DOCK-07-20-1371, 1420 NE 101 st StAdolfo J. Gonzalez, P.E. STRUCTURAL ENGINEER 2050 Caral way Suile 502, Miami FI 33145 T: 305.415.,732 Dock pile caps Inspection Miami Shores Village Building Division 10050 NE 2 Ave Miami Shores, Florida 33138 To: Mrs. Elizabeth Allen 1420 NE 101 St Miami Shores, FI 33138 Permit No: WSW- 11-19-2759 DEAR BUILDING OFFICIAL: V/4�/ma's August 25, 2021 I, Adolfo Gonzalez, P.E. having performed site inspection during new dock construction process on the above referenced site, approved reinforcement installation at two pile caps , hereby attest that to the best of my knowledge, belief and professional judgment, the structural components of the structure are in compliance with the FBC and other approved permit documents. •••• Should you have any questions or need additional information, pleFse do inot•� hesitate to contact me. • • • Sincerely, OF F40 ci.ccN O O 9 a PE58.X N NA - Adolfo J. Gonzalez. P.E. Structural Engineer Reg. No. 58620 •••• Digitally signed 9*00 byAdolfo J •••••• Gonzalez Date: 2021.08.25 15:37:42-04'00' WI ),,1-1 f-Z7S',/ Allen Dock - Pile Log -12x12 FDOT P.S. Concrete Piles / August 9, 2021 Pile # Date Installed FDOT Pile Pile Size Specified Pile Length (Ft) Original Pile Length (Ft) Cut Off Top (Ft) Top of Pile to Mudline (Ft) Blows/Ft For Last Ft Embedment (Ft) 1 7/27/21 12x12 35 36 0.5 10.5 39 25 2 7/23/21 12x12 35 36 0.5 12.5 28 23 31 7/23/21 12x12 35 36 0.5 14 35 21.5 4 7/27/21 12x12 35 38 0.5 15.5 35 22 5 7/23/21 12x12 35 36 0.75 10.25 32 25 6 7/23/21 12x12 35 36 0.5 12.5 33 23 7 7/22/21 12x12 35 36 0.5 14 37 21.5 81 7/26/21 12x12 35 38 0.5 15.5 27 22 9 7/26/21 12x12 35 38 0.5 15.5 29 22 10 7/26/21 12x12 35 38 0.5 14 32 23.5 11 7/26/21 12x12 35 38 0.5 14 35 23.5 12 8/2/21 12x12 35 36 2 10 23 24 13 8/2/21 12x12 35 36 2 10.5 29.5 23.5 14 8/2/21 12x12 35 36 2 10 21 24 15 8/2/21 12x12 35 36 3.5 10.5 39 22 16 8/2/21 12x12 35 36 3 10 31 23 17 8/6/21 12x12 35 36 2 10 27 24 18 8/6/21 12x12 35 36 2 10.5 34 23.5 19 8/6/21 1 12x12 35 36 2 10 26 24 20 8/6/21 1 12x12 1 35 36 2 10 28 24 Permit Number- DOCK-07-20-1371 Street Address - 1420 NE 101 ST, Miami Shores, FL Pile Equipment - 3500 Lb Drop -Hammer on 60' Metal Leads •••• Crane Specifications - 5300 American Crawler Crane, 70 ton on 100' x 38' spud barge • • • • 0000 • Drop distance - 5-6 Ft • $ PEDESTALS i • i 250 SF OF OVE9�,AX0d WR DECKXXG • FOR NEW VIE\Y�•IiL•ATFORfA ' • •' NEW' 7K LB CAPACITY EAST WITH IPE RAII"Qj Ya-H SS Co. ES. • �I COAST OR SINIILAR DOUBLE • • • • `JET -SKI LIFT WITH ARNIS AT , • • • • • • 15: AND (1) 2'c3' BOARDING • • • • • • r • • • 1 5 _ -- -t•L_J 1—�� _ • • i. ---4%j------- — — — —— — 1 "r 1_10 Digitally signed GOB y`P °' ° by Adolfo J OO 9f • < -*- Gonzalez A PE 58620 � 0\�� Date:2021.08.12 14:27:20-04'00' - -LOCATION MAP AND LEGAL DESCRIPTION indian Creek Indian Cr Country Club Nr '.1''r. z 6•1 Mlaml Snores ® 101S �1 �t NE 103rd St Z Country Cub 251 • i?EPART"")_--N1' OF REGULATORY RY Shores F,INC) r` .E3Sytii�ilC i�lt i i/ J 11 ATURAL RESOURCES DIVISION Club de golf NORMANDY Nom•armysnnrsp SHORES trtal Z NE Rind sl y ,Sv NE loth St m North Bav V 1 a .a i Nf Ir L. 1.RT (:F1\IFRAI NC)TFC- I. ELEVATIONS SHOWN REFER TO THE NATIONAL GEODETIC VERTICAL DATUM (NGVD) OF 1929. 2. ALL DIMENSIONS ON PLANS ARE SUBJECT TO VERIFICATION IN THE FIELD. 3. IT IS THE INTENT OF THESE PLANS TO BE IN ACCORDANCE WITH APPLICABLE CODES AND AUTHORITIES HAVING JURISDICTION. ANY DISCREPANCIES BETWEEN THESE PLANS AND APPLICABLE CODES SHALL BE IMMEDIATELY BROI IGHT TO THE ATTENTION OF ENGINEER BEFORE PROCEEDING WITH WORK. CONTRACTOR AND ALL SUBCONTRACTORS ARE RESPONSIBLE FOR ALL LINES. ELEVATIONS, AND MEASUREMENTS IN CONNECTION WITH THEIR WORK. 4. IT IS THE INTENT OF THESE PLANS AND THE RESPONSIBILITY OF THE CONTRACTOR TO COMPLY WITH LOCAL, STATE. AND FEDERAL ENVIRONMENTAL PERMITS ISSUED FOR THIS PROJECT. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO FAMILIARIZE AND GOVERN HIMSELF BY ALL PROVISIONS OF THESE PERMITS. 5. APPLICABLE BUILDING CODE AND DESIGN CRITERIA: 1. FLORIDA BUILDING CODE.. 2017 EDITION (AND CURRENT ADDENDUMS) 2. AMERICAN CONCRETE INSTITUTE; AC'I 440.IR-15 GUIDE FOR THE DESIGN AND CONSTRUCTION OF STRUCTURAL CONCRETE REINFORCED WITH FIBER -REINFORCED POLYMER (FRP) BARS. 6. APPROVED CONTRACTOR TO DETERMINE THE SUITABILITY OF EXISTING STRUCTURES AND VERIFY ALL DIMENSIONS. THE APPROVED CONTRACTOR IS RESPONSIBLE FOR ALL METHODS, MEANS. SEQUENCES AND PROCEDURES OF WORK. 7. DO NOT SCALE DRAWINGS FOR DIMENSIONS. 8. CONTRACTOR TO VERIFY LOCATION OF EXISTING UTILITIES PRIOR TO COMMENCING WORK. 9. CONTRACTOR TO PROPERLY FENCE AND SECURE AREA WITH BARRICADES. 10. ANY DEVIATION AND/OR SUBSTITUTION FROM THE INFORMATION PROVIDED HEREIN SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF WORK. 11. ALL NEW MATERIALS AND/OR PATCHWORK SHALL BE PROVIDED TO MATCH EXISTING MATERIAI AND/OR ADJOINING WORK WHERE PRACTICAL EXCEPT AS SPECIFICALLY NOTED HEREIN. 12. LICENSED CONTRACTOR SHALL USE ALL POSSIBLE CARE TO PROTECT ALL EXISTING MATERIALS. SURFACES, AND FURNISHINGS FROM DAMAGE DURING ALL PHASES OF CONSTRUCTION. 13. THE LICENSED CONTRACTOR TO INSTALL AND REMOVE ALL SHORING AND BRACING AS REQUIRED FOR THE PROPER EXECUTION OF THE WORK. 14. ALL NEW WORK AND/OR MATERIALS SHALL CONFORM TO ALL REQUIREMENTS OF EACH ADMINISTRATIVE BODY HAVING JURISDICTION IN EACH PERTAINING CIRCUMSTANCE. 15. THE CONTRACTOR WILL EMPLOY AND MAINTAIN 4DEQUATE SEDIMENT AND EROSION CONTROL MEASURES TO PROTECT BISCAYNE BAY FROM SE[7tiv1RW ANUVONSJRpCZI � DEBRIS: Y l BOLTS 1. ALL BOLTS SHALL BE 316 STAINLESS STEEL. UNLESS OTHERWISE NOTED. CONCRETE I. CONCRETE SHALL, CONFORM TO ACI 318 (LATEST ED.) AND SHALL BE REGULAR WEIGHT. SULFATE RESISTANT. WITH A DESIGN STRENGTH OF 5.000 PSI AT 28 DAYS W/ A MAX WATER-CEMENTIOUS PROJECT SITE LOCATION: MATERIALS RATIO, BY WEIGHT, NORMAL WEIGHT AGGREGATE CONCRETE OF 0A0. 1420 NE 101 Street 2. OWNER SHALL. EMPLOY AND PAY FOR TESTING SERVICES FROM AN INDEPENDENT TESTING Miami Shores, FL 33138-2613 LABORATORY FOR CONCRETE SAMPLING AND TESTING IN ACCORDANCE W/ ASTM. 3. LICENSED CONTRACTOR IS RESPONSIBLE FOR THE ADEQUACY OF FORMS AND SHORING AND FOR SAFE LATITUDE: 25052'4.59"N PRACTICE IN THEIR USE AND REMOVAL.. LONGITUDE: 80010'10.26"W REINFORCEMENT I. ALL SEAWALL REINFORCEMENT SHALL BE GLASS FIBER REINFORCED POLYMER (GFRP) CONFORMING TO ASTM D7957 FOLIO No.: 11-3205-023-0050 2. CONCRETE COVER: STIRRUPS AND TIES: 2" PRIMARY REINFORCEMENT 2 y'I 3. LAP SPLICE FOR #5 BARS IS: BOTTOM BARS: 33" TOP BA . �� WITH 12" OR MORE CONCRETE CAST BELOW THEM PPROVAL LEGAL DESCRIPTION: 4. # 10 BARS SHALL NOT BE SPLICED. M SHORES BAY PK ESTS PB 55-83 NAME PILE DRIVING NOTES �� cl 2; LOT 4 LESS WLYIOFT BLK I & LOT 5 I. PILE DRIVING OPERATIONS SHALL BE OBSERVED BY A BLK I MIA SHORES BAY PK ESTS AMD SUFFICIENT TO DETERMINE THE APPROXIMATE LENGTH REQUIRED TO MEET DESIGN CAPACITY. PB 56-86 2. PILES SHALL BE DRIVEN USING AN APPROVED CUSHION BLOCK CONSISTING OF MATERIAL SO ARRANGED SO AS TO PROVIDE THE TRANSMISSION OF THE HAMMER ENERGY. LOT SIZE IRREGULAR 3. PILES SHALL BE DRIVEN TO REQUIRED BEAR MINIMUM CAPACITY 15-TON WOOD/ 25-TON CONC'RETI OR 10438-1023 0479 5 + O 4. PILES SHALL BE DRIVEN WITH A DROP HAMMER OR GRAVITY HAMMER PROVIDED THE HAMMER SHALI Ydj WEIGH NO LESS THAN 3.000 POUNDS, AND THE FALL OF THE HAMMER SHALL NOT EXCEED 6 FT. 1• W I. I Y.1 I V I Vti L I\ L V V V I\ V L L N PILES SHALL BE DRIVEN WITH A VARIATION OF NOT MORE THAN J" PER FOOT FROM THE VERTICAL, OR nnr_l I&AIAI A OV APPROVAL FROM THE BATTER LINE INDICATED, WITH A MAX VARIATION OF THE HEAD OF THE PILE FROM THE .r-•••••• Y• • • • ' ` POSITION SHOWN ON THE PLANS OF NOT MORE THAN 3", F WHERE PILING MUST PENETRATE STRATA OFFERING HIGH RESISTANCE TO DRIVING, THE STRUCTURAL ENGINEER OF RECORD OR SPECIAL INSPECTOR MAY REQUIRE THAT PILES BE SET IN PRE -DRILLED OR CA T E ` PUNCHED HOLES. THE PILES SHALL REACH THEIR FINAL PENETRATION BY DRIVING. 1420 NE 101 ST SEAWALL REPLACEMENT PROJECT Miami Shores. Florida CLIENT: MS. LISA ALLEN 1420 NE 101 ST Miami Shores, FL 33138 ENUIRONMENTP ;W1i;)%1;I11 TA\ I OC$AN: 00, CUl'I�DLTINj,',•I��E� 3 0*AMtt:a Avenue. quite 7 • • • I 4PR FiRbles. Florida 33134 Iep.T-XWS921-93.qt-I•••• • • 14,mw(e91) 677-3254 • . • • • •• (70NTIkACTOR7,. • • • • • • • PROJECT ENGINEER GREEN COASTALENGINEERIN: CA 33313 2301 Laguna Cir, Suite 1505 North Miami, FL 33181 Tel: (786) 583-5545 SEAL. / SIGNATURE / DAM. ONIp10 • �1 �.041TIP '4 ��•��ORIOVrP.•G�? zi��//a ONA ;\ PERMIT DRAWINGS Issue # Issue Date ( October 4, 2019 1 PROJECT: 18-8280 CLI-2018-0311, 1 PROJECT LOCATION R NOTES ET No S-1 • 1420 NE 101 ST SEAWALL ' REPLACEMENT PROJECT Miami Shores, Florida CLIENT: MS. LISA ALLEN -)VAL 1 ...—m. . •c •. a . �'n. . e sc 1420NE 101 ST NAIVE Miami Shores, FL 33138 ENyIRONMENTA.. COWSULTANT: • DATE 1 j 0 iJ CQMV�TINI: • J�;C 3404QrtiQ�a Avenue, Suite 7 •. • \ `rJ CowLQ%bles, Florida 35134 • ,��� T�I, L105}921-93;4 • • • • • Fa:•(* 0•5) 677-3M4• • • ... • CiO CTOR. • e • • • • .:. • • Nov 20,19 DC-PAR ppitea r^�. F�ry l�C�Tp fir, �)� yy A�p� �J/90O lr' � m74GRi NY1Y(;jil_ ...`� L.O. ••:.:• • R£S@�r;�E�11Ja6jA / PROJECT ENGINEER: n204'-8" \ i19T-1 1 " GREEN COASTAL ENGINEERING �39'-9" CA 33313 2301 Laguna Cir, Suite 1505 (3) EXISTING MOORING EXISTING CONCRETE North Miami, FL 33181 EXISTING RIP PILES TO BE REMOVED T-PILES AND BATTER Tel: (786) 583-5545 RAP TO BE / REMOVED 0 0 000"' PILES TO BE REMOVED. SEAL / SI��O 0j"jpATE ,/// EXISTING CONCRETE EXISTING CONCRETE EXISTING PVC � \ \\ -VONJ /// T-PILES, KING AND T-PILES AND BATTER EXISTING SEAWALL PIPE 21 LF ��N -'N1 CENS�•�1ry i -A-PROPERTY BATTER PILES TO BE REMOVED. PILES TO BE REMOVED. AND SEAWALL CAP FROM WEST ALONG ENTIRE PERTY \ �, O ' No = SHORELINE LINE TO BE /I * , ( TO BE REMOVED. REMOVED. .— V Ail Ut N PRC�PF:RTI LINE P OF EXISTING CAP _ I VEL. PERMIT DRAWINGS A B +4.70' NGVD C p zI -4 S - 4 _5 � _ N.I� Issue # Issue Date ( October 4, 2019 UNAUTHORIZED PVC PILE AND EXISTING LADDER, AND YxY x INSTALL TEMPORARY HORSCH LARSSEN DAVIT PAD TO BE REMOVED � 2250-700 OR SIMILAR STEEL SHEET PILES RER - NAT RESOURCES Di'lISIOi�l'` PRIOR TO EXISTING SEAWALL DEMOLITION I G TO PREVENT EROSION IN TO BAY. EXISTING CONDITIONS N PPROVAL PROJECT: 18-8280 CLI-2018-0319 -14 0 VE 101 S1 - NAME 1liami Sl7w.c.. F1 SATE � I EXISTING CONDITIONS SCALE: AS SHOWN 16 SHEET NO. S-2 N SCALE: 1/16" = 1" 1420 NE 101 ST SEAWALL REPLACEMENT PROJECT i ) E Q --1 ) Miami Shores. Florida CLIENT: MS. LISA ALLEN 1420 NE 101 ST Miami Shores. FL 33138 ENYIRONMENTA:. CONSULTANT: � CO1V.S��TINC•� ;' � ` DVI. i'.1i1?��� ,�� h�VI\ IVP11 \dl\i,� 116•J Fd i.t iiV LoJ ✓+�. �., • • 34/0A4i$4r�a Avenue. Suite 7 ••• Z i pL�l 16lFBta! oR P'`ai A j�i frJi�;�L I Cor0I.Cjoliles. Florida 3S134 . J T%�3s5)• 121-93:1 • ; • • . Fj�:.(305)677-32!54••�• �Qpin� — ..•. DATE �F.. i�EPc'4I�T1l�2 PROJECT f:NGINFER: AND ECONG 2C: LESOURCE3 NATURAL RESOURCES DiVISION RER • NAfJRA,,1RESOURCES DIVISION GREEN COASTAL ENGINEERING j \ H PPROVAL CA 33313 NA ME 2301 Laguna Cir, Suite 1505 DATE ' � North Miami, FL 33181 Tel: (786) 583-5545 SEAL / SIGNATURE / DATE NEW 1-Y DIA. LIME ROCK RIP TO BE PLACED AT A 2H: IV SLOPE NEW TRUEL[NE 800 SERIES 8 FEET MAX. FROM WET FACE OF \\�X 4:10NIO* SEAWALL WITH REINFORCED TOP OF NEW CAP CONCRETE SEAWALL CAP.NEW SEAWALL ALONG 204'-8" OF EL. +'7.50 NGVD PROPERTY SHORELINE. \ \�\ Q' • �GENS� ;4yy �� N - ����SS•YONAL���. o I PERMIT DRAWINGS PROPER I 1 LI\L Issue # Issue Date S_5 October 4, 2019 DOURGLASS ROUND SOIL NAILS $'-0" RETURN NO SOILI Iz OR SIMILAR ANCHORS AT 8' O.C. PROPOSED CONDITIONS NAILS REQUIRED ''I 5'-0" RETURN NO SOIL -14 0 VE I �)I 'r ^, I NAILS REQUIRED 1 %lclllll .S'11U1'c's, F'/ I PRO.IEC'T:18-8280 CLI-2018-0319 Ic_ GI I G PROPOSED CONDITIONS I SCALE: AS SHOWN SHEET NO. 0 d. H. S-3 N SCALE: 1/4" = P, EXISTING CONCRETE BATTER PILES & RING PILES TO BE REMOVED EXISTING CONCRETE SEAWALL PANEL AND SEAWALL CAP TO BE REMOVED. EXISTING CONCRETE T-PILE TO BE REMOVED. O I IT 1\I) A INSTALL TEMPORARY HORSCH LARSSEN 2250-700 OR SIMILAR S-4 STEEL SHEET PILES PRIOR TO EXISTING SEAWALL DEMOLITION TO PREVENT EROSION IN TO BAY. C) ti' vy�? a, EXISTING SEAWALL CONDTIONS 1 INSTALL TEMPORARY, HORSCH LARSSEN .' 2250-700 OR SIMILAR STEEL SHEET PILES PRIOR/�- TO EXISTING SEAWALL DEMOLITION TO PREVENT V EROSION IN TO BAY. / , EXISTING CONCRETE SEAWALL PANEL AND SEAWALL CAP TO BE REMOVED. EXISTING CONCRETE T-PILES AND BATTER PILES TO BE REMOVED. 10' INSTALL TEMPORARY HORSCH —j LARSSEN 2250-700 OR SIMILAR ��E,� �"nI ki STEEL SHEET PILES PRIOR TO r��I °�n�at �' ;��-1—NAL e4C •� Y 1 ✓-\ B EXISTING SEAWALL DEMOLITION TO PREVENT EROSION IN TO BAY. NAME D kkTE I I I EXISTING SEAWALL CONDTIONS 2 S-4 SCALE: 3/8" = 1'-0" Z�Ij 3' DEPARITMFENT OF UGULATORY AND ECOi\rOij"'''C RE (: URC:E5 NATURAL RE —SOURCES DIVISION EXISTING CONCRETE SEAWALL CAP TO BE REMOVED. EXISTING SEAWALL SECTION A SCALE: 3/8" = F-0" S_L} TOP OF EXISTING CAP '- / EL. +4.70' NGVD EXISTING CONCRETE SEAWALL PANEL, AND KING, BATTER & T-PILES TO BE REMOVED. m MHW LINE EL. +1.70' NGVD ® MLW LINE EL. -0.50' NGVD EXISTING RIP RAP TO BE REMOVED AS NECESSARY FOR CONSTRUCTION OF NEW SEAWALL. REUSE ON SHORELINE AFTER NEW CONSTRUCTION. SCALE: 3/8" = F-0" S_L� EXISTING CONCRETE SEAWALL c CAP TO BE REMOVED. 31 Zx X/\fir 6' ,'TO ///' / SEAWALL �,� WETFACE INSTALL TEMPORARY\'. HORSCH LARSSEN 2250-700 OR SIMILAR ;. STEEL SHEET PILES PRIOR TO EXISTING SEAWALL DEMOLITION TO PREVENT EROSION IN TO BAY. ' TOP OF EXISTING CAP EL. +4.70' NGVD EXISTING CONCRETE SEAWALL PANEL, T-PILES AND BATTER PILES TO BE REMOVED. m MHW LINE EL. +1.70' NGVD m C ® MLW LINE O0 — EL. -0.50' NGVD NAME DATE EXISTING SEAWALL SECTION B SCALE: 3/8" = P-0" S-4 ES DIVISION 1420 NE 101 ST SEAWALL REPLACEMENT PROJECT Miami Shores, Florida CLIENT: MS. LISA ALLEN 1420 NE 101 ST Miami Shores, FL 33138 ENVJRONMENTAL• CONSULTANT: OCF4W- ••*0*' c(wNJ�TIN �.E 34011d+► XV Avenue, Suite 7 .. Coro PAIes, Florida 33134 Te%105 021-934- • • s • • • Fri s3a677-3234 oo. •• CO jt�&TOR:. •• •• •.; • •• •••0 PROJECT ENGINEER: GREEN COASTAL ENGINEERING CA 33313 2301 Laguna Cir, Suite 1505 North Miami, FL 33181 Tel: (786) 583-5545 SEAL / SIG DATE `\`00NIO Af �y p , pJE OF 1W .t�Pt 0 II11 PERNUT DRAWINGS Issue # Issue Date 10 October 4, 2019 PROJECT:18-8280 CLI-2018-0319 EXISTING SEAWALL SECTIONS SCALE: AS SHOWN SHEET NO. S-4 EXISTING CONCRETE EXISTING CONCRETE ' ER - NAT FEsour.- SEAWALL CAP AND T-PILES AND BATTER c.� FPRITJ`i; RULINE 800 SERIES 12" (TYPICAL) SEAWALL PANEL TO PILES TO BE REMOVED. BE REMOVED. r'E - 01 10, — ,— , T < _,�_ -T �T— l- l r 17—�T--,-- --T 00 cc NEW REINFORCE CONCRETE SEAWALL CAP GEOTEXTILE USE CLEAN BACKFILL PER FBC STANDARDS S'S or IN ALL AREAS BEHIND NEW SEAWALL. PROPOSED SEAWALL CONDITIONS 4 USE CLEAN BACKFILL PER FBC SCALE:%" STANDARDS IN ALL AREAS INSTALL TEMPORARY HORSCH C BEHIND NEW SEAWALL. LARSSEN 2250-700 OR SIMILAR NEW REINFORCED CONCRETE SEAWALL CAP STEEL SHEET PILES PRIOR TO rj 24" W x 16" L, 3- #5 CONTINUOUS REBAR EACH S-5 v+ FACE. #3 STIRRUPS 10' C/C 2-#5 x 24 REBAR EXISTING SEAWALL DEMOLITION a '°� �� b z BEHIND EACH ANCHOR, 3/4" CHAMFERED EDGE. TO PREVENT EROSION IN TO BAY. �'.�" NUV 1 4 20-119 I `O � 2 TOP OF NEW CAP EXISTING SEAWALL CONDTIONS 3 _ — — — EL. +7.50' NGVD SCALE: 3/8 F-0" S-5 � EPARTMFHNT OF BEG -AT _ - IT ANEL®ia1GIVIv R�,0,0URC I 1=III—I I o NATURAL MSOunCEv 'iviS_ WEI I S 1 El I I— SEAWALL WET -FACE TO BE FLUSH — III=III=I _ 8" ALONG PROPERTY SHORELINE AND EXISTING SEAWALL CONCRETE P TO BE I I _= I I i 4'-10" WILL NOT EXTEND GREATER THAN 12 INCHES WATER -WARD OF PREVIOUSLY REMOVED. EXITING SEAWALL WET -FACE. —1 I I=1 11=III=1 M11 AMETER BLUE MARLIN ANCHOR III=1 11- WEEP HOLES TO BE INSTALLED INR TOP OF EXISTING CAP DURGLASS ROUND SOIL 1 -III—III EACH PANEL, 10 FEET O.C. MAX, EL. +4.70' NGVD NAILS OR SIMILAR n 8'-0" _I I I=I I I=I I I f6" ABOVE MLW LINE (TYPICAL). -i I MHW LINE EXISTING CONCRETE I -III I I I I EL. +1.70' NGVD �N�; SEAWALL PANEL, ANCHOR INSTALLED PER b m X 4/'-10 TO 2'-2" T-PILES AND BATTER MANUFACTURER'S SPECIFICATIONS TO - /!SEAWALL PILES TO BE REMOVED. ACHIEVE A FACTORED PULLOUT WET FACE CAPACITY OF 3200p1f. m MHW LINE m MLW LINE EL. +1.70' NG V D ^ - EL. -0.50' NG V D �, TRULINE 800 SERIES 5000 PSI CONCRETE #10 GFRP BARS PER CELL TRULINE DRIVEN AND FILLED WITH INSTALL TEMPORARY CONCRETE TO LIMEROCK m MLW LINE HORSCH LARSSEN EL. -0.50' NGVD 2250-700 OR SIMILAR �� I I MUDLINE m STEEL SHEET PILES PRIOR TO EXISTING SEAWALL EL. -3.30' NGVD - - DEMOLITION TO PREVENT %�� I I c EROSION IN TO BAY. I I 8MAX CONCRETE FILL MUST EXTEND T LIMEROCK 8" NEW 18"-24" DIA. LIME ROCK RIP -RAP TO BE ��w �'ft.�l�lr2'-0" PIN PILE TOE 1.875" PLACED AT A 2H:1 V � �I OVA�� I-#10GFRPBARINTO CLEAR SLOPE8'MAX FROM WET 0VAL DRILLED HOLE COVER FACE OF NEW SEAWALL - ALONG ENTIRE EXISTING SEAWALL SECTION C ATE PROPOSED SEAWALL SECTION D PROPERTY SHORELINE. SCALE: 3/8" = F-0" S_5 SCALE: 3/8" = 1'-0" S-5 1420 NE 101 ST SEAWALL REPLACEMENT PROJECT Miami Shores, Florida CLIENT: MS. LISA ALLEN 1420 NE 101 ST Miami Shores, FL 33138 ENV IRONMENTAIP CONSULTANT: ccq .VL'TIN(g4LE 340,1�Q Lca Avenue, Suite 7 • • • . Coraj Pibles, Florida 33134 Tet43057921-9344 , • •. ., Fad- (II j 677-32V - •' • • CQWT"ACTOR:.••••• ••: •. •..• PROJECT ENGINEER: GREEN COASTAL ENGINEERING CA 33313 2301 Laguna Cir, Suite 1505 North Miami, FL 33181 Tel: (786) 583-5545 SEAL / SIGN / TE �\�OONIO /�i i 80011 OF , %i 1010Y' //��lllllll\\\0 PERMIT DRAWINGS Issue # Issue Date (1 October 4, 2019 PROJECT:18-8280 CLI-2018-0319 EXISTING & PROPOSED SEAWALL SECTIONS NO. S-5 • B .4 C% P L A N DS TRULINE 800 SERIES 5000 PSI CONCRETE 1- #10 GFRP BAR PER CELL TRULINE DRIVEN AND FILLED WITH CONCRETE TO LIME -ROCK. USE CLEAN BACKFILL PER FBC STANDARDS IN ALL AREAS BEHIND NEW SEAWALL. 7NEW 7t�, REINFORCED 14 CONCRETE CAP DEPFrI OF 6iEC�l�s �eTC1fi TYP. RETURN WALL DETAIL 5 NATURAL. � E QL:,R EF_ DI` I IL, � SCALE: %" = F-0" S-6 FIBROI JS JOINT FILLER OR SIMILAR NEW COLD C'ONCRI: IT CONTROL. JOINTS. SPACED AT APPROXIMATELY 50' O.C. ACROSS NEW SEAWALL CAP d ° • ° d - s . � d . NEW CONCRETE . d• • ° • SEAWALL CAP_ — NEW TRULINE SEAWALL. CONCRETE CONTROL JOINT DETAIL%6*\ NOT TO SCALE IQS-6 TRULINE 800 SERIES 5000 PSI CONCRETE 2- # 10 GFRP BARS PER CELL TRULINE DRIVEN AND FILLED WITH CONCRETE TO LIMEROCK MUDLINE m EL. -3.30' NGVD - CONCRETE FILL MUST EXTEND TO LIMEROCK T-0" PIN PILE TOE 1410 GFRP BAR INTO DRILLED HOLE 1420 NE 101 ST SEAWALL REPLACEMENT �I PROJECT Miami Shores, Florida C11��1 ctlP.ido1 R i@i i9►�+` CLIENT: WkME MS. LISA ALLEN DATE ICA 1420 NE 101 ST Miami Shores, FL 33138 ENVIRONMENTAL. COVULTANT: 0 AN. CQ�1kCTIN%LLC 34Q ylftca Avende, Suite 7 • NEW REINFORCED CONCRETE SEAWALL CAP CorlGables, Florida 33134 24" W x 16" L, 3- #5 CONTINUOUS REBAR EACH Fa.TdI: 3tl) 67 -9344 �•�� �.. Fax: ('3U3) 677-32g1 FACE. 43 STIRRUPS 10" CIC 245 x 24 REBAR of _ ... • BEHIND EACH ANCHOR, 3/4" CHAMFERED EDGE. CWNjZ4kCTOR: • • TOP OF NEW CAP EL.+7.50'NGVD �•� ;•••:. •••• . ." -III=III= ••.. PROJECT ENGINEER.. =1 I I► I I -1 I I I I �� III—� GREEN COASTAL ENGINEERING CA 33313 III=1 I RER • NATU L RESOURCES DIVISION 2301 Laguna Cir, Suite 1505 _ R4PPRUML North Miami, FL 33181 1—III Tel: (786) 583-5545 III —I 1 I NAME SEAL / SIGNATURE / DATE I -III- DATE � jONIp r �� ENSF'•+ i T F ' V/ - �11111111 PERMIT DRAWINGS Issue # Issue Date 8" (D October 4, 2019 1.875" CLEAR COVER PROPOSED SEAWALL SECTION E SCALE: 3/8" = P-0" S-6 PROJECT:18-8280 CLI-2018-0319 PROPOSED SEAWALL SECTIONS AND CONTROL JOINT DETAIL NO. S-6 • NOTE: THE FOLLOWING SPECIFICATIONS ARE FOR STEEL REINFORCED TRULINE WALL SYSTEM. FOR GROUP REINFORCED WALLS SEE CALCULATIONS. TRU Ll N E� ENGINEERING SPECIFICATIONS TRU Ll N Eo ENGINRei fNGdSP Crete wiA4 ONS Rebar The Innovative Hybrid Sheet Piling System The Innovative Hybrid Sheet Piling System Notes: The tables that follow are the recommended values for factoredREINFTABLE 7: 800 Series -Factored Moment Capacities* (in-Ibs/ft width of wall) -Reinforced Sections 4 Rebar • ' • Units 800 Series structural moment capacities and corresponding bending stiffnesses of Factored Moment Capacities See tables 1, 4 and 7 withl, 2 and 4 rebar for data. Bending Stiffness See tables 2, 5 and 8 withl, 2 and 4 rebar for data Factored Shear Capacities See tables 3, 6 and 9 for data Truline sections filled with reinforced concrete. The tabulated values were computed for a range of concrete compressive strengths and reinforcement options. The factored moment capacities were determined from nonlinear moment vs. curvature behavior computed using I -Pile 2012 software. The nominal moment capacities were determined when the maximum compressive strain in the concrete reached .003 in/in. The reported ultimate (factored) moment capacities were computed by multiplying the nominal moment capacity by a strength reduction factor of 0.65. The reported bending stiffnesses are for moment levels equal to the ultimate moment capacity and are for cracked sections. This method for Bar Size Concrete Compressive Strength, f'c psi 3,000 3,500 4,00 4,500 5,000 No.4 95,900 100,900 104,900 108,100 109,900 No. 5 127,100 132,800 138,100 143,100 147,700 No. 6 161,200 167,900 174,100 179,800 185,300 No.7 201,600 209,100 216,200 222,800 229,000 No.8 248,200 256,600 264,500 271,900 278,900 determining moment capacities for the Truline/Reinforced Concrete *As stated on page 1• the reported ultimate (factored) moment capacities were computed sections was validated by the actual lab test (page 7). hr mtdtiplring the nominal moment capacity br a strength reduction factor o'0. 6 WITHOUT• Units 800 Series Factored shear capacity is nominal shear capacity of the concrete and ---- -- the Truline form reduced by a strength reduction factor of 0.75. TABLE 8: 800 Series - Bending Stiffness (lb-in2/ ft width of wall) - Reinforce ections 4 Rebar Allowable Moment aPP arent* ft • Ibs/ft 4 427 Per ACI 318-08 Section 11.4.6.1 shear reinforcing steel is not typically required by the Truline system since the section depth is less than 10 Allowable Shear- lb/ft 6,313 inches and the walls typically have shear loads well under 50% of the factored shear capacity without steel. If in the rare case the shear Section Modulus theoretical 34 load exceeds this threshold, minimum shear reinforcing steel should be 3 apparent' in /ft 16.6 1 added per ACI 318-08 standard. Moment of Inertia I, theoretical in'/ft 136 I- apparent* 66 ° Based on full scale performance test by Architectural Testing, Inc. Report #70174.01-1 22-44, not theoretical calculations (page 8). Bar Size Concrete Compressive Stre 'c psi 3,000 3,500 4,000 4,500 5,000 No.4 234,820,000 239,000,000 242,900,000 246,235,000 249,500,000 No.5 309,785,000 317,402,000 323,775,000 330,000,000 334,400,000 No.6 383,022,000 394,125,000 404,646,000 413,000,000 420,000,000 No.7 459,000,000 475,658,000 489,700,000 501,500,000 511,750,000 No.8 537,000,000 558,815,000 576,993,000 592,869,000 606,500,000 Truline's allowable moment, for applications not filled with rein- forced concrete, is based on section properties that were deter - GENERAL SPECIFICATIONS Units 800 Series mined using full scale performance testing rather than theoretical TABLE 9: 800 Series -Factored Shear Capacity/ft width* -Reinforced Sections 4 Rebar rnlndntinnc- Thic is n rnncervntivta nnnrnnrh thnt nrenunts for the U-Channel Section Depth in 8 viscoelastic behavior of the material that determines its mechanical -- - properties. It results in a value that the design engineer can be U-Channel Section Width in 12 confident in without applying excessive factors of safety. - Vt + VF Concrete Compressive Strength, f, psi 3,000 3,500 4,000 4,500 5,000 lb/ft 8,000 8,260 8,516 8,740 8,950 Nominal I nlCKness ,n V.[/ All pile sections must be tilled with gravel or other material such as - *As stated on page 1. the reported factored shear cupwitiey- ere computed br soil, sand, pebble, etc. to ensure the web is fully supported and the niultiplring the nominal shear capacitr In- a swength reduction factor of 0.75. Weight Ibs/ft 7.1 shear load is transferred from flange to flange by the fill material Shear load must be applied by continuous beam or waler on the Modulus of Elasticity Psi 380,000 face of the wall. V' 800 Series - Rebar Placement - Reinforced Sections 4 Refzar Tensile Strength psi 6,300 t I (theoretical) is moment of inertia as calculated for the shape and adjusted to a per foot basis. Design Strength*°° psi 3,200 T CiLa a I (apparent) is moment of inertia determined experimentally by a full scale test and measuring the deflection of the wall. This is the Impact Strength in Ibs 850.2 value for moment of inertia that would predict the deflections that OT 0 0 0 0 0 Material: Proven, durable co -extruded rigid vinyl were measured across a range of known loads. This number is also material formulated for exterior weatherability and high adjusted to a per foot basis. impact resistance. The outer layer is a UV -resistant virgin '°° Based on published data by US Army Corps �r i der 0 0 0 0 vinyl compound. The inner layer is post-industrial recycled #ERDC/CRREL LR-03_1L -19is "`✓✓✓ j vinyl. See page 5 for recycled data. r'` I For comparative purposes, the total material icknes d , 1g9 -Vn narrunn� ofam� kinJ i.s madras to the suimhitinafTrtdina• hat a purtirui�r appluatiun,n dra•n•.ntr. nhwinrddu•ra tr:rna. c,r�r..ntr�t,rrge•.ei�rmda•r,.gira•rr should be -doubled -due to the Truline double wall design. ,_„�•,.o._o -- ' RER • NATU .AL ESOURGty L►..".. F. 'i ?,r":�1 1l1'' O, I`r=EII�Tf31 Y r,rr. .r spr �. a r+nr ar,n-r, ayl�,)P(t11� IJ �D 1. r.a♦ ' atrva va�d a�LVV�iv�s�v PROVAL hip � � evi .. .....A161 'J A P�a'ayAL www.fruline.us � e a' d a. a a c . o d r ✓, i n' ❑ page f lal�i�at;-�..__e •_Fi ��'1?3S9F.�1+�•,r, r,..ur.a,,,,,,,,J Pe 4 of 8 9 DATE � 1420 NE 101 ST SEAWALL REPLACEMENT PROJECT Miami Shores. Florida CLIENT: MS. LISA ALLEN 1420 NE 101 ST Miami Shores. Fl, 33138 ENV IRONMEN"I'AlsC'ON�UL"FANT: OGLAN'• ;••••• CgA9UVTINC•tLLC •• ';*!Dean•••• ••!• 340.Wirrarca Aventlh. S *it* • • Coral Gab•Ils. Florida 31134 • • • Te4r(TM221-93,W • i•• •� Faz:'(*3e1) 677-3251 • • • • ' � CjiRA TOR: •• • • 66 PROJECT ENGINEER GREEN COASTAL ENGINEERING CA 33313 2301 Laguna Cir, Suite 1505 North Miami, FL 33181 Tel: (786) 583-5545 SEAL / SI Tql-E A �� pN o Hq 0.ftwoll r , STATE OF ONIA%- PERMIT DRAWINGS Issue # Issue Date October 4, 2019 PROJECT: 18-8280 C1.1-2018-0319 TRUELINE VINYL SHEE PILE SPECIFICATIONS NO. S-7,1 NOTE: THE FOLLOWING SPECIFICATIONS ARE FOR STEEL REINFORCED TRULINE WALL SYSTEM. FOR GROUP REINFORCED WALLS SEE CALCULATIONS. TRULINE` The Innovative Hybrid Sheet Piling System ENGINEERING SPECIFICATIONS Reinforced Concrete with 1 Rebar TRU Ll N E� PRODUCT SPECIFICATIONS The Innovative Hybrid Sheet Piling System TABLE 1: 800 Series - Factored Moment Capacities* (in-lbs/ft width of wall) - Reinforced Sections 1 Rebar Bar Size Concrete Compressive Strength, f'c psi 3,000 3,500 4,000 4,500 5,000 No.4 41,300 42,500 43,400 44,200 44,700 No.5 43,100 44,600 45,600 46,400 47,100 No.6 52,300 56,100 58,100 59,600 60,800 No.7 56,900 63,500 69,100 73,400 75,800 No.8 59,800 67,600 74,700 81,000 86,600 No.9 62,300 70,500 78,300 85,600 92,400 No.10 65,000 73,800 82,000 89,900 97,500 No.11 67,500 76,800 85,300 93,600 101,600 No.14 73,200 82,900 92,300 101,400 110,000 * As stated on page 1, the reported ultimate (factored) moment capacities here computed fir multip/ring the nominal moment capaciq• by a strength reduction factor of 0.65. TABLE 2: 800 Series - Bending Stiffness (lb-in2/ ft width of wall) - Reinforced Sections 1 Rebar Bar Size Concrete Compressive Strength, f', psi 3,000 3,500 4,000 4,500 5,000 No.4 64,920,000 67,370,000 69,380,000 71,080,000 72,560,000 No.5 68,430,000 71,100,000 73,310,000 75,170,000 76,790,000 No.6 81,460,000 84,950,000 88,160,000 90,900,000 93,280,000 No.7 96,350,000 100,210,000 103,770,000 107,100,000 110,350,000 No. 8 111, 380,000 115,960,000 120,110,000 123,910,000 127,450,000 No. 9 125, 280,000 130,780,000 135,620,000 140,090,000 144,140,000 No. 10 140,620,000 147,160,000 153,050,000 158,290,000 163,130,000 No. 11 154,500, 000 162,020,000 168,900, 000 175,050,000 180,630,000 No.14 181,660,000 191,420,000 200,140,000 208,040,000 215,310,000 TABLE 3: 800 Series - Factored Shear Capacity/ft width* - Reinforced Sections 1 Rebar V, + Vf Concrete Compressive Strength, f'� psi 3,000 3,500 4,000 4,500 5,000 Ib/ft 8,000 8,260 8,510 8,740 8,950 _PARTS: 800 Series Part Part No. 12" wide Boo 8- deep Name U-Channel (1 2" wide x 8" deep) (304.8mm x 203.2mm) Female End Cap 801 (Attaches to the last installed u-channel or radius.) Male End Cap 802 (Attaches to the first u-channel prior to installation.) 803 804 22.5a Radius Recycled Content % Post -Industrial Recycled Material Content % by Wt - Installed Mix 92.5% 92.5 % Note that since the u-channel accounts for the vast majority of pounds used for any given installation, assuming no cross ties are used, the recycled 88.7 % content for the mix of products used in a typical wall is essentially the some as the recycled content of the 89.8 % u-channel itself. . 93.3 % f' Cross Tie 98.0 805 5° Radius CONFIGURATIONS - r NAMEI START Attach Male End Cap with screws DATE 1 to 1 st U-channel prior to driving - *As stated on page 1, the reported factored shear capacities were computed by multiplving the nominal shear capaciti ht• a strength reduction fiuror of 0. 75. 800 Series- Rebar Placement- Reinforced Sections 1 Rebar Mob � I o o 4 2019 DEPAR 61iJ€:N, f OF t%1; ;Lla� 7 RY Amm Er, - I www.truline.us it, 2 Continue adding U-channels or radius parts to create wall NPyI `/L r3�`J�S:�I�i�E 1 Q WW.truline.us page 2 of 8 3a t „' ,. , , m.,4 ,,T III l I �P11-1 ,. nn., �, d��. w�cv��..,T, 93.5 % -K i'VIVISIVOLVICOLORS (top view) Three standard colors (below) or a custom color. Colors shown provide only 77 an example and are not 1 exact matches. Sample chips are available upon request. i Light Gray IG,P-0t) Optional: Add a return I wall by attaching a Male End Cap to the wall Sand (SA-02) END 3 Beige Install Female End Cap (M-03) onto the last U-channel rrl-. •�nwl l�v.l 1-.ws+..l l.�nr�ra ey l`tl�l^pI, !ll-I� IYI11 \dl \S'1L 1\LVi,/iJl\Nf�V I.d IJ PsiI� l IrI/II71 A ov A PE)"3f 1. -a! s eaa Omla page 5 of 8 pppp qq N IkVE , DO ai Y . :: . . \O. /NM5I 1420 NE 101 ST SEAWALL REPLACEMENT PROJECT Miami Shores. Florida CLIENT: MS. LISA ALLEN 1420 NE 101 ST Miami Shores, Fl, 33138 ENVIRONMENTAL GONSVI-TANT: RINe 0Cso CO11��1QV• LTING, LC. iY�oo• o•••• �' 340 yji;p`C�� venue.. Suite 7 • Coral �i les. Florida 33184 �• Tel: f305) %J-9344• o •• •, Fax: (IMT.77-3254 006" ' oom- .- 00 •. COWJKR� WOR: 0..0.0 00 •0000. 0 0 0 • • • • :••0•• 000 it ••:0.• • • PROJECT ENGINEER: GREEN COASTAL ENGINEERING CA 33313 2301 Laguna Cir, Suite 1505 North Miami, FL 33181 Tel: (786) 583-5545 SEAL / Sk�0V I[to �E 1Y •r � r 680011, 1 �i ARIVP,r��� s/®IVA►- �e )i1111I1\W PERMIT DRAWINGS Issue # Issue Date Q October 4, 2019 1 PROJECT: 18-8280 CLI-2018-0319 1 TRUELINE VINYL SHEE PILE SPECIFICATIONS KALE: AS SHOWN MEET NO. S-7,2 Miami Shores Village Building Department 10050 NE 2 Ave Miami Shores FL 33138 Permit NO. WSW-11-19-2759 Type: Retaining Walls/Seawalls worwass: Seawall Permit Status: Approved Issue Date: 12/17/2019 Expires: 06/15/2020 INSPECTION REQUESTS: (305)762-4949 or log on at https:llbldg.msvfi.gov/energov_prodiselfservice Requests must be received by 3:30pm WORK IS ALLOWED: MONDAY THROUGH FRIDAY, 8:OOAM - 7:OOPM SATURDAY 8:00AM - B:OOPM. NO WORK IS ALLOWED ON SUNDAY OR HOLIDAYS BUILDING AND ROOFING INSPECTIONS ARE DONE MONDAY THROUGH FRIDAY . NO INSPECTION WILL BE MADE UNLESS THE PERMIT CARD IS DISPLAYED AND HAS BEEN APPROVED . PLANS ARE READILY AVAILABLE. IT IS THE PERMIT APPLICANT'S RESPONSIBILITY TO ENSURE THAT WORK IS ACCESSIBLE AND EXPOSED FOR INSPECTION PURPOSES. NEITHER THE BUILDING OFFICIAL NOR THE CITY SHALL BE LIABLE FOR EXPENSE ENTAILED IN THE REMOVAL OR REPLACEMENT OF ANY MATERIAL REQUIRED TO ALLOW INSPECTION POST ON SITE 1132050230050 Owner's Name: ELIZABETH ALLEN Owner's Phone: Job Address: 1420 NE 101 ST ST Total Square Feet: 0 Miami Shores, FL 33138 dotal Job Valuation: $ 199,574.00 Contractor(s) Phone Address CASE MARINE CONSTRUCTION INTERI (305)613-4241 429 LENOX AVE, MIAMI BEACH, FL 33139 Description: INSTALLATION OF NEW CONCRETE PANEL SEAWALL, NO MORE THAN 12" WATERWARD OF EXISTIN SEAWALL. ALSO PROPOSES TO INSTALL NEW CONCRETE BATTER PILES AND A NEW CONCRETE SEALWALL CAP WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE COMMENCING WORK OR RECORDING YOUR NOTICE OF COMMENCEMENT. Page 1 of 1 INSPECTION RECORD STRUCTURAL INSPECTION DATE INSP Foundation Stemwall Slab Columns (1st Lift) Columns (2nd Lift) Tie Beam Truss/Rafters Roof Sheathing Bucks Interior Framing Insulation Ceiling Grid Drywall Firewall Wire Lath Pool Steel Pool Deck Final Pool Final Fence Screen Enclosure Driveway Driveway Base Tin Cap In -Progress Roof Installation Roofing Final Shutters Attachment Final Shutters Rails and Guardrails ADA compliance DOCUMENTS Soil Bearing Cert Soil Treatment Cert Floor Elevation Survey Reinf Unit Mas Cert Insulation Certificate Spot Survey Final Survey Truss Certification STRUCTURAL COMMENTS WINDOWSDOORS INSPECTION DATE INSP Attachment WORKSPUBLIC INSPECTION DATE INSP Excavation ELECTRICAL INSPECTION DATE INSP Temporary Pole 30 Day Temporary Pool Bonding Pool Deck Bonding Pool Wet Niche Underground Footer Ground Slab Wall Rough Ceiling Rough Rough Telephone Rough Telephone Final TV Rough TV Final Cable Rough Cable Final Intercom Rough Intercom Final Alarm Rough Alarm Final Fire Alarm Rough Fire Alarm Final Service Work With ELECTRICAL COMMENTS INSPECTION DATE INSP Final Sprinkler Final Alarm PLUMBING INSPECTION DATE INSP Rough Water Service 2nd Rough Top Out Fire Sprinklers Septic Tank Sewer Hook-up Roof Drains Gas LP Tank Well Lawn Sprinklers Main Drain Pool Piping Backflow Preventor Interceptor Catch Basins Condensate Drains HRS Final PLUMBING COMMENTS MECHANICAL INSPECTION DATE INSP Underground Pipe Rough Ventilation Rough Hood Rough Pressure Test Final Hood Final Ventilation Final Pool Heater Final Vacuum MECHANICAL COMMENTS BUILDING PERMIT APPLICATION ME BUILDING ❑ ELECTRIC Miami Shores Village Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 Tel: (305) 795-2204 Fax: (305) 756-8972 INSPECTION LINE PHONE NUMBER: (305) 762-4949 ❑ ROOFING ❑PLUMBING ❑ MECHANICAL ❑PUBLIC WORKS JOB ADDRESS: 1420 NE 101st Street "01KIVEE, OV11 9/jOij ^( F 1BC� n20 Master Permit No. V V S V v— I IH I q Sub Permit No. ❑ REVISION ❑ EXTENSION ❑RENEWAL ❑ CHANGE OF ❑ CANCELLATION ❑ SHOP CONTRACTOR DRAWINGS City: Miami Shores County: Miami Dade Zia: 33138 Folio/Parcel#: 11-3205-023-0050 Is the Building Historically Designated: Yes NO NO Occupancy Type: Load: Construction Type: Flood Zone: BFE: FFE: OWNER: Name (Fee Simple Titleholder): Matthew A Ilan eL -eAk"ph h Q�,t�2Phone#: Address: 1420 NE 101st Street City: Miami Shores State: FL Zip: 33138 Tenant/Lessee Name: Phone#: Email: �'CPs�Co� j�C'T'(C) Go • u j�^ p� n + �- 7 I CONTRACTOR: Company Name: T C N 1 r b1�XL� 1 E �• � Phone#: w r) G L34M l Address: > City: ? IM V fSttate: ' � Zip: Qualifier Name: T �dCA1 w Phone#: State Certification or Registration #: Certificate of Competency #: DESIGNER: Architect/Engineer: Dynamic Engineering Solutions, Inc. c/o Mr. John Omslaerphone#: (954) 545-1740 Address: 351 S. Cypress Road, Ste 303 City: Pompano Beach State: FL Zip: 33060 Value of Work for this Permit: $ � . �7Y6 Square/Linear Footage of Work: +/- 2001inear feet Type of Work: ❑ Addition ❑ Alteration ❑ New Q Repair/Replace ❑ Demolition Description of Work: Installation of new concrete panel seawall, no more than 12" waterward of exisiting seawall. Also proposes to install new concrete batter piles and a new concrete seawall cap. Specify color of color thru tile: qz,-, ."d Submittal Fee $ i Permit Fee $ CCF $ CO/CC $ Scanning Fee $ Radon Fee $ DBPR $ Notary $ Technology Fee $ Training/Education Fee $ Double Fee $ Structural Reviews $ Bond $ TOTAL FEE NOW DUE $ (Revised02/24/2014) Bonding Company's Name (if applicable) Bonding Company's Address City State Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS, FURNACES, BOILERS, HEATERS, TANKS, AIR CONDITIONERS, ETC..... OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the inspection will not be approved and a reinspection fee will be charged. A Signature Signatu or AGENT CONTRACTOR The foregoing instrument was acknowledged before me this The foregoing instrument was acknowledged beforemethis 2'1fi day of . 20 k' , by 19f))1 _ day of Nov , 20 � 1 by f Cad&Ao AU4 who is personally known to S V� who is personally known to me or who has produced TJif JV&t) b OW -be as me or who has produced as identification and who did take an oath. NOTARY PUBLIC: NOT - i ..A2 Q2 Seal: ............. JUSTINA S. NANES Notary Public - StatedFlurida APPROVED BY (Revised02/24/2014) Seal: did take an oath. Fl�e , .•ssroy •; G� RCH24do iN C STAh. ati s�Ncrv1011�#t i!!i!#iti!!##i#itiii###iii\i#i#itti!!##!ii##!#i#ii!#i!###ii#iii#iiii &mdMthrough Nalinwl y , Plans Examiner I� I Zoning t' rl Structural Review Clerk Miami Shores Village 10050 NE 2 Ave Miami Shores FL 33138 305-795-2204 Permit NO.: WSW-11-19-2759 Permit Type. Retaining Walls/Seawalls Work Ciossiftcotion: Seawall Permit status: Approved Issue Date: 01/13/2020 1 Expiration: 10/12/2021 Location Address Parcel Number 1420 NE 101ST ST, Miami Shores, FL 33138 1132050230050 Contacts ELIZABETH ALLEN Owner KEARNS CONSTRUCTION COMPANY Contractor 1290 NE 102 ST, MIAMI SHORES, FL 331382618 CHARLES SWANSON KEARNS Mobile: 7864237016 lisaguancill30@gmail.com 4101 BRAGANZA AVE, MIAMI, FL 33133 Inspection Requests: Description: INSTALLATION OF NEW CONCRETE PANEL Valuation: $ 199,574.00 Ins 762 4949 SEAWALL, NO MORE THAN 12" WATERWARD OF EXISTING SEAWALL. ALSO PROPOSES TO INSTALL NEW CONCRETE Total 5q Feet: 0.00 BATTER PILES AND A NEW CONCRETE SEALWALL CAP. Fees Amount Application Fee - Other $50.00 CCF $120.00 Change of Contractor $110.00 DBPR Fee $89.81 DCA Fee $59.87 Education Surcharge $40.00 Permit Fee $5,937.22 Planning and Zoning Review Fee $35.00 Scanning Fee $9.00 Structural Review ($90) $90.00 Technology Fee $149.68 Total: $6,690.58 Building Department Copy Payments Date Paid Amt Paid Total Fees $6,690.58 Credit Card 11/19/2019 $50.00 Check # 3507 12/17/2019 $6,530.58 Credit Card 04/12/2021 $110.00 Amount Due: $0.00 In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations pertaining thereto and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores Village. In accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate permits are required for ELECTRICAL, PLUMBING, MECHANICAL, WINDOWS, DOORS, ROOFING and SWIMMING POOL work. OWNERS AFFIDAVIT: I certi that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulati0q constructioixand zoning\ Futhermore, I authorize the above named contractor to do the work stated. re: Owner / Applicant / Contractor / Agent Date April 12, 2021 Page 2 of 2 Miami Shores Village 10050 NE 2 Ave Miami Shores FL 33138 305-795-2204 Permit NO.: WSW-1 1 -19-2759 Permit Type: Retaining Walls/Seawalls Work Ciossificatforr: Seawall Issue Date: 01/13/2020 Location Address Parcel Number 1420 NE 101ST ST, Miami Shores, FL 33138 1132050230050 Contacts Expiration: 07/ 13/2020 ELIZABETH ALLEN Owner CASE MARINE CONSTRUCTION Contractor 1290 NE 102 ST, MIAMI SHORES, FL 331382618 INTERNATIONAL LLC JOSEPH WOODWORTH 429 LENOX AVE, MIAMI BEACH, FL 33139 Business: 3056134241 joey@caseconstructionco.us Description: INSTALLATION OF NEW CONCRETE PANEL Valuation: $ 199,574.00 Inspection Requests: SEAWALL, NO MORE THAN 12" WATERWARD OF EXISTING li65-762-4949 SEAWALL. ALSO PROPOSES TO INSTALL NEW CONCRETE Total Sq Feet: 0.00 BATTER PILES AND A NEW CONCRETE SEALWALL CAP. Fees Amount Application Fee - Other $50.00 CCF $120.00 DBPR Fee $89.81 DCA Fee $59.87 Education Surcharge $40.00 Permit Fee $5,937.22 Planning and Zoning Review Fee $35.00 Scanning Fee $9.00 Structural Review ($90) $90.00 Technology Fee $149.68 Total: $6,580.58 Payments Date Paid Amt Paid Total Fees $6,580.58 Credit Card 11/19/2019 $50.00 Check # 3507 12/17/2019 $6,530.58 Amount Due: $0.00 Building Department Copy In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations pertaining thereto and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores Village. In accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate permits are required for ELECTRICAL, PLUMBING, MECHANICAL, WINDOWS, DOORS, ROOFING and SWIMMING POOL work. OWNERS AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. Futhermore, I authorize the above named contractor to do the work stated. 1/13f7—C� Authorized Signature: Owner / Applicant / Contrac)or / Agent Date January 13, 2020 Page 2 of 2 Miami Shores Village f Zi_: I(z;I � BUILDING PERMIT APPLICATION Building Department 10050 N.E.2nd Avenue, Miami Shores, Florida 33138 B Tel: (305) 795-2204 Fax: (305) 756-8972 INSPECTION LINE PHONE NUMBER: (305) 762-4949 FB 20 Master Permit No. RC-5-18-118 Sub Permit Now _ - 1 l — l 9 BUILDING ❑ ELECTRIC M ROOFING PLUMBING ❑ MECHANICAL ❑PUBLIC WORKS JOB ADDRESS:1420 NE 101 STREET ❑ REVISION ❑ EXTENSION []RENEWAL Q CHANGE OF CANCELLATION ❑ SHOP CONTRACTOR DRAWINGS 33138 Folio/Parcel#:113ZU5UZjUUt)U Is the Building Historically Designated: Yes NO Occupancy Type: Load: � �I Construction Type: Flood Zone: BFE: FFE: OWNER: Name (Fee Simple Titleholder): 1d1ATTH EW ALLF NI 3056732847 Address:1420 NE 101 STREET Ciiy: 1d20 CIF 101 STREET �,.,e. FLORIDA Zip: 33138 Tenant/Lessee Name: Email: CONTRACTOR: Company Name: KEARNS CONSTRUCTION COMPANY Phone#: 305.461.0310 Address: 2550 S BAYSHORE DR STE 206E City: MIAMI State: FL gyp; 33133 Qualifier Name: CHARLES KEARNS Phone#: 786.295.1717 — - State Certification or Registration #: CGC060194 Certificate of Competency #: N/A DESIGNER: Architect/Engineer: Phone#: FLOMOA Address: City: State Zip: Value of Work for this Per.^.^.:i: Type of Work: ❑ Addition ❑ Alteration Description of Work: Specify color of color thru tile: Submittal Fee $ Permit Fee $ scanning Fee $ Radon Fee $ Square/Linear Font:�,a of W^•k' - 0 New ❑ Repair/Replace ❑ Demolition CCF $ CO/CC $ DBPR $ Notary S Technology Fee $ Training/Education Fee $ Double Fee $ Structura! Bond 1i TOTAL FEE NOW DUE $ _ !,^_':=j02/24/2014) Bonding Company's Name (if applicable) Bonding Company's Address City State Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip Tip Application Is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. 1 understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS, FURNACES, BOILERS, HEATERS, TANKS, AIR CONDITIONERS, ETC..... OWNER'S AFFIDAVIT: I certify that all the foregoing information Is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. "WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT." a Notice to Applicant: As a condition to the issuance of a building permit with an estimated valye'ljrceeding $25W, the dpplicpnt must promise in good faith that a copy of the notice of commencement and construction lien brochure will be delivered to the person whose property is subject to attachment Also, a certified copy of the recorded notice of 96prfthcement must be posted at the job site for the first inspection which occurs seven (7) days after the building permit is Iss I 'the absence of such posted notice, the inspection will not be approved and a reinspection fee will be charged. Signature OWNER or AGENT The foregoing Instrument was acknowledged before me this 2 day of MIL_ 20 , by G who is personally known to me or who has produced «u l —cekn , as identification and who did take an oath. NOTARY PUBLIC: CONTRACTOR The forego instrument was acknowledged before me this 20• y' day of dOV'�ri 20 , by who I personally known to me or who has produced as identification and who did take an oath. NOTARY PUBLIC: G Sign: Sign: Print: 0• Print: ?, -: Seal: Seal: AURA ALZA T;2023 W COWSSION N G33 EXPIRES:ApW 11 Puftftm APPROVED BY Plans Examiner Structural Review "ftry ftft State of Flaricia • YuwleidY De La Caridad Vazquez Suarez OF ON * Carmt g3= HH 033993 ### Zoning Clerk (Revised02/24/2014) Miami Shores Village Building Department 10050 NfInd Avenue Mimi Shores, Ronda 33138 Tel: (305)795.2204 Fax; (305) 756.8972 CHANGE OF CONTRACTOR / ARCHITECT Permit N. '01aS01-11-19-2 50 Owner's Name jFre Siomnple Title Holder,. M�ATi VII-i.': AND ELIZA SETH ALLEN Phone #: Owners Address, 1290 NL 102_TFsEET 78H-423- 0T6 OW 1MLAMI ,4.1QRr - Sore : � to Ogrf,-t Zip Cade -_ms Aii job Address AOfwhcrc wm* i% t%eing d-oneb: 14X !NE 1011 STREET - City: -- _ _Miami Shores __ State ---Florida zip Code- _ 3..il3a CAIJV MARINE CONSSTR:LIE`T DN IN U-NNI TI1�4K�4�1�JiC Corftraetor's Company Name - Addr��- Cif 4d1AMb BLACK State: FLOW-C-A == Zip Code: 331�'�— Lir. Number.`- `ram Quahl�r-r'sN�me:.JC`.z"..�-'►la�'":�f--�`►•.��°t}! _ ° �- - Arc hitecd€npinecr of Record NanreZ NAMI_G E-Nt-;1N L FRING S-OLLM- n-- JS INN Phone' 305-921-9344 Address: :� htly�Ri.;A AU1=MiJE. �I_flfiC 7 City- -- CORAL GABLES State, rL01410A Zip Code: iio3+t Describe Work — INSTALLAT10N OF NFIW 9Ea 01ieI I 305 6113-4241 I hereby certify that the work has been abandoned and/or the contractor/architect is unable or unwilling to complete the contract. I hold the Building Official and the Miami Shores harmless of all legal involvement. Signature Signature -- Cc rm=r cr Ar¢Frta TI►r forE%Gln}; instrument was. akkn�naw�"edgc_tAj�r�l (w-f lre nee ww''''�� ll The I'mr-�gong mUvi,ilte iE W3S aknowbtdr-d Wore 10t &5<O clay of .i' ZOIrsy� Ally [MI5 �r-v day of �JOV([t- r 20 bb I'y J1 p Who ,s persnnaily Known to one or who his produced T l lV5z_ -_ as indefltifi�lntion" Notary Public, r Sign: Sea'"-,j ;pt'K' sy my comw xyi 0 GG 32493MEX+.^ a,a 1T, 2UBelld ThN Num WI who a a nicav who has produtcd as u-identelicaur_cn. No Public: Sq2tv SK21 se31- ��, Tom' L2�mllft�_fl/�j3`�?M