RC-07-22-1868 Engineer Ltr 50 NE 110 StGOLDIN 9/9/2022 EVAN L. KENNEDY. P.E. CA # 29980 PROJECT: Ijamseau FLORIDA ENGINEER LICENCE #69895 ADDRESS: 50 Northeast 110th Strein 332 SW 7TH TERRACE Miami Shores, FL, 33161 BOCA RATON, FL 33486 (561)-573-1679 (�e r 07- 22-- 10-�=5�;. TO WHOM IT MAY CONCERN - SUBJECT: INSTALLATION CERTIFICATION LETTER i EVAN L. KENNEDY HAVE INSPECTED THE STRUCTRUAL AND ELECTRICAL INSTALLATION OF THIS PV SYSTEM IS ACCORDING TO PLAN AND MEETS ALL FBC 2020 7"' EDITION CODE REQUIRMENTS. THE INSTALLATION OF THE SS 4" X 5/16" LAG -BOLTS ARE INTO THE TRUSSES PER MOUNT AND ARE ACCORDING TO PLANS. LAG BOLT TORQUE TO 10-12 (FT*LBF) NO LAG BOLTS PENETRATED OUT OF THE SIDE OF THE TRUSSES. THE INSTALLATION OF THE SOLAR PV SYSTEM WILL NOT ADVERSELY AFFECT THE BUILDING STRUCTURE UNDER NORMAL CONDITIONS AND DURING A HURRICANE EVENT OF THE FBC SPECIFIED INTENSITY TO THE BEST OF MY KNOWLEDGE. EXISTING ROOF DETAILS: ROOF: WOOD CONSTRUCTION: PREFAB TRUSSES SPECIFIC GRAVITY: 0.50 WOOD TYPE: SPRUCE. PINE SOLAR SYSTEM DETAILS: MIN. ANCHOR DEPTH: 3" MAX. TENSION FORCE PER ANCHOR REQUIRED: 261 PSF ALLOWABLE TENSION FORCE PER ANCHOR: 798 LBS. TENSION FORCE SAFETY FACTOR: 3.1 LIVE LOADS: LIVE LOADS ASSOCIATED WITH SOLAR SYSTEMS ARE USUALLY ASSUMED TO BE DISTRIBUTED UNIFORMLY AND ARE SMALL, ON THE ORDER OF 4 PSF OR LESS. 'P.rHwy K _ +�►Q,r1 IV, fir �4. ■' i G E N S■-. ;o rr-09 1N� 09 A% 57ATE OF •�,,;% �1 A 1 : �� ���• Evan Kennedy" . ��trrrrtrr► TTIIS ITEAT HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY EVAN KENNEDY. P E ON D94M2 USING A DIGITAL SIGNATURE _ PRINTEDCOPIESOFnIISDOCUMENTARENOTCONSIDEHED SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES - Page 1