FW-12-20-2890, 800 NE 96th StMiami Shores Village
10050 NE 2 Ave
Miami Shores FL 33138
305-795-2204
Location Address
800 NE 96TH ST, Miami Shores, FL 33138
Parcel Number
1132060142920
Contacts
Guy Grady Owner HOME OWNER Contractor
570 103 HOME OWNER
Mobile: 7869850425 gvare0l.@Iive.com.
Ins Description: FENCING OF EAST & WEST SIDES OF BACK YARD Valuation: $ 5,000.00 ectton Requests:
FROM REAR MASONARY WALL TO THE SIDES OF THE HOUSE
WITH 6' HIGH METAL FENCE Total Sq Feet: 0.00
Fees
Amount
Application Fee - Other
$50.00
CCF
$3.00
DBPR Fee
$2.25
DCA Fee
$2.00
Education Surcharge
$1.00
Planning and Zoning Review Fee
$35.00
Scanning Fee
$9.00
Technology Fee
$3.75
Wire and Wood Fence Fee
$100.00
Total:
$206.00
Payments
Date Paid Amt Paid
Total Fees
$206.00
Credit Card
01/20/2021 $156.00
Credit Card
12/16/2020 $50.00
Amount Due:
$0.00
Building Department Copy
In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations
pertaining thereto and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores
Village. In accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate
permits are required for ELECTRICAL, PLUMBING, MECHANICAL, WINDOWS, DOORS, ROOFING and SWIMMING POOL work.
OWNER.. r'AFFIDAVIT: I certify that all the forgoing information is accurate and that all work will be done in compliance with all applicable laws
regulating cpnstruction aAd nnir;d)Futherm�e,,f authorize the above named contractor to do the work stated.
/ Applicant / Contractor / Agent
January 20, 2021
Date
Page 2 of 2
Miami Shores Village
10050 NE 2 Ave
Miami Shores FL 33138
305-795-2204
Location Address Parcel Number
800 NE 96TH ST, Miami Shores, FL 33138 1132060142920
Contacts
Guy Grady Owner HOME OWNER Contractor
570 103 HOME OWNER
Mobile: 7869850425 gvare0l@live.com
Ins section Requests:
Description: FENCING OF EAST & WEST SIDES OF BACK YARD Valuation: $ 5,000.00
FROM REAR MASONARY WALL TO THE SIDES OF THE HOUSE ;�
WITH 6' HIGH METAL FENCE Total 5q Feet: 0.00 '
Fees
Amount
Application Fee - Other
$50.00
CCF
$3.00
DBPR Fee
$2.25
DCA Fee
$2.00
Education Surcharge
$1.00
Planning and Zoning Review Fee
$35.00
Scanning Fee
$9.00
Technology Fee
$3.75
Wire and Wood Fence Fee
$100.00
Total:
$206.00
Applicant Copy
Payments
Date Paid Amt Paid
Total Fees
$206.00
Credit Card
01/20/2021 $156.00
Credit Card
12/16/2020 $50.00
Amount Due:
$0.00
For Inspections, Call (305) 762-4949 or Log on at https://bldg.miamishoresvillage.com/cap/.
Requests must be received by 3pm for following day inspections.
NOTICE: In addition to the requirements of this permit, there may be AND THERE MAY BE ADDITIONAL PERMITS REQUIRED FROM OTHER
additional restrictions applicable to this property that may be found in the GOVERNMENTAL ENTITIES SUCH AS WATER MANAGEMENT DISTRICTS,
public records of this county. STATE AGENCIES, OR FEDERAL AGENCIES.
January 20, 2021 Page 1 of 2
Miami Shores Village RECEIVED
BUILDING
PERMIT APPLICATION
BUILDING ❑ ELECTRIC
Building Department rE 6 2020
10050 N.E.2nd Avenue, Miami Shores, Florida 33138
BY:
Tel: (305) 795-2204 Fax: (305) 756-8972
INSPECTION LINE PHONE NUMBER: (305) 762-4949
FBC 20 VT �-
Master Permit No. �:-w" 12---2D" D
Sub Permit No.
❑ ROOFING ❑ REVISION ❑ EXTENSION ❑RENEWAL
❑PLUMBING ❑ MECHANICAL ❑PUBLIC WORKS ❑ CHANGE OF ❑ CANCELLATION ❑ SHOP
CONTRACTOR DRAWINGS
JOB ADDRESS: 0 L77' yl„T4 *Z4
City: Miami Shores County: Miami Dade zip..-3� 0
Folio/Parcel#: '-3Z A-42 Is the Building Historically Designated: Yes NO X
Occupancy Type: o Construction Type: Flood Zone: BFE: FFE:
` 7 5` 71,E
OWNER: Name ( ee Simp) Titleholder): rPhone#:
Address:
City: State: Zip:
Tenant/Lessee Name: Phone#:
Email: G�
CONTRACTOR: Company Name: Phone#:
Address:
City: State: Zip:
Qualifier Name: Phone#:
State Certification or Registration #: Certificate of Competency #:
DESIGNER: Architect/Engineer: Phone#:
Address: City: State: Zip:
Value of Work for this Permit: $ SCDO Square/Linear Footage of Work: !Ss
Type of Work: ❑ Addition ❑ Alteration /� El New ❑jfRepair/Replace ❑ Demolition
Description of Work:_
Specify color of color thru
Submittal Fee $_
Scanning Fee $ _
Technology Fee $_
Structural Reviews
Permit Fee $
Radon Fee $
_ Training/Education Fee $
CCF $
DBPR $
CCljCC $ .
Notary $
Double Fee $ _
Bond $
TOTAL FEE NOW DUE $
! � ' oc�
(Revised02/24/2014)
Bonding Company's Name (if applicable)
Bonding Company's Address
City
State
Mortgage Lender's Name (if applicable)
Mortgage Lender's Address
City
State
Uri
Zip
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS,
FURNACES, BOILERS, HEATERS, TANKS, AIR CONDITIONERS, ETC.....
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING
YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved and a reinspection fee will be charged.
Signature Signature
WNER or AGENT OF CONTRACTOR
The foregoing instrument was acknowledged before me this
f day of -eMIOC �- 20�_, by
G') rQ who is personally known to
me or who has produced as
identification and who did take an oath.
NOTARY PUBLIC:
Sign:
Print:
Seal:--
SELENA ARANDA
MY COMMISSION # GO 971705
EXPIRES: March 22, 2024
APPROVED BY
The foregoing instrument was acknowledged before me this
day of
me or who has produced
20 , by
who is personally known to
identification and who did take an oath.
NOTARY PUBLIC:
Sign:
Print:
Seal:
as
****************************************************************
Plans Examiner (� Zoning
(Revised02/24/2014)
Structural Review
Clerk
O : C
NAME:
ADDRESS: u (Jv
Miami Shores Village
Building Department
10050 N.E.2nd Avenue
Miami Shores, Florida 33138
Tel: (305) 795.2204
Fax: (305) 756.8972
Do hereby petition the Village of Miami Shores to act as my own contractor pursuant to the laws of the State of Florida, F.5 489.103(7). And I have
read and understood the following disclosure statement, which entitles me to work as my own contractor; I further understand that I as the owner
must appear in person to complete all applications.
State Law requires construction to be done by a licensed contractor. You have applied for a permit under an exception to the law. The exemption
allows you, as the owner of your property, to act as your own contractor even though you do not have a license. You must supervise the
construction yourself. You may build or improve a one -family or two-family residence. You may also build or improve a commercial building at a
cost of $25,000.00 or less (The new form states 75,000). The building must be for your own use and occupancy. It may not be built for sale or
lease. If you sell or lease a building you have built yourself within one year after the construction is complete, the law will presume that you built
for sale or lease, which is a violation of this exemption. You may not hire an unlicensed person as a contractor. It is your responsibility to make
sure the people employed by you have licenses required by state law and by county or municipal licensing ordinances. Any person working on
your building who is not licensed must work under your supervision and must be employed by you, which means that you must deduct F.I.C.A and
with -holdings tax and provide workers' compensation for that employee, all as prescribed by law. Your construction must comply with all
applicable laws, ordinances, buildings codes and zoning regulations.
Please read and initial each paragraph.
1. 1 understand that state law requires construction to be done by a licensed contractor and have applied for an owner -builder permit under an
exemption from the law. The exemption specifies that I, as the owner of the property listed, may act s my own contractor with certain
restrictions even though I do not have a license.
Initial
2. 1 understand that building permits are not required to be signed by a property owner unless he or she is responsible for the construction and
is not hiring a licensed contractor to assume responsibility.
Initial / ✓� e
3. 1 understand that, as an owner builder, I am the responsible party of record on a permit. I understand that I may protect myself from potential
financial risk by hiring a licensed contractor and having the permit filed in his or her name instead of y own name. I also understand that the
contractor is required by law to be licensed in Florida and to list his or license numbers on permits cont �a�J
Initial ✓ ,
4. 1 understand that I may build or improve a one family or two-family residence or a farm outbuilding. I may also build or improve a commercial
building if the costs do not exceed $75,000. The building or residence must be for my use or occupancy. It may not be built or substantially
improved for sale or lease. If a building or residence that I have built or substantially improved myself is sold or leased within 1 year after the
construction is complete, the law will presume that I built or substantially improved it for sale or le , which violates the exemption.
Initial
5. I understand that, as the owner -builder, I must provide direct, onsite supervision of the constructs
Initial
6. I understand that I may not hire an unlicensed person to act as my contractor or to supervise persons working on my building or residence. It
is my responsibility to ensure that the persons whom I employ have the license required by law and coun o�r�municipal ordinance.
Initial
I understand that it is frequent practices of unlicensed persons to have the property owner obtain an owner -builder permit that erroneously
implies that the property owner is providing his or her own labor and materials. 1, as an owner -builder, may be held liable and subjected to
serious financial risk for any injuries sustained by an unlicensed person or his or employees while working on my property. My homeowner's
insurance may not provide coverage for those injuries. I am willfully acting as an owner -builder am aware of the limits of my insurance
A
coverage for injuries to workers on my property. l ,
Initial_ /lti(/U�
8. 1 understand that I may not delegate the responsibility for supervising work to be a licensed contractor who is not licenses to perform the
work being done. Any person working on my building who is not licensed must work under my direct supervision and must be employed by
me, which means that I must comply with laws requiring the withholding of federal income tax and social security contributions under the
Federal Insurance Contributions Act (FICA) and must provide workers compensation for the employe I understand that my failure to follow
these may subject to serious financial risk.
Initial t
9. 1 agree that, as the party legally and financially responsible for this proposed Construction activity, I will abide by all applicable laws and
requirement that govern owner -builders as well as employers. I also understand that the
Construction must comply with all applicable laws, ordinances, building codes, and zoning regulatio
Initial
&l#
10. 1 understand that I may obtain more information regarding my obligations as an employer from the Internal Revenue Service, the United States
Small Business Administration, and the Florida Department of Revenues. I also understand that I may contact the Florida Construction Industry
Licensing Board at 850.487.1395 or http:/Iwww.mvfloridalicense.com/dbpr/pro/cilb/index.htmi
i�ff-
Initial
11. 1 am aware of, and consent to; an owner -builder building permit applied for in my name and understands that I am the party
legally and financially responsible for the proposed construction activity at the following address:
-(- d
;JILT 4�,
Initial
12. I agree to notify Miami Shores Village immediately of any additions, deletions, or changes to any of th nfo atiop at I have provided on
this disclosure. 7
Initial
Licensed contractors are regulated by laws designed to protect the public. If you contract with a person who does not have a license, the
Constr4uction Industry Licensing Board and Department of Business and Professional Regulation may be unable to assist you with any financial
loss that you sustain as a result of contractor may be in civil court. It is also important for you to understand that, if an unlicensed contractor or
employee of an individual or firm is injured while working on your property, you may be held liable for damages. If you obtain an owner -builder
permit and wish to hire a licensed contractor, you will be responsible for verifying whether the contractor is properly licensed and the status of
the contractor's workers compensation coverage.
Before a building permit can be issued, this disclosure statement must be completed and signed by the property owner and returned to the local
permitting agency responsible for issuing the permit. A copy of the property owner's driver license, the notarized signature of the property
owner, or other type of verification acceptable to the local permitting agency is required when the permit is issued.
Was acknowledged before me this day of D�Kx__ qo Q-0
By �� C-1�Cl who was personally known to me or who has
Produced there License or -�-L `.J L_ as identification.
s
OWNER
N OTAR
SELENA ARANDA
MY COMMISSION # GG 971705
EXPIRES: March 22, 2024
Bonded Thru Notary Public Underwriters
FND.I.R.01/2"
-',,COL. 0
CL
(NO ID.)
(1.4'x1.4')
IQ
CL.
CY)
(D
0
'r-
CL
LLJ
C-)
12.3
CONC.
SLAB.
7
6' WOV
P
OF BOUNDARY SURVEY
—ALLEY—
(i5' TOTAL R
/W)'
9' ASPHALT PAVEMENT FNb.I.R.01, Z
00 00
UL OULNO I D.,
lb
lTC.B.S. 301 j
775' 7. i
WALL
FOUNTgl
(0
Q,
/V
G(11-
in UPD , , � Id,3,,y,
e t.
SOD
hS6�I
Cy C �D.r's Of I ck::
a <
Q, ii0ri" CL
IS
61110 :4
70
41'
I C)f-. the of-
9
F. CE
•
0 4 r�, 0 0 C14
A3.9'
5.8'7
A/C
SIBS
(0
FIND.I.P.01/2"
(NO ID.)
5' SIDEWALK
O
Ld
<
+ 0 0
<
lb- lb- T: 'lli..j F—
Q._
0<
1=
it 9.7�b 0
Lj zoo C,4
12.0'
WA K
g.
�bcol 13
14.
onn
FND.I.P.01/2" 1'�b�o
+
(NO ID. 1 30'
ENTRY
FND.I.P.01/2"
(NO ID. %
--'7-R/W A00.570r
7' PARKWAY ---\., =39.27'u
R=25.00'
SOD
2.5'
cq
r-
C14
Ol A/C
j-d y 1 K_17
S
�p
2' CURB "9' 0!00'00!!'_'
CD
CD
22', ASPHALT PAVEMENT,
GU
'96th STREET
±71
%
(80',-TOTAL R/W)
'91
• P.
�a
..... .....
MEDIAN GRASS
7 -7
This
Survey
Map and Report are not full and complete
"Irl-L VVI I H Al-r--MDnr AL --
without the other.
A
Arc
ABBREVIATIONS & LEGEND
Yhain ,
Pg.
Page
------ �X Link Fence
FND
Found
R/W
ig Unknown Manhole
Right —of —Way
q, Fire Hydrant
Wood Fence
U. E.
Utility Easement
Center Line Q Sewer Manhole
E: Electric Box
Metal or plastic
IP
Iron Pipe
Monument Line Telephone Manhole
C9
Light Pole
Fence
IR
Iron Rebar
TBM
Temporary WM
Benchmark 0 Water Meter
#ILP
c0t.) Utility Pole
OUL —Overhead
Utility line
N&D
Nail & Disc
COL.
Column
PWY
W/P
Parkway wv Water Valve
Water Pump X
CLP Concrete Light
0
O
Pole + Spot Elevation
P. B.
PLat Book
ENC
Encroachment M Catch basin
* Property Corner
FormTech Job # 20-11040
Scc/e: I" = 20' Date: 11-16-2020
Land Surveying, Inc.
State of Florida LB # 7980
12209 S.W. 129th Court, Miami, Florida, 33186 0' 10' 20' 40'
Ph: (786)429-3034 (786)443-0285 (786)443-0678 GRAPHIC SCALE
www.formtechsurveyors.com email:intogformtechsurveyors.com Page 2 of 2
MAP OF BOUNDARY SURVEY
la
Property address:
800 N.E. 96th Street
City: Miami Shores
County: Miami -Dade
State: Florida Zip Code: 33138
Folio # 11-3206-014-2920
SUBJECT PROPERTY
SURVEYOR'S REPORT:
N.E. 96th STREET
1( i
8 7
s
G
LOCATION SKETCH
NOT TO SCALE
1. MAP OF BOUNDARY SURVEY, Fieldwork date of data acquisition: November 16th, 2020.
2. LEGAL DESCRIPTION:
Al
Lots 9 and 10, Block 75, of MIAMI SHORES SECTION THREE, according to the Plat thereof, as recorded in Plat Book
10, at Page 37, of the Public Records of Miami —Dade County, Florida.
3. AREA: • • • •
.... ..
Containing 14,'I'16 $quare'Fee? or 0.32 Acres more or less by calculations.
...... . .. . .
4. 4CCURACY:'
...... . .. .. ..
. .
........ ......
The.4:uracy obtained to •.Teasurement and calculations of a closed geometric figure was found to exceed this
requirepnent.%i112t3= 1 fdb�t•lrl•7,500 feet.
• 0 0 0 • .
b..D,ATA OF S"JRQES:..;...
.. . ..
1-411ILOfVTAL CQ4T� : • •
—The Legal Description was furnished by client.
—North Arrow as per Plat Book 10, at Page 37 of the Public Records of Miami —Dade County, Florida.
VERTICAL CONTROL:
Elevations are referred to N.G.V.D. 1929.
Benchmark used: Miami —Dade County Benchmark No. N-800 Elevation=9.34' (N.G.V.D. 1929)
located @ NE 96th Street and U.S Hwy # 1.
6. FLOOD INFORMATION:
By scale determination this property is located in Flood Zone X and 0.2 PCT Annual Chance Flood Hazard, as per Federal
Emergency Management Agency (FEMA), NFIP Community Name: Village of Miami Shores and Community Number 120652
Map/Panel Number 12086C0306, Suffix L, FIRM Panel Effective/Revised Date 09-11-2009.
7. LIMITATIONS:
No research was made for other instruments than the existing in the plat and provided by client.
No determination was made as to how the site can be served with utilities.
Fences and walls ownership by visual means only; legal ownership not determined.
No underground utilities and/or structures(foundations) was located within or abutting the Subject property.
CERTIFY TO:
GUY E. OGRADY
SURVEYOR'S CERTIFICATION:
I certify: This Map of Boundary Survey meets all applicable requirements of the Florida Minimum Technical
Standards as contained Chapter 5J-17. Unless indicated to the contrary, the measured distance and directions
shown on the Map of Boundary Survey are the same as the deed distances and directions.
Not valid without the signature and the original raised seal of Florida Licensed Surveyor and Mapper. Additions or
deletions to Map of Boundary Survey by other than signing party or parties is prohibited without written consent
of the signing party or parties. This Survey Map and Report are not full and complete without the other.
FormTech
Land Surveying, Inc.
State of Florida LB # 7980
12209 S.W. 129th Court, Miami, Florida, 33186
Ph:(786)429-3034 (786)443-0285 (786)443-0678
www.formtechsurveyors.com email:info@formtechsurveyors.com
Seal:
Job # 20-11040
11-16-2020
Date: _
E enia L. Formoso, P.S.M.
State of Florida LS # 6660 Page 1 of 2
QUALITY METAL PANELS
GENERAL NOTES
1. ALL WORK SHALL CONFORM TO FLORIDA BUILDING CODE 2017.
2. IT IS THE INTENT OF THESE DRAWINGS TO BE IN ACCORDANCE WITH APPLICABLE CODES AND AUTHORITIES HAVING
JURISDICTION. ANY DISCREPANCIES BETWEEN THESE DRAWINGS AND APPLICABLE CODES SHALL BE IMMEDIATELY
BROUGHT TO THE ATTENTION OF THE ENGINEER.
3. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO MEET WITH ALL APPLICABLE UTILITY COMPANIES TO VERIFY ALL
UNDER- GROUND FACILITIES PRIOR TO THE BEGINNING OF CONSTRUCTION. ALL EXCAVATIONS SHALL PROCEED WITH
EXTREME CAUTION AT ALL TIMES. IN THE EVENT THAT EXISTING UTILITIES ARE DAMAGED, IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR TO REPAIR OR REPLACE ALL DAMAGES.
4. THIS WORK REQUIRES A BUILDING PERMIT. DO NOT BEGIN WORKING UNTIL A BUILDING PERMIT IS OBTAINED.
5. CONTRACTOR IS TO FURNISH ALL LABOR, MATERIALS, SERVICES AND EQUIPMENT NECESSARY TO COMPLETE ALL WORK
SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN.
6. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN.
7. ENGINEER'S VISITS TO THE SITE, AS PER G.0 OR OWNER'S REQUEST DURING CONSTRUCTION SHALL BE SCHEDULED
WITHIN 24 HOURS PRIOR TO INSPECTION.
8. THE CONTRACTOR SHALL MAKE REQUIRED ARRANGEMENTS, SECURE AND PAY FOR ALL BARRICADES, ENCLOSURES, AND
FENCING AS NEEDED FOR AND DURING THE PROGRESS TO PROTECT ADJACENT PROPERTIES.
9. THE CONTRACTOR SHALL NOT PROCEED WITH ANY ADDITIONAL SERVICES OR WORK WITHOUT PRIOR NOTIFICATION TO
THE OWNER.
10. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS CONSTRUCTION, AND FOR THE SEQUENCES AND
PROCEDURES TO BE USED.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING WITH CURRENT SITE CONDITIONS, AND SHALL REPORT ANY
DISCREPANCIES TO THE ENGINEER PRIOR TO STARTING WORK.
12. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE JOB SITE. ANY DISCREPANCIES
BETWEEN PLANS, SECTIONS AND DETAILS OR THE APPLICABLE CODES OR REGULATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT OR ENGINEER DURING BIDDING OR BEFORE WORK BEGINS IN ORDER TO CLARIFY THE
REQUIREMENTS AND TO EFFECT THE NECESSARY MODIFICATIONS, CHANGES AND /OR INSTRUCTIONS.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR RESETTING ALL DISTURBED EXISTING COND111ONS AND PROPER DISPOSAL
OF ANY EXTRA MATERIALS do GARBAGE FROM THE SITE AFTER COMPLETION OF WORK.
14 DRAWINGS AND DIMENSIONS ARE BASED UPON DRAWINGS SUPPLIED BY THE CLIENT. EASTERN ENGINEERING GROUP
WILL NOT BE RESPONSIBLE FOR ERRORS OR MISINTERPRETATIONS OF THE SYSTEM DESIGNED BY US BASED ON CLIENT
CONFIRMED DESIGN AND DIMENSIONS. ADDITIONAL DRAFTING TIME EMPLOYED IN THE CHANGE OF THE DESIGN AFTER
SIGNING AND SEALING OF DRAWINGS WILL RESULT IN ADDITIONAL COST.
15. DO NOT SUBSTITUTE MATERIALS, EQUIPMENTS OR METHODS OF CONSTRUCTION UNLESS SUCH SUBSTITUTIONS OR
CHANGES HAVE BEEN APPROVED IN WRITING BY THE OWNER.
FENCE
WIND LOAD AS PER ASCE 7-10
KD=0.85
WIND VELOCITY AS PER ASCE 7-10
MIAMI-DADE
CATEGORY 2 ------ 115 mph
AS PER FBC 2017 SECTION 1616.2.1
1. STRUCTURAL STEEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
BUILDING CODE AND AISC SPECIFICATIONS NINTH EDITION.
2. STRUCTURAL STEEL SHALL MEET THE FOLLOWING REQUIREMENTS:
TYPE ASTM GRADE Fy
STEEL SHEETS A36 ----- 36 KSI
STRUCTURAL TUBING A500 B 46 KSI
3. ALL STEEL SHALL BE HOT -DEEP GALVANIZED.
4. ALL EXPOSED FERROUS METAL PANELS, RAILS AND POSTS TO BE OF
FACTORY HOT DIP GALVANIZED AND FACTORY PAINTED WITH
ALKALI -RESISTANCE COATINGS, SUCH AS HEAVY -BODIED BITUMINOUS
CALCULATIONS I PAINT OR WITHER -WHITE MOTHACRYLATE LACQUER.
In accordance with FBC 2017 and ASCE 7-10
Wind load Calculation: General Data:
Category:
I L (ft):
4
Exposure:
C Hpost(ft)
6
V (mph):
115.00
Fy (psi) 46000
I:
1.00
A-500 Fb (psi)
27600
Kd:
0.85
Fv (psi)
18400
h (ft):
6
Fy (psi)
36000
Pd (psf):
16.2
A-36 Fb (psi)
21600
Fv (psi)
14400
Rail to Posts Connection
Design
Actual Pullout
194.4
Allowable Pullout
200 Using 10-16 Hilti
Kwik
OK Flex Screw
Post Design
2 112x2 112x16 aaae steel galvanized
A-500
Mmax. (lb -in)
13997
Zx (in^3)
0.75
fb (psi)
Mmax/Sx
fb (psi)
18662
fb (psi)<Fb
OK
Top and Bottom Design
2x1x0.071 st galvanized
A-500
Mmax. (lb -in)
1166
Sx (in^3)
0.086
fb (psi)
Mmax/Sx
fb (psi)
13562.8
fb (psi)<Fb
OK
Foundation Design (nonconstrained FBC 2017-1807.3.2.1)
P 388.80 Lateral soil bearing 200
A 1.44 Footing Diameter (ft) 1.583
d 3.00 For poles 1806.3.4 2
- - 4'-0* MAX.
/ l -7
TIT. FENCE PLAN VIEW
SCALE: 3/4"=1'-O"
4'-0" MAX.
-r �A'-
FENCE CONNEC11ONS:
- RAIL TO POSTS TO BE CONNECTED WITH (2) 10-16 KWIK
FLEX SCREW by HILTI OR APPROVED EQUAL ACCESS HOLE AT
RAILS TO BE PROVIDED FOR CONNECTION, OR BE J" WELD 1"
WELD LENGTH IN 2 OPOSITE SIDES MINIMUM.
- PICKETS TO BE CONNECTED TO TOP AND BOTTOM RAILS WITH
(4 PER PICKET, 2 TOP do 2 BOTTOM) 10-16 KWIK FLEX SCREW
by HILII OR APPROVED EQUAL, OR BY 1/4" PUDDLE WELDS.
0.06 /!
S=0.47 IN'
Z=0.58 IN'
Mmax=16.2*4*6*6/2
=13 997 #-in
M xsD=Mn/0 ,
Mn=Fy*Z , 0 =1.67
M AsD=16 000 #-in
Mmax < M Aso
POSTS (16 GA)
TYP. FENCE ELEV. VIEW
SCALE: 3/4"=1'-O"
S = 0.0863 IN'
Mmax=16.2*6*.5*4*4/8
=1 166 #--in
M Aso-=Mn/0 ,
0.06 , Mn=Fy*S 0 =1.67
M AsD=2 170 f-in
S=0.48 IN'
Z=0.60 IN'
Mmax=16.2*4*6*6/2
=13 997 1-in
M AsD=Mn/0 ,
Mn=Fy*Z , 0 =1.67
M Aso=16 530 #-in
Mmax < M Aso
ALTERNATIVE
POSTS (16 GA)
u
!Or136
_.� L )74-
SHADOW sox DETAIL
sauz 11/z"-r-O'
2x1x16 GA
GALVANIZED
STEEL TUBE
RAIL TOP
MEMBER
24 GA (MIN.)
GALVANIZED
METAL SHEET
2.5x2.5xl6 GA.
GALVANIZED
STEEL POST
o SPACED A
Co 4'-0" MAX. O.C.
Q�
�CO
5
he e b 0,
}h ,� rrs TSr�'.
- f6 e
01 m
9
METALS PANELS 2020
2x1x16 GA
•""•
GALVANIZED
- -
: •' •
•
• • •
STEEL TUBE
FENCE
• • •
• • •
RAIL BOT.
••••••
: ••••
••..:.
MEMBER
•
DWGS
'HOP
r�cricw.
3000 PSI CONCRETE
FOOTING 012'X4'-O'
1 AT
••••
•••••
4 2C
w • •
D 4,15-ION •
7tTi • 4"4%
DEEP OR 019"x3'-0"
'v 23�z;LD A. PAZ
•
•
_
�• •
DEEP OR 024"x2'-6"
DRAWN BY: M
• •
- •
DEEP (lYP)
DESIGNED BY:
I
• • •
• •� •t.
APPLICABLE EXCLUSIVE
CHECKED BY: G P
• •
• • • • • •
ONLY FOR SEDIMENTARY
JOB No.: a P Y IC2
• •
• • • •
•00001
• •
AND FOLIATED ROCK SOILS
C
- --
- -
012'x2'-9" DEEP (*)
COPYING R RED
-
(*) SOIL SHALL BE VERIFIED TO BE
CONSISTENT WATH THE MENTIONED
CHARACTERISTICS. A FLORIDA
LICENSED ENGINEER SHALL VISUALLY
INSPECT AND PROVIDE A CERTIFIED
LETTER ATTESTING SO.
NON ?;, Z0?0
Mmax < M AM ALTERNATIVE
RAILS (19 GA)
Z=0.0065 IN'
Mmax=16.2*(6.125/12)*3.33*3.33*0.125*12
=135 #-in
M AsD=Mn/0 ,
Mn=Fy*Z , 0 =1.67
M AsD=140 #-in o
Mmax < M Aso 0
f r�
PICKETS (30 GA) MINIMUM
S=0.124 IN'
Mmax=16.2*6*.5*4*4/8
=1 166 #-in
M AsD=Mn/0 ,
Mn=Fy*S , 0 =1.67
M AsD=2 673 #-in
Mmax < M Aso
0.05
!- 2" !
RAILS (16 GA)
GORM A PAZ. PE (D< 6-WU) w'aSA z IDPE7 PE (D< w-SM) .utx6 wrrxa PE (m 11,0M)
9I0P DRAMM CHECM FOR STRUMURAL REQUIREMENTS MLY CAN / 7D•65
SD-1
DATE: 7,28;'2020
QUALITY METAL PANELS
G04FRAT . NOTES:
1. ALL WORK SHALL CONFORM TO FLORIDA BUILDING CODE 2017.
2. IT IS THE INTENT OF THESE DRAWINGS TO BE IN ACCORDANCE NTH APPLICABLE CODES AND AUTHORITIES HAVING
JURISDICTION. ANY DISCREPANCIES BETWEEN THESE DRAWINGS AND APPLICABLE CODES SHALL BE IMMEDIATELY BROUGHT TO
THE ATTENTION OF THE ENGINEER.
3. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO MEET WITH ALL APPLICABLE UTILITY COMPANIES TO VERIFY ALL UNDER-
GROUND FACILITIES PRIOR TO THE BEGINNING OF CONSTRUCTION. ALL EXCAVATIONS SHALL PROCEED WITH EXTREME CAUTION
AT ALL TIMES. IN THE EVENT THAT EXISTING UTILITIES ARE DAMAGED, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
TO REPAIR OR REPLACE ALL DAMAGES.
4. THIS WORK REQUIRES A BUILDING PERMIT. DO NOT BEGIN WORKING UNTIL A BUILDING PERMIT IS OBTAINED.
5. CONTRACTOR IS TO FURNISH ALL LABOR, MATERIALS, SERVICES AND EQUIPMENT NECESSARY TO COMPLETE ALL WORK SHOWN
ON THE DRAWINGS AND SPECIFIED HEREIN.
6. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN.
7. ENGINEER'S VISITS TO THE SITE, AS PER G.0 OR OWNER'S REQUEST DURING CONSTRUCTION SHALL BE SCHEDULED WITHIN 24
HOURS PRIOR TO INSPECTION.
8. THE CONTRACTOR SHALL MAKE REQUIRED ARRANGEMENTS, SECURE AND PAY FOR ALL BARRICADES, ENCLOSURES, AND
FENCING AS NEEDED FOR AND DURING THE PROGRESS TO PROTECT ADJACENT PROPERTIES.
9. THE CONTRACTOR SHALL NOT PROCEED NTH ANY ADDITIONAL SERVICES OR WORK WITHOUT PRIOR NOTIFICATION TO THE
OWNER.
10. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS CONSTRUCTION, AND FOR THE SEQUENCES AND
PROCEDURES TO BE USED.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING WITH CURRENT SITE CONDITIONS, AND SHALL REPORT ANY
DISCREPANCIES TO THE ENGINEER PRIOR TO STARTING WORK.
12. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE JOB SITE. ANY DISCREPANCIES BETWEEN
PLANS, SECTIONS AND DETAILS OR THE APPLICABLE CODES OR REGULATIONS SHALL BE BROUGHT TO THE ATTENTION OF
THE ARCHITECT OR ENGINEER DURING BIDDING OR BEFORE WORK BEGINS IN ORDER TO CLARIFY THE REQUIREMENTS AND TO
EFFECT THE NECESSARY MODIFICATIONS, CHANGES AND /OR INSTRUCTIONS.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR RESETTING ALL DISTURBED EXISTING CONDITIONS AND PROPER DISPOSAL OF ANY
EXTRA MATERIALS & GARBAGE FROM THE SITE AFTER COMPLETION OF WORK.
14 DRAWINGS AND DIMENSIONS ARE BASED UPON DRAWINGS SUPPLIED BY THE CLIENT. EASTERN ENGINEERING GROUP WILL NOT
BE RESPONSIBLE FOR ERRORS OR MISINTERPRETATIONS OF THE SYSTEM DESIGNED BY US BASED ON CLIENT CONFIRMED
DESIGN AND DIMENSIONS. ADDITIONAL DRAFTING TIME EMPLOYED IN THE CHANGE OF THE DESIGN AFTER SIGNING AND
SEALING OF DRAWINGS WILL RESULT IN ADDITIONAL COST.
15. DO NOT SUBSTITUTE MATERIALS, EQUIPMENTS OR METHODS OF CONSTRUCTION UNLESS SUCH SUBSTITUTIONS OR CHANGES
HAVE BEEN APPROVED IN WRITING BY THE OWNER.
DESING LOADS
FENCE
WIND LOAD AS PER ASCE 7-10
KD=0.85
WIND VELOCITY AS PER ASCE 7-10
MIAMI-DADE
CATEGORY 2 ------ 115 mph
AS PER FBC 2017 SECTION 1616.2.1
1. STRUCTURAL STEEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
BUILDING CODE AND AISC SPECIFICATIONS NINTH EDITION.
2. STRUCTURAL STEEL SHALL MEET THE FOLLOWING REQUIREMENTS:
TYPE ASTM GRADE Fy
STEEL SHEETS A36 ----- 36 KSI
STRUCTURAL TUBING A500 B 46 KSI
3. ALL STEEL SHALL BE HOT -DEEP GALVANIZED.
4. ALL EXPOSED FERROUS METAL PANELS, RAILS AND POSTS TO BE OF
FACTORY HOT DIP GALVANIZED AND FACTORY PAINTED WITH
ALKALI -RESISTANCE COATINGS, SUCH AS HEAVY -BODIED BITUMINOUS
CALCULATIONS PAINT OR WATHER-WHITE MOTHACRYLATE LACQUER.
In accordance with FBC 2017 and ASCE 7-10,
Wind Speed from FBC 2017, Chapter 16, Section 1616.2.1 v--115 mph
NEXT POST FENCE TO
BE AT NO MORE THAN 4 3'-0-/4'-0- MAX.
2x1x16 \ n N
GALVANIZED I �
STEEL FRAME .. ..
GATE (TYP)
GALVANIZED
STEEL POST
2-1/2'x2-1/
Z'x16 GA
24 GA. (MIN.)
GALVANIZED
METAL SHEET
DURA FENCE
I
i7
2x1 x16 GA.
GALVANIZED
STEEL FRAME
GATE (TYP)
HINGES TO
RESIST 180 LBS
2x1 x16 GA.
GALVANIZED N
STEEL FRAME
GATE (TYP)
LOCK
HARDWARE
GATE CONNECTIONS:i
- PICKETS TODBE
CONNECTED TO TOP
AND BOTTOM RAILS - ALL GATE FRAMES TO
WITH (4 PER PICKET, BE CONNECTED BY ALL
2 TOP & 2 BOTTOM) AROUND FILLET WELD.
10-16 KWIK FLEX
SCREW by HIL11 OR
APPROVED EQUAL
TW. SINGLE GATE ELEV. VIEW
SCALE: 3/4'=1'-O"
Wind load Calculation: General Data:
DL(psf):
5
Top and Bottom Design
V (mph):
115.00 Fence Span(ft):
4
Gate Span(ft):
4
(Gate Span = Gate Leaf, not opening) 2x1x0.071 st galvanized
Exposure:
C Hpost (ft)
6
Post Design
A-500
Gust Factor
0.85
Fy (psi) 46000
Steel galvanized A-500
Mmax. (lb -in)
2608
Cf:
1.30
A-500 Fb (psi)
27545
Section
Mw;,,d
MDR Mmax. (lb -in) ZA (in^3) fb (psi) Sx (in^3)
0.124
Kid:
0.85
Fv (psi)
18400
2.5x2.5x16Ga
14012
2880 14305 0.58 24663.7 fb (psi)
Mmax/Sx
h (ft):
6.00
Fy (psi)
36000
fb (psi)
21029.6
Kz:
0.85
A-36 Fb (psi)
216CO
fb (psi)<Fb
OK
fb (psi)<Fb
OK
qz (psi):
16.2
Fv (psi)
14400
Rail to Posts Connection Design
Foundation Design (nonconstrained
FBC 2017-1807.3.2.1) (2017-1806.2)
Actual Pullout
32
P
583.83
Lateral soil bearing
200
Allowable Pullou
200 Using 10-16 Hilti Kwik
A
2.16
Footing Diameter (ft)
1.58333
OK Flex Screw
d (Depth)
3.95
For poles 1806.3
2
NEXT POST FENCE TO
BE AT NO MORE THAN 4'
6
C9
- 3 KSI CONC. FOOTING
012"x4'-T DEEP OR
019x3-0 DEEP OR
METALS PANELS 2020
024'x2'-6" DEEP (TYP)
• •
' • -_
'
• ! ! • • •
PUCABLE EXCLUSIVE
ONLY FOR SEDIMENTARY
SINGLE SWING GATG ` .
• • •
•
_
IAND FOLIATED ROCK SOILS
• • • • • •
0 � 00
• • • • i •
01Yx2'-9' DEEP(*)
-
...:..
.
. .
TYPES ;-.
• • 1 •
• •
• •
_
PROJEC-:
O SOIL SHALL BE
ROJECT H - __ _OCAIONp • • • •
LOCATION:
•
• • • • •
VERIFIED TO BE
CLIENT: ie.ALl it NE -AL PAW_• • • • •
• • • •
s�
• ! • • •
CONSISTENT NTH THE
DATE: 7/28/2E
�. !'
D Er.Wi Tl N •
96i l N*k
MENTIONED
CHARACTERISTICS. A
FLORIDA LICENSED
ENGINEER SHALL
VISUALLY INSPECT AND
PROVIDE A CERTIFIED
LETTER ATTESTING S0.
PU: XNZA O " -AZ
• • •
DRAWN BY M P
• •
~
DESIGNED BY:
• • •
CHECKED BY: G.P.
•
•
Joe NO.: 0 1ity V02
• T • • • • •
---- -
•
---
SCALE: AS ',iOWN
-
• • • •
COPNEOa RfgRYO
TW. SINGLE GATE PLAN. VIEW Mmax=2 608 #-in
M Aso=Mn/0 ,
SCALE: 3/4"=1'-0" Mn=Fy'S , 0 =1.67
M A50=2 673 #-in
Mmax < M AM
0.06 4E Z=0.0065 IN'
Mmax=16.2•(6.125/12)*3.33*3.33*0.125*12 0.06 f -
S=0.47 IN'
Z=0.58 IN'
Mmax=14 305 #-in
M Aso=Mn/0 ,
Mn =Fy'Z , 0 =1.67
M As=t6 000 #-in
Mmax < M Aso
2
POSTS (16 GA)
S=0.48 IN'
Z=0.60 IN'
Mmax=14 305 f-in
M AsD=Mn/0 ,
�i Mn=Fy"Z , 0 =1.67
a M AsD=16 530 Vin
Mmax < M Asu
2 1 /Y
ALTERNATIVE POSTS
(16 GA)
=135 #-in �
M AsO=Mn/D ,
Mn=Fy'Z , D =1.67
M AsD=140 #-in
Mmax < M AM
N NI 2'
0 o RAILS (16 GA)
PICKETS (30 GA) MINIMUM
Ref# 20-00'
No% 25, 20211
•1
GOIOAIO A PAZ PE (Lk IY-iG%!Q =RASA R Un PE (Ile b-S M) -MM W rNI2 PE (Ik "00)_I
SHOP GRAwlas CEO® FOR EIM WORK& lmollw mm OILY CAN / 2M B 1
SHEET SD-2
DATE: 7 29,2020
NEXT POST FENCE TO
BE AT NO MORE THAN 4
QUALITY METAL PANELS ALVNIZED
STEEL FRAME
GATE (TYP)
1
GENERAL NOTES
1. ALL WORK SHALL CONFORM TO FLORIDA BUILDING CODE 2017. GALVANIZED
STEEL POST
2. IT IS THE INTENT OF THESE DRAWINGS TO BE IN ACCORDANCE WITH APPLICABLE CODES AND AUTHORITIES HAVING 2-1/2"x2-1/
JURISDICTION. ANY DISCREPANCIES BETWEEN THESE DRAWINGS AND APPLICABLE CODES SHALL BE IMMEDIATELY 2"x14 GA
BROUGHT TO THE ATTENTION OF THE ENGINEER.
24 GA. (MIN.)
3. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO MEET WITH ALL APPLICABLE UTILITY COMPANIES TO VERIFY ALL GALVANIZED
UNDER- GROUND FACILITIES PRIOR TO THE BEGINNING OF CONSTRUCTION. ALL EXCAVATIONS SHALL PROCEED WITH METAL SHEET ca
EXTREME CAUTION AT ALL TIMES. IN THE EVENT THAT EXISTING UTILITIES ARE DAMAGED, IT SHALL BE THE FENCE .>
RESPONSIBILITY OF THE CONTRACTOR TO REPAIR OR REPLACE ALL DAMAGES.
4. THIS WORK REQUIRES A BUILDING PERMIT. DO NOT BEGIN WORKING UNTIL A BUILDING PERMIT IS OBTAINED.
HINGES
TO
5. CONTRACTOR IS TO FURNISH ALL LABOR, MATERIALS, SERVICES AND EQUIPMENT NECESSARY TO COMPLETE ALL
RESIST
WORK SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN.
180 LBS
6. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN.
2x1x16 GA.-
7. ENGINEER'S VISITS TO THE SITE, AS PER G.0 OR OWNER'S REQUEST DURING CONSTRUCTION SHALL BE SCHEDULED
GALVANIZED it
STEEL FRAME
WITHIN 24 HOURS PRIOR TO INSPECTION.
1
GATE (TYP)
8.THE CONTRACTOR SHALL MAKE REQUIRED ARRANGEMENTS, SECURE AND PAY FOR ALL BARRICADES, ENCLOSURES,
AND FENCING AS NEEDED FOR AND DURING THE PROGRESS TO PROTECT ADJACENT PROPERTIES.
9. THE CONTRACTOR SHALL NOT PROCEED WITH ANY ADDITIONAL SERVICES OR WORK WITHOUT PRIOR NOTIFICATION TO
THE OWNER.
10. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS CONSTRUCTION, AND FOR THE SEQUENCES
1
AND PROCEDURES TO BE USED.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING WITH CURRENT SITE CONDITIONS, AND SHALL REPORT ANY
DISCREPANCIES TO THE ENGINEER PRIOR TO STARTING WORK.
12. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT THE JOB SITE. ANY DISCREPANCIES
BETWEEN PLANS, SECTIONS AND DETAILS OR THE APPLICABLE CODES OR REGULATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT OR ENGINEER DURING BIDDING OR BEFORE WORK BEGINS IN ORDER TO CLARIFY THE
REQUIREMENTS AND TO EFFECT THE NECESSARY MODIFICATIONS, CHANGES AND /OR INSTRUCTIONS.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR RESETTING ALL DISTURBED EXISTING CONDITIONS AND PROPER DISPOSAL
OF ANY EXTRA MATERIALS & GARBAGE FROM THE SITE AFTER COMPLETION OF WORK.
14 DRAWINGS AND DIMENSIONS ARE BASED UPON DRAWINGS SUPPLIED BY THE CLIENT. EASTERN ENGINEERING GROUP
WILL NOT BE RESPONSIBLE FOR ERRORS OR MISINTERPRETATIONS OF THE SYSTEM DESIGNED BY US BASED ON
CLIENT CONFIRMED DESIGN AND DIMENSIONS. ADDITIONAL DRAFTING TIME EMPLOYED IN THE CHANGE OF THE DESIGN
AFTER SIGNING AND SEALING OF DRAWINGS WILL RESULT IN ADDITIONAL COST.
3 KSI CONC. FOOTING --
15. DO NOT SUBSTITUTE MATERIALS, EQUIPMENTS OR METHODS OF CONSTRUCTION UNLESS SUCH SUBSTITUTIONS OR
019'x4'-O' DEEP OR
CHANGES HAVE BEEN APPROVED IN WRITING BY THE OWNER.
024"x3'-9" DEEP OR
030"x3'-4" DEEP OR
1. STRUCTURAL STEEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE
036"x3'-O" DEEP
D E S I N G LOADS
BUILDING CODE AND AISC SPECIFICA11ONS NINTH EDITION.
(TYP-)
FENCE
2. STRUCTURAL STEEL SHALL MEET THE FOLLOWING REQUIREMENTS:
WIND LOAD AS PER ASCE 7-10
KD=0.85
TYPE ASTM GRADE Fy
VIAND VEI OCITY AS PER ASCE -
----STEEL-SHEETSA36 ___ ----- - KSI- _ _-2xlx16
GA.
MIAMI-DADE
STRUCTURAL TUBING A500 B 46 KSI
GALVANIZED
CATEGORY 2 ------ 115 mph
STEEL FRAME
3. ALL STEEL SHALL BE HOT -DEEP GALVANIZED.
GATE (TYP.)
AS PER FBC 2017 SECTION 1616.2.1
4. ALL EXPOSED FERROUS METAL PANELS, RAILS AND POSTS TO BE OF
FACTORY HOT DIP GALVANIZED AND FACTORY PAINTED WITH
ALKALI -RESISTANCE COATINGS, SUCH AS HEAVY -BODIED BITUMINOUS
CA
LCULI I N
In accordance with FBC 2017 and ASCE 7-10,
Wind Speed from FBC 2017, Chapter 16, Section 1616.2.1 v 115 mph
Wind load Calculation: General Data:
DL(psf):
5
Top and Bottom Design
V (mph):
115.00 Fence Span(ft):
4
Gate Span(ft):
5
(Gate Span = Gate Leaf, not opening) 2x1x0.071 st galvanized
Exposure:
C Hpost (ft)
6
Post Design
A-500
Gust Factor
0.85
Fy (psi) 46000
Steel galvanized A-500
Mmax. (Ib4n)
4074
Cf:
1.30
A-500 Fb (psi)
27545
Section
MM,Hnd
MOIL Mmax. (lb -in) 4 (inA3) fb (psi) Zx (in A3)
0.155
Kd:
0.85
Fv (psi)
18400
2.5x2.5x14Ga
15764
4500 16393 0.71 23089.1 fb (psi)
Mmax/Sx
h (ft):
6.00
Fy (psi)
36000
fb (psi)
26287
Kz:
0.85
A-36 Fb (psi)
21600
fb (psi)<Fb
OK
fb (psi)<Fb
OK
qz (psi):
16.2
Fv (psi)
14400
Rail to Posts Connection Design
Foundation Design (nonconstrained FBC 2017-1807.3.2.1) (2017-1806.2)
Actual Pullout
32
P
583.83
Lateral soil bearing
200
Allowable Pullou
200 Using 10-16 Hilti Kwik
A
2.16
Footing Diameter (ft)
1.58333
OK Flex Screw
d (Depth)
3.95
For poles 1806.3
2
NW POST FDICE 10
10'-0" MAX BE AT NO MORE 1HIW 4
2x1x16 GA. GALVANIZED
STEEL FRAME GATE (TYP) 1
01
HAROWWARE
GATE CONNECTIONS
• PICKETS TO BE CONNECTED TO TOP AND BOTTOM RAILS WITH (4 PER PICKET, 2
TOP & 2 BOTTOM) 1D-16 KWIK FLEX SCREW by HILTI OR APPROVED EQUAL
• ALL GATE FRAMES TO BE CONNECTED WITH 1/8" FILLET WELD ALL AROUND.
TYP. DOUBLE GATE ELEV. VIEW 3 KSI CONC. FOOTING
SCALE: 1/2"=1'-O" 019*x4'-0" DEEP OR
024 x3'-9" DEEP OR
030"x3'-4" DEEP
OR 036"x3'-0" DEEP (TYP.)
_ 10'- Or MAX.
TW. DOUBLE GATE PLAN. VIEW STEEL
x s cA
SCALE: 1 /2"=1'-0"
0.08 --// S=0.124 IN'
Z=0.155 IN'
Mmax=4 074 #-in
S=0.57 IN'
Z=0.71 IN'
Mmax=16 393 #-in
M AsD=Mn/0 ,
Mn =Fy*Z , 0 =1.67
M Aw=19 550 #-in
Mmax < M Am
M AsD=Mn/D ,
Mn=Fy*Z , 0 =1.67
M AsD=4 269 #-in
Mmax < M Am
T
Zv / / 2"
POSTS (14 GA) RAILS (16 GA)
(*) SOIL SHALL BE
VERIFIED TO BE
CONSISTENT WITH
THE MENTIONED
CHARACTERISTICS. A
Eastern
Engineering Group
3401 NW 32nd Avenue
Ste. 370 DoraL FL 33122
Phone. (305 599-8133
info@easterneg. corn
www, easterneg. corn
METALS PANELS 2020
FLORIDA LICENSED • . • . • • •� •
ENGINEER SHALL DOUBLE SWING Uilf : •• • ,'
VISUALLY INSPECT • • • •
AND PROVIDE A •••••• • •• •••••a
CERTIFIED LETTER •
ATTESTING SO. TYPE OP SHOP Dw S s ••.T•
PROJECT: 0000
• • •
APPLICABLE PROJECT MULTIPLE LOCATIO • • • •
EXCLUSIVE ONLY FOR LOCATION:
crn111-A- I- CLIENT: I OUAL11 METAL PAWi....
DATE: 7/28/20
012'X2'-9" DEEP (*)_i PM: GONZALO A. PAL
DRAWNBY: M.L.P.
DESIGNED BY:
CHECKEDBY: c.P-
JOB NO.: Oudity v02
SCALE: AS SHOWN
amm w �
GALVANIZED
METAL SHEET
FENCE
Z=0.0065 IN'
Mmax=16.2*(6.125/12)*3.33*3.33*0.125*12
=135 1-in
M AsD=Mn/D ,
Mn=Fy*Z , D =1.67
M Aso=140 #-in
Mmax < M Aso
AV /
PICKETS (30 GA) MINIMUM
_O• M ► PAL PE A 6417) ❑V= L WIM PE (Lk b-") MM YARIIIEZ K (Ik IY-EOW)
SHOP DRAT RM CNE M FOR JIR MMI. Pi70U MENI5 ONLY CAN / 2UN
SHE - SD-3
DATE: 728,2020