RC-11-21-3128 SPECIAL INSPECTION1985 South Ocean Dr. Suite GL-3
Hallandale Beach, FL 33009
April 20, 2022
Inspection Report 21366-01
CLIENT: HRT Construction Group
ATTENTION: Contractor / Owner
SPECIAL INSPECTION REPORT
PERMIT M RC-11-21-3128
PROJECT: 21366
10634 NE 11 th Ave
Miami Shores, FL 33138
Main: (954) 591-8361
Fax: (954) 591-8361
Services@NOHMIS.com
www.NOHMIS.com
As requested, a representative of NOHMIS, LLC (NOHMIS) visited the subject site to do a visual inspection of the
placement of the field welds of structural steel support elements. This report outlines our findings.
PROJECT'S REFERENCED DOCUMENTS
1. Structural Floorplan submitted within Permit Package
2. Florida Building Code 71 Ed (2020)
DESIGN MODIFICATION
1. Per city inspector's request, we have reviewed the site condition of the bolt holes. Use of (2) 1-7/8" diameter x
1/8" thick washers are acceptable with the spacers (as inspected) inserted inside the steel holes.
2. Structural steel plates required to develop the bending resistance are the 8x8x1/2" plates on both sides of the
existing RC beam with the through bolts as noted on the plans. The plate underneath the beam is for stability and
continuity and is not part of the structural capacity requirement. Therefore, tack welds of the plate as inspected
are acceptable.
INSPECTION RESULTS: PASSED
On April 5, 2022, our representative visited the subject site and conducted visual observations.
Visual observation of the placement of structural steel installation bolting and welds was conducted. The work
listed was found to be in substantial conformance with the project's reference documents.
Contractor may continue work with the local building department approval.
Feel free to contact our office at 954-591-8361 anytime for further questions and/or comments with regards to this Project.
RespeFSimhon,
Josep PE
PE 86388
Principal
Joe@NOHMIS.com
954-591-8261 Ext 702
��155nuururr�r�
Digitally signed ,''`�oS�P" sry•..,`
by Joseph -*. No.86388 *�
Simhon
STATE OF
Date: 2022.04.26 R1 a..G X,:`
' 11:30:37 -04'00
CA FL 33057 Report #21366-01 Page 1 of 1
Miami Shores Village - BUILDING DEPARTMENT
10050 NE 2 Ave Miami Shores, FL 33138
305-795-2204 www.msvfl.gov
NOTICE OF EMPLOYMENT AS SPECIAL INSPECTOR Process Number: RC - 11 - 21 - 3128
I (We) have been retained by HRT construction Group to perform special inspector services under the Florida Building Code
71" Edition (2020) and Miami Dade County Administrative Code at the 10634 NE 11th Ave Miami Shores, FL 33138
project on the below listed structure as of 12/14/21 (date). I am a registered architect/professional
engineer licensed in the State of Florida.
Special Inspector for Reinforced Masonry, Section 2122.4 of the FBC 7T" Edition (2020)
Miami Dade County Administrative Code, Article II Section 8-22 Special Inspector for
_ Trusses > 35 ft. long or 6 ft. high
V5teel Framing and Connections welded or bolted Per city inspector's request.
_ Soil Compaction
Precast Attachments
Roofing Applications, Lt. Weight. Insul.Conc.
Other
Note: Only the marked boxes apply.
The following individual(s) employed by this firm or me is authorized representative to perform inspection*
1. 2.
3. 4.
*Special inspectors utilizing authorized representatives shall insure the authorized representative is qualified by
education or licensure to perform the duties assign by Special Inspector. The qualifications shall include licensure as a
professional engineer or architect: graduation from an engineering education program in civil or structural engineering;
graduation from an architectural education program; successful completion of the NCEES Fundamentals Examination; or
registration as building inspector or general contractor.
I (we) will notify the Miami Shores Building Department of any changes regarding authorized personnel performing
inspection services.
I (we), understand that a Special Inspector inspection log for each building must be displayed in a convenient location on
the site for reference by the Miami Shores Building Department Inspector. All mandatory inspections, as required by the
Florida Building Code must be performed by the Miami Shores Building Department. Inspections performed by the
Special Inspector hired by the owner are in addition to the mandatory inspections performed by the department.
Further, upon completion of work under each Building Permit, I will submit to the Building Inspector at the time of the
final inspection the completed inspection log form and a sealed statement indicating that, to the best of my knowledge,
belief and professional judgment those portions of the project outlined above meet the intent of the Florida Building
Code and are in substantial accordance with the approval plans.
Digitally signed �a!V1'I yam'-.,� Name Joseph Simhon, PE
Sig&PA109f5PMdd ;' No. 86388 '; . � Engineer / Architect - Print
Simhon
STATE OF
Address 1985 South Ocean Dr Suite GL-3, Hallandale Beach, FL 33009
' 11:29:48 -04'00
., r''pnrrunp
Rev10082021 Special Inspector Notice Page 1 of 1