May 11, 2022
Isaac's Roofing & Insulation
17225 South Dixie Highway, Unit 200
Miami, FL 33157
RE: TILE UPLIFT TEST
PROJECT INFORMATION PROVIDED BY CLIENT:
10090 NE 12 Ave
Miami Shores, Florida
Parcel ID 11-3205-019-0380
Permit #: RF-01-22-203
Date inspected: May 11, 2022
Date completed by: May 7, 2022
Roofing Contractor: Isaac's Roofing & Insulation
Carlab, Inc Project # 22-1274
Testing lab Certificate #: 19-0110.01
Dear Sirs,
In accordance with your request and authorization, a representative of Carlab, Inc completed the Roof
Tile Uplift Test at the above referenced project. This testing was performed in general accordance with
Roofing Application Standard TAS No.106 Standard procedure for field verification of the bonding of
mortar or adhesive set tile system and mechanically attached, rigid, discontinuous roof systems.
The total of the tested roof surface area was estimated to be less than 4800 square feet, and the mean
height of the roof is less Windsor Roof Tile. This tile was reported to have been foamed in place.
At the time of this testing at least one test for every 100 square feet of roof tile in the perimeter area,
one test for every 200 square feet of roof tile in the field area, and one test per corner were performed.
The results for this report are valid at the time of testing only. Walking on the roof or any other type of
physical disturbance may alter these results.
Based on our test results, we conclude that the installation of the roof tile at the above referenced
project meets the test requirement outlined in the above mentioned protocol. Attached please find a
copy of our test report for your review.
Should you have any questions or if we may be of further assistance, please do not hesitate to contact the
undersigned.
Respectfu ubmitfe' ; {t' .
J
Sergio Labistq PE 61 33
8730 SW 25 STREET • MIAMI • FL • 33165 • PHONE: 305.283.3512 *FAX: 305.226.0438
Test
Test load
(lbf)
Test
Status
109
35
Pass
110
35
Pass
111
35
Pass
112
35
Pass
113
35
Pass
114
35
Pass
115
35
Pass
116
35
Pass
117
35
Pass
118
35
Pass
119
35
Pass
120
35
Pass
121
35
Pass
122
35
Pass
123
35
Pass
124
35
Pass
125
35
Pass
126
35
Pass
127
35
Pass
128
35
Pass
129
35
Pass
130
35
Pass
131
35
Pass
132
35
Pass
133
35
Pass
134
35
Pass
135
35
Pass
136
35
Pass
137
35
Pass
138
35
Pass
139
35
Pass
140
35
Pass
141
35
Pass
142
35
Pass
143
35
Pass
144
35
Pass
145
35
Pass
146
35
Pass
147
35
Pass
148
35
Pass
149
35
Pass
150
35
Pass
151
35
Pass
152
35
Pass
153
35
Pass
Test
Test load
(lbf)
Test
Status
154
35
Pass
155
35
Pass
156
35
Pass
157
35
Pass
158
35
Pass
159
35
Pass
160
35
Pass
161
35
Pass
162
35
Pass
163
35
Pass
164
35
Pass
165
35
Pass
166
35
Pass
167
35
Pass
168
35
Pass
169
35
Pass
170
35
Pass
171
35
Pass
172
35
Pass
173
35
Pass
174
35
Pass
175
35
Pass
176
35
Pass
177
35
Pass
178
35
Pass
179
35
Pass
180
35
Pass
181
35
Pass
182
35
Pass
183
35
Pass
184
35
Pass
185
35
Pass
186
35
Pass
187
35
Pass
188
35
Pass
189
35
Pass
190
35
Pass
191
35
Pass
192
35
Pass
193
35
Pass
194
35
Pass
195
35
Pass
196
35
Pass
197
35
Pass
198
35
Pass
Test
Test load
(lbf)
Test
Status
199
35
Pass
200
35
Pass
201
35
Pass
202
35
Pass
203
35
Pass
204
35
Pass
205
35
Pass
206
35
Pass
207
35
Pass
208
35
Pass
209
35
Pass
210
35
Pass
211
35
Pass
212
35
Pass
213
35
Pass
214
35
Pass
215
35
Pass
216
35
Pass
217
35
Pass
218
35
Pass
219
35
Pass
220
35
Pass
221
35
Pass
222
35
Pass
223
35
Pass
224
35
Pass
225
35
Pass
226
35
Pass
227
35
Pass
228
35
Pass
229
35
Pass
230
35
Pass
231
35
Pass
232
35
Pass
233
35
Pass
234
35
Pass
235
35
Pass
236
35
Pass
237
35
Pass
238
35
Pass
239
35
Pass
240
35
Pass
241
35
Pass
242
35
Pass
243
35
Pass
8730 SW 25STREET • MIAMI • FL • 33165 • PHONE: 305.283.3512 *FAX: 305.226.0438
N
h�
t�cti'
5r
+
+ + + + +
+
+
+
+ + +
+ + + +
+ +
+ +
+
+
+ + +
+ + +
+ +
+ +
+ + + + +
+ + h +
+
+ + + +
+
+ + + + + + +
+ + + + + + +
I
86
LEGEND
+ FIELD TEST
— PERIMETER TEST
O CORNER TEST
A R L A B, I N C.
jC-
VEhXaNM AM�
CrWrMCkTE OF Al,"MOR'LATION 6W
M &W. 29 or. W"% n =0 TM 3C6 2&V= FAM 3W MOM
APPR❑X, ROOF TEST L❑CATI❑NS AND DIMENSI❑NS