Tropical Chevrolet, 10-06-23 UES No 107721 SPECIAL insp rept #047 (structural steel connections reinsp. & 2nd floor slab @ lobby) - GDZProject No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 1 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute Client: Lebolo Construction Management, Inc. 2100 Corporate Drive Boynton Beach, FL 33426 Project: Tropical Chevrolet Renovation/Expansion 8880 Biscayne Blvd. Miami Shores, FL 33138 Agent: Gaetano Di Zio, E.I. Date of Services: 10/06/2023 Village of Miami Shores Building Permit No: CC-12-20-2951 (issued date 11/07/22, expires 05/08/23) Scope of Field Services: Professional observation of completed structural elements (Special Inspector). Reference Documents: • JSG structural drawings sheets S1.0 thru S4.2 (15 pages), Bulleting 7 dated 07/21/2022, signed/sealed by Mark Johnson FL-PE#51983, reviewed/approved for structural compliance by the Village of Miami Shores Bldg. Dept. on 08/22, (permit set review by the Miami-Dade County Department of Regulatory and Economic Resources on 05/16/2022). • SUNCOR, Inc. structural steel erection/fabrication shop drawings sheets AB1 thru TP101 (total of 219 pages) dated 04/13/2022 (Rev. A – Issued for Approval) Submittal #051200-5.0 (Structural Steel Shop Drawings), reviewed for compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 05/03/2022. • Canam Steel Corporation (CSC) steel metal deck shop drawings sheets DE1.1 thru DE2.1 (total of 3 pages) dated 04/08/2022 (Issued for Approval) Submittal #051200-6.0 (Deck Shop Drawings), reviewed for compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 04/15/2022. Record of Field Observations: 1. Visual verification of the structural steel connections at the following locations indicated below: a) ½” Ø x 1½” shear studs welded connections to the proposed new C10x25 steel channels approx. between grids “C.5” thru “D.5” and lines “5.5” thru “6.5 for the precast concrete double “T’s” repair at the existing service department, as per Conemco Engineering, Inc. precast concrete double Tee’s structural repair drawings, as we addressed on UES Structural Observation Reports No. 38 (No.: 10040) dated 07/07/2023 and No. 41 (No.: 14712) dated 09/06/2023, re-inspection inconclusive (09/12/23) – pending current welder qualification certification (continuity paperwork- period of effectiveness): ➢ Welding slag was not completely removed from locations that require Visual Testing (VT). ➢ Incomplete or undersize fillet welds. ➢ Missing three (3) shear studs at locations marked in the field. ➢ A couple of shear studs were found to be spaced more than 8” o.c. b) New C10x25 steel channels bolted/anchored connections to the existing roof precast concrete double Tee’s/existing concrete beam approx. between grids “C.5” thru “D.5” and lines “5.5” thru “6.5 for the precast concrete double “T’s” repair at the existing service department, as per Conemco Engineering, Inc. precast concrete double Tee’s structural repair drawings, as we addressed on UES Structural Observation Report No. 044 (No.: 17436) dated 09/28/2023, corrections in progress on 10/06/23: ➢ Missing washers/nut at random locations. ➢ Anchor bolt threads were found not protruding (negative projection) beyond the outside surface of the nut (negative stick‐out) at several locations as per RCSC (Research Council for Structural Connections) Specification for Structural Joints Using ASTM A325 or A490 Bolts. ➢ One (1) loose-fitting thru bolt. ➢ One (1) screw anchor was found not to be ¾”. c) New W12x30 steel beam and MC12x50 steel channels welded/anchored connections (torque verified at 100 ft−lb as per the anchoring adhesive HILTI HIT-HY 200 required installation torque schedule for HAS Threaded Anchor Rods) to the existing CIP concrete columns/existing concrete CIP tie beam along grid “D.1” between lines “2.3” thru “3.43” and between grids “D.1” thru “E” and lines “3.43” thru “3.6” for the retrofit at the existing service department, DRAFT Project No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 2 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute as per S1.0R, as we addressed on UES Structural Observation Reports No. 044 (No.: 17436) dated 09/28/2023 and No. 046 (No.: 197678) dated 10/03/2023, re-inspection completed: ➢ Missing three (3) threaded anchor rods at random locations. ➢ Some threaded anchor rods were found to be loose-fitting (not meeting the minimum torque of 100 ft−lb). d) Continuous perimeter deck bearing angle L4”x4”x1/4” anchored connections (torque verified at 100 ft−lb as per Simpson Strong−Bolt 2 Wedge Anchor required installation torque schedule) to CMU bond beam along line “11” between grids “D.6” thru “E.2” at the Quick Lube (130), as per S1.0, S1.1/details 2 & 3, S2.2, 2/S3.1, 4/S4.1, E1000, E1001 and E1002, failed on 10/03/23 – pending re-inspection: ➢ Missing three (3) expansion anchors. The structural steel connections at the locations mentioned above were found to be in accordance with the reference documents, except for item 1a inconclusive, item 1b in progress and item 1d failed. The General Contractor will call for items 1b and 1d re-inspection after completion for final compliance verification. The welder qualification certificate was provided during our site visit on 07/27/2023, however current continuity paperwork pending for review (Period of Effectiveness). The welder that performed the work was not available onsite in order to verify his welder qualification. As per The Structural Welding Code: 6.2.3 Period of Effectiveness 6.2.3.1 Welders and Welding Operators. The welder’s or welding operator’s qualification as specified in this code shall be considered as remaining in effect indefinitely unless: (1) the welder is not engaged in a given process of welding for which the welder or welding operator is qualified for a period exceeding six months, or (2) there is some specific reason to question a welder’s or welding operator’s ability (see 6.25.1). 2. Visual verification of the reinforcing steel placement at the following locations indicated below: a) 6” CIP concrete elevated slab between grids “G” thru “H” and lines “8” thru “9” on the lobby 2nd floor, top of slab elevation approx. +8’−0”, as per S1.0, S2.1 and 1/S3.3, completed. b) Perimeter CIP concrete tie beam mark “TB101” (12”x12”) between grids “G” thru “H” and lines “8” thru “9” on the lobby 2nd floor, top of beam elevation approx. +8’−0”, as per S1.0, S2.1, 1/S3.3 and S1.1/Concrete Tie & Bond Beam Schedule, completed. c) CMU bond beam mark “BB108” and CIP concrete tie beam 8”x16” along line “5” between grids “F.5” thru “G”, top of beam elevation approx. +8’−8” at the existing service building, as per S1.0, S1.1/Concrete Tie and Bond Beam Schedule, S2.3, A100 (Bulletin 13), A102 (Bulletin 13) and attached RFI #88, completed. The reinforcing steel placement at the locations mentioned above was found to be in substantial compliance with the reference documents. Mr. Jim Jenco, Project Superintendent with Lebolo Construction, was notified of the aforementioned visual verification results. Please see adjacent report pages for photographs, welder certification qualification, RFI #88 and sheet S2.1. DRAFT Project No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 3 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute On 10/03/23 Welds to be grind off DRAFT Project No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 4 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute DRAFT Project No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 5 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute DRAFT Project No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 6 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute DRAFT DRAFT 1 Gaetano Di Zio From:Jim Jenco <jjenco@Lebolo.com> Sent:Friday, October 6, 2023 10:49 AM To:Gaetano Di Zio Cc:Maria Manjon; Kevinescobar88@yahoo.com Subject:RE: Tropical Chevrolet RFI 88 Attachments:2019-010 A100-Overall 1st Floor Plan.pdf; 2019-010 A102-Layout.pdf   This Message Is From an External Sender This message came from outside your organization.   Gaetano,    Please find the aƩached drawings for your records of the OHD opening you inspected this morning. This drawing is part  of BulleƟn 13 revision under review at MSV Bldg. Dept.  Thanks,       Jim Jenco  Superintendent       Lebolo Construction Management, Inc.  jjenco@lebolo.com m. (561) 667‐9726    www.lebolo.com  o. (561) 742‐7644          SAFETY  |  INTEGRITY  |  ACCOUNTABILITY  "This e‐mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510‐2521, and may be legally  privileged. The information contained in this e‐mail message is confidential information intended only for the use of the  individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified  that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this  communication in error, please immediately notify sender by telephone at 561‐742‐7644, and delete the original  message. Thank you."     From: Jim Jenco   Sent: Friday, October 6, 2023 10:33 AM  To: Gaetano Di Zio <GDiZio@teamues.com>  Cc: Maria Manjon <memanjon@Lebolo.com>; Kevinescobar88@yahoo.com  Subject: FW: Tropical Chevrolet RFI 88     Gaetano    Please find the below e‐mail for your records of the architect forwarded to me with the structural engineer’s approval of  my fix to install a 8” x 16” Ɵe beam in lieu of the BB108 & window lintel at Get Ready Room 120.  Thanks,  DRAFT 2 From: Brian Smedley <bsmedley@jhn.com>   Sent: Thursday, September 7, 2023 8:14 AM  To: Jim Jenco <jjenco@Lebolo.com>  Subject: FW: Tropical Chevrolet RFI 88     Jim:  Please see below from Pedro at JSG.    BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743   NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334   Florida  |  1807 Edgewater Drive (College Park) | Orlando, Florida 32804   From: Pedro R. Salom <psalom@johnsonstructural.com>   Sent: Thursday, September 7, 2023 7:27 AM  To: Brian Smedley <bsmedley@jhn.com>; Mark Johnson <mark@johnsonstructural.com>  Subject: RE: Tropical Chevrolet RFI 88     Hello Brian, I agree with Jim’s proposed fix.    Thanks.          Pedro Salom, P.E.  JohnsonStructuralGroup,Inc.  160 West Camino Real  Suite 1000  Boca Raton, FL  33432  Phone (561) 982‐8999 Ext. 13  Fax: (561) 982‐8899  www.johnsonstructural.com      From: Brian Smedley <bsmedley@jhn.com>   Sent: Wednesday, September 06, 2023 3:00 PM  To: Mark Johnson <mark@johnsonstructural.com>; Pedro R. Salom <psalom@johnsonstructural.com>  Subject: FW: Tropical Chevrolet RFI 88     Mark/Pedro:  Can you please review and reply to the below RFI for Tropical?    BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group bsmedley@jhn.com Office: 248.324.8800 x104 | Cell: 586.764.1743   NUDELL ARCHITECTS Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334   DRAFT 3 Florida  |  1807 Edgewater Drive (College Park) | Orlando, Florida 32804   From: Jim Jenco <jjenco@Lebolo.com>   Sent: Wednesday, September 6, 2023 2:54 PM  To: Brian Smedley <bsmedley@jhn.com>  Cc: Maria Manjon <memanjon@Lebolo.com>  Subject: Tropical Chevrolet RFI 88     Brian,    Please revisit RFI 88.   It pertains to detail to connect BB108 & precast lintel to exisƟng column.  The drawings do not have a detail for this specific connecƟon.  Because it is a non‐bearing condiƟon, the easiest fix would be the following:   form an 8½” x 16” Ɵe beam,   drill/epoxy 4 #5 dowels (6” Embedment) into exisƟng column,   4 #5 horizontal rebar spliced to dowels,   3000 PSI concrete.   If you give the ok, I will put it into acƟon.  Thanks,   Jim Jenco  Superintendent       Lebolo Construction Management, Inc.  jjenco@lebolo.com m. (561) 667‐9726    www.lebolo.com  o. (561) 742‐7644          SAFETY  |  INTEGRITY  |  ACCOUNTABILITY  "This e‐mail is subject to the Electronics Communications Privacy Act, 18 U.S.C. § 2510‐2521, and may be legally  privileged. The information contained in this e‐mail message is confidential information intended only for the use of the  individual or entity named above. If the reader of this message is not the intended recipient, you are hereby notified  that any dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this  communication in error, please immediately notify sender by telephone at 561‐742‐7644, and delete the original  message. Thank you."      DRAFT Project No.: 2110.2100049 Report No.: 197721 Date: October 6, 2023 8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479 STRUCTURAL OBSERVATION REPORT No. SPECIAL-047 CN: GDZ Page 7 of 7 cc: 1 − Job Site; 1 − Client; 1 The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute 2nd floor CIP concrete elevated slab completed Reviewed by: Universal Engineering Sciences Certificate of Authorization No. 549 Carlos Naumann, P.E., S.I. Florida Professional Engineer No. 18594 Florida Special Inspector No. 181 DRAFT