RF-12-22-3063 Engineer Ltrs 1247 NE 101 StLank Engineering LLC. Testing & Engineering Services Tel: 954.245.8976; Fax: 954.301.7776 1000 E Atlantic Blvd, #119 Pompano Beach, Florida, 33060 Attention: Test Date: 04/03/2023 Property Address: _ Roof Pitch: 4 in 12 I Tile Attachment Method: Field Instrument: Contractor: KMR Roofing Roof Tile Uplift Test Report Village of Miami Shores, Building Department. Permit # REV-12-22-3063 1247 NE 101st Street, Miami Shores, FL Type of Tile: Roof Area. - Roof Tile per NOA J 37.00 squares Adhesive Foam per NOA. IMADA Force Gauge 0-100 Serial number: 243454 Test Location Total Number of Tests Field Uplift Pull Test Test results Perimeter Area: 17.00 sq. 17 As per FBC 2020 Passed Field Area: 20.00 sq. 20 As per FBC 2020 Passed No. of Corner: 10 10 As per FBC 2020 Passed Ridge Areas: 290 pcs. 30 As per FBC 2020 Passed Important: These laboratory results can change due to future weather impacts and /or unavoidable roof traffic. Therefore, this report represents the TAS 106 results at the time of the test. All tested locations were done using an Imada Force Gauge instrument with a minimum uplift load of 35lbs (for mortar or adhesive set tiles) and If applicable, for mechanically attached tiles a minimum static test uplift load of 80% of the Resistance Moment (Mr') or 80% of the Resistance Load (f) as listed in Product Approval (NOA) was applied. Please see attached a Roof Sketch for this project Cordially, Lank Engineering LLC. (NOA 21-1122.01) Andre Bigatao, PE Fla. Reg. No: 80977 h}AR 0 4 2 �L� Lasoroc International A Consulting and Engineering Services 2431 Aloma Avenue, Winter Park, FL. Tel: 954-245-8976 To: Miami Shores Village, Building Department. April 3, 2023 Re: Slope roof underlayment after the fact inspection for property located at: 1247 NE 101 Street, Miami Shores, FL. Permit/Roofing Company: RF-12-22-3063 / KMR Roofing Dear Building Official: This letter is to advise Building Department that we have performed an inspection and reviewed the photographs taken by the roofing contractor during the base sheet, TU Max and drip edge installation for the slope roof section of the above referenced property. Specifically, we reviewed the roofing work of the deck re -nailing with 4" o.c. at the perimeter of the plywood sheet and 6" o.c. in the field of the plywood into the wood members 75# base sheet installed with 1 '/4 r.s. nails and tin caps in 2 rows at 12" o.c. in the middle of the sheet and one row at 6" o.c. at lap. The TU Max membrane was' uniformly self adhered to the base sheet and back nailed at 4" lap maximum 12" o.c.. The drip edge was found to be 3"x 3" gals. metal sheet primed and fastened to deck with nails 1 1/4" r.s. nails 4" o.c. Based on our site visit and field inspection, we can certify that the referenced work has been performed in conformance with the Permit and 2020 FBC 7th edition. Please note we are considering this letter an after the fact inspection to cover for inspections normally performed by the building officials during roof construction. This inspection does not cover roof drainage and does not provide a guarantee against roof leaks since these are still responsibilities of the contractor. Y. HAss6un, P.E. ei!No. # 61969 Op Lasoroc International A Consulting and Engineering Services 2431 Aloma Avenue, Winter Park, FL Ph: 954-245-8976 To: Miami Shores Village, Building Department. April 1th, 2023 Re: Slope Roof Tile Installation Inspection and Certification for residence located at: 1247 NE 101 Street, Miami Shores, FL, Contractor: KMR Roofing Permit No. RF-12-22-3063 Dear Building Official: This letter is to advise the Building Department that we have performed an exploratory site inspection and reviewed the pictures taken by the roofing contractor during the roof tile installation for the above referenced property. The roof tile inspection revealed the following: The roof tile has a pitch 4/12 according with the permit. The type of tile used was Boral Estate Spanish Tile with NOA # 21-0323.05 The ICP PolyFoam Tile Adhesive with NOA # 20-1124.07 was installed' as one medium paddy with approximate dimensions 2"/7". The tile head lap was found to be a minimum of 3 inches. Based on the above field observations, I can certify that the referenced work was performed in conformance with NOA # 21-0323.05 and the Permit. Please note that we consider this letter as being an after the fact inspection to cover inspections normally performed by building officials during roof construction. This inspection does not cover roof drainage and does not provide a guarantee against roof leaks since these are still responsibilities of the contractor. P:E. 1969 0 0 1 )491 Lasoroc International A Consulting and Engineering Services 2431 Aloma Avenue, Winter Park, FL. Tel: 954-245-8976 To: Miami Shores Village, Building Department. April 3, 2023 Re: Slope roof underlayment after the fact inspection for property located at: 1247 NE 101 Street, Miami Shores, FL. Permit/Roofing Company: RF-12-22-3063 / KMR Roofing Dear Building Official: This letter is to advise Building Department that we have performed an inspection and reviewed the photographs taken by the roofing contractor during the base sheet, TU Max and drip edge installation for the slope roof section of the above referenced property. Specifically, we reviewed the roofing work of the deck re -nailing with 4" o.c. at the perimeter of the plywood sheet and 6" o.c. in the field of the plywood into the wood members 75# base sheet installed with 1 1/4 r.s. nails and tin caps in 2 rows at 12" o.c. in the middle of the sheet and one row at 6" o.c. at lap. The TU Max membrane was uniformly self adhered to the base sheet and back nailed at 4" lap maximum 12" o.c.. The drip edge was found to be 3"x 3" galy. metal sheet primed and fastened to deck with nails 1 1/4" r.s. nails 4" o.c. Based on our site visit and field inspection, we can certify that the referenced work has been performed in conformance with the Permit and 2020 FBC 7 h edition. Please note we are considering this letter an after the fact inspection to cover for inspections normally performed by the building officials during roof construction. This inspection does not cover roof drainage and does not provide a guarantee against roof leaks since these are still responsibilities of the contractor. 1 ardially, a Y. Hass'oun. P.E. a l4. No. # 61969 A 00 0 12023 Lasoroc International A Consulting and Engineering Services 2431 Aloma Avenue, Winter Park, FL Ph: 954-245-8976 TO: Miami Shores Village, Building Department. April 111, 2023 Re: Slope Roof Tile Installation Inspection and Certification for residence located at: 1247 NE 101 Street, Miami Shores, FL. Contractor: KMR Roofing Permit No. RF-12-22-3063 Dear Building Official: This letter is to advise the Building Department that we have performed an exploratory site inspection and reviewed the pictures taken by the roofing contractor during the roof tile installation for the above referenced property. The roof tile inspection revealed the following: The roof tile has a pitch 4/12 according with the permit. The type of tile used was Boral Estate Spanish Tile with NOA # 21-0323.05 The ICP PolyFoam Tile Adhesive with NOA # 20-1124.07 was installed as one medium paddy with approximate dimensions 2"/7". The tile head lap was found to be a minimum of 3 inches. Based on the above field observations, I can certify that the referenced work was performed in conformance with NOA # 21-0323.05 and the Permit. Please note that we consider this letter as being an after the fact inspection to cover inspections normally performed by building officials during roof construction. This inspection does not cover roof drainage and does not provide a guarantee against roof leaks since these are still responsibilities of the contractor. ially, �. FY. Hassoun P.E. g. No. # 61969 A PP 0 1 9023 Lasoroc International 2431 Aloma Avenue, Winter Park, FL. 32792 PH: 954-245-8976 To: Miami Shores Village, Building Department. April 3"', 2023 Re: Flat roof inspection and certification for residence located at: 1247 NE 101 Street, Miami Shores, FL. Contractor / Permit No: KMR Roofing / REV-03-23-559 Dear Building Official: This letter is to advise the Building Department that we have performed a site inspection and reviewed the photographs taken by the roofing contractor during the flat roof system installation. Based on our roof inspection, we found the following: The deck was re -nailed 6" o.c. in the center of the 5/8" plywood sheet and 4" o.c. in the perimeter of the plywood sheet into the wood members. The 75# base sheet was fastened as follows: The 1' zone fastened with 11/4 r.s. nails 9" o.c. at lap with 2 rows at 9" o.c. in the center of the sheet. The field area was fastened 7" o.c. at lap with 2 rows at 7" o.c. in the center of the sheet. The perimeter was fastened with 1 1/4" r.s. nails and tin caps 5" o.c. at the lap with 2 rows in the center of the sheet at 5" o.c. The corners were fastened 5" o.c. at lap and 3 rows at 5" o.c. in the center of the sheet. Two ply IV of fiberglass were hot mopped over the base sheet and the last layer of GAF Mineral surfaced cap sheet was uniformly hot moped over the roof system. The drip edge was found to be 3"x 3" galy. sheet metal primed and fastened to the deck with 1 1/4" r.s. nails 4" o.c. Based on our inspection and reviewed the roofing work, we can certify that the referenced work has been performed in conformance with the Permit and 2020 FBC 7th edition. Please note we consider this letter an after the fact inspection to cover for inspections normally performed by the building officials during roof construction. This inspection does not cover roof drainage and does not provide a guarantee against roof leaks since these are still responsibilities of the contractor. Y. Uw6un, P.E. er No. 61969 A PR h ,) m Lasoroc International 2431 Aloma Avenue, Winter Park, FL. 32792 PH: 954-245-8976 To: Miami Shores Village, Building Department. April 3`d, 2023 Re: Flat roof inspection and certification for residence located at: 1247 NE 101 Street, Miami Shores, FL. Contractor / Permit No: KMR Roofing / REV-03-23-559 Dear Building Official: This letter is to advise the Building Department that we have performed a site inspection and reviewed the photographs taken by the roofing contractor during the flat roof system installation. Based on our roof inspection, we found the following: The deck was re -nailed 6" o.c. in the center of the 5/8" plywood sheet and 4" o.c. in the perimeter of the plywood sheet into the wood members. The 75# base sheet was fastened as follows: The l' zone fastened with 11/4 r.s. nails 9" o.c. at lap with 2 rows at 9" o.c. in the center of the sheet. The field area was fastened 7" o.c. at lap with 2 rows at 7" o.c. in the center of the sheet. The perimeter was fastened with 1 1/4" r.s. nails and tin caps 5" o.c. at the lap with 2 rows in the center of the sheet at 5" o.c. The corners were fastened 5" o.c. at lap and 3 rows at 5" o.c. in the center of the sheet. Two ply IV of fiberglass were hot mopped over the base sheet and the last layer of GAF Mineral surfaced cap sheet was uniformly hot moped over the roof system. The drip edge was found to be 3"x 3" gals. sheet metal primed and fastened to the deck with 1 1/4" r.s. nails 4" o.c. Based on our inspection and reviewed the roofing work, we can certify that the referenced work has been performed in conformance with the Permit and 2020 FBC 71h edition. Please note we consider this letter an after the fact inspection to cover for inspections normally performed by the building officials during roof construction. This inspection does not cover roof drainage and does not provide a guarantee against roof leaks since these are still responsibilities of the contractor. dially, Y. Ha�50ufl--P--E. F _eg,No.61969 ARP n 2923 'M h ���' ' ,� , . a .. • - 4. ��}�' - - _ - - - _ _ _ A-} Y�J. Jul, _-- - - - -- - -- _ - _ -_ _ - - - row O 40 O 4 4 r � + O Q O . ! O + O O e O O 3 O s' !� y Q s qb 411116 40 o � e � � e O � r ` e ' r• 1 ��1 ti ti v ' l Z;R r .r t' x r 1 . • AIL � �. `. �� r�'' � r i' ' t ' i' �' ■ ' r f `�#�?C � � �._ �_ -� :;fie. •__ - _ -- � `'.. � ,��� �` _= _ - � _ ��- rCr� � f.� _y�-` •� s Lam:• �r'��� A 1 i ���► fir. .������! QY ���woaz rdw LE •� f •' ,'Y ` } A'.. 1. 4�y. -~. R - ti•- ice• :vr '-` /J +� �. S' w �F t � ^�Ir''.'''� v r ��` i? -.. 4. �. - - �. ";:• � Ly ti - - � ..�� �5'. `h � S' ,• r1 . '-i: .- . _ a' �.'= � ` c' .S.a, - � ti. .�:• _ .F .. 'tiy �- .. AV- mm �el Ile, 7N Jwaf ppm Or AV :fv 1 1 10!!5m Alm- Joe 93 mq-0 Cc WA �- 74 1 t:- D 04 ,�V��_..__ � cam} ,_.. ., -^ •- �r Ag- ��,v� Pay• •� _ . .� 70 Ic%vovlsli PO 'St �tlrlj y y1mSL '�#� ������ `Ica �►e�� �. wk