Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
CC-07-21-1905_BUILDING RECERTIFICATION
Miami Shores Village Building Department 10050 N.E.2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2207 Fax: (305) 756.8972 BUILDING RECERTIFICATION Date: March 31, 2025 Permit No. CC-07-21-1905 To: Davinella, LLC 9165 Park Dr. Miami Shores, Florida 33138 Re: 50 years Building/Electrical Recertification. Folio 11-3206-014-1350 9165 Park Dr. Miami Shores, Florida 33138 The Village of Miami Shores Building Department received and reviewed the Building Structure and Electrical System recertification report dated March 5, 2025, by Ricardo L. Hernandez, Florida license number AR0013379. Based on the reports provided, the building on the above referenced property was found to be structurally and electrically safe for its continued use and occupancy. This Letter of Recertification is granted for the building on this property. The Recertification expires on the 60 year anniversary from original construction date. At that time, a new Recertification Report must be submitted to the Building Official. Although this Letter of recertification allows continued occupancy of the building, issuance of this letter does not preclude the Building Official from carrying out his responsibilities under Section 8-5 of the Code of Miami -Dade County. Further, issuance of this letter shall not be construed directly, or indirectly, as a guarantee of the safety of any portion of the structure. As per Miami Dade County Code Sec. 8-11. - Existing buildings. (a)The requirements contained in the Florida Building Code, shall apply to all buildings and/or structures now existing or hereafter erected. All buildings and/or structures and all parts thereof shall be maintained in a safe condition, and all devices or safeguards that are required by the Florida Building Code shall be maintained in good working order. Electrical wiring, apparatus and equipment, and installations for light heat or power and low voltage systems as are required and/or regulated by the Building Code, now existing or hereinafter installed, shall be maintained in a safe condition and all devices and safeguards maintained in good working order. Thank you for your cooperation in this matter. Sincerely, Ismael Naranjo, BO, CFM Building Director. �ARICBUILDERS AND GROUP INC. THE RECERTIFICATION SPECIALIST FOR THREE DECADES MAR 11 N25 r If Jy-�J 7301 SW 83 CT MIAMI, FL 33143 Tel - 305.275.6310 Fax - 888.744.8925 w .arcbuildersand9roup.cotn RE: l 1-3206-014-1350 (Folio #) C /� ^o-_^ I _ nos DATE: 03-OS-2025 OWNER NAME: DAVINELLA LLC 1. L "1 PROPERTY ADDRESS: 9165 PARK DR, MIAMI SHORES, FL 33138 City of Miami Shores Building Department ) MI� J Dear Mr. Ismael Naranjo, Building Official: Based on my evaluation as attached hereto of the aforementioned property, this building is structurally and electrically safe for its use and present occupancy as provided for "'Re -Certification. Therefore, on behalf of my client, I am respectfully requesting that this building(s) *be granted Re- certification per Section 8-11 (f) of the Miami Dade County Code. As routine matter, in order to avoid possible misunderstanding, nothing in this report should be construed directly or indirectly as a guarantee or warranty for any portion of the structure(s). To the best of my knowledge and ability, this report represents an accurate appraisal of the applicable and present condition of the building(s) based upon the careful evaluation of the observed conditions and documentation as provided by property owner, to the extent reasonably possible. Further it is understood by all parties to include the property owner that the recommendation for "'Re -Certification by ARCBuilders and Group, Inc., or the granting of "'Re -Certification by the Building Department does not release or indemnify the property owner in any way or form from properly maintaining the subject property safe for continued use and occupancy at all times. �N ThanGHemandez our attention to this matter. OF FLO ............. 0HE,?, ' .% QQ ya�': Very, �/�I C RickCapote, A.I.A. Ill it it — *_ President, AR0013379 f Dade County Building and Roofing Inspector BN2418 �1'., AR0013379 Special Inspector State of Florida No.0976 A �C'STFRED PR� Additional Comments: 'This report is prepared and is to be submitted to the Building Official as may be required for Re -Certification as referenced above, this report is not intended to be a buyer/seller inspection report nor is it to be used for any other purpose than that specifically stated herein. Arebuildim and Group, Inc makes no claim as to the validity of any documentation provided by owner and which we further rely on for accuracy.to include but not limited to: Microfilm, Permit History, Violation Search, Lien Search, which may have been reviewed and attached for purposes of this report. This report is not a zoning or code compliance report. Existing cast iron sanitary plumbing lines are not pan of this report. The contents of this report are based on applicable areas made accessibleat the time of the scheduled inspection, all other areas are excluded. No testing by this firm is pan or this report. Testing provided by third parties contacted by Ownership and which we rely on for validity may be attached as reference and for review only. 'this report is not to be copied, faxed, or altered in any way, additionally unless digitally sealed and verified as one PDF document each page must bear the original signature and seal on each page, or all contents is void and null. There is no warranty or guarantee expressed or implied and this document is not transfemabie to any person or entity for any purpose. Any repairs/corrections/alterations must be perfumed in compliance with FBC, NEC and all applicable codes and ordinances. Should any violations or open permits exist all must be corrected prior to granting of Re -Certification. Accordingly, the Building Official a his or her discretion or interpretation of the applicable codes may refuse to grant a recommendation of Re - Certification. This report is limited to the items specifically included by the Section 8-11 (1) of the Code of Miami -Dade County and dues not include many aspects of compliance to include but not limited to ADA, plumbing zoning Fair Housing, NFPA, nr certification of building code compliance. MIAMI•DADE 11 W.. Regulatory and Economic Resources 11805 SW 26th Street Miami, Florida 33175-2474 786-315-2000 miamidade.gov/building CERTIFICATION OF COMPLIANCE WITH PARKING LOT GUARDRAILS Re: Case No. CC-07-21-1905 FYear 1970 Property Address: 91"PARK DR, MMI' ORES, RM1 B, Bldg. No.:1 Sq. Ft.: 7,858 Building Description: CBS - One Story - Professional Service Bldg: Health Care I am a Florida registered professional ED engineer M architect with an active license. On February 2025 ,I inspected the parking lots servicing the above referenced building for compliance with Section 8C-6 and determined the following (check only onel: MThe parking lot(s) is not adjacent to or abutting a canal, lake, or other body of water. FLIThe parking lot(s) is adjacent to or abutting a canal, lake or other body of water and parked vehicles are protected by a guardrail that complies with Section 8C-6 of the Miami- Dade County Code. ❑❑ The parking lot(s) is adjacent to or abutting a canal, lake or other body of water and parked vehicles are not protected by a guardrail that complies with Section 8C-6 of Miami -Dade County Code. I have advised the property owner that he/she must obtain a permit for the installation of the guardrail and obtain all required inspection approvals to avoid enforcement action. of FLOR/Q Signature and Seal of Architect or Engineer 5.��0 �Y�'•: arMEMEMNOW V tit` 'Rua I.- 4WM*t* Q�Vs� LAU Print Name AR0013379 ; v r %� •. : ,ski c/STFRED Date I Ll- M IAM I•DADE '® ~ Regulatory and Economic Resources 11805 SW 26th Street Miami, Florida 33175-2474 786-315-2000 miamidade.gov/building STAN Date: 03-05-2025 Case No. CC-07-21-1905 FYear 1970 PropertyAddress: 9165 PARK DR, MIAMI SHORES, FL 33138 Bldg. No.: 1 , Sq. Ft.: 7,858 Folio Number. 11-3206-014-1350 Building Description: CBS - One Story - Professional Service Bldg: Health Care 1. 1 am a Florida registered professional engineer FE architectwith an active license. 2 On, 20 25, February at 6:45 ❑ AM Fm�PM, I measured the level of illumination in the parking lot(s)serving the above referenced building. 3. Maximum5•0 footcandle Minimum 1.0 footcandle Maximum to Minimum Ratio 5 1 , footcandle 4. The level of illumination provided in the parking lot[EmeetsQ does not meet the minimum standards for the occupancy classification of the building as established in Section 8C-3 of Miami -Dade County Code.. V. HEq Seal ofProfe%Iot* �Print Name Engineer orArchitect A &* A �m AW MIMI a REGULATORY AND ECONOMIC RESOURCES DEPARTMENT 11805 SW 26`h Street, Miami, Florida 33175 786-315-2000 Miamidade.gov/building CASE REFERENCE NUMBER: LICENSEE NAME: Rick Hernandez-Capote CC-07-21-1905 JURISDICTION NAME: Miami Shores Registered Architect - AR0013379 7301 SW 83 CT Miami, FI 33143 *Use separate sheets for additional responses by referencing the report section number. �.HE 1. DESCRIPTION OF BUILDING TARED P� Sge a. Name on Title: DAVINELLA LLC b. Building Street Address: 9165 PARK DR, MIAMI SHORES, FL 33138 Bldg. #: 2 c. Legal Description: MIAMI SHORES SEC 2 PB 10-37 ... Attached: d. owner's Name: Same as title e. Owner's Mailing Address: 9165 PARK DR, MIAMI SHORES, FL 33138 f. Folio Number of Property on which Building is Located: 1 1-3206-014-1350 g. Building Code Occupancy Classification: Business Occupancy - Group B, FBC 2023 / Ch. 3 Section 304.1 h. Present Use: Commercial Building -Professional Service Building: Health Care i. General Description of building (overall description, structural systems, special features): CBS, One-story, per Dade County Property Appraiser was built 1970 and has 7,858 ASF. j. Number of Stories: 1 k. Is this a Threshold Building' as per 553.71(12) F.S. (Yes/No): No I. Provide an aerial of the property identifying the building being certified on a separate sheet. Attached: ❑� m. Additional Comments: This report is not a Buyers Report, Due Diligence, Insurance Inspection, Mitigation Document or for any other purpose other Nan W be prepared and submitted to the Building Official solely in accordance and with the purpose of compliance with Section 8-11 (f) of the Code of Miami -Dade County, any other use is strictly prohibited and voids all content. This report must bear the ,d ti ... bossed a. ian sad, �,u . It , Metal of at T 1. 13,0 t Is 1 .1 tin.—femb o to an, . t,. en,ying, both , at dia, a 'y statistic, of 0 s repalt Is shictly in oil and voids all content. Both Building (Structural) and Electrical Reports must be attached and accompanied by a cover letter to the building official. As muting matter, in order to avoid possible misunderstanding, nothing in this report should be construed directly or indirectly as a guarantee for any portion of the structure(s). We rely on the validity of documentation provided by owner conducted of areas and components as made acoessible by property owner. Existing cast Iron sanitary pluming lines are not part of this report. Any repamialteregons/modlfcations must be in compliance with FBC, NEC and all applicable codes and ordinances. If any violations or open permits exist all must be connected prior to granting of Re-CeNfication. Further, it is understood by liability d continuously verify, correct. repair, and maintain all components of this building safe for continued use and occupancy whether Included in this limited inspection report or mt. MDC Building Recertification Structural Report Page 1 of 14 12/23111.3 s :. n. Additions to original structure: No additions to original structure as per property appraiser. lines, meters and appliances and equipment are specifically excluded for purposes of this report, however we urge property ewpielc t9 take any and a" neeessaFy ffeleautiens te ersupe that these iterns aFe ppepedy maintained is pfeteet pfflpelcty aFld above all life safety. o. Total Actual Building Area of all floors: 7,858 S.F. 2.INSPECTIONS a. Date of Notice of Required Inspection: 01 -29-2025 (Final Notice) b. Date(s) of actual inspection:02-18-2025 c. Name. license number, discipline of practice, and qualifications of licensee submitting report: Rick Hernandez-Capote, R.A. AR0013379. d. Description of laboratory or other formal testing, if required, rather than manual or visual procedures: N/A: ❑�/ Visual observallons conducted at present. No visible distress noted. This report is a "snapshot" of observed conditions of accessible and applicable components on the day of inspection. No testing is part of This report. Additionally, we rely on the votlidity of documentation as may be provided by owner for repairs performed to their pmpedy and for which they are solely responsible and liable for assuring they meet proper compliance with all applicable bodes and life safety. Omer is to conduct proactive preventive maintenance to include any possible testing that may be necessary. It is the tp continuously verify, correct, repair, and maintain all components of the building, whether included in this limited inspection report ornol, to assure building is safe for continued us e. Are Any Structural Repairs Required? (YES/NO): NO 1. If required, describe, and indicate acceptance: n if V N/A AR0013379 r O . f. Can the building continue to be occupied while recertification and repairs are ongoing? (YES 1. Explanation/Conditions: Good condition for age and use of structure. No visible distress noted. Any required correct-ions/repairs/alterations must be In compliance with and all applicable codes an ordinances, This report is not for bidding or for permitting purposes, Additionally. property owner is responsible and liable to continuously maintain property safe for continued use and occupancy. g. Is it recommended that the building be vacated? (YES/NO): No h. Has the property record been researched for violations or unsafe cases? (YES/NO): Yes 1. Explanation/Comments: Additionally, prior to any future repairs and modifications, Ownership, General Contractor, and all other trades to taKe all satety precautions ancl per sae guars during construction Uh. 33 and UZ5HA MDC Building Recertification Structural Report Page 2 of 14 12/23111.3 1 3. SUPPORTING DATA (Reference all photos indicated in report with corresponding section number) a. 0 Number of Additional sheets of written data b. 20+ Number of Photographs provided (plus each building elevation) C. 9 Number Drawings or sketches provided (aerial, site, footprint, etc.) d. 2 Number of Test reports attached 4. FOUNDATION a. Describe the building foundation: Seemingly foundation concrete slab on fill with continuous stem wall and steel reinforced concrete footers. Seemingly all integrated, structurally ie oge er, and time -tested. No walls nor floor settlement observed (interior as well as exterior conditions). b. Is wood in contact or near soil? (Yes/No): No c. Signs of differential settlement? (Yes/No): No d. Describe any cracks or separation in the walls, columns, or beams that signal differential settlement: , None observed �� OF .FL.. 5: DO e. Is water drained away from the foundation? (Yes/No/Needs Repair): Yes f. Is there additional sub -soil investigation required? (Yes/No): No 1. Describe: rERED ARC' N/A S. PRESENT CONDITION OF OVERALL STRUCTURE a. General alignment: (Note: good, fair, needs attention, explain if significant) • • - 1. Bulging: Good Good, for age of structure. 2. Settlement: Good Good, for age of structure. 3. Deflections: Good Good, for age of structure. 4. Expansion: Good Good, for age of structure. 5. Contraction: Good Good, for age of structure. MDC Building Recertification Structural Report Page 3 of 14 12/23111.3 y,..r � "!! p.� �.. � 9 �: � � �� .. .:# b. Portion showing distress: (Note, beams, columns, structural walls, floor, roofs, other) " • • • Good condition for age and use of structure. No visible distress noted. Any required correc Ions repairs a iterations must be in compliance with FBC, NEU and all applicable codes an ordinarlirps This report is not for hirlding nr for permitting pi irposps Additionally. prnppdy owner responsible and liable to continuously maintain property safe for continued use and occupancy. c. Surface conditions: Describe general conditions of finishes, cracking, spalling, peeling, signs of moisture penetration and stains. , , • • • • Good condition for age and use of structure. Surface conditions have good appearance 40 years +. No visible distress noted. is the owners responsibility to continuously verity, correct, repair, an assure building is safe for continued use and occupancy. d. Cracks: Note location in significant members. Identify crack size as HAIRLINE if barely discernible; FINE if less than 1 mm in width; MEDIUM if between 1- and 2-mm width; WIDE if over 2 mm. • • • • Hairline (Barely Discernable) Good condition for age and use of structure. No visible distress noted. It is the owners responsibility to continuously verify, correct, repair, an main ain a nnirnpnnents nf this hi dirionq whethpr inch irlpri in this limited re.port not, to assure building is safe for continued use and occupancy. e. General extent of deterioration: Cracking or spalling of concrete or masonry, oxidation of metals; rot or borer attack in wood. , , • • • • - Good condition for age and use of structure. No visible distress noted. Provide continued observations and inspections fbi tennites and othei possible agents that may cause deterioration, due to aye of building. Also, pivactive! preventive maintenance should be practiced. No testing for termites, other pest, deteriorating agent, contaminant or other is part ot this examination or report. Fumigation to be provided on a regular basis by owner as neeclecl. f. Previous patching or repairs (Provide description and identify location): • • • Continue preventative maintenance and repairs as may be necessary. It is the owner's responsibility to continuously verify, in r, a id naintain all ws i poi je, its of this buildi. ig, wl reb re. included this limited epul t 01 rot, to assure building is safe for continued use and occupancy. g. Nature of present loading: (Indicate residential, commercial, storage, other.) Commercial Structural commercial loading remains stable - built in 1970. The structural loads and loading systems such Leads as walls, eeillng, fleeFs, beams, and ealumns, refrains with eafniplete struetUFS! afe eeluell distributed throughout the envelop of the structure, per visual observations. h. Signs of overloading? (Yes/No): No �� f I. Describe: 5 N/A jo :* NW MDC Building Recertification Structural Report Page 4 of 14 6. MASONRY BEARING WALL: (indicate good, hir,needs reironappropriatelines) This section❑ � is N/A! ,•• • •• a. Concrete masonry units: Good Good, for age of structure. b. Clay tile or terra cota units: N/A NSA c. Reinforced concrete tie columns: Good Good, for age of structure. d. Reinforced concrete tie beams: Good Good, for age of structure. e. Lintel: Good Good, for age of structure. f. Other type bond beams: N/A N/A "• • • g. Exterior masonry finishes (choose those that apply): 1. stucco: Good Good, for age of structure. 2. Veneer: Good Good, for age of structure. 3. Paint only: Good Good, for age of structure. 4. Other (describe): N/A N/A h. Interior masonry finishes (choose those that apply): • • . 1. Vapor barrier: Good Good, for age of structure. 2� 0 • • i-LoRi 2. Furring and plaster: Good Good, for age of structure. `':� •°y , c 3. Paneling: Good Good, for age of structure.Ar 4. Paint only: Good Good, for age of structure. 5. Other (describe): N/A N/A ERED RRG f i. Cracks: E a NOW 0 • • 1. Location (note beams, columns, other): Exterior bearing walls 2. Description: Normal age stress cracks hairline, fine to medium sizes j. spalling None Observed "• • • • 1. Location (note beams, columns, other): None observed 2. Description: N/A MDC Building Recertification structural Report Page 5 of 14 12/23111.3 ,• �'`<.. 1 cif: n u.� " B 9 , e. ,. k. Rebar corrosion (indicate worst case by selecting one from lines 1-4): " • • • • 1. None visible: ❑� 2. Minor (patching will suffice): 3. Significant (but patching will suffice): ❑ 4. Significant (structural repairs required) oF R I. Samples chipped out for examination in spalled areas (Yes/No): NO <P: ' p �• HERH 1. Yes— describe color, texture, aggregate, general quality: ;' vQ �•; N/A •U i 7. FLOOR AND ROOF SYSTEM a. Roof (Must access and provide) 1. Describe (roof shape, type roof covering, type roof deck, framing system, condition): • • • • -Flat roof, built-up ply over twin tee concrete deck (typical) seemingly in good condition for age of building as visibly observed at unl s areas made accessible at time —of inspection. -Hip roof.barrel tile over prefab roof trusses and plMood roof sheathing (Iypical)seemingly in good condition. Please refer to roofing permit No. RF-10-12-1946 and final inspection. 2. Note water tanks, cooling towers, air conditioning equipment, signs, other heavy equipment and condition of supports: , , • • • • Central rooftop A/C equipment, seemingly secure. 3. Describe roof drainage system, main and overflow, and indicate condition: • • • Scuppers, downspouts, and gutters: Good condition for age of structure. 4. Describe parapet build and current conditions: • • • • . , Perimeter concrete beam parapet: Good condition for age of structure. S. Describe mansard build and current conditions: • • • • Perimeter wood -frame mansard seemingly in good condition for age of building as visibly observed at urns areas made accessible at time of inspection. MDC Building Recertification Structural Report Page 6 of 14 12/23111.3 6. Describe roofing membrane/covering and current conditions: • • • • • Built-up ply over twin tee concrete deck (typical) for flat roof: Good condition for age of structure. fef for Beffel tiles ever pFefebriested weed tFUSS fFElffling (typies') menewd and hip FOef-'. Geed eeigElifien age and Please refer to the structural photo documentation. use ef stfuetwe. 7. Describe any roof framing member with obvious overloading, overstress, deterioration or excessive deflection: .. • • • N/A 8. Note any expansion joints and condition: • . • • • Seemingly well fitted and still closed as visibly observed for age and use of structure. b. Floor system(s): 1. Describe the floor system at each level, framing, material, typical spans and indicate condition: .• • 0 • • , Concrete slab on fill, first floor: Good condition for age of structure. 2. Balconies: Indicate location, framing system, material, and condition: N/A: • • • • , None observed. 3. Stairs and escalators: indicate location, framing system, material, and condition: N/A: • • • • • • , None observed. 4. Ramps: indicate location, framing type, material, and condition: N/A: • • • None observed. 5. Guardrails and handrails: describe type, material, and condition: N/A: z . • • • • • , None observed. c. Inspection — note exposed areas available for inspection, and where it was found neces c t inspection of typical framing members. 0 : ' p L. H or Visual observations conducted of open accessible framing. N; 13379 ;'ff MDC Building Recertification Structural Report Page 7 of 14 It 3R1.3 D AR��\ J 8. STEEL FRAMING SYSTEM This Section is Not Applicable: a. Description of system at each level: " PROVIDE PHOTO 8 - None observed. b. Steel members: describe condition of paint and degree of corrosion: " • • • • N/A c. Steel connections: describe type and condition: " • • • • N/A d. Concrete or other fireproofing: note any cracking or spalling of encased member and note where any covering was removed for inspection: , , • • , • • , Visual observations done of open accessible areas on day of inspection. e. Identify any steel framing member with obvious overloading, overstress, deterioration, or excessive deflection (provide location): .. • • • • . _ N/A f. Elevator sheave beams and connections, and machine floor beams: note condition: N/A: " • • • • None 9. CONCRETE FRAMING SYSTEM This Section is Not Applicable: a. Full description of concrete structural framing system: ..• • • • ' Concrete masonry units (C.M.U.), foundation concrete slab on fill with continuous stem wall and steel reintorced concrete tooters, concrete tie beams, tie columns. b. Cracking " • • • • '' 1. Significant 1:1or Not significant W]: Normal age stress cracks. 2. Location and description of members affected and type cracking: OF F(p Exterior bearing walls - hairline cracks. •a ,�acuvio�ra .-•� MDC Building Recertification Structural Report Page 8 of 14 .3 /sTFRED ARG�\� c. General condition Seemingly stable concrete framing, built in 1970. No visible distress noted. It is the owner's responsibility to continuously verify, limited te eefFeet, Fepairt, and ffisintain all eampenents of this building, whetheF included in th a nspeetlen building is safe for continued use and occupancy. fepeft of met, assure d. Rebar corrosion — check appropriate line 1. None visible: Wl 2. Location and description of members affected and type cracking: N/A ✓❑ ' • • • ' • • • • 3. Significant but patching will suffice: N/A " • • • 4. Significant: structural repairs required (describe): N/A wl •' • • • • ' •' e. Samples chipped out in spall areas: 1. No:W1 ••• • • • •- 2. Yes, describe color, texture, aggregate, general quality: N/A f. Identify any concrete framing member (e.g. slabs and transfer elements) with obvious overloading, overstress, deterioration (e.g. efflorescence at underside of slab or at base of column or wall), or excessive deflection: • • • • N/A 10. WINDOWS, STOREFRONTS, CURTAINWALLS AND EXTERIOR DOORS a. Windows/Storefronts/Curtainwalls/Skylights 1. Type (Wood, steel, aluminum, vinyl, jalousie, single hung, double hung, casement, awning, 'LQ' '1 HF pivoted, fixed, other): C�); • p0 Storefront and affixed windows. ?¢ �r 2. Anchorage: type and condition of fasteners and latches: Good Machine screws and bolts attached to concrete casement frame. �S'TE'•'•••" r v MDC Building Recertification Structural Report Page 9 of 14 12/23R1.3 3. Sealant: type and condition of perimeter sealant and at mullions: Good Silicone caulking or silicone latex sealant: Good for age of structure. 4. Interiors seals: type and condition at operable vents: Good Silicone caulking or silicone latex sealant: Good for age of structure. 5. General condition: Good Good for age of structure, preventative maintenance should continue. It is the owner's responsibility to continuously verify, Ineluded limited Inspeetion eaffeet, repair, and maintain all eampanents of this building, whether in this repeft or not, to essufe building is safe for continued use and occupancy. 6. Describe any repairs needed: N/A b. Structural Glazing on the exterior envelope of Threshold Buildings (Yes/No): NO 1. Previous Inspection Date: N/A 2. Description of Curtain Wall Structural Glazing and adhesive sealant: N/A 3. Describe Condition of System: N/A c. Exterior Swing and Overhead Doors • • • • • 1. Type (Wood, Steel, Aluminum, Sliding Glass Door, other): OF FLQ E • Metal -frame out -swing doors with glazing. '�Q ' 0� HIPL 2. Anchorage: type and condition of fasteners and latches: Good Machine screws and bolts attached to concrete casement frame. ' V 3. Sealant: type and condition of sealant: Good �Sj'' " G Silicone caulking or silicone latex sealant: Good for age of structure. Is building, it the owner's responsibility to eantinuously YeFify, eeFfeet, fepaif, and maintain all eampaments of this whethef included in this limited inspection report or not, to assure building is safe for continued use and occupancy. MDC Building Recertification Structural Report Page 10 of 14 12/23R1.3 J 4. General condition: Good Good for age of structure, preventative maintenance should continue. It is the owner's responsibility to continuously verify, correct, FepaiF, and maintain all eempenents of this building, whetheF inS111FIRF1 in thk imited inspeetien FepeFt eF not, to asswe building is safe for continued use and occupancy. 5. Describe any repairs needed: Repairs Not Required N/A 11. WOOD FRAMING This Section is Not Applicable: a. Fully describe wood framing system: •' • • • • • Hip roof and perimeter mansard only: prefabricated wood truss framing, gable ends tied down straps o continuous concrete beams. Please refer to roofing permit No. RF-10-12-1946 and final inspection. b. Indicate the condition of the following: • . • • • , 1. walls: OF FLOR�� N/A c cj 2. Floors: ; F- N/A SST -RED P� 3. Roof member, roof trusses: Good Prefabricated wood trusses at hip roof and perimeter mansard only; gable ends tied down straps to continuous concre a eams: Good condition tor age and use of structure. c. Note metal connectors (i.e., angles, plates, bolts, split pintles, other, and note condition): •' • • • • Good Gusset plates nailed in place and steel straps tie -downs connected to the tie beams. d. Joints: note if well fitted and still closed: " • • • • The connections are well fitted. MDC Building Recertification Structural Report Page 11 of 14 12/23R1.3 • ,_,� :�, , ;. '��' -'R� �, '�' N 9 <i e. Drainage: note accumulations of moisture ..• • • • Seemingly watertight at time of inspection. f. Ventilation: note any concealed spaces not ventilated: ..• • ' • • All existing overhangs have continuous vents. g. Note any concealed spaces opened for inspection: " • • • • All visual observations. h. Identify any wood framing member with obvious overloading, overstress, deterioration, or excessing deflection): .. • • • • None observed, normal loading. 12. BUILDING FA ADE INSPECTION Threshold Buildings) This Section g ) is N/A: „• • • • a. Identify and describe the exterior walls and appurtenances on all sides of the building. (Cladding appliques, etc.) type, corbels, precast N/A oF.... O. C ' O� '¢ — b. Identify the attachment type of each appurtenance type (mechanically attached or adhered): N/A RED TEP� c. Indicate the condition of each appurtenance (distress, settlement, splitting, bulging, cracking, anchors and supports, water entry, movement of lintel or shelf angles, or other defects): loosening of metal N/A MDC Building Recertification Structural Report Page 12 of 14 12/23R1.3 13. SPECIAL OR UNUSUAL FEATURES IN THE BUILDING is NA is ection ❑✓ a. Identify and describe any special or unusual feature (i.e. cable suspended structures, tensile fabric roof, large sculptures, chimneys, porte-cochere, retaining walls, seawalls, signs, etc.) N/A b. Indicate condition of the special feature, its supports, connections, and if repairs are required: N/A F_ 14. UNDERGROUND OR LOWER -LEVEL PARKING GARAGES This section is N/A' CHECKLIST ITEMS TO CONFIRM OR CONSIDER FOR UNDERGROUND PARKING GARAGE: 14A. CURRENT BFE: ft. (Select Datum) Note: All elevation datums provided must be in the same datum as the Flood Insurance Rate Map (FIRM). 1. What is the wet season2 ground water elevation (water table): ft. (Select Datum) 2. What is the elevation of lowest parking garage finished floor: ft. (Select Datum) 3. What is the elevation of the parking garage entrance: ft. (Select Datum) 4. Is the wet season ground water elevation (water table) higher than the lowest floor elevation? Select (Yes pF FLp • 'HFR Explanation: N/A S. Is the garage entrance elevation lower than the base flood elevation? Select: (e r N5) Explanation: N/A a R E D P6G 6. List use of structure above the underground portion of the parking garage. (e.g. parking, terrace, occupiable space): Describe: N/A 7. Does underground parking structure show any evidence of bulging, settlement, cracking or deflection? Describe: Describe: N/A MDC Building Recertification Structural Report Page 13 of 14 12/23R1.3 8. Describe general surface conditions (cracking, spalling, peeling, or staining) Explanation: N/A 14B. 1. Do the parking garage slabs (overhead and floor slabs) and/or walls show evidence of leakage (efflorescence at the underside of slab or at base of column)? (Yes or No): Explanation: N/A 2. Is there any evidence of previous patching or repairs? (Yes or No): Explanation: N/A 'THRESHOLD BUILDING: In accordance with Florida Statute, any building which is greater than 3 stories or 50 feet in height, or which has an assembly occupancy classification that exceeds 5,000 square feet in area and an occupant content of greater than 500 persons. z WET SEASON: Compare the current Base Flood Elevation (BFE) on the latest FEMA Flood Insurance Rate Map (FIRM) with the October water table elevation shown in the Miami -Dade County Average Ground Water October maps available with the Miarr Department of Environmental Resource Management (DERM) 7 pROO13379 r'�RED PRG Reset Form f MDC Building Recertification Structural Report Page 14 of 14 12/23111.3 COUNTY , CASE REFERENCE NUMBER: CC-07-21-1905 JURISDICTION NAME: Miami Shores REGULATORY AND ECONOMIC RESOURCES DEPARTMENT 11805 SW 261h Street, Miami, Florida 33175 786-315-2000 Miamidade.gov/building LICENSEE NAME: Rick Hemandez-Capote rlrl c. Reaistered Architect - AR0013379 7301 SW 83 CT Miami, FI 33143 *Use separate sheets for additional responses by referencing the report section number. Ff. 1. DESCRIPTION OF BUILDING c/sj " •• •'' �G a. Name on Title: DAVINELLA LLC b. Building Street Address: 9165 PARK DR, MIAMI SHORES, FL 33138 Bldg. #: 1 c. Legal Description: MIAMI SHORES SEC 2 PB 10-37 ... Attached: ❑� d.Owner's Name:Same as title e. Owner's Mailing Address: 9165 PARK DR, MIAMI SHORES, FL 33138 f. Folio Number of Property on which Building is Located: 1 1-3206-014-1350 g. Building code occupancy classification: Business Occupancy - Group B, FBC 2023 / Ch. 3 Section 304.1 h. Present Use:Commercial Building - Professional Service Building: Health Care i. General Description of building (overall description, structural systems, special features): CBS, One-story, per Dade County Property Appraiser was built 1970 and has 7,858 ASF. j. Number of Stories: 1 k. Is this a Threshold Building as per 553.71(12) F.S. (Yes/No): No I. Provide an aerial of the property identifying the building being certified on a separate sheet. Attached: m. Additional Comments: This report is not a Buyers Report, Due Diligence, Insurance Inspection, Mitigation Document or for any other purpose other than to be prepared and submitted b the Building Official solely in accordance and with the purpose of compliance with Section 8.11 (f) of the Code of Miami Dade County, any other use is shictly prohibited and voids all conlenl. This report must bear the ll and voids all content. Both Building (Structural) and Electrical Reports must be attached and accompanied by a cover letter to the building official, As routine matter, in order to avoid possible misunderstanding, nothing in this report should be consbuea directly or indirectly as a guarantee for any portion of Me slmclure(s). We rely on the validity of documentation provided by owner conducted of areas and components as made accessible by property owner. Existing cast iron sanitary pluming Ines are not part of this report. Any repairslalleretionstmodificalions must be in compliance with FBC, NEC and all applicable codes and ordinances. If any violations or open permits exist all must be connected prior to granting of Re-CedRcagan. Further, it is understood by liability to continuously verify, correct, repair, and maintain all components of this building safe for continued use and occupancy whether included in this limited inspection repad or mi. MDC Building Recertification Electrical Report Page 1 of 9 12/23111.3 � p a f, .�I' NF,�,�.. s ir, 4 "r ;i 2. INSPECTIONS a. Date of Notice of Required Inspection: 01 -29-2025 (Final Notice) b. Date(s) of actual inspection: 02-18-2025 F FLO,q c. Name and qualifications of licensee submitting report: �Q� . HER4 , Rick Hernandez-Capote - Registered Architect - AR00133 d. Are Any Electrical Repairs Required? (YES/NO): No 1. If required, describe, and indicate acceptance: �kr e. Can the building continue to be occupied while recertification and repairs are ongoing? (YES/NO): Yes 1. Explanation/Conditions: Additionally, prior to any future repairs and modifications, Ownership, General Contractor, and all other trades to take all safety precautions and per FBC sae guars during 3. ELECTRICAL SERVICE • • • • • a. Size: Voltage( 240�) Amperage( 600 ) Type: Fuses ( ) Breakers (X ) b. Phase: Three -Phase (O ) Single Phase (® ) c. Condition: Good (O ) Fair () Needs Repair ( O ) Comments: Underground electrical service to from FPL transformer. Main electrical disconnect located at exterior rear wall (next to meter socket): Square D - 600amps. 4. METERING EQUIPMENT "• • • •' 1. Clearances: Good ( Fair (p) Needs Correction ( O ) Comments: Exterior -type metering equipment located at the rear East wall of the building. As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verify, correct, repair, and continued use and occupancy. MDC Building Recertification Electrical Report Page 2 of 9 12/23R1.3 S. ELECTRIC ROOMS Not Applicable: ❑ • • • • • • 1. Clearances: Good (O ) Fair (p ) Needs Correction (® ) Comments: Interior -type electrical service riser located at the rear East wall of the building. pF FLOC g O 6. GUTTERS Not Applicable: El • 1. Location: Good (Q ) Needs Repair ( 0 ) 2. Taps and Fill: Good ( O ) Needs Repair ( O ) Comments: Interior -type electrical service riser located at the rear East wall of the building. continuously verify, correct, repair, and maintain all components of this building, whether included in ti iis limited inspectioi i iepoi t ui not, to assuie building is safe foi continued use and occupancy. 7. ELECTRICAL PANELS . . 1. Panel # ( P #1 ) Location: Interior panel board - Square D - 400amps Good ( O ) Needs Repair ( ® ) 2. Panel # (P #Z ) Location: Interior panel board - Square D - 400amps Good ( Q ) Needs Repair ( O ) 3. Panel # (MDP ) Location: Interior panel board - 600amps Good ( Q ) Needs Repair ( ® ) 4. Panel # (G ) Location: Interior panel board - 400amps Good ( O ) Needs Repair ( O ) 5. Panel#(- ) Location: - Good ( O ) Needs Repair ( 0) Use separate sheets for additional panels. MDC Building Recertification Electrical Report Page 3 of 9 12/23111.3 k�a, •�1 ' �R. 3 :����� � � Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, and maintain all components of this buildin u �a ti 8. BRANCH CIRCUITS (Exiting panel enclosure) 1 ...• A • • • • 1. Identified: Yes (O ) Must be Identified (o ) �ST.'•""PpG FD Y- 2. Conductors: Good (� ) Deteriorated (© ) Must be ed (® ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verify, correct, repair, and maintain all components of this thig linnitpri qn,;pprtqnn report or not, to assure building is safe for cantimipc! building, whether imp. ;;nd ormipanry included In 9. GROUNDING OF SERVICE " • • • • ' Good ( O) Needs Repair ( ® ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, and maintain all components of this building, whetner incluaea In 10. BRANCH CIRCUIT EQUIPMENT GROUNDING SYSTEM • • • • • • • Good (O ) Needs Repair ( Q ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, and maintain all components of this building, whether included in MDC Building Recertification Electrical Report Page 4of9 12/23R1.3 11. SERVICE CONDUIT/RACEWAYS 0a 1.101TJ 111 lei I 16D Good ( • ) Needs Repair ( O ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verify, correct, repair, and maintain all components of this building, whether included In 12.GENERALCONDUIT/RACEWAYS "• • • • Good (� ) Needs Repair ( ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verify, correct, repair, and maintain all components of this building, whether included In 13.WIRE AND CABLES " • • • Good ( & ) Needs Repair ( ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, ana maintain all components of this building, whether included in 14.BUSWAYS Not Applicable: PROVIDE PHOTO 14 Good Needs Repair (0 �" , i;•�� MDC Building Recertification Electrical Report Page 5 of 9 1W BR '•• 1.3 ED ARCS r loy 1S.THERMOGRAPHY INSPECTION RESULTS Not Applicable: ❑ • • • • • • Design Professional to summarize results below. Attach thermography report by certified thermographer. Are there any anomalies reported in the thermography report? (Yes/No): No Comments: Please refer to passing Thermography Report by House of Ther thermal anomalies at time of inspection. g; o 40�3379 :�CiI 16.OTHER CONDUCTORS G'�s'' • Good (O ) Needs Repair (O ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, and maintain all components of this building, Whether included In c 17.TYPES OF WIRING METHODS " • • • •WA 1. Conduit Raceways Metallic: Good (Q ) Needs Repair ( 0 ) N/A ( ) 2. Conduit PVC: Good (O ) Needs Repair ( ® ) N/A (p ) 3. NM Cable: Good ( ) Needs Repair ( ®) N/A ( O ) 4. Other Conductors/Cables: Good ( ® ) Needs Repair ( ®) N/A ( O ) a. Other Conductors/Cables (Specify): Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, and maintain all components ot this building, whether included In 18.EMERGENCY LIGHTING "• • • • = Good (� ) Needs Repair ( ®) N/A ( ® ) Comments: Please refer to the Annual Fire Inspection Report from the Miami -Dade Fire Rescue Department citing no violations at present (re . perms - MDC Building Recertification Electrical Report Page 6 of 9 12/23111.3 19.13UILDING EGRESS ILLUMINATION •' • • • • Good (� ) Needs Repair ( O ) N/A (® ) Comments: S�n Please refer to the Annual Fire Inspection Report from the Miami -Dade Fire In no violations at present (re . permit - :¢ dam 20.FIRE ALARM SYSTEM • • • Good (O ) Needs Repair ( O ) N/A (p ) Comments: Please refer to the Annual Fire Inspection Report from the Miami -Dade Fire Rescue Department citing no violations at present (ref. permit - P r 21.SMOKE DETECTORS (Part of a fire alarm system only) Not Applicable: • . • • Good ( Q ) Needs Repair ( ® ) N/A (© ) Comments: Please refer to the Annual Fire Inspection Report from the Miami -Dade Fire Rescue Department citing no violations at present (ref. permit - 22.EXIT LIGHTS • • • • Good ( ) Needs Repair ( O ) N/A () Comments: Please refer to the Annual Fire Inspection Report from the Miami -Dade Fire Rescue Department citing no violations at present (ref. permit MDC Building Recertification Electrical Report Page 7 of 9 12/23111.3 Ar 23.EMERGENCYGENERATOR 0 a 1.160 191a 9 1. Lai• Good ( O ) Needs Repair (p ) N/A (® ) Comments: Exterior -type stand by power generator located at the roof area. S observed at time ot inspection based on age of structure. is the owners responsibility to this limited inspection report or not, to assure building is safe for continued use and occupancy. 24.WIRING IN OPEN OR UNDER COVER PARKING GARAGE AREAS • • • Good (� ) Requires Additional Illumination( ® ) N/A ( O ) Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verify, correct, repair, and maintain all components of this building, whetner included In 25.OPEN OR UNDERCOVER PARKING GARAGE AND EGRESS ILLUMINATION " • • • Good (� ) Requires Additional Illumination( ®) N/A ( ® ) Comments: As observed/measured at time of inspection based on age of structure. Property owner is to assure that continued proper lighting is times thmugh be for seemity pFevided at all pFeventive maintenamee, tipgrades or whatever fneans as may necessary compliance with section 8C-3 of the Code of Miami -Dade County. It is the owner's responsibility to continuously verify, correct, building, ineluded On limited inspeetien building is fepaif, and Fmaintain all earnponents of this whether this report er not, te assure safe for continued use and occupancy. 26.SWIMMING POOL WIRING •' • • • • Good (® ) Needs Repair ( 0 ) N/A ( e ) Comments: Aug N/A ''�O P_1�)_%�.�WAR001'3�3"79 NA MDC Building Recertification Electrical Report Page 8 of 9 =.., 12/23111.3 6 27. WIRING TO MECHANICAL EQUIPMENT " • • • •Wffm Good ( • ) Needs Repair ( ) N/A () Comments: As observed at time of inspection based on age of structure. It is the owner's responsibility to continuously verity, correct, repair, and maintain all components of this building, whether included In machinery or equipment which is for tenant use is excluded for the purposes of this report. 28. UNDERGROUND OR LOWER -LEVEL PARKING GARAGES N/A: ❑✓ =4111TJ I' a 9 1. Lei• CHECKLIST ITEMS TO CONFIRM OR CONSIDER FOR UNDERGROUND PARKING GARAGE: Number of Levels Below Grade Plane: •F' �•Q/� % A. Are the sump pumps operational? Select: (Yes/Need Repair/N/A) co...*, �O Explanation: N/A : cc B. If the elevator(s) travel below grade plane: v ;Pr , i9 1. Are they programmed to return to a level at or above BFE plus freeboard: Select: (Yes, No, Needs Repair, Will Retrofit): 'y'TERED I�Q' Explanation: N/A M 2. Are they equipped with sensors that prevent the cab from descending into a flooded hoistway? Select: (Yes, No, Needs Repair, Will Retrofit): Explanation: N/A C. Are the branch electrical circuits feeding devices below grade plane protected by a Ground Fault Circuit Interrupter (GFCI) breaker? Select: (Yes, No, Needs Repair, Will Retrofit): Explanation: N/A 29. GENERAL ADDITIONAL COMMENTS THIS REPORT IS NOT FOR BIDDING PURPOSES. Continue with proactive maintenance and provide repairs as may be necessary to maintain property sae tor continued use and occupancy. Please no e that this report does not include testing of any component. it as based on visual observations of applicable and accessible areas on day of inspection. Additionally, we rely on the validity of are solely responsible and liable for assuring they meet proper compliance with all applicable codes and life safety. Also, all CT and X-ray equipment is excluded for purposes of this report. R MDC Building Recertification Electrical Report Page 9 of 9 12/23R1.3 Miami Shores Village Building Department 10050 N.E. 2nd Avenue Miami Shores, Florida 33138 Tel: (305) 795.2204 FINAL NOTICE Notice of Required Building Recertification Date: January 29, 2025 To: Devinella LLC Re: 9165 PARK DR Miami Shores, FL 33138 Dear Owner: According to the information provided by the Miami Dade County Property Appraisers office the above referenced property has a building or structure that is fifty (50) years old or older. in accordance with Miami -Dade County Chapter 8 Section 8-11. the subject property must be inspected and re -certified by a Florida license architect or engineer. A building re -certification report signed and sealed by the Florida license engineer and or Architect along with the required fees shall be submitted to this office within thirty (30) days of receiving this notice. if you would like a copy of Minimum Inspection Procedural Guidelines for Structural and Electrical Recertification, or if you have any questions, please call my office at 305-795-2204. Sincerely, Ismael Naranjo, BO Building Director Email: bo@msvfl.gov Certified Mail #:9589071052701589461500 CC-07-21-1905 PROPERTY APPRAISER OF MIAMI-DADE COUNTY Summary Report Generated On: 03/03/2025 Folio 11-3206-014-1350 Property 9165 PARK DR Address MIAMI SHORES, FL 33138-3163 Owner DAVINELLA LLC Mailing Address 9165 PARK DR MIAMI, FL33138 Primary Zone 6800 COMMERCIAL - PROFESS OFF[ Primary Land 1943 PROFESSIONAL SERVICE BLDG : Use HEALTH CARE Beds / Baths 0/0/0 /Half Floors 1 Living Units 0 Actual Area 8,236 Sq.Ft Living Area 8,236 Sq.Ft Adjusted Area 7,858 Sq.Ft Lot Size 22,500 Sq.Ft Year Built 1970 Year 2024 2023 2022 Land Value $1,350,000 $1.350,000 $1,125,000 Building Value $923,158 $875,185 $884,909 Extra Feature Value $62,622 $63,300 $63,980 Market Value $2,335,780 $2,288,485 $2,073,889 Assessed Value $2,059,272 $1.872,066 $1,701,879 Benefit Type 2024 2023 2022 Non -Homestead Assessment $276,508 $416,419 $372,010 Cap Reduction Note: Not all benefits are applicable to all Taxable Values (i.e. County, School Board, City, Regional). MIAMI SHORES SEC 2 PB 10-37 SWLY1/2 LOT 24 & ALL LOTS 25 & 26 & NELY1/2 LOT 27 BILK 59 LOT SIZE SITE VALUE Year 2024 2023 2022 COUNTY Exemption Value $0 $0 $0 Taxable Value $2,059,272 $1,872,066 $1.701.879 SCHOOLBOARD Exemption Value $0 $0 $0 Taxable Value $2,335,780 $2,288,485 $2,073,889 CITY Exemption Value $0 $0 $0 Taxable Value $2,059,272 $1,872,066 $1,701,879 REGIONAL Exemption Value $0 $0 $0 Taxable Value $2,059,272 $1,872,066 $1,701,879 Previous Price OR Book - Qualification Description Sale Page 09/19/2011 $0 27839-0151 Corrective, tax or QCD; min consideration 05/09/2011 $725,000 27687-4007 Qua] by exam of deed 04/01/1971 $200,000 00000- 00000 Sales which are qualified The Property Appraiser is continually editing and updating the tax roll. This website may not reflect the most current information on record. The Property Appraiser and Miami -Dade County assumes no liability, see full disclaimer and User Agreement at http://www.miamidad e.gov/info/disclaimer.asp 3/3125, 2:51 PM Building Sketch Viewer 1 0 PROPERTY APPRAISER OF MIAMI-DADE COUNTY Building Sketch Viewer Folio: 11-3206-014-13SO Actual Area: Address: 9165 PARK DR Living Area: Owner: DAVINELLA LLC Adjusted Area: 8,236 Sq. Ft. 8,236 Sq. Ft. 7,858 Sq. Ft. Building Number: 1 of 1 Roll Year: 2024 Previous Next 5 1 ACA 20 9 OFF '--19—, 9�= OPU 5 4 4 ISO- 4 • OPU : Porch, Inserted • OFF: Office • ACA : Adjusted Commercial Area Click here to see all Sketch SubArea Descriptions Generated on: 3/3/2025 Disclaimer: The Office of the Property Appraiser is continually editing and updating the tax roll. This website may not reflect the most current information on record. The Property Appraiser and Miami -Dade County assume no liability. See full Liability Disclaimer and User Agreement. See full disclaimer and User Agreement at http://www.miamidade.gov/info/disclaimer.asp aboutblank 1/1 MIAMI-DADE FIRE RESCUE DEPARTMENT INSPECTION REPORT M(®MM FIRE PREVENTION BUREAU 9300 NW 41 ST STREET, DORAL, FLORIDA 33178-2424 (786) 331-4800 Date: 1 Permit Type: Business Permit Use: Business Offices CANCER HEALTHCARE ASSOCIATES Permit Status: Reinspected (45)1 Approved 9165 PARK DR Status Date: 1/1612025 MIAMI SHORES, FL 33138 Reviewed By: JOHNNYCE BOOKER Inspected By: JOHNNYCE BOOKER Phone: 786-913-9496 Inspected Address: Email: johnnyce.booker@miamidade.gov CANCER HEALTHCARE ASSOCIATES 9165-9165 PARK DR MIAMI SHORES, FL 33138 NOTICE OF VIOLATION AND ORDER TO CORRECT The hazards noted herein am in violation of the Florida Fire Prevention Code and/or Miami -Dade County Code and are deemed to be threats to life safety and/or property. You are hereby ordered to comply with the corrective measures prescribed. APPEALS: Any person who believes they were incorrectly issued a notice of violation or that the violation cited is not applicable to their occupancy dawifimbon or believes aggrieved by any action or decision of this code may appeal to the Miami- Dade County Fire Prevention and Safety Appeals Board by filing a written notice within 30 days of receiving the Notice or violation and Order to Correct. The appeal request most be submitted in writing to the Secretary of the Board. Information on filing an appeal can be obtained on the web at htto:/Mv+w.miamidade.aawfire/reouest-aooeal.aso. Filing of a written notice of appeal shall not stay the effect of any such action or decision which is the subject to the appeal. Section 14-36, Code of Miaml-Dade County, Created Comply By Code 11/26/2024 12/26/2024 FFPC 8th Edition, NFPA 1: 13.1.6 Violation: Failure to provide a current annual fire protection inspection and testing report. Status Corrected: 1/1512025 Correction: Provide detailed records documenting all systems and equipment testing and maintenance shall be kept by the property owner and shall be made available upon request for review by the AHJ. Comment: PROVIDE CURRENTANNUAL FIREALARM INSPECTION REPORT Note: A Life Safety Pemdl required by Section W39, Code of Miam-Dade County, to operate the above named occupancy v ill be issued upon correction of all outstanding violations and payment of fees assessed. Failure to obtain the required Dfe Safety Permitwill result In enforcement actions including fines. citations, Ilan and/or orders to cease and desist operation. Name: Title: How did we do? Page 1 of 1 Vile would like to about it. Scan the OR code to complete a survey. ors (13126A1921) ._ Printed: 1/15/2025 Version: 1 HOUSE OF THERMOGRAPHY INFRARED THERMOGRAPHY INSPECTION REPORT LOCATION OF INSPECTION: CANCER HEALTHCARE ASSOCIATES 916S PARK DRIVE, MIAMI SHORES, FL 33138 PREPARED BY: HERMES SOZA PRESIDENT LEVEL III MASTER THERMOGRAPHER admin(6@houseofthermography.com (786)-230-6065 a houseofthermography.com Digitally signed by Hermes Soza %.EVEL11/ DN: c=US, o=House ofThermography Qm.w<p.G ,pp,rE LLC, dnQualifier=A01410C00000190E51A3CC F0002927A, cn=Hermes Soza „efmas $p[a Unlfli°"'9031 Date: 2025.03.05 14:02:57-05'00' 'a�Ro tea' Adobe Acrobat version: 2024.005.20421 r t item has been digitally sby and sealed by Hermes Soza, Master Thermographer, � on the date adjacent to the seal. on haw Mr tR THER��G printed copies of this document are not considered signed and sealed and the signature \ must be verified on any electronic copies. Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 1. Table of Contents 1. TABLE OF CONTENTS ............... ........................................................ _......................................................................... 2 2. MIAMI-DADE COUNTY BORA MANDATE...............................................................................................................3 3. QUALIFICATIONS..........................................................................._..............................................................................6 4. EXECUTIVE SUMMARY........................................................................_......................_...............................................10 5. INSPECTION FINDINGS......................................................................_......................................................................J3 6. THERMAL ANOMOLY LIST......................................................................_.................................................................38 7. LIMITS OF STUDY........................................................................_..............................................................................39 House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 2 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofth 30-6065 1 admin(a'houseoftherm 2. Miami -Dade County BORA Mandate Department of Regulatory and Economic Resources Board Administration Section MIIAWDADE 11805 S.W. 26 Street (Coral Way) Rm. 230 mm Miami, Florida 33175 Tel (786) 315-2573 Fax (786)315-2570 www.miamidade.gov/development MEMO TO: All Building Officials in Miami -Dade County FROM: Secretary of the Board Board of Rules and Appeals (BORA) DATE: November 23, 2021 SUBJECT: BORA 40-Year Building Recertification General Considerations and Guidelines At their meeting of November W, 2021, the Miami -Dade County Board of Rules and Appeals (BORA) approved revisions to its Forty -Year Building Recertification's General Considerations and Guidelines, inclusive of the Structural and Electrical Recertification Inspection Guidelines. This action was based on recommendations received from several BORA Building Sub -Committee meetings held after the collapse of the Champlain Tower South in the Town of Surfside. A copy of the revised Forty -Year Building Recertification General Considerations and Guidelines is attached for your use. Should you have any questions, please contact Jaime Gascon, Board and Code Administration Division Director at (786) 315-2508. Thank you for your attention. House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 3 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services 00 HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com MIAW Na REGULATORY AND ECONOMIC RESOURCES DEPARTMENT Scone of Electrical Inspection The purpose of the required inspection and report is to confirm with reasonable fashion that the building or structure and all habitable and non -habitable areas, as deemed necessary, bythe inspect- ing professional to establish compliance are safe for continued use under present occupancy. As mentioned before, this is a recommendationprocedme, andunder no circumstances are these mini- mum recommendations intended to supplant proper professional judgment Electric Service A description ofthe type of service supplyingthe buildiagor structure must be provided, stating the size of amperage, if throe (3) phase or single (1) phase, and if the system is protected by fuses or breakers. Proper grounding of the service should also be in good standing. The meter and electric rooms should have sufficient clearance for equipment and for the serviceman to perform both work and inspections. Gutters andelectrical panels should all be in good condition in each meter room throughout the entire building or structure. Branch Circuits Branch circuits in the buildingmust all be identified, and an evaluation of the conductors must be performed Them shouldalso existproper grounding for equipment used in the building, such as an emergency generator, or elevator motor. Conduit Raceways All types of wiring methods present in the building must be detailed and individually inspected. The evaluation of each type of conduit and cable, if applicable, must be done individually. The conduits in the building should be free from erosion and checked for considerable dents in the con- duitsthatmay be prone to cause a short The conductors and cables in these conduits should be chafe free and their currents not over the rated amount Emergency Lighting Exit sign lights and emergency lighting along with a functional fire alarm system, if applicable, must all be in good working condition. Infrared Thermoamphy Inspection For electrical systems operating at 400 amperes or grater, an infrared Thermography inspection with a written report of the following electrical equipmentmustbe provided as applicable or as oth- erwise indicated below: busways, switchgear, panelboards (except in dwelling unit load centers), disconnects, VFDS, starters, control panels,timers, meter centers, gutters junction boxes, automat- ic/manual transfer switches, exhaust fans and transformers. The infrared inspection of electrical equipment shall be performed by a Level-B or higher certified infrared thermograpber who is quali- fied and trained to recognize and document thermal anomalies in electrical systems and possesses over 7 years of experience inspecting electrical systems associated with commercial buildings. HORA Approved -Revised July 20, 2023 PaW 7 of 3 OV24RIA House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 4 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G RA P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com MIAMI-DADE 1 MIAMI-DADE COUNTY, FLORIDA MIL HERBERT S. SAFFIR PERMITTING AND INSPECTION CENTER Departmern of Regulatoryand Economic Resources Board and Cade Administratlan Division 118M SW 2e" Sireet (Coral Way) • w no MIAMI. FLORIDA 33175-2474 (786) 315-2509 FAX (785) 315-2560 vwvw. miamicade.gov/building ADVISORY MEMO TO: ALL BUILDING OFFICIALS IN MIAMI-0ADE COUNTY FROM: Jaime D. Gascon, P.E. Board and Code Administration Division DATE: July 22, 2022 SUBJECT: Thermography Inspections and Clarifications At their regularly scheduled meeting of July 21, 2022, the Board of Rules and Appeals affirmed the clarification points issued by the BORA Building Subcommittee on April 21, 2022, regarding the thermographic inspection required as part of the Electrical 40 Year Recertification report • The threshold for requiring thermographic inspection shall be an electrical service rating of 400 amperes or higher. • The equipment called out in the guidelines for thermographic inspection must be supplied by an electrical service of 400 amperes or higher, but the individual equipment to be inspected DOES NOT need to be rated at 400 amperes or higher. • A Level 2 thermographer's required experience for performance of the inspections DOES NOT need to be exclusively obtained through the performance of thermographic inspections but can be obtained through inspections of electrical systems associated with commercial buildings in general. • The minimum number of years of experience required to perform thermographic inspections related to the Electrical Recertification was reduced to 5 years from 7 years. If you have any questions on this matter, please contact John T. Hall at 786-315-2557 (Office) or 786-351-4909 (Mobile) or via email at John.Hall2amiamidade.00v. House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 5 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com I (786)-230-6065 I admin(a houseofthermography.com 3. Qualifications l z z> Mz> AZm �v ®91_ m m m m = m m p (� q A m x O m m X c N A O c m 3 A p i m � fD 0 l m N Z y M D o N y Vf -n it �'to A o m V1 m y N 0 8 m o - O f -i N i 0 Z y n EL D o r m i z v _ mm z 9 p n m M 2 n T D ms �� 3 � _ ^ O 2 n V O n O ,Or A O m 2 Figure J - Level 111 Master rhermographer Certificate - Hermes Scza, Sr. House of Thermography Infrared Thermography Inspection Report I Project #05250201 Page 6 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Figure 2- Level /// Master Thermographer Certificate - Hermes Soza, Jr House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 7 of 39 MamP@&cunty g&oYear z Older Recertification SerAe Bem@ aunty e»m Safes Inspection Program swces HOUSE OF Commercial Imareddo _gra Ay +a±a THERMOGR&PHY Residential i7| / m2 / 2/2/| G@uAaredAn _gam % +Ryon: wwouemn _gam Wmmlc6>2>meadmin@houseofthermography.com 0r,%� « � (E \ !| e 2 of O \\ \ /|� &2 ® ©© ,,| ! ƒ | / FQ © k ! /|)/ ( \ a \\\ \`}t%' \ ||i f!!` }) S t; w {\ . /� }//i r: / }§ Ck \ \ } � ` m_ s OSHA »- Hour »f Training Completion House of The_mom Infrared r rograph gnsp _aReport I + #05250201 Page 8 of 39 ices Broward County Building Safety Inspection Prices HOUSE OF Commercial Infrared/Thermogration Miami -Dade County 30/40 Year or Older Recertifi71nspections T H E R M O G RA P H Y Residential Infrared/Thermograpons Forensic Infrared/Thermograpons Aerial Infrared/Thermograpons www.houseofthermography.com (786)-230-6065 admin;whouseofthermography.com �Ilk O m t rn = n _ N o r O —h \ 3 1. 6 l\Jo o m Q N- N W rt jV5 0 N rnTT a 9 Y 3 o D N r-r G�CIL a� oa n 0 T _ ti n t� rn F 11N �gt�Ha � Figure 4 - OSHA 1-Hour Electrical for Construction Completion House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 9 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 4. Executive Summary House of Thermography, LLC (HOT) conducted an infrared thermographic inspection on February 26, 2025, at the existing structure at 9165 Park Drive. The addresses is under the Folio# 11-3206-014-1350 according to the Tomas Regalado Miami -Dade Property Appraiser. The building is located in the Miami Shores Village. According to the Miami -Dade County Property Appraiser, the structure was first built in 1970 and currently has an approximate adjusted area of 7,858 square feet. The current use of the building is classified as "1943 Professional Service BLDG: Health Care". At a minimum, the building's complete electrical system operates at 400 amperes or greater, thus meeting the condition to require an Infrared Thermography Inspection, as per Miami -Dade County Board of Rules and Appeals (BORA) General Considerations and Guidelines. At the time of the inspection, the building's electrical operating system was running as it does on a normal basis. This allows us to capture and accurately document any potential thermal / electrical anomalies. As part of the inspection, we checked the following electrical components: busways, switchgear, panelboards (except in dwelling unit load centers), disconnects, VFDS, starters, control panels, timers, meter centers, gutters, junction boxes, automatic/manual transfer switches, exhaust fans and transformers. The nature of the inspection is visual only and non-destructive. Covers may have been removed at the discretion of the thermographer conducting the inspection. Furthermore, HOT uses a FUR thermal camera calibrated within the past six (6) months. This is done in accordance with industry standards and to ensure accurate pixel value on the detector as per the relation below based on Plank's Law: u a f7':. fJ.. fA4EA& Jrte4oquPi,2(ri7 2i t) R(A)cos(B)dQoPt dAd,t dAdt Based on our findings, House of Thermography DID NOT observe thermographic anomalies at the subject site at the time of the inspection. As a routine matter, in order to avoid possible misunderstanding, nothing in this report should guarantee any portion of the structure. To the best of my knowledge and ability, this report represents an accurate appraisal of the present condition of the building based upon careful evaluation of observed conditions, to the extent reasonably possible. View the following pages) for images and the tables) containing the current state of the subject structures electrical operating system. House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 10 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Figure 5 - Aerial of Subject Structure Figure 6 - Flectr ical Service of Subject Structure Figure 7 - Electrical Service of Subject Structure Figure 8 - Electrical Service of Subject Structure House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 11 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Inspection List Image # Electrical Item Location A (°F) IR_15384.jpg Electrical Service Meter East Exterior Wall 36.6 IR_15382.jpg Main Disconnect East Exterior Wall 65.1 IR_15350.jpg Panel MDP Electrical Room 58.2 IR_15356.jpg Panel MDP Electrical Room 39.4 IR_15358.jpg Subpanel P Electrical Room 9.8 IR_15360.jpg Subpanel P Electrical Room 8.3 IR_15362.jpg Panel P Electrical Room 4.3 IR_15364.jpg Panel P Electrical Room 11.2 IR_15366.jpg Panel P Electrical Room 7.2 IR_15368.jpg Panel P Electrical Room 8.1 IR_15370.jpg Panel G Electrical Room 23.2 IR_15372.jpg Panel G Electrical Room 9.3 IR_15374.jpg Gutter Electrical Room 7.5 IR_15376.jpg Gutter Electrical Room 4.7 IR_15378.jpg Gutter Electrical Room 5.6 IR_15380.jpg Gutter Electrical Room 7.8 IR_15386.jpg A/C Disconnect #1 Roof 72.1 IR_15388.jpg A/C Disconnect #2 Roof 68.4 IR_15390.jpg A/C Disconnect #3 Roof 44.6 IR_15392.jpg A/C Disconnect #4 Roof 34.6 IR_15394.jpg A/C Disconnect #5 Roof 45.9 IR_15396.jpg A/C Disconnect #6 Roof 86.4 IR_15398.jpg A/C Disconnect #7 Roof 38.0 IR_15400.jpg A/C Disconnect #8 Roof 68.8 IR_15402.jpg A/C Disconnect #9 Roof 45.6 House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 12 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection fr Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 84.9 °F' Emissivity Distance Reflected temp. Relative humidity Atmospheric tem Ext. optics trans. Measurements Max 117.7 OF Min 83.9 OF n euuu 2000 1000 0 5. Inspection Findings File information _ File name IR_15384.jpg ft Width 288 OF Height 384 V0 Minimum temp. 83.8 OF OF Maximum temp. 120.3 OF Temperature Delta 36.6 'F 92.9 91.1 Camera information Camera model FUR E85 Lens FOL18 Camera serial 7851908, Range max. 248.0 OF Range min. -4.0 OF Field of view 23.50 0 20 40 60 80 oz 9200 I, 533 557 520i 534' 54.. - 92 9105_ 517, 533' UI o 9041 84.0 90.0 96.0 102.0 108.0 'F I5�1 ^530 2 9fj¢13� House of Thermography I Infrared Thermography Inspection Report I Project #05250201 915 Bx1 120 140 161 px 621 _ Northeast 1 fl- 9030-_- I � Public 9F g jai ®oult Page 13 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com i I i Image Parameters File information Camera information Emissivity 0.95 File name IR_15382.jpg Camera model FLIR E85 Distance 9.72 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 78519087 Relative humidity 61.0% Minimum temp. 57.4 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 122.5 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 65.1 Field of view 23.50 Measurements Bx1 Max 120.3 OF Min 57.4 OF n 3000 2000 1000 OF 96.2 95.4 94.7 94.0 93.3 Bxl 0 20 40 60 80 100 120 140 160 180 px 92CO .. 533 557 r� nrrh 2.ic( P10 f': 'L.1.I -„I` irv2a.�P 520 53.1 54 J) 9105. 517. 533 1 gg- 0 J 0�. 9041 c06 53C Q 9035 f/ 60.0 70.0 80.0 90.0 100.0 1 OF I- I i14n House of Thermography I Infrared Thermography Inspection Report I Project #05250201 nL o+r cr. Page 14 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G RA P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Image Parameters File information Camera information Emissivity 0.95 File name IR_15350.jpg Camera model FUR E85 Distance 4.67 ft Width 384 Lens FOL18 Reflected temp. 81.0 OF Height 288 Camera serial 78519087 Relative humidity 61.0% Minimum temp. 52.2 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 110.3 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 58.2 Field of view 23.50 Measurements Bx1 °F BX1 Max 110.3 OF Min 52.2 OF 94.7 n 8000 6000 4000 2000 0 92.9 91.1 0 40 80 120 160 200 240 290 320 3 Px 9200 .533 557 5*,lh AVeI 520 534 54 92.�o Plo r,`crsi Z ?105 517J si3' a 530 u 9030 9041 LO 60.0 70.0 80.0 90.0 °F House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 15 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 106.6 °F Emissivity 0.95 Distance 3.46 ft Reflected temp. 81.0 OF Relative humidity 61.0% Atmospheric temp. 81.0 OF Ext. optics trans. 1.00 Measurements Bx1 Max 110.4 OF Min 77.7 OF n 6000 4000 2000 0 File information File name IR_15356.jpg Width 384 Height 288 Minimum temp. 77.7 OF Maximum temp. 117.0 OF Temperature Delta 39.4 •F 92.9 91.1 Camera information Camera model FUR E85 Lens FOL18 Camera serial 7851908; Range max. 248.0 OF Range min. -4.0 OF Field of view 23.50 Bxl 0 40 80 120 160 200 240 280 320 360 px 10 533 520 534 - 9105. 517, 533 SU6 530 557. 34 ,.'Rhea i ,.F Aven FL': ti Z 0 Sol 7 �m 9041 80.0 90.0 100.0 °F -louse of Thermography I Infrared Thermography Inspection Report I Project #05250201 Northeast 9030 ^� (9080 �f p:nn. say Page 16 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections 4 Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 913 °F Image Parameters File information Camera information Emissivity 0.95 File name IR_15358.jpg Camera model FUR E85 Distance 4.43 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 78519087 Relative humidity 61.0% Minimum temp. 89.1 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 98.9 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 9.8 Field of view 23.50 Measurements Bx1 OF ® Bxl Max 98.9 OF Min 89.1 OF 94.0 93.3 n 2400 1800 1200 600 0 92.6 91.9 0 30 60 90 120 150 180 210 24C z 5�533 557' ohH�. Au,veear.�t NOrthcas�.°7 8U i 5 J 534 54 _ 9105. 517 533 531 _. a p�. 9041 906 530 � _.qJFR5 90.0 92.0 94.0 96.0 OF House of Thermography I Infrared Thermography Inspection Report I Project #05250201 d "-"9030 ' m V Pu61ix 7[y� Ot- acutr Page 17 of 39 Px Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 94.8 °F ', Image Parameters 0.95 File information File name IR_15360.jpg Camera information Camera model Emissivity FUR E85 Distance 4.15 ft Width 288 Lens FOL78 Reflected temp. 81.0 OF Height 384 Camera serial 7851908i Relative humidity 61.0% Minimum temp. 87.6 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 95.9 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 8.3 Field of view 23.50 Measurements Bxi Max 95.9 OF Min 87.6 OF n tuuu 1600 1200 800 •F 92.6 92.2 91.9 91.5 91.1 0 50 100 m 9200 0�33 , 557 i Plc 520 534 1 L 975 ® Bx1 150 200 px 621 637657 673 Northeast 92 ` 517o? y105, . 533 .. SB. L_ � 400 --9030 0 -i -. p� 9041 90R publix 0i Fay. 88.0 89.0 90.0 91.0 92.0 93.0 94.'F ^, Q''. @oul(�% House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 18 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection 7 H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermographycom 92.4 °F Image Parameters 0.95 File information File name IR_15362.jpg Camera information Camera model Emissivity FUR E85 Distance 4.05 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 7851908� Relative humidity 61.0% Minimum temp. 92.1 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 96.5 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 4.3 Field of view 23.50 Measurements Bx1 'F Max 96.5 OF Min 92A OF 95.1 n 1600 1200 800 400 0 ?.0 93.0 94.0 95.0 OF 94.7 94.4 94.0 Bx1 0 20 40 60 80 100 120 140 160 180 200 2 px 1 33 557 _ 1/ Northeast 921 520: 534 S.ly FL 915 Z t0i_ 517. 533 .., SPS_ 'o IS N _030 41 House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 19 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G RA P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Ell Image Parameters Emissivity Distance Reflected temp. Relative humidity Atmospheric temp Ext. optics trans. Measurements Bx1 Max 101.3 OF Min 90.1 OF n 3000 1000 Camera information 95 File name IR_15364.jpg Camera model FUR E85 73 ft Width 288 Lens FOL18 1.0 OF Height 384 Camera serial 78519087 1.0% Minimum temp. 90.1 OF Range max. 248.0 OF .0 OF Maximum temp. 101.3 OF Range min. -4.0 OF )0 Temperature Delta 11.2 Field of view 23.50 OF Bxl 94.0 93.6 93.3 92.9 92.6 , 0 0,5 033 520 S34' 50 100 . F l 9200 557A RfF P.i�( ch; v-, rl 1 cl FL 915 110S, 317, A51 `. 41 90.0 92.0 94.0 96.0 98.0 OF I'_I,_„� 530 ^ ZuSb�! House of Thermography I Infrared Thermography Inspection Report I Project #05250201 150 200 px 6L 621 92 m I 3Ld Fr P,hls i Page 20 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G RA P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 96.5 °F 89.2 `F L _ Image Parameters 0.95 File information File name IR_15366.jpg Camera information Camera model Emissivity FUR E85 Distance 3.76 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 7851908-, Relative humidity 61.0% Minimum temp. 89.7 °F Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 96.9 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 7.2 Field of view 23.50 Measurements BX1 .F Max 96.9 OF Min �89.7 OF n 2000 1600 1200 800 400 0 92.9 92.0 0 30 60 r1o533 520 534 5'1. .115 517. 533 581 o? 1,_V41 Bxi 90 120 150 180 210 24C Northeast 92 7 FL 915 90.0 91.0 92.0 93.0 94.0 95.0 OF S House of Thermography I Infrared Thermography Inspection Report I Project #05250201 b� -LSJ aI W _. z I P,nox =v-fl r Page 21 of 39 Px Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Lit Image Parameters 0.95 File information File name IR_15368.jpg Camera information Camera model Emissivity FUR E85 Distance 4.23 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 785190E Relative humidity 61.0% Minimum temp. 87.2 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 95.3 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 8.1 Field of view 23.50 Measurements Bxl 'F Max 95.3 °F Min 187.3 OF 91.1 n 2000 1600 1200 800 400 0 90.2 0 30 60 0 533. 1557 520 534 54 9105. 517 533' j Bxl 90 120 150 180 210 240 27C Px U 'r' Northeast 9 .1 FL 915 ti 5s- 7.0 88.0 89.0 90.0 91.0 92.0 93.0 °F-a x House of Thermography I Infrared Thermography Inspection Report I Project #05250201 1 QC30 H �I RZ1.I Page 22 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Emissivity Distance Reflected temp. Relative humidity Atmospheric tem Ext. optics trans. Measurements File information _ File name IR_15370.jpg ft Width 288 OF Height 384 yo Minimum temp. 85.1 OF OF Maximum temp. 108.3 OF Temperature Delta 23.2 Bx1 ,F Max L.1 8.3 OF Min OF 94.7 n 3000 2000 loco 93.8 92.9 92.0 91.1 Camera information Camera model FUR E85 Lens FOL18 Camera serial 78519081 Range max. 248.0 OF Range min. -4.0 OF Field of view 23.50 ® Bx1 0 30 60 90 120 150 180 210 240 27C px 5 i51 a� 1 Northeasl'J 6tl� n 520: 534 54 9? FL 915 F 9105 517 533 587 o ��^ , —i ,i G� -9c41 506,� 530 Q75 .0 88.0 92.0 96.0 100.0 7'F _ House of Thermography I Infrared Thermography Inspection Report I Project #05250201 T N 9030 Pubhx Page 23 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G RA P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.h 1 90.6 OF 1 (786)-230-6065 Image Parameters 0.95 File information File name IR_15372.jpg Camera information Camera model Emissivity FLIR E85 Distance 3.51 ft Width 384 Lens FOL18 Reflected temp. 81.0 OF Height 288 Camera serial 7851908; Relative humidity 61.0% Minimum temp. 88.8 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 98.1 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 9.3 Field of view 23.50 Measurements Bx1 'F Max 98.1 OF Min 88.8 OF 92.9 n 2500 2000 1500 1000 500 0 92.0 91.1 5 Bxl 0 40 80 120 160 200 240 280 320 3 px w Dov F 9200 A Sol 533 547 I 621 GP. Northea 520 53.7 5'1 -, FL 915 ti 'Z 9105 517 533 o 58' � N � 9030 a, 2 in 9041 I9,%1 W 89.0 90.0 91.0 92.0 93.0 94.0 95.0 96 OF ' ' GuhliR E � House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 24 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com Imacle Parameters File information Camera information Emissivity 0.95 File name IR_15374.jpg Camera model FUR E85 Distance 2.19 ft Width 384 Lens FOL18 Reflected temp. 81.0 OF Height 288 Camera serial 7851908i Relative humidity 61.0% Minimum temp. 91.2 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 98.7 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 7.5 Field of view 23.50 Measurements Bx1 Max 98.7 OF Min 92.6 OF n 5000 4000 3000 2000 1000 0 V 95.5 95.1 94.7 94.4 0 40 80 120 160 200 $ 1200 1 ` 0033 557 1 520'. 5345.1 1105. 517. 533 58 1 9041 530 1.0 92.0 93.0 94.0 95.0 96.0 97 T Sa T - House of Thermography I Infrared Thermography Inspection Report I Project #05250201 im im �i �m �g F1 Bx1 280 320 360 4C px Northeast ; 2 +r30 91 Vubbs Page 25 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections ... .._..1 .. _4L ._L.. _ I il/i/♦ n�l/� /`/�/`r I �J.��:.-nL�.. 4L�..� .. L..��� Image Parameters 0.95 File information File name IR_15376.jpg Camera information Camera model Emissivity FLIP E85 Distance 2.45 ft width 384 Lens F01_18 Reflected temp. 81.0 OF Height 288 Camera serial 78519087 Relative humidity 61.0% Minimum temp. 92.3 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 97.0 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 4.7 Field of view 23.50 Measurements Bx1 Max 97.0 OF Min 92.3 OF n 2000 1500 1000 500 0 OF 94.9 94.4 Bxl 0 40 80 120 160 200 240 280 320 360 4( px 0033:1 557' .._.� >iorth4 Northeast12 1 4 1h " NIL 520 534 5'3 97rn:� 915 1105. 517 1 533 58t v 0 9041 d 53C f 35 1 93.0 94.0 95.0 96 OF 5I� 3 House of Thermography I Infrared Thermography Inspection Report I Project #05250201 9030 S Pt,bI x f: �D 1 Page 26 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 adminC@houseofthermography.com 99A °F Image Parameters 0.95 File information File name IR_15378.jpg Camera information Camera model Emissivity FUR E85 Distance 2.60 ft Width 384 Lens FOL18 Reflected temp. 81.0 OF Height 288 Camera serial 7851908; Relative humidity 61.0% Minimum temp. 91.4 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 97.0 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 5.6 Field of view 23.50 Measurements 13x1 ,F Max 97.0 OF Min 91.4 OF 94.4 n 3000 2000 1000 0 94.0 N Bxl 0 40 80 120 160 200 240 280 320 360 4C px 0 3- Northeast 92 rrl:� 520. 534 54�, 97 ti 905 917_ 533 581._ a. .P, 9041 92.0 93.0 94.0 99.0 'F I F 9A4 House of Thermography I Infrared Thermography Inspection Report I Project #05250201 TI Gr.M Page 27 of S9 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections /0 Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 5 °F i HOUSE 1 Image Parameters File information Camera information Emissivity 0.95 File name IR_15380.jpg Camera model FUR E85 Distance 2.88 ft Width 384 Lens FOL18 Reflected temp. 81.0 OF Height 288 Camera serial 78519087 Relative humidity 61.0% Minimum temp. 88.8 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 96.7 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 7.8 Field of view 23.50 Measurements Bx1 Max 96.7 OF Min 92.0 OF n 4uuu 3000 2000 1000 0 OF kZE] 93.6 93.3 92.9 Bx1 0 40 80 120 160 200 240 280 320 3 px 30.33 S�. �, j !�_ ""r"'40 Northeast 820 534 S:I— qr 105 517 533 SEL.. 530 9041 89.0 90.0 91.0 92.0 93.0 94.0 9! OF I House of Thermography I Infrared Thermography Inspection Report I Project #05250201 9030 4 JI c nlx Page 28 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Y H E R M O G R A P H Y Residential Infrared/Thermography Inspections �� Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com 108.7 °F 7[94F Image Parameters 0.95 File information File name IR_15386.jpg Camera information Camera model Emissivity FLIR E8: Distance 2.29 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 7851908 Relative humidity 61.0% Minimum temp. 34.3 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 106.4 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 72.1 Field of view 23.50 Measurements Bx1 Max 106.4 OF Min 63.3 OF n 3000 2000 1000 0 'F 92.9 91.1 89.3 87.5 Bxl 0 50 _100 rr 150 200 6th Av Q cm 1a Nor theasrf Q7 2nd5 reel 25°51'35°t N 25'5' 80'111LU ___560 i 0 WH W 8011 c Qft r O` N 9165 or r 9111 1Wm T-FL91 40.0 50.0 60.0 70.0 80.0 90.'F House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Page 29 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com i Image Parameters Emissivity 0.95 Distance 2.27 ft Reflected temp. 81.0 OF Relative humidity 61.0% Atmospheric temp. 81.0 OF Ext. optics trans. 1.00 Measurements Bx1 Max 103.6 OF Min 63.2 OF n 3000 20M 1000 File information File name IR_15388.jpg Width 288 Height 384 Minimum temp. 63.2 OF Maximum temp. 131.6 OF Temperature Delta 68.4 'F 91.1 89.3 87.5 0 50 100 150 ,:\I .14 lllli� JI Camera information Camera model FUR E85 Lens FOL18 Camera serial 7851908; Range max. 248.0 OF Range min. -4.0 OF Field of view 23.50 N 25'51'3E 9765 0 l k 9'11 100m .0 70.0 80.0 90.0 100.0 110.0 'F House of Thermography I Infrared Thermography Inspection Report I Project #05250201 ® Bx1 200 80°1 t 'I ' FL 915 Page 30 of 39 Px Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection Residential Infrared/Thermography Inspections T H E R M O G R A P H Y Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com i Image Parameters Emissivity 0.95 Distance 2.21 ft Reflected temp. 81.0 OF Relative humidity 61.0% Atmospheric temp. 81.0 OF Ext. optics trans. 1.00 Measurements Bx1 Max 106.0 OF Min 61.3 OF n 4000 30W 2000 1000 0 File information File name IR_15390.jpg Width 288 Height 1384 Minimum temp. 61.3 OF Maximum temp. 106.0 OF Temperature Delta 44.6 OF 91.1 89.3 87.5 85.7 83.9 information Camera model FUR E85 Lens FOL18 Camera serial 7851908; Range max. 248.0 OF Range min. -4.0 OF Field of view 23.50 0 30 60 v �o N 25°51'35"� W 80011'1 546 T P H 2 O 2 9'11 90 120 150 : Av�y I ®M IR 1539r00 (1 /� 3.0 70.0 80.0 90.0 OF House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Bxl 210 240 px 25°' 80, 0 FL915 1 i Page 31 of 39 Miami -Dade County 30/40 Year or Older Recertification Services Broward County Building Safety Inspection Program Services HOUSE OF Commercial Infrared/Thermography Inspection T H E R M O G R A P H Y Residential Infrared/Thermography Inspections Forensic Infrared/Thermography Inspections Aerial Infrared/Thermography Inspections www.houseofthermography.com 1 (786)-230-6065 1 admin@houseofthermography.com i i V r d Image Parameters File information Camera information Emissivity 0.95 File name IR_15392.jpg Camera model FUR E85 Distance 2.18 ft Width 288 Lens FOL18 Reflected temp. 81.0 OF Height 384 Camera serial 7851908; Relative humidity 61.0% Minimum temp. 66.5 OF Range max. 248.0 OF Atmospheric temp. 81.0 OF Maximum temp. 101.1 OF Range min. -4.0 OF Ext. optics trans. 1.00 Temperature Delta 34.6 K77 Field of view 23.50 Measurements Bx1 Max 101.1 OF Min 66.5 OF n 3000 2000 1000 °F 87.5 86.8 86.1 85.4 84.6 0 20 40 60 80 100 120 N V,Ko N 25°51'35'11 �0 - 92rid --� �� � 9711 _. 0 533 581 --- i6.0 72.0 78.0 84.0 90.0 °f 1 100 M- House of Thermography I Infrared Thermography Inspection Report I Project #05250201 Bxl 200 22 px FL 915 I?I Page 32 of 39