Loading...
CC-07-21-1891 Building Re-CertificationMiami Shores Village Building Department 10050 N.E.2nd Avenue Miami Shores,Florida 33138 Tel:(305)795.2207 Fax:(305)756.8972 BUILDING RECERTIFICATION Date:October 3,2024 Permit No.CC-07-21-1891 To:Miami Shores Baptist Church 370 Grand Concourse Miami Shores,Florida 33138-2747 Subject:70 years Building/Electrical Recertification. Folio 11-3206-013-6040 370 Grand Concourse Miami Shores,Florida 33138-2747 The Village of Miami Shores Building Department received and reviewed the Building Structure certification report dated September 16,2024 by Tahir Iqbal,MS,P.E,Florida license number 48061 and the Electrical System recertification report dated October 10,2022 by Gordon Myers P.E,Florida license number 36852 Based on the reports provided,the building on the above referenced property was found to be structurally and electrically safe for Its continued use and occupancy. This Letter of Recertification is granted for the building on this property.The Recertification expires on the 80**'year anniversary from original construction date.At that time,a new Recertification Report must be submitted to the Building Official.Although this Letter of recertification allows continued occupancy of the building,issuance of this letter does not preclude the Building Official from carrying out his responsibilities under Section 8-5 of the Code of Miami-Dade County.Further,issuance of this letter shall not be construed directly,or indirectly,as a guarantee of the safety of any portion of the structure. As per Miami Dade County Code Sec.8-11.-Existing buildings.(a)The requirements contained in the Florida Building Code,shall apply to all buildings and/or structures now existing or hereafter erected.All buildings and/or structures and all parts thereof shall be maintained in a safe condition,and all devices or safeguards that are required by the Florida Building Code shall be maintained in good working order.Electrical wiring, apparatus and equipment,and installations for light heat or power and low voltage systems as are required and/or regulated by the Building Code,now existing or hereinafter installed,shall be maintained in a safe condition and all devices and safeguards maintained in good working order. Thank you for your cooperation in this matter. Ismael Naranjo,BO,CFM SEP S 0 Z024TAJLIMITEDGROUP,INC 14216 SW160‘'‘Avenue Miami,FL 33196 (305)793-7656 BY: September 16,2024 Miami Shores Village Development Services Department 10050 Northeast 2"**Avenue Miami Shores,FL 33138 Attn:Building Official Folio No:11-3206-013-6040 70 Year Recertification Miami Shores Baptist Church 370 Grand Concourse, Miami Shores,FL 33138 Re: Dear Building Official: TAJ Limited Group,Inc.(TAJ)conducted an inspection for the purpose of determining the general condition of the structural system for the property referenced above for compliance with Chapter 8,Section 8-11(f)of Code of Miami-Dade County and in accordance with the minimum inspection procedure guidelines as issued by the County Board of Rules and Appeals. Visual examination and manual procedures were used to conduct the inspections.Property management personnel were consulted to obtain the maintenance and repair history of the building,all maintenance repairs were performed under Permit CC-03-24-76. As of the date of the attached report,the building is structurally SAFE for its use and PRESENT occupancy. As a routine mailer,to avoid possible misunderstanding,nothing in this report should be construed directly or indirectly as a guarantee for any portion of the structure system.To the best of my knowledge and ability,this report represents an accurate appraisal of the present condition of the building based upon careful evaluation of observed conditions,to the extent reasonably possible”. Please note that this certification is for the referenced building only and does not include other areas and structures of the community. SUFFICIENCY Please note that this report is limited to the evaluation of the selected areas described herein. Adequacy of the original design or improper construction is beyond the scope of TAJ Limited Group,Inc work.This report should not be used as a repair document,as substantial additional details and information must be furnished to the Contractor to perform adequate repairs. Miami Shores Baptist ChurchPage1of3TAJProjectNo.22-132 TAJ LIMITED GROUP,INC 14216 SW 160‘»>Avenue Miami,FL 33196 (305)793-7656 As a routine matter to avoid possible misunderstanding,nothing in this report shall be construed directly or indirectly as a guarantee of any portion of the structure. To the best of our knowledge and ability,this report represents an accurate appraisal of the current condition of the building,based upon careful evaluation of the observed conditions, to the extent reasonably possible. Limitations of Inspection Report 1.1.Observations and data collected by TAJ Limited Group,Inc for this report were obtained during their limited on-site obser\^ations. 1.2.Except as otherwise noted,the discussions,opinions,and conclusions described in this report are based on. a.The information provided by various parties without separate verification, b.Limited visual observations:data collected and/or made available concerning current as-built conditions of the building during the site visits to develop this report. 1.3.This report is not intended to provide,and does not provide,a comprehensive study of each noted deficiency and/or damage observed in the building.The report regarding the conditions observed represents professional engineering opinions in accordance with the applicable standard of care. 1.4.Any photos included in this report are meant to support the stated observations of the report authors;and any portions of the included photos that are not in the description of the observation are coincidental and are not relevant to the observation,nor were those portions reviewed.Photos do not include every deficiency and defect obsen^ed. 1,5.The information in this report is not meant to be a guarantee or warranty of any kind. The opinions expressed in this report are based primarily on a visual observation of reasonably accessible areas of the building at the time of the site visit(s).TAJ Limited Group,Inc therefore do not assume any responsibility for items that were not examined or were not observed. 1.6.Except as otherwise noted,this report does not contain any professional opinion regarding the completion of any previously recommended improvements associated with the structure. 1.7.TAJ Limited Group,Inc have prepared this report exclusively for the Client.Any use of this report by any other individual(s)or entity without the expressed wntten consent of TAJ Limited Group,Inc is prohibited.Should another individual or entity Miami Shores Baptist ChurchPage2of3TAJProjectNo.22-132 TAJ LIMITED GROUP,INC 14216 SW 160‘^'Avenue Miami,FL 33196 (305)793-7656 rely on this report without the prior specific written consent of TAJ Limited Group, Inc,they shall indemnify TAJ Limited Group,Inc from any damages,losses,or expenses they may incur because of such improper use. 1.8.TAJ Limited Group,Inc reserve the right to revise and supplement this report if in their sole opinion any additional information is made available to them including new documents,physical data,or new evidence. If you have any questions or comments,please contact our office. Respectfully Submitted by, Respectfully Submitted by, TAJ LIMITED GROUP,INC TWRCBM.SrS*~ rv rrcM B tt>A A i&uA irt o*TyMQr*no wTtA i uciWATiBE nmo>CtfVt or tin Inin wm mi hot rn»iabptti STK A mAUD AW SB nunw MAT I vtnwo OA fAr*mcncMC c^iATahirIqbal,MS,P.E. Structural Engineer FL.P.E #48061 Miami Shores Baptist ChurchTAJProjectNo.22-132 Page 3 of 3 VED SEP SO 2024 BY:ELC-ll-21-2978 -closed 3/21/2022 REPLACING PANEL AND BREAKER IN ROOF,REPLACING PANEL IN ROOM 202,REPAIRING ALL EMERGENCY LIGHTS NOT WORKING,AND OTHER MISCELLANEOUS ITEMS AS DESCRIBED IN THE RECERTIFICATION. C-03-24-736 -closed 8/8/2024 Concrete Repairs w Permit NO.CC-03-24-736 Miami Shores Village Building Department 10050 NE 2 Ave Miami Shores FL 33138 iff-:Type:Building (Commercial) WorUclass:Repair Permit Status:ClosedCARDIII1 ...tlliriiL Expires:12/02/2024IssueDate:6/5/2024 INSPECTION REQUESTS:visit https://www.msvfl.gov/departments/bui ldingdepartmentyRequestlnspection Requests must be received by 3:30pm WORK IS ALLOWED:MONDAY THROUGH FRIDAY,8:00AM -7:00PM SATURDAY 8;00AM -6:00PM. NO WORK IS ALLOWED ON SUNDAY OR HOLIDAYS BUILDING AND ROOFING INSPECTIONS ARE DONE MONDAYTHROUGH FRIDAY . NO INSPECTION WILL BE MADE UNLESS THE PERMIT CARD IS DISPLAYED AND HAS BEEN APPROVED .PLANS ARE READILY AVAILABLE .IT IS THE PERMIT APPLICANT’S RESPONSIBILITY TO ENSURE THAT WORK IS ACCESSIBLE AND EXPOSED FOR INSPECTION PURPOSES.NEITHER THE BUILDING OFFICIAL NOR THE CITY SHALL BE LIABLE FOR EXPENSE ENTAILED IN THE REMOVAL OR REPLACEMENT OF ANY MATERIAL REQUIRED TO ALLOW INSPECTION . POST ON SITE 1132060136040 Owner's Phone:(305)758-0559 Total Square Feet:29,145 Total Job Valuation:$20,000.00 Owner's Name:MIAMI SHORES BAPTIST CHURCH 370 GRAND CONC Miami Shores,FL 33138 Job Address: Address 1000 NW 106 AVE,PLANTATION,FL 33322 Phone (786)800-0971 Contractor(s) GORO CONSTRUCTION INC Description:Concrete Repairs AUb 0 d ehi'U ku NOTICE;In addition to the requirements of this permit,there may be additional restrictions applicable to this property that may be found in the public records of this county,and there may be additional permits required from other governmental entities such as water management districts,state agencies,or federal agencies. WARNING TO OWNER:YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY.A NOTICE OF COMMENCEMENT MUST BE RECORDED AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION.IF YOU INTEND TO OBTAIN FINANCING,CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE COMMENCING WORK OR RECORDING YOUR NOTICE OF COMMENCEMENT. Page 1 of 1 m Miami Shores Viiiage 10050 NE 2 Ave Miami Shores FL 33138 305-795-2204 5.k ■liiHlx -’i.I n Expiration:05/17/2022 U>cation Address Parcel Number 370 GRAND CONC,Miami Shores,FL 33138 1132060136040 Contacts MIAMI SHORES BAPTIST CHURCH INC 370 GRAND CONCOURSE,MIAMI SHORES,FL 331382747 LONGMAN ELECTRIC INC MICHAEL LONGMAN 95 NE 166 ST,Miami,FL 33162 Business:3057581211 Owner Contractor longmanelectric@bellsouth.net $6,750.00Description:REPLACING PANELAND BREAKER IN ROOF, REPLACING PANEL IN ROOM 202,REPAIRING ALL EMERGENCY UGHTS NOT WORKING,AND OTHER MISCELUNEOUS ITEMS AS DESCRIBED IN THE RECERTIFICATION. Valuation: Total Sq Feet:0.00 Fees Amount Amt PaidDatePaidPayments $224.23$50.00 $4.20 $3.04 $2.03 $1.40 $15250 $6.00 $5.06 Application Fee ●Other Total Fees Credit C^rd 11/12/2021 11/17/2021 CCF $50.00 DBPR Fee DCAFee Education Surcharge Permit Fee Scanning Fee Technology Fee Credit Card $174.23 $0.00AmountDue: $224.23Total: AUb'0 9 ENi'O BY: THIS MUST BE QM Applicant Copy For Inspections,Cali (305)762-4949 or Log on at https://bldg.m iamishoresvillage.coin/cap/. Requests must be received by 3pm for following day inspections. NOTICE:In addition to the requirements of this permit,there may be AND THERE MAY BE ADDITIONAL PERMITS REQUIRED FROM OTHER additional restrictions applicable to this property that may be found in the GOVERNMENTAL ENTITIES SUCH AS WATER MANAGEMENT DISTRICTS, public records of this county.STATE AGENCIES,OR FEDERAL AGENCIES. November 17,2021 Page 1 of 2 RECEIVED BY: October 18,2021 Miami Shores BAPTIST CHURCH Miami Shores Village Building Department 10050 NE2"'^Avenue Miami Shores,FL 33138 ●●●● r ●●●♦ Re:Notice of Required 70-Year Building Recertification ●●»% 4 4 4 4 444444ToWhomItMayConcern: Attached is the report the engineering firm that was hired to survey our facility,located at 370 Grand Concourse,Miami Shores,FL 33138. We are in the process of accomplishing these repairs.We have hired a General Contractor who is working on quotes for the concrete repairs.We have also hired Longman Electric to perform the electrical repairs.He is in the process of getting the permits ready. Sincerely, z eo Babun,President 370 Grand Concourse Miami Shores,FL 33138 305.758.0559 info(o)miamishoresbapiisi.orgmiamishoresbaptist.org # % ●●●● ♦●● ●● # ENTERiS^ OCT 11 202Z BY; l i.oici i>/v i^t I i.i>i:i«^ I 'V I-:«I ■v I*i:«I'«»i« «*rvini|f loricl i Co.>'.t to S 7 7 12555 Biscayne BIvcJ.U 93-4 North Miami.FL 33181 8 0 0 189-4- RE:Folio#11-3206-013-6040 O^V'NER NAME:MIAMI SHORES BAPTIST CHURCH PROPERTY ADDRESS:370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 DATE OF INSPECTION:10-5-2022 TO:MIAxVn SHORES BUILDING DEPARTMENT OFFICIAL On behalf of the above-mentioned property owner I would like to respectfully request that Recertification per Miami-Dade county Ordinance Miami-Dade County,Section 8- 11(0 be granted to the above-mentioned structure. I have inspected the above-mentioned property and find the building “electrically”safe for its use and present occupancy”. As routine matter,in order to avoid possible misunderstanding,nothing in the report attached should be construed directly,or indirectly as a guarantee for any portion of the structure.Future function is not guaranteed in any way.To the best of my ability and knowledge this report represents an accurate appraisal of the present conditions of the building(s)based upon careful evaluation of the observed conditions,to the extent reasonably possible. Thank you for your attention to this matter. ^^DATE ELEC i KICAl i><r Sincerely,APPROVEDl^ *No 36852 STATE OF Y RG S Digitally signed by Gordon W.Myers PE 36852 Gordon W. Myers PE 36852 Date:2022.10.08 13:30:19 -04'00' -o Or-ft X- Gordon W.Myers PE 36852 Florida Builders,Engineers &Inspectors,Inc. A Professional Engineering Firm CA 31260 1^5-2022 Although this Letter of Recertification allows continued occupancy of the building,issuance of this letter should not be construed directly or indirectly as a guarantee of the safety/code compliance of any portion of the structure. 1 REGULATORY AND ECONOMIC RESOURCES DEPARTMENT 11805 SW 26'^Street,Miami,Florida 33175 786-315-2000 Miamidade.gov/building MIAMI COUNTY MINIMUM INSPEaiON PROCEDURAL GUIDELINES FOR BUILDING ELECTRICAL RECERTIFICATION ^0 ●'No 3M52 \ *●-: STATE OF M .FLORIDA BUILDERS ENGINEERS &INSPECTORS,INCCASEREFERENCENUMBER:LICENSEE NAME:Y GORDON W.MYERS P.E 36852 VICE PRESIDENTTITLE:G S ●* ADDRESS-■'2555BISCAYNE BLVD #934 NO.MIAMI,FL 33181 305-895-8001/gordon@inspectionsandengineering.com ●c JURISDICTION NAME: MIAMI SHORES VILLAGE Gordon W.Myers D>gi»any signed by'Myers PE 36852 Date:2022,10,0813-3Q-4A -nam Gordon W. SIGNATURE:pE 36852 *Use separate sheets for additional responses by referencing the report number. 1.DESCRIPTION OF BUILDING .V1IA.MI SHORES BAPTIST CHURCHa.Name on Title: 370 GRAND CONCOURSE .MIAMI SHORES.FL 33138 2747 1Bldg.#;b.Building Street Address: Attached:MIAMI SHORF.S SEC 1 AMD PB 10-70 ALLBLK Bc.Legal Description: MIAMI SHORES BAPTIST CHURCHd.Owner's Name: 370 GRAND CONCOURSE MIAMI SHORES.FL 33138-2747e.Owner's Mailing Address: 11-3206-013-6040f.Folio Number of Property on which Building is Located: 7144 RELIGIOUS ●EXEMPT :RELIGIOUSg.Building Code Occupancy Classification: CHURCH BUILDINGh.Present Use: i.General Description of building (overall description,structural systems,special features): CBS (2)STORY TOTAL 29.145 ADI-AREA ACCORDING TO P.REC NOj.Number of Stories:^k.Is this a Threshold Building as per 553.71(12)F.S.(Yes/No): I.Provide an aerial of the property identifying the building being certified on a separate sheet.Attached:x m.Additional Comments: As routine matter,in order to avoid possible misunderstanding,nothing in the report attached should be construed directly,or indirectly as a guarantee fur any portion of the structure.Future function is not guaranteed in any H-av.To the best of mv ability and knowledge this report represents an accurate appraisal of the present conditions of the building(s)based upon careful evaluation of the observed conditions,to the extent reasonably possible. 12/21R1.0Page1of9BORAApproved-Revised November 18,2021 2.INSPEaiONS a.Date of Notice of Required Inspection:2019 iO-5-2022b.Date(s)of actual inspection: c.Name and qualifications of licensee submitting report: FLORIDA BUILDERS ENGINEERS &INSPECTORS.INC GORDON W MYERS P.E.36852 NOd.Are Any Electrical Repairs Required?(YES/NO): 1.If required,describe,and indicate acceptance: e.Can the building continue to be occupied while recertificatio n and repairs are ongoing?(YES/NO):YES 1.Explanation/Conditions: 3.ELECTRICAL SERVICE PROVIDE PHOTO Breakers (}Type;Fuses (Amperage {Voltage!‘20/240 )600a.Size: (©)(O)Single PhaseThree-Phaseb.Phase: (O)(O Needs RepairGoodFairc.Condition: 600AMP MAIN BREAKER PANEL /'lOOAMP SUB MAIN/2-300AMP SUB MAIN 3 200AxMP SUB xMAIN BOTHE BREAKERS AND FUSES PANELS.PANELS ARE IN SATISKAtrTORY CONDITIONS AT THIS TIME Comments: PROVIDE PHOTO4.METERING EQUIPMENT (O)(©)(O)Needs Correction1.Clearances:Good Fair SEE PHOTOSComments: 12/21R1.0BORAApproved-Revised November 18,2021 Page 2 of 9 PROVIDE PHOTO5.ELECTRIC ROOMS (©(O1.Clearances:Good Needs CorrectionFair Comments: SEE PHOTOS PROVIDE PHOTO6.GUTTERS (0 lQ)Good Needs Repair1.Location: (Q)(©)Good Needs Repair2.Taps and Fill: Comments: 7.ELECTRICAL PANELS PROVIDE PHOTO PANELS INSIDE CLASSROOMS RECENTLY REPLACED WITH PERMIT #-2129781-51.Panel #{Location: (©I 0 )Needs RepairGood 2.Panel #(Location: ©(©)Needs Repair (Good 3.Panel #{Location: (©)(©)Good Needs Repair 4.Panel #(Location: (©)(©)Good Needs Repair 5.Panel #(Location: (©)lQ)Good Needs Repair 12/21R1.0BORAApproved-Revised November 18,2021 Page 3 of 9 Comments; 8.BRANCH CIRCUITS PROVIDE PHOTO (©)'©)Must be Identified1.Identified:Yes (Q >(0 )'©)Must be ReplacedDeteriorated2.Conductors:Good Comments: PROVIDE PHOTO9.GROUNDING OF SERVICE LOi(©)Needs RepairGood Comments: PROVIDE PHOTOlO.GROUNDING OF EQUIPMENT (©(©)Needs RepairGood Comments; 12/21R1.0Page4of9BORAApproved-Revised November 18,2021 ll.SERVICE CONDUIT/RACEWAYS PROVIDE PHOTO OiiQGoodNeedsRepair{ Comments; PROVIDE PHOTO12.GENERAL CONDUIT/RACEWAYS (©Needs Repair (_Q>Good Comments; PROVIDE PHOTO13.WIRE AND CABLES (©)lQiNeedsRepairGood Comments; PROVIDE PHOTO14.BUSWAYS (©(©>Good Needs Repair Comments: 12/21R1.0BORAApproved-Revised November 18,2021 Page 5 of 9 PROVIDE PHOTO15.THERMOGRAPHY INSPECTION RESULTS {ADD SHEETS AS REQUIRED) See Report Attached Roger .Morales KPB Electrical Service Le\'el II Thermographer Cert»273120Comments: PROVIDE PHOTO16.0THER CONDUaORS (Oi©)Needs RepairGood Comments: PROVIDE PHOTO17.TYPES OF WIRING METHODS OlQ>(©)N/ANeedsRepair1.Conduit Raceways Rigid:Good (Q)Needs Repair (Q)(©I N/AGood2.Conduit PVC: <©'Repair (Q )N/ANeedsGood3.NM Cable: (Q)Needs Repair (o>(Q)N/A4.Other:Good 3.Other Wiring (Specify): Comments: PROVIDE PHOTO18.EMERGENCY LIGHTING o>(©)(©)N/ANeedsRepair(Good Comments: 12/21R1.0Page6of9BORAApproved-Revised November 18,2021 PROVIDE PHOTO19.BUILDING EGRESS ILLUMINATION (©OlQ)N/AGoodNeedsRepair Comments; PROVIDE PHOTO20.FIRE ALARM SYSTEM (O(O(©N/ANeedsRepairGood Comments: PROVIDE PHOTO21.SMOKE DETECTORS (©(©(©N/ANeedsRepairGood Comments: PROVIDE PHOTO22.EXIT LIGHTS (©>(O)(©)N/ANeedsRepairGood Comments: 12/21R1.0BORAApproved-Revised November 18,2021 Page 7 of 9 PROVIDE PHOTO23.EMERGENCY GENERATOR (O (©<0 )N/AGoodNeedsRepair Comments: PROVIDE PHOTO24.WIRING IN OPEN OR UNDER COVER PARKING GARAGE AREAS Requires Additional l)lumination(Q)(Q)(©N/AGood Comments: PROVIDE PHOTO25.0PEN OR UNDER COVER PARKING GARAGE AND EGRESS ILLUMINATION (Q){©lllumination()N/ARequiresAdditionalGood Comments: PROVIDE PHOTO26.SWIMMING POOL WIRING (©)(©(©)N/ANeedsRepairGood Comments: 12/21R1.0BORAApproved-Revised November 18,2021 Page 8 of 9 PROVIDE PHOTO I27.WIRING TO MECHANICAL EQUIPMENT (©(O)(O)N/AGoodNeedsRepair Comments; 28.ADDITIONAL COMMENTS As routine matter,in order to avoid possible misunderstanding,nothing in the report attached should be construed directly,or indirectly as a guarantee for any portion of the structure.Future function is not guaranteed in any way.To the best of my ability and knowledge this report represents an accurate appraisal of the present conditions of the building(s)based upon careful evaluation of the observed conditions,to the extent reasonably possible. Reset Form 12/21R1.0BORAApproved-Revised November 18,2021 Page 9 of 9 Regulatory and Economic Resources 11805 SW 26th Street Miami,Florida 33175-2474 786-315-2000 MIAMI DADE COUNTY miamtdade.gov/buildrng CERTIFICATION OF COMPLIANCE WITH PARKING LOT ILLUMINATION STANDARDS IN CHAPTER 8C-3 OF THE CODE OF MIAMI-DADE COUNTY 10-5-2022 Date: 1949-70 -YEAR RECERTIFICATION Case No.FYear 29,1451370GRANDCONCOURSEPropertyAddress:Sq.Ft.:Bldg.No.:. 11-3206-013-6040FolioNumber: CHURCH BUILDINGBuildingDescription: I am a Florida registered professional X engineer1.architectwith an active license. at"10-5-2022 AM |X |pM,I measured the level of iBuminatbn in the parking2.On,20. lot(s)serving the above referenced building. 6.63.foot candleMaximum 3.0 foot candleMinimum 3.6 foot candleMaximumtoMinimumRatio. The level of illumination provided in the parking lot X meets minimumstandardsforthe occupancy classificatbn of the building as established inSectbn 8C-3 of Miami-Dade County Code. 4.does not meet the FLORIDA BUILDERS ENGINEERS 8c INSPECTORS,INC GORDON W MYERS P.E.36852 305-895-8001 gordong'inspectionsandengineering.com tO-5-2022 Digitally signed by Gordon W.Myers PE 36852 Date:2022.10.0813;31K)2 -04'00' Gordon W. Myers PE 36852 Signature and Seal of Professional Print Name EngineerorArchitect No 368S2 \STAT6 OF .Q, V G S ; 1 2 RACEWAYS/ 3 4 CM 0> CUD ro 0. KPB Services Co.Int’l 2117 N.Dixie Highway Ft.Lauderdale,FL 33305 (305)710-8383 Electrical Contractor 13008559 Email:n>ucrfa insDection.<an(lemii»ceritiu.coin cn O) DO ro CL KPB Services Co.IntM 2117 N.Dixie Highway Ft.Lauderdale.FL 33305 (305)710-8383 Electrical Contractor 13008559 Email:nmerf(:/'inspcciion.saiuleni:incerim:.com V-t.VKL // 0 MItAlKO' UwU» l^OOER M0«AC£$ C«<titK4i«ANw*i>brt Q X27)120 fipMXron April n,?026 ●V?: ■> INSPECTION MADE BY: Roger Morales MSHng, Level II Thermographer Cert#273120 KPB Services Company,International Licensed Electrical Contractor EC13008559 Tel:(305)-710-8383 lO-S-2022 Digitally signed by Roger Morales Date:2022.10.08 13:31:29-04'00' Roger Morales DO NOT PERFORM ANY WORK WITHOUT PROPER PERMITS/INSPECTIONS BY BUILDING OFFICIALS.FINAL INSPECTION WILL NOT BE APPROVED BY OUR FIRM WITHOUT PROPER BUILDING PERMITS AND FINAL INSPECTIONS HA VING BEEN PERFORMED BY LOCAL BUILDING OFFICIALS. WE ARE NOT RESPONSIBLE FOR REQUESTING EXTENSIONS TO THE COUNTY/CITY BUILDING OFFICIALS FOR THE COMPLETION OF THE RECERTIFICATION PROCESS.BUILDING OWNER IS SOLELY RESPONSIBLE FOR THIS TASK. THIS INSPECTION REPORT IS OF THE DEFICIENCIES FOUND DURING OUR INSPECTION OF THE ABOVE REFERENCED PROPERTY AND NOTE THAT ADDITIONAL DEFICIENCIES MA Y BE DISCOVERED DURING FURTHER INSPECTION.WE RESERVE THE RIGHT TO AMEND THIS REPORT AS NECESSSARY. THE INSPECTION FEE CHARGED FOR THIS INSPECTION REPORT IS NON-FUNDABLE.WE DO NOT GUARANTEE THA T THE COUNTY/CITY OFFICIAL WILL GRANTRE-CERTIFICA TION. THIS REPORT IS ONLY OUR PROFESSIONAL OPINION OF WHAT WILL BE REQUIRED AND CONSIDERED SAFE FOR CONTINUED OCCUPANCY FOR THE CITY OR COUNTY OFFICIAL TO GRANT RECER TIFICA TION. WE RESER\E:the right TO DENY ISSUING FINAL CLEAR RECERTIFICA TION OF BUILDING IF REPAIRS MADE AND OR CONDITIONS ARE NOT DEEMED SA TISFACTOR Y OR APPROVED BY OUR FIRM AS SAFE FOR CONTINUED OCCUPANCY. 0) 00 CO a. KPB Services Co.Int’l 2117 N.Dixie Highway Ft.Lauderdale,FL 33305 (305)710-8383 Electrical Contractor 13008559 Email:rouer^j inspcciion.sjndcnjinccrint:.coiTi This is an Agreement between you,the undersigned Client,and us,the Inspector,pertaining to our inspection of the Property at the above referenced property. 1.The fee for our inspection is payable [in full at a time [before /after]the appointment. 2.We will perform a visual inspection of the home/building and provide you with a written report identifying the defects that we (1)observed and (2)deemed material.The report is only supplementary'to the seller’s disclosure. 3.Unless otherwise noted in this Agreement or not possible,wc will perform the inspection in accordance with the current Standards of Practice (SOP)of the International Association of Certified Home Inspectors (“InterNACHI”),posted at www.nachi.org/sop.If your jurisdiction has adopted mandatory standards that differ from InterNACHI’sSOP,we will perform the inspectionin accordance with your jurisdiction’s standards.You understand that InterNACHI's SOP contains limitations,exceptions,and exclusions.You understand that InterNACHI is not a party to this Agreement,has no control over us,and does not employ or supervise us. 4.Unless otherwise indicated in writing,we will NOT test for the presence of radon,a harmful gas.Unless otherwise indicated in writing,we will not test for mold.Unless otherwise indicated in writing,we will not test for compliance with applicable building codes or for the presence of or for any potential dangers arising from the presence of asbestos,lead paint,soil contamination,or other environmental hazards or violations.If any structure you want us to inspect is a log structure or includes log construction,you understand that such structures have unique characteristics that may make it impossible for us to inspect and evaluate them.Therefore,the scope of our inspectionwill not include decay of the interior of logs in log walls,log foundations or roofs,or similar defects. 5.Our inspection and report are for your use only.You give us permission to discuss our observations with real estate agents,owmers,repair persons,or other interested parties.You will be the sole owner of the report and all rights to it.We are not responsible for use or misinterpretation by third parties,and third parties who rely on it in any way do so at their own risk and release us (including employees and business entities)from any liability whatsoever.If you or any person acting on your behalf provide the report to a third party who then sues you and/or us,you release us from any liability and agree to pay our costs and legal fees in defending any action naming us.Our inspection and report are in no way a guarantee or warranty,express or implied,regarding the future use,operability,habitability or suitability of the home/building or its components.We disclaim all warranties,express or implied,to the fullest extent allowed by law. 6.LIMITATION ON LIABILITY AND DAMAGES.We assume no liability for the cost of repair or replacement of unreported defects,either current or arising in the future.In all cases,our liability is limited to liquidated damages in an amount not greater than 1.5 times the fee you paid us.You waive any claim for consequential,exemplary,special or incidental damages or for the loss of the use of the home/building. You acknowledgethat this liquidated damages is not a penalty,but that we intend it to:(i)reflect the fact that actual damages may be difficult or impracticalto ascertain;(ii)allocate risk between us;and (iii) enable us to perform the inspection for the agreed-upon fee.If you wish to eliminate this liquidated damages provision,we are willmg to perform the inspection for an increased fee of $500.00,payable in advance. 7.We do not perform engineering,architectural,plumbing,or any other job function requiring an occupational license in the jurisdiction where the property is located.If we hold a valid occupational license,we may inform you of this and you may hire us to perform additional functions.Any agreement for such additional services shall be in a separate writing. 8.If you believe you have a claim against us,you agree to provide us with the following:(1)written notification of your claim within seven days of discovery,in sufficient detail and with sufficient supporting documents that we can evaluate it;and (2)immediate access to the premises.Failure to comply with these conditions releases us from liability. LO o> cm n3 CL KPB Services Co.Inl’l 2117 N.Dixie Highway Ft.Lauderdale,FL 33305 (305}7 JO-8383 Elecfrical Contractor 13008559 Email:rouen'^;inspcciiurj>jtKlem;ineennu.coni 9.You agree that the exclusive venue for any litigation arising out of this Agreement shall be in the county where we have our principal place of business.If you fail to prove any claim against us,you agree to pay all our legal costs,expenses and attorney’s fees incurred in defending that claim.You agree that the exclusive venue for any legal action against InterNACHI itself,allegedly arising out of this Agreement or our membership in InterNACHI,will be in Boulder County,Colorado.Before bringing any such action, you must provide InterNACHI with 30 days’written notice of the nature of the claim,in sufficient detail and with sufficient supporting documents that InterNACHI can evaluate it.In any action against us or InterNACHI,you waive trial by jury. 10.If a court declares any provision of this Agreement invalid,the remaining provisions remain in effect. This Agreementrepresents our entire agreement;there are no terms other than those set forth herein.All prior discussions are merged into this Agreement.No statement or promise by us shall be binding unless reduced to writing and signed by one of our authorized officers.Any modification of this Agreement must be in writing and signed by you and by one of our authorized officers.This Agreement shall be binding upon and enforceable by the parties and their heirs,executors,administrators,successors and assignees. You will have no cause of action against us after one year from the date of the inspection. 11.Past-due fees for your inspectionshall accrue interest at 8%per year.You agree to pay all costs and attorney’s fees we incur in collecting the fees owed to us.If the Client is a corporation,LLC,or similar entity,you personally guarantee payment of the fee. 12.If you request a re-inspection,the re-inspection is subject to the terms of this Agreement. 13.You may not assign this Agreement. 14.If a court finds any term of this Agreement ambiguousor requiring judicial interpretation,the court shall not construe that term against us by reason of the rule that any ambiguity in a document is construed against the party drafting it.You had the opportunity to consult qualified counsel before signing this. 15.If there is more than one Client,you are signingon behalf of all of them,and you represent that you are authorized to do so. 16.If you would like a large print version of this Agreement before signing it,you may request one by emailing us. 17.PURSUANT TO SECTION 558.0035,FLORIDA STATUTES,AN INDIVIDUAL EMPLOYEE OR AGENT MAY NOT BE HELD INDIVIDUALLY LIABLE FOR NEGLIGENCE. Any dispute,controversy,interpretation or claim including claims for,but not limited to,breach of contract,any form of negligence,fraud,or misinterpretation arising out of,from or related to,this contract or arising out of,from or related to the inspection or inspection report shall be submitted first to a Non-Binding Mediation conference and absent a voluntary settlement through Non-Binding Mediation to be followed by final and Binding Arbitration,if necessary,as conducted by Construction Dispute Resolution Services,LLC or Resolute Systems,Inc.utilizing their respective Rules and Procedures.If you would like to utilize the Mediation or Arbitration services of another dispute resolution provider other than one of those so stated please submit your recommendation to us for our consideration.If the dispute is submitted to Binding Arbitration,the decision of the Arbitrator appointed there under shall be final and binding and the enforcement of the Arbitration Award may be entered in any Court or administrative tribunal having jurisdiction thereof. NOTICE:YOU AND WE WOULD HAVE A RIGHT OR OPPORTUNITY TO LITIGATE DISPUTES THROUGH A COURT AND HAVE A JUDGE OR JURY DECIDE THE DISPUTES BUT HAVE AGREED INSTEAD TO RESOLVE DISPUTES THROUGH MEDIATION AND BINDLNG ARBITRATION. a; CUD nj a. KPB Services Co.Ini"! 2117 N.Dixie Highway Ft.Lauderdale,FL 33305 (305)710-8383 Electrical Contractor 13008559 Email:rouerCa.in.spociion.sandemiinecnru’.coin IMPORTANT:ALL OF THE CONDITIONS OF THIS AGREEMENT APPLY TO ANY AND ALL INSPECTION REPOR TS PRO VIDED TO HOMEOWNER A FTER THIS INSPECTION DA TE, INCLUDING THE FINAL RECERTIFICATION PROVIDED TO THE LOCAL BUILDING DEPARTMENT OFFICIAL DO nj a. KPB Services Co.Tnt’l 2117 N.Dixie Highway Fl.Lauderdale,FL 33305 (305)7l0-8m Electrical Contractor 13008559 Email;rnucrfo.insnectionsjiident.’incerim'.com BOC&agV-.''if*■■■-■Jissr■r-imtuWWi ^●k a:!^YW mt^T 1^ ®N kt :INFRARED TRAINING CENTER Certification #: pi,I ’273120 t ■f,? r :$;t < i ICertifiedThermogI->»■ ■'4 ■>:-i'.»-This certifies that >●» ROGER MORALES I●Ft &I 4 L Has successfully completed all requirements for ITC certification Issue Date;April 08,2022 Expiration Date:April 08,2026 Infrared Training Center www.infraredtraining.com |info@infraredtraining.com m f )●% *r k 24 ITC Certification Renewal CreditsCertifiedIhslructor ©ITC.All rights reserved including the right of reproduction in whole or in part in any form. 'V V '■i 1I !■ TAJ LIMITED GROUP,INC 14216 SW 160*“Avenue Miami,FL 33196 (305)793-7656 RECEIVED SEP 1 3 2022 BY; September 09,2022 Miami Shores Village Development Services Department 10050 Northeast 2"^^Avenue Miami Shores,FL 33138 Attn:Building Official Folio No:11-3206-013-6040 70 Year RecertiHcation Miami Shores Baptist Church 370 Grand Concourse, Miami Shores,FL 33138 Re: '3rRUCTURAfRi\^; approved /date Dear Building Official: TAJ Limited Group,Inc.(TAJ)conducted an inspection for the purpose of determining the general condition of the structural system for the properly referenced above for compliance with Chapter 8, Section 8-11(0 of Code of Miami-Dade County and in accordance with the minimum inspection procedure guidelines as issued by the County Board of Rules and Appeals. Visual examination and manual procedures were used to conduct the inspections.Property management personnel were consulted to obtain the maintenance and repair history of the building. As of the date of the attached report,the building is structurally SAFE for its use and PRESENT occupancy. “As a routine matter,to avoid possible misunderstanding,nothing in this report should be construed directly or indirectly as a guarantee for any portion of the structure system.To the best of my knowledge and ability,this report represents an accurate appraisal of the present condition of the building based upon careful evaluation of observed conditions,to the extent reasonably possible”. Please note that this certification is for the referenced building only and does not include other areas and structures of the community. SUFFICIENCY Please note that this report is limited to the evaluation of the selected areas described herein. Adequacy of the original design or improper construction is beyond the scope of TAJ Limited Group,Inc work.This report should not be used as a repair document,as substantial additional details and information must be furnished to the Contractor to perform adequate repairs. As a routine matter to avoid possible misunderstanding,nothing in this report shall be construed directly or indirectly as a guarantee of any portion of the structure. Miami Shores Baptist ChurchTAJProjectNo.22-132 Page 1 of 3 TAJ LIMITED GROUP,INCReceived SEP 1 2 2022 14216 SW 160***Avenue Miami,FL 33196 (305)793-7656 BY: To the best of our knowledge and ability,this report represents an accurate appraisal of the current condition of the building,based upon careful evaluation of the observed conditions, to the extent reasonably possible. Limitations of Inspection Report 1.1.Observations and data collected by TAJ Limited Group,Inc for this report were obtained during their limited on-site observations. 1.2.Except as otherwise noted,the discussions,opinions,and conclusions described in this report are based on. a.The information provided by various parties without separate verification, b.Limited visual observations:data collected and/or made available concerning current as-built conditions of the building during the site visits to develop this report. 1.3.This report is not intended to provide,and does not provide,a comprehensive study of each noted deficiency and/or damage observed in the building.The report regarding the conditions observed represents professional engineering opinions in accordance with the applicable standard of care. 1.4.Any photos included in this report are meant to support the stated observations of the report authors;and any portions of the included photos that are not in the description of the observation are coincidental and are not relevant to the observation,nor were those portions reviewed.Photos do not include every deficiency and defect observed. 1.5.The information in this report is not meant to be a guarantee or warranty of any kind. The opinions expressed in this report are based primarily on a visual observation of reasonably accessible areas of the building at the time of the site visit(s).TAJ Limited Group,Inc therefore do not assume any responsibility for items that were not examined or were not observed. 1.6.Except as otherwise noted,this report does not contain any professional opinion regarding the completion of any previously recommended improvements associated with the structure. 1.7.TAJ Limited Group,Inc have prepared this report exclusively for the Client.Any use of this report by any other individual(s)or entity without the expressed written consent of TAJ Limited Group,Inc is prohibited.Should another individual or entity rely on this report without the prior specific written consent of TAJ Limited Group, Inc,they shall indemnify TAJ Limited Group,Inc from any damages,losses,or expenses they may incur because of such improper use. TAJ Project No.22-132 Page 2 of 3 Miami Shores Baptist Church TAJ LIMITED GROUP,INC RECEIVED14216SW160*"Avenue Miami,FL 33196 (305)793-7656 SEP 1 2 2022 BY: 1.8.TAJ Limited Group,Inc reserve the irght to revise and supplement this report if in their sole opinion any additional information is made available to them including new documents,physical data,or new evidence. If you have any questions or comments,please contact our office. Respectfully Submitted by. Respectfully Submitted by, TAJ LIMITED GROUP,INC Tahir Iqbal,MS,E.E._ Structural.Engine^r FL.P.E #48061 ^^ TAJ Project No.22-132 Page 3 of 3 Miami Shores Baptist Church I \>v.Vs●V N. /- V <\ t ●●●● F'L O K m /V lit ●●●● I >.●r-E C-T o «● ●o .->&-I I <^■C o <>s t ■■●●●●●● 8 0 0 1 ●●●●●● E >;<-I E E R *S F I o r i <J . ●●●●●● ●●●●●●t V *I I ●.I 3 7 T 12555 Biscayne Blvd.*t 93-4 8 9 4 « ●●♦♦●♦ North Miami,FL 33181 ●#●●●● ●●● ●♦●●●●●● Folio#04-3120-000-0080 OWNER NAME:MIAMI SHORES BAPTIST CHURCH PROPERTY ADDRESS:370 GRAND CONCOURSE MIAMI SHORES,FU 33138 DATE OF INSPECTION:August 31,2021 RE: ♦ TO:CITY OF MIAMI SHORES BUILDING DEPARTMENT OFFICIAL Recertification per Miami-Dade county Ordinance Miami-Dade County,Section 8-11(f) not be granted to the above-mentioned structure.Repairs are needed to Structure as well as Electrical of this building. I have inspected the above-mentioned property and find the building “structurally and electrically”safe for its use and present occupancy”will repairs are being made. As routine matter,in order to avoid possible misunderstanding,nothing in the report attached should be construed directly,or indirectly as a guarantee for any portion of the structure.Future function is not guaranteed in any way.To the best of my ability and knowledge this report represents an accurate appraisal of the present conditions of the building(s)based upon careful evaluation of the observed conditions,to the extent reasonably possible. Thank you for your attention to this matter. Sincerely Horida Builders,Engineers &Inspectors,Inc. A Professional Engineering Firm CA 31260 8-31-2021 CD i I ●APFF. Although this Letter of Recertification allows continued occupancy of the building,issuance of tliis letter should not be construed directly or indirectly as a guarantee of the safety/code compliance of any portion of the structure. I I >.I'li <■.TT <>ISu*S 0E>»■c-I >i'*-.1-;i=s S O O 1S77 125S5 Biscayne Blvd.tP 934 S 9 4 North Miami.FL 33181 ●●●0 ●●●<1 ●noBUILDINGDEPARTMENT MINIMUM INSPECTION PROCEDURAL GUIDELINES.FOR BUILDING’S ELECTRICAL RECERTIFICATION ●●●● BUILDING DEPARTMENT INSPECTION MADE BY: Florida Builders Engineers &Inspectors Gordon W Myers PE 36852 /CA 31260 12555 Biscayne Blvd #934 North Miami,Florida 33181 Tel:(305)895-8001/Fax:(305)895-7001 INSPECTION COMMENCED DATE:08-31-2021 INSPECTION COMPLETED DATE:08-31-2021 Name of Title: Street Address: Legal Description:MIAMI SHORES SEC 1 AMD PB 10-70 ALL BLK BLO^T SIZE IRREGULAR Owner’s Name: Owner’s Mailing Address:370 GRAND CONCOURSE MIAMI SHORES,FL 33138 Folio Number of Building:11-3206-013-6040 Building Code Occupancy Classification;7144 RELIGIOUS -EXEMPT:RELIGIOUS Present Use:CFIURCH BUILDING General Description,Type of Construction,Size,Number of Stories, MIAMI SHORES BAPTIST CHURCH 370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 MIAMI SHORES BAPTIST CHURCH CBS (2)STORY TOTAL ADJ.AREA 29,145SQ FT ACCORDING TOFeatures: P.REC 0 4 I oooo o o o o o o o o 9 00 0 o o o o o o oo o o o o o o o o o oo O O O 0 0 o o o o o o oo o O O O O O 0eoo 0 0 9 0 0 0 o o o oooooo ooooo ooooo oo o o o oo o o o o o o o oooooooooo o o o o o o o o o o 0 0oooooo o i '(o o 0 0.0o O O 00 o o oooo tY .Hooo o oo0o0o o o ooooooo oo o ooooo o oo o o o % I r.? V 1 : i 1I i J f ;i r'f }I GUIDELINES AND INFORMATION FOR RECERTIFICATION OF ELECTRICAL SYSTEM’S OF. FORTY (40)YEAR STRUCTURES —:●●= ●t ●● ●●●● «● 1.ELECTRIC SERVICE 1.Size: ●● Amperage 1 (600)1 (400)1 (300)3 (200) Fuses (X )Breakers (X) Three Phase ()Single (X) (X ) ●●● ●● 2.Phase: 3.Condition: 4.Comments:MAIN DISCONNECT LOCATED AT INTERIOR CLOSET \ ●●●●●● Nee^s Repair (^Good ()Fair HALLWAYS FIRST FLOOR ELECTRICAL PANELS/ELEMENTS HAVE WEAR DUE TO AGE AND USE;HOWEVER THEY ARE OPERABLE AT THIS TIME AND (N FAIR CONDITION.CONTINUED MAINTENANCE IS SUGGESTED TO ENSURE PROPER AND CONTINUED OPERATIONS.UN-EXPOSED ELECTRICAL.ELEMENTS WE.RE NOT INSPECTED;ONLY THOSE ELEMENTS THAT WERE VISBLE AT THE TIME OF THE INSPECTION WERE INSPECTED 2.METER AND ELECTRICAL ROOM: 1.Clearance: 2.Comments:NO METER ROOM PRESENT AT THIS BUILDING Fair ()Requires Correction ()Good (X) 3.GUTTERS 1.Location: 2.Taps and fill: Requires Repair () Requires Repair () Good (X) Good (X) 4.ELECTRICAL PANELS 1.Panel#(1-5)Location:INSIDE EACH OFFICE AND SCHOOL CLASSROOM 2.Panel #()Location: 3.Panel #() 4.Panel #() Location: Location: 5.Panel #()Location: 6.Panel #()Location: 7.Panel #()Location: 8.Panel #() Conditions: Comments:FUSE PANEL INSIDE ROOM 202-203 SHOWING WEAR TO AGE.UPDATE TO BREAKER PANEL WITH LICENSED ELECT! Location: Good ()Requires Repairs (X ) 3 ●●# ♦ ●●●●● ♦♦●« ●«● ●●●● ●● 9 9 9 99 9 9 ●● 5.BRANCH CIRCUITS 1.Identified: 2.Conductor: 3.Comments;LIGHT SWITCH ON WALL IN KITCHEN NEBD^ REPLACEMENT ●●●●Must be identified,(X )● Good (X )Deteriorated ()Must be Replaced!()●● Yes ()●●●● ●●♦ ●●●●● 6.GROUNDING OF SERVICE Condition: Comments: ●●● Repairs Requifcd *()Good (X )●● ●●●●●●●● ●● 7,GROUNDING OF EQUIPMENT Good (X )Repairs Required ()*●●Condition: Comments: 8.SERVICE CONDUITS/RACEWAYS Good (X )Repairs Required ()Condition: Comments: 9.SERVICE CONDUCTORS AND CABLES Good (X )Repairs Required ()Condition: Comments: 10.TYPES OF WIRING METHODS Condition: Conduit Raceways: Conduit PVC: NM Cables: BX Cables: Repairs Required () Repairs Required () Repairs Required () Repairs Required () Good (X ) Good (X) Good () Good () 11.FEEDER CONDUCTORS Condition: Comments: Repairs Required ()Good (X ) 12.EMERGENCY LIGHTING Condition:Repairs Required (X )Good () Comments:SOME LIGHTS THROUGHOUT BUILDING NOT WORKING 13.BUILDING EGRESS ILLUMINATION Good (X)Repairs Required ()Condition: Comments: 14.FIRE ALARM SYSTEM Condition: Comments: Repairs Required ()Good (X ) 4 \ ♦ # ●●♦ ♦●● ♦●♦ ●●●● ●●●●# ●● ●● # 15.SMOKE DETECTORS Condition: Comments N/A ●♦●● Repairs Required (,*),Good ()●♦●● 16.EXIT LIGHTS Condition: Comments: ●●●● *●●●Repairs Required"*(X )●Good () SOME LIGHTS THROUGHOUT BUILDING NOf'^^mKING ●● ●●●«●●●●●●●● 17.EMERGENCY GENERATOR Good () ●●●*●●●* Repairs Required ^**)Condition: Comments:N/A ●● ●● 18.WIRING IN OPEN OR UNDER COVER PARKING GARAGE AREAS Repairs Required ()Good (X )Condition: Comments: 19.OPEN OR UNDERCOVER PARKING SURFACE AND SECURITY LIGHTING Repairs Required (X )Good () Comments:LIGHT SWITCHES AT FRONT EXTERIOR ARE NOT WATER Condition: PROOF AND MISSING GFCL 20.SWIMMING POOL WIRING Condition: Comments:N/A Repairs Required ()Good () 21.WIRING OF MECHANICAL EQUIPMENT Good (X )Repairs Required ()Condition: Comments: GENERAL ADDITIONAL COMMENTS:ELECTRICAL REPAIRS NECESSARY CONSULT WITH LICENSED ELECTRICIAN TO MAKE REPAIRS Continued maintenance is suggested to maintain proper function.Inspection is made to what is readily visible and accessible only. AS A ROUTINE MAITER.AND IN ORDER TO AVOID POSSIBLE MUSUNDERSTANDING NOTHING IN THIS INSPECTION REPORT FORM ATTACHED MINIMUM INSPECTION GUIDELINES AND OUR NON-DESTRUCTIVE OBSERVATION SHOULD BE CONSTRUED DIRECTLY OR INDIRECTLY.AS A GUARANTEE OR WARRANTEE OF ANY PORTION OF THE STRUCTURE.TO THE BEST OF MY KNOWLEDGE AND ABILITY THIS REPORT REPRESENTS AN ACCURATE APPRAISAL OF THE PRESENT CONDITION OF THE STRUCTURE BASED UPON CAREFUL EVALUATION OF THE OBSERVED CONDITIONS TO THE EXTENT REASONABLY POSSIBLE. PURSUANT TO SECTION 558,0035.FLORIDA STATUTES.AN INDIVIDUAL EMPLOYEE OR AGENT MAY NOTINDIVIDUALLYLIABLEFORNEGLIGENCE.///HEL,D> 'ih 8-31-2021 5 t ●●●● # ●● ♦●« ●●●●* ●● ♦ # ●●»● 4 4Sri.●●●● T «-»I TV f.r-E cETVC-1 TV li I-:II *v J I ●.r i<i >●●●●●●I t.oG"r V i t .' 8 0 0 189>4877 12555 Biscayne Blvd.*t 934 North Miami.FL 33181 ●● ●●● * ●●●●●● BUILDING DEPARTMENT MINIMUM INSPECTION PROCEDURAL GUIDELINES FOR * BUILDING’S STRUCTURAL RECERTIFICATION' BUILDING DEPARTMENT ●● 444444 4 4 INSPECTION MADE BY: Florida Builders Engineers &Inspectors Gordon W Myers PE 36852 /CA 31260 12555 Biscayne Blvd #934 North Miami,Florida 33181 Tel:(305)895-8001/Fax:(305)895-7001 INSPECTION COMMENCED DATE:08-31-2021 INSPECTION COMPLETED DATE:08-31-2021 MIAMI SHORES BAPTIST CHURCH 370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 Name of Title: Street Address: Legal Description:MIAMI SHORES SEC I AMD PB 10-70 ALL BLK B LOT SIZE IRREGULAR MIAMI SHORES BAPTIST CHURCHOwner’s Name: Owner’s Mailing Address;370 GRAND CONCOURSE MIAMI SHORES,FL 33138 Folio Number of Building:11-3206-013-6040 Building Code Occupancy Classification:7144 RELIGIOUS -EXEMPT:RELIGIOUS Present Use:CHURCH BUILDING General Description,Type of Construction,Size,Number of Stories, CBS (2)STORY TOTAL ADJ.AREA 29,145SQ FT ACCORDING TOFeatures: P.REC 6 ADDITIONS TO ORIGINAL STRUCTURE: No visible additions noted to original structure at this time.This determination is made on what is visible and accessible at the site with no inquiry to construction plans and or microfilms.●●●● 2.PRESENT CONDITION OF STRUCTURE ●●●●●●a.General aiignmenl (not good,fair,poor,explain if significant)POOR I.Bulging MINOR STRUCTURAL EXPANSION THAT IS 1TPICAL FOR THIS STRUCTURE DOES NOT WARRANT REPAIRS AT THIS TIME ●●●●« TO PICAL AND MINOR DOES NOT WARRANT STRUCTURAL REPAfttS'AT THIS TIMTl* STRUCTURALCONDITIONS ARE FU’NCnONAL AT THIS TIME ●●●●*-** Settlement2. ●●● OF STRUCTURAL SIGNIFICANCE3.Defections ●●●●●●●●EXPANSION WARRANTED FOR REPAIRS AT THIS TIMEExpansion4, ●● ●●CONTRACTION WARRANTED FOR REPAIRS AT THIS TIME.Comraciion5. Portions showing distress (note beams,columns,structural walls,floors,roofs)NONE VISIBLEb. Surface conditions-describe general conditions of finishes,cracking,spalling,peeling signs of moisture penetration &stains: CRACKING NOTED AT EXTERIOR WALL FASCADE AS WELL AS AT WALTS AS MSIBLE FROM ROOF.W ATER PROOFING REPAIRS NEEDED AT THIS TIME c. Crack's-note location in significant members.Identify crack size as HAIRLINE if barely dissemble;FINE if less than I mm in width;MEDIUM if between 1 and 2 mm in width;WIDE if over 2 mm. STRUCTURAL REPAIRS.BRICK VENEER IS DETACHING FROM CBS WALL.REQUIRE REPAIRS AT ONCE. d. FINE WATER INTRUSION NOTED /WARRANTED e.General extent of deterioration -cracking or spalling of concrete or masonry;oxidation of metals;rot or borer attack in wood. MINOR REBAR EXPOSURE NOTED AT ROOF /CEH.ING IN TOWER. f Previous patching or repairs:YES Nature of present loading;indicate Residential,Commercial,other magnitude.g 3.INSPECTIONS Date of notice of required inspection:UNKNOWTV Daie(s)of actual inspection: Name and qualification of individual submitting report:Gordon W.Myers PE 36852 Description of any laboratory or other formal testing,if required,rather than manual or visual procedures: Structural repair note appropriate line: I.None Required XXXXXXX 2.Required (describe and indicate acceptance) a. b.8-31-2021 c. d. N/A e. SUPPORTING DATA4. II Sheet written dataa. Photographsb.0 0 Drawings or sketchesc. 5.MASONRY BEARING WALL =Indicate good,fair,poor on appropriate lines: FAIR NONE FAIR FAIR FAIR FAIR FAIR FAIR POOR NEED REPAIRS AS AP POOR Concrete masonry units: Clav tile or terracotta units: a. b. c.Reinforced concrete tile columns: d.Reinforced concrete tile beams: e,Lintei: f.Other type bond beams g.Masonry finishes -exterior I.Stucco 2.Veneer 3.Paint Only 4.Other (describe) 8-31-2021 7 ●●●● ●●●●● ♦ ●#●● 99 9 9 9 5.MASONRY BEARING WALL (con’t)POOR/CRACKING NOTED ON WALLS BY MAIN OFFICE ENTRANCE AS WELL AS AT CATWALK ABOVE MAIN OFFICE. h.Masonry finishes -interior ●«●●NONE FAIR FAIR POOR I.Vapor barrier 2.Furring ami Plaster 3.Paneling 4.Paint Only 5.Other (describe) i.Cracks: 1.Location -note beams,columns,otiter 2,Description:WARILVNTED TO Jl’STIFY REPAIRS AT THIS TIME j.Spalling: 1.Location-note beams,columns,other 2-Description k.Rebar corrosion-check appropriate line: 1.None visible 2.Minor-patching will suffice 3.Significant -but patching will suffice 4.Significant -structural repairs required I.Samples chipped out for examination in spall areas 1.^ 2,YES -describe color texture,aggregate,and general quality ●●●● ●●♦ CONTRACTING &EXPANDING CRACKING NOTED ●●●● ●●●●●● *NONE VISIBLE ●●● ●● ●●●●●●●● N/A ●●●●●●●●xxxx « «*● ●● xxxx 6.FLOOR AND ROOF SYSTEM a.Roof: Describe (flat,slope,type roofing,type roof deck,conditions SLOPE ROOF &FLAT ROOF /WOOD DECKING. ROOF IS WATER TIGHT AT THIS TIME 1. 2.Note water tanks,cooling towers,air conditioning equipment,signs,other heavy equipment and conditions of support:FAIR 3.Note types of drains and scupper and condition of cooling towers,air conditioners:DRAINAGE TO PERIMETER OF ROOF b.Floor system (s): 1.Describe (type of .system framing,material,spans,condition)SLAB/FAIR c.Inspection -note exposed areas available for inspection,and where it was found nccessaiy'to open ceilings,etc.for inspection of typical framing members:ALL ACCESSIBLE AREAS WERE INSPECTED. 7.STEEL FRAMING SYSTEM NO STEEL FRAMING CBSa.Description b.Exposed Steel -describe condition of paint &degree of corrosion c.Concrete or other fireproofing -note any cracking or spalling,and note where any covering was removed for inspection SATISFACTORY .AT THIS TIME NONE d.Elevator sheave beams &connections and machine floor beams -note condition:N/A 8 4 \ ●♦ ●● ●● ●● ♦ 8.CONCRETE FRAMING SYSTEM a.Full description of structural system CBS STRCCTl'RE b.Cracking 1.Not Significant 2.Location and description of members affected and type cracking XXXX /EXPANSION AND C0NTRACTT40N CRACKING NOTED AT THIS TIME.BRICK VENEER COLUMNS AND PLANTERS SHOWI^C.(^4CKINQ AT , EXTERIOR ●●●●● ●*●● c.General condition POOR ●●●● d.Rebar corrosion ●check appropriate line: 1.Non visible XXX 2.Location and description of members affected and type cracking 3-Significant -but patching will suffice 4.Significant -structural repairs required (describe) ●●● #●●●●●●●●● ♦♦ c.Samples chipped out in spall areas: 1.No 2.Yes,describe color,texture,aggregate,general quality; ●● XXXX ●●♦ 9.WINDOWS a.Tvpe (Window,steel,aluminum,jalousie,single hung,double hung,casement,awning,pivoted,llxed,other) ALUMINUM b.Anchorage -type &condition of fasteners and latches.SCREWED INTO WINDOW BliC'KS c.Sealant-type of condition of perimeter sealant &at mullions:TYPICAL CHAULKING AT FRAMES AND GASKETING AT GLAZING d.Interior seals -type &condition at operable venLs:GASKETING AT GLAZING SATISFACTORY ST THIS TIMEe.Conditions: 10.WOOD FRAMING a.Type -fully describe if mill construction,light construction,major spans,trusses,THE ROOF ARE FR.AMED WITH DIMENSIONAL RAFTERS AND JOISTS FRAMING LIMITED ACCESS TO VIEW NOTED. b.Note metal fitting i.c.,angles,plates,bolts,split pintles,other,and note condition:METAL FITTING IN FUCTIONAL CONDITIONS/LIMITED ACCESS FAIR CONDITIONS /LIMITED VIEWc.Joints -note if welt fitted and still closed: FAIR ROOF DRAINS TO PERIMETERd.Drainage -note accumulations of moisture; e.Ventilation -note anv concealed spaces not ventilated:ATFIC TYPICALLA’VENTED WITH PERIMETER SOFFIT VENTS f Note any concealed spaces opened for inspection:NONE/ALL .AREAS .AVAIL.ABLE WERE .ACCESSED II.GENERAL ADDITIONAL COMMENTS; THIS REPORT DOES NOT REFLECT ANY POTENTIAL VIOLATIONS THAT MAY BE PRESENT ON THE BUILDING.THIS IS ONLY AN INSPECTION OF THE VISUAL CONDITIONS FOUND DURING OUR INSPECTION. Continued maintenance is suggested to maintain proper function.Inspection is made to what is readily accessible and visible only. AS A ROUTINE MATTER,AND IN ORDER TO AVOID POSSIBLE MUSUNDERSTANDING NOTHING IN THIS INSPECTION REPORT FORM ATTACHED MINIMUM INSPECTION GUIDELINES AND OUR NON-DESTRUCTIVE OBSERVATION SHOULD BE CONSTRUED DIRECTLY OR INDIRECTLY,AS A GUARANTEE OR WARRANTEE OF ANY PORTION OF THE STRUCTURE.TO THE BEST OF MY KNOWLEDGE AND ABILITY THIS REPORT REPRESENTS AN ACCURATE APPRAISAL OF THE PRESENT CONDITION OF THE STRUCTURE BASED UPON CAREFUL EVALUATION OF THE OBSERVED CONDITIONS TO THE EXTENT REASONABLY POSSIBLE. THIS REPORT DOES NOT REFLECT ANY POTENTIAL VIOLATIONS THAT MAY BE PRESENT ON THE BUILDING.THIS IS ONLY AN INSPECTION OF THE VISUAL CONDITIONS FOUND DURING OUR INSPECTION.IF A VIOLATION EXISTS THEN THIS REPORT IS INVALID,PURSUANT TO SECTION 558,0035.FLORIDA STATUTES,AN INDIVIDUAL EMPLOYEE OR AGENT MAY NOT BE HELD INDIVIDUALLY LIABLE FOR NEGLIGENCE,« 8-3 (-202 / / 9 ''i I 7S E C T C>IS I ■>C o .I t ■■ E rv C-■>>■E E K ?S J*w- 1 >1 -K }o r i cl -‘'■●●●●S <?r V »7 7 12555 BIscayne Blvd.U 934 North Miami.FL 33181 ●●●●8 0 0 1894 CERTIFICATION OF COMPLIANCE WITH PARKING LOT ILUjjMNATljflV *● STANDARDS IN CHAPTER 8C OF THE CODE OF MIAMH)APE .... COUNTYAND OUTDOOR LIGHTING OVERSPILLING SECTIONOS-^l ● THE CODE OF MIAMI DADE COUNTY ●● INSPECTION MADE BY:..*!... Florida Builders Engineers &Inspectbrs * Gordon W Myers PE 36852 /CA 31260 12555 Biscayne Blvd #934 North Miami,Florida 33181 Tel:(305)895-8001/Fax:(305)895-7001 INSPECTION COMMENCED DATE:08-31-2021 INSPECTION COMPLETED DATE:08-31-2021 MIAMI SHORES BAPTIST CHURCH 370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 Name of Title: Street Address: Legal Description:MIAMI SHORES SEC 1 AMD PB 10-70 ALL BLK B LOT SIZE IRREGULAR MIAMI SHORES BAPTIST CHURCHOwnersName: Owner’s Mailing Address:370 GRAND CONCOURSE MIAMI SHORES,FL 33138 Folio Number of Building:11-3206-013-6040 Building Code Occupancy Classification:7144 RELIGIOUS -EXEMPT:RELIGIOUS Present Use:CHURCH BUILDING General Description,Type of Construction,Size,Number of Stories, CBS (2)STORY TOTAL ADJ.AREA 29,145SQ FT ACCORDING TO P.RECFeatures: The undersigned stales the following: 1 am a Florida registered professional engineer with an active license.1. On August 31,2021,at 9PM I measured the level of illumination in the parking lot(s)serving the above referenced building. 2. Maximum xx foot candle per SF,Minimum xx foot candle per SF,Minimum to Maximum ratio XX,foot candle,xx average per SF.NO PARKING LOT ON THIS PROPERTY.ONLY STREET PARKING.PARKING LOT IS ON ANOTHER FOLIO# 3. The level of illumination provided in the parking lot(s)meet the minimum standards for the occupancy classification of the building as established in Section 8C-3 of the Code of Miami-Dade County. 4. The level of outdoor lighting overspill meets the limitations established in Section 33-4.1 of the Code of Miami Dade County. 5. Gordon W.Myers PE 36852 Florida Builders,Engineers &Inspectors,Inc. A Professional Engineering Finn CA 31260 8-3I-202I 10 1 f % ## ●A ●● ●● ●● ●●● ♦● ●● ●● »* Mil.1 I ●>:s»f E c T o « 1 to C o <●«f.t ■■ E >.:c»i >.'E E R e. t I o r I cl .O ●!●<'r V I I 1 <I ●●●●8 0 0 1877 12555 Biscayne Blvd.tt 934- 8 9 -a ●●●● North Miami,FL 33181 CERTIFICATION OF COMPLIANCE WITH PARKING LOT GUA^^ILSREQUIREMENTSINCHAPTER8COFTHECODEOFMIAMl-DAPE.COUNTy ■, ●●●●●● # INSPECTION MADE BY;●●V ● Florida Builders Engineers &InspettonGordonWMyersPEJ6852(CA 3F2^(V** 12555 Biscayne Blvd #954 ● North Miami,Florida 33181 ●●● Tel;(305)895-8001/Fax:(305)895-7001 INSPECTION COMMENCED DATE;08-31-2021 # INSPECTION COMPLETED DATE;08-31-2021 Name of Title; Street Address; Legal Description;MIAMI SHORES SEC I AMD PB 10-70 ALL BLK B LOT SIZE IRREGULAR Owner's Name: Owner’s Mailing Address:370 GRAND CONCOURSE MIAMI SHORES,FL 33138 Folio Number of Building:11-3206-013-6040 Building Code Occupancy Classification:7144 RELIGIOUS -EXEMPT:RELIGIOUS Present Use:CHURCH BUILDING General Description,Type of Construction,Size,Number of Stories, MIAMI SHORES BAPTIST CHURCH 370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 MIAMI SHORES BAPTIST CHURCH CBS (2)STORY TOTAL ADJ.AREA 29,145SQ FT ACCORDING TO P.RECFeatures: The undersigned stales the following; 1 am a Florida registered professional engineer or architect with an active license.On August 31,2021 I inspected the parking lots servicing the above erferenced building for compliance with Section 8C-6 and determined the following (check only one); The parking lottsi is not adjacent to or abutting a canal,lake or other body of water. The parking lot(s)is adjacent to or abutting a canal,lake or other body of water and parked vehicles arc protected by a guardrail that complies with Section 8C-6 of the Miami-Dadc County Code. The parking lot(s)is adjacent to or abutting a canal,lake or other body of water and parked vehicles are not protected by a guardrail that complies with Section 8C-6 of the Miami-Dadc County Code.I have advised the property'owner that he/shc must obtain a pennit for die installation of the guardrail and obtain all required inspection approvals to avoid enforcement action. Gordon W.Myers PE 36852 Florida Builders,Engineers &Inspectors,Inc. A Professional Engineering Firm CA 31260 8-31-2021 11 RECEIVED BY: FLORIO/V lil.II.OKKS I N I*I-.f r o It sr.X c.I X K .r It s "Serving Florida Const to Coast” 87 7-S 9 4-S 0 0 1 12555 Biscayne Blvd.#934 North Miami.FL 33181 BUILDING DEPARTIVIENT MINIMUM INSPECTION PROCEDURAL GUIDELINES FOR BUILDING’S RECERTIFICATION PUNCH LIST REPORT ●● ●●«● INSPECTION MADE BY- Florida Builders Engine^jj^jpspeetprs 12555 Biscayne Blvd #934.“ii-A.3125p:.,● North Miami,Florida 33181 Tel:(305)895-8001/FaxJ (305^895-7001 INSPECTION COMMENCED DATE:8-31-2021 INSPECTION COMPLETED DATE:8-31-2021 ●●●● ●●● kalwoocHirm'^comcasLnetSENTVIA:●●●● Name of Title: Street Address: Legal Description:MIAMI SHORES SEC I AMD PB 10-70 ALL BLK B LOT SIZE IRREGULAR Owner's Name; Owner's Mailing Address:370 GRAND CONCOURSE MIAMI SHORES.FL 33138 Folio Number of Building:11-3206-013-6040 Building Code Occupancy Classification:7144 RELIGIOUS -EXEMPT:RELIGIOUS Present Use:CHURCH BUILDING General Description.Type of Construction.Size.Number of Stories. MIAMI SHORES BAPTIST CHURCH 370 GRAND CONCOURSE MIAMI SI lORES.FL 33138-2747 MIAMI SHORES BAPTIST CHURCH CBS (2)STORY TOTAL ADJ.AREA 29.I45SQ FT ACCORDING TOFeatures: P.REC 8-31-2021 4 4 4 4 4 4 4 ●●● 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 44 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 44 4 4 4 444 1.ENSURE THAT ALL BREAKERS INSIDE ALL ELECTRICAL PANELS INSIDE THE UNITS ARE IDENTIFIED AND LABELED IN ENGLISH. NOTE:DONOT LABEL WITH SHARPIE AND EXPECT TO PASS RECERTIFICATION.GRID CHART DIRECTORY MUST BE AFFIXED TO INSIDE OF BREAKER PANEL WITH CORRESPONDING IDENTIFICATION OF BREAKERS IN ALL PANELS.ENSURE THAT THERE ARE NO OPEN SLOTS IN BREAKER PANELS.USE PLASTIC KNOCK OUT COVERS...NO ELECTRICAL BLACK TAPE ●●● ●●● ●●●● ●●● #● F.\SEL iOCA TED.1T ROOF TOP OPES KSOCK OUTFRESEST 2.FUSE PANEL LOCATED IN ROOM 202 NEEDS TO BE UPDATED TO BREAKER PANEL. I -) #●● ●●● ●●● ●●●● ●●● ●● ●● ♦# ENSURE ALL EMERGENCY LIGHTS AND ILLUMINATED EXIT SIGNS THROUGHOUT THE BUILDING ARE FUNCTIONAL.Some lights not working at this time. 3. LIGHT SWITCH AT ENTRY TO SANCTUARY NEEDS TO HAVE WATER PROOF COVER OR LIGHT SWITCHES REMOVED TO INSIDE. 4. t # ●● ●● ●● ●● 5.CAP/REMOVE OUTLETS AND SWITCH NEXT TO HOOD IN KITCHEN. r t V %wi .iV I/ I r i t ●●● ●●● ●●●●●● #f ●●● ●#●●4 #●● ●♦ # ●● 4 ♦#●● ●●● ●●● ●●●t ●# ●● ♦ ●● ♦ ●●● ●♦● ●●● #● #●● ●● ♦ ●●● ●●♦ ●●# ●● THIS IS WORK IS TO BE DONE BY UCESSED PROFESSIONALS AMD IN ACCORDANCE TO F.B.C. AND N.E.C.BUILDING PERMITS ARE NECESSARY FOR MANY OF THE REPAIRS NOTED ABOVE. DO NOT PERFORM ANY WORK HITHOLT PROBER PERMITS/INSPECTIONS BY BUILDING OFFICIALS.FINAL INSPECTION WILL NOT BE APPROVED BY OCR FIRM WITIIOCT PROPER BCILDING PERMITS AND FINAL INSPECTIONS HA IING BEEN PERL ORMED BY LOCAL BUILDING OFFICIALS. WE ARE NOT RESPONSIBLE FOR REQUESTING EXTENSIONS TO THE COUNTY/CITY BUILDING OFFICIALS FOR THE COMPLETION OF THE RECERTIFICATION PROCESS.BUILDING OWNER IS SOLELY RESPONSIBLE FOR THIS TASK. THIS INSPECTION REPORT IS OF THE DEFICIENCIES FOUND DURING OUR INSPECTION OF THE ABOVE REFERENCED PROPERTY .AND NOTE TH.4T ADDITIONAL DEFICIENCIES M.4Y BE DISC 'OVERED DURING FURTHER INSPECTION.WE RESERVE THE RIGHT TO .AMEND THIS !.. 4 4REPORT.AS .NEC'ESSSA R). ●●4 4 44 4 4 4 4 THE INSPECTION FEE CHARGED FOR THIS INSPECTION REPORT IS NON\i;;y‘^DABLE*WY DO NOTGU.AR.ANTEE THAT THE COUNTY'CITY OFFICIAL WILL GR.ANT REA'ER^TjYiCA TIO^'.*^ THIS REPORT IS ONLY OUR PROFESSIONAL OPINION OF WHAT WILL BE REOUlli^^AND :●● CONSIDERED SAFE FOR CONTINUED OCCUPANCY FOR THE CITY OR COUNT^M'^JCIALJO GRANT RECERTIFICA TION. 4 4 4 4 4 4 4 4 4 4 4 4 4 4 44444 4 4 4 4 ADDITIONAL INSPECTION TO RE-CERTIFY BUILDING AFTER COMPLETION Of (YORK IS [}0%'E>* THA T IS WITHIN 90 DA YS OF THIS REPORT IS DONE A T NO .AADITIONAL CHARGE.*4 4 Please provide photographs,invoices of repairs,work orders etc.to assist with this process of final recertificationinspection. INSPECTIONS NEEDED AFTER 90 DA YS TO BE SCHEDULED THROUGH OFFICE AND FEE 5 495.00IS WE RESERVE THE RIGHT TO DENY ISSUING FINAL CLEAR RECERTIFIC.ATION OF BUILDING IF REPAIRS .MADE .AND OR CONDITIONS ARE NOT DEEMED S.ATISF.ACTORY OR APPROVED BY OUR FIRM.AS SAFE FOR CONTINUED OCCUP.ANCY NUM9ER M1356 \ .<3 tt. "2X0o-n Uj% d-1-2021 Roger Morales MSEng.SI.HI President.Director of Operations Florida Builders.Engineers &Inspectors.Inc. A Professional Engineering Firm CA 31260 7 4 44 ●444 4 4 4 4 4 44 4 4 44 444 4 4 44 4 4 This is an Agreement between you.the undersigned Client,and us,the Inspector,pertaining to our inspection of the Property at the above referenced property. I.The fee for our inspection is payable [in full at a time [before after]the appointment. 2.We will perform a visual inspection of the home-building and provide you with a written report identifying the defects that we (1)obserx'ed and (2)deemed material.The report is only supplementaiy to the seller's disclosure. 3.Unless otherwise noted in this Agreement or not possible,wc w'ill perform the inspection in accordance with the current Standards of Practice (SOP)of the International Association of Certified Home Inspectors (■'InterNACHI"),posted at www.nachi.org sop.If your jurisdiction has adopted mandatory standards that diffei-from ImerNACHrs SOP,we will perform the inspection in accordance with your Jurisdiction's standards.You understand that InterNACI ll's SOP contains limitations,exceptions,and exclusions.You understand that InterNACHI is not a party to this Agreement,has no control over us.and does not enjplpy!,or supervise us.* 4.Unless otherwise indicated in writing,we will NOT test for the presence of radon,a hamifu]gas.Lfn1es*s otherwise indicated in writing,we will not lest for mold.Unless othenvise indicated in we vvill not test for compliance with applicable building codes or for the presence of or for any potfiiti^/fengers****** arising from the pre,sence of asbestos,lead paint,soil contamination,or other environm^g^^hazardspr ,, violations.If any structure you want us to inspect is a log structure or includes log constfi3i;ti(3n,you*,;*,* understand that such structures have unique characteristics that may make it impossible efw Ai6*to inspect, and evaluate them.Therefore,the scope of our inspection will not include decay of the»interi»r of lo^s in ●log walls,log foundations or roofs,or similar defects.●●●●● ●*●●● ●●●«.●●5.Our inspection and report are for your use oiiK’.You give us permission to discuss our observations with real estate agents,owners,repair persons,or other interested parties.You v^ill be the sole owner of the report and all rights to it.We are not responsible for use or misinterpretation by third parties,and third parties who rely on it in any way do so at their own risk and release us (including employees and business entities)from any liability whatsoever.Ifyou or any person acting on your behalf provide the report to a third party who then sues you and/or us,you release us from any liability and agree to pay our costs and legal fees in defending any action naming us.Our inspection and report are in no way a guarantee or warranty,express or implied,regarding the future use.operability,habitability-or suitability-of the home building or its components.We disclaim all warranties,express or implied,to the llillest extent allowed by law. ●«●●● 6.LIMITATION ON LIABILITY AND DAMAGES.We assume no liability’for the cost of repair or replacement of unreported defects,either current or arising in the future.In all cases,our liability’is limited to liquidated damages in an amount not greater than 1.5 times the fee you paid us.You waive any claim for consequential,exemplary,special or incidental damages or for the loss of the use of the home/building. You acknow’ledge that this liquidated damages is not a penalty,but that we intend it to:(i)rellect the fact that actual damages may be difficult or impractical to ascertain:(ii)allocate risk betw'een us;and (iii) enable us to perfori’n the inspection for the agreed-upon fee.Ifyou w'ish to eliminate this liquidated damages provision,we are willing to perform the inspection for an increased fee of S500.00.payable in advance. 7.We do not perform engineering,architectural,plumbing,or any other job function requiring an occupational license in the jurisdiction where the property is located.Ifwe hold a valid occupational license,we may inform vou of this and >ou may hire us to perform additional functions.Any agreement for such additional services shall be in a separate writing. 8.If you believe you have a claim against us,you agree to provide us with the following;(1)written notification of your claim within seven dav’s of discovery,in sufficient detail and with sufficient supporting documents that we can evaluate it:and (2)immediate access to the premises.Failure to comply with these conditions releases us from liabilitv’. 8 9,You agree thal llie exclusive venue for any litigation arising out of this Agreement shall be in the county where we have our principal place of business.If you fail to prove any claim against us,you agree to pay all our legal costs,expenses and attorney's fees incurred in defending that claim.You agree that the exclusive venue for any legal action against InterNACHl itself,allegedly arising out of this Agreement or our membership in InterNACHl.will be in Boulder County.Colorado.Before bringing any such action, you must provide InterNACHl with 30 days'written notice of the nature of the claim,in sufficient detail and with sufficient supporting documents that InterNACHl can evaluate it.In any action against us or InterN.ACHI.you waive trial by juiy. 10.If a court declares an>'provision of this Agreement invalid,the remaining provisions remain in effect. This Agreement represents our entire agreement:there are no terms other than those set forth herein.All prior discussions are merged into this Agreement.No statement or promise by us shall be binding unless reduced to writing and signed by one of our authorized officers.Any modification of this Agreement must be in writing and signed b>’you and b>one of our authorized officers.Tliis Agreement shall be binding upon and enforceable by the parties and their heirs,executors.admini.strators.successors and assigne£.‘i...,I. You will have no cause of action auainst us after one year from the dale of the inspection.●●*''●●●●●●● «● 11.Past-due fees for your inspection shall accrue interest at 8%per year.You agree toj^awlfcosts and ** attorney's fees we incur in collecting the fees owed to us.If the Client is a corporation.or simijar entity’.>011 personally guarantee payment of the fee. ●●●●●● ●●●● 12.If >’ou request a re-inspection,the re-inspection is subject to the terms of this AgreepiieTU.,* 13.You mav not assign this Aureement.●«●●“●* ●●● 14.If a court finds any term of this Agreement ambiguous or requiring judicial interpreti?t«)n.<he court shall not construe that term against us by reason of the rule thal any ambiguity in a document is construed against the party drafting it.You had the opportunity to consult qualified counsel before signing this. «»●●●● 15.If there is more than one Client,you are signing on behalf of all of them,and you represent thal you are authorized to do so. 16.If you would like a large print version of this Agreement before signing it.you ma>’request one by emailing us. I 7.PURSUANT TO Si-CTION 55X.()035.ri.ORIDA ST.\TUT1-S.AN INDIVIDUAI.UMPl OY14-OR AGF.NT MAY NOT RF HFI.DlMDlVIDUAi.I.Y l.lARt.F FOR NFCil.IGI^NCl-:. Any dispute,controversy,interpretation or claim including claims for.but not limited to.breach of contract,any form of negligence,fraud,or misinterpretation arising out of,from or related to.this contract or arising out of.from or related to the inspection or inspection repon shall be submitted first to a Non- Binding Mediation conference and absent a voluniar>'settlement through Non-Binding Mediation to be followed b\’final and Binding Arbitration,if necessar>’.as conducted by Construction Dispute Resolution Services.LLC or Resolute Systems.Inc.utilizing their respective Rules and Procedures.If you would like to utilize the Mediation or Arbitration services of another dispute resolution provider other than one of those so stated please submit your recommendation to us for our consideration.If the dispute is submitted to Binding Arbitration,the deci.sion of the Arbitrator appointed there under shall be final and binding and the enforcement of the Arbitration Award may be entered in any Court or administrativ e tribunal havingjurisdictionthereof NOTICE:YOU AND WE WOULD HAVE A RIGHT OR OPPORTUNITY TO LITIGATE DISPUTES THROUGH A COURT AND HAVE A JUDGE OR JURY DECIDE THE DISPUTES BUT HAVE AGREED INSTEAD TO RESOLVE DISPUTES THROUGH MEDIATION AND BINDING ARBITRATION. IMPORTA.ST:ALL OF THF CO.\DniO.\S OF THIS AGRFE.\/E\T APPLY TO Aj\Y A.\D ALL L\SPECTIO.\REPORTS PROY IDED TO HOMEOW!SER AFTER TII/S L\SPECTIO.\DA TE, I\CLiDI.\G THEFIX iL RECERTIFICATIOX PROVIDED TO THE LOCAL BUILDIXG DEPARTMEXT OFFICIA L 9 c ●● Certification of Compliance with Parking Lot Guardrails Requirements in Chapter 8C of the Code of Miami-Dade County Date:09/08/2022 RECEIVED SEP 1 2 20ZZ370GrandCon,Miami Shores,FL 33PropertyAddress: BY: 11-3206-013-6040FolioNo.: Building Description:Two Story CBS Religious Building 370Bldg.No.: The undersigned states the following: I am a Florida registered professional engineer or architect with an active license. ,I inspected the parking lot(s)serving the above referenced building for compliance with Section §8C-6 and determined the following (check only one): On 09-08-2022 (●The parking lot(s)is/are not adjacent to or abutting a canal,lake or other body of water. r The parking lot(s)is/are adjacent to or abutting a canal,lake or other body of water and parked vehicles are protected by a guardrail that complies with Section §8C-6 of the Miami-Dade County Code. C The parking lot(s)is/are adjacent to or abutting a canal,lake or other body of water and parked vehicles are not protected by a guardrail that complies with Section §8C-6 of the Miami-Dade County Code.1 have advised the property owner that he/she must obtain a permit for the installation of the guardrail and obtain all required inspection approvals to avoid enforcement action. TAHIR IQBAL P.E.No.48061 Signature and Seal of Professional Engineer or Architect Print Name Revised June 2014 r /●s r Go gleMaps 370 Grand Concourse Imageries O 2022 ONES /Airbus,Maxar Technologies,Sanborn,U.S.Geological Survey,Datos del mapa O 2022 SEP 12 2022 BY; RECEIVti-l-> SEP 1 2ttMSEVENTY-YEAR RECERTIFICATION?^ EVALUATION REPORT 370 Grand Concourse Miami Shores,Florida 33138-2747 Folio #11-3206-013-6040 Prepared by: TAJ LIMITED GROUP,INC 14216 SW 160'*'Avenue Miami,FL 33196 (305)793-7656 September 08,2022 REGULATORY AND ECONOMIC RESOURCES DEPARTMENT 11805 SW 26^^Street,Miami,Florida 33175 786-315-2000 Miamidade.gov/building MIAMI-DADE. COUNTY MINIMUM INSPECTION PROCEDURAL GUIDELINES FOR BUILDING STRUCTURAL RECERTIFICATION UCENSEE NAMEJahir Iqbal.P.E. jljLE;Structural Engineer FL P.E.#48061 CASE REFERENCE NUMBER: ADDRESS*^^^^SW 62nd Ave,Suite 4 Miami,FL 33143JURISDICTIONNAME: Miami Shores Village SIGNATURE: Tahir Iqbal P.e: (FL P.E.#48061)*Use separate sheets for additional responses by referencing the report number. 1.DESCRIPTION OF BUILDING a.Name on Title:MIAMI SHORES BAPTIST CHURCH b.Building Street Address:370 Grand Concours©,Miami Shor©s,FL 33138"2747 Bldg.#: c.Legal Description:Miami Shores Sec 1 AMD PB 10-70 all Blk B Lot Size Irregular Attached: d.Owner's Name:Miarni Shoros Baptist Church e.Owner's Mailing Address:370 Grand Concoufse,Miami Shores,FL 33138-2747 f.Folio Number of Property on which Building is Located:11 -3206-013-6040 g.Building Code Occupancy Classification:7144 Religious -Exempt!Religious h.Present use:Church Building I.General Description of building (overall description,structural systems,special features): Two stories CBS building,with concrete floor,slab on grade,2nd floor concrete slab supported by concrete beams,columns and CBS walls.Wood roof trusses with roof tiles in top. k.Is this a Threshold Building as per 553.71(12)F.S.(Yes/No):Noj.Number of Stories:2 I.Provide an aerial of the property identifying the building being certified on a separate sheet.Attached:^ m.Additional Comments:REc:F:TVKr> &EP 1 2 ●'Vli-VV BY: Tahir Iqbat P.E. (FL P.E.#48061) BORA Approved -Revised November 18,2021 Page 1 of 13 04/22R1.1 o^los[v)U. /.(/■ 4 ●●i:</I'I' ●(\(r ^f*.<)■;!■ c-rt.'1.■●-<«<*,'/f.^‘t●,v\vuni((,,<o"' 4 \N V 'llliw X \ > I4 V V/J I > /.HV. V >' ,\|V.',"'“● n.Additions to original structure; No Applicable S.F.o.Total Actual Building Area of ail floors:29,145 2.INSPEaiONS a.Date of Notice of Required Inspection: b.Date(s)of actual inspection:08-31 -2022 c.Name,license number,discipline of practice,and qualifications of licensee submitting report: Tahir Iqbal,P.E.(FL P.E.#48061) d.Description of laboratory or other formal testing,if required,rather than manual or visual procedures: Not Required at this time e.Are Any Structural Repairs Required?(YES/NO):No 1.If required,describe,and Indicate acceptance: f.Can the building continue to be occupied while recertificatio n and repairs are ongoing?(YES/NO):Yes 1.Explanation/Conditions: Acceptable Conditions g.Is it recommended that the building be vacated?(YES/NO):No h.Has the property record been researched for violations or unsafe cases?(YES/NO);No 1.Explanation/Comments;RKORIVF.r) F.P 1 %tij'i'l Tahir Iqbal P.E. BT: (FL P.E.#48061) BORA Approved -Revised November 18,2021 Page 2 of 13 04/22R1.1 N V /V >.T -*1. \/●,N ^.»■*s \ /● 3.SUPPORTING DATA Additional sheets of written dataa. X Photographs provided (where required plus each building elevation)b. Drawings or sketches (aerial,site,footprint,etc.)c. d.Test reports 4.FOUNDATION a.Describe the building foundation: Foundation Consist of isolated column footing under individual columns and continuous footing under the walls. b.Is wood in contact or near soil?(Yes/No):No c.Signs of differential settlement?(Yes/No):No d.Describe any cracks or separation in the walls,columns,or beams that signal differential settlement: PROVIDE PHOTO None e.Is water drained away from the foundation?(Yes/No):Yes f.Is there additional sub-soil investigation required?(Yes/No):No 1.Describe: 5.PRESENT CONDITION OF OVERALL STRUCTURE a.General alignment:(Note:good,fair,poor,explain If significant)PROVIDE PHOTO RECEIVED1.Bulging:None Noted SEP 12 20222.Settlement:None Noted 3.Deflections:None Noted BY: 4.Expansion:None Noted Tahir robal P.E. (FL P.E.#48061) 5.Contraction:None Noted BORA Approved -Revised November 18,2021 Page 3 of 13 04/22R1.1 Ay ^^ <.4 :Oii*:a ;t «●I I :'C●●V *<!●. -1 t,i.'i'*»'»; n ».ji ...r u i ‘.l i'j I }I)s.t ’K-4r IfcV ●*VIt.' r\.-i»J K J4 m-M M /4 I I I M "1 I '/ -s'%●n /Tn.N'''4./●N ^● V.■N \«r.♦V A VV\●>V'.CJI> /V PROVIDE PHOTOb.Portion showing distress:(Note,beams,columns,structural walls,floor,roofs,other) None Observed c.Surface conditions:Describe general conditions of finishes,cracking,spalling,peeling, signs of moisture penetration and stains. Exterior Stucco is in acceptable conditions.Maintenance Repairs were recently performed to structure PROVIDE PHOTO to keep building Aesthetically Pleasing. d.Cracks:Note location In significant members.Identify crack size as HAIRLINE if barely discernible; FINE if less than 1 mm in width;MEDIUM If between 1-and 2-mm width;WIDE if over 2 mm.PROVIDE PHOTO Repaired Hairline cracks in the stucco surface. e.General extent of deterioration:Cracking or spalling of concrete or masonry,oxidation of metals; rot or borer attack in wood. PROVIDE PHOTO None Noted PROVIDE PHOTOf.Previous patching or repairs (Provide description and identify location): None noted g.Nature of present loading:(Indicate residential,commercial,storage,other -estimate magnitude for each level) Commercial Office:50 PSF live load h.Signs of overloading?(Yes/No):No 1.Describe: Tahir Iqbal P.E. SEP 12 2022 BY: (FL P.E.#48061) BORA Approved -Revised November 18,2021 Page 4 of 13 04/22R1.1 i .li . ..►» \ yf?s''■s.N \i\ A'-'V* ^V*s^'^Ti' « XV.\%'N ✓N \■C't'. 6.MASONRY BEARING WALL:(Indicate good,fair,poor on appropriate lines)PROVIDE PHOTO a.Concrete masonry units;Acceptable Conditions b.Clay tile or terra cota units:Acceptable Conditions c.Reinforced concrete tie columns:Acceptable Conditions d.Reinforced concrete tie beams:Acceptable Conditions e.LintehAcceptable Conditions PROVIDE PHOTOf.Other type bond beams: g.Exterior masonry finishes (choose those that apply): 1.stucco:Acceptable Conditions 2.veneerrAcceptable Conditions 3.Paint only:Acceptable Conditions 4.Other (describe): PROVIDE PHOTOh.Interior masonry finishes (choose those that apply): 1.Vapor barrier:Not Visible 2.Furring and piasterrAcceptable Conditions 3.Paneiing;Acceptable Conditions 4.Paint only:Acceptable Conditions 5.other (describe): i.Cracks:PROVIDE PHOTO 1.Location (note beams,columns,other):None Noted 2.Description: j.Spalling PROVIDE PHOTO 1.Location (note beams,columns,other):None Noted 2.Description:Rkceived SfP 1 2 'lOll Tahir Iqbal P.E. (FL P.E,#48061) BORA Approved -Revised November 18,2021 Page 5 of 13 04/22R1.1 ●V-.^ -‘i A*●<"’. m¥> '.^-*.*'Vr-●●-4r . .'A' NN ●/V," V Am .» ●A V ●%.¥' \/* V PROVIDE PHOTOk.Rebar corrosion (indicate on lines 1-4): 1.None visible:1/ 2.Minor (patching will suffice):Not ObSOrVOd .Not observed3.Significant (but patching will suffice): No4.Significant (structural repairs required) I.Samples chipped out for examination in spalled areas (Yes/No):No 1.Yes -describe color,texture,aggregate,general quality: 7.FLOOR AND ROOF SYSTEM a.Roof (Must provide) PROVIDE PHOTO1.Describe (roof shape,type roof covering,type roof deck,framing system,condition): Wood roof trusses with terracotta tiles in top 2.Note water tanks,cooling towers,air conditioning equipment,signs,other heavy equipment and condition of supports: Acceptable Conditions PROVIDE PHOTO 3.Describe roof drainage system,main and overflow,and indicate condition:PROVIDE PHOTO Roof drawings towards building sides and some locations with gutters and downspouts in Acceptable Conditions. 4.Describe parapet build and current conditions:PROVIDE PHOTOHECEIVED SEP 1 -1 2022 Not applicable BY! 5.Describe mansard build and current conditions:PROVIDE PHOTO Not Applicable Tahir Iqbal P.E. (FL P.E.#48061)BORA Approved -Revised November 18,2021 Page 6 of 13 04/22R1.1 ✓V- V li ♦\n\✓\V .V. S;.r-r. VtV●fi Isf * T 4 VI4 'Tblv CitDIOi ’'■■rjf.1 ■IPn:,'c.1i f ●*:.K , r r %ic●●. r <\ 4 ■r *“t'* t 'i.V r /■■<«. P <»j»A ■T X -/●%.*tL ‘i. %<1^. n* « ♦ ●‘I ■-^my A-'f i 6.Describe roofing membrane/covering and current conditions:PROVIDE PHOTO Roof tiles in acceptable conditions and small area with flat roof with granulate cap sheet in top 7.Describe any roof framing member with obvious overloading,overstress,deterioration or excessive deflection: PROVIDE PHOTO None Observed 8.Note any expansion joints and condition:PROVIDE PHOTO Not Applicable b.Floor system(s): 1.Describe the floor system at each level,framing,material,typical spans and indicate condition: PROVIDE PHOTO Slab on grade at 1st floor and elevated reinforced concrete slab at 2nd floor. 2.Balconies:Indicate location,framing system,material,and condition:PROVIDE PHOTO Not Applicable 3.Stairs and escalators:indicate location,framing system,material,and condition:PROVIDE PHOTO Concrete stairs in acceptable conditions 4.Ramps:indicate location,framing type,material,and condition:PROVIDE PHOTO Concrete ramps in acceptable conditions received SEP 1 2 7M 5.Guardrails:describe type,material,and condition:PROVIDE PHOTO Metal guard rails in acceptable conditions. byf c.Inspection -note exposed areas available for inspection,and where it was found necessary to^open ceilings,etc.for inspection of typical framing members..r some drop ceiling tiles were removed to observe roof conditions. O^/70^ Tahir Iqbal P.E. (FL P.E.#48061)BORA Approved -Revised November 18,2021 Page 7 of 13 04/22R1.1 ’"’●svjAorrtvj-i -u0‘. \VH*<SiV-KJ.^riOJ f»a^itt - I «V >utixi ●vt^:I ..w.TWkr.i*●■i»<.l?>CKn YOb yT"w«©5.*v I●Of..VC'wr’;'**;^I J*●y Z?4 3r‘.':>1: A cn.:2/fUo4 KJi?)^CCiX9 ^Af,1 I rs^li »●- II 1 f;':.f i:<» >'>:<-jifti*'i^y ".v;:>●:’4;(?●*ivi'i-I I-.- ;●!iU;' ■»ocH 6o«i;)ro Or''?;)0 6 lOc"'tii*'.H’3 ●J -.'^r.'j j9:-■‘1 j > t 4(t ,.;.-s Vr-.Irni. X 1elO'-.cjoA wv'ijt I » ► 1 L rso:£l*3<*bri*-mi;‘I t●o“j ir..i,?lUH!..V V >V-*' t.●iCb-v^-*bifjr^.joO3..^ c '.rtoi’syi''j,1 .■>.'f.'j,»' ●^];«oii.£n-oflkifch)ou:>s iv aqiniii ;f^.>v. ■~iM■<>●>(> ●>0 r4fi5^.CL’l'-ri.●t'i ti ni cliil’i o^uo ifiieM:ao':it>;.'-.o 1S j .UuUT.-.jji ^«?V-^T,3t V18*<’?m!QvW *:i '^'■r.AI,’i < r'7 i.V,-●●●y. A'●V ■5 I A. ●' «iy'w .JN> ●w: I 'f 8.STEEL FRAMING SYSTEM PROVIDE PHOTOa.Description of system at each level: Not Applicable PROVIDE PHOTOb.Steel members;describe condition of paint and degree of corrosion: Not Applicable PROVIDE PHOTOc.Steel connections;describe type and condition: Not Applicable d.Concrete or other fireproofing:note any cracking or spalling of encased member and note where any covering was removed for inspection: PROVIDE PHOTO Not Applicable e.Identify any steel framing member with obvious overloading,overstress,deterioration,or excessive deflection (provide location): PROVIDE PHOTO Not Applicable PROVIDE PHOTOf.Elevator sheave beams and connections,and machine floor beams;note condition: Not Applicable 9.CONCRETE FRAMING SYSTEM PROVIDE PHOTOa.Full description of concrete structural framing system: Two Story CBS building with a concrete slab system supported by concrete beams and column system SEP i 2 ■ b.Cracking Bi: 1.Significant or Not significant:Not ObSOrved 2.Location and description of members affected and type cracking: Tahir Iqbal P.E. (FL P.E.#48061)BORA Approved -Revised November 18,2021 Page 8 of 13 04/22R1.1 * \/*X %-s \N A AA' ●/ c,\\'">.i (●«/<'t A \iN c.General condition Acceptable conditions. d.Rebar corrosion -check appropriate line 1.None visible:^ PROVIDE PHOTO2.Location and description of members affected and type cracking: PROVIDE PHOTO3.Significant but patching will suffice: Not observed PROVIDE PHOTO4.Significant:structural repairs required (describe): No e.Samples chipped out in spall areas: 1.No:✓PROVIDE PHOTO 2.Yes,describe color,texture,aggregate,general quality: f.Identify any concrete framing member with obvious overloading,overstress,deterioration, or excessive deflection:PROVIDE PHOTO None Observed BY; 10.WINDOWS,STOREFRONTS,CURTAINWALLS AND EXTERIOR DOORS a.Windows/Storefronts/Curtainwalls PROVIDE PHOTO 1.Type (Wood,steel,aluminum,vinyl,jalousie,single hung,double hung,casement,awning, pivoted,fixed,other): Old Aluminum glass windows 2.Anchorage:type and condition of fasteners and latches: Old -Acceptable conditions bai P.E. 3? Tahir Iq (FL P.E.#48061)BORA Approved -Revised November 18,2021 Page 9 of 13 04/22R1.1 4 ( i ■w «v < f'VVs,>T v ^ifj.y*>●^ n/ »\■/ .N. A/\-: A'A /●A V.N V >●X 'Vr* ;a* RECEIVED! 3.Sealant:type and condition of perimeter sealant and at mullions:SLP I 2 /iT-.7 Acceptable Conditions BY: 4.Interiors seals:type and condition at operable vents: Acceptable conditions 5.General condition: Acceptable Conditions.Building was recently re-painted. 6.Describe any repairs needed: None at this time b.Structural Glazing on the exterior envelope of Threshold Buildings {Yes/No}:No 1.Previous Inspection Date: 2.Description of Curtain Wall Structural Glazing and adhesive sealant: Not Applicable 3.Describe Condition of System: Not Applicable c.Exterior Doors PROVIDE PHOTO 1.Type (Wood,Steel,Aluminum,Sliding Glass Door,other): Steel and Aluminum doors in Acceptable conditions 2.Anchorage:type and condition of fasteners and latches: Old -Acceptable conditions 3.Sealant:type and condition of sealant: Tahir tqbal-P.E. Acceptable conditions (Ft P.E.#48061) BORA Approved -Revised November 18,2021 Page 10 of 13 04/22R1.1 ●K N y /●v' '^●Z* „v V.>.'● V-..,●>^ /> Ah ^ylJ«S-.r 4.General condition; Acceptable Conditions 5.Describe any repairs needed: BYTNoneatthistime. 11.WOOD FRAMING PROVIDE PHOTOa.Fully describe wood framing system: Pre-fabricated wood trusses in acceptable conditions b.Indicate the condition of the following:PROVIDE PHOTO 1.Walls: Not Applicable 2.Floors: Not Applicable 3.Roof member,roof trusses: Acceptable conditions c.Note metal connectors (i.e.,angles,plates,bolts,split pintles,other,and note condition):PROVIDE PHOTO Not visible d.Joints:note If well fitted and still closed:PROVIDE PHOTO Tahir Iqbal P.E. (FL P.E.#48061) BORA Approved -Revised November 18,2021 Page 11 of 13 04/22R1.1 1 4 < ) y. J. >, ><Xn/\s%\ V - ●/ \* w>. *● -N/●-\A ^V*>NV/’'A\1 /● receivei^PROVIDE PHOTOe.Drainage:note accumulations of moisture No water damage was observed SFP12 im PROVIDE PHOTOf.Ventilation:note any concealed spaces not ventilated: Metal screens are at all perimeter of the building a exterior soffit PROVIDE PHOTOg.Note any concealed spaces opened for inspection: None h.Identify any wood framing member with obvious overloading,overstress,deterioration, or excessing deflection): PROVIDE PHOTO None Observed PROVIDE PHOTO12.BUILDING FACADE INSPECTION (Threshold Buildings) a.Identify and describe the exterior wails and appurtenances on all sides of the building.(Cladding type,corbels,precast appliques,etc.) Not Applicable. b.Identify the attachment type of each appurtenance type (mechanically attached or adhered): Not Applicable c.Indicate the condition of each appurtenance (distress,settlement,splitting,bulging,cracking,loosening of metal anchors and supports,water entry,movement of lintel or shelf angles,or other defects): Not Applicable T7.J Tahir IqW P.E. (FL P.E.#48G61) BORA Approved -Revised November 18,2021 Page 12 of 13 04/22R1.1 ●V/S V✓.-.●VV ✓.W 'w' V y /y \N.✓ 4 /4 ,} y f 4. I \●% 4 4 PROVIDE PHOTO13.SPECIAL OR UNUSUAL FEATURES IN THE BUILDING a.Identify and describe any special or unusual feature (i.e.cable suspended structures,tensile fabric roof,large sculptures,chimneys,porte-cochere,retaining walls,seawalls,etc.) Not Applicable SEP 1 2 2022 BY: b.Indicate condition of the special feature,Its supports,and connections: Not Applicable ■t tolA. I'ahir Iqfel P.E. -(FLP.E.#48061) Reset Form BORA Approved -Revised November 18,2021 04/22R1.1Page13of13 Jf I.-S3 z' X s ,N ●X .N ‘#.. CC-C3-U-7?>C Auu 0 8 ENI'D July 10,2024 BY: Chief Building Inspector Miami Shores Village Building Department 10050NE2 Ave Miami Shores,FL 33138. Miami Shores Baptist Church Stucco Repairs and Minors Structural Repairs For 40/50 Re-Certification Report Permit No.CC-03-24-736 370 Grand Concourse Miami Shores,FL 33138 Job.No.2024-117 RE: Dear Sir; We have performed and approved the required inspections of the Stucco Repairs, Minors Structural Repairs,and Paint of the above-mentioned project.To the best of my knowledge,belief,and professional judgment,the above-described construction all load bearing components complies with the permitted documents submitted to the enforcement agency.I also attest that to the best of my knowledge,belief,and professional judgment,the approved permit plans represent the as-built condition of the structural components of said structure. This document is being prepared in accordance with section 110.8.4.1 of the Florida Building Code,2023 8^^Edition,and is being submitted to the Miami Dade Building & Zoning in conjunction with the application for a Certificate of Occupancy for the above referenced structure. Should you have any questions or need additional information,please do not hesitate to contact me. Sincerely; Tahir Iqbal,P.E. TAHIR 06AL C SICMfcD «SLaLXC IWALPbOMm CkA7Tl>'TMCAt(P C4grT41 mxnr seocvKorn TATSX CSKCSTDIB’ SO)●AMA DMaTVM MVfT CM AHT lUi^rVOW CI3WTahirIqbal,P.E. MS FRSEP.E.No.48061 QOr\fs r TAJNroo TAHIR IQBAL P.E.M.S FRSE P.E No.48061H}o O TAHIR IQOALU0NK»A RALC&9T CM r««Tu^CQO \s/usMo (»torTA iscoMAnifti nrtmo cc*iu OTTMC eOaVDm AU MCT CM lOCUX* SKM<A nAUD A>«me Huunru lAWT tl vtiumc Oi<AH r n4cnto«*c cc*m SPECIAL INSPECTOR LOG Project No.2024-117 GORO Construction Inc. CC-03-24-736 370 Grand Concourse,Miami Shores,FL 33138 Contractor: Building Permit No.: Building Address: Owner:Miami Shores Baptist Church Project:Miami Shoi*es Baptist Church Location:370 Grand Concourse,Miami Shores,FL 33138 CommentsAreaofInspectionStatusTypeofInspectionNameofInspector West elevation at locations denoted in the permit drawings with No.2 &5.Details A/SR-4, C/SR-4 &F/SR-4 Area ready for Stucco ApplicationCompletedStnicturalRepairsRobeitoPerez West elevation at locations denoted in the permit drawings with No.1.Detail E/SR-4 In ProgressStuccoRepairsLuisJimenez West elevation at locations denoted in the permit drawings with No.1.Detail E/SR-4 Ready For Paint ApplicationCompletedStuccoRepairsLuisJimenez East elevation at locations denoted in the permit drawings with No.2.Detail E/SR-4 Ready For Paint ApplicationCompletedStuccoRepairsRobertoPerez North elevation at locations denoted in the permit drawings with No.2 Ready For Paint ApplicationCompletedStructuralRepairsRobertoPerez West Elevation Planter wall. Detail G/SR-4 CompletedStructuralRepail'sLuisJimenez North,West,East and South Elevation Paint Application In ProgressStructuralRepairs/PaintLuisJimenez 100%CompletedAllelevations100%work Completed 100%CompletedStructuralRepail's/PaintLuisJimenez 370 Grand ConcoursePageProjectNo.CC-03-24-736 Miami Shores Village Building Department received 10050 N.E.2nd Avenue,Miami Shores,Florida 33138 Tel:(305}795-2204 Fax:(305)756-8972 INSPECTION LINE PHONE NUMBER:(305)762-4949 BY:C FBC 20 Cc-cn-2i-miBUILDING PERMIT APPLICATION Master Permit No. Sub Permit No. RENEWALEXTENSIONREVISION^BUILDING ELECTRIC ROOFING CANCELLATION □SHOP DRAWINGS CHANGE OF CONTRACTOR PLUMBING □MECHANICAL PUBLIC WORKS .370 Grand ConcourseJOBADDRESS: Zip:Miami DadeMiamiShoresCounty:City: .11-3206-013-6040 Is the Building Historically Designated:Yes Flood Zone: NOFolio/Parcel#: FFE:BFE:Construction Type: (Fee Simple Titleholderl:Shores Baptist Church,Inc. .370 Grand Concourse Load:Occupancy Type: .305-758-0559Phone#:OWNER:Name Address:---- f-Hy.Miami Shores .33138.FL Zip:state: Phone#:_ j iKJFb oiz^L>rniarvi ( Tenant/Lessee Name: msbcreceptionist@gmail.comEmail: in.N/A Phone#:CONTRACTOR:Company Name:1 Address: Zip:State:City: Phone#:Qualifier Name: State Certification or Registration #: DESIGNER:Architect/Engineer: Address; Value of Work for this Permit:$ Type of Work:EH Addition EH Alteration Q Description of Work:70 Year Building Recertification Certificate of Competency #:_ Phone#: Zip:City: Square/Linear Footage of Work: Repair/Replace State: EH DemolitionNew Specify color of color thru tile: co/cc$_ Notary $. Double Fee $_ Bond $ CCF $_ DBPR$ Submittal Fee $ Scanning Fee $ Technology Fee $ Structural Reviews $ Permit Fee $ Radon Fee $ Training/Education Fee$ TOTAL FEE NOW DUE $ (Revised02/24/2014) Bonding Company's Name {if applicable) Bonding Company's Address City State Zip Mortgage Lender's Name (if applicable) Mortgage Lender's Address City State Zip. Application is hereby made to obtain a permit to do the work and Installations as indicated.I certify that no work or installation has commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction.I understand that a separate permit must be secured for ELECTRIC,PLUMBING,SIGNS,POOLS, FURNACES,BOILERS,HEATERS,TANKS,AIR CONDITIONERS,ETC OWNER'S AFFIDAVIT:I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. u WARNING TO OWNER:YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY.IF YOU INTEND TO OBTAIN FINANCING,CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.H Notice to Applicant:As a condition to the issuance of a building permit with an estimated value exceeding $2500,the applicant must promise in good faith that a copy of the notice of commencement and construction lien low brochure will be delivered to the person whose property is subject to attachment.Also,a certified copy of the recorded notice of commencement must be posted at the job site for the first inspection which occurs seven (7)days after the building permit is issued.In the absence of such posted notice,the inspection will not be approved and a reinspection fee will be charged. Signature Signature. OWNER or AGENT CONTRACTOR The foregoing instrument was acknowledged before me this L?c hd>L>er The foregoing instrument was acknowledged before me this day of/9 ■20 e/day of /pD j by ./by.,20 .,who is personally known to .,who is personally known to ^me or who has produced identification and who did take an oath. me or who has produced identification and who did take an oath. as as NOTARY PUBLIC:NOTARY PUBLIC: UnoOij(X- Sign^: Print: Seal: Sign:.yi lo\C~ Print: SUMAYAVDAVIW Commission #06334772 Expires June 3.2023 Bonded TMi Bwigst Hottry Sinlcw Seal: m *♦♦♦♦♦***♦***#***♦*****♦*♦#***#*****#***********#**♦***♦♦***»#***#*******#***************»*##*#***#*#*####** APPROVED BY Plans Examiner Zoning structural Review Clerk (Revised02/24/2014) Miami Shores Village Building Department 10050 N.E.2nd Avenue Miami Shores,Florida 33138 Tel:(305)795.2204 Notice of Required 70 year B»iMdi TMU.S.Postal Service CERTIFIED MAIL®RECEIPTJuly19,2021Date:p-Domestic Mail Only For delivery information,visit our website at mvw.usps,com_^ ja fU OFFICIAL USETo:MIAMI SHORES BAPTIST CHURCH 370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 zr Certifled Mail Fee 3-Extra Services S Fees (chec*box,mJdUaasvxiroprlan}P Ratum Racnipl (hardc^ □H«um Receipt (electronic) □Certltled Mall Restricted Delivery S □Adult Signature Required QAduftSIgnaturs Restricted OeBvsty $ $□Postmark Here $□ CD $O □Postageui Re:370 GRAND CONCOURSE MIAMI SHORES,FL 33138-2747 j-Total Postage and Feesru SVtnres afxpViSV Omrh -^●^8 G}raM...Ca!rcxMirse <oVion»^,ri_ CD ru □ p- See Reverse for InstructionsPSForm3800,April 2015 PSN 7530-02-000-9047 Dear Owner: According to the information provided by the Miami Dade County Property Appraisers office the above referenced property has a building or structure that is forty (40)years old or older.In accordance with Miami-Dade County Chapter 8 Section 8-11,the subject property must be inspected and re-certified by a Florida license architect or engineer. Sec.8-11.-Existing buildings, a)The requirements contained in the Florida Building Code,covering the maintenance of buildings,shall apply to all buildings and/or structures now existing or hereafter erected.All buildings and/or structures and all parts thereof shall be maintained in a safe condition,and a!!devices or safeguards that are required by the Florida Building Code shall be maintained in good working order. Electrical wiring,apparatus and equipment,and installations for light heat or power and low voltage systems as are required and/or regulated by the Building Code,now existing or hereinafter installed,shall be maintained in a safe condition and all devices and safeguards maintained in good working order. A building re-certification report signed and sealed by the Florida license engineer and or Architect along with the required fees shall be submitted to this office within thirty (90)days of receiving this notice. If you would like a copy of Minimum Inspection Procedural Guidelines for Structural and Electrical Recertification,or if you have any questions,please call my office at 305-795-2204. Sincerely, / ismae!Naranjo,BO Building Director Email:bo@msvfl.gov Sent via DSPS regular and certified mail #7020-2450-0000-4634-2 667 SECTION ON DEUVEBVcompi-ETE this sender:COMPLETE TH/SSe^Q Agent '□AridresseeJteofDelivery ' A.Signature X ■Complete Items ^a^^ed.item 4 if Xress on the reverse■Print your name and adore 1.Article Addressed to: C.Da' Ql ABVA^SlL D Yes D Nodifferentfromitem1? address below:D.Is delivery addressIfYES,enter delivery fvA\avV»6nonssOnurCVA (Ji,aw»eJoD'rC-S,V-l-"SSSMa.. gSri,DCdleclonOe!^ 2bb7 □Yes 21450 ODDD70HD2.Article Number (Transfer from - .PS Form service label) 3811.July 2013 Domestic Return Receipt