
10d Common
3'/r
Clear Span + 256"
128"
7"
Installed In wood wan a specuic gravity tram v.4z to v.av
Clear Span + 90" 45" 102 16d Common 13/,
CMST12 12 3 40 Clear Span + 206" 103" 118 10d Common 3'/? 9320
Clear Span + 410" 205' 7"
Clear Span + 72" 36" 80 16d Common 13/4•
CMST14 14 3 52% Clear Span + 164" 82" 94 3'/r 6630
Clear Span + 326" 163" 10d Common r,
For SI: 1 inch = 25.4 mm. 1 lbf = 4.46 N.
'Allowable loads have been adjusted for a load duration factor, Co, of 1.6. corresponding to a ten-minute load duration (i.e., wind or
earthquake loading), In accordance with the NDS. The allowable loads do not apply to loads of other durations. See Sections 4.1 and 4.2 for
additional design and Installation requirements.
2See Section 3.11.3 for required fastener dimensions and mechanical properties.
'Allowable loads shown are for installations in wood members complying with Section 3.11.2 except that the CMST coil strap may be attached
to wood members having a spedflc gravity from 0.42 to 0.49, as shown.
4The minimum fastener quantity indicated is the minimum number fasteners required at each end of the connection. Products may have
additlonal holes not needed to meet the allowable tension toad of the strap.
• t. L:
i
TYPICAL CM5T RIM
CM5T J015T IN5TALLA-+10N
FIGURE 2--CMST COIL STRAP
ESR4881 I Most Widely Accepted and Trusted Page 6 of 14
TABLE 4—HCPRS HURRICANE / SEISMIC ANCHOR ALLOWABLE LOADS''2'3'4'-r'e
STOCK NO.
STEEL GAGE
FASTENER
SCHEDULE
LOAD DIRECTION
ALLOWABLE LOADS Qbs)
Co =1.6
Plate
Stud
Qty.
Type
Qty
Type
HCPRS
18
5
8d Common
6
8d Common
Uplift
540
171
500
F2
340
5
8dxl'/2
6
8dxl'/2
Uplift
540
F1
500
F2
205
For SI: 1 Inch = 25.4 mm,1 Ibf = 4.45 N.
'Allowable loads have been adjusted for a load duration factor, CD, of 1.6, corresponding to a ten-minute load duration (i.e., wind or
earthquake loading), In accordance with the NDS. The allowable loads do not apply to loads of other durations. See Sections 4.1 and 4.2 for
additional design and Installation requirements.
2See Section 3.11.3 for required fastener dimensions and mechanical properties.
'Allowable loads shown are for installations in wood members complying with Section 3.11.2.
4The F1 load direction Is for lateral loading within the plane of the wall. The F2 load direction is for lateral loading perpendicular to the plane of
the wail.
Tabulated allowable loads are for a single connector. HCPRS connectors should be installed in pairs at opposite sides of the stud to reduce
eccentricity.
6Nails into pressure -treated bottom / sill plates must have a level of corrosion resistance that is compatible with the preservative treatment.
See Section 3.11.4 of this report.
5 1 /4'
HCPR,S
i
1 11
TYPICAL HCPR5 IN5TALIATION
FIGURE 3—CMST COIL STRAP
ESR4881 I Most Widely Accepted and Trusted Page 7 of 14
TABLE 5—HUS SLANT NAIL JOIST HANGER ALLOWABLE LOADS'"'4
STOCK
NO.
STEEL
GAGE
DIMENSIONS
(in.)
FASTENER SCHEDULE
ALLOWABLE DESIGN LOADS (lbs.)
W
H
D
A
Header
.foist
Download
Uplift
Qty
Type
Qty
Type
Co = 1.0
Co m 1.15
Cp = 1.25
CD = 1.6
HUS26
16
15/8
5'/zs
3
2
14
16d Common
6
16d Common
2635
3030
3295
1925
HUS28
16
15/6
73/16
3
2
22
16d Common
8
16d Common
3970
4345
4345
2570
HUS210
16
15/0
93/16
3
2
30
16d Common
10
16d Common
5310
5510
5510
3205
HUS175
16
113/16
53/6
3
2
14
16d Common
6
16d Common
2635
3030
3295
1925
HUS177
16
113/16
7%
3
2
22
16d Common
8
16d Common
3975
4345
4345
2570
HUS179
16
113/76
91/a
3
2
30
16d Common
10
16d Common
6310
5510
5510
3205
HUS24-2
14
31/a
3'/16
2
1
4
16d Common
2
16d Common
8G0
920
1000
495
HUS26-2
14
31/a
51/4
2
1
4
16d Common
4
16d Common
1030
1185
1290
1115
HUS28-2
14
31/a
71/6
2
1
6
16d Common
6
16d Common
1660
1780
1935
1810
HUS210-2
14
31/a
91/6
2
1
8
16d Common
8
16d Common
2065
2375
2580
2210
HUS212-2
14
31/a
111/5
2
1
10
16d Common
10
16d Common
2580
2985
3225
3060
HUS2W2
14
3%
131/6
2
1
12
16d Common
12
16d Common
3095
3560
3870
3060
HUS46
14
35/6
5
2
1
4
16d Common
4
16d Common
1030
1185
1290
1115
HUS48
14
35/8
7
2
1
6
16d Common
6
16d Common
1550
1780
1935
1810
HUS410
14
35/a
87/6
2
1
8
16d Common
8
16d Common
2065
2375
2580
2210
HUS412
14
35/6
10'/6
2
1
10
16d Common
10
16d Common
2580
2965
3225
3060
For Sh 1 inch = 25.4 Trim, 1 lbf = 4A5 N.
'Allowable loads have been adjusted for load duration factors, CD, as shown, In accordance with the NDS. The allowable loads do not apply to loads of
other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 4.2 for additional design and Installation
requirements.
2Aloowable loads shown are for installations in wood members complying with Section 3.11.3. Wood members must also have a reference compression
perpendlcular to grain design value, Fcz, of 625 psi (4.31 MPa) or greater.
See Section 3.11.3 for required fastener dimensions and mechanical properties.
4HUS hangers provide torsional resistance, where torsional resistance is defined as a moment not less than 75 pounds (334 N) times the depth of the joist
at which the lateral movement of the top or bottom of the joist with respect to the vertical position of the joist Is 0.125 Inch (3.2 mm).
5.loist nails must be driven horizontally Into the joist at an angle of 30- to 45-degrees from normal, such that they penetrate through the joist, and into the
header.
- I TYPICAL MU51P
INVERTED fLANGE
HU5 TYPICAL HU5 IN57AUATION
T RU55 I N51 ALLATION
FIGURE 4—HUS SLANT NAIL JOIST HANGER
ESR4881 I Most (4rdely Accepted and Trusted
8of14
TABLE 6—JUS SLANT NAIL JOIST HANGER ALLOWABLE LOADS'"o
DIMENSIONS (in.)
FASTENER SCHEDULE
ALLOWABLE DESIGN LOADS (Ibs.)
STOCK
NO.
STEEL
GAGE
W
H
D
A
Header
Joist
Download
Uplift
Oty
Type
01Y
Type
Ca=
1.0
Cc.
1.15
Co-
1.25
Co =1.8
JUS24
18
19/16
3%
131,
1
4
10d Common
2
1od Common
655
750
820
510
JUS26
18
19/,e
4"/,s
13/4
1
4
tOd Common
4
1Od Common
850
975
1060
1115
JUS28
18
to/,s
61/0
131,
1
6
tOd Common
4
1Od Common
1076
1235
1345
1116
JUS210
18
is/,a
7'/4
04
1
8
10d Common
4
1Od Common
1305
1500
1630
1115
JUS36
18
29/,e
e1v
2
1
1 4
led Common
4
16d Common
1015
1170
1220
1355
JUS38
18
2°/,e
63/4
2
1
6
led Common
4
led Common
1290
1485
1615
1355
JUS310
18
29/16
91/e
2
1
8
16d Common
6
16d Common
1800
2070
2250
1980
JUS24-2
16
3%
37/1s
2
1
4
led Common
2
1Sd Common
780
900
966
325
JUS26-2
18
314
51/4
2
1
4
led Common
4
16d Common
1015
1170
1220
1355
JUS28-2
18
3%
7%
2
1
6
t6d Common
4
16d Common
1290
1485
1615
1355
JUS210-2
18
31/,
9%
2
1
8
l6d Common
6
16d Common
1800
2070
2250
1980
JUS214-2
1 18
31/e
13%
2
1
12
led Common
6
led Common
2345
2700
2935
1980
JUS44
16
P.
3'/4
2
1
4
18d Common
2
16d Common
780
900
965
325
JUS46
18
3s/e
5
2
1
4
18d Common
4
led Common
1015
1170
1220
1355
JUS48
18
31/e
el,
2
1
6
1Sd Common
4
16d Common
1290
1485
1616
1365
JUS410
18
3%
8710
2
1
8
16d Common
8
16d Common
1800
2070
2250
1980
JUS414
18
3%
12%
2
1
12
16d Common
6
16d Common
2345
2700
2935
1980
JUS26.3
16
46/8
4%
2
1
4
16d Common
4
16d Common
1015
1170
1220
1355
JUS28-3
18
46/9
6%
2
1
6
18d Common
4
16d Common
1290
1485
1616
1365
JUS210-3
1 18
4°/a
83/8
2
1
8
16d Common
8
16d Common
1800
2070
2250
1980
For SI: 1 Inch = 25.4 mm, 1 Ibf = 4.45 N.
'Allowable loads have been adjusted for load duration factors, CO, as shown, in accordance with the NDS. The allowable loads do not apply to loads of
other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 4.2 for additional design and installation
requirements.
'Allowable loads shown are for installations in wood members complying with Section 3.11.2. Wood members must also have a reference compression
perpendicular to grain design value, Fa, of 625 psi (4.31 MPa) or greater.
See Section 3.11.3 for required fastener dimensions and mechanical properties.
4JUS hangers provide torsional resistance, up to a mapmum joist depth of H + 1 inch (H + 25.4 mm) where torsional resistance is defined as a moment
not less than 75 pounds (334 N) fimes the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the vertical
position of the joist is 0.125 Inch (3.2 mm).
Joist nails must be driven horizontally into the joist at an angle of 30- to 45-degrees from normal, such that they penetrate through the joist, and Into
the header.
TYPICAL JU5
IN5TALLATION
FIGURE 5—JUS SLANT NAIL JOIST HANGER
ESR4881 I Most Widely Accepted and Trusted Page 8 of 14
TABL 7—MP_F MULTI -LATERAL PLATE TIE ALLOWABLE LOADS'"'b
STOCK
NO.
STEEL
GAGE
DIMENSIONS
indtes
INSTALL.
CONFiG.
FASTENERS
DIR.
LOAD
ALLOWABLE LOADS (lbs.)
HeadeHStud
Joistiplaia
W
L
QWT
T pe
Qy TM
C° c
1.0
C° >r
1.15
C° s
1.26
ICD7
Installed In wood with
a specific gravity
of
0.50 or greater
MP4F
20
3
4'/4
Type 1
6
8d x 1'/2
8
8d x 1'/2
V
565
660
705
845
H
565
650
705
845
Type 2
6
8d x 02
6
8d x 1'12
V
565
650
705
1 845
H
565
650
660
660
Type 1
6
8d Common
6
8d Common
V
565
650
705
845
H
565
650
1 705
845
Type 2
6
8d Common
6
8d Common
V
565
650
1 705
845
H
565
650
660
660
MPBF
20
33/4
4'/4
Type 1
6
8d x 1'/2
6
8d x 1'/2
V
565
605
605
605
H
565
605
605
605
Type 2
6
8d x 1'/2
6
8d x 02
V
565
605
605
605
H
565
605
605
605
Type 1
6
8d Common
8
8d Common
V
585
605
605
605
H
565
605
605
605
Type 2
6
8d Common
6
8d Common
V
565
605
605
605
H
565
W5
605
1 605
Installed In wood with
a specific gravity
from 0.42 to 0.49
MP4F
20
3
4'/4
Type 1
6
8d x 11/2
6
ed x 11/2
V
485
560
610
710
H
485
560
610
710
Type 2
6
8d x 1'/2
6
8d x 02
V
485
560
610
710
H
485
555
565
555
Type 1
6
8d Common
6
8d Common
V
485
560
610
710
H
485
560
610
710
Type 2
6
8d Common
6
8d Common
V
485
555
610
710
H
485
555
555
555
MP6F
20
33/4
4'/4
Type 1
6
8d x 1'/2
6
8d x 1'/2
V
485
510
510
510
H
485
510
510
510
Type 2
6
8d x 1'/2
6
8d x 02
V
485
510
510
510
H
485
610
610
510
Type 1
6
8d Common
6
8d Common
V
485
510
510
510
H
485
510
510
510
Type 2
6
8d Common
6
8d Common
V
485
510
10
510
H
485
510
6
510
510
For 81:1 Inch
= 25.4 mm. 1 ibf = 4.45
N.
'Allowable loads have been adjusted for load duration factors, CD, as shown, In accordance with the NDS. The allowable loads do not apply
to loads of other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 42 for additional design and
Installation requirements.
2Aloowable toads shown are for installations in wood members complying with Section 3.11.2.
3See Section 3.11.3 for required fastener dimensions and mechanical properties.
4See Figure 6 for depiction of Installation configurations.
6For direction of load: 'V' Indlcates a vertical (uplift) load; 'H' indicates a horizontal (shear) load within the plane of the MP F plate.
6The MP F may be Installed over wood -based structural sheathing (as shown In Figure 6) having a maximum thickness of 1/2 Inch (12.7 mm)
without adversely affecting the tabulated allowable loads
TO
� I v
MP F ;
Type 2
...I 1: ,
TYN CAL Mr F
INSTALLATION
FIGURE 6--MP_F MULTI -LATERAL PLATE TIE
ESR-1881 I Most Widely Accepted and Trusted Page 10 of 14
8. TABLE 8—PAU POST ANCHOW 134 M
STOCK
NO.
STEEL
GAGE
Dimensions (in.)
FASTENER
SCHEDULE
ALLOWABLE LOADS ([be)
Base
Stand-
Off
Plate
Washer
Nails
Bolts
Anchor
Bolts
Bearing
Uplift
W
H
L
Nails Bolts
My
Type
Qty
Sine
Qty
SI2e
100%
Co =1.6
Co =1.6
PAU44
12
16
10
39/1e
57/18
3
12
16d Common
2
1/2
1
5/8
6775
2535
2265
PAU46
10
12
10
39/1e
6
5
12
16d Common
2
1/2
1
'/B
13815
2535
2265
PAU66
10
12
10
51/2
6
5
12
16d Common
2
112
1
5/8
16005
2380
2265
PAU88
12
12
3
7%
73/18
7'/1e
14
16d Common
—
—
2
5/8
24900
3185
—
PAU88R
1 12
12
3
8'/1e
6'S/1e
7'/Se
1 14
16d Common
I —
I —
1 2
1 5/8
24900
3185
—
For Si:1 Inch = 25.4 mm,1 Ibf = 4.45 N.
'Allowable loads have been adjusted for load duration factors. CD, as shown, In accordance with the NDS. The allowable loads do not apply to loads of
other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 42 for additional design and Installation requirements.
2See Section 3.11.3 for required fastener dimensions and mechanical properties.
AAloowable loads shown are for installations In wood members complying with Section 3.11.2. Values apply only to parallelAo-grain loading of wood
members.
4Aloowable loads shown do not apply to the anchorage to concrete or masonry. Anchorage to concrete or masonry must be designed by a registered
design professional in accordance with Section 4.1 of this report.
'The PAU Post Anchor has no moment or lateral capacity and should not be used In fixed post applications.
BAloowable nail loads and bolt loads are not permitted to be added together.
tt
2 3/4
PAU
TYPICAL PAU
INSTALLATION
FIGURE 7—PAU POST ANCHOR
ESR-1881 I Most Widely Acoepted and Trusted Page 11 of 14
TABLE 9—RSPT STUD PLATE TIE ALLOWABLE LOADS'"r4's'8
STOCK
NO.
STEEL
GAGE
DIMENSIONS (in.)
FASTENER
SCHDULE
ALLOWABLE
LOADS (lbs)
Stud
Plate
Uplift
Lateral F,
Lateral F2
W
H
City
Type
Qty
Type
Co a 1.6
Co a 1.6
Co a 1.6
RSPT4
20
1'/2
41/8
4
8d x 1'/2
4
8d x 1'/2
470
230
3W
RSPT6
18
1'/2
57/18
4
10d x 1'/2
RE[
10d x 1'/2
700
—
--
RSPT6-2
18
23/4
57/18
8
10d x 1'/2
10d x 1'/2
955
—
—
For SI: 1 inch = 25.4 mm,1 lbf = 4.45 N.
'Allowable loads have been adjusted for a load duration factor, CD, of 1.6, corresponding to a ten-minute load duration (i.e., wind or
earthquake loading), In accordance with the NDS. The allowable loads do not apply to loads of other durations. See Sections 4.1 and 4.2 for
additional design and Installation requirements.
2See Section 3.11.3 for required fastener dimensions and mechanical properties.
3A towable toads shown are for Installations in wood members complying with Section 3.11.2.
4The 'Lateral F1' load direction Is for lateral loading within the plane of the wall. The 'Lateral F2' load direction Is for lateral loading
perpendicular to the plane of the wall.
'Tabulated allowable loads are for a single connector. RSPT connectors should be Installed In pairs at opposite sides of the stud to reduce
eccentricity.
BNalls into pressure -treated bottom / sill plates must have a level of corrosion resistance that is compatible with the preservative treatment.
See Section 3.11.4 of this report.
h n
n
� - 1
kv
R5PT4
RSPTG-2
• R5PTG
TYPICAL R5PT 51NGLE TYPICAL R.5PT DOU13LE
PLATE INSTALLATION PLATE IN5TALLATION
FIGURE 8—RSPT STUD PLATE TIE
ESR4881 I Most Widely Accepted and Trusted Page 12 of 14
TABLE 10--SPT AND SPTH STUD PLATE TIE ALLOWABLE LOADS'"
STOCK NO.
CTAGE
DIMENSIONS
(In.)
FASTENER SCHEDULE
ALLOWABLE UPLIFT LOADS
W
E67/81
Qty
Type
CD =1.6
SPT4
20
39/16
66
10d x 1'/2
945
SPT6
20
59/16
75/6
6
10d x 1'/2
945
SPT8
20
75/16
8'/2
6
1 Od x 02
945
SPTH4
18
39/16
85/6
12
10d x 1'/2
1730
SPTH6
18
59/16
93/6
12
10d x 02
1730
SPTH8
18
75/16
8'/2
12
10d x 02
1730
SPTHW4
18
4'/,e
83/6
12
10d x 1'/2
1290
SPTHIN6
18
61/16
91/8
12
10d x 1'/2
1290
For SI: 1 Inch = 25.4 mm, 1 Ibf = 4.46 N.
'Allowable loads have been adjusted for a load duration factor, CD, of 1.6, corresponding to a ten-minute load duration (i.e., wind or
earthquake loading), in accordance with the NDS. The allowable loads do not apply to loads of other durations. See Sections 4.1 and 4.2
additional design and installation requirements.
2See Section 3.11.3 for required fastener dimensions and mechanical properties.
3Aloowable loads shown are for installations In wood members complying with Section 3.11.2. Wood sill plates must also have a reference
compression perpendicular to grain design value, Fcz, of 625 psi (4.31 MPa) or greater.
e , W
114
;s�� s�u1uW SPTn 5PrHW
TYPICAL 5PT
IN5TALLATION
t511w, st-rn, s 91-MW SWI Aw
FIGURE 9—SPT AND SPTH STUD PLATE TIES
ESR4881 I Most Widely Accepted and Trusted Page 13 of 14
TABLE 11 THON FACE MOUNT HANGER ALLOWABLE LOADS"4
TOOK NO.
STEEL
GAGE
DIMENSIONS (in.)
FASTENER SCHEDULE
ALLOWABLE DESIGN LOADS IN
DOUGLAS+1R LARCH (Ibs.)
ALLOWABLE DESIGN LOADS IN
SPRUCE -PINE -FIR (tbs.)
W
H
0
Header
Joist
Download
Upin
Download
Uplift
ay
Type
OLY
Type
Coa1.0
Coa1.15Coa1.25
Coa1.6
C6a1.0
Coa1.15Coa12A
Coa1.6
TKDH26
12
15/8
5'/,e
5
20
16d Common
8
16d Common
3915
4505
4895
2340
3370
3880
4200
1965
TKDH28
12
1e/e
73/1e
5
36
16d Common
12
16d Common
6770
7395
7395
4370
5830
6210
6210
3670
THDH210
12
15/e
98/18
5
46
16d Common
16
16d Common
8725
9580
9600
5400
6835
7385
7750
4535
THDH27926
12
el.
9'/a
4
46
16d Common
12
16d Common
8260
8260
8260
3490
6935
6935
6835
2930
TKDH27112
12
2'/4
10'/e
4
56
16d Common
14
16d Common
9W5
9845
9845
5225
7655
8135
8270
4390
THDH2714
12
23/4
12'/4
4
66
led Common
16
16d Common
9845
9845
9845
6810
8110
8270
8270
5835
THDH26.2
12
3'/16
5'le
4
20
16d Common
8
16d Common
3916
4605
1 4795
2235
3370
3880
4030
1880
THDH28-2
12
371Se
7'18
4
36
16d Common
10
16d Common
6535
7515
8025
2665
5635
8480
6740
2240
THDH210-2
12
e1,e
W18
4
46
16d Common
12
16d Common
8260
8260
8260
3490
6935
6935
6935
2930
THDH3210
12
33/S8
931e
4
46
16d Common
12
led Common
8260
8260
8260
3490
6935
6935
6935
2930
THDH3212
12
33/1e
105/8
4
56
16d Common
14
16d Common
8845
9845
9846
5960
8270
8270
8270
5105
THDH46
12
3°1Se
5318
4
20
16d Common
8
16d Common
3915
4505
4895
2605
3370
3860
4216
2190
THDH48
12
3 1a
7'/e
4
36
led Common
10
16d Common
6535
7515
7835
3185
5635
6480
6580
2675
THDH410
12
3°/1e
91/e
4
46
16d Common
12
16d Common
8260
9010
9010
3970
7120
7570
7570
3335
THDH412
12
3°/18
10'12
4
56
16d Common
14
16d Common
9846
9845
9845
5226
8270
8270
8270
4390
THDH414
12
30/1e
13'/18
4
66
16d Common
16
16d Common
9845
9845
9845
6810
8270
8270
8270
5835
THDH26-3
12
5'/e
571,8
4
20
16d Common
8
16d Common
3916
4505
4795
2235
3370
3880
4030
1880
THDH28-3
12
5'le
73l,e
4
36
16d Common
12
16d Common
6770
7785
8025
2686
5830
6705
6740
2240
THDH210-3
12
5'/8
9'/,e
4
46
16d Common
16
16d Common
8725
9855
9855
4565
7520
8275
8275
3836
THDH212 3
12
51/8
113/Se
4
56
16d Common
20
16d Common
9935
9935
9935
5180
8345
8345
8345
4355
THDH214-3
12
5118
133/,e
4
66
16d Common
22
16d Common
11646
11646
11646
5795
9780
9780
9780
4886
THDH610
12
5%
9
4
46
16d Common
16
16d Common
8725
9855
980
4665
7520
8275
8275
3836
THDH612
12
51/2
11
4
56
16d Common
20
16d Common
9936
9936
9935
5180
am
8346
8345
4356
THDH614
12
5'/2
13
4
66
16d Common
22
16d Common
11645
11645
11645
5795
9780
9780
9780
4865
THDH6710
12
6'/e
8'3/,e
4
46
led Common
12
16d Common
8260
8280
8280
3490
6935
6935
6935
2930
THDH6712
12
6718
1013/18
4
56
16d Common
14
16d Common
9845
9845
9845
5225
8270
8270
8270
4390
THDHO714
12
ele
12"118
4
66
led Common
16
16d Common
9845
9845
8845
6810
8270
8270
8270
5835
THDH7210
12
7114
9
4
46
16d Common
12
16d Common
8280
9010
9010
3970
7120
7570
7570
3336
THDH7212
12
71/4
10'12
4
56
16d Common
14
16d Common
9545
9845
9845
5225
8270
8270
8270
4390
TKDH7214
12
71/4
1214
4
68
16d Common
16
18d Common
9845
9845
1 9845
6810
8270
8270
8270
6835
For SI:1 Inch = 25.4 mm,1 IV = 4A5 N.
'Allowable loads have been adjusted for load duration factors, CD, as shown, In accordance with the NDS. The allowable loads do not apply to loads
of other durations, and are not permitted to be adjusted for other load durations. See Sections 4.1 and 4.2 for additional design and Installation
requirements.
'Allowable loads shown are for installations in wood members complying with Section 3.11.2.
3See Section 3.11.3 for required fastener dimensions and mechanical properties.
4THDH hangers provide torsional resistance, up to a maximum joist depth of H + 1 inch (H + 25.4 mm) where torsional resistance is defined as a
moment not less than 75 pounds (334 N) times the depth of the joist at which the lateral movement of the top or bottom of the joist with respect to the
vertical position of the joist Is 0.125 inch
J3.2 mm).
Joist nails must be driven horizontally Into the joist at an angle of 30- to 45-degrees from normal, such that they penetrate through the joist, and Into
the header.
°Allowable design loads given for Installation with Douglas fir -Larch members are based on an assumed specific gravity of 0.50 for the purpose of
fastener design, and an assumed reference compression perpendicular to grain design value, Fcz, of 625 psi (4.31 MPa).
'Allowable design loads given for Installations with Spruce -Pine -Fir members are based on an assumed specific gravity of 0.42 for the purpose of
fastener design, and an assumed reference compression perpendicular to grain design value, Fcz, of 425 psi (2.93 Mpa).
ESR4881 ( Most Widely Accepted and Trusted Page 14 of 14
'I H
W D
TYPICAL THDH
THDH INSTALLATION
FIGURE 10—THDH FACE MOUNT HANGER
TABLE 12—STEEL TYPE, STRENGTH AND CORROSION RESISTANCE
Product
Steel
Coating
CLPBF Butterfly Hanger
ASTM A 653, SS designation, Grade 33
G90'
CMST Coil Strap
ASTM A 653, SS designation, Grade 50, Class 1
G90'
HCPRS Hurdcane/Selsmic Anchor
ASTM A 653, SS designation, Grade 33
G901
HUS Slant Nall Joist Hanger
ASTM A 653, SS designation, Grade 33
G90', G185'
JUS Slant Nall Joist Hanger
ASTM A 653, SS designation, Grade 33
G901, G185'
MP F Muni -Lateral Plate Tie
ASTM A 653, SS designation, Grade 33
G901, G185'
PAU Post Anchor
Nos. 10,12,16 Ga. Material: ASTM A 653, SS designation, Grade 33
Nos. 3,10 Ga. material: ASMT A 36
G90% G185'
Painted
RSPT Stud Plate tie
ASTM A 653, SS designation, Grade 33
G90', G185'
SPT and SPTH Stud Plate Ties
ASTM A 653, SS designation, Grade 33
G90', G18W
THDH Face Mount Hanger
ASTM A 653, SS designation, Grade 33
G90', G185'
For Sh 1 Ibf/in2 = 6.89 kPa.
'Corrosion protection Is a zinc coating in accordance with ASTM A 653.