DENSIY REPORT 2022GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES Ec DYNATECH ENGINEERING CORP. WWW.DYNATECHENGINEERING.COM Miami, August 15, 2022 Mr. Miguel Perez SERVILACON CORP. 7213 NW 46 Street Miami, FL 33166 Re: Proposed Addition 9509 North Miami Avenue Miami Shores, FL 33150 Dear Mr.: Perez Pursuant to your request, Dynatech Engineering Corp. (DEC) performed a Compaction Test on August 13, 2022 at the above referenced project. DEC was authorized to perform a compaction test only. The purpose of our test was to determine the degree of compaction of the tested layer of material only. In no way shall a compaction test replace a demucking inspection, soil bearing capacity determination, or a pad certification. A soil boring test must be performed by client if not yet done, prior to construction to verify subsoil conditions. Underlying soils below test levels must be verified to prevent future settlements. (DEC) was not authorized to perform supervision and certification of the building pad preparation. This is not a pad certification. Our reports must be provided to all involved parties for their approval. Our findings are relative to the date and areas of our site work and should not be relied upon to represent conditions on other areas or dates. Any subsequent site disturbances due to water erosion, rain, storm gutters discharging at footings, construction activities, excavations, overgrown, vegetation, traffic and other disturbances will void this test and the site must be re - compacted and re -tested prior to construction. Environmental analysis of the soil materials is not art of the scope of services. If environmental analysis of the soils is required, we can provide proposal for performing an environmental analysis of the soil materials. No other analysis is implied or warranted. As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients, and authorization for use, publication of statements, conclusions or extracts from or regarding our reports is reserved pending our written approval. Enclosed find copies of the compaction test results. It has been a pleasure working with you and look forward to do so in the near future. ��,ttttlulrrrrrr�� Sincerely yours, �iaamru�i, P, E. No. 39584 * " DYNATECT I ENGFNEERTNG CORP. Florida Reg. No. 39584 _'p STATE OF Special Inspector No. 757 's��p�;.,.,e•` Q R 1�p ,: y- V % Certificate of Authorization No.: CA 5491 '��,r '3+ �yNl t ,S 10140N�1.E0,. GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES c DYNATECH ENGINEERING CORP. VNWW.DYNATECHENGINEERING.COM MOISTURE -DENSITY RELATIONS OF SOILS PROCTOR COMPACTION TEST DATE: August 15. 2022 CLIENT: SERVILACON CORP. PROJECT: Proposed Addition ADDRESS: 9509 North Miami Avenue Miami Shores. FL 33150 CONTRACTOR: SERVILACON CORP. MATERIAL DESCRIPTION:_ Light brown sand with rocks SAMPLED BY: WD TESTED BY: WD TEST RESULTS Sample Number 1 The following compaction test was conducted in accordance with the Standard Methods for Moisture Density Relations of soil using a 10 lb. Hammer and an 18" drop ASTM D-1557. % MOISTURE DRY DENSITY 4.9 117.2 6.0 120.7 7.4 122.5 125 11.8 121.8 J 123 1 121 Optimum Moisture 9.2 Percent 100% Maximum Dry Density 123.4 lbs./cu.ft. 119 % Passing V Sieve 86% Percent 117 115 Sampled By: WD Tested By: WD Checked By: WN ��►'SA t t 111 t u+ V 4 6 8 10 12 14 ,,,••'�, SAAD Nq'�•.,, �.` Gj�• • �jC E NSE .�-- Respectively subT4 m As a mutual protection to clients, the public and ourselves, all reports -�J �,� are submitted as the confidential property of clients, and authorization ••� Na. 39584 -� for use, publication of statements, conclusions or extracts from or regardalg* ' iSSPn1 i a Bill, P.E. our reports is reserved pending our written approval. = * �)YNATECH ENGINEERING CORP. STATE OFFlorida Reg. No. 39584 Certificate ofAuthorization No.: CA 5491 ';� jj ;S/OtNAL ��••'. D R Y D E N S I T Y 2 GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES aEc DYNATECH ENGINEERING CORP, WWW.DYNATECHENGINEERING.COM FIELD DENSITY TEST OF COMPACTED SOILS DATE: August 15, 2022 CLIENT: SERVILACON CORP. PROJECT: Proposed Addition ADDRESS: 9509 North Miami Avenue Miami Shores FL 33150 CONTRACTOR: SERVILACON CORP. Test No. I Location: East side of addition underslab Test No. 2 Location: West side of addition underslab Test No. 3 Location: North side of interior underslab Test No. 4 Location: Center of interior tmderslab Test No. 5 Location: South side of interior underslab Description of Material: Light brown sand with rocks TEST NO. 1 2 3 4 5 DEPTH 12" 12" 12" 12" 12" FIELD DENSITY 122.1 122.4 122.8 122.6 122.3 MOISTURE CONTENT % 7.0 7.2 7.7 7.4 7.2 MAX. DENSITY IN THE FIELD % 98.9 99.2 99.5 99.4 99.1 COMPACTION REQUIREMENTS % OF MAXIMUM 98% 98% 98% 98% 98% 100% MAXIMUM DENSITY (LAB) 123.4 123.4 123.4 123.4 123.4 REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION REQUIREMENTS * Please note this is not a pad certification. A soil boring must be performed to determine subsoil conditions below the tested compaction layer prior to construction. ,�t►IIII II1rr,,,� `t`�,•�P�,SAAD grrrrr' Respectfully submitted, -:.-�� ��cFNsf••:�y Tested By: WD IA�I Checked By: WN ,E ; No. 39584 * -'Wissam Naamani, P.E. 5DYNATECH FNGINEERING CORP. .p STATE OF •:� Florida Reg. No. 39584 '.��Q• �F4 �;�p�,� Certificate of Authorization No.: CA 5491 *A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination. A soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved pending on our written approval.