t-Ek DYNATECH ENGINEERING CORP.
W W W.DYNATECHENGINE£RING. COM
MOISTURE -DENSITY RELATIONS OF SOILS
PROCTOR COMPACTION TEST
DATE: March 8. 2022
CLIENT: UNIVERSAL US CONSTRUCTION, INC.
PROJECT: Proposed Residence
ADDRESS: 1202 NE 93r6 Street Miami Sllores FL 33138
CONTRACTOR: Universal US Construction. Inc.
MATERIAL DESCRIPTION: Tan sand Wrock fragments
SAMPLED BY: JA TESTED BY: JA
TEST RESULTS
Sample Number 1
The following compaction test was conducted in accordance with the Standard Methods for Moisture Density Relations of soil using a
10 lb. Hammer and an 18" drop ASTM D-1557.
% MOISTURE
DRY DENSITY
3.9
108.1
6.1
111.8
8.6
113.7
116
11.7
112.8
114
112
Optimum Moisture 114.2
Percent
100% Maximum Dry Density9.9
lbs./cu.ft.
110
% Passing %" Sieve 74
Percent
108
Sampled By: WD
106
Tested By: WD II + I I 1 '
Checked By: WN
��,t�t+tttttlrl�4 6 8 10 12 14
,,LL SAAD ,y..,
As a mutual protection to clients, the public and ourselves, all reports=.`�.pM �1 G E jll �rrf Respectively sttbmited,
are submitted as the confidential property of clients, and authorization _
for use, publication of statements, conclusions or extracts from or red artiZnk ; No. 395Bd ; * Wissam Na tnani, P.E.
our reports is reserved pending our written approval. = * =DYNATECH ENGINEERING CORP.
STATE of =Florida Reg. No. 39584
�' _
-
Certificate of Authorization No.: CA 5491
,,��•� •F4OR1�P•G� :.
5S/0 •" N
11r,+tNA� r,0''
D
R
0
0
GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
Lf t-PEC DYNATECH ENGINEERING CORP.
W WW.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 8.2022
CLIENT: UNIVERSAL US CONSTRUCTION INC.
PROJECT: Pra osed Residence
ADDRESS: 1202 NE 93rd Street,Miami Shores FL 33138
CONTRACTOR: Universal I Iq Construction, Inc.
Test No.
1
Location:
East side of residence
ad 1" lift
Test No.
2
Location:
Center of residence 12ad,
IS,lift
Test No.
3
Location:
West side of residence
nad, 1" lift
Test No.
4
Location:
North side of residence
pad, 2nd lift
Test No.
5
Location:
Center of residence ad
2" Iift
Description of Material:
Tan sand wlrock fragments
TEST NO.
11
2
3
4
DEPTH
12"
12"
12"
12"
12"
FIELD DENSITY
112.9
112.5
112.7
113.0
112.4
MOISTURE CONTENT %
8.6
9.0
8.8
8.4
8.8
MAX. DENSITY IN THE FIELD %
98.9
98.5
98.7
98.9
98.4
COMPACTION REQUIREMENTS
% OF MAXIMUM DENSITY
98%
98%
98%
98%
98%
100% MAXIMUM DENSITY (LAB)
114.2
114.2
114.2
114.2
114.2
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION RE
UIREMENTS
Tested By: WD
Checked By: WN
��s t r<� �1,t n � unr►►t►
��.�` Cam, -•�G E ••. •q / Respectfully Submitted,
-. .
f tN
No. 39584
_ Wissa aamani, P.E.
* — DYNATECH ENGINEERING
�.O STATE OF rr� Florida Reg. No. 39584
','per �. A,•; %,�►` Certificate of Authorization No.
.� 0 RSA
/,f�rsS70 L
fxrrraIttf,It 0
*A density test determines th d f
CORP.
CA 5491
e egree o compactron of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval.
GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
tEcD DYNATECH ENGINEERING CORP.
WWW.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 8.2022
CLIENT: UNIVERSAL US CONSTRUCTION INC.
PROJECT: Proposed Residence
ADDRESS: 1202 NE 93rd Street Miami Shores FL 33138
CONTRACTOR: Universal US Construction Inc.
Test No. 6 Location: South side of residence pad, 2nd lift
Test No. Location:
Test No. Location:
Test No. Location:
Test No. Location:
Description of Material: Tan sand wlrock fragments
TEST NO. 6
DEPTH 12"
FIELD DENSITY 112.7
MOISTURE CONTENT % 8.7
MAX. DENSITY IN THE FIELD % 98.7
COMPACTION REQUIREMENTS 98%
% OF MAXIMUM DENSITY
100% MAXIMUM DENSITY (LAB) 114.2
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION REQUIREMENTS
���EttttattrrryJr
Tested By: WD �.� D s^lJl f`'�i
Checked BW y: N `��.��a• I.�Cf ks;•%,� Respectfully Submitted,
No. 39584
Wissam Naamani, P.E.
* = DYNATECH ENGINEERING CORP.
STATE OF :'4 Florida Reg. No. 39584
Certificate of Authorization No.: CA 5491
-A density test determines the degree of compaction of the tested layer of material only, In noway shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval.
GEOTECHNICAL I ENVIRONMENTAL_L_MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
} -DEG DYNATEGH ENGINEERING CORP.
W W W. DYNATECHENGINEERING. COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 8 2022
CLIENT: UNIVERSAL US CONSTRUCTION. INC.
PROJECT: Pro used Residence (&
ADDRESS: 1202 NE 93rd Street Miami Shores FL 33138
CONTRACTOR: Universal US Construction Inc.
Test No. 7 Location: South side of residence pad. 3rd lift
Test No. 8 Location: Center of residence nad. 3rd lift
Test No. 9 Location: West side of residence pad, 3rd lift
Test No. 10 Location: North side of residence Dad. 4th lift
Test No. 11 Location: Center of residence pad, 4th lift
Description of Material: Tan sand w/rock fragments
TEST NO.
7
8
9
10
11
DEPTH
12"
12"
1277
12"
1297
FIELD DENSITY
113.1
113.5
112.6
112.8
113.3
MOISTURE CONTENT %
8.2
7.9
7.6
8.4
8.1
MAX. DENSITY IN THE FIELD %
99.0
99.4
98.6
98.8
99:2
COMPACTION REQUIREMENTS
% OF MAXIMUM DENSITY
98%
98%
98%
98%
98%
100% MAXIMUM DENSITY (LAB)
114.2
114.2 11
114.2 1
114.2
114.2
KhMAKKJ: ALL ABOVh -1h; ;'Y RESUL'i'S COMPLY WITH COMPACTION REOUIREMENTS
AAD
Tested B WD .`�' ,' •
y =�R.,. �N q,,,' Respectfully Submitted,
Checked By: WN�' '•.
Nra. 39584 :y
Wissam Naamani, P.E.
'rr — DYNATECH ENGINEERING CORP.
STATE OF 4 Florida Reg. No. 39584
��� A•.� W�` Certificate of Authorization No.: CA 5491
OR10�,.
70 NA
r�rrr►ri r r n r r titittit►►��
*A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval.
GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
,D E c DYNATECH ENGINEERING CORP.
WWW.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 11.2022
CLIENT: UNIVERSAL US CONSTRUCTION INC.
PROJECT: Prol2osed Residence
ADDRESS: 1202 NE 93rd Street Miami Shores FL 33138
CONTRACTOR: Universal US Construction Inc.
Test No. 12 Location: South side of residence agd 4th lift
Test No. Location:
Test No. Location:
Test No. Location:
Test No. Location:
Description of Material: Tan sand w/rock fra ments
TEST NO. 12
DEPTH 12"
FIELD DENSITY 113.4
MOISTURE CONTENT % 7.5
MAX. DENSITY IN THE FIELD % 99.3
COMPACTION REQUIREMENTS 98%
% OF MAXIMUM DENSITY
100% MAXIMUM DENSITY (LAB) 114.2
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION REQUIREMENTS
AD `����+It s t rI i t rrryr'rf
Tested By: WD `.�` p,.• ..••••• .q 'rf,■ Respectfully Submitted,
Checked By: WN *-r.�s?: `!G E IVS�;•., �1
* ; No. 39584VZ;;iEsa MaamOni,E.
* — DYNATECH ENGINEERING CORP.
. p :• STATE OF Florida Reg. No. 39584
�■ *� Certificate of Authorization No.: CA 5491
ti
*A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval.
B3 MATERIAL TESTING ENGINEERING
1676 West 31 PL., Hialeah FL, 33012 Off. 786,773.5871 - FJK. 786,615-5801
CERTIFICATE OF COMPLETED
May 9, 2022
Waich
400 S. Dixie Highway, Suite 3
Hallandale Beach, Florida 33009
Subject: Foundation Sail Density and Bearing
Capability Certification for Project:
Proposed Residence
1202 NE. 93Id Street., Miami Shores, Fl. 33138
GENTLEMEN:
in accordance with your request, we have inspected the general site preparation procedures
forthe above -named project and soil borings performed by (B3MTE) and density test results
performed by Dynatech Engineering Corp, on May 3, 2022, on fill material used to raise the
site to grade, Site preparation procedures were in accordance with the geotechnical report
prepared by B3 Material Testing Engineering dated May 26, 2021 under project No, 21-0259.
Based on our observation, results of borings and density testing., it is our professional
opinion that the building pad is suitable for the Construction of proposed structure with
foundation proportioned for a design bearing stress of 2500 pounds per square foot
without settlement detrimental to the building placed upon it- In my opinion, the
settlement will not exceed 0.240 inches
y99y5492tz
9; :`� x
sinter,a)p
Dario A. r '
Fla: ftE�- 77 6 -p;L �W
B3 Material nesting En�irlc A4'
! D 1 Y•r<�� � y
WWW. a3Engineering. com
i
ROCHELL ENGINEERING, INC.
May 20, 2022
Mr. Ismael Naranjo - Building Official
Miami Shores Village Building Dept.
10050 N.E. 2nd Avenue
Miami Shores, Florida 33138
Re: 1202 Residence
1202 NE 9311 Street
Miami Shores, FL 33138
Permit Number: RC-09-21-2485
Dear Building Official,
The present letter is to notify to the concerned parties and corresponding authorities that Julio
Torres, as our Field Inspector has performed an inspection of the foundations for this project.
The inspection included a visual review of the foundations based on the compaction performed
by Dynatech Engineering Corp., dated March 8, 2022 and the Foundations Recommendations
specified by B3 Material Testing Engineering on May 26, 2021 under Project No. 21-0259.
The topsoil around the proposed foundations was removed to the necessary depth, backfilled
with a mixture of sand, limerock and limesand fill in compacted layers of approximately six (6)
inches and compacted per AASHTO T-180 to a minimum compaction of 98% of the optimum
dry density. We can attest that the Foundation Recommendations set forth on the Geotechnical
Report have been followed accordingly and recommend your approval of the foundations and to
allow the casting of the Foundations per approved Structural Plans.
Should you have any question regarding the above, please do not hesitate to contact our office.
ResER RO
����111 1 rllllr
• Na. 607350 CC
Alexander Rochell, P.E. �';, STATE: OF 1
Florida Professional Engineer �dc�'•, At aRkpp, 2w�
Registration No. 60735 ��frs�►ON��
Ir1lt I I 1 10
1500 NW 891'' GOUfI- Suite 212, Doral, FL 33172 Tel: 305.649.4049
B3 MATERIAL TESTING ENGINEERING
E s s e n c e o f P e r r e c t i o n
1676 West 31 PL., Hialeah FL, 33012 - Off. 786.773-5871/5889 - Fax. 786.615-5801
May 26, 2021 Project No. 21-0259
SDH Studio
FOUNDATION RECOMMENDATIONS:
Our recommendations are based on the information provided from the client as to the type of structure
planned and on our subsurface investigation performed on the proposed site. Our recommerdations
are as follows:
1. Clear entire building area plus 6-0" outside the perimeter of construction am remove all topsoil,
and unsuitable subsurface material to the necessary depth. We anticipate an average clearanct-
depth of approximately six (6) inches.
2. Compact cleared area to a minimum compaction of 98% of the ❑ptimu:n dry denctty as per
AASHTO T-180. Verify densification procedures by taking an adequate of field density
compaction tests. The cleared area should be inspected prior to the commencement of the
backfilling operation to ensure that all the unsuitable material has been removad.
3. Backfill building area, plus 6-0" outside the perimeter of the structure to the required elevation with
a clean mixture of sand, lime rock and lime sand fill (or approved fill material) in compacted layers
not to exceed 10 inches of thickness. Compact each layer to a minimum of 98% of the optimum
dry density as per AASHTO T180.
4. Excavate footing trenches to the required depth from the ground elevation. Compact the bottom of
the footing trench to a minimum compaction of 98% of the optimum dry density as per AASHTO
T-180. Verify densification procedures by taking an adequate number of field density compaction
tests.
Special Considerations:
a) The subgrade at the design elevation should be observed by a geotechnical engineer and any
topsoil, organic, unsuitable, or deleterious material removed. Proof rolling of the resultant
subgrade should be performed to locate objectionable soils that should be removed. During
the proof rolling procedure, the stripped soil surface is rolled with the heaviest piece of
construction equipment available at the site, such as a heavily loaded tandem axle dump truck
having a gross weight of not less than 25 tons. Areas exhibiting deflection or rutting over 1.25
in (32 mm) should be removed and the proof rolling continued until all unsuitable soils have
been located and removed or improved in -place. However, the on -site inspector should ensure
that the finished subgrade does not exhibit more than 0.5 inch (12.5 mm) of rutting.
b) Floor Slab: After the existing building is demolished and the debris carter off -site, all buried
structures and utilities should be removed from the planned building area plus 5-foot-wide
perimeter. Obtain demolition permit after conducting asbestos surveys before commencement
of demolition activities. The cleared site should be graded and filled to required elevation. Fill
used to raise the building pad should be granular in texture, have not particle size larger than
three inches and have a fines content of no more than 12%.
Page416
I
B3 MATERIAL TESTING ENGINEERING
E s s e n c e o f P e r -f e c. t i o n
1676 West 31 PL., Hialeah FL, 33012 - Off. 786.773-5871/5889 - Fax. 786.615-5801
May 26, 2021 Project No. 21-0259
SDH Studio
i. A vapor barrier should be placed over the building pad fill, prior to placement of
concrete for the floor slab. This will tend to minimize the entrance of subgrade moisture
into the slab. Normally a 10-mil film of polyethylene is used for this purpose.
DESIGN RECOMMENDATIONS:
The above foundation recommendation having been achieved and verified, we anticipate that the
foundation and footings may be appropriately proportioned for a safe soil bearing capacity not to exceed
2,500 psf (pounds per square foot). The use of spread footings and single column oads is suggested.
A monolithic slab foundation may also be adopted.
LIMITATIONS OF STUDY
The exploration and evaluation of the foundation conditions reported herein are considered sufficient
in detail and scope to form a reasonable basis for the foundation design. The recommendations
submitted for the proposed construction are based on the available subsurface information and the
preliminary design details furnished by the client.
Any revisions to the plans for the proposed structure from those enumerated in this report should be
brought to the attention of the soil engineer, so that he might determine if changes in the foundation
recommendations are required. If deviations from the noted subsurface conditions are encountered
during construction, they should also be brought to the attention of the soil engineer, so that he can
review the changed conditions ad revise these recommendations, if warranted.
GENERAL QUALIRCA T1ONS
The analysis and recommendations presented in this report are based upon the data obtained from the
soil borings performed at the indicated locations and from any other information discussed in this report.
This report does not reflect any variations that may occur between borings or across the site. Any
statements which appear in this report or on the boring logs regarding odors, color, unusual or
suspicious items or conditions are strictly for the information of the client. In addition, the soils samples
cannot be relied on to accurately reflect the strata variations that usually exist between sampling
locations. The nature and extent of such variations may not become evident until construction. If
variations appear evident, it will be necessary to reevaluate the recommendations of the report. In
addition, it is recommended that B3 Material Testing Engineering, LLC. be retained to perform
construction observation and thereby provide a complete professional geotechnical engineering service
through the observational method. For environmental due to diligence, a phase I and/or phase II
Environmental Site Assessments is recommended.
Page 5 16
B3
MATERIAL
TESTING
ENGINEERING
E s
s e n c e
o f P e
r f e c t i o n
1676 West 31 PL., Hialeah FL, 33012 -Off. 786.773-5871- Fax. 786.615-5801
CERTIFICATE OF COMPLETED FILL
May 9, 2022
Waich
400 S. Dixie Highway, Suite 3
Hallandale Beach, Florida 33009
Subject: Foundation Soil Density and Bearing
Capability Certification for Project:
Proposed Residence
1202 NE. 93'd Street., Miami Shores, FI. 33138
GENTLEMEN:
In accordance with your request, we have inspected the general site preparation procedures
for the above -named project and soil borings performed by (B3MTE) and density test results
performed by Dynatech Engineering Corp, on May 3, 2022, on fill material used to raise the
site to grade. Site preparation procedures were in accordance with the geotechnical report
prepared by B3 Material Testing Engineering dated May 26, 2021 under project No, 21-0259.
Based on our observation, results of borings and density testing., it is our professional
opinion that the building pad is suitable for the construction of proposed structure with
foundation proportioned for a design bearing stress of 2500 pounds per square foot
without settlement detrimental to the building placed upon it. In my opinion, the
settlement will not exceed 0.240 inches
% , I //!
14
Sincere
Dario A. r "
Fla: Reg. ME* OF W .:
B3 M I esting En iin, �g.
�' �'� .fib p � �9 . • F�.
DHlbm;sdf+sw4
W W W.83Engineering.com
'"£OTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRELUNG SERVICES
-DEd DYNATECH ENGINEERING CORP.
W W W.DYNATECHENGINEERING. COM
MOISTURE -DENSITY RELATIONS OF SOILS
PROCTOR COMPACTION TEST
DATE: March 8, 2022
CLIENT: UNIVERSAL US CONSTRUCTION INC.
PROJECT: Proposed Residence?
ADDRESS: 1202 NE 93rd Sireet. Miami Shores. FL 33138
CONTRACTOR: Universal US Construction. Inc.
MATERIAL DESCRIPTION: Tan sand whock fragments
SAMPLED BY: JA TESTED BY: JA
TEST RESULTS
Sample Number 1
The following compaction test was conducted in accordance with the Standard Methods for Moisture Density Relations of soil using a
10 lb. Hammer and an 18" drop ASTM D-1557.
% MOISTURE
3.9
6.1
8.6
11.7
DRY DENSITY
Optimum Moisture 114.2 Percent
100%Maximum Dry Density 9.9 lbs./cu.R.
% Passing 3/4" Sieve 74.3 Perccr�l
Sampled By: WD
Tested By: WD
108.1
111.8
113.7
112.8
116
114
112
110
108
106
Checked By: WN ►►►►►,ttIIII ►r1111 4 6 8 10 12 14
5Q.••••jC•E NS'• '� '� Respectively submitted,
As a mutual protection to clients, the public and ourselves. all reports �` �� �, f •'•. ��
are submiticd as the confidential property of clients, and authorization
for use, publication of slatcrnents. conclusions or extracts from or regardinor : No• 39584 * i Wissam Na mani, P.E.
our reports is reserved pcndke our written approval. — 9r=DYNATECH ENGINEERING CORP.
:�Florida Reg. No.
.p STATE OF Certificate of Authorization No.: CA 5491
?� •.
'•,,�,�: • �� Q R ID Ilk
11r1rr+t l t 11 t1t►►►�►
D
R
Y
D
E
N
S
I
T
Y
,EOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTINO I ASBESTOS I ROOP TESTING I INSPECTION SERVICES I DRILLING SERVICES
JrD Ec DYNATECH ENGINEERING CORP.
W WIV.DYNATECHENGINEBRINO.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE:
March 8, 2022
CLIENT:
UNIVERSAL US CONSTRUCTION INC.
PROJECT:
Pro used Residence
ADDRESS:
1202 NE 93rd Street. Miami Shores. FL 33138
CONTRACTOR: Universal US Construction Inc.
Test No. I
Location: East side of residence pad, 1" lift
Test No. 2
Location: Center of residence pad, lit lift
Test No. 3
Location: West side of residence pad. lit lift _
Test No. 4
Location: North side of residence pad, 2"d lift
Test No. 5
Location: Center of residence ad 2"d lift
Description of Material: Tan sand wlrock fraements
TEST NO.
1
2
3
4
5
DEPTH
12"
12"
12"
12"
12"
FIELD DENSITY
112.9 1
112.5
112.7
113.0
112.4
MOISTURE CONTENT %
8.6
9.0
8.8
8.4
8.8
MAX. DENSITY IN THE FIELD %
98.9
98.5
98.7
98.9
98.4
COMPACTION REQUIREMENTS
OF MAXIMUM DENSITY
98%
98%
98% 1
98%
98%
100% MAXIMUM DENSITY (LAB)
114.2 1
114.2 1
114.2
114.2 1
114.2
REMARKS: ALL ABOVE TEST -RESULTS COMPLY WITH COMPACTION REQUIREMENTS
����sts s t r u t rrrrrr'�I
SAAD
Tested By: WD ��.�`�Q•• •••• E Respectfully Submitted,
�•'•.; 9
Checked By: WN :���•r • ��� �f y
* , No. 39584 * --
• - Wissa aamanr, P.E.
* = DYNATECH ENGINEERING CORP.
.,p•: STATE OF Florida Reg. No. 39584
�,'P '• ' ��: Certificate of Authorization No.: CA 5491
%f�.: • F� a R 1� •'Grp'
r�r'►rurrnnts�N��'�
"A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual prmc�;ion to the clients, the public and ourselves, all reports
arc submitted as the confidential property of clients, and authorization for publication of statement conclu%ins or extracts from or regarding our reports is reserved
pending on our written approval.
.OTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING 1 INSPECTION SERVICES I DRILLING SERVICES
€c DYNATECH ENGINEERING CORP.
W W W.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 8.2022
CLIENT: UNIVERSAL US CONSTRUCTION, INC.
PROJECT: Proposed Residence n
ADDRESS: 1202 NE 93" Street Miami Shores. FL 33138
CONTRACTOR: Universal US Construction. Inc.
Test No. 6 Location: Soil side of residence pad. 2"d lift
Test No.
Location:
Test No.
Location:
Test No.
Location:
Test No.
Location:
Description of Material: Tan sand whock fra ments
TEST NO.
6
DEPTH
12"
FIELD DENSITY
112.7
MOISTURE CONTENT %
8.7
MAX. DENSITY IN THE FIELD %
98.7
COMPACTION REQUIREMENTS
% OF MAXIMUM DENSITY
98%
100% MAXIMUM DENSITY (LAB) 1
114.2
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION RL• UIREMENTS
���tttttttt+r►er►1►
Tested By: WD ,``�•`P�,.SAAfl•h'4rrrr,�fA
ti
Respectfully $ubmitted,
Checked By: WN -fit?; `IC E ✓Ifse •:,� •.�
' No. 39584 - -
Wissam Naarnani, P.E.
* = DYNATECN ENGINEERING CORP.
0% STATE OF '4tr S Florida Reg, No. 39584
C2'•.•,.�. •�� Certificate of Authorization No.: CA 5491
00
►ss70hfALj�•�'`�
►►►r►rrtItlltttWt 0
•A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
arc submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval.
,QTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
�oEc DYNATECH ENGINEERING CORP.
WWW.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 8.2022
CLIENT: UNIVERSAL US CONSTRUCTION. INC.
PROJECT: Proposed Residence ng
ADDRESS: 1202 NE 93rd Street. Miami Shores, FL 33138
CONTRACTOR: Universal US Construction, Inc.
Test No. 7 Location: South side of residence pad, 3rd lift
Test No. 8 Location: _ Center of residence pad. 3rd lift
Test No. 9 Location: ^ West side of residence pad. 3rd lift _
Test No. 10 Location: North side of residence pad. 41h lift
Test No. 11 Location: Center of residence pad, 4th lift
Description of Material: Tan sand w/rock fragments
TEST NO.
7
8
9
10
11
DEPTH
12"
12"
12"
12"
12"
FIELD DENSITY
113.1
113.5
112.6 1
112.8
113.3
MOISTURE CONTENT %
8.2
7.9
7.6
8.4
8.1
MAX. DENSITY IN THE FIELD %
99.0
99.4
98.6
98.8
99.2
COMPACTION REQUIREMENTS
% OF MAXIMUM DENSITY
98%
98%
98%
98%
98%
100% MAXIMUM DENSITY (LAB) 1
114.2 1
114.2
114.2 1
114.2 1
114.2
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION REQUIREMENTS
,,,,ttun+rrrr►►
t,> X* SAAD �►�.,,
Tested By: WD .�`��..,. �� E Ns. .q�,Respectfully Submitted,
Checked By: WN .����: �-
* ; No. 39584 * _ -
Wissarn Naarnani. P.E.
* = DYNATECH ENGINEERING CORP.
STATE OF Florida Reg. No. 39584
���/ f,•,: ' ��� Certificate of Authorization No.: CA 5491
to •rffi C s ... S
NitYlONA ON,
•A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring lest must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
arc submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval
„gpTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
Ec DYNATECH ENGINEERING CORP.
V WW.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: March 11, 2022
CLIENT: UNIVERSAL US CONSTRUCTION, INC.
PROJECT: Proposed Residence r@ _
ADDRESS: 1202 NE 93rd Street. Miami Shores FL 33138
CONTRACTOR: Universal US Construction Inc. _
Test No. 12 Location: South side of residence pad. 4 h lift
Test No. Location:
Test No. Location:
Test No. Location:
Test No. Location:
Description of Material: Tan sand w/rock fragments
TEST NO.
12
DEPTH
12”
FIELD DENSITY
113.4
MOISTURE CONTENT %
7.5
MAX. DENSITY IN THE FIELD %
99.3
COMPACTION REQUIREMENTS
OF MAXIMUM DENSITY `
98%
100% MAXIMUM DENSITY (LAB) 1
114.2
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION REQUIREMENTS
,���►tltfIII fill►►►/
'CipAa ,••�� Res ectfull Submitted,
Tested By: WD .��` Q� � �`�� Respectfully
Checked By: WN �.•` tamNS�:•.,,�'.�
Nv. 39584 1�
Wissat Naamani. P.E.
* = DYNATECH ENGINEERING CORP.
STATE OF Florida Reg. No. 39584
�� F A•;` Certificate of Authorization No.: CA 5491
►,s10NA1.�►
�►1tPIilTittt���
•A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination a
soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all reports
are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is reserved
pending on our written approval.
GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
DYNATECH ENGINEERING CORP.
W W W.DYNATE CHENGINEERING.COM
Miami, May 3, 2022
Mr. Ricardo Elias
UNIVERSAL US CONSTRUCTION, INC.
9330 SW 1681h Street
Palmetto Bay, FL 33157
Re: Proposed Residence @
1202 NE 931d Street
Miami Shores, FL-1-3138
Dear Mr. Elias:
Pursuant to your request, Dynatech Engineering Corp. (DEC) performed a Compaction Test on
May 3, 2022 at the above referenced project. DEC was authorized to perform a compaction test
only. The purpose of our test was to determine the degree of compaction of the tested layer of
material only. In no way shall a compaction test replace a demucking inspection, soil bearing
capacity determination, or a pad certification. A soil boring test must be performed by client if
not yet done, prior to construction to verify subsoil conditions. Underlying soils below test levels
must be verified to prevent future settlements. (DEC) was not authorized to perform supervision
and certification of the building pad preparation. This is not a pad certification. Our reports must
be provided to all involved parties for their approval.
Our findings are relative to the date and areas of our site work and should not be relied upon to
represent conditions on other areas or dates. Any subsequent site disturbances due to water
erosion, rain, storm gutters discharging at footings, construction activities, excavations,
overgrown, vegetation, traffic and other disturbances will void this test and the site must be re -
compacted and re -tested prior to construction.
Environmental analysis of the soil materials is not part of the scope of services. If environmental
analysis of the soils is required, we can provide a proposal for performing an environmental
analysis of the soil materials. No other analysis is implied or warranted.
As a mutual protection to clients, the public and ourselves, all reports are submitted as the
confidential property of clients, and authorization for use, publication of statements, conclusions
or extracts from or regarding our reports is reserved pending our written approval.
Enclosed find copies of the compaction test results. It has been a pleasure working with you and
look forward to do so in the near future.
Sincerely yours,
til
�1
Wissam aamani, P. E.
DYNATECH ENGINEERING CORP.
Florida Reg. No. 39584
Special Inspector No. 757
Certificate of Authorization No.: CA 5491
���IIIIIII!!lr++�
�.�`,`+��► 5AA D N�gr`,�r�
k ; No. 39584
.fl STATE OF r oc�-
''•tea-' Q Rtda�'{`.'=
G
F 111+li111111+�',1 `
1
GEOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
�DEc DYNATECH ENGINEERING CORP.
WWW.DYNATECHENGINEERING.COM
MOISTURE -DENSITY RELATIONS OF SOILS
PROCTOR COMPACTION TEST
DATE: May 3.2022
CLIENT: UNIVERSAL US CONSTRUCTION INC.
PROJECT: Proposed Residence @.
ADDRESS: 1202 NE 93rd Street. Miami Shores. FL 33138
CONTRACTOR: Universal US Construction, Inc.
MATERIAL DESCRIPTION: Tan sand
SAMPLED BY: WD TESTED BY: WD
TEST RESULTS
Sample Number 1
The following compaction test was conducted in accordance with the Standard Methods for Moisture Density Relations of soil using a
10 lb. Hammer and an 18" drop ASTM D-1557.
% MOISTURE
4.9
6.3
7.9
12.0
DRY DENSITY
Optimum Moisture 9.2 Percent
100% Maximum Dry Density 1 QL lbs./cu.ft.
% Passing 1/4" Sieve 96 Percent
Sampled By: WD
Tested By: WD
1020.2
103.8
105.2
104.4
108
106
104
102
100
98
Checked By: WN A`AQ►rr► 4 6 8 10 12 14
N Res ectivel submitted
��� ��••'•1 Ci•E 1NS'' �/ �'. P Y ,
As a mutual protection to clients, the public and ourselves, all reports ' • �' £�•'•.'�
are submitted as the confidential property of clients, and authorization =• No. 39584
for use, publication of statements, conclusions or extracts from or rcgard'mg* W issarn Naam ,
our reports is reserved pending our written approval. — * S)YNATECH NGINEERING CORP_
.� SfATE OF ;�Tlorida Reg. No. 39584
• 4► Certificate of Authorization No.: CA 5491
ol el
OR
D
R
Y
D
E
N
S
I
T
Y
2
GLOTECHNICAL I ENVIRONMENTAL I MATERIALS TESTING I ASBESTOS I ROOF TESTING I INSPECTION SERVICES I DRILLING SERVICES
j,',jrE'6 DYNATECH ENGINEERING CORP.
WWW.DYNATECHENGINEERING.COM
FIELD DENSITY TEST OF COMPACTED SOILS
DATE: Mqy 3 2022
CLIENT: UNIVERSAL US CONSTRUCTION, INC.
PROJECT: Proposed Residence 1�7a,
ADDRESS: 1202 NE 93rd Street. Miami Shores, FL 33138
CONTRACTOR: Universal US Construction, Inc.
Test No. 1 Location: East side of residence underslab
Test No. 2 Location: West side of residence underslab
Test No. 3 Location: Center of residence underslab
Test No. 4 Location: North side of residence underslab
Test No..5 Location: South side of residence underslab
Description of Material: Tan sand
TEST NO.
1
2
3
4
5
DEPTH
12"
12"
12"
12"
12"
FIELD DENSITY
105.2
105.6
104.9
105.8
105.1
MOISTURE CONTENT %
7.0
7.4
6.8
7.7
7.1
MAX. DENSITY IN THE FIELD %
98.5
98.9
98.2
99.1
98.4
COMPACTION REQUIREMENTS
% OF MAXIMUM
98%
98%
98%
98%
98%
100% MAXIMUM DENSITY (LAB)
106.8
106.8
106.8
106.8 106.8
REMARKS: ALL ABOVE TEST RESULTS COMPLY WITH COMPACTION REQUIREMENTS
* Please note this is not a pad certification. A soil boring must be performed to determine subsoil conditions below the tested compaction layer prior
to construction. '`,►��i11111l111111f,
5AA D N,�q•,,,f, Respectfully submitted,
Tested By: WD
Checked By: WN ' * •. No. 39584
fDYNATECH ENGINEERING CORP.
.0 STATE OF .'�� Florida Reg. No. 39584
�p^;. f� 0 1D Certificate of Authorization No.: CA 5491
. \
NA
1j"IfI111a/m►►��
*A density test determines the degree of compaction of the tested layer of material only. In no way shall a density test replace a soil bearing capacity determination.
A soil boring test must be provided by client, prior to construction to verify subsoil conditions. As a mutual protection to the clients, the public and ourselves, all
reports are submitted as the confidential property of clients, and authorization for publication of statement conclusions or extracts from or regarding our reports is
reserved pending on our written approval.
3
21 P - Awpa i e- I - i Z 7 2:7 ---1 Z �- '�� z �//2 / ; a 9 0 r J
3256 W Hillsboro Blvd. Deerfield Beach, FL 33442
Phone: (954) 549-5509
m)ww.pestdepot• coy?
Date of Treatment(s): May 4, 2022
1202 NE 93rd Street, Miami Shores, FL 33138
This structure has received a treatment for the prevention of subterranean termites.
This treatment is in accordance with the rules and regulations established by the
Florida Department of Agriculture, Consumer Services and Broward County
Codes. If you have any questions or concerns please feel free to contact us at the
number above.
EM
3256 W Hillsboro Blvd, Deerfield Beach, FL 33442
Phone: 954-549-5509
Certified Environmental Inspectors and Remediation Specialists
Balancing Life in the Soil, the Foundation of Life
"Intellligent Termite Control"
TERMITE CONTROL A NOTICE OF THIS TREATMENT HAS BEEN AFFIXED TO THE FUSE
SERVICE AGREEMENT BOX OR HOT WATER TANK UNLESS OTHERWISE INDICATED
I� Residential i,.... Commercial
PURCHASER NAME
STREET ADDRESS
CITY STATE ZIP CODE
786,715.1873
SERVICE PHONE
METHOD OF PAYMENT
Payment upon completion fir Terms -Stated Below
At Closing -Title Co T
"title Co -Add F
50% Deposit
Terms TO BE PAID IN FULL PRIOR TO TREATMENT
PESTDEPOT.COM IS HEREBY AUTHORIZED TO TREAT
THE PREMISES DESCRIBED ABOVE FOR THE CONTROL OF:
Dryw ood Termites eControl of
• Subterranean Termites (' Presumptive Evidence Of
I• other Soil Pretreat f1� Prevention of
Fumigation -" Clean Heat
Localize Treatment
SERVICE AGREEMENTS:
Lifetime Retreatment Renewable Service Agreement
5 Year Renewable Service Agreement
No Guarantee Issued
1 Year Guarantee Limited
Damage Guarantee Additional $
PESTDEPOT.COM will retreat the structure(s) for covered Termites at no
cost to the Customer should an infestation be found.
Buyer agrees to pay a late charge the greater of $25.00 or 10% of the
amount of any installment which is not paid within 10 days of date due,
In case of default in the payment of any installment for more than 30
days. PESTDEPOT.COM, or its assignee, may elect to declare the entire
balance to be immediately due and payable together with all costs of
collections, Including reasonable attorney's fees.
CONTINUOUS PROTECTION AGREEMENT
Annual Renewal payment is currently: $
plus lax where applicable PESTOEPOT COM reserves the right to change the renewal amount a'
any time without prior notice or terminate this agreement if terms and conditions are not coirnPhe[
will, A transfer fee of $35 will be charged to transfer this agreement Change in Law: In IM
evenl of a change In applicable Federal Slate., or Local Law. material In the manner in whitll
I'CSTDI'POI COM delivers its services or discharges its obligations under this agreement
R I•SIOFPOT COM reserves the right to increase the Annual Renewal Fee wghcut the .[ry7uvt
:-u-tionud Iimitalion or terminate this agreement,
Date of Treatment Wed 05/04/22 9:00
LIMITED RE -TREATMENT ONLY GUARANTEE
NAME
1202 NE 93rd Street
STREET ADDRESS
Miami Shores FL 33138
CITY STATE ZIP
Soil Pretreat 2028 Sq Ft Outside _
TYPE NUMBER STRUCTURES
DEV: GRID LOC:
1. Initial Treatment - Soil Pretreat $800.00
2. Other Service
3. Tax
4. Total Price $800,00
5. Less Cash Down payment
6. Unpaid Balance Due $800.00
(to be paid as slated below)
1. THIS CONTRACT CONTAINS EXCLUSIONS, LIMITATIONS
AND DISCLAIMERS LISTED ON THE REVERSE SIDE
2. YOU THE BUYER MAY CANCEL THIS TRANSACTION ANY
PRIOR TO MIDNIGHT OF THE THIRD (3RD) BUSINESS DAY
AFTER THE DATE OF THIS TRANSACTION
3. YOU ARE ENTITLED TO AN EXACT EXECUTED COPY OF
THIS AGREEMENT
4. ALL OR PART OF THIS WORK MAY BE SUBCONTRACTED
A CERTIFIED AND LICENSED COMPANY
Accepted by (Print)
BUYER OR BUY R'5 AUrtlOytl7FO AGF T SiGNATURf r
YE?Srpf:PL 31 CID • IN CT4f7
'Notice of IcWstm it as been affixed
Comments:
954-549-5509
www.pestdepoLcom ' www.wholesaletermite.com
www.wholesalefurnigation.corn ' www.wholesalemold.corn '
www.wholesalerodents.com
GENERAL TERMS AND CONDITIONS
By specific, reference hereto. the Purchaser understands that General Terms and Conditions are hereby made a part of the Service Order and apply without exception. Purchaser
further understands that their signature on this Agreement accepts the terms offered by PESTDEPOT.COM, hereby referred to as "The Company," for good and valuable
consideration receipt of which is hereby acknowledged.
1. If moisture and/or structural conditions which are conducive (o Termites are subsequently found to exist without ground contact, then The Company shall be relieved of any
and all liability.
2. Structural or mechanical defects which result in water leakage in interior areas or through the roof or exterior walls of the premises may destroy the effectiveness of The
Company's treatment, thereby permitting infestation to continue after the dale of Initial treatment. If such a condition is discovered, it Is agreed that the customer will be
responsible for making such repairs as are necessary to correct the structural or mechanical defect(s) immediately upon discovery of such defect. Should a re -treatment of
any affected area(s) be needed, the expense of such will be charged to the customer as a condition of a continuation of the warranty, or warranty may be terminated unless
full re -treatment is purchased by purchaser.
3, The Company's liability shall be terminated should 'fhe Company be prevented from fulfilling its responsibilities under the terms of this Service Order of the Guaranty by
reason of Acts of War, whether declared or undeclared, Acts of any duly constituted Government Authority, strikes, or Acts of God.
4, This Agreement covers the premises diagramed on (he Graph and Specifications Sheet as of the dale of actual treatment, and in the event the premises are structurally
modified, altered, or otherwise changed after the date of initial treatment, this Agreemen( shall terminate unless a prior written agreement shall have been entered Into by the
Purchase for The Company unless alteration or changes in writing and executed by a corporate officer of The Company under the corporate seal.
5. It is understood and agreed between the parties that this Contract, the Graph and Specifications Sheets which bear this Contract Number, and, upon issuance, the Guaranty
constitute the complete agreement between parties and that said agreement may not be changed or altered in any manner, oral or otherwise, by any representative of The
Company unless alteration of change be in writing and executed by a corporate officer of The Company under the corporate seal.
6. This Agreement is a limited control guarantee, which is limited to local lrealment only and does nol cover re-lurnigation after the initial one yearguarentee. The Company shall not be liable for any
consequential damage as a result of treatment to the subject properly. Re -inspection will be done it requested or will be done annually at the lime of renewal
%.. It is understood and agreed between (he parties that should it be necessary for The Company to institute legal proceedings to recover damages from the Purchaser for the
breach of this Agreement or for non-payment under its terms the Purchaser shall be responsible for and shall pay all of The Company's attorney's fees, court costs, pre and
post tudament interest. and anv and all collection fees,
8. Payment shall be made within thirty (30) days from the date of services rendered Any account with an unpaid balance at the end of said term will be charged interest on the
unpaid portion of the rate of 1.5% (one and one half percent) interest per month until such time the account has been paid in full.
9- It is understood and agreed between the parties that the Purchaser's signature on this agreement acknowledges notice of hen on the structure(s)which form the subject
matter of (his agreement, In the event that legal or collection measures are necessary to enforce the terms of this agreement.
10. The Company's liability under this contract shall terminate when access to the premises for the purpose of carrying out the terms and conditions of the contract is refused by
the Purchaser or its agent,
11. The Company will exercise reasonable care in its treatment procedures but will not accept responsibility for broken roof tiles, gutter, solar healer, landscape foliage, puncture
and subsequent leakage of undetectable buried or hidden water pipes, electrical conduits, TV cables. and A/C or Healing ducts or plumbing, or any other inadvertent
damage occasioned by properly performed procedures.
12. Notwithstanding that the serviced property is the subject of real estate transfer, refinance, etc., payment for services rendered shall be made within the staled time.
13, This agreement shall be governed by the laws of the Stale of Florida and venue with respect to any legal action to enforce, interpret, or otherwise deal with any provision
hereof shall be maintained exclusively in Broward and Palm Beach Counties, Florida.
14, All or part of this work may be contracted to a Certified and Licensed Company.
15, Postponement or job must be received by 9:00 AM of the prior day prior to the date of (he scheduled job Fee for postponement wlthoul required no(ce: 20% of fumigation lee
16. SUBTERRANEAN TERMITE WARRANTY DOES NOT INCLUDE FORMOSAN TERMITE TREATMENT (COPTOTERMES FORMOSANUS) UNLESS SPECIFICALLY
NOTED ON THE FRONT OF THIS CONTRACT.
SUBTERRANEAN TERMITE LIMITED CONTROL. GUARANTEE
SUBJECT TO THE GENERAL TERMS AND CONDITIONS, 'THE COMPANY WILL ISSUE A LIMITED CONTROL GUARANTEE AND. AT NO EXTRA COST
APPLY ANY NECI:'SSARY ADDITIONAL_ TREATMENT TO THE: PRE.MISF..S IF RF-INFFS'fAfION IS FOUND THEREIN DURING THE PERIOD OF THE
GUARANIEE THE PURCHASER FURTHER UNDERSTANDS THATTHE COMPANY'S LIABILITY UNDER'THIS AGREEMENT IS LIMITED TO RETREATEMNT
ONLY AND IS IN NO WAY IMPLIED OR OTHERWISE IS RESPONSIBLE FOR DAMAGES OR REPAIRS TO THE STRUCTURE OR CONTENTS.
DRYWOOD TERMITE, POWDER POST BEETLE AND WOOD BORER LIMITED GUARANTEE
SUBJECT TO THE TERMS AND CONDITIONS THE COMPANY WILL RETREAT THE STRUCTURE FOR THE CONTROL OF DRYWOOD TERMITES OR
POWDER POST BEETLES AND WOOD BORERS, AND WILL ISSUE A LIMITED CONTROL GUARANTEE WHICH WILL PROVIDE FOR RETREATMENT AT NO
EXTRA COST, SHOULD A RE -INFESTATION BE DISCOVERED DURING THE PERIOD THE GUARANTEE IS IN FORCE. COMPANY'S LIABILITY UNDER THIS
AGREEMENT IS LIMITED TO RETREATMENT ONLY AND IN NO WAY. IMPLIED OR OTHERWISE, IS RESPONSIBLE FOR DAMAGES OR REPAIRS TO THE
STRUCTURE OR CONTENTS.
Florida Department of Agriculture and Consumer Services
--r� Division of Agricultural Environmental Services
CONSUMER NOTICE FORM
NICOLE "NIKKI" FRIED Rule 5E-14.105, F.A C.
COMMISSIONER
A pest control company must give you a written contract prior to any treatment of each wood -destroying organism. It is very
important that you read and understand the contract you are signing. The pest control company is only obligated to follow the
terms of the contract you have signed, regardless of other statements by the company or salesperson. (Note: Contracts for
treatment for new construction can be issued to the builder and provided to you at closing).
BASIC REQUIREMENTS F,QR CQNTRACTS
• The contract must state the common name of the wood -destroying organism to be controlled by the company (e.g. subterranean
termite, powder post beetle). If the contract is for termite control, the contract must clearly state whether Formosan termites are
covered or not.
• Some contracts do not include a treatment at the time the contract is issued, and that should be clearly stated. If a treatment is performed
as part of the contract, the cost for the treatment must be stated. If the treatment is only for certain areas. the contract should clearly
state that it is for "spot treatment" only.
• The contract must state if it is a retreatment only or a retreatment and repair contract. If it is a retreatment and repair contract, carefully
read the sections of the contract that state when repairs will or will not be covered by the contract.
REQUIREMENTS FOR STATING WHEN TREATMENT OR REPAIR WILL NOT BE COVERED BY THE CONTRACT
• Repair contracts will not cover repairs from termite damage under every condition. The contract must state when retreatment or
repair will be done, and conditions under which the company can refuse to retreat or repair,
• These conditions have to be stated and be under headings in the contract that are in bold print. Companies typically refuse repair or
retreatment if the condition of the house is such that moisture or leaks result in termite infestation, or where siding makes it hard to see
termite infestation
Examples of this are:
• Cracks in concrete slabs
• Wood or wall siding in contact with ground
• Plumbing leaks
• Leaks in the roof
• Water accumulating against side of house
The law does require that companies notify you if they see conditions which would void the repair promise and they have to give you a
chance to correct the condition before voiding the contract or denying repair coverage.
• Contracts may have a condition that does not cover Formosan termite damage until a specific time period has passed. This means
that if damage occurs during this period the company will not pay for repair.
■ You have the right to compare contracts from other companies before signing a contract with a company. Choose the company that
gives you the best contract options.
■ If you have any questions about the terms of the contract, cr concerns about the compliance history of the company with regard to
pest control laws or regulations, contact the Department of Agriculture and Consumer Services at phone number: 850-617-7996 or
email: biircomplaints@fdacs.gov.
I understand that I am enteringinto a contract with PESTDEPOT.COM
(fill in company name) to
provide wood -destroying organism(s) treatment, and I have read and understood the terms of the contract.
Print Name of Consumer
Signature of Consumer
Print Name of P 9t ConlrbAlepresentative
Signature of Pest Cont
Vprer ati
FDACS-13692 Rev 07/21
Dat
Title: Property Owner orr authorized agent
Company, PESTDEPOT. COM
Page 1 of 2 (La traduccibn espa)ola en la espalda)
Bureau of Inspection and Incident Response, 850-617-7996
New Construction Subterranean Termite OMB Approval No.2502-0525
Service Record (exp.05/30/2018:
This form is completed by the licensed Pest Control Compan
Public re.portIng burden for this collection of information is estimal[i} Ur average 15 minutes per response, including the time for reviewing instructions,
searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information. This Information
tis required to obtain benefits. HUD may not collect this information, and you are not required to complete this form, unless it displays a currently valid OMB
control number,
Section 24 CFR 200,926d(b)(3) requires that the sites for HUD insured structures must be free of termite hazards. This information collection requires the
6UiIdef 10 certify that an authorized Pest Control company performed all required treatment for termites, and that the builder guarantees the treated area
against Infestation for one year. Builders. pest control companies, mortgage lenders, homebuyers, and HUD as a record of treatment for specific homes will
Use the information collected. The information is not considered confidential, therefore, no assurance of confidentiality is provided.
'This report is submitted for informational purposes to the builder on proposed (new) construction cases when treatment for prevention of subterranean termite
infestation is specified by the builder, architect, or required by the: lender, architect, FHA, or VA.
All contracts for services are between the Pest Control company and builder, unless stated otherwise.
Section 1: General Information (Pest Control Company Information)
Company Name: Pestdepot.corn
Company Address 3256 W Hillsboro Blvd
Company Business License No, JB:312274
FHA/VA Case No. (if any)
Section 2: Builder Information T
Company Name
Section 3: Property Information
City Deerfield Beach State FL
Company Phone No. 954-549-5509
Phone No. 786.715.1873
Zip 33442
Location of Structures Treated Street Address or Legal Description, City,State and Zip) 1202 NE 93rd Street, Miami Shores, FL 33138
Section 4: Service Information
Date(s) of Service(s) 05/04/22
Type of Construction (More than one box may be checked) Fx I Slab Basennont l ] Crawl U Other
Check all that apply:
[,� A. Soil Applied Liquid Termiticide
Brand Name of Termiticide: Premise EPA Registration No. 432-1331
Approx. Dilution (%): 0.05 Approx. Total Gallons Mix Applied: 203 - - Treatment completed on exterior: [x_� Yes [ No
B Wood Applied Liquid Termiticide
Brand Name of -Termiticide' _ _ _ EPA Registration No..
Approx Dilution (%): Approx. Total Gallons Mix Applied;
C. Bail system Installed
Name of System
D. Physical Barrier System Installed
Name of System
EPA Registration No.- Number of Stations installed
Attach installation information (required)
Service Agreement Available? ✓ Yes No
Note' Some state laws require service agreements to be issued. This form does not preempt state law.
Attachments (List) Contract
Comments 2028 SQ FT Outside
Name of Applicator(s) StanleyJacobs - _ y Certification No. (if required by State law) JE„1 21307
The applicator has used a product in accordance with the product label and state requirements All materials and methods used comply with state and federal
regulations.
Authorized Signature t� Date 05/04/22