RF-11-22-2909 Uplift Test 1098 NE 96 StLank Engineering LLC. Testing & Engineering Services Tel: 954.245.8976; Office:754.307.3391 1000 E Atlantic Boulevard, U-119 Pompano Beach, FL 33060 Attention: Test Date: 03/19/2023 Property Address: Roof Pitch: 3.in 12 Tile Attachment Method: Field Instrument: Roof Tile Uplift Test Report Miami Shores Village, Building Department 10050 WE 2"d Avenue, Miami Shores, Florida 33138 Contractor: Planet Roofing Permit #: RF-11-22-2909 1098 NE 96 Street, Miami Shores, FI e of Tile: Roof Tile per NOA Roof Area: 4.00 squares Two Component Polyurethane Foam Adhesive -Poly Pro AH 160 IMADA Force Gauge 0-100 Serial number: 243454 Test Location Total Number of Tests Field Uplift Pull Test Test results Perimeter Area: 2.00 sq. 2 As per FBC 2020 Passed Field Area: 2.00 sq. 2 As per FBC 2020 Passed No. of Corner: 8 8 As per FBC 2020 Passed Ridge Areas: 20 pcs. 2 As per FBC 2020 Passed Important: These laboratory results can change due to future weather impacts and /or unavoidable roof traffic. Therefore, this report represents the TAS 106 results at the time of the test. All tested locations were done using an Imada Force Gauge instrument with a minimum uplift load of 35lbs (for mortar or adhesive set tiles) and if applicable, for mechanically attached tiles a minimum static test uplift load of 80% of the Resistance Moment (Mr') or 80% of the Resistance Load (f') as listed in Product Approval (NOA) was applied. Please see attached a Roof Sketch for this project. Lank Engineering Inc. (NOA 21-1122.01) Andre Bigatao, P.E. Fla. Reg. No: 80977 r MAR 1 9 2023 �� r