RF-05-19-1007 TILE UPLIFTCIVIL Reileh Engineering Corp. (Consulting Engineer) 2370 Southwest 123"' Avenue RMiami, Florida 33175-1174 Tel: 305-823-8008/305-397-6414 ENGINEER Fax: 305-823-3300 / 305-884-8834 May 10, 2019 Erhan Kostepen 270 Grand Concourse [ /� Miami Shores, Florida Project: ROOF Ti LE UPLIFT TEST REPORT Residential Home 270 Grand Concourse Miami Shores, Florida Information provided by client: Permit Number: Not Provided Date Completion: May 7, 2019 Roofina Contractor: EA Emanuel LLC Project Number: 19-0831 (Testing Laboratory Certificate # 16-0602.01) Dear Sirs; In accordance with your request and authorization, a representative of Reileh Engineering Corporation completed the Roof Tile Uplift Test at the above referenced project. This testing was performed in general accordance with Roofing Application Standard TAS No.106 -- Standard procedure for field verification of tile bonding of mortar or adhesive set the system and mechanically attached, rigid, discontinuous roof•systems. The total of the tested roof surface area was less than 10000 square feet, and the mean height of the roof is less than 40 feet above ground surface. The type of tile used for this project was reported to be concrete/clay Roof Tile. This tile was reported to have been foamed in place. At the time of our inspection, the entire area of the roof was examined for loose tiles. Not less than one (1) the in ten (10) of all components in the field area and one (1) the in five (5) of all tiles in the perimeter and comer areas were physically examined. A minimum of one (1) test per every two (2) squares in the field, one (1) test per square in the perimeter area, ridge caps and one (1) test, in each corner were conducted. ` Based on our test results, we conclude that the installation of the roof tile at the above referenced project meets the test requirement outlined in the above -mentioned protocol. Attached please find a copy of our test report for your review. Reileh Engineering Corporation appreciates the opportunity of assisting you in this project. If you have any questions or if we may be of further assistance, please do not hesitate to contact the undersigned. Respectfully submitted; Reileh Engineering Corporation i1 allamad Sonny Salleh, P.E.49014 Project Manager TILE UPLIFT TEST Residential Home 270 Grand Concourse Miami Shores, Florida Submittals: Cover Page Page 2 thru 6 of 6 Drawing 19-0831 Rcilch Engineering Corporation -- Project Number - 19.0831 — Page 2 of 6 Report of TILE UPLIFT TEST for Residential Home 270 Grand Concourse Miami Shores, Florida Project Number: 19-0831 Test Number Test Load lb Test Status 1 35 Pass 2 35 Pass 3 35 Pass 4 35 Pass 5 35 Pass 6 35 Pass 7 35 Pass 8 35 Pass 9 35 Pass 10 35 Pass 11 35 Pass 12 35 Pass 13 35 Pass 14 35 Pass 15 35 Pass 16 35 Pass 17 35 Pass 18 35 Pass 19 35 Pass 20 35 Pass 21 35 Pass 22 35 Pass 23 35 Pass 24 35 Pass Reileh Engineering Corporation — Project Number - 19-0831 — Page 3 of 6 Test -Number Test Load b Test Status 25 35 Pass 26 35 Pass 27 35 Pass 28 35 Pass 29 35 Pass 30 35 Pass 31 35 Pass 32 35 Pass 33 35 Pass 34 35 Pass 35 35 Pass 36 35 Pass 37 35 Pass 38 35 Pass 39 35 Pass 40 35 Pass 41 35 Pass 42 35 Pass 43 35 Pass 44 35 Pass 45 35 Pass 46 35 Pass 47 35 Pass 48 35 Pass 49 35 Pass 50 35 Pass 51 35 Pass 52 35 Pass 53 35 Pass 54 35 Pass Reilch Engineering Corporation — Project Number - 19-0831— Page 4 of 6 mnber. ' lisilbid b Test Status 55 35 Pass 56 35 Pass 57 35 Pass 58 35 Pass 59 35 Pass 60 35 Pass 61 35 Pass 62 35 Pass 63 35 Pass 64 35 Pass 65 35 Pass 66 35 Pass 67 35 Pass 68 35 Pass 69 35 Pass 70 35 Pass 71 35 Pass 72 35 Pass 73 35 Pass 74 35 Pass 75 35 Pass 76 35 Pass 77 35 Pass 78 35 Pass 79 35 Pass 80 35 Pass 81 35 Pass 82 35 Pass 83 35 Pass 84 35 Pass Raileh Engineering Corporation -- Project Number - 19.0831— Page 5 of 6 T,esi Number Teat Load b Teat Status 85 35 Pass 86 35 Pass 87 35 Pass 88 35 Pass 89 35 Pass 90 35 Pass 91 35 Pass 92 35 Pass 93 35 Pass 94 35 Pass 95 35 Pass 96 35 Pass 97 35 Pass 98 35 Pass 99 35 Pass 100 35 Pass 101 35 Pass 102 35 Pass 103 35 Pass Test 1-18 Corner, 19-29 Ridge Caps, 30-51 Perimeter, 52-103 Field Relish Engineering Corporation -- Project Number - 19-0931 — Page 6 of 6 C I V I L Reileh Engineering Corp. (Consulting Engineer) 2370 Southwest 123"' Avenue Ral Miami, Florida 33175-1174 Tel: 305-823-8008/305-397-6414 ENGINEER Fax: 305-823-3300 / 305-884-8834 May 10, 2019 Erhan Kostepen 270 Grand Concourse Miami Shores, Florida Project: ROOFTILE PLiFT TEST REPORT Residential Home 270 Grand Concourse Miami Shores, Florida '2 Information provided by client: Permit Number: Not Provided Date Completion: May 7, 2019 Roofing Contractor: EA Emanuel LLC Project Number: 19-0831 (Testing Laboratory Certificate # 16-0602.01) Dear Sirs; In accordance with your request and authorization, a representative of Reileh Engineering Corporation completed the Roof Till Uplift Test at the above referenced project. This testing was performed in general accordance with Roofing Application Standard TAS No.106 -- Standard procedure for field verification of the bonding; of mortar or adhesive set tile system and mechanically attached, rigid, discontinuous rogf.systems. The total of the tested roof surfacI Ie area was less than 10000 square feet, and the mean height of the roof is less than 40 feet above grqurn•i surface. The type of tile used for this project was reported to be concrete/clay Roof Tile. This tile was reported to have been foamed in place. I At the time of our inspection, the 6wire area of the roof was examined for loose tiles. Not less than one (1) the in ten (10) of all comp;nents in the field area and one (1) the in five (5) of all tiles in the perimeter and coiner areas were physically examined. A minimum of one (1) test per every two (2) squares in the field, one (1) test per square in the perimeter area, ridge caps and one (1) test in each corner were conducted. Based on our test results, we co �HI de that the in tallation of the roof tile at the above referenced project meets the test requiremen tuned in the alove-mentioned protocol. Attached please find a copy of our test report for your,,,iew. i � I '� i Reileh Engineering Corporation appreciates the opportunity of assisting you in this project. If you haw any questions or if we may be of further assistance, please do not hesitate to contact the undersigned. Respectfully submitted; Reileh Engineering Corporation Mohatnad Sonny Salleh, P.E.49014 Project Manager TILE j U41 I T Rosidenual Home 270 Orand concourse Miami Sham, Plorida Submittals: Cover Page Page 2 thru 6 of 6 Drawing 19-0831 Reileh Engineering Corporation » Project Number-19.0831— Page 2 of Report of TILE UPLIFT TEST for Residential Home 270 Grand Concourse Miami Shores, Florida Project Number: 19-0831 Test Number Test Load b Test Status 1 35 Pass 2 35 Pass 3 35 Pass 4 35 Pass 5 35 Pass 6 35 Pass 7 35 Pass 8 35 Pass 9 35 Pass 10 35 Pass 11 35 Pass 12 35 Pass 13 35 Pass 14 35 Pass 15 35 Pass 16 35 Pass 17 35 Pass 18 35 Pass 19 35 Pass 20 35 Pass 21 35 Pass 22 35 Pass 23 35 Pass 24 35 Pass Roileh Engineering Corporation -- Project Number - 19-0831 — Page 3 of 6 Test Number Test Load b Test Status 25 35 Pass 26 35 Pass 27 35 Pass 28 35 Pass 29 35 Pass 30 35 Pass 31 35 Pass 32 35 Pass 33 35 Pass 34 35 Pass 35 35 Pass 36 35 Pass 37 35 Pass 38 35 Pass 39 35 Pass 40 35 Pass 41 35 Pass 42 35 Pass 43 35 Pass 44 35 Pass 45 35 Pass 46 35 Pass 47 35 Pass 48 35 Pass 49 35 Pass 50 35 Pass 51 35 Pass 52 35 Pass 53 35 Pass ! 54 35 Pass Reileh Engineering Corporation -- Project Number - 19-0831 — Page 4 or 1W.Nimber Test Losd b Test Status 55 35 Pass 56 35 Pass 57 35 Pass 58 35 Pass 59 35 Pass 60 35 Pass 61 35 Pass 62 35 Pass 63 35 Pass 64 35 Pass 65 35 Pass 66 35 Pass 67 35 Pass 68 35 Pass 69 35 Pass 70 35 Pass 71 35 Pass 72 35 Pass 73 35 Pass 74 35 Pass 75 35 Pass 76 35 Pass 77 35 Pass 78 35 Pass 79 35 Pass 80 35 Pass 81 35 Pass 82 35 Pass 83 35 Pass 84 35 Pass Rcilch Engineering Corporation -- Project Number • 19.0831 — Page s of 6 Test Number Test Load b Test Status 85 35 Pass - 86 35 Pass 87 35 Pass 88 35 Pass 89 35 Pass 90 35 Pass 91 35 Pass 92 35 Pass 93 35 Pass 94 35 Pass 95 35 Pass 96 35 Pass 97 35 Pass 98 35 Pass 99 35 Pass 100 35 Pass 101 35 Pass 102 35 Pass 103 35 Pass Test 1.18 Comer, 19-29 Ridge Caps, 30.51 Perimeter, 52-103 Field Reileh Engineering Corporation -- Project Number - 19.0831— Page 6 of 6 co 2 ¥¥ � � % 2/ . / � IN � � ` ` ` 2 S � � � . 22 IS2 � . . \ �� � u IS2 %��u�