RF-19-499Miami Shores Village
10050 NE 2 Ave
Miami Shores FL 33138
305-795-2204
Location Address
384 NE 94TH ST, Miami Shores, FL 33138
Contacts
Issue Date: 03/07/2019
Parcel Number
1132060136140
Permit No.: RF-03-19-499
Permit Type: Roof
Work Classification: Tile
Permit Status: Approved
Expiration: 09/03/2019
PENN DAVIS Owner T&S ROOFING SYSTEMS INC. Contractor
54 NW 94 ST, MIAMI SHORES, FL 33138 LOUIS TOLEDO
Other: 3057510325 1461 NW 23 ST, MIAMI, FL 33142
Business: 3052652654
Other:3057727954
Description: RE -ROOF TILE Valuation: $ 51,000.00 Inspection Requests:
762-4949
Total Sq Feet: 6,000.00
Fees
Amount
Application Fee - Other
$50.00
CCF
$30.60
DBPR Fee
$5.63
DCA Fee
$3.75
Education Surcharge
$10.20
Roofing Fee
$325.00
Scanning Fee
$9.00
Technology Fee
$9.38
Total:
$443.56
Building Department Copy
Payments
Date Paid Amt Paid
Total Fees
$443.56
Check # 35876
03/07/2019 $443.56
Amount Due:
$0.00
In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations
pertaining thereto and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores
Village. In accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate
permits are required for ELECTRICAL, PLUMBING, MECHANICAL, WINDOWS, DOORS, ROOFING and SWIMMING POOL work.
OWNER FFIDAVIT: I rtify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws
regulati g con uction zo _ ing. Futhermore, I authorize the above %nedntractor to do the work stated.
Ic �� .5 r �Z0Iq
Authoriz - nature: O er / Applicant / Contractor Agent Date
March 07, 2019 Page 2 of 2
i
ACB2 Engineering Inc.
Testing & Engineering Services
Certificate of Authorization # 8131
Tel: 954-245-8976 Fax: 954-301-7776
5230 NE 18TH Avenue
Fort Lauderdale, FL 33334"
Roof Tile Uplift Test Report
Attention: Miami Shores Village, Building Division,
10050 NE 2nd Avenue, Miami Shores, FL 33138
Client: T&S Roofing
Test Date: 07/22/2019
Permit # RF-03-19-499
Property Address: 384 NE 94 Street, Miami Shores, FL
Roof Pitch:
Type of Tile:
Roof Area:
4 in 12
Santa Fe Roof Tile
60.00 squares
Tile Attachment Method:
Two Component Polyurethane Foam Adhesive -Poly Pro H 160
Field Instrument :
IMADA Force Gauge 0-100 Serial number: 243454
Test Location
Total Number of Tests
Field Uplift Pull Test
Test results
Perimeter Area: (T1-T20)
20.00 sq. 20
As per FBC 2017
Passed
Field Area: (T21-T60)
40.00 sq. 40
As per FBC 2017
Passed
No. of Corner (T61-T86)
26 26
As per FBC 2017
Passed
Ridge Areas: (T87-T101)
150 PCs 15
As per FBC 2017
Passed
Important:
These laboratory results can change due to future weather impacts and/or unavoidable roof
traffic. Therefore, this report represents the TAS 106 results at the time of the test.
Please see attached a Roof Sketch for this project.
Cordially,
eering Inc. (NOA 09-1005.01)
Acevedo, PE
No: 36466
0-�/Z4 20/?
• • Im
Fed Lse�m---s-l-.FJod&M34 ..
�2
P2 125 F=c ((954)3-0l 7 )6
QS
F4-
r3 I
12
-
$-9
.'
5
-
3 �
29
I $
3-0
NN
2�
.,
2S
V
>S3
-3
BUILDING
PERMIT APPLICATION
Miami Shores Village
Building Department RECEIVE®
10050 N.E.2nd Avenue, Miami Shores, Florida 33138 MAR 0 i 10;9
Tel: (305) 795-2204 Fax: (305) 756-8972
INSPECTION LINE PHONE NUMBER: (305) 762-4949
FBC 201--
Master Permit No. �f - 02 "1��
Sub Permit No.
r-IBUILDING ❑ ELECTRIC ❑ ROOFING ❑ REVISION ❑ EXTENSION RENEWAL
PLUMBING ❑ MECHANICAL PUBLIC WORKS ❑ CHANGE OF CANCELLATION ❑ SHOP
CONTRACTOR DRAWINGS
JOB ADDRESS:
City: Miami Shores — 1 1 N [ u County: Miami Dade Zip:
?j-IR Folio/Parcel#: �\_ _M I Is the Building Historically Designated: Yes NO
Occupancy Type: Load: Construction Type: Flood Zone: BFE: FFE:
OWNER: Name (Fee Simple Titlehold ): Vqy) ) Phone#:
Address: A��(� /_ C t
City: M i� m'% 2 O I Q J State: L Zip: _ J1 39
Tenant/Lessee Name: Phone#:
Email:
CONTRACTOR: Company Name:
Address: NO N W 2.
City:
Qualifil Name:
State Certification or Registration #:
cGjcIV
ne#: —3Gj
_State: �� Zip:
Phone#:
2 Certificate of Competency #:
DESIGNER: Architect/Engineer: Phone#:
Address: City: State: Zip:
Value of Work for this Permit: $ I QQd Square/Linear Footage of Work: �CJCJ
Type of Work: ❑ Addition ❑ Alteration� ❑ New ElRepair/Replace ❑ Demolition
Description of Work: a Poo ( I l '(
Specify color of color thru tile: a e ( f () (,0i'1
Submittal Fee $ Permit Fee $ CCF $ CO/CC $
Scanning Fee $ Radon Fee $ DBPR $ Notary $
Technology Fee $
Structural Reviews $
Training/Education Fee $
Double Fee $
Bond $
TOTAL FEE NOW DUE $
(Revised02/24/2014)
,
Borlding Company's Name (if applicable)
Bonding Company's Address
City
State
Mortgage Lender's Name (if applicable)
Mortgage Lender's Address
City
State
Zip
Zip,
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS,
FURNACES, BOILERS, HEATERS, TANKS, AIR CONDITIONERS, ETC.....
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING
YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved and a reinspection fee will be charged.
*
Signature �� — Signature
OWNER or AGENT
The foregoing instrument was acknowledged before me this
day of a 20 by
J 1 S who is personally known to
me or who has produced as
CONTRACTOR
The fgregoiinenstrument was acknowledged befor a this
/�J day of 9 a (C�- 20 by
G who is personally known to
me or who has produced as
identification and who did take an oath. identification and who did take an oath.
NOTARY PU
Print:
***********
Zoning
(Revised02/24/2014)
Structural Review Clerk
3/7/2019 Property Search Application - Miami -Dade County
41
ONFICE OF THE PROPERTY APPRAISER
Summary Report
Property Information
Folio:
11-3206-013-6140
384 NE 94 ST
Property Address:
Miami Shores, FL 33138-2832
PENN E DAVIS TRS
PENN E DAVIS REVOC LIVING TR
Owner
MICHELLE S CANERO TRS
MICHELLE S CANERO REVOC
LIVING TR
384 NE 94 ST
Mailing Address
MIAMI SHORES, FL 33138 USA
PA Primary Zone
1100 SGL FAMILY - 2301-2500 SQ
0101 RESIDENTIAL - SINGLE
Primary Land Use
FAMILY: 1 UNIT
Beds / Baths / Half
5/5/0
Floors
1
Living Units
1
Actual Area
Sq.Ft
Living Area
Sq.Ft
Adjusted Area
5,875 Sq.Ft
Lot Size
25,400 Sq.Ft
Year Built
1925
Assessment Information
Year
2018
2017
2016
Land Value
$761,638
$761,638
$635,034
Building Value
$285,525
$285,525
$285,525
XF Value
$19,082
$19,082
$19,082
Market Value
$1,066,245
$1,066,245
$939,641
Assessed Value
$819,262
$802,412
$785,908
Benefits Information
Benefit
Type
2018
2017
2016
Save Our Homes
Cap
Assessment
Reduction
$246,983
$263,833
$153,733
Homestead
Exemption
$25,000
$25,000
$25,000
Second Homestead
Exemption
$25,0001
$25,0001
$25,000
Note: Not all benefits are applicable to all Taxable Values (i.e. County, School
Board, City, Regional).
Short Legal Description
MIAMI SHORES SEC 1 AMD PB 10-70
LOTS 1 TO 4 INC BLK 46
LOT SIZE 200.000 X 127
OR 9909 1258 1277 3
Generated On : 3/7/2019
Taxable Value Information
2018
2017
2016
County
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
$769,262
$752,412
$735,908
School Board
Exemption Value
$25,000
�$25000$25,000
Taxable Value
$794262
$760,908
City
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
$769,262
$752,412
$735,908
Regional
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
$769,262
$752,412
$735,908
Sales Information
OR
Previous
Price
Book-
Qualification Description
Sale
Page
01/28/2017
$100
30407-
Corrective, tax or QCD; min consideration
2489
07/17/2012
$740,000
28191
Qual by exam of deed
3475
09708-
Sales which are disqualified as a result of
03/01/1977
$1
1763
examination of the deed
00000-
Sales which are disqualified as a result of
02/01/1976
$1
00000
examination of the deed
The Office of the Property Appraiser is continually editing and updating the tax roll. This website may not reflect the most current information on record. The Property
Appraiser and Miami -Dade County assumes no liability, see full disclaimer and User Agreement at http://www.miamidade.gov/info/disclaimer.asp
Version
SECTION 1524
HIGH VELOCITY HURRICANE ZONES — REQUIRED OWNERS NOTIFICATION FOR ROOFING
CONSIDERATIONS
1524.1 Scope. As it pertains to the section, it is the responsibility of roofing contractor to provide the 9"ervith
the required roofing permit, and to explain to the owner the content of the section. The ly'ovigibps of Se"M R4402' • • •; •
govern the minimum requirements and standards of the industry for roofing system installation?. Additidnally;the
'.
following items should be addressed as part of the agreement between the owner ant the Mractor. The
initial in the designated space indicates that the item has been explained. `•"• owner's
'
.... ....
. .
.... ....
...... ...
.....
.
2. Renailing wood decks: When replacing roofing, the existing woed roof`deck may 6ieve to
.....
0 • ....
be renailed in accordance with the current provisions of Section R4403. (The rq *tt is usually
• •
concealed prior to removing the existing roof system). 0 0 0•
• • • • •
2�4.
Exposed Ceiling: Exposed, open beam ceilings are where the underside of the roof decking
can be viewed from below. The owner may wish to maintain the architectural appearance; therefore,
roofing nail penetration of the underside of the decking may not be acceptable. This provides the option of
maintaining the appearance.
6. `J.-Overflow scuppers (wall outlets): It is required that rainwater flows off so that the roof is
not overloaded from a buildup of water. Perimetededge wall or other roof extension may block this
discharge if overflow scuppers (wall outlets) are not provided. It may be necessary to install overflow
scuppers in accordance with the requirements of Sections R4402, R4403 and R4413.
iIA'a'
ent's Signature Date Co tr for Signature Date
Property Address
Revised on 7/9/2009 LD;07/01/2015;
Permit Number
Miami Shores Village
Building Department
10050 N.E.2nd Avenue
Miami Shores, Florida 33138
Tel: (305) 795.2204
Fax: (305) 756.8972
OWNERTS AFFIDAVIT OF EXEMPTION 0000
ROOF TO WALL CONNECTION HURRICANE MITIGATION RETROFIT FOR f.XL&JING SITE4-
BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES ......
PERSUANT TO SECTION 553.844 F.S.
To: Miami Shores Village Building Department
10050 NE 2nd Ave
Miami Shores, FI 3313ti
Re: Owner's Name:
Property Ad
Roofing Permit Number:
......
......
.... .... . .
•
D;te a�
. . . . ......
.... %
Dear B�Tq
g Officia
I r certify that I am not required to retrofit the roof to wall connections of my
building because:
The just valuation for the structure for purpose of ad valorem taxation is less than $300,000.00. Please attach proof of ad
valorem taxation.
o The building was constructed in compliance with the provisions of the Florida Building Code (FBC) or with the provisions
of 1994 edif of the South Florida Building Code (1994 SFBC)
Signature Print Name
State of Florida
County of Dade
The undersigned, being the first duly sworn, deposes and says that he/she is the owner for the above property mentioned.
Sworn to and subscribed before me this
Notary Public, Sate of Florida at Large
gpAmy t!—
N `suR�1
20G
2.0762
C001331pN5,2022 9TVPE3:01 nrcUnd
• When the just valuation of the structure for p of ad valorem taxation is equal to or more than $300,000,00, and the building was not constructed with FBC nor a 1994
SFBC. Then you must provide a building application from a General Contractor for the Roof to Wall connection Hurricane Mitigation.
Revised on 5/21/2009
2/14/2019
Property Search Application - Miami -Dade County
OFFICE OF THE PROPERTY APPRAISER
Summary Report
Property Information
Folio:
11-3206-013-6140
384 NE 94 ST
Property Address:
Miami Shores, FL 33138-2832
PENN E DAVIS TRS
PENN E DAVIS REVOC LIVING TR
Owner
MICHELLE S CANERO TRS
MICHELLE S CANERO REVOC
LIVING TR
384 NE 94 ST
Mailing Address
MIAMI SHORES, FL 33138 USA
PA Primary Zone
1100 SGL FAMILY - 2301-2500 SQ
0101 RESIDENTIAL -SINGLE
Primary Land Use
FAMILY: 1 UNIT
Beds / Baths / Half
5/5/0
Floors
1
Living Units
1
Actual Area
Sq.Ft
Living Area
Sq.Ft
Adjusted Area
5,875 Sq.Ft
Lot Size
25,400 Sq.Ft
Year Built
1925
Assessment Information
Year
2018
2017
2016
Land Value
$761,638
$761,638
$635,034
Building Value
$285,525
$285,525
$285,525
XF Value
$19,082
$19,082
$19,082
Market Value
$1,066,245
$1,066,245
$939,641
Assessed Value
$819,262
$802,412
$785,908
Benefits Information
Benefit Type 1 2018 2017 2016
Generated On : 2/14/2019
Taxable Value Information
2018
201
22016
County
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
1 $769,262
$752,412
$735,908
School Board
Exemption Vale • •: :
: • • $2�i3OBO
• • $25,000
$25,000
Taxable Value •. •: ;
; ; 3*079:,2$2
• • $777,412
$760,908
City
Exemption Vilye ...
• • $50,000
• $50,000
$50,000
Taxable Val•!@ •
•
+ : *69,2k
: :$752,412
$735,908
. • •• . • . . • •
Regional . . . • • • . • •
Exemption Value
$50,000
$50,000
$50,000
Taxable Value*:*
Ip7ft,42
$752,412
$735,908
. .. .. . . . .. ..
Sales Information. ... .
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
Florida Building Code 5th Edition (2014)
i
High -Velocity Hurricane Zone Uniform Permit Application Form.
1
1
Section A (General Information)
1
1
Master Permit No. Process No.
1
1
Contractor's Name's
....
1
Job Address
21� . . ....
..
... I..
•
......
.. ..
... ..
ROOF CATEGORY ••••••
1 •
❑ Low Sloe "" ""
P ❑ Mechanically Fastened Tile MortarlfgjiDVV1e Set Tiffs„ •
•
O Asphaltic Shingles ❑ Metal Panel/Shingles ❑ Wood SK09lef/Shak25• •,
,,,1,
• • 0 1 •
❑ Prescriptive BUR-RAS150 " " "
"'j;'
ROOF TYPE • • •
•
•..�.•
New roof ❑ Repair ❑ Maintenance ❑ Reroofing , El Recovering
ROOF SYSTEM INFORMATI 0 : . 0 •.
0 1 '
Low Slope Roof Area (SF) Steep Sloped Roof AREA (SSF)M Total (SF)_L6"
1
i
Section B (Roof Plan)
1
Sketch Roof Plan: Illustrate all levels and sections, roof drains, scuppers, overflow scuppers and overflow drains. Include dimen-
sions of sections and levels, clearly identify dimensions of elevated pressure zones and location of parapets.
1
i
ME ME■■■■■■■■■■■■■■■■■■■■■■■
■■■■■■■■■■■■■■■■■■■■■■
MEMO
MEN■M■MA■r/)�7■■■■■■■■■■■MEN
■■■■■M■L.�MNONE /�■■■M■■■
IN ME
ME No
ONEMENE ON: Now go No
MEN ME ME ME MEN No
NONE ME No
MEMO so ■■■■■■■■■■■■■
MEN so M M IN ONE
■MMOMEN OMOE■MIMEN ■M■MOM■■
MENIMM■M■MO■EEMMEN ■OMEN M■■
■■■■■■■■�■■■■■EMEN E■■
FLORIDA BUILDING CODE — BUILDING, 5th EDITION (2014) 15.37
r I I I ' CoPyrigbt to, or licensed by. ICC (ALL RIGHTS RESERVED); accessed by Eliezer Palacio on Jun 8, 2015 10:32:12 AM pursuant to license
Agreement. No further reproductions authorized.
1,26,AEAGLErIEW
Y
LLI V V 1 fl UJLM%JRhU"I
Total Line Lengths:
Ridges = 157 ft
Hips =79ft
Premium Report
1/18/2018
Claim: Libutti
Valle 4 Flashing = 173 ft` R E C E � � f ED
Rakes = 278 Step flashing = 168 ft
Eaves = 754 ft Parapets = 148 f'AP 6 I -wnr
have been removed for readabilitV.'�PIUs signs preface some -numbers to avoid confusion when rotated (e.g. +6 and +9).
m O 2008-2018 Eagle'Aew Technologies, Inc. and Pictoetry International Corp. — All Rights Reserved — Protected by European Patent Application No. 10162199.3 — Covered by one or more of U.S. Patent Nos. 8,078,436; 8,145,578; 8,170,840;
8,209,152; 8,515,125; 8,825,454; 9,135,737; 8,670,961; 9,514,568; 8,818,770; 8,542,880; 9,244,589; 9,329,749; 9,599,466. Other Patents Pending.
PAGE 4
-
r Mlama-Dade County HVHZ Electronic rloof {ParnO Form
1 Section D Tile Roof System
(%Ji31 ✓e';df: i.`��ience Ev r f� f lit ,
Roof System Manufacturer: ISAN I A FE TILE CORP ^�
Notice of Acceptance Number (NOA):
Minimum Design Wind Pressures, If Applicable (from RAS 127 or Calculations):
1100.7
P 1: 39.1
P 2: 68.1 P 3: . . ....
......
Maximum Design Wind Pressures, (From the NOA Specific
system): �61.9 psf •. •: • • •. • •
"""
Fiji in fife specific roof assen7bly componen;`s. ifa comoonant is not regwire-J, ins er i noL applicable a text bp,;c,.
� • • • • •
I -
.... ....
..
Deck Type: -5/8 Plywood..
.....
.....
_ _;= • •�'; _ ..
i ..
Optional Insulation:
• • • • • •
0 0 0:
,1Optional
Nailable Substrate:
- —
Optional Nailable Substrate Attachment:
Roof Slope: 712"
Roof Mean Height: ,15_.. ft.
Method of Tile Attachment:
-Adhesive, Medium Paddy Polyfoam Polypro- o�
Alternate Method of Tile Attachment per NOA:
i
Drip Edge Size &Gauge: '--3" fiace 26 ga.--
Drip Edge Material Type: 1--Galvinized Metal--
Drip Edge Fastener Type: 111 1/4 RS NAILS
Hook Strip/Cleat gauge or weight: `--Select Hook Strip
--
Basesheet Type:
#30 ASTM TYPE If
Fastener Type for Basesheet Attachment:
1',11 1/4 RS NAILS 6" OC AND 12" FIELD
Tile Underlayment (Cap Sheet) Type:
'BORAL TILE SEAL — I
Tile Underlayment•Attachment Method:
SELFADHERED
Tile
Profile:
SPAN1SH "S"
�,,jx ai-lhg, Eyce!feyi ce Every Day"
Miami -Dade County FgVHZ F-orm -
Section E (Tile Calculations,3
Method I "Moment'Based Tile Calculations P-ar RAS 127"
For Moment based tile systems, use Method. 1. Compare the values for Nirvith f.1-16 values from Mf. if the Mf values are
greater than or equal to the Mr values, for each area of the'roof, then the tile attachment method is acceptable.
P 1: XX Mg: Mr 1: [-5 < NOA*%f. . ......
Mg: IV, r2-: 53-1:511 NOA"i... 0
P 2: x XEI EE - ......
0000 *000 0
Zj il 00.7 Mg: Mr3-: i6i .9. NOAU. o o •... so o..o.
P 3: x 1 0
00:09: 0 000:::::o
Method 3 "Uplift Based Tile Calculations Pe67 RAS 127" ::.::o so* so
: o : 6, o e*oo:o
' the F'v,a1L10 are greaterthen or equal to Velflrovglues, fQr
or Uplift based tile systems use Method 3. Compare the values for F'Vith the values for Fr. 11 o
)@ch area of the roof, then the tile attachment method is acceptable. Cll,. so 6 so :Goes:
a o
o*oo
x 1: x w: -W. x C-os 0: Frl: NOA P
x w: -W: x Cos e:
NOA F
x W.- -W: I = x Cos 8: 'Fr3: NOA F
Where to Obtain Information to complete tile, calculations
IVYKere t6 Find
Description
SYM601
Table I RAS 127, or by an engineer analysis- prepared, signed and sealed by a professional
Design Pressure
P1 or P2 or P3
engineer based on ASCE 7.
Mean Roof Height
Hi
Site
Roof Slope
—Pob-Slte
Aerodynamic Multiplier
Produc"Approval (NOA)
Restoring Moment due to Gravity
M
-
Product Approval "(NOA)
117-
Attachment Resistance
Mf
-.Proeluc'C��pprt?v al -(NOA)
,Rpqulred Moment Resistance
Mr
'Calculated'
Attachment Resistance
A111rd-murn Att
F'
— Pro I �hu Approval (NOA)
Ra:aired Uplift Resistance
Fr
Average Tile Weight
W
Prdddct-Approval (NOA)
Tile Dimensions
I length
Produc.Fxpproval (N'OA)
w = width
M I® DiADE
MIAMI-DADE COUNTY
�
PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
11805 SW 26 Street, Room 208
BOARD AND CODE ADMINISTRATION DIVISION
Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA)
www.miamidade.aov/economv
Santafe Tile Corporation
8825 NW 95' Street
Medley, FL 33178
sees
. . ee.e
SCOPE: .eeeee � •
This NOA is being issued under the applicable rules and regulations governing the use of construction rnatesia:s. The
documentation submitted has been reviewed and accepted b Miami -Dade County RER - Go****
o • • t Control �ecfion to •
p Y tY i4S�� . o
be used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction AH • • • • • •
.... .... .....
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County.RwAict Cgpgol $ectiorl,:,, •
(in Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve tke sight to have'th:s Osseo*
product or material tested for quality assurance purposes. If this product or material fails to.Tei faV in the accepted e
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately reltoke, tppoit, or • • • • o •
suspend the use of such product or material within their jurisdiction. RER reserves the riglt to -(evoke this :....:
acceptance, if it is determined by Miami -Dade County Product Control Section that this product or material'fails to •
soee
meet the requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Santafe Spanish `S' Clay Roof Tile
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any
section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be
done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA No. 15-0915.09 and consists of pages 1 through 5.
The submitted documentation was reviewed by Freddy Semino N
MIAMFDADE COUNTY NOA No.: 18-0604.04
Expiration Date: 02/01/21
Approval Date: 08/02/18
Page 1 of 5
ROOFING ASSEMBLY APPROVAL
Category: Roofing
Sub -Category: Roofing Tiles
Material: Clay
Deck Type: Wood
1. SCOPE
This approves a roofing system using Santa Fe "Santafe `S" Clay Roof Tile, as manufactured by Ladrillera
Santafe S.A. in Bogota, Colombia and distributed by Santafe Tile Corporation as described in SectioigZQf this
Notice of Acceptance. For locations where the pressure requirements, as determined by applicable*RYilding ......
Code, do not exceed the design pressure values obtained by calculations in compliance with RAS 12' us irr:g the • •
values listed in section 4 herein. The attachment calculations shall be done as a momeilf Wed systeftf. • • • • • • • •
.... .... . .
. PRODUCT DESCRIPTION .... .....
. ... .
Manufactured by Test Pro ufit•.... . ..... • • 0 : 0 •
Applicant Dimensions Specifications Desczip" •
Santafe `S' Clay Roof L = 18" TAS 112 One piece high profile clap roof tile eqp��with ......
Tile W = 11.1 " Type I two nail holes. For nail-o$, mortar set'and adhesiv$ . . , •
Thickness = 0.39" Grade 1 set applications.
Trim Pieces 1= varies TAS 112 Accessory trim, clay roof pieces for use at hips,
w = varies rakes, ridges and valley terminations. Manufactured
varying thickness for each tile profile.
2.1 MANUFACTURING LOCATION
1. Bogota, Colombia
2.2 SUBMITTED EVIDENCE
Test Agency
Test Identifier
Test Name/Report
Date
The Center for Applied Engineering, Inc.
94-156-8
TAS 101
Aug. 1994
94-156-9
TAS 102
The Center for Applied Engineering, Inc.
25-7205-1
TAS 101
March 1995
The Center for Applied Engineering, Inc.
Project: 07-07-00-91
TAS 100
Sept. 1994
(307023)
Redland Technologies
7161-03
TAS 108
Dec. 1991
Appendix II
(Nail -On)
Redland Technologies
7161-03
Static Uplift Testing
Dec. 1991
Appendix HI
TAS 102 & TAS 102(A)
Redland Technologies
P 0402
Withdrawal Resistance
Sept. 1993
Testing of Screw vs smooth
shank nails
Redland Technologies
P 0647-01
TAS 108
Aug. 1994
(Mortar Set)
NOA
No.: 18-0604.04
M'AMI•DADE COUNTY
Expiration Date: 02/01/21
Approval
Date: 08/02/18
Page 2 of 5
2.2 SUBMITTED EVIDENCE
Test Agency Test Identifier Test Name/Report Date
Redland Technologies P 063 1 -01 PA 108 July. 1994
(Mortar Set)
Celotex Corporation Testing Services 520305-01 thru 05 PA 102 June 1999
IBA Consultants, Inc. 2353-4 Restoring Moment Aug. 1999
PRI Asphalt Technologies, Inc. SFTC-003-02-01 TAS 101 12/06/02
IBA Consultants, Inc. 2353-70 TAS 101 t9lg2/03
. . .... ......
IBA Consultants, Inc. 2353-71 TAS 101..' . 09/2.2/03
IBA Consultants, Inc. 2353-93 ASTM C 1 MI : • � ' 1 71?8/05 ....
• •
American Test Lab of South Florida RT0624.01-15 ASTM C1167.03 • • • • Ur7101/15
PRI Construction Material Technologies COPO-002-02-08 TAS 101 .... • 14f2/16 • •...
• ... • • 0090 • • I • • .
• • • • • • • • • • • •
3. LIMITATIONS • • • • • • ' •
•
3.1 Fire classification is not part of this acceptance. • • • ... ......
3.2 For mortar or adhesive set the applications, a static field uplift test shall be peff�ot'In�d in apco;dance w•t't• • •
TAS 106. •
3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform quarterly test
in accordance with TAS 112, appendix `A'. Such testing shall be submitted to the Miami -Dade County
Product Control Section for review.
3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed
section 4.1 herein.
3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated
otherwise by the underlayment material manufacturers published literature.
3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with
applicable building code.
3.7 May be installed on slopes 7:12 and greater.
4. INSTALLATION
4.1 Santafe 'S' and its components shall be installed in strict compliance with Roofing Application Standard
RAS 118, RAS 119 and RAS 120.
4.2 Data For Attachment Calculations
NOA No.: 18-0604.04
MIAMM)ADECOUNTY Expiration Date: 02/01/21
6 1 Approval Date: 08/02/18
Page 3 of 5
Table 1: Average Weight (W) and Dimensions (I x w )
Tile Profile
Weight-W (Ibf)
Length -I (ft)
Width-w (ft)
Santafe 'S'
6.7
1.5
0.958
Table 2: Aerodynamic Multipliers— %(ft3)
Tile
Profile
). (ft3)
Batten Application
(ft)
Direct Deck
Santafe 'S'
0.274
0.297 .
Table 3: Restoring Moments due to Gravity - M9 (ft.-Ibf) '
...... .. ..
Tile
Profile
2":121'
3"•12"
4"•12"
5":12"
611.4-A•
•••••
7":12" or.
0.
•gre ter •
Battens
Direct
Deck
Battens
Direct
Deck
Battens
Direct
Deck
Battens
Direct
Deck
Battens•
••
"rect
k
Bdtt M
•••
Direet-
Deck•
Santafe 'S'
5.93
5.90
5.85
5.82
5.73
5.69
1 5.56
5.53
1 5.32• •
-3.29
5.03• •
5.09•
Table 4: Attachment Resistance Expressed as a Moment - Mf (ft.-10
for Nail -On Systems
• • • • • • -
•Affens
Tile Profile
Fastener Type
Direct Deck
Santafe 'S'
2-10d Ring Shank Nails
21.8
N/A
One #8 Screw
29.16' 2
N/A
Two #8 Screws
38.28'
N/A
One #8 Screw w/ Clip
57.311.2
1 N/A
Two #8 Screws w/ Clip
57.60'
61.77'
1. Approved screws as noted 'Product manufactured by others'.
2. When using one screw it must be installed in the inside hole located nearest to the hump of the tile.
Table 5: Attachment Resistance Expressed as a Moment Mf (ft.-Ibf)
for Two Patty Adhesive Set Systems
Tile Profile
Tile Application 2
Minimum Attachment Resistance
Santafe 'S'
Tile Bond
38.93
Polyfoarn Polypro AH 160TM
33.1 4
2 See manufactures component approval for installation requirements.
3 Flexible Product, Inc. Average weight per patty 10.4 grams.
4 Polyfoarn Product, Inc. Average weight per patty 9.4 grams.
Table 5A: Attachment Resistance Expressed as a Moment - Mf (ft.-Ibf)
for Single Patty Adhesive Set Systems
Tile Profile
Tile Application 2
Minimum Attachment Resistance
Santafe 'S'
Polyfoarn Polypro AH 160Tm
66.55
Polyfoam Polypro AH 160'rm
63.8 6
DAP Foam Touch N Seal Storm Bond 2
1007
5 Paddy placement of 63 grams of
Polypro AH 160Tm.
6 Paddy placement of 24 grams of
Polypro AH 160TM.
7 Paddy placement of 45 grams DAP Foam Touch N Seal Storm Bond 2
NOA No.: 18-0604.04
Expiration Date: 02/01/21
Approval Date: 08/02/18
Page 4 of 5
Table 6: Attachment Resistance Expressed as a Moment - Mf (ft-lbf)
for Mortar or Adhesive Set Systems
Tile Profile Tile Application Attachment Resistance
Santafe 'S' Mortar Set 23.6
5. LABELING
5.1 All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo as shown below,
or following statement: "Miami -Dade County Product Control Approved".
sees
SANTA FE TM MADE IN COLOMBIA:•:•: •••�:•
see:se ee ee sees..
sees..
LABEL FOR SANTA FE SPANISH "S" CLAY ROOF TILE • • • • e e e e :so**:
sees ssse sees•
e.:..•
6. BUILDING PERMIT REQUIREMENTS sees.. ... s
ee ee e• sees..
6.1 Application for building permit shall be accompanied by copies of the followint! •: •: • •
• sees..
6.1.1 This Notice of Acceptance. sees..
6.1.2 Any other documents required by the Building Official or applicable buildingscode Inorder to %s e e
properly evaluate the installation of this system. 0009
• •
PROFILE DRAWING
"SANTAFE S" CLAY ROOF TILE
END OF THIS ACCEPTANCE
When using one screw
3e this hole.
NOA No.: 18-0604.04
Expiration Date: 02/01/21
Approval Date: 08/02/18
Page 5 of 5
M!®D�ADE
MIAMI-DADE COUNTY
�
PRODUCT CONTROL SECTION
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
11805 SW 26 Street, Room 208
BOARD AND CODE ADMINISTRATION DIVISION
Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA)
www.miamidade.gov/economy
Boral Roofing LLC.
7575 Irvine Center Drive, Suite 100
Irvine, CA 92618 ....
. . .... ......
SCOPE: •.
This NOA is being issued under the applicable rules and regulations governing the use of c8iftn etion materials. Tha • • • :.
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Pfddi%'t'Control Section tol).e�
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiclioo FAHJ).0*00
This NOA shall not be valid after the expiration date stated below. The Miami -Dade CountyVro%ct COn'lrol Sectiorf
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve moat * to have tl iss 0 * ":'
product or material tested for quality assurance purposes. If this product or material fails to;perfoi:n in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, 1315fly'ffor
suspend the use of such product or material within their jurisdiction. RER reserves the right -to revoke tki lac+,�eptanae,
if it is determined by Miami -Dade County Product Control Section that this product or material fails to inset the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: BORAL TileSeal
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed
by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then
it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This new NOA consists of pages 1 through 4.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 18-0502.03
Expiration Date: 08/02/23
Approval Date: 08/02/18
Page 1 of 4
ROOFING COMPONENT APPROVAL
Category: Roofing
Sub -Category: Underlayment
Material: SBS
PRODUCTS DESCRIPTION:
Test
Product
Product Dimensions Specification
Description
••••
BORAL TileSeal 36" x 36'
rolls TAS 103
SBS self -adhering asp%alt Sheet maierial with a ......
36" x 72'
rolls ASTM D1970
white glass re -enforced DblydSter stgfajintig fabric; • •
for use as an underlaymen$ iri sloped l bot* • • • • • •
assemblies. ....:
• • • • • • • •
• • •
Boral Citadel Plus 36" x 72'
rolls ASTM D1970
SBS self -adhering aspta*'t et mate:aNith a 00
0.
untjlaymgn ,poly flm-facer; for use aS chd-plye
••• in sloped roof assemblies,,... •
MANUFACTURIGN LOCATION:
• . .
••••••
1. Brentwood, NH.
....
2. Houston, TX.
EVIDENCE SUBMITTED:
Test Agency
Test Identifier
Test Name/Report Date
PRI Construction Materials
OCF-356-02-04
ASTM D1623 07/25/18
Technologies, LLC.
OCF-356-02-02
TAS 103 07/24/18
OCF-356-02-01
ASTM D1970 07/26/18
OCF-424-02-04
ASTM D1623 07/25/18
OCF-424-02-01
ASTM D1970 07/25/18
OCF-424-02-03
TAS 103 07/25/18
Trinity ERD
BRLRF-SC16810.11.17 ASTM D 1876 11/28/17
NOA No.: 18-0502.03
Expiration Date: 08/02/23
Approval Date: 08/02/18
Page 2 of 4
APPROVED ASSEMBLIES:
Deck Type 1: Wood, non -insulated
Deck Description: 15/32" or greater plywood or wood plank
System E(1): Anchor sheet mechanically fastened deck, membrane adhered.
Base Sheet:
One or more plies of ASTM D226 Type II or ASTM D2626 with a minimum 4" head lap and a
6" end lap mechanically fastened to deck with approved nails and tin caps 6" o.c. at the laps
and two staggered rows 12" o.c. the field of the roll.
Ply Sheet
. . .... ......
Apply one layer of Boral Citadel Plus over Base sheet as per current apprOval. . •
(Optional) •
• • • • • • .. .. ......
Membrane:
One or more plies of BORAL TileSeal Underlayment with a minimu o *T'ohead 1alimd •
minimum 6" end lap. Place the first course of membrane parallel to the eave, rolling the
membrane to obtain maximum contact. Remove the release memb;q%:; the membWo e is 0 0 * * 6
applied. Vertical strapping of the roof with BORAL TileSeal Underdayment is acceptable. All •
end laps and laps without black selvage area shall be sealed under ;ap using an FbBS modified...:.
mastic.
0.0
Note: When used in Tile roof systems BORAL TileSeal Underlayment shall be back'nailed to
deck with approved annular ring shank nails and tin caps at a maximum 12" o.c. at the side
laps. No nails or tin caps shall be exposed.
Surfacing: Approved for Adhered Roof Tile using TILE BOND or AH-160, Mechanically Fastened Roof
Tile, Metal Roofing, Wood Shake & Shingles, and Asphaltic Shingle assemblies.
NOA No.: 18-0502.03
Expiration Date: 08/02/23
Approval Date: 08/02/18
Page 3 of 4
LIMITATIONS:
1. Fire classification is not part of this acceptance.
2. This acceptance is for prepared roofing applications. Minimum deck requirements shall be in compliance with
applicable building code. BORAL TileSeal underlayment shall be installed in strict compliance with applicable
Building Code.
3. BORAL TileSeal underlayment shall be applied to a smooth, clean and dry surface with deck free of irregularities.
4. BORAL TileSeal underlayment shall not be applied over an existing roof membrane as a recover, but may be
applied over a roofing Base/Anchor sheet underlayment. ."
5. BORAL TileSeal underlayment shall not be left exposed as a temporary roof for longer t11av78V days 9f •, 00
• •
application. ... 0 .. ... ...
, •
6. The standard maximum roof pitch for BORAL TileSeal underlayment shall be 6:12 wheel 14? Are loaded'directly ;
to the BORAL TileSeal underlayment; loading boards or battens are required on roof pitchJ `&-xater than &12". •
7. Refer to Prepared Roofing system Product Control Notice of Acceptance for listed approval of this prpcduct yvith •, ; •
. .
specific prepared roofing products. • • • • .. ......
8. Tiles shall be stored on battens on roof pitches greater than 6:12". •
9. BORAL TileSeal underlayment may be used with any approved roof covering Notice of. cceptance ig"i-
BORAL TileSeal underlayment as a component part of an assembly in the Notice of Acceptance. If UORAL :go*-,:
TileSeal underlayment is not listed, a request may be made to the Authority Having Jurisdiction (AHJ}6619e
Miami -Dade County Product Control Department for approval provided that appropriate documentation is
provided to detail compatibility of the products, wind uplift resistance, and fire testing results.
10. All nails in the deck shall be carefully checked for protruding heads. Re -fasten any loose decking panels. Sweep
the deck thoroughly to remove any dust and debris prior to application.
11. When applying the membrane in the valley, start at the low point and work to the high point, rolling the membrane
from the center outward in both directions. For ridge applications, center the membrane and roll from the center
outward in both directions.
12. Roll or broom the entire membrane surface so as to have 100% contact with the surface, giving special attention to
overlap areas.
13. Flash vent pipes, stacks, chimneys and penetrations in compliance with Roof Assembly current Product Control
Notice of Acceptance and applicable Building Code.
14. All protrusions or drains shall be initially taped with a 6" piece of underlayment. This target piece shall be pressed
in place and formed around the protrusion to ensure a tight fit. A second layer of BORAL TileSeal underlayment
shall be applied over the underlayment, and sealed using an SBS modified mastic.
15. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
16. All membranes or packaging shall bear the imprint or identifiable marking of the manufacturer's name or logo, city
and state of manufacturing facility, and the following statement: "Miami -Dade County Product Control Approved"
or the Miami -Dade County Product Control Seal as shown below
MIAMI•DADE COUNTY
•
END OF THIS ACCEPTANCE
NOA No.: 18-0502.03
Expiration Date: 08/02/23
Approval Date: 08/02/18
Page 4 of 4
MIAMI-DADE COUNTY
WAKIC- M- PRODUCT CONTROL SECTION
a
11805 SW 26 Street, Room 208
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786)315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.nuanudade.eov/economv
ICP Adhesives and Sealants, Inc.
12505 NW 44" Street
Coral Springs, FL. 33065
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of eonstraction rnate'rials. TIl8' `; •
documentation submitted has been reviewed and accepted by Miami -Dade County RER -Prp� Vjtr �ontroi Sect ;on to be •
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiay.14"HJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade Coun4*Pr6duct Wi trBL Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve tt� ` to have V1s product:
or material tested for quality assurance purposes. If this product or material fails to perform ja%e. acceptedd iWer, tbi:
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, amod+ or suspend the use •
of such product or material within their jurisdiction. RER reserves the right to revo;e t6-i acceptance, if it.is.. ; .
determined by Miami -Dade County Product Control Section that this product or material falls tpVeet the requirements•
of the applicable building code. ; , .. •
....
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: ICP Adhesives Polyset® AH-160
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews NOA 16-0315.01 and consists of pages 1 through 11.
The submitted documentation was reviewed by Alex Tigera.
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 1 of 11
ROOFING COMPONENT APPROVAL:
Category: Roofing
Sub Category: Roof tile adhesive
Materials: Polyurethane
SCOPE:
This approves ICP Adhesives Polyset® AH-160 as manufactured by ICP Adhesives and Sealants, Inc. as described
in this Notice of Acceptance. For the locations where the design pressure requirements, as determined by applicable
building code, do not exceed the design pressure values obtained by calculations in compliance with Roofing
Application Standard RAS 127. For use with approved flat, low, and high profile roof tile sgsterrls usingd•.*Goo• •
Adhesives Polyset® AH-160. • • .
...... .. •• ......
PRODUCTS MANUFACTURED BY APPLICANT: • • • • •
�i.•J ••..••
Product Dimensions Test Produ&Dcsdriytiol •
Specifications .. • •
• •
ICP Adhesives N/A TAS 101 Two component polurethane foam'�dhesi• •; •
. ....
Polyset®AH-160 •
ICP Adhesives Foam N/A Dispensing Equipment • • • •
Dispenser RTF1000 • •
s
ICP Adhesives ProPack® N/A Dispensing Equipment 41.6
30 & 100
PRODUCTS MANUFACTURED BY OTHERS:
Any Miami -Dade County Product Control Accepted Roof Tile Assembly having a current NOA which list attachment
resistance values with the use of ICP Adhesives Polyset® AH-160 roof tile adhesive.
MANUFACTURING LOCATION:
1. Tomball, TX.
PHYSICAL PROPERTIES:
Proper Test Results
Density ASTM D 1622 1.6 lbs./ft.3
Compressive Strength ASTM D 1621 18 PSI Parallel to rise
12 PSI Perpendicular to rise
Tensile Strength ASTM D 1623 28 PSI Parallel to rise
Water Absorption ASTM D 2127 0.08 Lbs./Ft2
Moisture Vapor Transmission ASTM E 96 3.1 Perm / Inch
Dimensional Stability ASTM D 2126 +0.07% Volume Change @ -40' F., 2 weeks
+6.0% Volume Change @158'F., 100% Humidity, 2
weeks
Closed Cell Content ASTM D 2856 86%
Note: The physical properties listed above are presented as typical average values as determined by
accepted ASTM test methods and are subject to normal manufacturing variation.
NOA No.: 17-0322.03
MIAMMADE COUNTY
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 2 of 11
EVIDENCE SUBMITTED:
Test Agency Test Identifier Test Name/Report Date
Center for Applied Engineering
#94-060
TAS 101
04/08/94
257818-IPA
TAS 101
12/16/96
25-7438-3
SSTD 11-93
10/25/95
25-7438-4
25-7438-7
SSTD 11-93
11/02/95
25-7492
SSTD 11-93
12/12/95
Miles Laboratories
NB-589-631
ASTM D 1623
.
OA1714
Polymers Division
'..'
....
••.•.•
00
• • • ��
Ramtech Laboratories, Inc.
9637-92
ASTM E 108
• • • •
04/30193
•
Southwest Research Institute
01-6743-011
ASTM E 108
01-6739-062b[l]
ASTM E 84
:••:
Oim9:
••�•••
.. ..
..
......
Trinity Engineering
7050.02.96-1
TAS 114
; • • • •;
0�114/96
P36700.04.12
ASTM D 1623
.
(Iy�8�12
�••"'
P39740.02.12
TAS 101
••••
W-12I/l2
;••••�
TAS 123
'
Celotex Corp. Testing Services
528454-2-1
TAS 101
10/23/98
528454-9-1
528454-10-1
520109-1
TAS 101
12/28/98
520109-2
520109-3
520109-6
520109-7
520191-1
TAS 101
03/02/99
520109-2-1
LIMITATIONS:
1. Fire classification is not part of this acceptance. Refer to the Prepared Roof Tile Assembly for fire rating.
2. ICP Adhesives Polyset' AH-160 shall solely be used with flat, low, & high tile profiles.
3. Minimum underlayment shall be in compliance with the Roofing Application Standard RAS 120.
4. Roof Tile manufactures acquiring acceptance for the use of ICP Adhesives Polyset® AH-160 roof tile adhesive
with their tile assemblies shall test in accordance with TAS 101.
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20-3 of the Florida Administrative Code.
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 3 of 11
INSTALLATION:
1. ICP Adhesives Polyset AH-160 may be used with any roof tile assembly having a current NOA that lists
attachment resistance values with the use of ICP Adhesives Polyset AH-160.
2. ICP Adhesives Polyset AH-160 shall be applied in compliance with the Component Application section and the
corresponding Placement Details noted herein. The roof tile assembly's adhesive attachment with the use of ICP
Adhesives Polyset' AH-160 shall provide sufficient attachment resistance to meet or exceed the resistance value
determined in compliance with Miami -Dade County Roofing Application Standards RAS 127. The adhesive
attachment data is noted in the roof tile assembly NOA.
3. ICP Adhesives Polyset AH-160 and its components shall be installed in accordance with Roofing Application
Standard RAS 120, and ICP Adhesives and Sealants, Inc.'s Operating Instruction and Maintenance Bggl�lgt.
4. Installation must be by a Factory Trained 'Qualified Applicator' approved and licensed 4y IC,%Adhesives and ......
Sealants, Inc. ICP Adhesives and Sealants, Inc. shall supply a list of approved applicators' to t1fe autho?ity hiving • � � 0 � •
jurisdiction. •
...... .
5. Calibration of the ICP Adhesives Foam Dispenser RTF 1000 dispensing equipment is reguime befor a application: "
of any adhesive. The mix ratio between the "A" component and the "B" component shalt be maintained�3tween• . • . •
...... ... . .....
.. .. .. ..... .
6. ICP Adhesives Polyset' AH-160 shall be applied with ICP Adhesives Foam Dispenser RTE 1000 or ICP. . • •
Adhesives ProPacke 30 & 100 dispensing equipment only. •
. . . ..... .
7. ICP Adhesives Polyset AH-160 shall not be exposed permanently to sunlight. :....:
8. Tiles must be adhered in freshly applied adhesive. Tile must be set within 1 to 2 minutes after ICP ,?4d1;osives
Polyset® AH-160 has been dispensed.
9. ICP Adhesives Polyset' AH-160 placement and minimum patty weight shall be in accordance with the
'Placement Details' herein. Each generic tile profile requires the specific placement noted herein.
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 4 of 11
Table 1: Adhesive Placement For Each Generic Tile Profile
Tile Profile
Placement Detail
Minimum Paddy Contact
Minimum Paddy Gram
Area
Weight
Eave Course - Flat, Low, High
All Eave Course
17-23 sq. inches
45-65
Profiles
Flat, Low, High Profiles
#1
17-23 sq. inches
45-65
Flat Profile
#2
10-12 sq. inches
30
Low Profile
#2
12-14 sq. inches
30
High Profile
#2
17-19 sq. inches
30
Flat, Low, High Profiles
#3
Two Paddys: 8-9 sq. inches at
1.2 grams }yes faddy ..
head of file 9-11 sq. inches at
• • •
overlap
"" • • • • • • •
Two -Piece Barrel (Cap Tile)
Two Piece
2 Beads (1 each longitudinal
• • • 4 7 granpparibead
edge) 20-25 sq. inches each
11666 see** • •
bead
""' " • • •
Two Piece Barrel (Pan Tile)
Two Piece
65-70 sq. inches
•' :Yt grams under pan
LABELING:
All approved products listed herein shall be labeled and shall bear the imprint or identifiable marking of the
manufacturer's name or logo and following statement: "Miami -Dade County Product Control Approved" or the Miami -
Dade County Product Control Seal as shown below.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or applicable building code in order to properly evaluate the installation of this
system.
NOA No.: 17-0322.03
MIAMFDADE COUNTY
... � , Expiration Date: O5/10/22
Approval Date: 04/27/17
Page 5 of 11
.9:
ADHESIVE PLACEMENT DETAIL # 1
N"through plastic swtent Paddy [Bma shUht)
4wknroqulrodi} J aw
-. _ X y
� .-. iip� r�l •..4 Z
Eaernursr, y';,'
Nail through otas* oemem
#when requlmo
tlnr!•rlayhgzrt V �"�
s' w r9
l*sue.,
fattens apSianal �, ._•h-•' = _ . •� 5a-
l a' Save Closure
Cm {cursa �<� �� � Fa"
easy+§-Pl..:ie —
Oheri"Lared} rr � ., P.eIdylBrn"ghd'ilwl
iFstd•rlaynsr�t[ Yya �iti ~ •".�',
y ,� tff in.i ~'`•.tea �"ti+ ' .�h•
lattans
�T
.. '-• >,ea a -h . : fe'•.I�.� L^
�+ •L �v M1 y 1 11 �rtit. yp Ys'r
_ EaveC;aurSt4 -'Pas
r'...
^•.., - frJ� A "y, �EarWWllosOP:e
MIAMFDADE COUNTY
. r
Flat/Low Profile Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown,
under the strengthening rib closest to the overlock
of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.......
. • .... ......
•••••• •• •• ••••••
•
•••• •••• • •
•••• •••• •••••
Medium Profile / Double Raa 'ale ... ..:.. •
•• •• •• ••••••
1. Starting at the eave cour:(!,tMy a minimum 2" • •
(50.8 mm) x 10" (254 mm) x 1" (25.Q"foam • • •• •
paddy onto the underlayient positioned as shown:....
under the pan portion of the tile closest 0 the
overlock of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.
High Profile / Single Pan Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown
under the pan portion of the tile closest to the
overlock of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 6 of 11
ADHESIVE PLACEMENT DETAIL # 2
Obilth 9hphiticteimwnt NddyIh o i
klixl•t9ayntnns �''~` �, � - ti
B�ttea"saational �•� - "' ,;3 _- _'`� -"
'-,•yam �,�.:
€a, closure..__
mail throujph Rustic cement.
#evhen rs4eiredl
�t _= PaddyOftneatbtile)
3 iin. r
Flat/Low Profile Tile
Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 nun) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
strengthening rib of the tile closest to the overlock of
the tile being set. Insure approximately 17 (109.7 cm'-)
— 23 (148.4 cm2) square inch adhesive contact with the
underside of the tile.
2. At the second course,
apply a minimum
2'1Mmm)
x7"(177.8mm)xl"(25.4W)fpampaddntoh''yoe
underlayment positioned as.,%j"4q undef tle • ; • 0 0 0:
strengthening rib closest to tlha overlock of the the
being set. 000000 ...... .... .
3. Continue in same manner. lh%D?(? approxiMejy 10" • • o • •
(64.5 cm2) - 12 (77.4 cm2) s qua'r8 inch adhesi% • • • • ; •
contact with the underside of t�'e't le. ' •
......
• . ..... .
0.
Medium Profile / Double Pan Tile '.:..'
Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
pan portion of the tile closest to the overlock of the
the being set. Insure approximately 17 (109.7 cm2) —
23 (148.4 cm'-) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 nun) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the pan
portion of the tile closest to the overlock of the tile
being set.
3. Continue in same manner. Insure approximately 12"
(77.4 cm2) - 14 (90.3 cm2) square inch adhesive
contact with the underside of the tile.
(Instructions continued on next page)
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 7 of 11
ADHESIVE PLACEMENT DETAIL # 2 (CONTINUED)
Nail through pUsik ea ,
thudw AAyment
r_
4 Aa '•. `.
1�7
elk
2in L
ittrns apclaesal ff �'`•..', `4s `�- ,. _ ~�.�i �.� ��
}N.
r EaveC49mrst 5 Fafcia
s�
lY.rph�
G-
$' Ex ciasure
High Profile / Single Pan Tile
1. Starting at the eave course, apply a minimum 2" (50.8
nun) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
pan portion of the tile closest to the overlock of the
tile being set. Insure approximately 17 (109.7 cm2) —
23 (148.4 cm') square inch adhesive contact with the
underside of the tile.
.••.
2. At the second course, apply mlaimum 2'• (s0.8mn j • • • • -
x 7" (177.8 mm) x 1" (25.4 •mm) toam paddy onto the • * . •
underlayment positioned aj sDO vp under the pan •
portion of the tile closest to the pverlockRf tj a tile • • • • •
•
being set. •....' • • .••, •••••
•
3. Continue in same manner. "sdre approximately 17'39 * e 9
(109.7 cm2) - 19 (122.6 cr4� %ktidre inch adhesive • •
contact with the underside of thetile. ; . • • • • • •
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 8 of 11
ADHESIVE PLACEMENT DETAIL # 3
mail diroughplastic cesnent Paddy (between tiles)
4when required►
Battens optional °
Paddy(undertile)
single paddy i
Y on top ottrle
4xiin •'~•
Single paddy
on 2 x d in.
b �101n~�t,`
2in. Facia
—�-Gave Closure
€ M/Law profile Tile
Nall through .plasficcement Single paddy Under tie
when required)
Paddy lbetween tiles)
Battens
Paddy [under tile►
Single paddy
on top ottde
l� 4x4in.
Single paddyon
un ynxnt
214in
'�
10in.��4`a
2m.
• Fave Closure
Eave Course
fascia
Medium pro8leTile
1. On the eave course only, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown, under
the strengthening rib for flat tile or under the pan
portion of the tile for low or high profile tile closest
to the overlock of the tile being set. Leave
approximately 4" (101.6 mm) up from the eave
edge free of foam to prevent the expanded adhesive
from blocking the weep holes. Insure
approximately 17-23 in' (109.7-148.4 cal of
adhesive contact with tlT underside of gwAile ......
•• • •
2. Apply a 4" (101.6 mm) x VC1101.6 mm)*x V (25a.
mm) foam paddy onto thederlay nl)� ct below • •
the second course line Wgrled fob, paddy ..0 ..
j
under the strengthening"13 Wflat tile, dr.Vder t1ig.
pan portion of the tile, oles" to the undgrlock for . •
the second course tile tv be lAalledr Insure .... ; •
approximately 8-9 in' (11.6.-55.1 cm: of adhesive
••••••
contact with the undersideof the tile: . • •. •
••••
(Instructions continued on next page)
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 9 of 11
ADHESIVE PLACEMENT DETAIL # 3 (CONTINUED)
Man through Plasticce Sanglepaddy under tile
(when re4uired)
Paddy ibetween tiles)
Battens optional `��{ Paddy (under tilel
i' �
an un ert•ymen
S[ ie 2x4in.
pa #taeon'�
tap a=
Eave Course =`'
�* Fascia
Weephole .
14 in.3 in. Eave dosvre
Drip edge
High PmfllsTile
MIAWDADE COUNTY
l jo
3. Also apply a 2" (50.8 mm) x 4" (101.6 mm) x 1/4"
(19 mm) paddy on top of the eave course tile
surface as shown, on top of the strengthening rib
for flat tile or on top of the pan portion of the tile,
closest to the underlock of the first course of tile.
Install second course of tile. Insure approximately
9 (58.1 cm) - 11 (71cm2) square inch adhesive
contact with the underside of the tile at the overlap
and 7 (45.2 cm') - 9 (58.1 cm) square JAck
adhesive contact with tho underside of t4G bite at ....
. •
the head of the tile. Continue irosame naannar.
•
•ease•
bees s•s• •••r•
•••sae ••• • •s•••
• • • •bee••
•• • • .. e •
•
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 10 of 11
ADHESIVE PLACEMENT DETAIL
TWO PIECE BARREL
1) Place enough adhesive to achieve 65 to 70 sq. in. Steep pitch applications
in contact with the pan tile. (when required)
2) Turn covers upside down. Place adhesive in
to 1 in.from outside edge of cover tile.
Then install the tile. Ensure 20 to
25 sq. in. contact area.. -.
Underlayment
(motarshown)
Fascia
Remove top portion of the eave course cover tile. Abut to second course of
pan tiles. Ensure eave end of pan and cover tiles are flush at eave line.
Two Piece Barrel - High Profile Tile
Two Piece Barrel (Cap and Pan) Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as
shown under two adjacent pan tiles. Support eave
tiles from rocking until adhesive has a chance to
cure.
•ee•
2. Continue in same manner bringing%"pAn
courses up toward the ndge.;nsure •
approximately 65 (419 4*V) — 70 ( 14 cm2)• • • • : •
square inch adhesive M111f with the dndersidP •
of the pan tile. • • • �. . "". ' •
.... .... sees•
3. Turn covers upside dgwftAjxtosing Nei'Jdersi 4•:•
of the tile. Apply a mk imL" 1" (25.4rmn) x 10"
(254 mm) bead of adhesive lirectl on the inner...;.
edge of each side of toe cQvpr tile. eave e
approximately 3/4" (19' filmy to 1" 12�-* Inm) : • • • •:
from the outside edge of the tile, in*Vd, free of
foam to allow for expansion.
4. Turn cover tile over after foam is applied and
place onto pan tile course. Insure a minimum of
20 (129 cm2) - 25 (161.3 cm2) square inch
contact area on each side of the cover file to the
pan tile. Continue in same manner. Trim away
any cured exposed foam adhesive. Pointing of
longitudinal edges of the cover tiles are
considered optional.
5. When additional nailing is required, 2" (50.8
mm) x 4" (101.6 mm) nailers or the tie wire
system using galvanized, stainless steel, or
copper wire and compatible nails may be used.
END OF THIS ACCEPTANCE