ELC-12-21-3284 11300 NE 2 AVEELECTRICAL LEGEND SYMBOL I DESCRIPTION 2O CEILING OUTLET FOR FIXTURE: '2' = CIRCUIT NUMBER, 'a' = SWITCH LEG. HOI WALL OUTLET FOR FIXTURE. HEIGHT TO BE VERIFIED WITH ARCHITECT AND/OR OWNER. Q L®J FLUORESCENT LIGHT FIXTURE WITH T-8 LAMPS AND ELECTRONIC BALLAST. I LIGHT FIXTURES ON EMERGENCY CIRCUIT ® TRACK LIGHTING. O LIGHTING FIXTURE DESIGNATION, REFER TO LIGHTING FIXTURE SCHEDULE EMERGENCY BATTERY TYPE LIGHT FIXTURE. ® 10T OUTLET FOR CEILING OR WALL MOUNTED EXIT FIXTURE, DARK AREA INDICATES FACE OF FIXTURE. -0I PENDANT LIGHT 0 RECESSED DOWNLIGHT b WALL MOUNTED LIGHT Q RECESSED DOWN LIGHT - PINSPOT 8 RECESSED DOWNLIGHT - WALL WASHER EXTERIOR STEP LIGHT TO BE MOUNTED 2'-0" A.F.F. OO SURFACE MOUNTED LIGHT so SINGLE POLE TOGGLE SWITCH 'a' = SWITCH LEG, MTD ® 48" A.F.F. S3 S4 SINGLE POLE TOGGLE SWITCH '3' = THREE WAY, '4' = FOUR WAY, MTD ® 48" A.F.F. SM MOTOR RATED SWITCH WITH THERMAL OVERLOAD ELEMENT, MTD ® 48" A.F.F. OR PER FIELD CONDITIONS. TTIMER SWITCH, MTD ® 48" A.F.F. OR PER FIELD CONDITIONS. SD DIMMER SWITCH, RATING PER LIGHTING LOAD REQUIREMENT, MTD ® 48" A.F.F. SINGLE POLE DOOR SWITCH DUPLEX GROUNDING RECEPTACLE, WALL MOUNTED +15" A.F.F., 125v., 15A. NEMA 5-15R EXCEPT AS INDICATED OTHERWISE. DUPLEX GROUNDING RECEPTACLE, ABOVE COUNTER. EXACT MOUNTING HEIGH` SHALL BE DETERMINED BEFORE ROUGHING -IN, UNLESS NOTED ON PLANS. DUPLEX GROUNDING RECEPTACLE WITH ONE SIDE SWITCHED, MTD ® 15" A.F.F. DUPLEX GROUNDING RECEPTACLE. GROUND FAULT INTERRUPTER, MTD ® 15' A.F.F. DUPLEX GROUNDING RECEPTACLE. GROUND FAULT INTERRUPTER ABOVE COUNTER 0 FLOOR MOUNTED RECEPTACLE, FLUSH TYPE. SINGLE GROUNDING RECEPTACLE, 125V., 20A., +15" A.F.F. NEMA 5-20R, UNLESS OTHERWISE NOTED. ® 2 POLE + GROUND, 3 WIRE, 250 V, 20 AMPS WALL MOUNTED RECEPTACLE OUTLET. DJ DISCONNECT SWITCH OR CIRCUIT BREAKER JQ FQJ CEILING OR WALL MOUNTED JUNCTION BOX, 4 INCHES SQUARE WITH BLANK COVER. ® 120/208 VOLTS LIGHTING AND/OR POWER PANEL (SEE PANEL SCHEDULE). P' 277/480 VOLTS LIGHTING AND/OR POWER PANEL (SEE PANEL SCHEDULE). OUTLET FOR EXHAUST FAN (FRACTIONAL HORSEPOWER). PROVIDE CONNECTION AS REQUIRED. �p AREA OF REFUGE CALL STATION PUSH-BUTTON SWITCH +48" A.F.F. O THERMOSTAT, +48" A.F.F. EXACT LOCATION SHALL BE VERIFIED IN FIELD. COORDINATE WITH MECH. CONTRACTOR. DH MAGNETIC DOOR HOLDERS PROVIDED BY ELECTRICAL CONTRACTOR CONTROLLED BY FIREALARM. ML MAGNETIC DOOR LOCK (12 VOLTS) TIED TO FIRE ALARM. OS OCCUPANCY SENSOR D FIRE DAMPER p CONTROL DAMPER CONTROLLED OUTLET AS PER FBC C405.7 AND ASHRAE 90.1.8.2. CONTROLLED OUTLETS SHALL BE (� BE MARKED WITH THIS SYMBOL TO IDENTIFY IT AS CONTROLLED. SD STANDALONE, 120V, INTERCONNECTED SMOKE DETECTOR WITH BATTERY BACKUP. D�D STANDALONE, 120V, INTERCONNECTED COMBINATION SMOKE AND CARBON MONOXIDE DETECTOR WITH BATTERY BACKUP. GFCI GROUND FAULT CIRCUIT INTERRUPTER DL/WL DAMP LOCATION / WET LOCATION W.P. INDICATES WEATHERPROOF ENCLOSURE. A.I.C.S. INDICATES AMPERES INTERRUPTING CAPACITY SYMMETRICAL. E.W.C. INDICATES ELECTRIC WATER COOLER. Aj REVISION #1. WHEN APPLICABLE. NOTE: NOT ALL SYMBOLS SHOWN ON THIS LEGEND ARE NECESSARILY REFLECTED ON PLANS. OUTDOOR NOTES 1. ALL JUNCTION BOXES EXPOSED TO THE OUTSIDE ATMOSPHERE SHALL BE WEATHERPROOF TYPE. 2. ALL RECEPTACLES ARE TO BE FLUSH MOUNTED, WHEN INSTALLED IN WALLS THOSE RECEPTACLES LOCATED WHERE EXPOSED TO THE OUTSIDE SHALL BE PROVIDED WITH A WET LOCATIONS (WL) TYPE COVER PER NEC, RECEPTACLES SHALL OF THE "GFCI" TYPE. THE RECEPTACLES SHALL BE PROVIDED WITH AN ENCLOSURE THAT IS WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. THESE RECEPTACLES SHALL BE LISTED AS WEATHER RESISTANT TYPE. 3. WHERE PVC UNDERGROUND RUNS ARE USED, RIGID GALVANIZED SHALL BE USED WHERE RACEWAY RISES THROUGH GRADE OR BOTTOM SLABS. PROVIDE PROPER ADAPTER FOR PVC TO METAL RACEWAY & PROVIDE CORROSION PROTECTION PER NEC ARTICLE 300-6. 4. ALL CONDUITS ARE TO RUN CONCEALED. IF NOT POSSIBLE, THEN THEY SHALL RUN AS INCONSPICUOUSLY AS POSSIBLE. WHEN RUNNING EXPOSED, THE ROUTING SHALL BE VERIFIED WITH LANDSCAPE ARCHITECT AND/OR PROJECT ARCHITECT. 5. ALL CONDUITS IN DECK AREAS ARE TO RUN ABOVE SLAB MEMBRANE EXCEPT FEEDER RUNS WHICH ARE TO RUN IN OR UNDER SLAB MEMBRANE. GENERAL NOTES 1 ALL CONDUIT RUN EXPOSED, CONCEALED IN MASONRY WALLS OR CONCRETE SLAB, BENEATH SLABS ON GRADE OR RUN UNDERGROUND SHALL BE IN PVC. MC CABLE ELECTRICAL METALLIC TUBING AND FLEXIBLE NON-METALLIC TUBING, AS PERMITTED BY THE CODES, MAY BE CONCEALED IN INTERIOR HOLLOW WALLS AND ABOVE SUSPENDED CEILINGS. ALL FITTINGS SHALL BE COMPRESSION TYPE AND WATERTIGHT FOR OUTDOOR AND UNDERGROUND INSTALLATIONS. POLYVINYL CHLORIDE (PVC) SCHEDULE 80 LISTED RACEWAY MAY BE IN ALL RUNS UNDERGROUND AND BENEATH AND IN GROUND SLAB PROVIDED SIZE IS SUFFICIENT TO ACCOMMODATE GROUND WIRE AND ADAPTERS ARE INSTALLED AT PVC TO METAL TRANSITIONS, WHERE RACEWAYS RISE THROUGH GRADE AND/OR BOTTOM SLABS. 2 ALL FEEDER'S CONDUCTORS TO BE COPPER WITH THHN INSULATION UNLESS OTHERWISE NOTED. ALL FEEDERS FOR LOADS 100A AND LARGER TO BE ALUMINUM. 3 ALL WIRES SHALL BE #12 AWG COPPER AND UNLESS SPECIFICALLY INDICATED OTHERWISE ON THE DRAWINGS ALL INSULATION SHALL BE TYPE THWN/THHN. (STRANDED WIRE SHALL NOT BE USED). 4 MANUFACTURERS' NAME AND CATALOG NUMBERS ARE USED TO DEFINE THE TYPE AND QUALITY OF EQUIPMENT AND MATERIAL. EQUAL ITEMS OF OTHER MANUFACTURERS ARE ACCEPTABLE PROVIDED THEY ARE APPROVED EQUAL OR BETTER IN THEIR QUALITY. 5 ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER, AND IN FULL ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. ALL APPLICABLE STATE AND LOCAL CODES, AND THE LOCAL UTILITY COMPANY REQUIREMENTS. 6 CONTRACTOR SHALL VERIFY NAMEPLATE RATINGS OF ALL EQUIPMENT FOR CORRECT SIZE OF OVERCURRENT DEVICES AND WIRING BEFORE ROUGHING IN. 7 CONTRACTOR SHALL VERIFY LOCATION OF ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTION AND THE EXACT CONNECTION REQUIREMENT OF EQUIPMENT WILL DETERMINE THE ACTUAL CONDUIT ROUTES. 8 CONDUIT ROUTINGS ARE SHOWN SCHEMATICALLY AND CONTRACTOR SHALL FOLLOW ROUTINGS AS CLOSELY AS POSSIBLE. HOWEVER, BUILDING CONDITIONS WILL DETERMINE THE ACTUAL CONDUIT ROUTES. 9 ALL ELECTRICAL RACEWAY PENETRATIONS THROUGH BUILDING FIREWALLS, PARTITIONS, FLOORS, OR CEILINGS SHALL BE ADEQUATELY SEALED WITH A FIRE RESISTANT SILICONE FOAM THAT MEETS OR EXCEEDS N.E.C. ARTICLE 300-21, MINIMUM HORIZONTAL SEPARATION BETWEEN BOXES ON OPPOSITE SIDES OF A FIRE RATED WALL SHALL BE 24 INCHES OR HAVE A UL FIRE SEALANT SURROUNDING THE PENETRATIONS. 10 WHERE WIRE SIZES ARE INDICATED ON THE PLANS FOR INDIVIDUAL CIRCUITS, THE INDICATED WIRE SIZE SHALL APPLY TO THE COMPLETE CIRCUIT UNLESS OTHERWISE INDICATED. 11 THE SHORT-CIRCUIT AVAILABILITY AT PANEL BOARDS SHALL BE LIMITED TO THE INTERRUPTING CAPACITY OF THE LOWEST RATED DEVICES. 12 TANDEM AND TIE BREAKERS WILL NOT BE ACCEPTABLE. 13 ALL MOTOR STARTERS FOR FANS, PUMPS, BOILERS, AIR CONDITIONERS, ETC., SHALL BE EQUIPPED WITH OVERLOAD PROTECTION IN EACH PHASE LEG. STARTERS FOR MOTORS RATED AT 75 HP OR LESS AT 480 OR 208 VOLTS, MAY BE ACROSS -THE -LINE TYPE. WHEN APPLICABLE, STARTERS FOR LARGER MOTORS SHALL BE AUTO -TRANSFORMER REDUCED VOLTAGE TYPE. 14 ALL EQUIPMENT FURNISHED WITH CORD SHALL HAVE MINIMUM LENGTH CORD INSTALLED WITH CORRECT OUTLET PLUG JACKS, ETC., AS REQUIRED FOR COMPLETE INSTALLATION OF EQUIPMENT. ALSO, WHEN APPLICABLE, RECEPTACLE SHALL BE FURNISHED TO MATCH ELECTRICAL EQUIPMENT SERVED BY IT. 15 ALL ELECTRICAL EQUIPMENT SHALL BE READILY ACCESSIBLE, LOCATED IN A CLEAN AND DRY LOCATION, AND BE PROTECTED FROM PHYSICAL DAMAGE. ALSO, A CLEAR WORKING SPACE SHALL BE PROVIDED AROUND EQUIPMENT TO COMPLY WITH N.E.C. 16 JUNCTION AND PULL -BOXES SHALL BE GALVANIZED CODE -GAUGE SHEET STEEL, WITH SCREWED ON COVER, NEMA 1, OF SIZES AND SHAPE TO ACCOMMODATE WIRING ACCORDING TO N.E.C. AND TO SUIT LOCATION. 17 JUNCTION AND PULL -BOXES SHALL BE SECURELY MOUNTED TO THE BUILDING STRUCTURE WITH SUPPORTING FACILITIES INDEPENDENT OF THE CONDUITS ENTERING OR LEAVING THE BOXES. BRACKETS, RODS HANGERS, BOLTS OR OTHER SUITABLE SUPPORTING METHOD MAY BE USED. 18 ALL JUNCTION AND PULL -BOXES SHALL BE ACCESSIBLE ALL THE TIME. 19 ALL INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED AS FOLLOWS: 120/208 V SYSTEM PHASE "A" BLACK PHASE "B" RED PHASE "C" BLUE NEUTRAL: WHITE GROUND: GREEN 20 ALL RESIDENTIAL UNIT'S 15 AND 20 AMP RECEPTACLES ARE TO BE TAMPER RESISTANT AS PER N.E.C. ARTICLE 406.12. 21 ALL RESIDENTIAL UNIT'S 15 AND 20 AMP RECEPTACLES ARE TO BE ARC FAULT 'TYPE AS PER N.E.C. ARTICLE 210.12. 22 BACK TO BACK RECEPTACLE OUTLETS BETWEEN UNITS, TO BE SEPARATED BY A METAL STUD AND, A MINIMUM DISTANCE OF 24" FROM EACH OTHER. 23 ALL ELECTRICAL BOXES IN THE DEMISING WALL SHALL BE INSTALLED WITH FIRE STOP PUTTY FOR SOUND CONTROL. 24 ALL LIGHTING SHALL COMPLY WITH THE F.B.C. 2017, 25 CORRIDOR OUTLETS SHALL BE AVAILABLE FOR TENANT USE FOR MAINTENANCE TO A/C EQUIPMENT THAT IS LOCATED IN CLOSETS IN THE COMMON CORRIDORS FOR A/C THAT SERVE THE TENANTS UNIT. NOTE: THE APPLIABLE CODES FOR THIS PROJECT ARE THE 2020 FLORIDA BUILDING CODE, ENERGY CONSERVATION, SIXTH ED. AND THE 2017 NATIONAL ELECTRICAL CODE. NOTES: 1. THE SCOPE OF WORK IS LIMITED TO PROVIDING BACK UP POWER TO REFRIGERATORS, NMR, COMPUTER, A/C UNIT AND AIR COMPRESSOR. THE BACKUP POWER WILL BE PROVIDED BY A 35 KW GENERATOR. AN A.T.S. WILL BE ADDED IN THE ROOM THAT EACH DEVICE THAT IS BEING PROVIDED WITH BACK UP POWER IS LOCATED. THE NORMAL POWER THAT CURRENTLY FEEDS THESE DEVICES IS TO REMAIN. 2. THE DEVICES THAT ARE BEING PROVIDED WITH BACK UP POWER ARE LOCATED IN MULTIPLE BUILDINGS. LOSS OF NORMAL POWER IN ANY OF THE BUILDINGS WILL CAUSE THE GENERATOR TO START AND THE DEVICES THAT LOST NORMAL POWER WILL TRANSFER TO THE GENERATOR. SCOPE OF WORK 1. INSTALL THE RELOCATED 35 KW THREE PHASE GENERATOR IN THE ADRIAN EXTERIOR CHILLER PLANT AREA. THE GENERATOR INCLUDES A WEATHER PROOF ENCLOSURE. (CUMMING POWER GENERATION QUIET SITE GENERATOR GGFD-56998200). 2. INSTALL NEW 100 AMPERE DISTRIBUTION PANEL "A" IN THE ADRIAN EXTERIOR CHILLER PLANT AREA. 3. INSTALL NEW ATS (20 AMPERE, THREE PHASE) FOR THE AIR COMPRESSOR LOCATED IN THE C.B.S. MAINTENANCE SHED. NORMAL POWER WILL REMAIN AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 4. INSTALL NEW ATS (20 AMPERE, SINGLE PHASE) FOR THE REFRIGERATOR LOCATED IN THE ADRIAN 101-B. THE NORMAL NORMAL POWER WILL REMAIN FROM PANEL LA AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 5. INSTALL NEW ATS (20 AMPERE, SINGLE PHASE) FOR THE REFRIGERATOR LOCATFD IN THE ADRIAN 104. THE NORMAL POWER WILL REMAIN FROM PANEL 16" LOCATED IN ANDRIAN 104-E AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 6, INSTALL NEW ATS (20 AMPERE, SINGLE PHASE) FOR THE NMR, A NEW ATS L-3 AMPERE, SINGLE PHASE) FOR THE COMPUTER LOCATED IN THE ADRIAN 105 AND A NEW ATS (20 AMPERE, SINGLE PHASE) FOR THE A/C LOCATED IN ADRIAN 105 THE NORMAL POWER WILL REMAIN FROM PANEL "L" LOCATED IN ANDRIAN 105 AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 7. INSTALL NEW ATS (20 AMPERE, SINGLE PHASE) FOR THE REFRIGERATOR LOCATED IN THE TWOHIG 110. THE NORMAL POWER WILL REMAIN FROM PANEL 12" LOCATED IN TWOHIG 110 AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 8. INSTALL NEW ATS (20 AMPERE, SINGLE PHASE) FOR REFRIGERATOR LOCATED IN THE WEIGAN 151, A NEW ATS (20 AMPERE, SINGLE PHASE) FOR REFRIGERATOR LOCATED IN THE WEIGAN 151. THE NORMAL POWER WILL REMAIN FROM PANEL "5" LOCATED IN WEIGAN 104E AND GENERATOR POWER WILL BE FROM THE Dl"s<IBUTION PANEL "A". 9. NEW ATS (20 AMPERE, SINGLE PHASE) FOR REFRIGERATOR LOCATED IN THE WEIGAN 234, A NEW ATS (20 AMPERE, SINGLE PHASE) FOR REFRIGERATOR LOCATED IN THE WEIGAN 134. THE NORMAL POWER WILL REMAIN FROM PANEL "E" LOCATED IN WEIGAN 234 AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL W. RFC ETN7FIn � EWU _§ MILAMI SHORES �u aMI-Ai APPROVED B t LIA E STRUCTURAL l ELECTRICAL sal II` PLUMBING MECHANICAL I I SUBJECT TO CO.MFUANC ` ALL 1 STATE AND COUNTY RULES AND RLS"''LA" . I 1 b, CITY COPY F NGINEERS Miami, FL33186 453 wew,oeengmeers.nom l BU Wei P.E., LEED® AP d&11/ No. 52146 Eduardo Ramos P E LE'W No. 56741 Gregory M. Jensen P E LE�'AP /// No. 63828 4 r i 7�nO'ji Seal of Project Engineer iiiii F � J � W 0 Z Z N�N Z 1./. W V W ui u d "o a` Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date 0 0 LEGEND, NOTES DIAGRAMMATIC POWER RISER Drawn By: XX Checked By: XX Job No: Scale: Sheet Number: LEGEND, NOTES AND POWER RISER N.T.S. T 1r' I a OUTDOOR NOTES ELECTRICAL LEGEND; 1. ALL 'JUNCTION 'BOXES EXPOSED TO THE OUTSIDE ATMOSPHERE SHALL',QE WEA ERPROOF'TYPE:� SYMBOL DESCRIPTION ,, ' 2. ALL RECEPTACLES ARE TO BE FLUSH MOUNTED, WHEN INSTALE.O; IN WALLS TOSE RECEPTACLES. " LOCATED WHERE EXPOSED TO THE OUTSIDE SHALL BE PROVIDED WITH A WET LOCATIONS (WL) TYPE COVER. WITH O CEILING OUTLET FOR FIXTURE: 2 = CIRCUIT NUMBER, a .•=..SWITCH LEG r e kl . PER NEC, RECEPTACLES SHALL OF THE GFCI TYPE. THE RECEPTACLES °,SHALL BE PROVIDED' AN THESE .. 2. Q . s ENCLOSURE THAT, IS WEATHERPROOF WHETHER OR NOT THE ATTACHMENT.PLUG CAE.IS.INSERTEO." FO � u WALL OUTLET FOR FIXTURE. HEIGHT TO BE VERIFIED WITH ..... _ ... ARCHITECT AND/OR"OWNER.. ., RECEPTACLES SHALL BE LISTED AS WEATHER RESISTANT TYPE. U... ® ic� .. ... FLUORESCENT LIGHT FIXTURE WITH 7-8 LAMPS AND ELECTRONIC BALLAST 3. WHERE PVC UNDERGROUND RUNS ARE USED, RIGID GALVANIZED SHALL BE USED WHERE RACEWAY RISES THROUGH GRADE OR BOTTOM SLABS. PROVIDE PROPER ADAPTER FOR ;PVC TO METAL RACEWAY'& PROVIDE LIGHT FIXTURES ON EMERGENCY CIRCUIT CORROSION PROTECTION PER NEC ARTICLE 300-6.. 4. ALL CONDUITS ARE TO RUN CONCEALED. IF NOT POSSIBLE, THEN THEY SHALL RUN AS'- TRACK LIGHTING. INCONSPICUOUSLY AS POSSIBLE. WHEN RUNNING EXPOSED, THE ROUTING_,SHALL BE VERIFIED WITH LANDSCAPEARCHITECT AND/OR PROJECT ARCHITECT. AO LIGHTING FIXTURE DESIGNATION, REFER TO LIGHTING FIXTURE SCHEDULE 5. ALL CONDUITS IN DECK AREAS ARE TO RUN ABOVE SLAB MEMBRANE, EXCEPT FEEDER' RUNS WHICH ARE P EMBRANE NOTES: 1. THE SCOPE OF WORK IS LIMITED TO..PROVIOING BACK UP POWER TO REFRIGERATORS, NMR, COMPUTER,A/C UNIT AND AIR COMPRESSOR THE BACKUP POWER WILL BE PROVIDED BY EMERGENCY BATTERY TYPE LIGHT FIXTURE, I TO RUN IN OR UNDtR SLAB M — , A 35 KW GENERATOR. AN A.T.S. WILL BE�ADDED IN THE ROOM OUTLET FOR CEILING OR WALL MOUNTED EXIT FIXTURE, DARK AREA INDICATES. FACE OF FIXTURE. THAT EACH 'DEVICE THAT IS BEING PROVIDED'WITH BACK UP �T POWER IS LOCATED. THE NORMAL POWER THAT CURRENTLY FEEDS THESE DEVICES IS TO REMAIN. {} PENDANT LIGHT 0 RECESSED DOWNUGHT V : WALL MOUNTED LIGHT 0 RECESSED : DOWN LIGHT' -' PIN SPOT.' e RECESSED DOWNLIGHT - WALL WASHER (�- EXTERIOR STEP LIGHT TO BE MOUNTED 2—Cr A.F:F. QO SURFACE MOUNTED 'LIGHT` . _ SINGLE POLE TOGGLE .SWITCH 'a' = SWITCH LEG; MTD 048" A.F.F�'' S3 S4 . SINGLE POLE TOGGLE SWITCH '3' = THREE WAY, '4' :,= FOUR::,WAY,'MTD ®48" A F F SM MOTOR RATED SWITCH WITH THERMAL OVERLOAD ELEMENT, MTD 048,, FF OR PER FIELD CONDITIONS. TIMER SWITCH, MTD ® 48"'A.F.F. OR PER FIELD CONDITIONS. SD DIMMER SWITCH, RATING PER LIGHTING LOAD REQUIREMENT, MTD ® 48,",A F.F. SINGLE POLE DOOR SWITCH V/ wDUPLEX GROUNDING RECEPTACLE; WALL M OUNTED .+157 A.F.F. 125v.' 15A•': NEMA ,. ..... ",5-15R;EXCEPT AS INDICATED' OTHERWISE.; t t. ,, DUPLEX RECEPTACLE,. ABOVE ;COUNTER. EXACT MOUNTING „L. IGHT SHALL- _ - _ _.... _ -.---- A BE DETERMINED BEFORE ROUGHING -IN, UNLESS NOTED ON RLANS. DUPLEX GROUNDING RECEPTACLE WITH ONE SIDE SWITCHED,: 'MTD ® 15"°AF:Pu E3= DUPLEX GROUNDING RECEPTACLE. GROUND FAULT INTERRUPTER, MTD - Vf5" A.F.F. DUPLEX GROUNDING RECEPTACLE. GROUND FAULT INTERRUPTER ABOVE OCINTER " 0 FLOOR MOUNTED RECEPTACLE, FLUSH TYPE. SINGLE GROUNDING RECEPTACLE, 125V., 20A., +15" A.F.F. NEMA 5-20R, UNLESS ,°' OTHERWISE NOTED. ® 2 POLE + GROUND, 3 WIRE,>250 V, 20�AMPS WALL MOUNTED RECEPTACLE OUTLET. Q I DISCONNECT SWITCH OR CIRCUIT BREAKER ' Q rtJ� CEILING OR WALL MOUNTED JUNCTION BOX, 4 INCHES SQUARE WITH BLANK _COVER. [� 120/208 VOLTS LIGHTING AND/OR POWER PANEL (SEE PANEL SCHEDULE) j� 277/480 VOLTS LIGHTING AND/OR POWER PANEL (SEE PANEL SCHEDULE). OUTLET FOR EXHAUST FAN (FRACTIONAL HORSEPOWER). PROVIDE CONNECTION AS REQUIRED. ❑p AREA OF REFUGE CALL STATION, PUSH-BUTTON SWITCH +48" A.F.F. Q THERMOSTAT, +48" A.F.F. EXACT LOCATION SHALL BE VERIFIED IN FIELD.' COORDINATE WITH MECH. CONTRACTOR. DH MAGNETIC DOOR HOLDERS PROVIDED BY ELECTRICAL CONTRACTOR CONTROLLED BY FIREALARM. ML MAGNETIC DOOR LOCK (12 VOLTS) TIED TO FIRE ALARM. OS OCCUPANCY SENSOR FIRE DAMPER. " 7y CD CONTROL DAMPER CONTROLLED OUTLET AS PER FBC C405.7 AND ASHRAE 90.1.8.2. CONTROLLED OUTLETS SHALL BE BE MARKED WITH THIS SYMBOL TO IDENTIFY IT AS CONTROLLED., s, STANDALONE, 120V, INTERCONNECTED -SMOKE DETECTOR WITH BATTERY BACKUP. D�U STANDALONE, 120V, INTERCONNECTED COMBINATION SMOKE AND CARBON,pMONOXIDE DETECTOR WITH BATTERY BACKUP. GFC! GROUND FAULT CIRCUIT INTERRUPTER DL/WL DAMP LOCATION / WET LOCATION c W.P. INDICATES WEATHERPROOF ENCLOSURE. w a A.I.C.S. INDICATES AMPERES INTERRUPTING CAPACITY SYMMETRICAL.' E.W.C. INDICATES ELECTRIC WATER COOLER. r4 QREVISION #1. WHEN APPLICABLE. �1MIREN"Bl'INEERS 12915 SW 132nd street Umt 1 Miami, FL 33139 P. 305.87D.0320 F. 305.233.9453 www.iwrenginaers.com Bul Wei PS, LEED® AP, CXA No. 52146 Eduardo Ramos P.E. LEED® AP No. 58741 Gregory M. Jenson P.E. LEEDO AP No. $3028 1�1 �3IfilPv`1r1 /,f .63t,. W 00 ��— `Z—• STATE ESP •:: 4 Seal of Project Engineer 1 > > o 0 oa a as a o . a>eaeo. o as aoaoa ' >eoaao a a > o oaoaoo »oa a >ana> > oDo» > a a ro a >o >n o�a.'> >a»o 0 a a a> o >Oaao > a > o o > aeaa> ooa»o a 2. THE DEVICES THAT ARE BEING PROVIDED WITH BACK UP .`POWER ARE LOCATED IN. MULTIPLE BUILDINGS. .LOSS OF,NORMAL POWER'IN ANY OF THE BUILDINGS WILL CAUSE THE GENERATOR TO START AND THE 'eA1 DEVICES THAT LOST NORMAL POWER WILL TRANSFER TO THE GENERATOR. vd a Z .SCOP E 'OE- WORK'' Q W w_ F THE 1. ' INSTALL THE RELOCATED 35 KW THREE PHASE GENERATOR IN THE ADRIAN'EXTERIOR CHILLER, PLANT AREA I, _ _ W GENERATOR INCLUDES' A WEATHER PROOF ENCLOSURE.. , {GUMMING POWER GFNERADON QUIET SffE GENERATOR GGFD 56998200). A 12. INSTALL NEW 100 AMPERE DISTRIBUTION PANEL "A" IN THE ADRIAN EXTERIOR CHILLER PLANT AREA: 3. INSTALL NEW ATS (20 AMPERE, THREE PHASE) FOR THE.AIR COMPRESSOR; LOCATED IN THE C.B.S. MAINTENANCE SHED. M NORMAL POWER WILL REMAIN AND GENERATOR POWER WILL BE:,FROM,�THE: 'DISTRIBUTION PANEL "A". W 4. INSTAL NEW ATS. (20 AMPERE, SINGLE PHASE) FOR THE REFRIGERATOR LOCATED IN THE ADRIAN 101-B, THE NORMAL NORMAL POWER WILL REMAIN FROM PANEL LA AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 5.:.INSTALL NEW ATS (20. AMPERE, SINGLE PHASE). FOR THE ;REFRIGERATOR. LOCATED IN THE ADRIAN 104. THE NORMAL POWER" " "' , - ' e .y„ y R WILL BE FROM THE -DISTRIBUTION PANEL REMAIN FROM .PANEL ,L6 LOCATED IN ANDRIAN 104-E AND, GENERAAR POWER „ 6. INSTALL NEW ATS (20 AMPERE, SINGI.L.Pi�XSalTOR rRE i.NMR, A NEWrA1S (20 `AMPERE, SINGLE PHASE)g. FOR'THE COMPUTER LOCATED IN THE ADRIAN:'.1'05. ANT`A NEW ATS`;(20 AMPERE,tSiNGLE.PHASE)-FOR`THE-A/C LOCATED IN-ADRIAN- '•. 105' THE NORMAL POWER WILL REMAIN FROM PANEL "L" COCA' ('"P�'ANDRIAN 105 AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A".' a' 7. INSTALL NEW ATS (20 AMPERE, SINGLE.PHASE) FOR ,THE: 'REFRIGERATOR -LOCATED IN":THE TWOHIG 110. THE NORMAL POWER WILL REMAIN FROM PANEL "L2" LOCATED IN TWOHIG 110 AND' --'GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL "A". 8. INSTALL NEW ATS (20 AMPERE, SINGLE PHASE) FOR REFRIGERATOR LOCATED IN THE WEIGAN:151, A NEW ATS (20 AMPERE, SINGLE PHASE) FOR REFRIGERATOR LOCATED IN THE WEIGAN 151. THE:;NORMAL POWER WILL REMAIN FROM PANEL "5" LOCATED IN WEIGAN 104E AND GENERATOR POWER WILL BE FROM THE DISTRIBUTION PANEL. 'A". ' 9 AN 234, A NEW ATS (20 AMPERE, SINATS GLE H NGLE PHASE) FOR EREFRGLERATOR LOCATED INE PHASE) FOR THEWEOIGAN 134.DTHErrTHE GNORMALPOWER WILL REMAIN FROM PANEL "E" aLL L ?7 LOCATED IN WEIGAN 234 AND GENE RATOR POWER WILL BE FROM THE.-11 PANEL ,"A". By , MIAMI SHO SS VILLAGE:° Date of Issue: APPROVED 8Y G11E 92-07.-2021. PERMIT ISSUE p. ,, gg ZONING "4 - 3 Rev No. Description Date, . 1 STRUCTURAL... ( Q _ I ELECTRICAL i PLUMBING. I. I h1PCHAI IC AL i k 1 BLDG. SUBJECT TO Cr,)MPLlANCE i,�CN ALL fti STATE AND COUNTY RULES A uND toEL`�ULA . LEGEND, NOTES DIAGRAMMATIC Lou LD W A ti POWER RISER T y 1' , a. ft N.W, 115th STREET N.E, 115th STREET - to BARRY UNIVERSITY / LC SHEET 3 / i N. E. 1 1 5th ST. .-.. - .. ... .. .... .. - .....,vT._ :h^➢ n :Y4 'ti ._-£. v.:wJ:. .v ". ..�.\ .\ h, '1a Y,, 1v _ } lV� :(, 77 SHEET 2 ---------------- FFFTTFMTFFTM - x — — i ..u: �:.>-r T""�-'.t,».�;^'<.-•"--'-�`F.'.-,.""1" r+:•.' - _.,.. _ / '% /� //. 11 / b I �_L-L`----_-�� •... ,-�{x�.• �.;� "�- /!;f ...-., �= N.W.1 :;ri,/ /� ty III r , CL SROOM✓FACULTY- k i Or CE RCunnea Z' r. ry_ LOCATION MAP: at Ai$GANn CENRRR L NOT TO SCALE m u I IIIL— � •. IE �. \ �.� f / _.- /%f /. /% % /f /i/'' ..r'. J .`._. ,_...........s .. r..::_.e '� ^ `c": w 0 /, � ,//;r/ it /, :•""� �- �., __ � � --fir/%i �- / \ < e�.i U j 4 r 51- g �I '%-; ' �i'/' /,, -/;r/ /,,//;'//,✓,.%,, ,,r,�'/ :. �.': \� x.a..H-.>-___ �, x :t, �,_:, �t a , ') �a{ o �K��� - r .i, +� \.cr W3a � + , / 1 •� ... \ f i/r ,W lr / ' s ,/ � J /.' , ," , , %r,�� J /,. / - r '; .4.;:. xtib--Y='n. -vi, a S`^ . -•''µ 1 i P � I //,//,W'� • s .'cS,� o, a�i ':: t� � i D6QP+i � " :, � �. �'"``�.�;�r` /✓� �°' z u II _ ..rc„ I .•. j/� /..' / 2�-�s*„"S``ii� %`' x°' I � � e9 t \' t t'\n,1 III ` .rff�/.r"'`rfj w.•iZx A.Ae�>. °- __ _ - -', }`'"` ' t \ E2 4 S, Ii 'J,/, ! �' Y, }(y-,sys,. • yr i�.�v cri'- > _—'�-_/' l� .�,3k'.^ ..,.......:..ti?.2 �' ( - .,,t ( • i I I ` j� ,� / ` l// L+'\tiw,ai.: .. . '*, .r .. 'rr` v"''�`* t-. .. -• I:b IVIxx I III��/ l/ % / 1 WN r`, r :J J //, .+ r `S; i n , i< �r s-1.. • 5 ,tx`.` III , %,/✓� /� %j "'�" ��t / : : v oI 'r � U t '�^ � �/ f� �/'✓/ ?!.� - l� i wi v.,Ji x .Yrcr' b` n 04 I �x1,. .g i�i � •'u =e r W `N • 1 05 a -a III'%,% • /� r ' I ,,�ii'/; '�%' ' j %' .� - �� 'r � �� °✓"' �>' -O "✓ % ` I +�, n � j�r�.w��\,A{ �, r��'�=_ �_ ��•. ».wr [z �� " °� f,/,�/!�0�y�, /ram/ /' � t n+me � v i �YL !///�/" �//` ,�•. '/ /°///'jf1;/f�/ I J°/ 1 .1-a.. IIII � f a ,% / /'J % / i - >an.+..'.. .v.- , s... ...k•' w,} - \ IIII f>` /'✓/�/'�jr.i,!/%/ r'/':'✓�, III, //; : / ✓'4. % ✓/./ , /.�// J // j r _,.j - j,.� ; /,r. \ IIII. I 'i'r'✓ /' . „ '., �- — .�.`:`�:. _._. � .'• / �%% I ,�, /f j ' �' ' sr� �>�'�i �`^/, '" ' � i ELEC7f; AL • ( I f ,, / : �.:_. �. ire �:r�i-� '*�"'. -=�z �/'-✓j �;,✓ - a,�c�' /' - REVIEW k IN t' � IIII � _' t a � ,/>''f,�/ i� ' ;_,/ J , � ,/ /,/✓ jam:%' ; j/' �;.'' '�'/�/ / g i' APPROvtC AYE III � � • - ti�� Jm/�O� i 4 f _ • � IIII r .� .. , .' ,, M \F �"` `;'�; {M er . IIII. I °/ /` I I �; ,,� � � I � /�//r+ �rr�i'/`�,, /,/ �I�'�f 1�/ �% -�.. � •v IIII ( / /�/� I I nJi. _ / ✓ � A - r ( � ,/�//,+ j / P /l ,✓ ° '/,�%J/0�/ ./ //fJ � � k' ly' � �/ � % J 1' � � � 1/"f/ I /`r '✓ j -s. c ` r r I � .. g / //r/!J'",/`� r,f -/,%r % // f ,//./A//�% s - � *r �. IIII /Vx, r IIII � / �/ �/-/,�� /� ' , � - I ' /,. /, , , / _ ,✓ �; � .�;� .� �� � - - -- { C t IIII —/' /✓ — — — — RarrRR "YOTTP" DOSS HALL { - - ' L III j Z- }'+ v';k 4 • N.E. 1 1 1 th ST_ ,;► - I IIII � IIN I I on SITE PLAN 3/16"=1'-0" 71MINENGINEERS 12915 SW 132nd Street Unit 1 Miami, FL33186 P. W5.67a.W20 F.3 .233.9453 w .t rengineer&com Bui Wei P.E., LEED® AR CxA No. 52146 Eduardo Ramos P E LEED ® APNo. 58741 Gregory M. ``TTI Q rl ® Uliq r'q +P No. M28 � � I I si�l®hPAL Seal of Project Engineer , , e••se •s • e• e • e e•e•ee •• r F , • 4 I"aaaa Cl) Ix SEMI ® Z Q W Z LLJ a .o d Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date SITE PLAN Drawn By: XX Checked By: XX Job No: Scale: Sheet Number: •I. X N.W. 115th STREET N.E. 115th STREET 71MIRENGINEERS LL (5,^+{� /p� (}-(^� }n� �y/ ` /r. R��+ 1I T Y P.3Cdi870.0820 P. 305233.9453 wNw.rxPengtneers.eom UTI71l , 1 UNIVERSITY l ! 'V ,�: %' i' ' l G Sul WelPE.. pARP.jC No. 52i41 n' �/i / '/// Eduardo Re(no�� I,EDwJAPIJ f No. 58741 % Grego%V 6 V E LEEpi��•P/J No. 63828 X. SHEET 3 VIM ec • P '. , r.; r , tv -y _ Y '1 Al 1 .,v:.•n s YanY• t r.Fy i .'h v i. _ L.eY `•s .- "n-""tea , . . •, 111 I� iv 1 a ,xy.c -0_ f. n`. '.•N. x:+,�,N,•y,:.,vy, 'rv. .: ,TT, ?Oi^r' 3v >.S C .IP J:.. '�' p SHEET I \7—�` \ \ \ \�` \, ' ' E, Seal of Project Engineer a J jr. , , r W > 1` II a � H+H+ I a / „ va�'�i ' �'' F:. rt'•.� ~x•"5 Z��"�"� ! ! f / y.//�r✓� / F t �idY ..4 . '/f/'fJJJ �'�'.. 1 p II / l r 2 y Il -m Pkb 0EG Att[ 3S [ PA4LML m �/ %F 17 % / J i. NO TO SCALEE AP: La f II� � ::.'".�L• "" ::rw, I K{ r„ > " % �/ i // � f'./� 1/ f� � � ./ � �✓� -./ / / r!' � 3 • ( � � aceoao 000amo Doom 00000a c ac o000 o / o c oc0000 / / •% �� V\� �\.\ / J /// /' // \ o e '(L.,.: �/a,.s/ "- cmca o Ell 1 O a emmo o moo oa CCOoea o0000m imams �(. I c-�/. .'Y,„„.} I ,r/ ,r JQ/� - \ �`\ ./ � •" ¢O ad co c c 'aa000 /ot/- � j/ / ocaaco O g I • „i. / / Vraat � /% �/ % / �'`: ' ' M�µl � � \\ a� I / � IGj�iS"� ... n C o x`•.//J/ / S- �',"T�.'<•s \ e'///'�'U.�Lr�.i.i�ryj/�� F✓r�•'/,Imy ' d �' « :'�S` \ . * ::'r: c o o a do r oo a e �l s'Y / / �!! r.L'i7i ;/ !/ Via,. .��✓� \ : \ �y _ : .. e m c moo c a Oa ¢ C O C a "�r*Cmc �I tl II ✓ ,. /. ^i•W.R✓ � � - j, .J f' ® �J.\.rv`\,„.. tf' � . \' � � � � � . i.■ ��� ,s __.. ooa000 k 'II /f !1'// 1.4���Iy • Y a - .. � W . \t �\ \v L V I I ' ...24.5 .,.i>, J \ 4ii.Y �i}Ct ,/, /�/ �� u.1 '+4 \ • r " I-5•' ,'r44 ePd .i, '�.. _•L%l •:-C"4 . T "Y' � � / / i I All. Iti. �•' .:'+;:' ChM vwnaai i. y{ �•�-, r a / 1 // / �tY�v.1 1 nuy �C i/ III13 � r e Ex LU I �� .•>�„-:4 ;.gin •; !�?�, �# /.�/// /%/ . /� ��� � � ': !I d _ I ♦t}�r�`:IM ?PM,'�, .. �'. .. • � ' ;I�j 'y'.$$ .ti,.f `\ t Y'',. '. - .. _ � � . _ . .. ., ... - . I', I h^a, v . yFhs. 2,a e.... 1 •�tiii,'4r4 ,Sf . . _.... .- .. .. -... _ ._ .. .. .. . _ ..... 1 - a II M, 5'+�.� vi ry,JT.(1 -. _.. L. ,.._ .. _. p . .. .. _ .. .. . l .. :;;'' dti- +,L �•. l .yx, l r , ^ . II 4 ,. „2�s' J,`,"„"�'• ,`-,°i< :. .; .,v. ; .. � .«,asnJy+;,:, � v''�' .� � .. ;� , r, . I— r> : •rL ? v e A O CTRtCAL RE . :�.t*fix • ` S- 1 , rn r ' APPRov viEw z t LLJ ✓ r "�'- w ®r' �gyt�'gIPI'��1I �� ror 11 / rv//// fill `_hm .:",ems," � � / / /'/ �'/ f.•'' � '^2 'a art,: ' � I' hl //,"`�// 'Se g"'� . d ^;r. ` L■i ,7 III . }r, °�^. tT f / � .,r' '.+.,-r+3�uT:rr, . _ u^.+ a. ..�i• 3 .. '. � T'ri:• J _ ti J i ±a w r P { e I t r. %f h• _M r ww I x , : .r, o-•.t .:'- Ar'L. r4,a,CJ'+ .,, N i .:.' r. r. _ ... ., ..t,,._r - - .. .. �j '.. ,.. j I - .. ._. -. i n . v .. Q+•v41a [ .F .., a. R:.♦.e !S . Y - � ' '. IF S. 1 •. i•t.. . ,. .. <._r r I� ,.. nS J..- "h ti: k: '� . ,,. .^:"a_, c+...... dr•.. t:,...p .7. �, ..,�,.. h,.w`" ... w //J// ,wY ams I I / �.,:,"I { ::s:r`;r.?:•i� a, ..�,�Py,. rr r:,-`...�.; 1♦. kx1x.••:a`•rµr :", ,+P, .. z ., r. :+ •. ;..:• }•., 'yMt:..•lsro, .:.g .. .. ,, ilw^. ,,.. u•tr: y" `ws`ei'.` ._. _- __ .. ..-, r• I ..o 4 - "rc i III l a\ e s .,::. _ .�-^:..'< g[{ .a;; •r _ 1_ .:� , ,yj +�."»''• ` 4 C ";i: , rr; . u .•:.R.„t"W l� Y :-:�..., .;K' �"'' ^ R. ' n: ' r Z • •r I II tlo � • \ ,l1 �/////// `r :Y„ ,ti3H�i" �` I 1• `'+�,ei � s % / 5 i 1 low • I if//i // / /i� � y '.•�"V,yta'?�^".•d - • �i-r,_rt'1•.`Y jla }4F4 ?. � Cw "'c` / �rf 1 I w^ I, NI I Ll / n•l: —L I IIAi i rr L ' A. �e III' ,. ;- , P V"4.: .• : ' .. r , •..p M' "�.; Q,. Nr• N I. ,� I i �' %"?in 4 i!(♦ 1- nliX • •J }', ii.. �'/. 'P� _ .. i 9 u Date of I se: 12-07-2021 , Y , r .. .. ._.. _ �, .� f �� :z-:.:,: � :•., .,; •� �.�.: - PERMIT ISSUE � 11 '� � „.•e�„-' ,.�--,.F� , .j a_a °.� ., J - I ..,% /// L — �':•^�: — f '�, % � I —ear:. � / /'�. �°� � `' :,.��• ,rt i:: Rev No: Description Date I/� / .,�-. ,. i..P • a :ht•. j � y'✓dry. .,.. �... my. ... i4 7 y !tf ti , NI 'dlSlil '. vr�•'i ■ L- �.L / 'Y P i[LLl L / •. a?"='S Y I Ii f' 4 IN it 0 NII 9 ,..a.-',+L. n4 t•.u�ti¢i:x`' . ^ is )r`...?.�Y.r ;y ti�a t U'•:`a:', r^}`.i- � x �� NII �_, ..;�• _ - �..�" ' S : INII NIL .. INI I � �/ � f % � ' r a ��'�/ •S,:F.t'v: ••„E. svr-ixi�.t`�\a''_`, ?k •. - ]d. W SITE PLAN fuel""�i I �f---------- — — — — — — .. .. Drawn By: XX NN XX IIII Checked By: Job No: ,Scale: ADRIAN HALL 1 SCALE:N.T.S. ADRIAN HALL 4 SCALE: N.T.S. E2 ADRIAN HALL r2 SCALE:N.T.S, E2 77 1 P9 r� TWOHIG 3 SCALE: N.T.S. E2 WIEGAND 6 SCALE: N.T.S. E2 ETI lMl IR ERGIHEERS 12915 SW 132nd Street Unit 1 Miami, FL 33166 P. 305.670.0820 F. 305.233.W3 w .Wrengineersxom Bui Wei P.E., LEEDO AP, CxA No. 52146 Eduardo Ramos P.E., LEEDO AP No. 58741 Gregory M. J `'`r` `Et LEED OAIP j No. 63828 ' U1 FENS 0 2 6f7 ,n •• STATE of 1j1111110 Seal of Project Engineer r � J � J � = o Z Q LU p! Z ^� W li Q M� W N F- U d O 1 IL Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date L A SITE PLAN [Drawn XX XX Scale: Sheet Number: TWOHIG 5 SCALE: N.T.S. Q2 Lami Dade .22010668 -2A-041420.._ . r _ Kaminer Date Time Stamp Trade Stamp Name IMIRENGINEERS 12815 SW 132n> Street Unit 1 Mloml, FL 33185 P. 305.870.0820 F. 305233.5453 www.lwrengineers.cam Sul Wel P.E., LEED® AP, CxA No. 52148 Eduardo Ramo i�E.j 11E�e' *APIt� No, 53741 Gregory M`\e.QV P,S.eLEEOt AWlr Ne.53E28 0 ii :Y9 • • °��`.p"r�i EN t � ®.5w28 jj r Seal of Project Engineer O O a ^JOOOO o a � 0 O 0 00 0 00 > > a o o>o>ea o oa a o 0 000a o o > a 000000 oo>e o � ooe000 0000 > o 0 0 > ao » oe a oo>ooe o o e o > o o> o 0 o e 0 o e >a 0 0 o o> > o a r 000eoo 0 Fm I— z W .® ry_I S �. Q I m F� v to p 0.. Date Of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date SITE PLAN Drawn By: 7dxxx Checked By: Job No: Scale: Sheet Number: SERVICE 30, 4W MAIN BUS 125 AMP CU D I S TI B U TI O N PANEL A VOLTAGE 120/208V NEUTRAL 125 AMP CU NEW MAIN BKR 100 A MCB NEMA 3R L❑CATI❑N: ADRIAN CHILLER YARD CKT, NUM, EQUIPMENT PROTECTED LOAD KVA VOLTS POLE BREAKERS WIRE AND CONDUITS A.I,C TRIP 1 AIR COMPRESSOR 3.9 208 3 22K 20 4#10 THHN/THWN CU IN 3/4' C. 2 REFRIGERATOR ADRIAN 1018 1.9 120 1 22K 20 3#10 THHN/THWN CU IN 3/4' C. 3 REFRIGERATOR ADRIAN 104 1.0 120 1 22K 20 3#10 THHN/THWN CU IN 3/4' C. 4 NMR ADRIAN 105 1.9 208 2 22K 30 4#8 THHN/THWN CU IN 3/4' C, 5 COMPUTER ADRIAN 105 119 208 2 22K 20 4#10 THHN/THWN CU IN 3/4' C, 6 A/C ADRIAN 105 1.4 208 2 22K 20 4#10 THHN/THWN CU IN 3/4' C. 7 REFRIGERATOR TWOHIG 110 1.0 120 1 22K 20 3#10 THHN/THWN CU IN 3/4' C. 8 REF/FREEZER WIEGAN 151 0.7 120 1 22K 20 THHN/THWN CU IN N 3/4' C. 9 REF/FREEZER WIEGAN 151 0.7 120 1 22K 20 3#10 THHN/THWN CU IN 3/4' C. 10 FREEZER WIEGAN 234 110 120 1 22K 20 3#10 THHN/THWN CU IN 3/4' C. 11 COLD PREP ROOM WEGAN 234 2.0 208 2 22K 20 4#10 THHN/THWN CU IN 3/4' C. 12 SPACE -- 208 3 22K TOTAL 17.4 FEEDER, SEE RISER AND RISER NOTES 17.4 KVA/(208X1,73)V = 48.3 AMPS MAIN BUS; 225A SERVICE; 120/208V, 30, 4W PANEL L POLES; 42 MAIN BKR1 M,L,❑, EXISTING L❑CATI❑N, ADRIAN 105 A.I.C. 22K K.V,A, TRIP POLE CON- DUIT WIRE REMARKS CKT NO. CKT. NO. REMARKS WIRE CON- DUIT TRIP POLE K.V.A. 1.0 1/20 1/2 #12 EXISTING 1 2 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 3 4 EXISTING #12 1/2 1/20 0.8 110 1/20 1 1/2 #12 1EXISTING 5 1 16 EXISTING #12 1/2 1/20 1.2 1.0 1/20 1/2 #12 EXISTING 7 8 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 9 10 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 11 12 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 13 14 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 15 16 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 17 18 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 19 20 EXISTING #12 1/2 1/20 1.0 110 1/20 1/2 #12 EXISTING 21 22 EXISTING #12 1/2 1/20 1.0 110 1/20 1/2 #12 EXISTING 23 24 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 251 1 26 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 27 28 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 29 30 EXISTING #12 1/2 1/20 110 1.0 1/20 1/2 #12 EXISTING 31 32 EXISTING #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 33 34 AC MAGNET #14 1/2 2 0.7 110 1/20 1 1/2 #12 EXISTING 35 36 AC MAGNET 15 0.7 1.9 2 1/2 #10 NMR VIA UPS 37 38 SUPERCONDUCTOR MAGNET #12 1/2 2 1.0 1.9 30 -- -- NMR VIA UPS 39 40 SUPERCONDUCTOR MAGNET 20 1.0 -- -- -- -- SPACE 41 42 EXISTING #12 1/2 1/20 1.0 21.8 21.8 KVA + 20,4 KVA = 42.2 KVA 20.4 42,2 KVA/(208V A 1.73) = 117.7 AMPS FEEDER; EXISTING TO REMAIN (1) (1) NMR ADRIAN 105 (2) AC MAGNET ADRIAN 105 (3) SUPERCONDUCTOR MAGNET ADRIAN 105 SERVICE; 120/208, 30, 4W PANEL E MAIN BUS; 125A POLES: 30 MAIN BKR1 50A L❑CATI❑N; WEIGAN 234 EXISTING A.I.C. 22K K,V,A, TRIP POLE CON- DUIT WIRE REMARKS CKT NO. CKT. NO, REMARKS WIRE CON- DUIT TRIP POLE K.V.A. 1.0 2 1/2 #12 COLD PREP ROOM 1 2 EF9 AND EF7 #12 1/2 1/20 1.0 110 20 COLD PREP ROOM 3 4 DUCT SMOKE DETECTOR #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 REFRIGERATOR RM 234 5 6 SOLENOID VALVE #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 ICE MAKER RM 234 7 8 DEIDNIZATION WATER RECEPT. #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 REFRIGERATOR RM 234 9 10 SPACE -- -- -- -- 1,0 1/20 1/2 #12 HOOD RM 234 11 12 SPACE -- -- -- -- 1.0 1/20 1/2 #12 HEF1 RM 234 13 14 SPACE -- -- -- -- 1.0 1/20 1/2 #12 HEF2 RM 234 15 16 SPACE -- -- -- -- 1,0 1/20 1/2 #12 HEF3 RM 234 17 18 SPACE -- -- -- -- -- -- -- -- SPACE 19 20 SPACE -- -- -- -- -- -- -- -- SPACE 21 22 SPACE -- -- -- -- -- -- -- -- SPACE 23 24 SPACE -- -- -- -- -- -- -- -- SPACE 25 26 SPACE -- -- -- -- -- -- -- -- SPACE 27 28 SPACE -- -- -- -- -- -- -- -- SPACE 29 30 SPACE -- -- -- -- 9,0 9.0 KVA + 4.0 KVA = 13.0 KVA 4.0 13.0 KVA/(208X1.73)V = 36.1 AMPS FEEDER; EXISTING TO REMAIN (2) (2) (3) (3) SERVICE; 120/208, 30, 4W PANEL L 2 MAIN BUS; 125A POLES; 18 MAIN BKR1 100A L❑CATI❑N, TW❑HIG 110 EXISTING A,I,C, 22K TRIP CON- WIRE REMARKS CKT CKT. REMARKS WIRE CON- TRIP K.V.A. K,V,A. POLE DUIT NO. NO. DUIT POLE 1.7 2 3/4 #10 CU-1 1 2 LAB EQUIPMENT #12 1/2 1/20 018 1.7 30 CU-1 3 4 HEF-8 #12 1/2 1/20 1.6 2.2 2 3/4 #10 AHU-1 5 6 POWER POLE #12 1/2 1/20 0.8 2,2 25 AHU-1 7 j8 POWER POLE #12 1/2 1/20 018 1.2 1/20 1/2 #12 HEF-4 9 10 LOAD CENTER E #8 3/4 3 4.3 1.3 1/20 1/2 #12 HEF-5 & EF-8 11 12 LOAD CENTER E 4.3 1.0 1/20 1/2 #12 REFRIGERATOR 13 14 LOAD CENTER E 50 43 1.6 1/20 1 1/2 1 #12 ICOMPUTER 15 16 SPACE -- -- -- -- 0.6 1/20 1 1/2 1 #12 1 EXT. RECEPTACLES 17 18 SPACE -- -- -- -- 13.5 13.5 KVA + 16.9 KVA = 30.4 KVA 16.9 30,4 KVA/(208X1,73)V = 84,4 AMPS FEEDER, EXISTING TO REMAIN (1) REFRIGERATOR IN TWOHIG 110 (1) COLD PREP ROOM WIEGAN 234 (2) ICE MAKER WIEGAN 234 SERVICE; 120/208, 30, 4W PANEL 5 MAIN BUS; 125A POLES, 12 MAIN BKR; M,L.O, EXISTING A,I,C, 22K L❑CATI❑N; WEIGAN ELECTRIC ROOM 104E TRIP CON- WIRE REMARKS CKT CKT. REMARKS WIRE CON- TRIP K.V.A. K,V,A, POLE DUIT N0, NO. DUIT POLE 110 2 1/2 #10 HOOD RM 151 1 2 REFRIGERATOR #12 1/2 1/20 0.7 1.0 25 HOOD RM 151 3 4 REFRIGERATOR #12 1/2 1/20 0.7 1.0 1/20 1/2 #12 NEW FUME HOOD 5 6 S. WALL OUTLET #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 LAB TABLE 151 7 8 N, WALL OUTLET #12 1/2 1/20 110 1.0 1/20 1/2 #12 LAB TABLE 151 9 10 DUCTLESS 102 #12 1/2 1/20 1.0 1.0 1/20 1/2 1 #12 LAB TABLE 151 Ill 12 DUCTLESS 102 #12 1/2 1/20 1,0 6.0 6.0 KVA + 5,4 KVA = 14.4 KVA 5.4 14,4 KVA/(208X1,73)V = 40,0 AMPS FEEDER; EXISTING TO '.EMAIN (1) REFRIGERATOR WIEGAN 151 (2) REFRIGERATOR WIEGAN 151 PANEL SCHEDULES ELEC I RICr\L Fli-VIEV\/ III APPROVED% :1) (2) (1) SERVICE: 120/208V, 30, 4W PANEL LA MAIN BUS, 225A POLLS: 42 MAIN BKR1 M,L.❑, EXISTING L❑CATI❑N: ADRIAN 101B A.I.C. 22K K.V.A. TRIP POLE CON- DUIT WIRE REMARKS CKT NO. CKT. NO. REMARKS WIRE CON- DUIT TRIP POLE K,V,A, 1.0 3 1/2 #12 SEWAGE SUBMERSIBLE PUMPS PANEL 1 2 LIGHTS ANATOMY #12 1/2 1/20 1,0 1.0 SEWAGE SUBMERSIBLE PUMPS PANEL 3 4 LIGHTS #12 1/2 1/20 0.8 110 20 SEWAGE SUBMERSIBLE PUMPS PANEL 5 6 LIGHTS EXTERIOR #12 1/2 1/20 1.2 0.9 1/20 1/2 #12 EF101A & EF101B 7 8 DEMONSTRATION TABLE #12 1/2 1/20 0.6 1,0 1/20 1/2 #12 OFFICE RECEPTACLES 9 10 STUDENT TABLE RECEPTACLE #12 1/2 1/20 1.8 1.0 1/20 1/2 #12 ❑FFICE RECEPTACLES 11 12 STUDENT TABLE RECEPTACLE #12 1/2 1/20 0.8 1.9 1/20 1/2 #12 GENERAL PURPOSE RECEPTACLES 13 14 STUDENT TABLE RECEPTACLE #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 DIONIZED WATER SYSTEM 15 16 COUNTERTOP RECEPTACLE #12 1/2 1 1/20 0.7 1,1 1/20 1/2 #12 ROOF AND EXT. RECEPTACLES 17 118 COUNTERTOP RECEPTACLE #12 1/2 1/20 0.7 1.1 1/20 1/2 #12 ANATOMY LAB STORAGE RECEPTACLE 19 VACUUM PUMP #12 1/2 3 1.0 1.1 1/20 1/2 #12 EF101 & EF103 21 #24 VACUUM PUMP 1.0 -- -- -- -- SPACE 23 VACUUM PUMP 20 1,0 1,1 1/20 1/2 #12 PODIUM RECEPTACLE 25 26 AIR COMPRESSOR #12 1/2 3 LO 0.6 1/20 1/2 #12 FIRE ALARM BOOSTER 27 28 AIR COMPRESSOR 1.0 -- -- -- -- SPACE 29 30 AIR COMPRESSOR 20 1,0 -- -- -- -- SPACE 31 32 SPACE -- -- -- -- -- -- -- -- SPACE 33 34 SPACE -- -- - -- -- -- -- SPACE 35 36 SPACE -- -- -- -- -- -- -- -- SPACE 37 38 GAS WATER HEATER #12 1/2 1/20 0.2 -- -- -- -- SPACE 39 40 SPACE -- -- -- -- -- -- -- -- SPACE 41 42 SPACE -- -- -- -- 5,0 5.0 KVA + 1.0 KVA = 6.0 KVA l.o 6.0 KVA/(208V )K 1.73) = 16.7 AMPS FEEDER; EXISTING TO REMAIN (1) REFRIGERATOR IN ADRIAN 101-B SERVICE; 120/208V, 30, 4W PANEL L 6 MAIN BUS+ 225A P❑LES+ 42 MAIN BKR1 175A EXISTING A.I.C. 22K L❑CATI❑N: ADRIAN ELECTRIC ROOM 104E SECTION ONE K.V.A. TRIP POLE CON- DUIT WIRE REMARKS CKT NO, CKT. N0, REMARKS WIRE CON- DUIT TRIP POLE K.V.A. 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 1 2 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 3 4 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 1 #12 FLOOR RECEPTACLES RM 104 5 6 FLOOR RECEPTACLES RM 101 #12 1 1/2 1/20 1 1.0 110 1 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 7 8 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 9 110 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 11 12 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 13 114 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 15 16 FLOOR RECEPTACLES RM 101 #12 1 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 17 18 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 19 20 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 21 22 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 23 24 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 25 26 FLOOR RECEPTACLES RM 101 #12 1 1/2 1/20 110 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 27 28 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 29 30 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 31 132 IFLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 33 134 IFLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 35 36 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 37 38 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 39 40 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 41 4 2 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 21.0 21.8 KVA + 20.4 KVA = 42.2 KVA 21,0 42.2 KVA/(208V w 1.73) = 117.7 AMPS SEE SECTI❑N TWO SERVICE; 120/208V, 30, 4W PANEL L� 6 MAIN BUS; 225A POLES: 42 MAIN BKR; 175A L❑CATI❑N: ADRIAN ELECTRIC ROOM 104E EXISTING A.I.C. 22K SECTION TWO K.V.A. TRIP POLE CON- DUIT WIRE REMARKS CKT NO. CKT. NO, REMARKS WIRE CON- DUIT TRIP POLE K.V.A. 1.0 2 1/2 #12 SPECIAL RECEPTACLE 43 44 FLOOR RECEPTACLES RM 104 #12 1/2 1/20 1.0 1.0 30 SPECIAL RECEPTACLE 45 46 HUT OFF FOR GAS VALVES #12 1/2 1/20 0.2 110 2 1/2 #12 SPECIAL RECEPTACLE 47 48 EF-IL #12 1/2 1/20 1.2 1.0 30 SPECIAL RECEPTACLE 49 150 1 EF-21L #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 CRISTAT UNIT 51 52 SF-1 #12 1/2 1/20 1.0 -- -- -- -- SPACE 53 54 MOTORIZED DAMPERS #12 1/2 1/20 0.5 -- -- -- -- SPACE 55 56 SPACE -- -- -- -- -- -- -- -- SPACE 57 1 58 SPACE -- -- -- -- -- SPACE 59 60 SPACE -- -- -- -- -- -- -- -- SPACE 61 62 SPACE -- -- -- -- -- -- -- -- SPACE 63 64 SPACE -- -- -- -- -- -- -- -- SPACE 65 66 SPACE -- -- -- -- -- -- -- SPACE 67 68 SPACE -- -- -- -- -- -- -- -- SPACE 69 70 SPACE -- -- -- -- -- -- -- -- SPACE 71 72 SPACE -- -- -- -- -- -- -- -- SPACE 73 174, SPACE -- -- -- -- -- -- -- -- SPACE 75 1761 SPACE -- -- -- -- -- -- -- -- SPACE 77 78 SPACE -- -- -- -- -- -- -- -- SPACE 79 80 SPACE -- -- -- -- -- -- -- -- SPACE 81 82 SPACE -- -- -- -- -- -- -- -- SPACE 183 84 SPACE -- -- -- -- 5.0 21.0 KVA + 21.0 KVA + 5.0 KVA + 4.9 KVA = 51.9 KVA 4.9 51,9 KVA/(208V w 1.73) = 144,2 AMPS FEEDER; EXISTING TO REMAIN a IMIRENSINEERS 12915 SW 132nC Street Unit i Miami, FL33186 P. 305.6700820 F. 305233.9a53 w ,Mmngmeemimm Bui We, P.E., LEED® AR CxA No. 52146 Eduando Ramos P. ORCI(v No. 58741 Gregory M. J�r�9e� E_,�E QT,My// f No.63828 0����ORID1" Seal of Project Engineer Cl) J � = 0 Z Q W Z I.L Q MQ W ei u m .o a` ra -2021 ISSUE ption Date PANEL SCHEDULES Drawn By: XX Checked By: XX Job No: F N.T.S. (1) REFRIGERATOR IN ADRIAN 104 (1) .SERVICE 30, 4W MAIN BUS 125 AMP CU DISTIBUTION, PANEL,� VOLTAGE 120./208V A NEUTRAL 125 AMP CU NEW NEMA 3R MAIN 13KR 100 A MCB. LOCATION: ADRIAN CHILLER YARD CKT. NUM, EQUIPMENT PROTECTED LOAD KVA VOLTS POLE BREAKERS WIRE A.I.0 TRIP AND CONDUITS I AIR COMPRESSOR 3.9 208 3 22K a, 4#10 THPN/THWN CU IN 3/4' C. 2 REFRIGERATOR ADRIAN 101B 119 120 1 22K 20 3#10 THHN/THWN CU - IN 3/4' C. 3 REFRIGERATOR ADRIAN 104 110 120 1 22K 20 3#10 THHN/THWN CU IN 3/4' a ____4--NMR_­ADRIAN__1_O5___ - ----- -- 808-- '22K 3 . 0 . 4#8- THHN/THWN-CU­ IN 3/4' C. COMPUTER ADRIAN 105 1.9 208 2 22K K 20, 4#10 THHN/THWN CU .5�1_ IN 3/4' Cj 6 A/C ADRIAN 105 1.4 208 2 22K 20 4#10 THHN/THWN CU IN 3/4' C. 7 REFRIGERATOR TWOHIG. 110 to 120 1 1 22K 2) 0 3#10 THHN/THWN CU 1. 1 IN 3/4' C. 8 REF/FREEZER WIEGAN 151 0.7 .420 1 22K 26, 3#10 THHN/THWN CU IN 3/4' C. 9 REF/FREEZER WIEGAN 151 OJ 120 1 22K 2.0 3#10 THHN/THWN CU IN 3/4'- C. 10 FREEZER R WIEGAN 234 110 120 1 22K cg 3#10 THHN/THWN CU IN 3/4' C, 11 COLD PREP ROOM VEGAN 234 210 208 a 22K all 4#10 THHN/THWN CU : IN 3/4' C. 12 SPACE 208 3 22K T� TOTAL 17.4 FEEDER, SEE RISER AND RISER NOTES 17,4 KVA/(208XL73)V4 483 AMPS SERVICE, 120/208V, 30, 4W MAIN BUS, 225A . PANEL POLES: 48 EXISTING MAIN BKR, M,L,D,, LOCATION, ADRIAN 105 4 A,I,C, 22K K,V.A. TRIP POLE CON -:WIRE DUIT REMARKS CKT NO, ICKT ;[ Nd! REMARKS-' WIRE CON- DUIT TRIP POLE K.V.Al 110 1/20 1/2 #12 EXISTING 1 2 EXISTING 412 1/2 1/20- 110 .110 1/20 112 #12 EXISTING 3 4 EXISTING #12 1/2 1/20 018 110 1/20 112 #12 EXISTING 5 617, EXISTING #12 1/2 1/20 1.2 LO 1/20 1/2 #12 EXISTING 7 8 EXISTING #127l/2 1/20 1,0 110 1/20 1/2 #12 EXISTING 9 10 EXISTING #12 1/2 1/20 110 110 1/20 1/2 #12 EXISTING 11 12 EXISTING #12 1/2 1/20 110 110 1/20. 1/2 #12 EXISTING 13 14 1 EXISTING #12 1/2 1/20, 110 1,0 1/20 1/2 - #12 EXISTING 15 16, rEXISTING 1,41, #12 1/2 1/20 110 1.0 1/20 1/2 #12 EXISTING 17 18 EXISTING. *12 1/2 1/20 ilo 110 1/20 1/2 #12 EXISTING 19 20 EXISTING d, #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 EXISTING 21 22 EXISTING #12 1/2 1/.20 1.0 1.0 1/20 1/2_--_#12_-EXISTING 23 24__EXIS-TING:.. . #12- 7-,­1/2­_- 1/20 110 1/20 l/2 ' #12 EXISTING, 251. 26 EXISTING #12 /27 11/20 1.0 1.0 1/20 1/2- #12, EXISTING:. -27 128 EXISTING #12 1/2 1/20 LO 1.0 1/20 1/2 #12.- EXISTING 29 30 EXISTING #12 1/2 1120 1.0 1.0, 1/20 1/2 #12 EXISTING 3 jr 32 EXISTING #12 l/a 1/20 110 1.0 1/20 1 112 #12 EXISTING 33 34 AC MAGNET 1/2 0.7 1.0 1/20 1/2 #12 EXISTING 35 36 AC MAGNET _#14 1; �,Z5 0.7 119 2 1/2 #10 NMR VIA UPS 37 1.38: S SU I cSUPERCONDUCTIIR MAGNET #12 1/2 2 1.9 30 NMR VIA UPS 39 9 1,40 t2�EkISTING 7 SUPERCONDUCTOR MAGNET 20 1,0 ISPACE. 41 ; #12.. 1/2 1/20 l'O 2i.8 KVA + 20;4 KV4�,:" .42,2 KVA 20,4 42,2 KVA/(208V )r,1,7:J",:= 117,7 ;AMPS FEEDER: EXISTING TO,. REMAIN U) NMK AJJKIAN 105 (2) AC MAGNET ADRIAN 105 (3) SUPERCONDUCTOR MAGNET ADRIAN 105 SERVICE, 120/208, 30, POLES: 18 LOCATIONi TWOHIG 110 4W P,A N EIL L2-.- EXISTING MAIN MAIN AJ.C, BUS:' 125A BKRi 100A 22K K,V,A, TRIP POLE CON- DUIT WIRE - REMARKS CKT NO, CKT, REMARK;S WIRE CON- DUIT TRIP POLE K.V.A. 1,7 2 �3zo 3/ #10 CU-1 1 2 LAB EQUIPMENT' #12 1/2 1/20 0.8 1.7 CU-1 3 4 HEF-8 #12 1/2 1/20 1,6 2.2 2 3/4-- #10 AHU-1 5 1 16 POWER POLE #12 1 1/2 1/20 Ole 2,2 /25 - AHU-1 7 IS POWER POLE #12 1/2 1/20 018 1.2 1/20 1/2 #12 HEF-4 9 110 LOAD CENTER' E. #8 3/4 3 4.3 1.3 1/20 1/2 #12. HEF-5 & EF-8 11 112 LOAD CENTER L 4.3 1.0 1/20 1/2 #12 REFRIGERATOR 13 114 LOAD CENTER E /50 4.3 1.6 1/20 1/2 #12 COMPUTER :15 16 SPACE 0.6 1/20 1/2 #12 EXT. RECEPTACLES 17 18 SPACE 13.5 13.5 KVA + 16.9 KVA = 30.4 KVA 3014 KVA/(208XI,73)V = 84.4 AMPS FEEDER, EXISTING TO REMAIN 16.9 (1) REFRIGERATOR IN TWOHId, 110 OWN SERVICE, 120/208, 30, 4W MAIN BUS. 125A POLES; E 30 PANE L_ MAIN BKRt 50A EXISTING LOCATION, WEIGAN 234 AJ.C, 22K V. K.A. TRIP POLE CON- DU,IT WIRE REMARKS CKT NO. It Nf�bT REMARKS I WIRE CON- DUIT TRIP POLE K.V,A, 1.0 2Z 1/2 #12 ICOLD PREP ROOM 1 F�. AND EF7 #12 1/2 1/20 110 1.0 20 20 - - COLD PREP ROOM, 3 4' J.DUCT SMOKE DETECTOR k?_ l/a I/ao 110 --I-,O-'---I-/20---r/-2----#12---'-REFRIGERATaR-RM--2j4 5- VALVE- #12 1/2 1/20 ---------- - 110 LO 1/20 1/2 #12 ICE MAKER RM 234 7 S' ObONIZATION WATER RECEPT, #12 1/2 1/20 1.0 1.0 1/20 1/2 1 #12 REFRIGERATOR . RM 234 9 10 , ",SPACE 110 1/20 1/2 412 HOOD RM 234 11 12 SPACE 1.0 1/2 #12 HEF1 RM 234 13 14 ,SPACE 110 1/20 1/2 #12 HEF2 RM 234 15 16 ISPACE 1.0 1/20 1 1/2 #12 HEF3 RM 234 17 18 -,I-,,.SPACE. -- SPACE 1c)T 2 6 sp F A,'tE SPACE P1 22 SPACE SPACE 234124 SPACE SPACE 251 1 6 SPACE SPACE 27 1 28 "SPACE SPACE 29 130 1 SPACE 9.0 9.0 KVA + 4.0 KVA = 13.0 KVA 4.0 13.0 KVA/(208X1,73)V .�;��36.1 AMPS FEEDER, EXISTING I TO REMAIN SERVICEi 120/208; 30, .4W P A N E L 5 MAIN BUS: 125A -POLLS, MAIN 3KRl M,L,C, EXISTING LDCATIDN: WEIGAN ELECTRIC RIIIIM� A.I.C, 22K TRIP CON- WIRE REMARKS CKT CKT;. REMARKS I WIRE CON-- 'TRIP K,V,A, POLE DUIT NO, NO. I DUI' POLE POLE K.V,A, 110 2 z4- 1/2 #10 HOOD RM 151 1 ":.2- ],REFRIGERATOR #12 1/2 1/20 0.7 110 /225 HOOD RM 151 3 4 .,REFRIGERATOR #12 1/2 1/20 0.7 1.0 1/20 1/2 1 #12 NEW FUME HOOD 5 6 S, WALL OUTLET #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 LAB TABLE 151 7 8 ITV, WALL OUTLET #12 1/2 1/20 to 1.0 1/20 1/2 #12 LAB TABLE 151 9 10 DUCTLESS 102 #12 112 1/20 lo 110 1/20 112 #12 LAB TABLE 151 11 112,,.-'bUCTLESS lop #lp .1 1/2 1 1/20 L0 6.0 6.0 KVA + 5,4 KVA 14,4 KVA 5.4 14.4 KVA/(208XL73.)V.t. 40,0 AMPS FEEDER, EXISTING" TO REMAIN N.T.S. :1) :2) (1: SERVICE, 120/208V, 30, 4W MAIN BUS, 225A POLES42 P AN E. L LA_ MAIN 13KR1 M.L.0, EXISTING LOCATION, ADRIAN 101B 221K X K.V.A. TRIP POLE CON- DUIT WIRE REMARKS ;tkT NO, CKT. NO. REMARKS WIRE CON- DUIT' TRIP POLE K.V.A, 1.0 3 1/2, #12 SEWAGE SUBMERSIBLE PUMPS PANEL 1:. LIGHTS ANATOMY #12 1/2 1/20 1.0 1,0 SEWAGE SUBMERSIBLE PUMPS'PANEL 3 4 LIGHTS #12 1/2 1/20 018 1,0 20 SEWAGE SUBMERSIBLE . BMERSIBLE PUMOPANEL . S . 6 LIGHTS TS EXTERIOR 12 112 1120 1.2 0,9 1/20 1/2 #12 EF101A & EF101D t7. 8 DEMONSTRATION TABLE #12 1/2 1120 0,6 110 1/20.. 1/2 #12 OFFICE RECEPTACLES 5 10 ISTUDENT TABLE RECEPTACLE #12 1/2 1120 118 1.0 1/20 1/2 #12 OFFICE RECEPTACLES i . T 12 [STUDENT TABLE RECEPTACLE #12 1/2 1/20 Ole 119 1/20 1/2 #12 GENERAL PURPOSE RECEPTACLES 13. 14 [STUDENT TABLE RECEPTACLE 1/2,1 1/20 1.0 110 1/20 1/2 #12 DIONIZED WATER SYSTEM 15 116 COUNTERTOP RECEPTACLE #12 1/2 1/2C 0.7 1.1 1/20 1/2 #12 ROOF AND EXT, RECEPTACLES 17 118 COUNTERTOP RECEPTACLE #12 1/2 1/20 0.7 1.1 1/20 1/2 #12 ANATOMY LAB STORAGE RECEPTACLE 9 20 VACUUM PUMP #12 1/2 3 110 ill 1/20 1/2 #12 EF101 & EF103 21 122 VACUUM PUMP 1.0 SPACE 03, 2 4 VACUUM VACUUM PUMP PUMP 20 1.0 11 1/20 1/2 #12 PODIUM RECEPTACLE - 25 11 26 AIR COMPRESSOR #12 1/2 1,0 0.6 1/20 1/2 #12 FIRE ALARM BOOSTER 27 28 AIR COMPRESSOR 110 SPACE 9 30 AIR COMPRESSOR 20 1.0 SPACE 131 32 SPACE SPACE 33 34 SPACE SPACE 35 361 SPACE SPACE 37 38 GAS WATER HEATER #12 1/2 1/20 0,2 ISPACE 39 40 SPACE 41, 42 SPACE 5.0 51 KVA 4- `10 KVA 6l0 KVA 110 6,0r KVA/(208V )K L73) = 16.7 AMPS FEEDE'l.l. EXISTING TO REMAIN r<Lr KJLJLN,A I Ut< IN AIJXIAN lUl-B SERVICE: 120/208V, 30, 4W MAIN BUS: 225A POLES- 42 L6 MAIN BKRi 175A EXISTING. �LOCATIDN: ADRIAN ELECTRIC ROOM 104E SECTION ONE A.LC, 22K KV.A, TRIP POLE CON.- DUIT WIRE REMARKS CXT. NO; CKT, NO, REMARKS WIRE CON- DUIT TRIP POLE K.V.A, 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 2 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 112 #12 FLOOR RECEPTACLES RM 104 3' 4 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 110 110 1/20 112 #12 FLOOR RECEPTACLES RM 104 .5 1 16 FLOOR RECEPTACLES RM 101 #12 1/2 1 1/20 110 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RIM 104 7 .18 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 110 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 P 10 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 104 1 12 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12. FLOOR RECEPTACLES RM 103.,13 14 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 110 1.0 - 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 16 IFLOORRECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 '.'V7 118 FLOOR RECEPTACLES ACLES RM 101 #112 1/2 1/20 lA 110 1120 1/2 #12 FLOOR RECEPTACLES RM 103 C) 20 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 21,. 22 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 110 1;0 1/20 1/2 #12 FLOOR RECEPTACLES RMT16Y -83 _8'4 FLOOR RECEPTACLES RM 101 #2 1/2 1/20 1.0 110 1/20 1,/.2. #12 IFLOOR FLOOR RECEPTACLES RM 103 25 26 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1/20 1/2 #12 RECEPTACLES RM 103 27 28 FLOOR RECEPTACLES RM 101 #12 1/2 1/20 1.0 1,0 1/20 1/2 412 FLOOR RECEPTACLES RM 103 29 30 FLOOR RECEPTACLES RM r 101 #12 1/2 1/20 1.0 1.0 1/20, 1/2 #12 FLOOR RECEPTACLES RM 103 31 32 FLOOR RECEPTACLES r RM 101 #12 1/2 1/20 1 110 1.0 1120 1/p_ #12 FLOOR RECEPTACLES RM 103 -�3 34 FLOOR RECEPTACLES RM 101r #12 112 _ I rl/po, 110 110 1/20 1/2 #12 FLOOR RECEPTACLES RM 103 351 36 FLOOR RECEPTACLES RM 101 412 1/2 1/20 1.0 1.0 1/20 1/2 r #12 FLOOR RECEPTACLES RM 103 3171 138 FLOOR RECEPTACLES. RM 101 #12 112 1/20 1.0 1.0 1/2r 1/2 #12T LOOR RECEPTACLES RM 103 3:9 40 IFLOOR' r RECEPTACLES PM 101 #12 1 1/2 1 1/20 1.0 1.0 1/20 1/2 #12 FLOOR RECEPTACLE S�r RM 103 �4 142 IFLOOR r RECEPTACLES RM 101 #12 1/2 1120 1 1.0 21.0 21,8 KVA + 20.14 KVA = 422- KVA 21.0 42.,2 KVA/(208V )* 1,73) = 117.7 AMPS SEE SECTION TWO SERVICE, 120/208V, 30, 4W MAIN BUS, 225A POLES; 42 PANEL L6 MAIN BKR1 175A LOCATION, ADRIAN ELECTRIC ROOM 104E EXISTING A,I.C, 22K SECTION TWO K,V.A, TRIP ODLE CON- DUIT WIRE REMARKS CKT No M ICKT, NO, REMARKS WIRE CON- DUIT TRIP POLE K,VlA, 1.0 2 Z 1/2 #12 SPECIAL RECEPTACLE 43 144 FLOOR RECEPTACLES RM 104 #12 112 --1/20- 1.0 1.0 30 SPECIAL RECEPTACLE 45 146 3HUT OFF FOR GAS VALVES #12 1/2 1/20 0.2 1.0 2 / 1/2 1 #12 SPECIAL RECEPTACLE 4.7 48, EF-IL #12 1/2 1/20 1.2 1.0 30 SPECIAL RECEPTACLE 49 50 1 EF-2L #12 1/2 1/20 1.0 110 1/20 1/2 #12 CRISTAT UNIT 521 SF-1 #12 1/2 1/20 LO SPACE �53 54 1 MOTORIZED DAMPERS #12 1/2 1/20 01.5 SPACE 55 56 SPACE SPACE 7 58 SPACE 7- SPACE 359 60 SPACE SPACE '61 62 SPACE SPACE63T64, SPACE SPACEy65 1661 SPACE SPACE 67 681 SPACE ISPACE 619M 7,0 SPACE I ISPACE 71 72 SPACE SPACE 73 74 SPACE 7- SPACE 75, 76 SPACE 1 7- SPACE, 77 78 SPACE SPACE 79 80 SPACE SPACE 81 82 SPACE ISPACE 83 184 SPACE 5.0 21.0 KVA + 21,0 KVA + 5,0 KVA + 4.9 KVA = 51,9 KVA 43 51.9 KVA/(208V w 1,73) -_ 144.2 AMPS FEEDER; EXISTING TO REMAIN lU Kt-rKilit-MMIUM IN A.UKiAN IU4 ®:I �IMIREGINEERS 12915 SW 132nd Street Unk I Miami, FL=86 P, 305,670.0820 F. 306=W3 Bu I We; P.E., LEED@AP, CxA No. 52146 Eduardo Rams P.E,, LEED 0 AP No. 58741 Gregory M. Jensen ffii p No. 6382E 7 % StATE 00 L Sea] of Proiect Fnininplar 0 c COEGOO c cooc�* 0 Co. 0 0 c coo 0 Coco ccec 00.0c,P O 00 oco CC 49 acco.� 0OG 0 a9CE Ea 0 oe CC cc .0c o OCOG4 CC CEC 00 0 O c o olsoc Q 10 U) w j <. 0 LLJ: > X-1 1. z z w w Z ce W w ca PANEL SCHEDULES )rawn By: xx xx ,hecked By: 110 ATS - _L_30 A PANEL L2 10 REFRIGERATOR AN 105 ATS 30 A 10 NMR COMPUTER L 4#10 CU. IN 1/2' C ATS —-iFATSi A 30 A PANEL L 10 1010 i A/C ,,— 4#10 CU. IN 1/2' C —4#10 CU, IN 1/2' C ,--4#10 CU, IN 1/2' C ADRIAN 104 ELECTRIC RM ADRIAN 101-B 104E ADRIAN CBS MAINTENACE SHED 4#12 CU. IN 1/2' C 4#12 CU. IN 1/2' C DISC. ATS PANEL L6 ! F L LA ATS 20 A 30 A — 30 A 30 30 12 THREE PHASE 30 A — ! SMALL �� — — �— AIR COMPRESSOR REFRIGERATOR J 4#12 CU. IN 1/2' C EXTERIOR CHILLER YARD NOTE RUN LOW VOLTAGE CONTROL WIRING FROM EACH A.T.S. TO THE GENERATOR. 120/208V 30 4W 4#3 THHN/THWN CU. IN 1-1/4' C DIST. PNL A 100 A GENERATOR THREE PHASE CB 1ODA 35KWNOT A SEPARATELY DERIVED SYSTEM CUMMING POWER GENERATION QUIET SITE GENERATOR GGFD-5699820 1#3/0 THHN/THWN CU. IN 1/2'C, CONNECT TO EXISTING GROUND SYSTEM GENERATOR SPECIFICATIONS BRAND: CUMMING POWER GENERATION QUIET SITE GENERATOR MODEL GGFD-5699820 TYPE: STANDBY SIZE: 35 KW/43.75 KVA VOLTAGE 120/208 VOLTS PHASE THREE PHASE FUEL TYPE: NATURAL GAS FUEL CONSUMPTION: 493 CFH NOTE GENERATOR PROVIDED WITH WEATHER-PROOF ENCLOSURE. ADRIAN 105 ADRIAN 104 ELECTRIC RM ADRIAN 101-B ADRIAN CBS EXTERIOR 104E PANEL L6 PANEL LA MAINTENACE SHED CHILLER YAR[Y- PANEL L REFRIGERATOR THREE PHASE NMR EMF UTER CONSOLE SMALL FAIR COMPRESSOR REFRIGERATOR EXISTING PARTIAL DIAGRAMMATIC POWER RISER SCALE: N.T.S. RJMJR ENGINEERS 12915 SW 132nd Street Unit 1 Miami, FL 33186 ?. 305.810.0820 F. 305.233.9453 w .meengineers,com Bui Wei P.E., LEER® AR CxA No. 52146 Eduardo Ramos P.E., LEEDO AP No. 58741 Gregory M. J `, ` i ��EI, "fpf A` No. 626 /�' 63 — O. *: 2 =�ob 22*� 10�•. STATE OF •' j4�� � l� '�=ORIDP,.•'• � � Seal of Project Engineer Feee � J J � \W a / Q Q W Z i 0 W 0 M� W ai v d 'o a Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date 0 EILD DEPT COMM 02/18/22 DIAGRAMMATIC POWER RISERS Drawn By: XX Checked By: XX Job No: Scale: Sheet Number: DIAGRAMMATIC POWER RISER V.T.S. 71MIRENSINEERS 12915 SW 132r Sbeet Unit Miami. FL 3318E P. 3O5.87O.O82O F. 3OS.233.9953 w .Wenglnasrs.Com Sul Wei P.E., LEED®AP, CxA No. 52146 Etluaroo Ramos P.E., LEED 0 AP No. 58741 Gregory M.Jansen ,`; �i 83828 ..�i...'.e..... M. ...��.e r � - G..yy,� r ssas ttATEW `V w Seal of Proj a 0 aaaaoo 0 0 0 C> a 00 O 0 0 a 0�0>00 > > oaaOao 0 0 ODOi )o OaO> 0 0 > > a 0 aooaaa aaaO > o a >,9>ao >000 a>O: o > 0 a n as Oa oa o 0OO: 0 oaoOoa a 0 a o a o Oa > 00O: o J O a O > 00 > 0 a>+ 000 0 r r Date of Issue: 12-07`.2021 PERMIT ISSUE Rev No. Description Date ®1AGr%^51WV1MAT1C POWER RISERS Drawn By: • XX Checked By: XX -Job-No: Scale• .ami Dad .2201066 •4 P1-04142022.pdf :aminer Date Time Stamp Trade Stamp Name WIEGAND 234 WTEGAND 151 ELECTRIC RM jTWOHIG 110 104E 105 1 ADRIAN 104 ELECTRIC RM I ADRIAN 101-8 104E ADRIAN CBS MAINTENACE SHED EXTERIOR CHILLER YARD NOTE RUN LOW VOLTAGE CONTROL WIRING FROM EACH A.T.S. TO THE GENERATOR. 4#12 CU. IN 1/2' C �— 4#12 CU, IN 1/2' C ATS - JR ATS PANEL 5 30 A PANEL t2� ATS ATS ATS DISC. ATS ATS PANEL E 30 A 10 30 A 030 A 30 A PANEL L ATS PANEL L6 ATS PANEL LA ATS 20 A r - - 3M A t 0 r - - 1 I I 10 10 10 I ( 30 A 30 A 30 A 3# %44#3 T I __ __ _11� 1# THREE PHASE 3� N CU. IN 1-1/4 C FREE E-ERRRREEZERRATOR/ REFRIGERATOR I - _ REFRIGERATOR �- -COLD PREP SMALL - J ` NMR COMPUTER A/C - SMALL -AIR COMPRESSOR TMREE PHASE FREEZER REFRIGERATOR_ #12 CU. IN 1/2' C L- - -1 I- �- -- --- NOT A SEPARATELY DERIVED SYSTEM GUMMING POWER GENERATION QUIET SITE GENERATOR GGFD-5699820 4#10 CU. IN 1/2' C 4#10 CU. IN 1/2' C 1#3/0 THHN/THWN CU, IN 1/2'C, 4#10 CU. IN 1/2' C - 4#10 CU, IN 1/2' C CONNECT TO EXISTING GROUND a SYSTEM NEW PARTIAL DIAGRAMMATIC POWER RISER SCALE: N.T.S. ELECfkICALREVIEW z� APPROVED�DATE WTEGAND 234 WIEGAND 151 ELECTRIC RM TWO HIG 110 DRIAN 105 ADRIAN 104 ELECTRIC RM ADRIAN 101-8 ADRIAN CBS EXTERIOR 104E 104E I I MAINTENACE SHED CHILLER YARD PANEL E I 1 1 1 I PANEL 5 PANEL 19 �TOR/ (FREE ER�TOR/I I I I I I REFRIGERATOR FREEZER RA COLD PREP SMALL u ROOM FREEZER EXISTING PARTIAL DIAGRAMMATIC POWER RISER SCALE: N.T.S. SMALL REFRIGERATOR PANEL L6 I I I I PANEL LA REFRIGERATOR AIR COMPRESSOR �JMJRENGINEERS 12915 SW 132nd Street Unit 1 Miami, FL 33186 P. 315.670(M20 F. 3052339453 www.twrengineers.con: Bui Wei P.E.. LEEDO AP, GxA No. 521-F Eduardo Ramos P.E., LEEDO AP pNo. 56741 Gregory M. Jan s�1 a I t.P, No, U828 �. •0 f 1oRig Seal of Project Engineer .. . ...... .... �r W o Z Z Q W Z p LLI LL Q d F U d 0 a` Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date 0 DIAGRAMMATIC POWER RISERS Drawn By: XX Checked By: XX Job No: Scale: Sheet Number: DIAGRAMMATIC POWER RISER N.T.S. VIMINENSINEERS 12915 SW 132nd Street Un@ 1 Mi aFL 33186 P. 305.610.0820 F. 305.233.M3 w .A ,snginee o m Bui Wei P.E., LEED®AP, CxA No. 52146 Eouwda Ramos P.E. LEED ® AP No. 58741 Gregory M. Jensen P.E., LEED ® AP No. 63828 Gregory M Jensen DN: c=US, o=TWR Engineers, ou=A01410C0000 616B1F23D33D00 Jensen Date: 2022.06.01 10:31:03-04'00' Seal of Project Engineer J W = Z Z w =az a m Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date © BLD DEPT COMM 02 18 22 ® BLD DEPT COMM 06/01/22 DIAGRAMMATIC POWER RISERS Drawn By: XX Checked By: XX Job No: Scale: Sheet Number: Em4 Miami Dade 1122010668 E-4 131-0607�„�� Examiner Date Time Stamp Trade Stamp Name FRIAS, JOSE 6/9/2022 9:48:10 AM FIRE Void L "NORK TO BE DONE N ACCOR ;ANC= ',4T1 r - RIDA 8UI _D`N G CODE F3C. 2017 'I „~v1BINU SF, ` ON. STA F AND Ct N OPi'NAN(-, r �G vi r �NcTFTt! FT L ihl cn, I , np 5 DIPF AND V Pii i.Nv SHNL5E E CLE N 01L, TS F'V`FR i 75 FT AND ik E RASE 0 Di'ER { 'WASTES TACK. CLOS_. Ol S ILSH MO U N Eu. AL) AND AS FOLLOWS: B�'JE GROUND AND COPPEr !YFL L M B38 UNDERGROUND. ALL WATER GI `IRIBU ION INSIDE THE UNITS SHAL _ ,E PPVC ASTM , 2846 AND F 493 SCHEDULE 40 FOP HO AND CG,..D WATER DISIR?BUI!OiN. Y,,f A I f` 11 �PC"� �Fl { f�I y R "',^ P t ^ ' .•L r ���. .� _r,(Vv ait ,�,�11'�� 1_ ��A .. -„�".r. L� ` NSULA.T O\y TO All CONDENSATE DRAIN P 1 P NG UNLESS RUNN';NG I;N RGI:OuND. "AS =!PING B, AC . STEEL S C H, D U 1_E Z., AS II, 7 E. ;;;OR !LEAN OiJTS: JOSAc` SERIES ;AnC2u LJR EQU:4_. F. WALL CLAN 0U S: JOSAM S _RIES 38750 'N TH ACCESS CC\ R OR EQUAL. 1-V3 Y`S. '25 Y.S! NIBCO SCOTI, `>TU KHAM R '-CKt.h_. HOSE BIBBS: CHICAGO 837 OR EQUAL `vVITH VACUUM �'TEA.KER. 5. `'ERFOPM THE FOLLOWING TEST, A. WATER PIPING SHALL BE SUBJECTED TO HYDROSTATIC PRESSURE TEST OF 100 PSIG FOR A PERIOD OF TIME SUFFICIENT TO EXAMINE ENTIRE SYSTEM BUT NOT LESS THAN ONE HOUR. B. DRAINAGE SYSTEM: BEFORE INSTALLATION OF ANY DRAINS, THE END OF THE SYSTEM SHALL BE CAPPED & ALL LINES FILLED WITH WATER TO HIGHEST POINT & ALLOWED TO STAND UNTIL INSPECTION IS MADE AND WATER LEVELS REMAIN CONSTANT C. CORRECT ALL DEFECTS DISCLOSED BY ABOVE TESTS, D. COMPLETE SYSTEM FIXTURE & EQUIPMENT SHALL BE GIVEN AN IN SERVICE TEST AFTER COMPLETION OF THE INSTALLATION. E. STERILIZE ALL WATER 'LINES WITH A MIXTURE OF (2) POUNDS OF CHLORINATED LIME TO EACH 1000 gal. OF WATER (50 PPM OF AVAILABLE CHLORINE.) RETAIN MIXTURE IN PIPES FOR 24 HOURS AND FLUSH THOROUGHLY WITH POTABLE 'HATER BEFORE PLACING IN SERVICE. A BACTERIOLOGICAL TEST SHALL BE SUBMITTED SHOWING NO CONTAMINATION REMAINS PRESENT N THE SYSTEM. & PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL PLUMBING WORK SHALL BE FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR ,A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE, AND THAT HE WILL, AT HIS EXPENSE, REPAIR AND REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING GUARANTEE PERIOD. 7, CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION OF EXISTING UTILITIES AND POINTS OF CONNECTION BEFORE COMMENCING ANY WORK. 8. PLUMBING CONTRACTOR SHALL PAY ALL FEES, INSPECTION AND CONNECTION CHARGES REQUIRED. 9, SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL OF ALL EQUIPMENT, MATERIALS AND LAYOUTS PRIOR INSTALLATION. 10. OFFSET PIPING AS REQUIRED TO CLEAR BUILDING STRUCTURE, DUCTWORK, ETC. AS SHOWN ON DRAWINGS AND AS REQUIRED BY FIELD CONDITIONS. 11. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL A/C CONDENSATE DRAIN AND TRAP. SEE A/C PLANS FOR LOCATION OF UNITS AND DRAINS. 12, PLUMBING CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. 13. COORDINATE WORK WITH OTHER TRADES, 14, FURNISH AND INSTALL FIXTURES AS SPECIFIED IN SCHEDULE, THIS DRAWING. 15. EACH BATHROOM GROUP SHALL BE PROVIDE WITH AIR CHAMBERS OR SHOCK ABSORBER. 16. PROVIDE SHUTOFF VALVE FOR EACH FIXTURE, JUST BEFORE CONNECTING TO FIXTURE, 17. WHEREVER DISSIMILAR METALS ARE TO BE JOINED, A DIELECTRIC FITTING SHALL BE PROVIDED TO CONNECT BOTH TYPES OF PIPES. 8. PIPE INSULATION: A. ALL CONDENSATE LINES SHALL BE INSULATED WITH 3/4" FIRE RETARDANT ARMAFLEX INSULATION WITH A MAXIMUM OF 25f50 FLAME SPREAD AND SMOKE DEVELOPED RESPECTIVELY, B. ALL HOT WATER LINES IN SYSTEM THAT IS RE CIRCULATING SHALL BE NSU'_ATED +,^j" T H 1" FIRE `R TARDAN I ARN?AF L EX INSULATION WITH A MAXIMUL%, OF 5Ci FLAME SPREAD AND IMOKE DFVE_OPED RESP,r iVELY. C. AL S(. EDUL G 'HAS F PIPES RUNNING HORIZCNT.ALLY INSD:E UNITS IAU_ BE SOUND INSUILA - 'tAlITH HIGH' :DENSITY PIP- ''NRAP SOUND JSl1 :`tTiO'�. ALL \jC NIPING IN SIDE PI ENUM SHALL BE INSULATED WITH FIRE RETARDANT ARVAR-Ex NSUI_ATION. PLUMBING ABBREVIATIODN't"' DESCRIPTION TWO COMPARTMENT SINK THREE COMPARTMENT SINK AIR ADMITTANCE VALVE ABOVE FINISHED FLOOR AIR GAP AIR HANDLING UNIT CUBIC FEET PER HOUR CLEAN OUT CLEAN OUT TO GRADE COLD WATER COLD WATER FILTER SOFTENED COLD WATER CONDENSATE PUMP DRINKING FOUNTAIN DECK DRAIN DRAINAGE FIXTURE UNIT DOWN DISHWASHER EXISTING TO REMAIN ELEVATOR SUMP PUMP ELECTRICAL CONTRACTOR EYE WASH ELECTRIC WATER COOLER FROM ABOVE FROM BELOW FLOOR CLEAN OUT FIXED AIR GAP FOOD WASTE GRINDER FLOOR DRAIN FLOOR SINK GAS GREASE INTERCEPTOR GREASE WASTE HANDICAP HAND SINK HOSE BIBB HOT WATER HOT WATER RECIRCULATION DRAIN PAN ICE MACHINE OUTLET BOX KITCHEN SINK LAVATORY TRENCH DRAIN GARAGE DRAIN SYMBOL I DESCRIPTION ..... ... _ ........ — LF LINEAR FOOT MS MOP SINK MV MIXING VALVE N NEW 01 OIL INTERCEPTOR P.C. I PLUMBING CONTRACTOR PD PLANTER DRAIN RD ROOF DRAIN (R) REMOVE RDO OVERFLOW ROOF DRAIN RTU ROOF TOP UNIT RP RECIRCULATION PUMP RWL RAIN WATER LEADER RWCO OVERFLOW RAIN WATER CONDUCTOR SAN SANITARY SFU SUPPLY FIXTURE UNIT I SH SHOWER SI SOLIDS INTERCEPTOR SP SPRINKLER SEP SEWAGE EJECTOR PUMP SS SAFETY SHOWER THIN TEMPERED HOT WATER TP TRAP PRIMER VTR VENT THROUGH ROOF U/C UNDER COUNTER UH UNIT HEATER UR URINAL V i VENT VIF VERIFY IN FIELD I W i WASTE WC WATER CLOSET WCO WALL CLEAN OUT W/D WASHER/DRYER COMBO WMOB WASHING MACHINE OUTLET BOX P&T PRESSURE & TEMPERATURE WH WALL HYDRANTS WHA WATER HAMMER ARRESTOR EWH ELECTRIC WATER HEATER WHG GAS WATER HEATER 0 DIAMETER TWH TANKLESS WATER HEATER PLUMBING SYMBOLS PLUMBING LINETYPES RWL GW —CD— — PD COLD WATER SUPPLY PIPING HOT WATER SUPPLY PIPING HOT WATER RECIRCULATION GAS SUPPLY PIPING RAIN WATER CONDUCTORS SANITARY PIPING GREASE WASTE PIPING VENT PIPING CONDENSATE DRAIN PIPING PLANTER DRAIN PIPING SYMBOLS —XX"—XX XX" - PIPE SIZE --Q PIPE TURNING UP PIPE TURNING DOWN CONNECTION TOP CONNECTION BOTTOM TEE, OUTLET DOWN v TEE, OUTLET UP f90' PIPING BEND PIPING TEE — X11 LF INCH OF SLOPE PER LINEAR FOOT VALVE IN DROP n METER " BALL VALVE �r PLUG VALVE HWR BALANCING SYSTEM THERMOSTATIC MIXING VALVE GAS COCK VALVE PRESSURE REDUCING VALVE I— UNION BALANCING VALVE �— FLOW CONTROL VALVE CV — SWING CHECK VALVE ANGLE VALVE I ANGLE GLOBE VALVE SOLENOID VALVE AUTOMATIC CONTROL VALVE THERMOSTATIC AIR VENT TH RANGE THERMOMETER EXPANSION JOINT HOT WATER RECIRCULATING PUMP FLOOR CLEANOUT FLOOR DRAIN XX SANITARY RISER OCONDENSATE RISER OX WATER RISER WATER HAMMER ARRESTOR (ASSE 1010) I I I II I I II I I I I I II I I I I I II I I EXISTING I EXISTING I I I MECH EQ MECH EQ I I II I I I 1 I II I I I i I I II L---------L EXISTINIG CHILLEf YARD I 1 I I F_ -1 L_----_—J I I I— — 7 1 1 EIXI STI N 13 gENERATOR I I L_ — _J EXISTING I GENERATO� I I I I I I I I I I L __J 0 RELOCATED NATURAL GAS GENERATOR EXISTING AHU / MECHANICAL ROOM DISTANCE TO FURTHEST GAS APPLIANCE: 100' LN.FT (WORST CASE) TOTAL BTUH: 512,275 BTUH TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE, INLET PRESSURE LESS THAN 2 PSI, PRESSURE DROP AT 0.5" W.C. SPECIFIC GRAVITY = 0.60 NOTE: ALL UNDERGROUND PIPING INSTALLATION SHALL BE POLYETHYLENE PLASTIC PIPE AND TO COMPLY FBC CODE REFER TO NFPA 54-2012 TARI_F 6.9(V) NEW GAS METER AND REGULATOR BY GAS CO. (PRESSURE SET AT LESS THAN 2.0 PSI) COORDINATE WITH UTILITY COMPANY c-, GAS LINE c, D ci T. o NATURAL GAS GENERATOR ON 6" HOUSEKEEPING PAD. GENERATOR EXHAUST SHALL BE LOCATED MIN. 10 FEET FRO MECHANICAL ROOM DOOR MECHANICAL YARD 1 SCALE: 7SSURE REGULATOR FROM DSI TO LESS THAN 1 PSI GAS RISER DIAGRA 2 SCALE: N.T.S. P-1 TJMJRENGINEERS 12915 SW 132nd Street Unit 1 Miami, FL 33186 P. 3M5 0.0820 F. 305.233.9453 w .t rengineers.mm Bui Wei P.E., LEEDO AR CxA No. 52146 Eduardo Ramos P.E., LEER® AP No. 58741 Gregory M. Jensen P.E., LEEDB AP No. 63828 / _m;pp = —Z— ;� CD C' Seal bf!Pid�ect Engineer J LU 0 F- 2Z9 Z 0 W I.L Q W F_ i= u d .o a` Date of Issue: 12-07-2021 PERMIT ISSUE Rev No. Description Date 1Q BUILDING DEPT 2/18/22 02 BUILDING DEPT 3/3/22 SITE PLAN Drawn By: XX Checked By: XX Job No: Scale: Sheet Number: pml 1 NEW DRAWING NIL NOTES: I. ALL WORK TO BE DONE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE FBC 2017 PLUMBING SECTION, STATE AND LOCAL ORDINANCES. ?> BUILDING DRAINAGE SYSTEM TO BE SLOPED AT 1/8" PER FT. MIN. FALL FOR 3" PIPE AND LARGER 1/4" PER FT. SLOPE FOR 2" PIPE SIZE AND SMALLER DEVIATIONS SHALL BE APPROVED BY ARCHITECT/ENGINEER. 3. PROVIDE CLEAN OUTS EVERY 75 FT. AND AT BASE OF EVERY WASTESTACK. ALL CLOSE-OUTS TO BE FLUSH MOUNTED. 1. MATERIALS SHALL BE ALL NEW AND AS FOLLOWS: a a. DRAINAGE WASTE, STORM DRAINAGE ,AND VENT PIPING: NO HUB ; AST IRON ..CISPI STANDARD 301 ABOVE GROUND ALL VERTICAL STACKS AND PVC SCHEDULE 40 PVC ASTM D2665 SERVICE WEIGHT FOR STUB -STACKS, WASTE ARMS,,, VENTILATION, EXPOSED GARAGE COLLECTION AND UNDERGROUND COLLECTION. .P. 3> WATER PIPING: ALL WATER. MAINS AND RISERS SHALL BE COPPER TYPE "L" ASTM B-88.1 -ABOVEGROUND AND COPPER TYPE 'Y' ASTM.B-88 UNDERGROUND. ALL WATER DISTRIBUTION INSIDE THE UNITS SHALL BE CPVC ASTM D 2846 AND F-493 SCHEDULE 40 FOR HOT AND COLD WATER. DISTRIBUTION. ? C. CONDENSATE DRAIN 'PIPING: COPPER TYPE "M" ASTM B-88 INSIDE THE BUILDING AND PVC SCHEDULE 40 ABOVE ROOF AND UNDERGROUND. PROVIDE ARMAFLEX PREFORMED PIPE INSULATION TO ALL CONDENSATE DRAIN PIPING UNLESS RUNNING UNDERGROUND. D, GAS PIPING: BLACK STEEL SCHEDULE 40 ASTM-53 E, FLOOR CLEAN OUTS: JOSAM SERIES 56020 OR EQUAL. F. WALL CLEAN OUTS: JOSAM SERIES 58750 WITH ACCESS COVER OR EQUAL. H• VALVES: 125 PSI NIBCO SCO.TT,'STOCKHAM OR.EQUAL. 1. HOSE BIBBS: CHICAGO 837 OR EQUAL WITH VACUUM BREAKER. 5. PERFORM THE FOLLOWING TEST: A. WATER PIPING SHALL BE SUBJECTED TO HYDROSTATIC PRESSURE TEST OF 100 PSIG FOR A. PERIOD. OF TIME SUFFICIENT TO EXAMINE. ENTIRE SYSTEM BUT NOT LESS THAN ONE HOUR. t 8. DRAINAGE_'SYSTEM: BEFORE' INSTALLATION OF ANY DRAINS, THE END OF THE SYSTEM 1 SHALL BE CAPPED & ALL LINES FILLED WITH WATER TO HIGHEST POINT & ALLOWED w TO STAND UNTIL 'INSPECTION IS MADE AND WATER LEVELS REMAIN CONSTANT C. CORRECT ALL DEFECTS DISCLOSED BY ABOVE TESTS. D. COMPLETE SYSTEM FIXTURE & EQUIPMENT SHALL BE GIVEN AN IN SERVICE 0 TEST AFTER COMPLETION OF THE INSTALLATION. E. STERILIZE .ALL, WATER LINES WITH A MIXTURE OF(2). POUNDS.OF CHLORINATED . . LIME TO EACH 1000 gal, OF WATER: (50 PPM OF . AVAILABLE CHLORINE.). RETAIN MIXTURE IN: PIPES FOR'24 HOURS AND FLUSHTHOROUGHLY WITH POTABLE WATER BEFORE IN 'SERVICE. A BACTERIOLOGICAL TEST. SHALL BE SUBMITTED SHOWING .PLACING CONTAMINATION REMAINS PRESENT IN THE SYSTEM. 6. PLUMBING CONTRACTOR SHALL FURNISH A WRITTEN GUARANTEE THAT ALL. PLUMBING WORK SHALL BE FREE FROM DEFECTS, OF MATERIALS AND WORKMANSHIP FOR A PERIOD ONE YEAR.. FROM DATE OF FINAL ACCEPTANCE,. AND THAT HE WLL,_AT HIS EXPENSE, _._._OF REPAIR AND REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING GUARANTEE PERIOD -! . 7. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION OF EXISTING UTILITIES AND POINTS 0 CONNECTION BEFORE COMMENCING ANY WORK. 8. PLUMBING CONTRACTOR SHALL PAY ALL FEES, INSPECTION AND CONNECTION CHARGES REQUIRED. . g. SUBMIT SHOP DRAWINGS TO ENGINEER'FOR APPROVAL OF ALL EQUIPMENT,' MATERIALS AND LAYOUTS PRIOR INSTALLATION. ; 10. PIPING'AS„REQUIRED TO CLEAR BUILDING STRUCTURE, DUCTWORK, ETC. .-OFFSET AS SHOWN ON DRAWINGS AND AS REQUIRED BY FIELD CONDI'TIONS.. PL" MSIN A B 5 R EVIAT'10NS � SYMBOL DESCRIPTION. SYMBOL DESCRIPTION 2CS TWO COMPARTMENT SINK LF LINEAR FOOT 3CS THREE COMPARTMENT SINK MS MOP SINK . AAV AIR ADMITTANCE VALVE MV MIXING VALVE j AFF ABOVE FINISHED FLOOR. N NEW AG AIR GAP OI OIL INTERCEPTOR AHU AIR HANDLING UNIT P.C. PLUMBING CONTRACTOR CFH CUBIC FEET PER HOUR CO } CLEAN OUT PD PLANTER DRAIN . COTG CLEM OUT TO GRADE RD ROOF DRAIN CW COLD .WATER (R) REMOVE .. CWF COLD WATER FILTER RDO OVERFLOW ROOF DRAIN CWS SOFTENED COLD WATER RTU ROOF TOP UNIT CP. CONDENSATE PUMP RP RECIRCULATION PUMP, DF DRINKING FOUNTAIN RWL RAIN WATER LEADER DID DECK DRAIN RWCO OVERFLOW RAIN WATER CONDUCTOR FU DRAINAGE FIXTURE UNIT SAN SANITARY DN DOWN SFU SUPPLY FIXTURE UNIT DW DISHWASHER SH SHOWER (E) EXISTING TO REMAIN 1 SI SOLIDS INTERCEPTOR ( EP ELEVATOR SUMP 'PUMP EC.. ELECTRICAL CONTRACTOR SP SPRINKLER SEP SEWAGE EJECTOR PUMP EW EYE WASH . EWC ..�CTR1C WATER COOLER' Ss SAFETY SHOWER I: FA FROM ABOVE THW TEMPERED HOT, WATER ! FB FROM BELOW TP TRAP. PRIMER FCO FLOOR CLEAN OUT VTR VENT'THROUGH. ROOF I FAG FIXED AIR GAP U/C UNDER COUNTER FWG FOOD WASTE GRINDER UH UNIT HEATER ED FLOOR DRAIN' UR URINAL FS FLOOR SINK V VENT GAS -' GAS VIF VERIFY IN FIELD GI • GREASE INTERCEPTOR W WASTE GW GREASE WASTE WC WATER CLOSET. HC -HANDICAP WCO WALL -CLEAN OUT HS HAND.SINK W/D WASHER/DRYER .COMBO.` HB HOSE BIBS -.------- - - ........... WMOB WASHING MACHINE OUTLET BOX HW HOT WATER HWR HOT WATER RECIRCULATION P&T PRESSURE & TEMPERATURE DP DRAIN PAN WH WALL HYDRANTS °. 'IMOB ICE MACHINE OUTLET BOX WHA WATER 'HAMMER ARRESTOR KS KITCHEN SINK EWH ELECTRIC WATER HEATER LAV LAVATORY WHG GAS WATER HEATER C TD TRENCH DRAIN .0 DIAMETER il. GD GARAGE DRAIN TWH TANKLESS WATER .HEATER 11. PLUMBING CONTRACTOR SHALL :FURNISH AND INSTALL A/C 06RDENSATE`'DRAIN ------------ 12. PLUMBING CONTRACTOR SHALL VERIFY ALL SPACE CONL;ITIONS AND DIMENSIONS Z AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF: MATERIALS AND EQUIPMENT'S 13. COORDINATE WORK WITH OTHER TRADES s' 14. FURNISH AND INSTALL FIXTURES AS SPECIFIED IN SCHEDULE, THIS DRAWING. 15. EACH BATHROOM GROUP SHALL BE PROVIDE WITH AIR CHAMBERS OR SHOCK! ABSORBER, ;-- 16, PROVIDE SHUTOFF VALVE FOR EACH FIXTURE, JUST BEFORE CONNECTING TO FIXTURE, 17, WHEREVER DISSIMILAR METALS ARE TO BE JOINED, A DIELECTRIC FITTING SHALL BE PROVIDED TO CONNECT $OTH TYPES OF PIPES, 18. PIPE INSULATION: ' A. ALL CONDENSATE LINES SHALL BE INSULATED NTH 3/4" FIRE RETARDANT ARMAFLEX INSULATION WITH A MAXIMUM OF 25/50'FLAME SPREAD.AND SMOKE _ DEVELOPED RESPECTIVELY. . B. ALL HOT WATER LINES IN SYSTEM THAT IS RE -CIRCULATING SHALL BE INSULATED WITH 1" FIRE RETARDANT ARMAFLEX INSULATION WITH A MAXIMUM OF 25/50 FLAME SPREAD AND SMOKE DEVELOPED RESPECTIVELY. C. ALL SCHEDULE 40 WASTE PIPES RUNNING HORIZONTALLY INSIDE UNITS SHALL BE SOUND INSULATED. WITH HIGH DENSITY PIPE WRAP SOUND INSULATION. D. ALL PVC PIPING IN SIDE PLENUM SHALL BE INSULATED WITH FIRE RETARDANT ARMAFLEX INSULATION. 'k Miami. Dade CAiin+_%, T1ot�w®eme n'm®+ of Ri •7 n .++-is �nri T.'i.nnnm+'. 1122010668 - 7/14/2022 3:34:27 PM P-1-04142022,pdf Examiner Date Time Stamp Trade Stamp Name FRIAS, JOSE 6/9/2022 9:50:05 AM FIRE Approved As Noted ,P LUM B I N•G SYMBOLS 'PLUMBING-LINETYPES .__ - COLD WATER SUPPLY PIPING -- HOT WATER SUPPLY PIPING --- HOT WATER RECIRCULATION -GAS GAS SUPPLY PIPING RWL - RAIN WATER CONDUCTORS SANITARY PIPING GW GREASE WASTE PIPING VENT PIPING —CD— — CONDENSATE DRAIN PIPING PD PLANTER DRAIN :I .:fft C t a �I PIPING SYM XX" NEW GAS AND REGULATOR —XX"--- V -- XX" PIPE SIZE _ — -GAS CO (MPRESSURE EIER sE7 AT LESS THAN 2.0 PS!) COORDINATE WITH —Q PIPE TURNING UP I _ _ _ I t I I unLmr COMPANY D PIPE TURNING DOWN I { I I I I I a sr,:... 1-1/2" GAS,; LINE I I I I I EXISTING': --z��— CONNECTION . TOP �t I EXISTING I I. {MECH EQ I' MECH EQ I I I I I I CONNECTION BOTTOM I I I I I i I v S;T. I I I t I II N TEE, OUTLET DOWN I - - - -I ,x I ---tom-- TEE; 'OUTLET' UP r - - - - - - -I EX15TVG CN I LLE� f+ 90' PIPING. BEND !. YARD PIPING. TEE L-+---- J EXISTING, ' I i GENERAT01� a X" LF INCH OF SLOPE PER LINEAR FOOT J. I I L t I VALVE IN ;.DROP gxisTINO y., gENERATOR METER { .. L- — -J I ( I y --Do*— BALL VALVE - - PLUG VALVE: jGENERATOR, RE vDi LOCATED ' HWR BALANCING; SYSTEM' _ I;� NATURAL GAs h GENERATOR 5.4. THERMOSTATIC. MIXING VALVE GAS COCnVALVE, e` =— PRESSUR xREDUCING VALVE ,. : .',' �d NATURAL GA6 q . HOUSEKEEPIOR --; I- UNION �1 ExHAusr SHMINA .10 ;lFEET FRO MWO i W, --�- BALANCINGIYVALVE QD FLOW CONaTROL' VALVE L- SWING' CHECK, VALVE ANGLE VALVE''_ __. OBE VALVE Ei i1NG MU / VDIAN11CAL R ANGLE GL -..... _.. - SOLE _ -NOID .. .. .. .... ... ... .... -. -, -.y .� AL -�— AUTOMATIC i CONTROL VALVE 3 :: THERMOSTATIC AIR VENT { MECHANICAL YARD 1 TH RANGE ,`. SCALE: THERMOMEJTER. ; EXPANSION, -JOINT M D F R NOTE _.. OPTIONAL STANDBY GENERATOR NOT SERVING LIFE SAFETY EMERGENCY SYSTEMS, IN HOT WATER._RECIRCULATING -PUMP _ _-- ACCORDANCE WITH NFPA 70 ARTICLE 702. FLOOR CLEANOUT I FLOOR DRAIN:; DISTANCE TO FURTHEST GAS APPLIANCE: XX SANITARY RISER 100' LN.FT .(WORST CASE) TOTAL BTUH: 512.275 STUN TABLE 402.4(2) SCHEDULE 40 METALLIC PIPE, INLET PRESSURE LESS THAN 2 PSI, �X CONDENSATE `RISER PRESSURE DROP AT 0.5" W.C. SPECIFIC GRAVITY - 0.60 / t 1 � Q WATER RISER' NOTE: ALL UNDERGROUND PIPING;' INSTALLATION =' SHALL BE POLYETHYLENE PLASTI PIPE AND TO COMPLY FBC CODE REFER TO NFPA Imo' WATER HAMMER ARRESTOR 54-2012 TABLE 6.2(V) (ASSE 1010), GENERATOR ` 512,278 BTUH / 494 CFH PRESSURE PSII REGULATOR TO LESSTHANAN 1 PSI 2 .s A i IM INNER 12915 SW 132nd Street Unit 1 Miami, FL33186 P. 305.670.0820 F. M.233.9453 wwwt wgineeo.eom Bul Wei RE. LEEDO AP, CXA No. 5214E Eduardo Rama P.E„ LEMID AP No. 5aw Gregory M. Jeneen P.E., LEED® AP No. 63828 Ss A ........ � .. q r. ca ' � ��: S�ealNof ,PSoject�Ehglneer Z Z maw 0 , _4 U N 0 - a — Date of Issue:-- T — 12-07-2621 PERMIT. ISSUE -- -Rev No: -' 'Descrlptlon --- Date . . 1 BUILDING DEPT 2/18/22 ' BUILDING DEFT 3/3/22 SITE PLAN rn,By: XXked By: XX Job No: Scale: Sheet Number: Pal 1 NEW DRAWING. 1 CBS BUILDING CONCRETE EQUIPMENT PAD "!sl ,'b db GAS METER d CONCRETE NEQUIPMENT PAD o n C 0 r 5 Z ,dbh Ni d .y05 ,ry6b ELECTRIC D PANEL 4 g m� CLEAN 0 IL OUT '�, m 0 n d b. I METAL m LI 15 5d d IN 2' 2' eb ,4 bd pry. GAS METER D b 3' CONCRETE WALK tiyb LEGEND: b 223 CKD CHECKED BY CONC CONCRETE 9ti 9° DWN DRAWN BY FB/PG FIELD BOOK AND PAGE 13 28 SIR SET IRON ROD & CAP #6448 SNC SET NAIL AND CAP #6448 FIR FOUND IRON ROD FIP FOUND IRON PIPE FNC FOUND NAIL AND CAP FND FOUND NAIL & DISC P.B. PLAT BOOK —X— CHAIN LINK/ WOOD FENCE ELEV ELEVATION NOTES: CBS CONCRETE BLOCK STRUCTURE A/C AIR CONDITIONER 1. NOT VALID WITHOUT THE SIGNATURE AND THE ORIGINAL RAISED SEAL 78.8� ELEVATION OF A FLORIDA LICENSED SURVEYOR AND MAPPER. GV GAS VALVE 2. LANDS SHOWN HEREON WERE NOT ABSTRACTED FOR RIGHTS —OF —WAY, FH FIRE HYDRANT EASEMENTS, OWNERSHIP, OR OTHER INSTRUMENTS OF RECORD. MLP METAL LIGHT POLE M/D.C.R. MIAMI/DADE COUNTY RECORDS 3. THIS SURVEY WAS DONE SOLELY FOR FACILITATE ARCHITECTURAL AND BFP BACK FLOW PREVENTER ENGINEERING DESIGN AND DOES NOT DEPICT THE JURISDICTION OF ANY MUNICIPAL, STATE, FEDERAL OR OTHER ENTITIES. CLP CONCRETE LIGHT POLE CPP CONCRETE POWER POLE 4. UNDERGROUND IMPROVEMENTS NOT SHOWN. ICV IRRIGATION CONTROL VALVE 5. ELEVATIONS SHOWN HEREON ARE BASED ON THE NATIONAL GEODETIC VERTICAL DATUM OF 1929. 6. BENCHMARK DESCRIPTION: MIAMI/DADE COUNTY BENCHMARK # N-566 ELEVATION= 10.78' COUSINS SURVEYORS & ASSOCIATES, INC. 3921 SW 47TH AVENUE, SUITE 1011 DAVIE, FLORIDA 33314 CERTIFICATE OF AUTHORIZATION : LB # 6448 PHONE (954) 689-7766 FAX (954) 689-7799 CLIENT BARRY UNIVERSITY RARRY UNIVERSITY ADRIAN PHYSICAL PLANT lCL g I L �� L SITE �� I l it o —rJ II II 2 - Miami Shores I 1 SPECIFIC PURPOSE SURVEY FOR AREA TO RELOCATE FINE ARTS GENERATOR LOCATION MAP (NTS) I HEREBY CERTIFY THAT THE "SPECIFIC PURPOSE SURVEY" OF THE HEREON DESCRIBED PROPERTY IS TRUE AND CORRECT TO THE BEST OF MY KNOWLEDGE AND BELIEF AS SURVEYED IN THE FIELD UNDER MY DIRECTION IN FEBRUARY, 2022. 1 FURTHER CERTIFY THAT THIS SURVEY MEETS THE MINIMUM TECHNICAL STANDARDS FOR SURVEYING IN THE STATE OF FLORIDA ACCORDING TO CHAPTER 5J-17 OF THE FLORIDA ADMINISTRATIVE CODE. PURSUANT TO SECTION 472.027, FLORIDA STATUTES. THERE ARE NO ABOVE GROUND ENCROACHMENTS OTHER THAN THOSE SHOWN HEREON, SUBJECT TO THE QUALIFICATIONS NOTED HEREON. FOR THE FIRM, BY: - - - - - - `- -d� RICHARD E. COUSINS PROFESSIONAL SURVEYOR AND MAPPER SURVEY DATE 02/15/22 FLORIDA REGISTRATION NO. 4188 R E V I S 1 0 N S DATE FB/PG j DW—N CKD SPECIFIC PURPOSE SURVEY 02/15/22 SKETCH �JD REC _ � I PROJECT NO: 7026-13 (SCALE : 1" = 10' SHEET 1 OF 1 SHEET i " PUF'pUSE Cgs BUILDING 3 W N 4A WE M_A�am K ots 100102ML-wom m-RA IN 0 CONCRETE - EQUIPMENT PAD w t oil N t 0 �ACREV,5. k, R, AUIPMENT PAD W I _ A,* M9 1_1511 ELECTRIt PANEL 'B o CLEAN OUT i al io arra NIS IM .54 -M i,. =10 "M GAS METER I pow-111110A 95rk CONCRETE WALL CONCRETE WALK LEGEND:, CKD -...CHECKED* BY CONC CONCRETE: •DWN BY- - LOCATION:. MAP (NETS) ;QPAWNi FB/PG: FIELD BO.OK AND'--PAGL., d" 8�11­. I --t Z -8 -S IRON .644' ROD & CAP��# - -SET 'NAIL AND CAP SNC #6448 y. w FIR FOUNIJ IIRON POD AIL FIP FOUND',4RON PIPE FNC FOUND ;NAIL jt��CAP D NAILII__�'& D'iSC d' ND FND P. B. PUT BOOK 4 _X_ -CHAIN I N­K/ WOOD .-REINCE _'-_:ELCV- MON :1LEV NOTES: C.0 NCRETF BLOCK--STRU- CBS A/C AIR' tON M 'I Ojq.E R `T HE E SIGNATURE AND THE ORIGINAL RAISED ;SEAL 71. NOT VALID '0' `FLORIDA LICENSED SURVEYOR::AND. 'MAPPER. F. A�' EIL0 GV GAS VALVE NOT ABSTRACTED FOR RIGHTS -OF -'WAY, 2. LANDS SHOWN HEREON WERE FH` FIRE HYD RAN AI.. EASEMENTS, OWNERSHIP, OR OTHER INSTRUMENTS -OF RECORD. - LIGHT POLE I HEREBY CERTIFY THAT THE SPE*0117it": 'PURPOSE'- SURVEY"- OF -THE HEREON MLP METAL_ 4 D. C. MIAMi/'!­D'ADE COUNTYREC�VDS`­, DESCRIBED PROPERTY IS TRUE AND CORRECT 'TO- THE BEST OF MY R 3. t THIS SURVEY WAS DQNE SOLELY FOR FACILITATEARCHITECTURAL AND K KNOWLEDGE AND BELIEF AS -SURV"'EYED IN THE FIELD UNDER MY DIRECTION B.FP BACK DOSS -ANY ..ENGINEERING DESIGN 'AND .S.-.NOT DEPICT THE JURISDICTION' OF'. LOW PREVENTER! IN FEBRUARY, 2022.;�'I FURTHER CERTIFY THAT THIS SURVEY MEETS THE MUNICIPAL; STATE, FEDERAL OR -OTHER ENTITIES, GLP CONCRETE LIGHT ROLE MINIMUM TECHNICAL STANDARDS FOR.: STATE OF FLORIDA CPP CONCRETE -POWER ��'POLE'.SURVEYING IN THE :ACCORDING TO CHAPTER 5J-17 0. F­ THE '`FLORIDA ADMINISTRATIVE CODE. 4. UNDERGROUND IMPROVEMENTS SHOWN, -CONTROL-VAL PURSUANT TO SECTION 472.02-7, FLORIDA STATUTES. THERE ARE NO ABOVE ...... ICV IRRIGATION GROUND ENCROACHMENTS OTHER THAN THOSE SHOWN HEREON, SUBJECT TO RE BASED :ON THE NATIONAL GEODETIC A. N� 5. -ELEVATIONS HEkItO "`QUALIFICATIONS :N OTt D HEREON.-, THE V.ERTICAL DATUM OF 1 4. yBENC-HMARK iD ` ESCRiPTION: MIAMI/DADE COUNTY BENCHMARK # N-566 ELEVATION- 10;78 frVAT( FOR THE FIRM, BY: - - - - - - - - - - - - - - - - - - - - - RI -HARD E.,COUSINS A --P.ROFESSIONAL SURVEYOR AND MAPPER SURVEY DATE: .02/1-5/22 -�.�-.,.:FLORIDA' R'E.GIS-TRATION NO. 4188 - W, & CLIENT Ag..p st U. tlio D: R.-�. V I S 1 0 N, S 4,.DATE _.Go U S1 -ASSOCIATES. INC. FE _0�0 6WN CKD SHEET NS SURVEYOR�S; SPECIFIC H JD REC SW 47 �kETC 10 11 :0VRP6Si SORVEY D2/15 Rz ..,3921 BARRY UNIVERSITY -RP S. ��SURVEY -13 TKAVENU�,,I§QIT'E SPECIFIC �'PU PROJECT NO: 7026 _7 L5btk pbo4i800;j5* 'and�,Zcojrfomlaj�qsqutdbl OF */2 022 E1R MTER F �.AOH LB :-#:�'644 _1=01 -R� :-AREA EA`: TO*�RELOCAT E FINE utir-Y OP. [P `O�ONRW UNIVERSITY A DRIA N ;PHYSICAL PLANT ,O.RIZATION _7766 FAI,"�, .689.-, 7.7 _PHONE 95 5 4) 6 8 9�4,7-7 9 9 AREA -ARTS ;!G-E, E,.=. -OR 31 - N� R AT SCALE F-RiAS, JOSE 5/2 1 4/2022 9:51:23 AN FIRE Reference Only... SNEE a