Loading...
RF-04-22-1030 UPLIFTLank Engineering LLC. Testing & Engineering Services Tel: 954.245.8976; Fax: 954.301.7776.; 5230 NE 18 Avenue Fort Lauderdale, FL 33334 Roof Tile Uplift Test Report Attention: City of Miami Beach, Building Division, 1700 Convention Center Drive, Miami Beach, FL 33139 Client: On Time Roofing Test Date: 03/18/2022 Permit # RF-12-22-1030 Property Address: 10626 NE 11 Court, Miami Beach, FI Roof Pitch: Type of Tile: Roof Area: 3 in 12 Roof Tile per NOA 30.00 squares Tile Attachment Method: Two Component Polyurethane Foam Adhesive -Poly Pro AH 160 Field Instrument : IMADA Force Gauge 0-100 Serial number: 243454 Test Location Total Number of Tests Field Uplift Pull Test Test results Perimeter Area: 12.00 sq. 12 As per FBC 2020 Passed Field Area: 18.00 sq. 18 As per FBC 2020 Passed 8No. of Corner: 8 8 As per FBC 2020 Passed Ridge Areas: 260 pcs. 26 As per FBC 2020 Passed Important. These laboratory results can change due to future weather impacts and /or unavoidable roof traffic. Therefore, this report represents the TAS 106 results at the time of the test. All tested locations were done using an Imada Force Gauge instrument with a minimum uplift load of 35lbs (for mortar or adhesive set tiles) and for mechanically attached tiles a minimum static test uplift load of 80% of the Resistance Moment (Mr') or 80% of the Resistance Load (f ) as listed in Product Approval (NOA) was applied. Please see attached a Roof Sketch for this project. Cordially, Lank Engineering LLC. (NOA 21-1122.01) Andre Bigatao, PE Fla. Reg. No: 80977 MAY i i 2929 . �. .