RF-07-22-1909 Uplift Test 9880 NE 9 AveA. Tomassi Roof Testing, Inc.
5451 NW 24th Street, Suite # 3
Margate, Florida 33063
TAS —106 Tel. 954 — 979 —1180
Fax. 954 — 979 —1182
Roof Tile Static Uplift Test Report
Test Date:
Janus 16t", 2023
Project:
9880 N.E. 9111 Ave., Miami Shores, FL.
Contractor:
Southern Coast Enterprises
Permit #:
RF-07-22-1909
Roof Pitch:
399: 12"
Tile Installation Date:
December 22"', 2022
Attachment Method:
Pol foam
Tile Type:
Boral Saxon
All testing is in strict accordance with the 2020 Florida Building Code,
High Velocity Hurricane Zone Testing Application Standard (TAS) 106
Each Test location was pulled using a Imada Force Gauge to a minimum of 35 lbs.
TEST SUMMARY:
Roof Area Total # of Tests # of Tests Passed % Passed
Field
12
12
100%
Corner
6
6
100%
Perimeter
20
20
100%
Hi (Approximately 0 Total)
N/A
N/A
N/A
Rld e (Approximately 63 Total)
6
6
100%
TEST RESULTS: PASSED
See Attached Sketch For Further Details.
Report Reviewed by:
7-3
Dominick Scarfo, AR0 10248
Dade Coun1y Certified Testing Agency # 22-0830.05 Revises: # 03-0317.03
Roof Testing Services * Fastener Withdrawal Resistance * Tile Static Uplift * Moisture Surveys * Membrane Adhesion -FM & FBC
`,
pr
0
r
It
0
00
00
0
�o
a
c
fD
I
I
J
W
00
W
00
m
fD
ow
y
eD
a
b
eD
o.
Certificate of Calibration
Kimbell Electronic Laboratory, ��uIII��������A���
mM
CallbnOPR Po forMed By:
KIMBALL ELECTRONIC LABORATORY, INC.
8081 W 21 LANE
HIALEAH, FL. 33018
Equlpmsrrt Information KELI I.D.: KEI_-1
Description: DIGITAL FORCE GAUGE
Manufacturer
IMADA
Model Number:
DPSH-440
Part Number
DPSH-440
Serial Number.
199171
Customer ID:
N/A
Cust. Barcode:
N/A
Cust. Dept.:
N/A
Cal Location:
ON -SITE
. Range: 0 TO 440 LBS
Purchase Order #
For: A.509
A. TOMASSI ROOF TESTING INC
5451 NW 24 STREET
#3
MARGATE FL 33063
Cal Date: 02-Nov-22
Cal. Due Date: 02-Feb-23
Cal. Interval: 3 MONTHS - DAY -MONTH -YEAR
Received: IN TOLERANCE
Calibration Result: PASS
Environmental Conditions: 78 DEG F / 62 % RH
Performed By: JULIO
GARCIA
Procedure: SYN156
Specifications: MANUFACTURER
This Is to certlfythat the above hated instrument meets or exceeds all spectflcaIIon s as stated In the referenced procedure at the polnts tested (unless otherwise noted). it has
been call bmted using measurement standarda traceable to the SI unite of measurement via NISI, or to N1STaccepts d intrinsic standards of measurement, or
derived by the ratio ppe of aelf-callbration teohniquss. ThIs calibratlon Is In accordance with KfmbalI Electra We Laboratory, Inc QUall ly Assurance Manual, KELi's Quality system Is
A&A-Accredited to 19UIiEG17025:20i7and compliantwith MIL-STO-45662A and ANSYNCSL Z640-1.1994, TURS when applicable are greater than or equal to 4:1 except where
noted with expanded uncertainty used to calculate the Test Uncertainty Ratio, with a coverage factor of 02 at canfldance Level of approximately 95%, unleaa otherwise hated.
All measuring equipment used for callbrallan meets a 4:1 TAR or better, except Where noted
Any number of factors may cause the calibration Item to drift out of calibration before the recommended Interval has expired.
IiEU will not take Into account measurement uncertainty on condIda na# statements such as In tolerance, out of tolerance, pass and fall. Kell's conditional statements will only take into
account the nominal value at a specific test point +1- the tolerance. Measurement uncertalnty will be stated on the certificate and where applicable at each meesumd test point.
KELI shall allow the customer to assess and concluda If the results meettheir spa aft needs.
Callbyp4on *Marks
THIS UNIT WAS FOUND TO BE IN TOLERANCE AT THE TIME OF CALIBRATION.
PERFORMED ROUTINE CAL. NO ADJUSTMENTS REQUIRED
trkdarda Used To Calibrate Equipment
Company I.D. Manufacturer Model/PN Description Serial Number Last Cal. Cal. Due Date
KIM001 3082 AKO TSD 2052-SB DEAD WEIGHT SYSTEM 3082 06-Deo-21 31-Doe22
$I ra s•
Technician: Y „� -n Quality Assurance:
JULIO JAVIER ey • "
GARCIA 02—Nov-22 2:49:15 PM BALCEIRO 04—Nov-22 2:49:36 PM
This report may not be reproduced, except In full, unless permission for the publication of an approved abstract is obtained In writing from KELI Labe., Inc.
Kimball Electronic Laboratory, Inc. - 8081 W. 21 st Lane - Hialeah, FL. 33016
Tel: 305-822-5792 - Toll Free: 800-393-1094 - Fax: 305-362-3125 - Web: www.keliiabs.com
Oats of Issue: 04-Nov-n Pace 1 of 1