Tropical Chevrolet, 10-06-23 UES No 107721 SPECIAL insp rept #047 (structural steel connections reinsp. & 2nd floor slab @ lobby) - GDZProject No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 1 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
Client: Lebolo Construction Management, Inc.
2100 Corporate Drive
Boynton Beach, FL 33426
Project: Tropical Chevrolet Renovation/Expansion
8880 Biscayne Blvd.
Miami Shores, FL 33138
Agent: Gaetano Di Zio, E.I. Date of Services: 10/06/2023
Village of Miami Shores Building Permit No: CC-12-20-2951 (issued date 11/07/22, expires 05/08/23)
Scope of Field Services: Professional observation of completed structural elements (Special Inspector).
Reference Documents:
• JSG structural drawings sheets S1.0 thru S4.2 (15 pages), Bulleting 7 dated 07/21/2022, signed/sealed by Mark
Johnson FL-PE#51983, reviewed/approved for structural compliance by the Village of Miami Shores Bldg. Dept.
on 08/22, (permit set review by the Miami-Dade County Department of Regulatory and Economic Resources on
05/16/2022).
• SUNCOR, Inc. structural steel erection/fabrication shop drawings sheets AB1 thru TP101 (total of 219 pages) dated
04/13/2022 (Rev. A – Issued for Approval) Submittal #051200-5.0 (Structural Steel Shop Drawings), reviewed for
compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 05/03/2022.
• Canam Steel Corporation (CSC) steel metal deck shop drawings sheets DE1.1 thru DE2.1 (total of 3 pages) dated
04/08/2022 (Issued for Approval) Submittal #051200-6.0 (Deck Shop Drawings), reviewed for compliance (stamped
“Reviewed as Noted - Make Corrections”) by JSG on 04/15/2022.
Record of Field Observations:
1. Visual verification of the structural steel connections at the following locations indicated below:
a) ½” Ø x 1½” shear studs welded connections to the proposed new C10x25 steel channels approx. between grids
“C.5” thru “D.5” and lines “5.5” thru “6.5 for the precast concrete double “T’s” repair at the existing service
department, as per Conemco Engineering, Inc. precast concrete double Tee’s structural repair drawings, as we
addressed on UES Structural Observation Reports No. 38 (No.: 10040) dated 07/07/2023 and No. 41 (No.: 14712)
dated 09/06/2023, re-inspection inconclusive (09/12/23) – pending current welder qualification certification
(continuity paperwork- period of effectiveness):
➢ Welding slag was not completely removed from locations that require Visual Testing (VT).
➢ Incomplete or undersize fillet welds.
➢ Missing three (3) shear studs at locations marked in the field.
➢ A couple of shear studs were found to be spaced more than 8” o.c.
b) New C10x25 steel channels bolted/anchored connections to the existing roof precast concrete double
Tee’s/existing concrete beam approx. between grids “C.5” thru “D.5” and lines “5.5” thru “6.5 for the precast
concrete double “T’s” repair at the existing service department, as per Conemco Engineering, Inc. precast concrete
double Tee’s structural repair drawings, as we addressed on UES Structural Observation Report No. 044 (No.:
17436) dated 09/28/2023, corrections in progress on 10/06/23:
➢ Missing washers/nut at random locations.
➢ Anchor bolt threads were found not protruding (negative projection) beyond the outside surface of the nut
(negative stick‐out) at several locations as per RCSC (Research Council for Structural Connections)
Specification for Structural Joints Using ASTM A325 or A490 Bolts.
➢ One (1) loose-fitting thru bolt.
➢ One (1) screw anchor was found not to be ¾”.
c) New W12x30 steel beam and MC12x50 steel channels welded/anchored connections (torque verified at 100 ft−lb
as per the anchoring adhesive HILTI HIT-HY 200 required installation torque schedule for HAS Threaded Anchor
Rods) to the existing CIP concrete columns/existing concrete CIP tie beam along grid “D.1” between lines “2.3” thru
“3.43” and between grids “D.1” thru “E” and lines “3.43” thru “3.6” for the retrofit at the existing service department, DRAFT
Project No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 2 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
as per S1.0R, as we addressed on UES Structural Observation Reports No. 044 (No.: 17436) dated 09/28/2023
and No. 046 (No.: 197678) dated 10/03/2023, re-inspection completed:
➢ Missing three (3) threaded anchor rods at random locations.
➢ Some threaded anchor rods were found to be loose-fitting (not meeting the minimum torque of 100 ft−lb).
d) Continuous perimeter deck bearing angle L4”x4”x1/4” anchored connections (torque verified at 100 ft−lb as per
Simpson Strong−Bolt 2 Wedge Anchor required installation torque schedule) to CMU bond beam along line “11”
between grids “D.6” thru “E.2” at the Quick Lube (130), as per S1.0, S1.1/details 2 & 3, S2.2, 2/S3.1, 4/S4.1, E1000,
E1001 and E1002, failed on 10/03/23 – pending re-inspection:
➢ Missing three (3) expansion anchors.
The structural steel connections at the locations mentioned above were found to be in accordance with the reference
documents, except for item 1a inconclusive, item 1b in progress and item 1d failed. The General Contractor will call for
items 1b and 1d re-inspection after completion for final compliance verification. The welder qualification certificate was
provided during our site visit on 07/27/2023, however current continuity paperwork pending for review (Period of
Effectiveness). The welder that performed the work was not available onsite in order to verify his welder qualification.
As per The Structural Welding Code:
6.2.3 Period of Effectiveness
6.2.3.1 Welders and Welding Operators. The welder’s or welding operator’s qualification as specified in this code shall be
considered as remaining in effect indefinitely unless:
(1) the welder is not engaged in a given process of welding for which the welder or welding operator is qualified
for a period exceeding six months, or
(2) there is some specific reason to question a welder’s or welding operator’s ability (see 6.25.1).
2. Visual verification of the reinforcing steel placement at the following locations indicated below:
a) 6” CIP concrete elevated slab between grids “G” thru “H” and lines “8” thru “9” on the lobby 2nd floor, top of slab
elevation approx. +8’−0”, as per S1.0, S2.1 and 1/S3.3, completed.
b) Perimeter CIP concrete tie beam mark “TB101” (12”x12”) between grids “G” thru “H” and lines “8” thru “9” on the
lobby 2nd floor, top of beam elevation approx. +8’−0”, as per S1.0, S2.1, 1/S3.3 and S1.1/Concrete Tie & Bond
Beam Schedule, completed.
c) CMU bond beam mark “BB108” and CIP concrete tie beam 8”x16” along line “5” between grids “F.5” thru “G”, top
of beam elevation approx. +8’−8” at the existing service building, as per S1.0, S1.1/Concrete Tie and Bond Beam
Schedule, S2.3, A100 (Bulletin 13), A102 (Bulletin 13) and attached RFI #88, completed.
The reinforcing steel placement at the locations mentioned above was found to be in substantial compliance with the
reference documents.
Mr. Jim Jenco, Project Superintendent with Lebolo Construction, was notified of the aforementioned visual verification
results.
Please see adjacent report pages for photographs, welder certification qualification, RFI #88 and sheet S2.1. DRAFT
Project No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 3 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
On 10/03/23
Welds to be
grind off DRAFT
Project No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 4 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
DRAFT
Project No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 5 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
DRAFT
Project No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 6 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
DRAFT
DRAFT
1
Gaetano Di Zio
From:Jim Jenco <jjenco@Lebolo.com>
Sent:Friday, October 6, 2023 10:49 AM
To:Gaetano Di Zio
Cc:Maria Manjon; Kevinescobar88@yahoo.com
Subject:RE: Tropical Chevrolet RFI 88
Attachments:2019-010 A100-Overall 1st Floor Plan.pdf; 2019-010 A102-Layout.pdf
This Message Is From an External Sender
This message came from outside your organization.
Gaetano,
Please find the aƩached drawings for your records of the OHD opening you inspected this morning. This drawing is part
of BulleƟn 13 revision under review at MSV Bldg. Dept.
Thanks,
Jim Jenco
Superintendent
Lebolo Construction Management, Inc.
jjenco@lebolo.com
m. (561) 667‐9726
www.lebolo.com
o. (561) 742‐7644
SAFETY | INTEGRITY | ACCOUNTABILITY
"This e‐mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510‐2521, and may be legally
privileged. The information contained in this e‐mail message is confidential information intended only for the use of the
individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified
that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this
communication in error, please immediately notify sender by telephone at 561‐742‐7644, and delete the original
message. Thank you."
From: Jim Jenco
Sent: Friday, October 6, 2023 10:33 AM
To: Gaetano Di Zio <GDiZio@teamues.com>
Cc: Maria Manjon <memanjon@Lebolo.com>; Kevinescobar88@yahoo.com
Subject: FW: Tropical Chevrolet RFI 88
Gaetano
Please find the below e‐mail for your records of the architect forwarded to me with the structural engineer’s approval of
my fix to install a 8” x 16” Ɵe beam in lieu of the BB108 & window lintel at Get Ready Room 120.
Thanks, DRAFT
2
From: Brian Smedley <bsmedley@jhn.com>
Sent: Thursday, September 7, 2023 8:14 AM
To: Jim Jenco <jjenco@Lebolo.com>
Subject: FW: Tropical Chevrolet RFI 88
Jim:
Please see below from Pedro at JSG.
BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group
bsmedley@jhn.com
Office: 248.324.8800 x104 | Cell: 586.764.1743
NUDELL ARCHITECTS
Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334
Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804
From: Pedro R. Salom <psalom@johnsonstructural.com>
Sent: Thursday, September 7, 2023 7:27 AM
To: Brian Smedley <bsmedley@jhn.com>; Mark Johnson <mark@johnsonstructural.com>
Subject: RE: Tropical Chevrolet RFI 88
Hello Brian, I agree with Jim’s proposed fix.
Thanks.
Pedro Salom, P.E.
JohnsonStructuralGroup,Inc.
160 West Camino Real
Suite 1000
Boca Raton, FL 33432
Phone (561) 982‐8999 Ext. 13
Fax: (561) 982‐8899
www.johnsonstructural.com
From: Brian Smedley <bsmedley@jhn.com>
Sent: Wednesday, September 06, 2023 3:00 PM
To: Mark Johnson <mark@johnsonstructural.com>; Pedro R. Salom <psalom@johnsonstructural.com>
Subject: FW: Tropical Chevrolet RFI 88
Mark/Pedro:
Can you please review and reply to the below RFI for Tropical?
BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group
bsmedley@jhn.com
Office: 248.324.8800 x104 | Cell: 586.764.1743
NUDELL ARCHITECTS
Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334 DRAFT
3
Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804
From: Jim Jenco <jjenco@Lebolo.com>
Sent: Wednesday, September 6, 2023 2:54 PM
To: Brian Smedley <bsmedley@jhn.com>
Cc: Maria Manjon <memanjon@Lebolo.com>
Subject: Tropical Chevrolet RFI 88
Brian,
Please revisit RFI 88.
It pertains to detail to connect BB108 & precast lintel to exisƟng column.
The drawings do not have a detail for this specific connecƟon.
Because it is a non‐bearing condiƟon, the easiest fix would be the following:
form an 8½” x 16” Ɵe beam,
drill/epoxy 4 #5 dowels (6” Embedment) into exisƟng column,
4 #5 horizontal rebar spliced to dowels,
3000 PSI concrete.
If you give the ok, I will put it into acƟon.
Thanks,
Jim Jenco
Superintendent
Lebolo Construction Management, Inc.
jjenco@lebolo.com
m. (561) 667‐9726
www.lebolo.com
o. (561) 742‐7644
SAFETY | INTEGRITY | ACCOUNTABILITY
"This e‐mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510‐2521, and may be legally
privileged. The information contained in this e‐mail message is confidential information intended only for the use of the
individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified
that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this
communication in error, please immediately notify sender by telephone at 561‐742‐7644, and delete the original
message. Thank you."
DRAFT
Project No.: 2110.2100049
Report No.: 197721
Date: October 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-047
CN: GDZ Page 7 of 7
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
2nd floor CIP concrete elevated slab completed
Reviewed by:
Universal Engineering Sciences
Certificate of Authorization No. 549
Carlos Naumann, P.E., S.I.
Florida Professional Engineer No. 18594
Florida Special Inspector No. 181
DRAFT