SGN-19-402 (2)I PROJECT: MONUMENT SIGN CLIENT: USA SIGNS n eased on INPUT DATA Exposure category (B, C or D) Importance factor, 1.0 only, (Table 1.5-2) Basic wind speed (ASCE 7 26.5.1) Topographic factor (26.8 8 Table 26.8-1) Height of top Vertical dimension (for wall, s = h) Horizontal dimension Dimension of return corner DESIGN SUMMARY Max horizontal wind pressure Max total horizontal force at centroid of base Max bending moment at centroid of base Max torsion at centroid of base ANALYSIS Velocity oressur PAGE: 1OF1 DESIGN BY: AG Iw 1.00 V = 175 mph, (281.63 kph) I J KA = 1 Flat F` o a y won h = 26 R, (7.92 m) ; 5.0 sw^ I L s = 16 R, (4.88 m) B = 8 ft, (2.44 m) i4 L, = 2 ft, (0.61 m) M P= F = M= T 92 pst,, (4425 NIM2) 11.83 kips, (53 kN) 212.94 ft-kips, (289 kN-m) 18.93 ft-kips, (26 kN-m) qh = 0.00256 Kh K:t Kd Ke Vz = 63.17 psf where: qh = velocity pressure at mean roof height, h. (Eq. 26.10-1 page 268), Kh - velocity pressure exposure coefficient evaluated at height, h, (Tab. 26AG-1, pe 268) Kd = wind directionality factor. (Tab. 26.6-1, page 266) h = height of top Wind Force Case A: resultant force though the geometric center (Sec. 29.3.1) p=ghGC1= 92 psi F = p A, = 11.83 kips M = F (h - 0.5s) for sign, F (0.55h) for wall 212.94 ft-kips T = = 0.00 ft-kips where: G = gust effect factor. (Sec. 26.9) Cf = net force coefficient. (Fig. 29.3-1, page 323) As=Bs Wind Force Case B: resultant force at 0.2 B offset of the geometric center (Sec. 29.3.1) p = Case A = 92 psf F = Case A 11.83 kips M = Case A 212.94 ft-kips T = 0.2 F B = 18.93 ft-kips Wind Force Case C: resultant force different at each region (Sec. 29.4.1) - GC s' �t K. = 1.00 , (Tab. 26.9-1 page 268) 0.95 0.85 26.00 ft 0.85 1.72 128.0 ft2 p_ gh 1 c.once s s s s F=Epk 1 1 1 1 _ M = E [ F (h - 0.5s) for sign, F (0.55h) for wall j T = E T, IIIIIII h, Distance C1 PI A a Fi Mi TI (ft) (Fig.29.3.1) (psf) (ft) (kips) (ft-kips) (ft-kips) 8.0 2.250 121 128 15.47 278.37 0.00 8.0 1.500 81 0 0.00 0.00 0.00 E 15.47 278.37 0.00 STRUCTURAL r�Y VICW APPROVED �. % Q: * : No. 52742 ,o STATE OF c== Case C may not be'e9r( mo, Aztrdtq��f'-ig.-6�20\\� %,.11ONitl. ; -;?2j l PROJECT: MONUMENT SIGN. LOWER POST CLIENT: USA SIGNS JOB NO.: DATE : 12) Sign Design Based on INPUT DATA 6 DESIGN SUMMARY COLUMN SECTION (Tube, Pipe, or WF) HSS14X0.375 Pipe COLUMN YIELD STRESS Fy = 42 ksi, (290 MPa) DIMENSIONS L = 8 ft, (2.4 m) HS = 16 ft, (4.9 m) H C = 10 it, (3.0 m) SIGN GRAVITY LOAD ( Ibs / ft2) D = 0.5 psf, ( 24 N/m2) SIGN LATERAL LOAD ( Ibs / ft2) W = 55 psf, ( 2634 N/m2), ASD COLUMN LATERAL LOAD ( plf) F= 55 pff, (802 N/m), ASD DIAMETER OF POLE FOOTING b = 5 ft, (1.5 m) ALLOW SOIL PRESSURE Qa = 2 ksf, ( 96 kN/m2) LATERAL SOIL CAPACITY PP = 0.5 ksf /ft, ( 78 kN/m3) RESTRAINED @ GRADE ?(1=yes,0=no) 0 No Use 5 It dia x 6.43 It deep footing unrestrained @ ground level THE DESIGN IS ADEQUATE. PAGE: 1OF1 DESIGN BY: AG REVIEW BY: AR L r W AF s ANALYSIS CHECK COMBINED COMPRESSION AND BENDING CAPACITY OF COLUMN (AISC 360 H1) P`+8 +Mrvfor P'z0.2 Pc 9(�Lr, Mcx Mcy Pc = 1.23 < 4/3 [Satisfactory] P' 4m, +Mry for P' <0.2 2PcMcx Mcy Pc Where P, = 0.26 kips M,,, = 129.47 ft-kips, at bottom of column My = 38.841 ft-kips, 30% M,,, used Pc = Pn / dlc = 225 / 1.67 = 134.72 kips, (AISC 360 Chapter E) > P, (Satisfactory] Mc = Mn / ab = 227.85 / 1.67 = 136.44 ft-kips, (AISC 360 Chapter F) > 3/4 M,x [Satisfactory] Mcy = Mn / 12b = 227.85 / 1.67 - 136.44 ft-kips, (AISC 360 Chapter F) > 314 Mry [Satisfactory] DESIGN POLE FOOTING (IBC/CBC 1807.3) By trials, use pole depth, d = 6,435 ft Lateral bearing @ bottom, S3 = 2 Pp Mind, 12') = 6.43 Lateral bearing@ d/3,S, =2Pp Min(d13, 12')= 2.14 Require Depth is given by I 2 C1 + 1+ 4. A h for nonconstrained d= _ 4.25Ph for constrained bS3 Where P= Vn x = 7.59 kips A= 2.34P/(bS1)= 1.65 h = Mmax / V max = 17.06 ft CHECK VERTICAL SOIL BEARING CAPACITY (ACI 318 13.3.1.1) ksf ksf b14 — R,q,y'%, `���:•�,y� E N S E' •• ��� ��• No, 52742 S7 T OF Ptop -10 oQ\�� 6.435 ft [Satisfactory] 9soij = (D HS L + col wt) / (ir b214) = 0.01 ksf, (net weight of pole footing included.) < Qa [Satisfactory] 9 PROJECT: MONUMENT SIGN. TOP POST (ONLY FOR PIPE CALCULATIONS) CLIENT : USA SIGNS on DATA & DESIGN SUMMARY IN SECTION (Tube, Pipe, or WF) IN YIELD STRESS GRAVITY LOAD ( Ibs / fe ) LATERAL LOAD ( Ibs / ft2 ) MN LATERAL LOAD (pif ) =TER OF POLE FOOTING N SOIL PRESSURE 3AL SOIL CAPACITY RAINED @ GRADE ?(1=yes,0=no) PAGE: 1 OF 1 DESIGN BY: AG REVIEW BY: AR L HSS6X0.250 Pipe Fy - 42 ksi, (290 MPa) L - 8 ft (2.4 m) HS - 8 R, (2.4 m) W HC - 0 ft, (0.0 m) _ D = 0.5 psf, ( 24 N/m 2) W = 55 psf, ( 2634 Wm 2), ASD F= 0 pH, (0 NI m), ASD b = 3 ft, (0.9 m) F U Qe = 2 ksf, ( 96 kWm2) _ PP - 0.266 ksf/ft, ( 42 kN/m3) 0 No Use 3 ft dia x 5.31 ft deep footing unrestrained @ ground level THE DESIGN IS ADEQUATE. YSIS K COMBINED COMPRESSION AND BENDING CAPACITY OF COLUMN (AISC 360 1­11) Pr+8 Prz+M ry for P►>_0.2 8 Pc 9 M cx M cy Pc = 1.13 < 4/3 [Satisfactory] Pr + ` ,+M for Pr <0.2 2P� MCx MCy PC Where Pr = 0.05 kips Mrx - 14.08 ft-kips, at bottom of column Mry - 4.224 ft4dps, 301/o Mx used Pc = Pn / nc = 103 / 1.67 - 61.67 kips, (AISC 360 Chapter E) > Pr [Satisfactory] Mcx = Mn / Slb = 27.125 / 1.67 - 16.243 ft-kips, (AISC 360 Chapter F) > 3/4 Mrx [Satisfactory] Mcy - Mn / !lb - 27.125 / 1.67 - 16.243 ft-kips, (AISC 360 Chapter F) > 314 Mry [Satisfactory] DESIGN POLE FOOTING (IBC/CBC 1807.3) By trials, use pole depth, d = 5.308 ft Lateral bearing @ bottom, S3 -2 Pp Min(d, 12') = 2.82 ksf Lateral bearing @ d / 3, S I = 2 P p Min d / 3, 12') = 0.94 ksf Require Depth is given by l 2 1 1+ 1+4.3 hl for nonconstrained d = = 5.308 ft 4.25Ph for constrained bS3 Where P- V"" = 3.52 kips A= 2.34PI(bS1)- 2.91 h = Mmax / V max = 4.00 ft 120%j `��ttu I l l l r rrttt��� •�``��OR� RA .•\E'EN �'� • No. 52742 STATE OF [Satisfactory] VERTICAL SOIL BEARING CAPACITY (ACI 318 13.3.1.1) gsou - (D Hs L + col wt) /(z b2/4) - 0.01 ksf, (net weight of pole footing included.) < Qe [Satisfactory] LL AN SCOPE OF WORK: REMOVE EXISTING & INSTALL NEW D/S ILLUMINATED DETACHED SIGN -u0As REGULAR IIIIII'� Cl II i I� PLUS i� . o i PREMIUM H i i+ IIIi�I i_I. [I ❑ -uGAi _ REGULAR II_I 0.uu PREMIUM 1.0ii 1 I 9111111111111111111 v URBIETA OIL (U GAS) CONTRACT 402 12186 7230 N'VV 46th St.. Miami, FL 33166 8700 BISCAYNE BLVD TYPE OF SIGN: DIS ILLUMINATED DETACHED SIGN SIGNAT LITE LIC. # ER13015158 -# 15E000431 MIAMI SHORES, FL 33138 DATE: 12.03.2018 c u DESIGN FABRICATION ON L LOCAL ' ACCORDING TO ALL LOCAL I STATES N-ONAL CODE REOU—MENTS. — —,i A NEC 1.11 USA 7230 NW 461h St., Miami. FL 33166 SIGNS., PH. 305A70.2333 t. 305.470.2320 A Sy o44 NK_ �s++Estcu vwrn•1 cwsaNi �.-„c,.«,...._ •...,••..• w,.•..••. NORTH & SOUTH ELEVATION EI OUTDOOR SIGNS SIGN PLAN #02 12188 SIDE FRONT OVER 2112"x2112"x1!4" STEEL ANGLE FRAMING (PLACE ONE ANGLE IN THE MIDDLE OF THE CANTILEVER JOINING BOTH ANGLES). 1/4" WELDED CABINET TO POLE (TOP & MIDDLE) PAN FACE AL. 3/16" W/VINYL GRAPHICS 100W/60HZ LED POWER SUPPLY 06" x 1/4" STEEL TOP POLE LED MODULES - 12V SECONDARY 1 1/2" x 1 1/2" x 1/8" STEEL ANGLE @ MAX 22" FLAT FACE AL. 3/16" WI VINYL GRAPHICS TOP CABINET FLAT FACE AL. 3/16" W/ VINYL GRAPHICS DAKTRONICS FL-3000-24-R-D1 1/2'. STEEL PLATE _ ` ' LED PETROLEUM PRICE DISPLAY WELDED TO BOTH PIPES (SPECS: ATTACHED) 1/4" WELDED CABINET FLAT FACE AL. 3/16" W/ VINYL GRAPHICS TO POLE (MIDDLE & BOTTOM) q 2'-0"MIN. INSERTION LOWER CABINET 1 1/2" ALUMINUM T-BARS #10 x 1" SELF SCREW TO SECURE lo , DAKTRONICS: FL-3000-24-R-D1 LED PETROLEUM PRICE DISPLAY (SPECS: ATTACHED) 1/4" WELDED CABINET TO POLE ue, i�,, , : _.. = _ ---- 1 1/2" x 1 1/2" x 1/8" ALUMINUM RETAINERS TO SECURE FACES 014" x 3/8" STEEL LOWER POLE GROUND - Minimum soil bearing capacity: 2000 psf - Minimum strength of concrete: 3000 psi 014" x 3/8" STEEL LOWER POLE (PAINT COLOR: RED) DISCONNECT SWITCH INSIDE 4"x2"WEATHERPROOF ELECTRICAL BOX GROUND TO PRIMARY LINE (BY OTHERS) New footing DESIGN CALCULATION: Checking vertical angles: frontal wind: Wind load=8'x8'x55 psf = 3 520 lb Bending moment: B.= 3 520 lb / 2 x 96"/8 = 21 120 in lb Sx needed = 21 120 in lb / 18 000 In/in2 Sx needed = 1.17 in3 Sx for angle 1'/zx1'/2x'/4" = 0.13 in3 « 1.17 in3 NO Checking vertical angles working together: Bending moment: Wind load=3.42'x5.83'x43 psf = 857 lb Bm= 3 520 lb / 2 x 96"/8 = 21 120 in lb Sx needed = 21 120 in lb / 12 000 In/in2 Sx needed = 1.76 in3 Sx for angle 1'/2x1'/2x'/4" = 0.13 in3 « 1.76 in3 Area for angle 1'/2x1'/Zx'/<" = 0.68 in2 Sx for combined angles = 2x0.13in3 + 0.68 (in2)x23" Sx equiv. = 15.9 in3 > 1.76 in3 OK Maximum separation distance between union profiles: L= 0.44"x50 = 22" Checking vertical angles: lateral wind: Wind load=8'x2'x55 psf = 880 lb Bending moment: Bm= 880 lb / 2 x 96"/8 = 5 280 in lb Sx needed = 5 280 in lb ! 18 000 In/in2 Sx needed = 0.293 in3 Sx for angle 2'/zx2'/2x'/4" = 0.39 in3 > 0.293 in3 OK Checking Al. face. Max. height : Wind load=l'x3.5'x55 psf = 193 lb Bending moment: Bm= 193 lb x 42"/8 = 1 011 in lb Sx needed = 1 010 in -lb / 18 000 In/in2 Sx needed = 0.056 in3 Sx for Al sheet 3/16" = 0.069 in3 > 0.056 in3 OK Checking horizontal structure: Bending moment: Wind load=4'x(3.3'/2 + 2.6'/2)'x55 psf = 649 lb B.= 649 lb x 472 = 1 298 ft-lb = 15 576 in -lb Sx needed = 15 576 in -lb / 12 000 In/in2 Sx needed = 1.298 in3 Sx for angle 2x2xl/8" = 0.13 in3 < 1.3 in3 Area for angle 1'/zx1'/zx'/4" = 0.48 in2 Sx for combined angles = 2x0.13in3 + 0.48 in2x11" Sx equiv. = 5.54 in3 > 1.3 in3 OK Maximum separation distance between union profiles: L= 0.62"x50 = 31" Use: 24" (place in the middle of the cantilever) ELECTRICAL INFORMATION ALL ELECTRICAL WIRING AND INSTALLATION SHALL COMPLY WITH CURRENT FBC 2017 & NEC 2014 ALL COMPONENTS APPROVED BY NRTL (SEE DATA SHEET ATTACHED) SIGN GROUNDED & BONDING ACCORDING TO NEC 250.4 GENERAL GROUNDING & BONDING (02) U.L. POWER SUPPLY 100 W112V 120V W #12 THWN WIRE CONNECTION TO POWER GFCI PROTECTION REQUIRED FOR SECONDARY AS PER NEC 600.23 (B) ALL METAL PAINTED - NON CORROSIVE FINISH (01) 20 AMP DISCONNECT SWITCH - NEC 600.5 (A)(1)(2) (01) COMBINATION OF PHOTOCELL AND TIMER OR ASTRONOMICAL TIMER FBC 2017 (BY OTHERS) (01) 20 AMPS CIRCUIT WIBREAKER #6 - EXISTING (CABINET) FOR WIND LOAD SEE PAG 1 FOR LOWER POSTAND FOOTING SEE PAG 2 FOR TOP POST SEE PAG 3 Engineer: ALEJANDRO RAMIREZ PE 10464 SW 114 ch Terrace MIAMI. FL.33176 Ph: 786 768 6307 LICENSE No:52742 X120v - 277 v Scope of work: GENERAL STRUCTURAL NOTES: 1. Design is based on 175 mph 3 seconds gust design wind speed per Installation of new FBC 2017 6th Edition. Exposure C. illuminated sign in new footing. gn�in ed monument 2 Reference Specifications, Codes and Standcrs: FBC 2017 6th Edition si / ASCE 318-1 1 / AISC 360-10/16 / ACI - 318 - 11 / NEC 2014.