RF-11-20-2519 UPLIFTA February 5, 2021 To: Miami Shores Village Building Department 10050 NE 2nd Avenue Miami Shores, FL 33138 Engineering & Testing Co. 7450 Griffin Road, Suite 140, Davie, FL 33314 Phone: (954)581-7115, Fax: (954)581-2415 www.cebb.net Roof Tile Uplift Test Report Test Date: February 5, 2021 Permit #: RF-11-20-2519 Address: Quijada Residence 103 NW 97 St, Miami Shores, FL Contractor: Paul Ban e Roofing Roof Pitch: 3:12 Attachment method: ICP Pol Pro AH 160 Tile Type: Eagle Capistrano Device Used: "IMADA DPS 110" force gauge (Serial # 425458) Total Sloped Roof Area: 25.00 squares All Testing is in strict accordance with the Florida Building Code, 2017 Edition, High Velocity Hurricane Zone — Testing Application Standard (TAS) 106. Roof Area: 25.00 squares Total Number of Tests Number of tests Passed % Passed Field Area (1): 10.00 squares 13 T34-T46 13 100% Perimeter Area (2): 15.00 squares 15 (T19-T33) 15 100% No. of Corner Areas (3): 11 11 T1-T11 11 100% Ridge/Hip Areas: 105 pcs 7 T12-Tl 7 100% Based upon the field tests, I certify that 100% of the static up -lift tests "PASSED" the testing criteria of 35.0 lbf load, and meets the attachment resistance for adhesive Set Systems, as specified in the NOA. Should you have any questions regarding the above, or if require additional information, please do not hesitate to contact this office. Sincerely, CeBB Engineering & Testing Co. (NOA 18-11%Th'I O2/05/2021 Eduard I3 i '.E. Fla. Reg. o: 997 For The Firm Cc: Paul Bange Roofing Enc. Location Sketch Calibration Certificate �(74 003 MM101 Engineering & Testing Co. 7450 Griffin Road, Suite 140, Davie, FL 33314 Phone: (954)581-7115, Fax: (954)581-2415 www.cebb.net HANDLIFT RESULTS: Passed the protocol criteria of less than 3% loose. We performed the up -lift test. T - Tested tiles and Passed; Total Area: 25.00 squares No. of tested Tiles: F - Tested tiles and Failed; - Field Area (1): 10.00 squares - Field Area: 13 M - Missing Tiles; - Perimeter Area (2): 15.00 squares - Perimeter Area: 15 B - Broken Tiles; - No. of Corner area (3): 11 - Corner areas: 11 -Ridge/hip areas: 105 pcs - Ridge/Hip areas: 7 I w I � � 1 �•o'- S"od o - �d i� L13qb Ss 3 �N 3� 3E V 3a Legend: 34-46 Field tests 19-33 Perimeter tests 1-11 Corner tests 7-18 Ridge Tests TAS 106 TESTS LOCATION SKETCH Permit # RF-11-20-2519 Quijada Residence 103 NW 97 St, Miami Shores, FL Engineering & Testing Co. 7450 Griffin Road, Suite 140, Davie, FL 33314 Phone: (954)581-7115, Fax: (954)581-2415 www.cebb.net TEST RESULTS (P = PASSED, F = FAILED) Test Location Uplift Pull Test or Test Uplift Test ' Uplift Location Pull Test Location Pull Test (PorF)i (PorF) Test Uplift Location Pull Test orF) Test Location Uplift Pull Test PorF 1 P 26 P T-� 2 P 27 P _ 3 P 28 P 4 P 29 P 5 P 30 P 6 P 31 P 7 P 32 P 8 P 33 P 9 P 34 P 10 P 35 P 11 P 36 P 12 P 37 P 13 P 38 P 14 P 39 P 15 P 40 P 16 P 41 P 17 P 42 P 18 P 43 P 19 P 44 P 20 P 45 P 21 P 46 P 22 P 23 P 24 P 25 P i Engineering & Testing Co. 7450 Griffin Road, Suite 140, Davie, FL 33314 Phone: (954)581-7115, Fax: (954)581-2415 www.cebb.net ®�r0 PORO! A TOROU! MMAAURl MINT � F 190 flnnl RPCi1flTf RF_IS 1.9rJIII?f: iTl1�l1 ACf]RPf]ITrr1 CALIBRATION CERTIFICATE Issue Date: May 15. 2020 Calibration Date: May 15, 2020 cerd cate 0 051520-425458E Temperature: 73 "r Humidity: 40 %Itll Description: Digital Force GaLIge Model Number: DST-110A Serial Number: 425458 Capacity: 110 Ibl' Accuracy: t0.2 %F.S.t I LSD Resolution: 0.1 Ibf Procedure: EXA01D QMr-1 1-3-I M Description S/N Cenifure # Due Dale 7emp/RH Ni fR 16311997 2031507 8P- -1021 I fmger .2 LL11 2571867A 3/152021 W-set 5FAX 2562225J .3/23n022 W..da 23H5 2807999C Amended 12/1/2020 Weight .23GR 2716545 322/2028 This document certifies that the above instrument has been calibrated and tested in accordance with lmada calibration procethtres conducted under the conditions noted with standards, which establish an unbroken link traceable to the International System of Units (S1) via the relevant primary national or international standards, including National Institute of Standards and Technology (MIST). This document must not be reproduced without written authorization from 1MADA INC. TEST RESULTS AV rrll:Nn AC I.r'" 'IESTPOINT ACHIAI. A AC311A1. 1) l'mis- -110.0 tlbf) -110.0 Qbf) -110.0 Ibt) .2) 0.0 0.0 0.0 3) Comp. I Mo 110.0 110.0 i Technical Manager: Noboru [lmaguki Inuuln, Inc. 3100 Dundee Rd., Suite 707 N- ld—uh, Illinois 611062 hwu NmnW ; la http://IVWW.imada.com E-1liail: ini.dana imada.cum 1-S00.373-9989 h—T)--01Rn19 Page 1 of I