Tropical Chevrolet, 07-06-23 UES No 7242 SPECIAL insp rept #034 (structural steel connections @ exp. bldg.) - GDZProject No.: 2110.2100049
Report No.: 7242
Date: July 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-034
CN: GDZ Page 1 of 5
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H -18.11, Chapter 471, Florida Statute
Client: Lebolo Construction Management, Inc.
2100 Corporate Drive
Boynton Beach, FL 33426
Project: Tropical Chevrolet Renovation/Expansion
8880 Biscayne Blvd.
Miami Shores, FL 33138
Agent: Gaetano Di Zio, E.I. Date of Services: 07/06/2023
Village of Miami Shores Building Permit No: CC-12-20-2951 (issued date 11/07/22, expires 05/08/23)
Scope of Field Services: Professional observation of completed structural elements (Special Inspector).
Reference Documents:
• JSG structural drawings sheets S1.0 thru S4.2 (15 pages), Bulleting 7 dated 07/21/2022, signed/sealed by Mark
Johnson FL-PE#51983, reviewed/approved for structural compliance by the Village of Miami Shores Bldg. Dept.
on 08/22, (permit set review by the Miami-Dade County Department of Regulatory and Economic Resources on
05/16/2022).
• SUNCOR, Inc. structural steel erection/fabrication shop drawings sheets AB1 thru TP101 (total of 219 pages) dated
04/13/2022 (Rev. A – Issued for Approval) Submittal #051200-5.0 (Structural Steel Shop Drawings), reviewed for
compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 05/03/2022.
• Canam Steel Corporation (CSC) steel metal deck shop drawings sheets DE1.1 thru DE2.1 (total of 3 pages) dated
04/08/2022 (Issued for Approval) Submittal #051200-6.0 (Deck Shop Drawings), reviewed for compliance (stamped
“Reviewed as Noted - Make Corrections”) by JSG on 04/15/2022.
Record of Field Observations:
1. Visual verification of the structural steel connections at the following locations indicated below:
a) W roof steel beams welded/bolted connections to CIP concrete beam embed plates at gridlines D.5x11 and D.5x12
at the oil storage room, as per S1.0, S2.2, 2/S3.2, 4/S4.1, E1000 and E1001, completed.
b) 3” deep 22 gauge galvanized G80 corrugated roof metal deck profile type “N” prior roof openings (A/S ducts,
ventilations, roof hatches, etc.), connected to intermediate supports with 5/8ӯ puddle welds on a 24/4 pattern,
5/8”Ø puddle welds at 6” o.c. at deck perimeter and with #12 Type self-tapping screws @ 3” o.c. at side laps per
span between grids “A” thru “E.3” and lines “8” thru “11” and between grids “D.1” thru “D.6” and lines “11” thru “12”,
as per S1.0, S2.2, 2/S3.2, S4.1/details 1, 2, 3, 4 & 5, Canam Steel Corporation deck shop drawing sheets DE1.1,
DE1.3 & DE2.1 and attached clarification submitted by the steel erector via e-mail, partial.
c) Continuous perimeter deck bearing angle L4”x4”x1/4” anchored connections (torque verified at 100 ft−lb as per
Simpson Strong−Bolt 2 Wedge Anchor required installation torque schedule) to CIP concrete beam and to CMU
bond beam along grid “D.1” between lines “11” thru “12” and along lines “11” & “12” between grids “D.1” thru “D.6”
at the oil storage room, as per S1.0, S1.1/details 2 & 3, S2.2, 2/S3.1, S3.2, S4.1/details 1 & 4, E1000 and E1001,
completed.
d) Continuous perimeter deck bearing angle L4”x4”x1/4” anchored connections (torque verified at 100 ft−lb as per
Simpson Strong−Bolt 2 Wedge Anchor required installation torque schedule) to CMU bond beam along grid “D.6”
between lines “11” thru “12” at the oil storage room, as per S1.0, S1.1/details 2 & 3, S2.2, 2/S3.1, 4/S4.1, E1000
and E1001, in progress:
➢ Two (1) expansion anchors were found to be loose fitting at approx. gridlines D.6x11.3 and D.6x11.5.
The structural steel connections at the locations mentioned above was found to be in substantial compliance with the
reference documents, except for item 1b partial and 1d in progress. General Contractor will call for items 1b and 1d
re−inspection after completion for final compliance verification.
Mr. Jim Jenco, Project Superintendent and Mr. Sebastian Cienfuegos, Assistant Superintendent with Lebolo Construction,
were notified of the aforementioned visual verification results.
Please see adjacent report pages for photographs, clarification submitted by the steel erector via e-mail and sheet S2.2. DRAFT
Project No.: 2110.2100049
Report No.: 7242
Date: July 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-034
CN: GDZ Page 2 of 5
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H -18.11, Chapter 471, Florida Statute
DRAFT
Project No.: 2110.2100049
Report No.: 7242
Date: July 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-034
CN: GDZ Page 3 of 5
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H -18.11, Chapter 471, Florida Statute
DRAFT
Project No.: 2110.2100049
Report No.: 7242
Date: July 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-034
CN: GDZ Page 4 of 5
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H -18.11, Chapter 471, Florida Statute
DRAFT
1
Gaetano Di Zio
From:Jim Jenco <jjenco@Lebolo.com>
Sent:Wednesday, July 5, 2023 2:43 PM
To:Gaetano Di Zio
Cc:Victor Castro; Sebastian Cienfuegos; Maria Manjon
Subject:FW: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
This Message Is From an External Sender
This message came from outside your organization.
Gaetano,
Please find the below e‐mail indicaƟng the spacing for puddle weld at the Corrugated Deck seam connecƟon in lieu of
TEK screw 3” O.C.
Thanks,
Jim Jenco
Lebolo Construction Management, Inc.
jjenco@lebolo.com I www.lebolo.com
M: (561) 667‐9726 I O: (561) 742‐7644
SAFETY – INTEGRITY – ACCOUNTABILITY
From: Brian Smedley <bsmedley@jhn.com>
Sent: Monday, July 3, 2023 7:02 AM
To: Jim Jenco <jjenco@Lebolo.com>
Subject: FW: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
Jim:
Please see email below.
BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group
bsmedley@jhn.com
Office: 248.324.8800 x104 | Cell: 586.764.1743
NUDELL ARCHITECTS
Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334
Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804
DRAFT
2
From: Pedro R. Salom <psalom@johnsonstructural.com>
Sent: Saturday, July 1, 2023 8:42 AM
To: Brian Smedley <bsmedley@jhn.com>
Cc: Mark Johnson <mark@johnsonstructural.com>
Subject: RE: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
Brian, use 5/8” puddle welds spaced at not more than 6” o.c.
Thanks.
Pedro Salom, P.E.
JohnsonStructuralGroup,Inc.
160 West Camino Real
Suite 1000
Boca Raton, FL 33432
Phone (561) 982‐8999 Ext. 13
Fax: (561) 982‐8899
www.johnsonstructural.com
From: Brian Smedley <bsmedley@jhn.com>
Sent: Friday, June 30, 2023 10:18 AM
To: Pedro R. Salom <psalom@johnsonstructural.com>
Subject: FW: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
Pedro:
Can you please review the below and advise? The reason for the request is in the email thread below.
DRAFT
3
BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group
bsmedley@jhn.com
Office: 248.324.8800 x104 | Cell: 586.764.1743
NUDELL ARCHITECTS
Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334
Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804
From: Jim Jenco <jjenco@Lebolo.com>
Sent: Friday, June 30, 2023 10:12 AM
To: Brian Smedley <bsmedley@jhn.com>
Cc: Dave Pond <Dave.P@suncor.net>; Victor Castro <Victor.C@suncor.net>; Sebastian Cienfuegos
<SCienfuegos@Lebolo.com>; Maria Manjon <memanjon@Lebolo.com>
Subject: RE: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
A secƟon of the decking seam ran on the edge of the W27 x 84 (approx.. 32 LF). The TEK screws are hiƫng steel and not
securing the lap.
From: Brian Smedley <bsmedley@jhn.com>
Sent: Friday, June 30, 2023 10:04 AM
To: Jim Jenco <jjenco@Lebolo.com>
Cc: Dave Pond <Dave.P@suncor.net>; Victor Castro <Victor.C@suncor.net>; Sebastian Cienfuegos
<SCienfuegos@Lebolo.com>; Maria Manjon <memanjon@Lebolo.com>
Subject: RE: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
Jim:
What is driving the need for puddle welding in this area only?
BRIAN SMEDLEY, AIA NCARB |Director ‐ Automotive Group
bsmedley@jhn.com
Office: 248.324.8800 x104 | Cell: 586.764.1743
NUDELL ARCHITECTS
Michigan | 30403 West 13 Mile Road | Farmington Hills, MI 48334
Florida | 1807 Edgewater Drive (College Park) | Orlando, Florida 32804
From: Jim Jenco <jjenco@Lebolo.com>
Sent: Friday, June 30, 2023 9:59 AM
To: Brian Smedley <bsmedley@jhn.com>
Cc: Dave Pond <Dave.P@suncor.net>; Victor Castro <Victor.C@suncor.net>; Sebastian Cienfuegos
<SCienfuegos@Lebolo.com>; Maria Manjon <memanjon@Lebolo.com>
Subject: Tropical Chevrolet RFI 90 Puddle Weld in lieu of TEK Screw
Good Morning Brian,
RE: ClarificaƟon of RFI 90 Puddle Weld in lieu of TEK Screws
All laps on the deck are TEK screwed except one area of decking that ran on top of the edge of W27 x 84.
This is the area where the lap was puddle welded (approx. 32’ LF).
I edited the Procore RFI90 and included the aƩached marked up S2.2 Roof Framing Plan indicaƟng this area. DRAFT
4
Thanks,
Jim Jenco
Lebolo Construction Management, Inc.
jjenco@lebolo.com I www.lebolo.com
M: (561) 667‐9726 I O: (561) 742‐7644
SAFETY – INTEGRITY – ACCOUNTABILITY
DRAFT
Project No.: 2110.2100049
Report No.: 7242
Date: July 6, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-034
CN: GDZ Page 5 of 5
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H -18.11, Chapter 471, Florida Statute
Roof metal deck in progress
Reviewed by:
Universal Engineering Sciences
Certificate of Authorization No. 549
Carlos Naumann, P.E., S.I.
Florida Professional Engineer No. 18594
Florida Special Inspector No. 181
DRAFT