RF-05-22-1316 UPLIFTLank Engineering LLC. Testing & Engineering Services Certificate of Authorization #33264 Tel: 954-245-8976- Fax: 954.301.7776 5230 NE 18T" Avenue Fort Lauderdale, FL 33334 Attention: Client: Cherry Roofing Test Date: 07/14/2022 Roof Tile Uplift Test Report Village of Miami Shores, Building Department, 10050 NE 2"d Avenue, Miami Shores, FL 33138 Permit # f� Property Address: 185 Northeast 108th Street, Miami Shores, FL Roof Pitch: 4in12 I Tile Attachment Method: Field Instrument : of Tile: Roof Tile per NOA Roof Area: 19.85 squares Two Component Polyurethane Foam Adhesive -Poly Pro H 160 IMADA Force Gauge 0-100 Serial number: 8G190014 Test Location Total Number of Tests Field Uplift Pull Test Test results Perimeter Area: 9.85 sq. 10 As per FBC 2020 Passed Field Area: 10.00 sq. 10 As per FBC 2020 Passed No. of Corner: 8 8 As per FBC 2020 Passed Ridge Areas: 70 pcs. 7 As per FBC 2020 Passed Important: These laboratory results can change due to future weather impacts and /or unavoidable roof traffic. Therefore, this report represents the TAS 106 results at the time of the test. All tested locations were done using an Imada Force Gauge instrument with a minimum uplift load of 35lbs (for mortar or adhesive set tiles) and If applicable, for mechanically attached tiles a minimum static test uplift load of 80% of the Resistance Moment (Mr') or 80% of the Resistance Load (f') as listed in Product Approval (NOA) was applied. Please see attached a Roof Sketch for this project Cordially, Lank Engineering LLC. (NOA 21-1122.01) Andre Bigatao, PE Fla. Reg. No: 80977