Tropical Chevrolet 05-26-23 UES No 354485 SPECIAL insp rept #027 (structural steel connections @ exp. bldg.) - GDZProject No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 1 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
Client: Lebolo Construction Management, Inc.
2100 Corporate Drive
Boynton Beach, FL 33426
Project: Tropical Chevrolet Renovation/Expansion
8880 Biscayne Blvd.
Miami Shores, FL 33138
Agent: Gaetano Di Zio, E.I. Date of Services: 05/26/2023
Village of Miami Shores Building Permit No: CC-12-20-2951 (issued date 11/07/22, expires 05/08/23)
Scope of Field Services: Professional observation of completed structural elements (Special Inspector).
Reference Documents:
• JSG structural drawings sheets S1.0 thru S4.2 (15 pages), Bulleting 7 dated 07/21/2022, signed/sealed by Mark
Johnson FL-PE#51983, reviewed/approved for structural compliance by the Village of Miami Shores Bldg. Dept.
on 08/22, (permit set review by the Miami-Dade County Department of Regulatory and Economic Resources on
05/16/2022).
• SUNCOR, Inc. structural steel erection/fabrication shop drawings sheets AB1 thru TP101 (total of 219 pages) dated
04/13/2022 (Rev. A – Issued for Approval) Submittal #051200-5.0 (Structural Steel Shop Drawings), reviewed for
compliance (stamped “Reviewed as Noted - Make Corrections”) by JSG on 05/03/2022.
• Canam Steel Corporation (CSC) steel metal deck shop drawings sheets DE1.1 thru DE2.1 (total of 3 pages) dated
04/08/2022 (Issued for Approval) Submittal #051200-6.0 (Deck Shop Drawings), reviewed for compliance (stamped
“Reviewed as Noted - Make Corrections”) by JSG on 04/15/2022.
Record of Field Observations:
1. Visual verification of the structural steel connections at the following locations indicated below:
a) W roof steel beams welded/bolted connections to CIP concrete beam embed plates along grid “A” between lines
“8” thru “11” at the service building expansion, as per S1.0, S2.2, 2/S3.2, 1/S4.1, E1000 and E1001, inconclusive
on 05/22/23.
b) W roof steel girder beams welded/bolted connections to CIP concrete beam embed plates at gridlines B.8x11 and
D.3x11 at the service building expansion, as per S1.0, 2/S1.1, S2.2, 1/S3.2, 1/S4.1, E1000 and E1002,
inconclusive on 05/22/23.
c) W roof steel beams welded/bolted connections to W roof steel beams/roof steel girder beams between grids “B.8”
thru “D.3” and lines “8.7” thru “10.8” at the service building expansion, as per S1.0, S2.2, 2/S3.2, 1/S4.1, E1000
and E1002, inconclusive on 05/22/23.
d) Continuous perimeter deck bearing angle L4”x4”x1/4” anchored connections to CIP concrete beam along grids “A”
and “E.4” between lines “8” thru “11” at the service building expansion, as per S1.0, S1.1/details 2 & 3, S2.2, S3.2,
S4.1/details 1 & 4, E1000 and E1001, preliminary on 05/22/23 – pending reinspection:
➢ Expansion anchors were found not to meet the minimum embedment of 4”, as per 3/S1.1 and
E1001/Section C−C.
➢ Pending deck bearing angle splice detail.
e) Continuous perimeter deck bearing angle L4”x4”x1/4” welded connections to CIP concrete beam embed plates
along line “11” between grids “A” and “E.4” at the service building expansion, as per S1.0, S2.2, S3.2, 2/S4.1,
E1000 and E1001, inconclusive on 05/22/23.
f) Roof opening steel supporting frame welded connections to W roof steel beams for the proposed RTU’s between
grids “B.8” thru “C.5” and lines “10.2” thru “10.5” at the service building expansion, as per S1.0, S2.2, A/S4.2, E1000
and E1005, inconclusive on 05/22/23.
g) W roof steel girder beams welded/bolted connections to HSS steel columns at gridlines B.8x9, B.8x10, D.3x9 and
D.3x10 at the service building expansion, as per S1.0, 1/S1.1, S2.2, E1000 and Column Alignment Detail,
inconclusive on 05/24/23. DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 2 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
h) Visual verification of HSS steel column (C2 & C3) base plates bolted connections to existing concrete footings (prior
to the installation of the grout bedding) at gridlines B.8x9, B.8x10, D.3x9 and D.3x10, as per S1.0, S1.1, S2.0,
8/S4.0 and AB1, completed.
i) W roof steel beams welded/bolted connections to W roof steel girder beams at gridlines B.8x8 and D.3x8 at the
service building expansion, as per S1.0, S2.2, 2/S3.2, 1/S4.1, E1000 and E1002, inconclusive on 05/26/23.
j) W roof steel girder beams bolted connections to existing wall at gridlines B.8x8 and D.3x8 at the service building
expansion, as per S1.0, S2.2, 2/S3.2, 8/S4.1 and attached Girder Bearing at Existing Wall detail SK 04−10−23
submitted by the SEoR, preliminary on 05/26/23 – pending reinspection:
➢ Loose expansion anchor at existing wall clip at gridline B.8x8.
➢ Missing washer for wall clip bolt to steel girder beam at gridline D.3x8.
➢ Threaded rods were found to be installed (drilled & epoxied) prior to our visual verification. A UES
representative did not verify any drilled holes for cleanness, embedment, epoxy application and threaded
rods installation. Torque verified at 100 ft−lb as per Hilti HIT HY-100 anchoring adhesive required
installation torque schedule.
k) W roof steel beams welded/bolted connections to CIP concrete beam embed plates along grid “E.4” between lines
“8” thru “11” at the service building expansion, as per S1.0, S2.2, 1/S3.2, 1/S4.1, E1000, E1001 and attached
Section @ Roof Beam Repair detail SK 04−12−23 submitted by the SEoR, preliminary on 05/26/23 – pending
reinspection:
➢ Some expansion anchors (@ 4 beams) were found to be loose fitting. Torque verified at 100 ft−lb as per
Simpson Strong−Bolt 2 Wedge Anchor required installation torque (in Masonry) schedule.
The structural steel connections at the locations mentioned above were found to be inconclusive/preliminary (items 1d,
1j & 1k) on 05/22/23, 05/24/23 and 05/26/23. General Contractor will call for items 1d, 1j & 1k re-inspection after completion
for final compliance verification.
Welder’s Qualification Certificates were provided at the time of this inspection, however current continuity paperwork
pending for review (Period of Effectiveness). The welder(s) that performed the work was (were) available onsite in order
to verify their welder’s qualifications.
As per The Structural Welding Code:
6.2.3 Period of Effectiveness
6.2.3.1 Welders and Welding Operators. The welder’s or welding operator’s qualification as specified in this code shall be
considered as remaining in effect indefinitely unless:
(1) the welder is not engaged in a given process of welding for which the welder or welding operator is qualified
for a period exceeding six months, or
(2) there is some specific reason to question a welder’s or welding operator’s ability (see 6.25.1).
Mr. Jim Jenco, Project Superintendent with Lebolo Construction, was notified of the aforementioned visual verification
results.
Please see adjacent report pages for photographs, miscellaneous field repair details, welder’s certifications and sheet S2.2.
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 3 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
On 05/22/23
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 4 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 5 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
On 05/24/23
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 6 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
On 05/26/22
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 7 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 8 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
DRAFT
DRAFT
DRAFT
ConstructionSikacrete® 211 SCC Plus
One-component, cementitious, polymer-modified, self consolidating
concrete mix with an integral migrating corrosion inhibitor
Description Sikacrete 211 SCC Plus is a one-component, self consolidating concrete containing factory
blended coarse aggregate. This self consolidating concrete bag is silica fume and polymer
modified and also contains a migrating corrosion inhibitor.
Where to Use n Full depth repairs.
n On grade, above and below grade on concrete.
n On horizontal surfaces.
n Vertical and overhead surfaces when formed and pumped or poured.
n As a structural repair material for parking facilities, industrial plants, walkways, bridges,
tunnels, dams, and balconies.
n Filler for voids and cavities.
Advantages n Self consolidating concrete - excellent placement characteristics.
n Polymer-modified.
n Integral penetrating corrosion inhibitor.
n Silica fume enhanced.
n Prepackaged coarse aggregate. Eliminates the need to extend material in the field. Elimi-
nates the risk of reactive aggregate.
n Can be pumped or poured into forms and gets excellent consolidation without vibrating.
Yield Approximately 0.50 ft.3/bag. Actual results on site may vary.
Packaging 65 lb. multi-wall bag.
Product Data Sheet
Edition 2.2.2010
Identification no.
Sikacrete 211 SCC Plus
Typical Data (Material and curing conditions @ 73°F (23°C) and 50% R.H.)
Shelf Life 1 year in original, unopened packaging.
Storage Conditions Store dry at 40°-95°F (4°-35°C). Condition material to
65°-75°F (18°-24°C) before using.
Initial Spread SCC, 27-33 in. approx.
Spread @ 30 min. > 15 in.
Application Time 60 minutes
Flexural Strength (ASTM C-78) 1 day 500 psi (3.4 MPa)
7 days 750 psi (5.2 MPa)
28 days 1,000 psi (6.9 MPa)
Splitting Tensile Strength (ASTM C-496) 7 days 750 psi (5.1 MPa)
28 days 1,000 psi (6.9 MPa)
Slant Shear Bond Strength* (ASTM C-882 modified)
1 day 1,000 psi (6.9 MPa)
7 days 1,500 psi (10.3 MPa)
28 days 2,500 psi (17.2 MPa)
Direct Tensile Bond (ACI 503) 1 day 250 psi (1.7 MPa)
7 days 300 psi (2.1 MPa)
Compressive Strength ( ASTM C-39)
1 day 2,000 psi (13.8 MPa)
7 days 6,000 psi (41.4 MPa)
28 days 7,000 psi (48.3 MPa)
Shrinkage (ASTM C-157) 28 days <0.05%
Chloride ion permeability (ASTM C-1202) 28 days <650 Coloumbs
Freeze Thaw Resistance (ASTM C-666) 300 cycles > 99%
Scaling Resistance (ASTM C-672) 50 cycles 2
Sulfate Resistance (ASTM C-1012)
Length change after 6 months 0.006
* Mortar scrubbed into substrate.
How to Use
Surface Preparation Remove all deteriorated concrete, dirt, oil, grease, and all bond-inhibit-
ing materials from surface. Be sure repair area is not less than 1 in. in DRAFT
ConstructionVisit our website at www.sikaconstruction.com 1-800-933-SIKA NATIONWIDE
Regional Information and Sales Centers. For the location of your nearest Sika sales office, contact your regional center.
Sika Corporation Sika Canada Inc. Sika Mexicana S.A. de C.V.
201 Polito Avenue 601 Delmar Avenue Carretera Libre Celaya Km. 8.5
Lyndhurst, NJ 07071 Pointe Claire Fracc. Industrial Balvanera
Phone: 800-933-7452 Quebec H9R 4A9 Corregidora, Queretaro
Fax: 201-933-6225 Phone: 514-697-2610 C.P. 76920
Fax: 514-694-2792 Phone: 52 442 2385800
Fax: 52 442 2250537
KEEP CONTAINER TIGHTLY CLOSED • KEEP OUT OF REACH OF CHILDREN • NOT FOR INTERNAL CONSUMPTION • FOR INDUSTRIAL USE ONLY
All information provided by Sika Corporation (“Sika”) concerning Sika products, including but not limited to, any recommendations and advice relating to the
application and use of Sika products, is given in good faith based on Sika’s current experience and knowledge of its products when properly stored, handled
and applied under normal conditions in accordance with Sika’s instructions. In practice, the differences in materials, substrates, storage and handling condi-
tions, actual site conditions and other factors outside of Sika’s control are such that Sika assumes no liability for the provision of such information, advice,
recommendations or instructions related to its products, nor shall any legal relationship be created by or arise from the provision of such information, advice,
recommendations or instructions related to its products. The user of the Sika product(s) must test the product(s) for suitability for the intended application
and purpose before proceeding with the full application of the product(s). Sika reserves the right to change the properties of its products without notice.
All sales of Sika product(s) are subject to its current terms and conditions of sale which are available at www.sikacorp.com or by calling 800-933-7452.
Prior to each use of any Sika product, the user must always read and follow the warnings and instructions on the product’s most current Technical
Data Sheet, product label and Material Safety Data Sheet which are available online at www.sikaconstruction.com or by calling Sika's Technical
Service Department at 800-933-7452. Nothing contained in any Sika materials relieves the user of the obligation to read and follow the warnings and
instruction for each Sika product as set forth in the current Technical Data Sheet, product label and Material Safety Data Sheet prior to product use.
LIMITED WARRANTY: Sika warrants this product for one year from date of installation to be free from manufacturing defects and to meet the technical properties on the current Technical Data Sheet if used as directed within shelf life. User determines suitability of product for intended
use and assumes all risks. Buyer’s sole remedy shall be limited to the purchase price or replacement of product exclusive of labor or cost of labor. NO OTHER WARRANTIES ExPRESS OR IMPLIED SHALL APPLY INCLUDINg ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. SIKA SHALL NOT BE LIABLE UNDER ANY LEgAL THEORY FOR SPECIAL OR CONSEqUENTIAL DAMAgES. SIKA SHALL NOT BE RESPONSIBLE
FOR THE USE OF THIS PRODUCT IN A MANNER TO INFRINgE ON ANY PATENT OR ANY OTHER INTELLECTUAL PROPERTY RIgHTS HELD BY OTHERS.
Sika and Sikacrete are registered
trademarks. Made in USA. Printed in Canada.
depth. Preparation work should be done by high pressure water blast, scabbler, or other
appropriate mechanical means to obtain an exposed aggregate surface with a minimum
surface profile of ±1/8in. (CSP-7-8). Saturate surface with clean water. Substrate should be
saturated surface dry (SSD) with no standing water during application.
Reinforcing Steel:Steel reinforcement should be thoroughly prepared by mechanical
cleaning to remove all traces of rust. Where corrosion has occurred due to the presence
of chlorides, the steel should be high-pressure washed with clean water after mechanical
cleaning. For priming and protection of reinforcing steel use Sika Armatec 110 EpoCem
(consult Technical Data Sheet).
Mixing Start mixing with 5.5 pints of water. An additional 0.5 pint can be added if needed. Do not
overwater as excess water will cause segregation. Add Sikacrete 211 while continuing to
mix. Mix to a uniform consistency, maximum 3 minutes. Mechanically mix with a low-speed
drill (400-600 rpm) and paddle or in appropriate-size mortar mixer or concrete mixer.
Application Pre-wet surface to SSD (Saturated Surface Dry). Ensure good intimate contact with the
substrate is achieved. To accomplish this, material should be scrubbed into the substrate
or other suitable means should be employed such as vibration of the material or pumping
under pressure. Vibrate form while pouring or pumping. Pump with a variable pressure
pump. Continue pumping until a 3 to 5 psi increase in normal line pressure is evident then
STOP pumping. Form should not deflect. Vent to be capped when steady flow is evident,
and forms stripped when appropriate.
Curing As per ACI recommendations for portland cement concrete, curing is required. Moist cure
with wet burlap and polyethylene, a fine mist of water or a water based* compatible curing
compound. Curing compounds adversely affect the adhesion of following layers of mortar,
leveling mortar or protective coatings. Moist curing should commence immediately after
finishing. Protect newly applied material from direct sunlight, wind, rain and frost.
. *Pretesting of curing compound is recommended.
Limitations n Application thickness: Minimum 1 in. (25 mm); Maximum 8 in. (200 mm)
n Minimum ambient and surface temperatures 45°F (7°C) and rising at time of application.
n As with all cement based materials, avoid contact with aluminum to prevent adverse
chemical reaction and possible product failure. Insulate potential areas of contact by
coating aluminum bars, rails, posts etc. with an appropriate epoxy such as Sikadur 32
Hi-Mod.
Warning IRRITANT, SENSITIZER. Contains Portland Cement (CAS 65997-15-1), Silica Quartz
(CAS: 14808-60-7). Causes eye irritation. May cause skin/respiratory irritation. Prolonged
and/or repeated skin contact may cause an allergic reaction/sensitization. May cause de-
layed lung damage (silicosis). May be harmful if swallowed.
Handling & Storage Avoid direct contact with eyes and skin. Wear chemical resistant gloves/goggles/cloth-
ing. Avoid breathing vapors. Use with adequate general and local ventilation. In absence
of adequate ventilation, use properly fitted NIOSH approved respirator. Wash thoroughly
after handling product. Store in a cool, dry, well ventilated area. Keep containers tightly
closed.
First Aid Eyes – Hold eyelids apart and flush thoroughly with water for 15 minutes. Skin – Remove
contaminated clothing. Wash skin thoroughly for 15 minutes with soap and water. In-
halation – Remove to fresh air. Ingestion – Do not induce vomiting. Dilute with water.
Contact physician. In all cases contact a physician immediately if symptoms persist.
Clean Up Wear chemical resistant gloves/goggles/clothing. In absence of proper ventilation use
properly fitted NIOSH respirator. Confine spill, collect using absorbent material and place in
properly sealed container. Dispose of excess product in accordance with applicable local,
state and federal regulations. DRAFT
WQTR No,
WPS No.
RP-3G -Siirl,c','vT W.:lder Nanre PABLO JESUS ROLC
Revision 90
Welder Id RP-3c-S[,,lf.\,rv
1-80:0982.1 n.r+^ 4{/7/rn{a
Welder Guralificaiisn Test Record
Page 1 of 'l
RP.3G-SMAlA/
Variables Reccrci Actual Values Used ln Qualification
Process (Table 4.10, item (2)) Sf\4AW
Transfer Mode (GMAW): Short-Cir. I Globular X
Type Manual 1,{ Machirre I Semi-Auto I
Number of Eiectrodes Single .xl Multiple [_-l
CurrenuPolanty AC il DCEP E DCEN fl
Position (Table 4.10, iteri (5)) 3G
Spray n
Auto I
Pulsed fl
Weld Progression: (Table 4,10, item (7)) Up
Backing fTable 4.10, Item (8)] Use Backing
Down Iixt
x
nConsunrablo lnse.t (G-I-AW)
Material/Spec. ,A36
Thickness (PIate): Groorre irr )
Fillet ( )
Thickness (Pipe/tu!:e): Groove (
Fillet (
Diameter(Pipe): Grccve( )NiA
Fillei ( ) l.t/A
Notes NOl.iE
Filler Nleial il3rrle 'i0, Ite,rr (.i))
Spec. A5,'ilA5.5
Class l!f_3
i:-Nc. F-4
Gas/Flux Type (Tabis 4
Othef hl/A
Use lnsert
to A1]6
)
)
.5/ C
I{/A
u4_*__
N/A
.10. ltenr ("i)) illa
Qualification Rarige
SMAW
Short-CircLiitittg,--l
Manual X fulachine
Single X l,4ultiple
AC fl DCEP X
ilat, Vertical, Horizonial
Globular X Spray l
tr Semi-Auio I Auto I
D
DCEI\I il Pulsed i_I
Up X Down X
With Backing X
With Insert I
GROUPl
Without Backing i-l
Without lnsert i .l
.]?5 ___
,t4J
4r4.
.12J_ -__
1A
.750 _
UNLII\JIITED
110____
UNLIiVIITED
in
in
in
in
AI.IY
U FJLIi\4II'EI]
UNLITVlITED
Elx1s,Ei.I.16,?Ii.1B,EXUq1r,i4{19:ril4{.t;_:L
E4i5,EIX16,!. IX1qJ:_II]iLijEII]_0:L ts X.{ji,Li! _
F'i io Fli
ViSUAL INSPECTIOI.J (4.3.i) .'r;r;4ptableYes
GLIIDED BEND TEST iii::STJLTS (4.30.5)
Type
FACE
ROOT
Fillet Test Results (4.3A.2.3 arrd 4.30.4.1)
Appearance N/A Fillet Size i'lll\.Macroetch N/,4.
Fracture Test Root Peneiration N/A Descripiron
lnspected By ALBERT l-iERMIDA Test No. 8l'_1c_:9t*4,{ OrganizationCOi,i'ill'JEl.ll-AL iVELDINO li\iSPE11 -i17120.'i3
RADIOGRAPHIC TEST RESuii I il (ri.3o a. i)
Film loentrfiiatio,,lio - {"*rI
lnierpieted By N/A
Ahertoil{Gfi*la Oi'ganization
i 'l'est No. RF-3G-SIIA'//
I
II Date
I
We, the undersigneci. c:ertifl; tni.i, tlre statements in tiris recorci are coirect arii ',irat the test ivelds were pi"eparrd, weldi:cl, anC
tested in accorc.ncewitfl lile requirenrents of secLion 4 of AI.iSi/A\rvS 1i.1, ( l0 )Structural Welding Code-Steel.
Manufacturer t-, C; i.j I' i i',1 t l.r'i ; i i . V/ E L D I i.j G I N S P F C 1" I O h,l r.utho'i:cciay /t"i!!!l,f fqllfiqA 9qryi u01o01I Daie 11iil2813
lli:rrt i ryp: _=--iResurt __
h^oo - irAJD i IrilPASS Ir--l-
N/A
sc1ru faotoota
oclE)trP.1rl,2ot5 119J413
ier AWS D1.1 /,O Gartner StudiosDRAFT
DRAFT
DRAFT
DRAFT
Project No.: 2110.2100049
Report No.: 354485
Date: May 26, 2023
8050 NW 77th Court · Miami, FL 33166 · P: 305.249.8434 · F: 305.249.8479
STRUCTURAL OBSERVATION REPORT No. SPECIAL-027
CN: GDZ Page 9 of 9
cc: 1 − Job Site; 1 − Client; 1
The Original of this Report was Signed and Impressed Sealed by the Above Registered Engineer in Accordance with Rule 21H-18.11, Chapter 471, Florida Statute
Roof steel framing preliminary on 05/26/23
Reviewed by:
Universal Engineering Sciences
Certificate of Authorization No. 00549
Carlos Naumann, P.E., S.I.
Florida Professional Engineer No. 18594
Florida Special Inspector No. 181
DRAFT