Tropical Chevrolet, 01-02-23 UES No 198687 SPECIAL insp rept #060 (Quik Lube & Lobby roof framing) - GDZProject No.: 2110.2100049 Report No.: 198687 Date: January 2, 2024 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-060 CN: GDZ Page 1 of 6 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute Client: Lebolo Construction Management, Inc. 2100 Corporate Drive Boynton Beach, FL 33426 Project: Tropical Chevrolet Renovation/Expansion 8880 Biscayne Blvd. Miami Shores, FL 33138 Agent: Gaetano Di Zio, E.I. Jose Luis Linares Date of Services: 01/02/2024 Village of Miami Shores Building Permit No: CC-12-20-2951 (issued date 11/07/22, expires 05/08/23) Scope of Field Services: Professional observation of completed structural elements (Special Inspector). Reference Documents: • JSG structural drawings sheets S1.0 thru S4.2 (15 pages), Bulleting 7 dated 07/21/2022, signed/sealed by Mark Johnson FL-PE#51983, reviewed/approved for structural compliance by the Village of Miami Shores Bldg. Dept. on 08/22, (permit set review by the Miami-Dade County Department of Regulatory and Economic Resources on 05/16/2022). • SUNCOR, Inc. structural steel erection/fabrication shop drawings sheets AB1 thru TP101 (total of 219 pages) dated 04/13/2022 (Rev. A – Issued for Approval) Submittal #051200-5.0 (Structural Steel Shop Drawings), reviewed for compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 05/03/2022. • Canam Steel Corporation (CSC) steel metal deck shop drawings sheets DE1.1 thru DE2.1 (total of 3 pages) dated 04/08/2022 (Issued for Approval) Submittal #051200-6.0 (Deck Shop Drawings), reviewed for compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 04/15/2022. Record of Field Observations: 1. Visual verification of the structural steel connections at the following locations indicated below: a) ½” Ø x 1½” shear studs welded connections to the proposed new C10x25 steel channels approx. between grids “C.5” thru “D.5” and lines “5.5” thru “6.5 for the precast concrete double “T’s” repair at the existing service department, as per Conemco Engineering, Inc. precast concrete double Tee’s structural repair drawings, as we addressed on UES Structural Observation Reports No. 38 (No.: 10040) dated 07/07/2023 and No. 41 (No.: 14712) dated 09/06/2023, re-inspection inconclusive (09/12/23) – pending current welder qualification certification (continuity paperwork- period of effectiveness): ➢ Welding slag was not completely removed from locations that require Visual Testing (VT). ➢ Incomplete or undersize fillet welds. ➢ Missing three (3) shear studs at locations marked in the field. ➢ A couple of shear studs were found to be spaced more than 8” o.c . b) New C10x25 steel channels bolted/anchored connections to the existing roof precast concrete double Tee’s/existing concrete beam approx. between grids “C.5” thru “D.5” and lines “5.5” thru “6.5 for the precast concrete double “T’s” repair at the existing service department, as per Conemco Engineering, Inc. precast co ncrete double Tee’s structural repair drawings, as we addressed on UES Structural Observation Report No. 044 (No.: 17436) dated 09/28/2023, inconclusive on 10/25/23: ➢ Pending final compliance verification for item 1a above. ➢ Missing washers/nut at random locations. ➢ Anchor bolt threads were found not protruding (negative projection) beyond the outside surface of the nut (negative stick‐out) at several locations as per RCSC (Research Council for Structural Connections) Specification for Structural Joints Using ASTM A325 or A490 Bolts. ➢ One (1) loose-fitting thru bolt. ➢ One (1) screw anchor was found not to be ¾”. c) Additional support steel angle clips anchored/welded connections (torque verified at 100 ft−lb as per Simpson Strong−Bolt 2 Wedge Anchor required installation torque schedule) to continuous perimeter roof deck bearing angle L4”x4”x1/4”CIP and to CIP concrete beam along grid “E.4” between lines “11” thru “13” at the Quik Lube, as per DRAFT Project No.: 2110.2100049 Report No.: 198687 Date: January 2, 2024 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-060 CN: GDZ Page 2 of 6 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute S1.0, S1.1/details 2 & 3, S2.2, S3.2, S4.1/details 1 & 4, E1000, E1001 and attached letter submitted by the SEoR, completed. d) Continuous perimeter roof deck bearing angle L4”x4”x1/4” anchored connections (torque verified at 100 ft−lb as per Simpson Strong−Bolt 2 Wedge Anchor required installation torque schedule) to CIP concrete beam along grids “G” and “H” between lines “8” thru “9” at the Lobby, as per S1.0, S1.1/details 2 & 3, S2.2, 1/S3.3, 10/S4.1, 2/S4.2, E1000, E1001 and attached letter submitted by the SEoR, completed. e) W12x14 roof steel beam welded/bolted connections to CIP concrete tie beam along grid “G.5” between lines “8” thru “8.6” at the Lobby, as per S1.0, S2.2, 2/S3.2, 10/S4.1, 2/S4.3, E1000 and E1002, completed. The structural steel connections at the locations mentioned above were found to be in accordance with the reference documents, except for items 1a & 1b inconclusive. The welder qualification certificate for item “a” was provided during our site visit on 07/27/2023, however current continuity paperwork pending for review (Period of Effectiveness). The welders that performed the work were not available onsite in order to verify their welder qualifications. As per The Structural Welding Code: 6.2.3 Period of Effectiveness 6.2.3.1 Welders and Welding Operators. The welder’s or welding operator’s qualification as specified in this code shall be considered as remaining in effect indefinitely unless: (1) the welder is not engaged in a given process of welding for which the welder or welding operator is qualified for a period exceeding six months, or (2) there is some specific reason to question a welder’s or welding operator’s ability (see 6.25.1). Mr. Jim Jenco, Senior Superintendent with Lebolo Construction, was notified of the aforementioned visual verification results. Please see adjacent report pages for photographs, clarification submitted by the SEoR via e-mail and sheet S2.2. DRAFT Project No.: 2110.2100049 Report No.: 198687 Date: January 2, 2024 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-060 CN: GDZ Page 3 of 6 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute On 09/12/23 DRAFT Project No.: 2110.2100049 Report No.: 198687 Date: January 2, 2024 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-060 CN: GDZ Page 4 of 6 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute DRAFT Project No.: 2110.2100049 Report No.: 198687 Date: January 2, 2024 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-060 CN: GDZ Page 5 of 6 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute DRAFT 1 Gaetano Di Zio From:Jim Jenco <jjenco@Lebolo.com> Sent:Tuesday, January 2, 2024 9:43 AM To:Gaetano Di Zio Subject:FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) This Message Is From an External Sender This message came from outside your organization. For your use and records, please find the below e-mail from the EOR with answers for the length of the clips and the anchor bolt size w embedment depth. Thanks, Jim Jenco Superintendent Lebolo Construction Management, Inc. jjenco@lebolo.com m. (561) 667-9726 www.lebolo.com o. (561) 742-7644 SAFETY | INTEGRITY | ACCOUNTABILITY "This e-mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510-2521, and may be legally privileged. The information contained in this e-mail message is confidential information intended only for the use of the individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this communication in error, please immediately notify sender by telephone at 561-742-7644, and delete the original message. Thank you." From: Mark Johnson <mark@johnsonstructural.com> Sent: Friday, December 29, 2023 12:21 PM To: Jim Jenco <jjenco@Lebolo.com>; Brian Smedley <bsmedley@jhn.com> Cc: Pedro R. Salom <psalom@johnsonstructural.com>; Maria Manjon <memanjon@Lebolo.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Sorry about that. I was not clear on what you were looking for. The 12” long piece of angle with the two expansion bolts is acceptable. Mark Johnson, PE USAR FL-TF2 Structures Specialist FL Board Recognized Structural Engineer Johnson Structural Group, Inc. (561) 982-8999 x11 From: Jim Jenco <jjenco@Lebolo.com> Sent: Thursday, December 28, 2023 12:31 PM To: Brian Smedley <bsmedley@jhn.com> DRAFT 2 Cc: Mark Johnson <mark@johnsonstructural.com>; Pedro R. Salom <psalom@johnsonstructural.com>; Maria Manjon <memanjon@Lebolo.com> Subject: FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Brian, Please note the below reply did not answer “length of 5” x 5” support clips”. Attached is what was interpreted and installed the 1 st round of this RFI. This condition also applies to Lobby 301 TB301 on west elevation. Although the work performed looks to be adequate, the Special Inspector need to see the length of the clips from the EOR. Thanks, Jim Jenco Superintendent Lebolo Construction Management, Inc. jjenco@lebolo.com m. (561) 667-9726 www.lebolo.com o. (561) 742-7644 SAFETY | INTEGRITY | ACCOUNTABILITY "This e-mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510-2521, and may be legally privileged. The information contained in this e-mail message is confidential information intended only for the use of the individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this communication in error, please immediately notify sender by telephone at 561-742-7644, and delete the original message. Thank you." From: Dave Pond <Dave.P@suncor.net> Sent: Thursday, December 28, 2023 11:02 AM To: Jim Jenco <jjenco@Lebolo.com> Cc: Victor Castro <Victor.C@suncor.net> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Jim, Attached is the layout, shop, and wedge anchor product data. The anchors are 8” apart with the angle clips being 1’-0 long. Thanks, David Pond | Project Engineer office 608-846-9300 | Mobile 605-201-6757 www.suncor.net & www.nationalmetals.com From: Jim Jenco <jjenco@Lebolo.com> Sent: Thursday, December 28, 2023 9:26 AM To: Dave Pond <Dave.P@suncor.net> Cc: Victor Castro <Victor.C@suncor.net> Subject: FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) DRAFT 3 Dave, I will call you to further discuss if what your erector installs complies with this. Thanks, Jim Jenco Superintendent Lebolo Construction Management, Inc. jjenco@lebolo.com m. (561) 667-9726 www.lebolo.com o. (561) 742-7644 SAFETY | INTEGRITY | ACCOUNTABILITY "This e-mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510-2521, and may be legally privileged. The information contained in this e-mail message is confidential information intended only for the use of the individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this communication in error, please immediately notify sender by telephone at 561-742-7644, and delete the original message. Thank you." From: Brian Smedley <bsmedley@jhn.com> Sent: Wednesday, December 27, 2023 12:20 PM To: Jim Jenco <jjenco@Lebolo.com> Subject: FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Jim: Please see below. BRIAN SMEDLEY, AIA NCARB |Director - Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743 NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334 Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804 From: Mark Johnson <mark@johnsonstructural.com> Sent: Wednesday, December 27, 2023 12:08 PM To: Brian Smedley <bsmedley@jhn.com>; Pedro R. Salom <psalom@johnsonstructural.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Brian, ¾” Diameter Expansion bolt with 4” embedment. Provide minimum of 2 between steel beams. Angle occurs throughout the length of the CB103. Mark Johnson, PE USAR FL-TF2 Structures Specialist FL Board Recognized Structural Engineer Johnson Structural Group, Inc. (561) 982-8999 x11 DRAFT 4 From: Brian Smedley <bsmedley@jhn.com> Sent: Wednesday, December 27, 2023 11:10 AM To: Mark Johnson <mark@johnsonstructural.com>; Pedro R. Salom <psalom@johnsonstructural.com> Subject: FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Mark/Pedro: Can you please see the below request for Tropical? BRIAN SMEDLEY, AIA NCARB |Director - Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743 NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334 Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804 From: Jim Jenco <jjenco@Lebolo.com> Sent: Wednesday, December 27, 2023 11:06 AM To: Brian Smedley <bsmedley@jhn.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Brian, Please be informed the Special Inspector needs the following information to complete the inspection:  Size of the Anchor  Anchor Embedment  Length of 5” X 5” support clips Kindly forward this information on or before tomorrow Thursday 12/28 @ 10:00 AM. Thanks, Jim Jenco Superintendent Lebolo Construction Management, Inc. jjenco@lebolo.com m. (561) 667-9726 www.lebolo.com o. (561) 742-7644 SAFETY | INTEGRITY | ACCOUNTABILITY "This e-mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510-2521, and may be legally privileged. The information contained in this e-mail message is confidential information intended only for the use of the individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this communication in error, please immediately notify sender by telephone at 561-742-7644, and delete the original message. Thank you." From: Brian Smedley <bsmedley@jhn.com> Sent: Thursday, October 5, 2023 3:11 PM To: Jim Jenco <jjenco@Lebolo.com> Subject: FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Jim: Please see email thread below. If you need further clarification please let me know. DRAFT 5 BRIAN SMEDLEY, AIA NCARB |Director - Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743 NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334 Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804 From: Mark Johnson <mark@johnsonstructural.com> Sent: Thursday, October 5, 2023 3:03 PM To: Brian Smedley <bsmedley@jhn.com>; Pedro R. Salom <psalom@johnsonstructural.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Tell them to use the additional angle supports. I think they would want to use the 5x5 angle to make the weld easier. Provide 2 intermediate supports between beams. Mark Johnson, PE USAR FL-TF2 Structures Specialist FL Board Recognized Structural Engineer Johnson Structural Group, Inc. (561) 982-8999 x11 From: Brian Smedley <bsmedley@jhn.com> Sent: Thursday, October 5, 2023 1:58 PM To: Mark Johnson <mark@johnsonstructural.com>; Pedro R. Salom <psalom@johnsonstructural.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Please let me know which direction to provide the GC. BRIAN SMEDLEY, AIA NCARB |Director - Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743 NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334 Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804 From: Mark Johnson <mark@johnsonstructural.com> Sent: Thursday, October 5, 2023 1:27 PM To: Pedro R. Salom <psalom@johnsonstructural.com>; Brian Smedley <bsmedley@jhn.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Well the tie beam will take the chord forces. The deck angle here is really more used to finish the metal deck. With the beams spaced at 10 feet on center, the deck angle will need an additional support or 2 between beams. They can leave the angle toe-up and weld to the top of the beams. For an intermediate support, they can take a piece of L3x3x1/4”x4” long and weld it to the underside of the deck angle and bolt it into the face of the beam. They could also use a 5x5 angle and then the weld would be a downward weld rather than an overhead weld. DRAFT 6 Mark Johnson, PE USAR FL-TF2 Structures Specialist FL Board Recognized Structural Engineer Johnson Structural Group, Inc. (561) 982-8999 x11 From: Pedro R. Salom <psalom@johnsonstructural.com> Sent: Thursday, October 5, 2023 12:49 PM To: Brian Smedley <bsmedley@jhn.com> Cc: Mark Johnson <mark@johnsonstructural.com> Subject: RE: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Hey Brian, see below in blue and green for possible solution.. They’ll have to notch out the vertical leg of the angle at the knife plate (sticks out from embedded plate on CB103) that connects to the steel beams web.. MJ, let us know your thoughts.. other solutions. Thanks. DRAFT 7 Pedro Salom, P.E. JohnsonStructuralGroup,Inc. New Mailing Address: 160 West Camino Real Suite 1000 Boca Raton, FL 33432 Phone (561) 982-8999 Ext. 13 Fax: (561) 982-8899 www.johnsonstructural.com From: Brian Smedley <bsmedley@jhn.com> Sent: Wednesday, October 4, 2023 4:36 PM To: Pedro R. Salom <psalom@johnsonstructural.com> Subject: FW: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Pedro: DRAFT 8 Can you please review and reply to the below RFI for Tropical? BRIAN SMEDLEY, AIA NCARB |Director - Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743 NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334 Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804 From: Jim Jenco (Lebolo Construction Management, Inc.) <Lebolo_Construction_Management_Inc_notifications@procoretech.com> Sent: Wednesday, October 4, 2023 4:28 PM To: Brian Smedley <bsmedley@jhn.com> Subject: Tropical Chevrolet Renovation: New RFI 100 (QUICK LUBE 130 DECK ANGLE @ EAST ELEV.) Tropical Chevrolet Renovation More details: View online Open In App | View PDF To respond to this RFI simply reply to this email. Need help? Watch a short training video. New RFI #100 has been assigned to Smedley, Brian (Nudell Architects) by Jim Jenco (Lebolo Construction Management, Inc.) on 10/04/23. RFI Details This RFI is due on Friday, October 6, 2023. QUESTION 1 Asked By: Jim Jenco (Lebolo Construction Management, Inc.) Date: Wed Oct 4, 2023 at 04:27 pm EDT Location: Services Building Question: Please indicate an alternate deck angle attachment for Quick Lube 130 East Elevation. CB103 was casted at correct elevation +18'-5", Steel Beam was connected to Embed at correct elevation +18'-2.5". Not enough concrete beam remaining at enter of L4"x 4"x 1/4" to follow 3/4" Exp. Bolt connection detail. Attachments: 253 - S4.1 Structural Sections.pdf 249 - S3.4 Building Sections.pdf 237 - A2.2 Roof Framing Plan.pdf 231 - S1.1 Structural Notes & Schedules.pdf DRAFT 9 ADDITIONAL DETAILS Project: Tropical Chevrolet Renovation Subject: QUICK LUBE 130 DECK ANGLE @ EAST ELEV. Date Initiated: 10/04/23 Created By: Jim Jenco (Lebolo Construction Management, Inc.) Assigned To: Smedley, Brian (Nudell Architects) Responsible Contractor: Suncor (Hialeah, Florida) Received From: Dave Pond (Suncor (Hialeah, Florida)) Distribution List: Kuiper, Scott (Suncor (Hialeah, Florida)) Manjon, Maria Elena (Lebolo Construction Management, Inc.) Pond, Dave (Suncor (Hialeah, Florida)) Schedule Impact: TBD Cost Impact: TBD Drawing Number: S1.1, S2.2, S3.4, S4.1 More details: View online Open In App | View PDF Powered By Procore | support@procore.com | https://support.procore.com DRAFT Project No.: 2110.2100049 Report No.: 198687 Date: January 2, 2024 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-060 CN: GDZ Page 6 of 6 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute Roof deck bearing angle welded/anchored connections completed (01/02/24) Reviewed by: Universal Engineering Sciences Certificate of Authorization No. 549 Carlos Naumann, P.E., S.I. Florida Professional Engineer No. 18594 Florida Special Inspector No. 181 DRAFT