42581 ROOFV '5 1 IR T Bob Tedder, RRO, CSI, RCI Independent Roof Testing & Consulting of S. Florida, Inc. Latite Roofing & Sheet Metal Co., Inc. 999 Northwest 53rd Court Fort Lauderdale, Florida 33309 President, Senior Consultant April 14,1998 RE: -142(1Northeast-1U2Stt&t-- Miami Shores, Florida. Permit #42581 IRT #8296 Pursuant to your request, INDEPENDENT ROOF TESTING of South Florida (IRT), performed uplift tests on the tile roofing at the above address. The the type is Pioneer Hacienda. The roof area tested is approximately 3451 square feet in area and was tested at forty -five (45) locations. The tiles had been installed using the "Foam Application" method. The uplift tests consisted of placing a load test device manufactured by CHATILLON (Model DFIS), over the tile with an adjustable connector placed under the front lip of the tile, and gradually increasing the pressure. The gauge readings are indicated in pounds. Pressure was exerted on the tile until a reading of thirty five (35) pounds was obtained. Visible separation was noted at zero (0) test locations at this reading. The rood passed (n ,accordance with Dade County Protocol PA -I06. HU's responsibility in this project was specifically uplift testing to a specific point. No other conclusions or observations are expressed or implied. The tests were conducted, and the results have been reported in accordance with Dade County Protocol, PA -106. IRT appreciates this opportunity to be of service. If you have any questions, or need additional information, please do not hesitate to call. Submitted, �� .' _ — b Tedder, RRO, CSI, RCI President, Senior Consultant 4107 Richard S. Yates, PE Project Engineer 3944 NE Fifth Avenue Oakland Park, Florida 33334 Phone: (954) 630 -0201 Fax: (954) 630 -0506 51' 1420 Northeast 102 Street Miami Shores, Florida IRT #8296 72' PA 106 Test Locations Tested at 45 Locations All Passed SYNERGY Certificate of Calibration - Labs, Inc Manufacturer: CHATILLON Model Number: DFIS -100 Sepal Number: 25187 Customer SN: 002 D.- scription: FORCE GAGE Customer: INDEPENDENT ROOF TESTING C rtificate Number: 59373 This certifies that the above equipment was calibrated in compliance with the requirements of ANSI /NCSL 2540 -1, MIL -STO 45662A, ISO 9002 4.10/4.11, ISO Guide 25, ISO 10012 using applicable procedures. A: planned intervals, Synergy Labs, Inc measurement standards are calibrated by comparison to or measurement against national standards, natural physical constants, consensus standards, or by ratio type measurements using self- callbrating techniques. National standards are administered by NIST (National Institute of Standards and Technology) or other recognized national standards laboratories. S.tpporting documentation relative to traceability Is on file and is available for examination upon request. L mits: NONE Remarks: UNIT RECEIVED IN TOLERANCE - NO ADJUSTMENTS REQUIRED Calibration Date: 3/13/98 Calibration Due: 6/13/98 Reference Standards Used: Model Serial Trace Manufacturer Number Number Number Cal Due Date ,AMETEK -M&G WG-23 18830 48037 4128199 Synergy Labs, Inc 6211 NW 64 ST #3 Miami, FL 33166 Ph (305)-477 -5414 William Everest Quality Assurance W'11 PERMIT APPLICATION FOR MIAMI SHORES VILLAGE Date 3 '/y " S Job Address 0 Al / 0 2.Nh �T . Tax Folio Legal Description L�-r5 /31k3��y AV %,fie• Historically Designated: Yes No Owner/Lessee /Tenant / L G / R & l ) 1 r F r Master Permit # S-8/ Owner's Address J <1,2n /IF 102 .yi� 5T Phone Q /� Contracting Co. � T F & d /�cl /�- Address 9 9 9 /t� UZ 'Sr 3 Gy 7-. r1 Zg U /) . Qualifier nl f3 Xt t S E I-1 6JS 0,1 SS# � V7Phone 9,5*- 7 7 z -3 State # Municipal # Competency #�7(° (°0 5/4 7 Ins. Co. Architect/Engineer l A Address Bonding Company N/ Address Mortgagor Address Permit Type (circle one): BUILDING ELECTRICAL PLUMBING MECHANICAL ROOFING PAVING FENCE SIGN WORK DESCRIPTION( f � // FA �f�. , D°E r D r. F 7'. a s Square Ft. %3900 Estimated Cost (value) /y�, 000 WARNING TO OWNER: YOU MUST RECORD A NOTICE OF COMMENCEMENT AND YOUR FAILURE TO DO SO MAY RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY (IF YOU INTEND TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.) Application is hereby made to obtain a permit to do work and installation as indicated above, and on the attached addendum (if applicable). I certify that all work will be performed to meet the standards of all laws regulating construction in this jurisdiction. I understand that separate permits are required for ELECTRICAL, PLUMBING, SIGNS, POOLS, ROOFING and MECHANICAL WORK. OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all applicable laws regulating construction and zoning. Furthermore, I authorize the above -named contractor to do the wor ted. -)d' A ) t� '2�� .,iA -� I ( ( ( s, gnature o o er and/or 'ondo President Date Signature of 4a� Own r- Builder Date Plotary as t Owner and/or Condo President Date Notary as t ontractor or Owner - Builder Date Co fission Expires: My Commission Expires: �� :iliP4l E. ALLBRITTON # CC48902G ' EXP! ES AUG. 16,1999 FEES: PERMIT i I' ! 4'00 RADON C.C.F. ty 66 NOTARY APPROVED: `T�` -N Building Electrical Mechanical Plumbing fir. _ Engineering o�P„v P's 11 MI E. ALLBRITTON GIVI iSSI01l # CC489020 EXPIRES AUG. 16,1999 BOND /?�001 Q 0 TOTAL DUE `' 1 01 i PERMIT NO. STATE OF FLORIDA:_ COUNTY OF DADE: NOTICE OF COMMENCEMENT TAX FOLIO NO. 'Z-71R iC1167 59 1998 HAR 10 10.'41 THE UNDERSIGNED hereby gives notice that improvements will be made to certain real property, and in accordance with Chapter 713, Florida Statutes, the following information is provided in this Notice of Commencement. �1 1. Legal description of property and stredt address: 6T" ��OC�.3, /Li/l3d f i ft/Ol£ 5 6&1 At- 2. Description of improvement: & - /'O o--/ 3.Owner(s) name and address: W ILL ,e a 1) F 1 a i' r -interest in property: O/a Name and address of fee simple titleholder: A 4. Contractor's name and address: _7_- emu F FLOC ®A, �o of - 5. Surety:(Payment bond required by owner from contractor, if any) eo c�RTiFY fho' +his j5 ° �°r ° ° ®v Name and address: ,(//� d ,°!!,„ owice ®n 70 19, 1 .raBain ®I file � Amount of bond $. 6. Lender's name and address: aov- d r d O$ utiai Se (. yyTNE55 ^y h lLFti, n$ " MAINE av 7. Persons within the State of Florida designated by Owner upon whom notices or other documents may eTas provided by Section 713.13(1)(a)7., Florida Statutes, Name and address: 46& 8. In addition to himself, Owner designates the following person(s) to receive a copy of the Lienor's Notice as provided in Sec- tion 713.13(1)(b), Florida Statutes. Name and address: Aze 9. Expiration4date of this Notice of Commencement: (the expiration date is 1 year from the date of recording unless a different date is,%r)w fiedL , signature oTbwner W1 L_L./ 6M /„% t / r LYL �/ Sworn to and subscribed before me this i day of r l� , 19 %d o~�Y �MIMI E. ALLsRITTON z nCOMMISSION # cC489023 Notary Public EXPIRES AUG-16,1999 My Commission Expires: Prepared by: �i /- /1LB%IT�N Address: ?i 91 JA/ ,:f Cam• y/. 3339 i } Project: . Address: City: _ 999 NORTHWEST 53RD COURT FT. LAUDERDALE, FL 33309 (954) 772 -3446 OFFICE (954) 938 -9158 FAX (800) 344 -3510 FL WATTS 3. INC. Ill rAIT11 11 • Derrer residence 1420 NE 102 Street Miami Shores Date: 3/11/98 Tile Roofing Tile Type: Hacienda Size of Roof in square feet: 3450 Manufacturer: Pioneer Ridge Elevation: 17 ft. Product Control No.: 95- 1128.12 Eave Elevation: 11 ft. Attachment Method: Polyfoam Adhesive set Mean Roof Height: 14 ft. Importance factor 1.05 Exposure category C Basic wind speed 110 mph Roof pitch 3/12 Hip or Gable Hip_ Max pressure from PA 127 Table 1 -P max 1: 72.3 PSF, P max 2 &3: 103.7 PSF Aerodynamic Multiplier = X = 0.29 Gravity moment =mg= 6.8 Resisting moments - Field Mr1= (P max 1 x ) - mg ( 72.3 x 0.29 ) - 6.8 = 14.17 Perimeter Mr2 = (103.7 x 0.29 ) - 6.8 = 23.273 Corners Mr3 = (103.7 x 0.29 ) - 6.8 = 23.273 Note: Polyfoam Adhesive set has resistance of 86.61 which exceeds requirements of all three zones. z Appendix "E" UNIFORM ROOFING PERMIT APPLICATION PROrFSS Nn type: wa e V caUflst(on? WA MEAN HEIGHT SLOPED SYSTEM DESCRIPTION Fastener type & spacing: Cap Sheet: Roof ROOF SLOPL D E T A I L 3 �►�•9ts t tt�.Ll�,� � i� F.1F'i� D�•i�t....� ring: kL r Drip edge: ATTACHMENTS REQUIRED 1) Fire Directory Listing Page 2) Dade County Product Control Notice of Acceptance -Cover Sheet a) Specific System Description b) Specific System Limitation c) General Limitations d) Applicable Detail Drawings 3) Municipal Permit Application 4) Other Component Approvals TILE CALCULATIONS (Pmaxl: 3 X X (Aerodynamic Multiplier):_) - M9 = MrI: �`2— PCA: DG - 6 (Pmax2: In -7 X ii. (Aerodynamic Multiplier): -2•j ) - Mg: 6. = Mrl :Z ,3 PCA: °Ur G _ to II (Pmax3 :1 o3 --I x X (Aerodynamic Multiplier): • 2 C� ) - Mg: G • b =M r3:.1133 PCA: Page -2 i Appendix "E" UNIFORM ROOFING PERMIT APPLICATION PROCESS No. Contractor's Name: VOC Job Address: 0� (Low Slope Application) ❑ (Asphalt/Fiberglass Shingles) ❑ New Roof 2-Re - roofing ROOF CATEGORY ❑ (Nail -On Tile) . , J2 (Mortar- Adhesive Set Tile) ❑ ( Metal Roofs \Wood Shingles & Shakes) ❑ (Other) ROOF TYPE ❑ Recovering ❑ Repair ❑ Maintenance Flat Roof Area (W Sloped Roof Area (ft`)�-5 Aln'O Total (ft) �J .Z, g Master Permit No. Exposure category (per ASCE 7 -88): Building Classification category (per ASCE 7 -88 table 1): Ft. �0I Ft. ROOF HEIGHT AND SYSTEM DETAILS (Draw details as needed) ROOF PLAN I ' r - ---- - - - --- ' , r ' ' I ' r - ---- - ------ -- ' I ' , Deck type: P% N ;F-i - - - - - - -- - - -- - - - -- a) ' -- -- -- ------ - -- -- -- -- - - - -- ------- I , , - ---- -- -- ---- -- -- -- - -- , ATTACHMENT �11�.i/ V'-�V IL-L Fastener Type: SPACING b, I I Field: `v L- Perimete D -t +• Ru Comer:�P L, +N L4AV,1, Y B.L eJ LAOS # ----- - ---- ---- -- ; ;21 u I I - - - Gili 49•G- 11:�f3 D•L, ttJ4 61- 0 i , ' '- -- - ------------ -- - -- I 33X3' I ' - -- - - - - - -- - - - - - -- - - -- DETAIL 1 & 2 ; ' - -- - -------------- ---- -- - - -' - -- ---- - - - - -- ---- - - - - -- '----------------------------------- - - - - -' , '-------------------------------------- - - - - -' 123.01-78 OM Page -1 LS (TEVT) — Continued asuring 0.208 in. thick min and weigh - g assemblies provided they do not ex- .ins" will include the following: '*Ultra- ', Rmax "MultiWax" or "Multi -Max FA ", •ien "GlasPly iV ", "Glasply Premier" or systems. as SPM Lap Caulk. ncline: 2 cyanurate, perlite, perlite /urethane /per- socyanurate composite or wood fiber, 1000 Ibs /sq. ncline: 2 "Fesco- Foam ", "Fes- Core ", "UltraGard ", d over polystyrene or any UL Classified 3t mopped. 1000 lb/sq. ncline: 3 Board ", "UltraGard ", "Fes- Core ", "Fes- polystyrene or any UL Classified poly- 000 Ibs /sq. ncline: 1 :rs "Fesco ", "Fesco-Foam ", "Fes- Core ", ;co" over polystyrene or any UL Clessi- or hot mopped. "GlasPly Premier ", "PermaPly R" or in or "DynaPly" or "DynaBase' (modl- ;las FR 30" or "DynaLastic 180" (modi- ncline: 2 gypping asphalt. Aanniglas 1200" slip sheet, loose laid. -d ", "Fesco-Foam ", "Fes- Core ", "Fesco ", r any UL Classified polyisocyanurate in- 100 lbs/sq. ncline: 2 )rs "Fesco ", "Fesco-Foam ", "Fes- Core ", lassified polyisocyanurate Insulation, in ioard, or 3/4 in. "Fesco" over polysty- NasPly Premier ", "PermaPly R" or Type or "DynaPly" or "DynaBase" (modified al-astic 180 ", hot mopped. 1cline: 3 ors "Fesco ", "Fesco- Foam ", ­Fes-Core", lassified polyisocyanurate insulation, in card, or 3/4 in. "Fesco" over polysty- 3mier ", "PermaPly R" or Type G2 "Per - Ply" or "DynaBase" (modified bitumen), aLastic 180 ", hot mopped. icline: 3 +rs "Fesco ", "Fesco-Foam ", "Fes- Core ", Classified polyisocyanurate insulation, optional) with 1/2 in. "Retro-Fit" cover ilasPly Premier', "PermaPly R" or Type or "DynaPly" or "DynaBase" (modified nstie 180" or "DynaBase" (modified bi- icline: 1 rs, "Fesoo ", "Fesco-Foam ", "Fes- Core", Classified polylsocyanurate Insulatlan, RODUCT y -�y ROOF COVERING MATERIALS (TEVT) ROOFING SYSTEMS (TGFU)— Continued .483 mechanically fastened or hot mopped in combination (optional) wig► 1/2 in. "Retro-Fit" cover board, or 3/4 in. "Fesco" over polystyrene. Ply Sheet: Two or more plies Type G1 "GlasPly IV", "GlasPly Presser ", "PermaPly R" or Type G2 "PermaPly No.- 28 ", "GlasBase" or "Ventsulation ", or "DynaPly- or "DynaBase" (modified bitumen), mechanically fastened or hot mopped. Ply Sheet: "DynaKap ", "DynaPly', "DynaGlas ", "DynaLastic 180" ar "DynaBase" (modified bi- tumen), hot mopped. Surfacing: Gravel and hot roofing asphalt. 10. Deck: C- 15/32• Incline: 2 Insulation: (Optional) Any thickness, one or more layers, "Fesco", -Fesco Foam ", "Fes- Core ", "Fiber Glass Roof Insulation ", "UltraGard" or any UL Classified polyisocyanurate insulation, mechanically fastened. or hot mopped in combination (optional) win 1/2 in. "Retro-Fit" cover board, or 3/4 in. "Fesco" over polystyrene. Ply Sheet Three or more plies Type G1 "GlasPly IV ", "GlasPly ftemier ", "PermaPly R" or Type G2 "PermaPly No. 28 ", "GlasBase" or "Ventsulation ", or "DynaPly' or "Dyna Base" •(modi- fied bitumen), mechanically fastened or hot mopped. Ply Sheet: "DynaKap ", "DynaPly", "DynaGlas ", "DynaLastic 180" or "DynaBase" (modified bi- tumen), hot mopped. Surfacing: Gravel and hot roofing asphalt. Class S - Ballasted 1. Deck: C -15/32 Incline: 1 Insulation: (Optional) Any thickness, one or more layers, "Fesco", -Fesco-Foam", "Fes- Core ", "Fiber Glass Roof Insulation ", "UltraGard" or any UL Classified pslyisocyanurate insulation, mechanically fastened or hot mopped in combination (optional) wig 1/2 in. "Retro-Fit" cover board, or 3/4 In. "Fesco" over polystyrene. Base Sheet: One or more plies Type G 1 "GlasPly IV ", "GlasPly Premier ", "PermaPly R" or Type G2 "PermaPly No. 28 ", "GlasBase" or "Ventsulation", or "DynaPly" or "DynaBase" (modi- fied bitumen), mechanically fastened or hot mopped. Ply Sheet: "DynaKap ", "DynaPly ", "DynaGlas ", "DynaLastic 180" or "DynaBase" (modified bi- tumen), hot mopped. Surfacing: Gravel and hot roofing asphalt. 2. Deck: C -15/32 Incline: 2 Insulation: (Optional) Any thickness, one or more layers, "Fesco ", `Fesco-Foam ", "Fes- Core ", "Fiber Glass Roof Insulation ", "UltraGard" or any UL Classified polyisocyanurate insulation, mechanically fastened or hot mopped in combination (optional) with: 1/2 in. "Retro-Fit" cover board, or 3/4 in. "Fesco" over polystyrene. Ply Sheet: Two or more plies Type G 1 "GlasPly IV ", "GlasPly Premier ", "PermaPly R" or Type. G2 "PermaPly No. 28 ", "GlasBase" or "Ventsulation ", or "DynaPly' or "DynaBase" (modified bitumen), mechanically fastened or hot mopped. Ply Sheet: "DynaKap ", "DynaPly "DynaGlas ", "DynaLastic 180" or - DynaBase" (modified bi- tumen), hot mopped. Surfacing: Gravel and hot roofing asphalt. 3. Deck: C -15/32 Incline: 1 -1/2 Insulation: (Optional) Any thickness, one or more layers "Fesco , - Fesco-Foam ", "Fes- Core ", "UltraGard" or any UL Classified po lyisocya nu rate insulation, in combination (optional) with 1/ 2 in. "Retro-Fit" cover board, or 3/4 in. "Fesco" over polystyrene, mechanically fastened or hot mopped. Ply Sheet: One or more plies "GlasPly iV", "GlasPly Premier ", "PermaPly R" or Type G2 "Per- maPly No. 28 ", "GlasBase" or "Ventsulation ", or "DynaPly" or "DynaBase" (modified bitumen), nailed or hot mopped. Membrane: "DynaKap FR "Wasor"DynaGia or "DynaGla R 30", hot mopped. Surfacing: Gravel and hot alt. A - Fully Adhered in the SE6A systems describe insulation is mecha ically attached with fasteners and plates, hot roofing asphalt or co. Unless otherwise I icated, the specified membrane Is adhered to the insulation with "ng Cement" at 1- gal /sq. Field membrane splices, 3 to 4 in. wide are adhered with "ment - Black" 0 -150 lin ft/gai. Splice edges are cov- ered with "SPM Lap Caulk - Black In the SPM -60W systems described below, the Installation is the same as listed above except "SPM Lap Cement-White" is used in the place of "SPM Lap Cement - Black". Coverage rates are the same. Splice edges are covered with "SPM Lap Caulk - White" at 11 oz/22 Pm ft. 1. Deck: C -15/32 Incline: 1/2 Insulation: Any thickness, one or more layers "Fesco", "Fes- Core% "Fesco-Foam or "Ultra- Gard", hot mopped or mechanically fastened, in combination (optional) with 1/2 in. "Retro-Fit" cover board, or 3/4 in. "Fesco" over polystyrene, hot mopped or mechanically fastened. All In- sulation joints offset from plywood deck joints, 6 in. min. Base Sheet: One or more plies Type G1 "GlasPly iV ", "Glasply Premier" or "PermaPly R" or Type G2 "PermaPly No. 28 ", "GlasBase" or "Ventsulation ", or "DynaPly" or "DynaBase" (modi- fied bitumen), hot mopped. Membrane: "DynaKap FR ", "DynaGlas 30 FR ", "DynaLastic 180 FR" or "DynaGlas FR" (modi- fied bitumen). 2. Deck: NC Incline: 1/2 Insulation: (Optional) One or more layers, any thickness, "Fesco ", "Fesco-Foam ", "Fes- Core ", "UltraGard" or any UL Classified polyisocyanurate insulation, mechanically fastened or hot mopped in combination (optional) with 1/2 in. "Retro-Fit" cover board, or'3 /4 in. "Fesco" over polystyrene, mechanically fastened or hot mopped. Base Sheet: One or more plies Type G1 "GlasPly Premier ", "GlasPly IV" or "PermaPly R" or Type G2 "PermaPly No. 28", "GlasBase" or "Ventsulation ", or "DynaPly" or "DynaBase" (modi- fied bitumen), mechanically fastened-or hot mopped. Membrane: "DynaKap FR ", "DynaGlas 30 FR" or "DynaGlas FR" (modified bitumen), hot mopped. 3. Deck: NC incline: 1/2 insulatlon: (Optional) Any thickness, one or more layers, "Fesco", "Pasco - Foam ", "Fes- Core ", "UltraGard" or any UL Classified polyisocyanurate insulation, hot mopped or mechanically fas- LOOK FOR MARK ON PRODUCT ROOF 484 NT) ROOF COVERING MATERIALS (TENT) ROOFING ROOFING SYSTEMS (TGFU )— Continued a tened in combination (optional) with 1/2 in. "Retro-Fit" cover board, or 3/4 in. "Fesco" over In the following mechanically 1 polystyrene. Ply Sheet: Two or more plies Type tit "GIaaPIy Premier ", "GlasPly IV ", "PermoPly R" or Type "Ventsulation ", "DynaPiy" "DynaBase" (modified Gard" with a cover board of ells wood fiber are suitable alternates s G2 "PermaPly No. 28 ", ' GlasBase" or or or The• insulation Is attached with a bitumen), hot mopped. First layer may be nailed. sive. Tho specified membrane is Membrane: "DynaLastic 180 FR" (modified bitumen), hot mopped. placed in the field splices.. Field am• 4. Deck: C -15/32 Incline: 1 Black" at 85 to 95 lin ft/gal. Splic Barrier Board: Gypsum board, 0.463 in. min 184 Ib /sq, mechanically fastened. ft. Insulation: "Fesco- Foam ", "UltraGard", -Fes-Core", "Fesco" or wood fiber, 3.6 in. max, 112 in. In the SPM -60W Systems deso wood fiber over polystyrene, 3.6 in. max, mechanically fastened with metal screws and metal "SPM Lap Cement - White" Is used or plastic insulation plates. same. "SPM Lap Caulk- White" at 1 Membrane: Schuller International "SPM -60FR" (EPDM), SE6A fastening system. 1. Dock: NC 5. Deleted. Incline: 1/2 in. Insulation: "UltraGard" or "F "SPM ": 6. Deck: C -15/32 Membrane: -45R" or Base Sheet: " GlasBase ", "Ventsulation" or "DynaBase", nailed. Ply Sheet: One or two plies "DynaBase", "DynaPiy ", "GlasPly IV" or "GlasPly Premier`, hot 2. Deck: NC Insulation: Wood fiber, 1/2 mopped. Membrane: "DynaKap FR ", "DynaGlas 30 FR ", "DynaLastic 180 FR" or 'DynaGlas FR ", hot fiber or "Retro-Fit ", 1/2 in. cellular concrete, precast coo mopped. Membrane: "SPM -48R" or ": Deleted. Deck: C -15/32 Incline: 1/2 3. Deck: C -15/32 Insulation: One of or combk Base Sheet: "GlasBase ", "Ventsulation" or' DynaBase ", nailed. One two " DynaBase". "DynaPly ", "GlasPly IV" or "GlasPly Premier ", hot A. Gypsum board. "Fesc Ply Sheet: or plies B. Gypsum board over mopped. Membrane: "DynaKap FR ", "DynaGlas 30 FR ", "DynaLastic 180 FR" or "DynaGlas FR ", hot styrene, urethane, any thicka C. Wood fibor or "Retro -Fit mopped. Deck: NC Incline: As specified below sum board. Insulation: Wood fiber, 1/2 to 3 in., wood fiber, 1/2 in. min over "Fesco", "Fesco-Foam ", D. Wood fiber or "Retro -Flt:, "Fes- Core", "UltraGard ", polyisocyanurate, urethane, any thickness; cellular concrete, precast thane, any total thickness, in concrete with grouted joints or structural (poured in place) concrete. E. Wood fiber or "Retro-Fit", Membrane: "SPM -60" or "SPM -60FR" (System SE6A), "SPM45R" or "SPM -60R" (System Membrane: "SPM -45" or "S' SE4RA or SE611A), 1 in. incline; "SPM-60W" ((System SE6A), 1 -1/2 in. incline. 4. Deck- C -15/32 10. Deck: C -15/32 Incline: As specified below Barrier Board: Gypsum boar Insulation: One of or combination of the following: Insulation: "UltraGard" or 'I A. Gypsum board. B. Gypsum board over "Fesco ", "Fesco-Foam ", "Fes- Core ", **UltraGard", polyisocyanurate, ure- Membrane: "SPM -45R" or thene, any thickness, C. Wood ilber, 1/2 In. min over "Fesco ", "Fesco-Foam ", "Pee - gore ", over gypsum board. in. " UltraGard", polyisocyanurate, polystyrene, urethane, any total 1. Dooki Q�t8 /8II Base Sheet: One layer "Glas "SPM D. Wood fiber, 1/2 min over thickness, over gypsum board. Membrane: -45R" or E. Wood fiber, 1/2 in. min over gypsum board, Membrane: "SPM -80" or "SPM -80FR" (System SE6A), "8111M -48121" or "SPM•80R" (System incline; "SPM-GOW" (System -As in, Incline, SCHUTZ LOSUNOEN A 4 11. SE4RA or SE6RA), 1 in. Deck: NC Incline: specified below COMB Insulation: "UltraGard" or "Referenced Insulations ". Membrane: "SPM -60W" or "SPM -60FR" (System SE6A), 1/2 in. incline; "SPM -45R" or "SPM- Deck: NC 60R" (System SE411A or SE6RA), 1/4 in. incline. incline: As specified below 1. Insulation: 12. Deck: C -15/32 r glass ,a n wood fiber or glass fiber, an Barrier Board: Gypsum board. Insulation: "UltraGard" or "Referenced insulations ". "SPM or '*SPM- Base/Ply Sheet: One or me mechanically fastened. Membrane: "SPM -60W" or "SPM -60FR" (System SE6A), 1/2 in. incline; -45R' Surfacing: "Mineral Mastic 60R" (System SE4RA or SURA), 1/4 In. incline. Incline: 1/2 ibs/sq of roofing granules. 13. Deck- NC Insulation: Rmax "Multi -Max FA ", any thickness. so Membrane: "SPM -60 ". Surfacing: One coat "SPM Color Coating" at 2/3 gal /sq. Dry silica sand at 35 lbs/sq is broad -, , 1. Deck: NC cast onto wet coating. Excess sand may be removed after coating has air dried. Bald (unsand- Insulation: Polylsocyanurate ad) spots shall be recoated and resanded at same rates. (System Designation — SEBA), wood fiber or glass fiber, ar Class B — Fully Adhered Base /Ply Sheet: One or me 1. Deck: C -15/32 Incline: 1/2 Insulation: (Optional) One or more layers, any thickness "Fesco ", "Fesco-Foam ", "Fes- Core" or "Retro-Fit" mechanically fastened. Membrane: One or more a "UltraGard ", mechanically fastened in combination (optional) with 1/2 in. cover fused. board, or 3/4 in. "Fesco" over polystyrene or any UL Classified polyisocyanurate insulation. "Glas- Surfacing: "Mineral Mastic Base Sheet: One or more plies Type G1 "GlasPly Premier' or "GlasPly IV", Type G2 2, Deck: NC Base" or "Ventsulation ", or "DynaBase" or "DynaPly" (modified bitumen), mechanically fas- Insulation: Polyisocyanuratt tened or hot - mopped. Membrane: "DynaKap FR ", "DynaGlas FR ", "DynaLastic 180 FR" or "DynaGlas 30 FR" (modi- wood fiber or glass fiber, at Base /Ply Sheet: One or me fied bitumen), hot mopped. ' Incline: 1/4 mechanically fas tened. 2. Deck: C -15/32 Barrier Board: Gypsum board, 0.463 in. min 184 Ib /sq, mechanically fastened. Membrane: One or more t Insulation: Wood fiber board, 1/2 in. min over (optional) "Fesco-Foam ", "UltraGard ", "Ultra- ", "Fes-Core", "Fesco" fastened with metal screws and fused. Surfacing: "Mineral Mastic Gard SP or polystyrene, mechanically metal or plastic insulation plates. Membrane: "SPM -60", "SPM -60FW or "SPM -60W" (EPDM), SE6A fastening system. Class C — Fully Adhered SCOTT POLYMERS INC, 1. -Deck: NC Incline: 1/2 Insulation (Optional): One or more layers, any thickness, "Fesco", "Fesco- Foam ", "Fes Core ", ASPHALT FEI "UltraGard" or any UL Classified polyisocyanurate roof insulation, hot - mopped or mechanically "Fesco" Deck: NC fastened in combination (optional) with 1/2 in. "Retro-Fit" cover board, or 3/4 in. over 1. Insulation: "Ray- Lite ", 4 in. polystyrene. Base /ply Sheet: One or more plies of Type G2 "GlasBase ", "GlasBasePlus ", "Ventsulation" or Insulation: Perlite or wood "DynaBase" or Type G 1 GlasPly IV" or "GlasPly Premier', hot mopped. Surfacing: Gravel surfaced, Surfacing: "DynaKap" or "DynaGlas", hot mopped. LOOT LOOK FOR MARK ON PRODUCT R 1 Modified Bitumen Specifications Specificcttioi1 4CND /4FND /4PNII) Four Ply Hot Mopped Modified Bitumen Mineral Surfaced Roofing System Mailable Deck GlasBase. GlasBase Plus. DynaBase or PeminPly 28 m Id 0 1 Asphalt 4" Lap I ; Nails 4° End Lap -� — —• (6° for 4PND) ' L__ End Laps I . • ^� • Staggered I�- 18` —►I 3' Apart (Min) . I. . . 3" Lap to + • —• N GlasPly Premier. GlasPly IV or PermaPly -R 2` Lap Asphalt DynaKap, Dyn"Kap FR, DynaGlas, DynaGlas FR. DynaGlas 30 FR, DynaLastic 180 or DynaLastic 180 FR Geer:ral This specification is for use over any type of approved structural deck (without insulation) which can receive and adequately retain nails or other mechanical fasteners that may be recommended by the deck manufacturer. Examples of these decks are wood, plywood, and approved oriented strand board (OSB). This specification is not for use directly over lightweight, insulating concrete decks. Design and installation of the deck and /or roof sub- strate must result in the roof draining freely, to outlets numerous enough and so located as to remove water promptly and completely. Areas where water ponds for more than 24 hours are unacceptable and will not be eligible for a Schuller Roofing System Guarantee. Note: All general instructions contained in the current Schuller Commercial /Industrial Roofing Systems Manual shall be considered part of this specification. ria-Flinct- Flashing details can be found in the "Bituminous Flashings" section of the Schuller Commercial /Industrial Roofing Systems Manual. APltliccetioll On roof decks with slopes up to %° per foot (41.6 mm /m), the roof- ing felts and modified bitumen sheets may be installed either per- pendicular or parallel to the roof incline. Over wood board decks, one ply of sheathing paper must be used under the base felt, next to the deck. Using one of the base felts listed, start with a piece 24" (610 mm) wide. The remaining felts are to be applied full width with 3" (76 mm) side and 4" (102 mm) end laps over the preceding sheets. Nail the laps at 9" (229 mm) centers, and down the longitudinal center of each felt place two rows of nails, with the rows spaced approximately 11" (279 mm) apart, and nails staggered on approx- imately 18" (457 mm) centers. Use nails or fasteners appropriate to For use over plywood or other nailable decks on inclines up to 311 per foot (250 mm /m) For Regions 1, 2 and 3 Materials per 100 sq. ft. of Roof Area Sheathing Paper: Wood board decks only ........................... ..............................1 layer Felts: Base: GlasBase, GlasBase Plus, DynaBose or PermoPly 28 .........1 layer Intermediate: GlasPly Premier, GlasPly W'or PermaPly-R .........2 layers Cap: 4CND— DynaKap or DynaKop FR 4FND— DynaGlas, DynaGlas FR or DynaGlas 30 FR . 4PND — DynaLastic 180 or DynaLastic 180 FR .........................I layer Bitumen (Refer to Paragraph 7.8): Incline per foot Bitumen Total Weight Up to '/2" 1901, Type III, Steep 6916s. V to 3" 220 °F, Type IV, Special Steep 6916s. s Approximate installed weight: 195 - 410 lbs. the type of deck, with 1" (25 mm) minimum diameter caps. For additional fastener information, refer to the fastener data in the "Roof Decks" section of the current Schuller Commercial /Industrial Roofing Systems Manual. Roll an 18" (457 mm) wide piece of one of the intermediate felts listed into a full mopping of bitumen. Over that, apply a full width piece. The remaining felts are to be applied full width, overlapping the preceding felts by 19" (483 mm), so that at least 2 plies of felt cover the base felt at all locations. Apply a full width piece of one of the cap sheets listed into a full mopping of bitumen. Subsequent sheets are to be applied in the same manner, with 4" (102 mm) side and end laps over the preced- ing sheets (6" [152 mm] end laps for DynaLastic products). Apply all felts so that they are firmly and uniformly set, without voids, into the hot bitumen. Bitumen temperature should be at the Equiviscous Temperature (EVT), +_25 °F ( ±l 4 °C), at the point of application. All felt edges shall be well sealed. The bitumen shall be applied just before the felt, at a nominal rate of 23 lbs. per square (1.1 kg /m2). When applying over insulations, more than 23 lbs. per square (1.1 kg /m2) of bitumen may be needed due to the absorbency of the insulation. For modified bitumen sheets, the bitumen temperature shall be at a minimum of 4007 (204 °C), or at the EVT, whichever is higher, when the sheet is set into it. This higher temperature maximizes the bonding of the modified bitumen sheet. For cold weather application techniques, refer to Paragraph 7.31. Steels Slope Requirements Special procedures are required on inclines over '/7" per foot (41.6 mm /m). Refer to Paragraph 7.29. Surfacileg No additional surfacing is required. W METRO-DADE METROPOLITAN DADE COUNTY, FLORIDA METRO -DADE FLAGLER BUILDING Schuller International, Inc. Roofing Systems Division 717 17th Street P.O. Box 5108 Denver, CO 80217 -5108 BUILDING CODE COMPLIANCE OFFICE SUITE 1603 METRO -DADE FLAGLER BUILDING 140 WEST FLAGLER STREET MIAMI, FLORIDA 33130 -1563 (305) 375 -2901 FAX (305) 375 -2908 PRODUCT CONTROL SECTION (305) 375 -2902 FAX (305) 372 -6339 Your application for Product Approval of: Schuller International, Inc. Modified Bitumen Roofing Systems under Chapter 8 of the Metropolitan Dade County Code governing the use of Alternate Materials and Types of Construction, and completely described in the plans, specifications and calculations as submitted by: Factory Mutual Research Corporation, Underwriters Laboratories, Inc. and Dvnatech Engineering, Inc. has been recommended for acceptance by the Building Code Compliance Office to be used in Dade County, Florida under the specific conditions set forth on pages 2 -95 and the standard conditions on page 96. This approval shall not be valid after the expiration date stated below. The Building Code Compliance Office reserves the right to secure this product or Iliaterial at any time from a jobsite or manufacturer's plant for quality control testing. If this product or material fails to perform in the approved manner, the Building Code Compliance Office may revoke, modify, or suspend the use of such product or material immediately. The Building Code Compliance Office reserves the right to revoke this approval, if it is determined by the Building Code Compliance Office that this product or material fails to meet the requirements of the Building Code Compliance Office that this product or material fails to meet the requirements of the South Florida Building Code. The expense of such testing will be incurred by the manufacturer. Acceptance No.: 8 02 Revises No.: 95- 0606-02 Expires: 1998 Raul Rodriguez Product Control Division Supervisor . milk-Tel . �Mjjll : 11__ � — 0 This application for Product Approval has been reviewed by the Metropolitan Dade Counv Building Code Compliance Office and approved by the Florida under the conditions set forth above. Approved: ACT 0 2 1995 Building Code Committee be used in a County, Charles Dancer, P.E. Director Building Code. Compliance Dept.Metropolitan Dade County t x Product Control No.: 95- 0809.02 T CONrROL NoncE OF Am ROOFING SYSTEM APPROVAL Schuller International, Inc. Product Control No.: 95- 0809.02 Roofing Systems Division 717 17th Street Approval Date: 2 1995 P.O. Box 5108 Denver, CO 80217 -5108 Expiration Date: OCT 0 2 1998 to Membrane Roofing System Sub - Category: Built -up Roofing TYM. Modified Bitumen u e• SBS System Description The Roofing Systems Division of Schuller International, Inc. (a division of Manville Corp.), a fiber glass based building material company, manufactures and markets nationally a complete line of commercial BUR and modified bitumen roofing products. The product offering includes a full line of accessory products including expansion joint covers, moisture relief vents, metal fascia systems and several insulation products. Schuller markets these products through local distribution in the South Florida jurisdiction. The diversity and extent of the product offering is the result of years of manufacturing experience and product development by all of the Schuller building products subsidiaries including the newest acquisition, Owens Corning. Schuller offers a variety of approved insulated and non - insulated built -up roofing systems. For detailed system constructions, refer to the "Schuller Product and Specification Manual" for Modified Bitumen Roofing Systems. Schuller roofing products and systems have been tested in compliance with all provisions of the South Florida Building Code as well as Underwriters Laboratories, Inc., and Fact, .y. Mutual Research Corporation for fire and wind uplift resistance. Schuller provides technical assistance through local representatives. For more detailed information, please contact the Product Information Center at 1 -800- 654 -3103. Contact: Larry Glass Technical Service Supervisor 11246 Crofton Overlook Court Duluth, GA 30155 800 - 258 -1426• Frank Zuloaga Plans Examin trol Division I t Product Control No.: 95- 0809.02 TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT Product Bestile Flashing Cement CD -10 DynaBase DynaFlex DynaGlas DynaGIas 30 FR DynaGlas FR DynaKap DynaKap 7R DynaLastic 180 Dynal.astic 180 FR Various 54'10" x 36 "; roll weight: 88 lbs various 36'9" x 36 "; roll weight: 100 lbs. 369" x 37 "; roll weight: 90 lbs. 369" x 37 "; roll weight: 108 lbs. 27'8" x 37'; roll weight: 85 lbs. 278" x 37 "; roll weight: 89 lbs. 36'9" x 37 "; roll weight: 98 lbs. 36'9" x 37 "; roll weight: 108 lbs. Test Product Specification Description ASTM D 4586 A trowel grade, cutback bitumen flashing grade cement mixture including inorganic fibers and mineral stabilizers. PA 114 Insulation fastener for concrete decks. ASTM D 5147 An SBS modified bitumen coated, fiber glass reinforced base sheet. ASTM D 5147 A flexible polyester /glass scrim reinforced, granular- surfaced flashing sheet. ASTM D 5147 An SBS modified bitumen membrane surfaced with granules for application in hot asphalt. ASTM D 5147 A fire resistant SBS modified bitumen membrane surfaced with granules for application in hot asphalt. ASTM D 5147 A fire resistant SBS modified bitumen membrane surfaced with granules for application in hot asphalt. ASTM D 5147 A polyester reinforced SBS modified bitumen membrane surfaced with granules for application in hot asphalt. ASTM D 5147 A fire resistant, polyester reinforced SBS modified bitumen membrane surfaced with granules for application in hot asphalt. ASTM D 5147 A polyester reinforced SBS modified bitumen membrane surfaced with granules for application in hot asphalt. ASTM D 5147 A 180 gram polyester mat reinforced, granular- surfaced, modified bitumen cap sheet for use in fire -rated systems�-- 3 Frank Plans 4 Product Control No.: 95-0809.02 Product Dimensions Test Product Specification Description DynaPly 369" x 37 "; roll ASTM D 5147 A polyester reinforced SBS weight: 88 lbs. modified bitumen ply sheet for use in conventional and modified bitumen built -up roof systems. Expand -O -Flash various N/A Expansion joint covers manufactured from non - reinforced, form - supported elastomeric bellows with a bifurcated waterproof attachment to metal flanges. Available in various standard configurations and may be custom manufactured to specific dimensions. Expand -O -Guard various N/A Elastomeric expansion joint cover for vertical expansion and seismic joints. Manufactured from non- reinforced, form- supported elastomeric bellows with a bifurcated waterproof attachment to metal flanges. Available in various standard configurations and may be custom manufactured to specific dimensions. FP -10 Vents 10" deck flange, NIA One -way roof vent, designed for base diameter of use in various roof systems, for the 4" and a height of release of pressure created by gases 6" or moisture vapor trapped within the roofing system. Fes -Core various PA 110 Rigid polyisocyanurate roof insulation bonded to a top and bottom layer of perlite board for use in conventional built -up and other roofing. FesCant Plus Cant Strips, various PA 110 Factory pre - fabricated cant strips and Taper Edge and taper edge, manufactured from expanded perlite insulation. Fesco Board various PA 110 Rigid perlite roof insulation board for built -up roofing systems; available flat or tapered. Frank Zuloaga Plans Examiner 6du of Division 4 9 ,t t 9 Product Control No.: 95- 0809.02 Frank Zuloaga Plans Exam in , P Division 5 Test Product Product Dimensions Specification Description Fesco Foam various PA 110 Rigid polyisocyanurate roof insulation with perlite board facing bonded to one side for use in conventional built -up and other roofing. Fiber GIass Roof various PA 110 Fiberglas roof insulation. Insulation Flex -I -Drain various BOCA 76-61 Two piece flexible drain system SBCCI 89204 composed of a Noryl deck flange, a UBC 3236 flexible neoprene bellows and no hub connection. Available in various sizes and styles for most retro -fit applications. GlasBase 36" x 108; roll ASTM D 4601 Type II asphalt impregnated and weight: 84 Ibs. coated glass fiber base sheet for use in conventional and modified bitumen built -up roofing. GlasBase Plus 36" x 108; roll ASTM D 4601 Type II asphalt impregnated and weight: 84 lbs. coated glass fiber base sheet for use in conventional and modified bitumen built -up roofing. GlasFast Plate/UltraFast various PA 114 Insulation fastener and plate Screw assembly for fiber glass insulation only (steel and wood decks) GlasPly IV 36" x 200' ASTM D 4601 Type IV asphalt impregnated glass Type IV felt for use in conventional and modified bitumen built -up roofing. GlasPly Premier 36" x 180' ASTM D 2178 Type VI asphalt impregnated glass Type VI felt for use in conventional and modified bitumen built -up roofing. Industrial Roof Cement ASTM D 4.586 A trowel grade, cutback bitumen cement mixture including inorganic fibers and mineral stabilizers. Lightweight Concrete various PA 114 G -90 galvanized double spreading (LWC) CR Base Fastener leg fastener for securing base sheets to lightweight insulating concrete and some poured gypsum decks. MBR Flashing Cement N/A Proprietary Activator component for use with Activator MBR Flashing Cement Base. Frank Zuloaga Plans Exam in , P Division 5 a i J Product Control No.: 95- 08o9.o2 Product Dimensions Test Product Stzecification Description MBR Flashing Cement N/A Proprietary A two component elastomeric, cold Base application adhesive, consisting of a modified proprietary compound with an asphalt base. MBR Utility Cement N/A ASTM D 4586 General purpose trowel grade, cutback bitumen cement mixture including inorganic fibers and mineral stabilizers. NTB 1 Hand 2H various PA 114 A glass - filled nylon, double internal hex drive head, buttress thread, %" (19 mm) diameter fastener for securing roof insulation to gypsum and structural wood fiber decks. PermaPly No. 28 36" x 108'; roll ASTM D 4601 Type I1 asphalt impregnated and weight: 72 lbs. coated glass fiber base sheet for use in conventional and modified bitumen built -up roofing. PermaPly -R 36" x 180' ASTM D 2118 Type VI asphalt impregnated glass Type VI felt for use in conventional and modified bitumen built -up roofing. Presto -Lok Fascia and various PA 114 A multi -piece fascia and flashing Flashing System system for built -up and modified bitumen roofing systems manufactured from aluminum or steel. Extender plates available for wide fascia applications. This assembly meets the criteria of FMRC 1-49 for wind resistance of perimeter flashing. UltraFast various PA 114 Insulation fastener assembly (steel decks only). UltraGard various PA 110 Rigid polyisocyanurate roof insluation for use in conventional built -up and other roof systems; available flat or tapered. UltraGrip various PA 114 Insulation fastener assembly (steel decks only). Frank Zuloag Plans Examin Phtrol i vision 6 f t i Product Contiol No.: 95-0809.02 Test Product Product Dimensions Specification Description Ventsulation Felt 36" x 36' ASTM D 4897 Heavy duty fiber glass base sheet Type II impregnated and coated on both sides with asphalt with or without fine mineral stabilizer. Surfaced on the bottom side with coarse mineral granules embedded in asphaltic coating. Retro-Fit Board various PA 110 A high density perlite roof insulation board for use in conventional and modified bitumen built -up roofing systems. Frank Zuloaga Plans Exami ntrol Division 7 Product Pyrox ACFoam II Celcore Product Control No.: 954809.02 TRADE NAMES OF PRODUCTS MANUFACTURED BY OTHERS Test Product Dimensions Specification a r' Manufacturer various PA 110 Polyisocyanurate foam Apache Products Co. insulation (with current PCA) various PA 110 PA 110 Hy -Therm Nail -line various PA 110 Hy -Therm AP various PA 110 Dekfast Fasteners PA 114 #14 , I Dekfast Hex Plate 2 7/8" x PA 114 3 1/4" Dekfast Lock Plate 3" x 3 1/4" PA 114 Dekfast Fasteners n15 Dekfast Fasteners n12 i FM -30, FM-45, FM -60, FM -90 Fasteners PA 114 PA 114 PA 114 PA 114 Polyisocyanurate foam insulation Cellular insulating concrete system Polyisocyanurate foam insulation Atlas Energy Products (with current PCA) Celcore, Inc. (with current PCA) Celotex Corp. (with current PCA) Polvisocyanurate foam Celotex Corp. insulation (with current PCA) Insulation fastener for steel Construction and concrete decks Fasteners Ind. (with current PCA) Galvalume hex stress plate. Construction Fasteners Inc. (with current PCA) Polypropylene locking Construction plate. Fasteners Inc. (with current PCA) Insulation fasteners for Construction concrete decks Fasteners Inc. (with current PCA) Insulation fastener for steel Construction and wood decks. Fasteners Inc. (with current PCA) Aluminum fastener for Creative lightweight, gypsum and Construction tectum decks Components (with current PCA) Base ply fastening systems ES Products, Inc. for lightweight concrete (with current PCA) decks Frank Zuloasa Plans Examiner, odic ivision 8 Product Control No.: 95-0809.02 Prod c Dimensions Test Specification Product Description Manufacturer Asphalt Emulsion PA 121 Asphalt emulsion Gardner (with current PCA) Asphalt ASTM D 312 Type III or IV hot asphalt generic bitumen adhesive Asphalt Primer ASTM D 41 Asphalt Primer generic EPS various PA 110 Extruded polystyrene generic insulation (with current PCA) High Density Wood various PA 110 Wood fiber insulation generic Fiberboard board (with current PCA) Oriented Strand various PA 110 Oriented strand board generic Board (with current PCA) Pelite/Urethane various PA 110 Perlite / urethane composite generic Composite board insulation (with current PCA) Perlite Insulation various PA 110 Perlite insulation board generic (with current PCA) Polyethylene 4 mil min. Vapor barrier / Air barrier generic Red Rosin various Rosin paper for barrier generic layer on wood decks Roofing Nails Minimum ' PA 114 Corrosion resistant annular generic 12 ring shank nails Tin Caps Min. 32 ga. x Corrosion resistant circular generic 1518" discs. Type X Gypsum various Fire resistant rated gypsum generic Type X Gypsum various Fire resistant rated gypsum generic Dens -Deck 4'x 8' PA 110 Gypsum board Georgia - Pacific (with current PCA) Overlayment Board 4' x 8' PA 110 Gypsum board Georgia - Pacific Frank Zuloaga Plans Examiner, PWct of Division 9 Product Control No.: 95- 0809.02 ENRG'Y -2 ISORoc Con -Tite wood fiber insulation (with current PCA) Test Product insulation Product Dimensions Specification Description Manufacturer insulation Sturdi -Top various PA 110 Wood fiberboard Georgia - Pacific Group, Inc. (with current PCA) ISO 95+ various PA 110 Polvisocyanurate foam International insulation Permalite (with current PCA) #12 Roofgrip PA 114 Insulation fastener for steel ITW Buildex or wood decks (with current PCA) # 14 Roofgrip PA 114 Insulation fastener steel, ITW Buildex wood or concrete decks (with current PCA) Gripdek Fastener PA 114 Insulation fastener ITW Buildex (with current PCA) Hexcel Fastener PA 114 Insulation fastener ITW Buildex (with current PCA) Hextra PA 114 Insulation fastener and ITW Buildex metal or plastic plate (with current PCA) Polymer Gyptec PA 114 Glass reinforced nylon ITW Buildex gypsum deck fastener (with current PCA) Premium Metal 3" square PA 114 3" square galvalume AZ55 ITW Buildex Plate stress plate (with current PCA) Standard Plastic 3" round PA 114 Polyolefin plastic plate ITW Buildex Plate (with current PCA) Barrier Board Plus various PA 110 Polvisocvanurate foam / NRG Barriers, Inc. ENRG'Y -2 ISORoc Con -Tite wood fiber insulation (with current PCA) various PA 110 Polvisocyanurate foam NRG Barriers, Inc. insulation (with current PCA) various PA 110 Polyisocyanurate foam / NRG Barriers, Inc. rockwool composite (with current PCA) insulation PA 114 Conctrete deck insulation Olympic fastener Manufacturing Group, Inc. 10 Frank Zuloaga Plans Examine; Product Control No.: 95-0809.02 Product Dimensions Test Specification Product Description Manufacturer Olympic Standard 3" round PA 114 3" round galvalume Olympic AZ55 steel plate Manufacturing Group, Inc. (with current PCA) Olympic Fastener PA 114 Insulation fastener Olympic 914 Manufacturing Group, Inc. (with current PCA) Olympic 3.25" round PA 114 Polypropylene Olympic Polypropylene plastic plate Manufacturing Group, Inc. (with current PCA) Olympic Fastener PA 114 Insulation fastener Olympic 912 Manufacturing Group, Inc. (with current PCA) Fiber Glass Roof 6'x 300' proprietary Glass fiber mat together Owens- Corning Tape with reinous binder to Fiberglas Corp. reinforce fiber glass roof (with current PCA) insulation. t Fiberglas various PA 110 Fiber glass roof insulation Owens- Coming Fiberglas Corp. (with current PCA) GlasFast Fastener PA 114 Insulation fastener Owens- Corning assembly with recessed Fiberglas Corp. plastic plate (with current PCA) GlasFast/Striker PA 114 Insulation fastener Owens - Corning assembly and metal plate Fiberglas Corp. for use over concrete decks (with current PCA) Paroc Base Board various PA 110 Rock-wool insulation Partek, Inc. (with current PCA) Paroc Cap Board various PA 110 Rockwool insulation Partek, Inca (with current PCA) Multi -Max various PA 110 Polyisocyanurate foam Rmax, Inc. insulation (with current PCA) HD Insul -Fixx PA 114 Insulation fastener for use SFS /Stadler Fastener in steel and concrete decks (with current PCA) Frank Zuloasa Plans Examiner, 1 Division 11 t r Product Control No.: 95- 0809.02 j J 12 Frank Zuloaaa Plans Examiner Test Product Product Dimensions Specification Description Manufacturer Insul -Fixx Fastener PA 114 Insulation fastener for steel SFS /Stadler and wood decks (with current PCA) Insul -Fixx S 3" square PA 114 3" square galvalume AZ55 SFS /Stadler stress plate (with current PCA) Insul-Fixx P 3" round PA 114 3" round polyethylene SFS /Stadler stress plate (with current PCA) Plate Fixx Fastener PA 114 Insulation fastening SFS /Stadler assembly (with current PCA) Rawl Drive PA 114 Insulation fastener and steel The Rawlplug and plastic stress plate for Company Inc. concrete deck (with current PCA) Rawl Fasteners PA 114 Insulation fastener for steel The Rawlplug # 12 and wood decks Company Inc. (with current PCA) Rawl Fasteners t PA 114 Insulation fastener for use The Rawlplug X14 in steel, wood or concrete Company Inc. (with current PCA) Rawl 2" Plate 2" round PA 114 2" round galvalume AZ55 The Rawlplug membrane plate Company Inc. (with current PCA) Rawl 3" Plate 3" round PA 114 3" round galvalume AZ55 The Rawlplug steel plate Company Inc. (with current PCA) Rawl Spike PA 114 Insulation fastener and steel The Rawlplug and plastic stress plate for Company Inc. concrete deck (with current PCA) Rawlite PA 114 Insulation fastener for The Rawlplug cementitious and gypsum Company Inc. decks (with current PCA) Rawlite 3" Plate 3" round PA 114 3" round galvalume AZ55 The Rawlplug steel plate for use with Company Inc. Rawlite fasteners (with current PCA) j J 12 Frank Zuloaaa Plans Examiner Product Control No.: 95- 0809.02 Product Dimensions Test Specification Product Description Manufacturer TL Stress Plate 3" round PA 114 3" round galvalume AZ50 Tru -Fast steel plate for use with (with current PCA) Tru -Fast TL fasteners Tru -Fast DL PA 114 Insulation fastener for steel, Tru -Fast or wood (with current PCA) Tru -Fast Plastic 3.04" round PA 114 3.04" round polyethylene Tru -Fast Plate plastic plate (with current PCA) Tru -Fast MP -3 3.23" round PA 114 3.23" round galvalume Tru-Fast AZ50 steel plate (with current PCA) Tru-Fast HD PA 114 Insulation fastener for use Tru-Fast in wood, steel or concrete (with current PCA) decks Tru-Fast Ultra PA 114 Stainless Steel fastener for Tru-Fast use in steel, wood and (with current PCA) concrete decks Tru -Fast TL PA 114 Glass reinforced nylon Tru-Fast fastener for use in tectum or (with current PCA) gypsum decks Tru-Fast DP PA 114 Insulation fastener for use Tru -Fast in steel or wood decks (with current PCA) Tru-Fast TP PA 114 Insulation fastener for use Tru-Fast in steel or wood decks (with current PCA) Tru-Fast CF PA 114 Insulation fastener for Tru-Fast Fasteners concrete decks (with current PCA) Insulcel PA 110 Cellular insulating concrete W.R- Grace system (with current PCA) Structodeck various PA 110 High density wood fiber Wood Fiber Industries l Frank Zuloaga Plans Examin of Division 13 Product Control No.: 95-0809.02 Test Reports Test Agency/Identifier Name $gam jig Factory Mutual Research J.I. # 2P3A4.AM Wind Uplift Classification 09.23.88 Corporation J.I. # IQ6A4.AM Wind Uplift Classification 12.11.90 J.I. # 2NOA6.AM Wind Uplift Classification 9 22.88 FMRC 1994 Current Insulation and 01.01.94 Fastening Requirements. Dynatech Engineering, 4360.03.95 -1 Wind Uplift Classification 3.95 Inc. 4360.03.95 -2 Wind Uplift Classification 3.95 4361.5.95 -1 Wind Uplift Classification 5.95 Underwriters R -10167 (I) Fire Classification 01.01.95 Laboratories, Inc. Compliance 14 Frank Zuloaga Plans Examinee Product Control No.: 95-0809.02 Fibrous glass Perlite Polyisocyanurate Composite Board Rockwool High Density Wood Fiber u . u u 9 a0 ' Material Design Pressure Wood........ .............................45 psf Steel .......... .............................60 psf Concrete ....... ............................232 psf (see System Limitations for details) Lightweight Concrete ......................57 psf Poured Gypsum Concrete ..................55 psf Cementitious Wood Fiber ..................45 psf u• �r Maximum Fire Classification Classification 00 ........ ............................ Class'A' Steel....... ............................... Class'A' Concrete ... ........... ..................... Class'A' Lightweight Concrete ..................... Class'A' Cementitious Wood Fiber ................. Class'A' Poured Gypsum Concrete ................. Class'A' Note: Fire classifications and maximum design pressures do not reference all assemblies over all deck types. Review system listings for design pressures and the Underwriters Laboratories Roofing Materials Directory for Fire Classifications. t Frank Zuloaga 2 Plans Exam' t Control Division 15 1 Product Control No.: 95-0809.02 Membrane Type: Deck Type 1: Deck Description: System Type E: SBS Wood, Non - insulated " /,Z" or greater plywood or wood plank decks Base sheet mechanically fastened. All General and System Limitations apply. Base Sheet: One ply of Schuller PermaPly No. 28, DynaBase, GlasBase, GlasBase Plus or Ventsulation fastened to the deck as described below: Fastening: Base sheet shall be lapped 4" and fastened with approved roofing nails and tin caps 9" o.c. in the lap and two rows staggered in the center of the sheet 12" o.c.. Ply Sheet: One, two or three plies of DynaBase, GlasBase, GlasBase Plus, PermaPly No. 28, GlasPly Premier, Glas Ply IV, PermaPly -R, or DynaPly adhered to the base sheet with approved mopping of asphalt applied within the EVT range and at a rate of 20-40 lbsJsq.. Membrane: One ply of DynaKap, DynaKap FR, DynaGlas, DynaGlas FR DynaGlas 30 FR, Dynalastic 180, Dynalastic 180 FR or DynaPly adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20-40 lbs./sq. (See Schuller application instructions for approved method of installation). Surfacing: (Optional) Install one of the following: 1.2 -3 gallons TopGard B emulsion/sq. or 2 gallons aluminum coating/sq.. Coatings shall be applied according to the manufacturers' recommendations regarding specific application rates and weathering. 2. Flood coat and gravel/slag with an application rate of 60 lbsJsq. & 400 lbsJsq., respectively._ Maximum Design Pressure: -45 psf. Maximum Fire Classification: Class 'A; see General Limitation 42. Maximum Slope: 3:12; see General Limitation T3. Specification No.: 4CND, 4FND, 4PND, 3CND, 3FND, 3PND, 2CND, 2FND, 2PND, 3CNG, 3FNG, 3PNG, 2CNG, 2FND, 2PND Frank Zuloaga Plans Examiner of Division 4 Product Control No.: 95-0809.02 Wood Deck System Limitations: 1. A red rosin sheet shall be installed on all wood plank decks to eliminate asphalt seepage and bonding of base sheet to wood plank deck. Red rosin sheet may also be installed on plywood decks as an option. 2. Pre-assembled 'Cap Nail' shall not be used for base sheet attachment. Frank Zuloaaa Plans Exam u in ntrol Division 25 Product Control No.: 95- 0809.02 General Limitations: 1. All asphalt shall comply with ASTM D 312 type III or type IV requirements. All proposed asphalt producers must be approved by the applicant. 2. Fire ratings are determined by a combination of slope, deck type and assembly. Refer to current Underwriters Laboratories Roofing Materials Directory or other fire testing data listed by an approved listing laboratory agency. Fire ratings shall be in compliance with Sections 3401.5 and 3401.6 of the South Florida Building Code. 3. Maximum slope range shall vary for each system; consult current Underwriters Laboratories Roofing Materials Directory and manufacturer's specifications for compliance with design criteria for each project. 4. An overlay /recovery board insulation panel is required on all applications over closed cell foam insulations when the base sheet is fully mopped. If no recovery board is used the base sheet may be applied using spot mopping with approved asphalt, 12" diameter circles, 24" o.c.; or strip mopped 8" ribbons in three rows, one at each sidelap and one down the center of the sheet allowing a continuous area of ventilation. Encircling of the strips is not acceptable. A 6" break shall be placed every 12' in each ribbon to allow cross ventilation. Asphalt application of either system shall be at a minimum rate of 12 lbsJsq.. Note maximum design velocity j pressure restrictions on spot attached systems. 1 5. Any amendments to these provisions shall be in compliance with Sections 203 and 204 of the South Florida Building Code. 6. All work shall be performed by a Dade County licensed roofing contractor. Contractor shall be familiar with the details and specifications published by the manufacturer. 7. In re- roofing applications, moisture content in an existing built -up roof must be in compliance with Section 340I.10(m) of the South Florida Building Code. 8. Prior to application, all existing roof surfaces used as a bonding substrate shall be tested for uplift resistance in compliance with Dade County Protocol PA 124 to the calculated design pressure of the roof deck. 9. If required, any Factory Mutual Approved vapor barrier in conjunction with proprietary or approved adhesives may be used prior to the application of the insulation layer. 10. Perimeter and corner areas shall have an increase in fastener density for both insulation and base sheet in compliance with Dade County Protocol PA 117 of the South Florida Building Code. 11. All attachment and sizing of perimeter nailers and metal profile designs shall conform with Dade County Protocol PA 111 of the South Florida Buildin Frank Zuloaga i Plans Examiner, o Division 94 J Product Control No.: 95- 0809.02 12. Flashings shall be installed according to the manufacturers standard details, and may be applied in cold application adhesive, approved asphalt or may be applied in conjunction with an approved torch applied modified bitumen membrane. Specific details, approved by the manufacturer, shall be submitted with the Section lI Permit Application. 13. Roll good materials shall be stored on end and on a clean, flat and dry surface. 14. Consult current Underwriters Laboratories Directory for the appropriate coating for each roofing assembly to obtain the required fire rating. The assembly shall be installed in strict compliance with Chapter 3401.5 and 3401.6 of the South Florida Building Code for maximum fire classification. 15. Asphalt moppings shall be with applied with asphalt approved by the applicant and shall be approved in compliance with equiviscous temperature (EVT) methods of asphalt determination. Asphalt containers or bulk tickets shall indicate an EVT, finished blowing temperature (FBT) and flash point. Asphalt types and temperature ranges shall be in compliance with Subsection 3403.4(x)(3) of the South Florida Building Code. 16. Insulation may be installed in multiple layers. The first layer shall be attached in compliance with Product Control Approval guidelines. All other layers shall be adhered in a full mopping of approved asphalt applied within the EVT range and at a rate of 20 -40 lbsJsq., or mechanically attached using the fastening pattern of the top layer. Refer to manufacturer's literature and/or the NRCA Roofing and Waterproofing Manual for correct application procedures of insulation panels in approved asphalt or adhesive. 17. Pre - assembled cap nails may only be used for termination of fully bonded surfaces such as mechanical termination at wood blocking, head and side laps, and base flashing terminations. Cap nails shall not be used for the mechanical attachment of a base sheet. Tin caps are required by the South Florida Building Code. 18. The submission of system specifications and details shall accompany the Section II Building Code Permit. This information is available in the publications listed in the 'System Description' of this Product Control Approval. The submission of these documents, as well as the proper application "and installation of all materials shall be the sole responsibility of the contractor. 19. All standard panel sizes are acceptable for mechanical attachment. When applied in approved asphalt, panel size shall be 4' x 4' maximum. 20. Fastener spacing for insulation attachment is based on a minimum withdrawal resistance value of 300 lbf. as tested in compliance with PA 105. If the fastener value, as field tested, are below 300 lbf. insulation attachment shall not be acceptable. Frank Zuloaga Plans Examiner, P Division 95 Schuller International, Inc. Roofing Systems Division 717 17th Street P.O. Box 5108 Denver, CO 80217 -5108 Product Control No.: 95- 0809.02 ACCEPTANCE NO.: - -080M APPROVED Q�( O ? 1 9W EXPIRES NOTICE OF ACCEPTANCE STANDARD CONDITIONS 1. Renewal of this Acceptance (approval) shall be considered after a renewal application has been filed and the original submitted documentation, including test supporting data, engineering documents, are no older than eight (8) years. 2. Any and all approved products shall be permanently labeled with the manufacturer's name, city, state, and the following statement: "Dade County Product Control Approved ", or as specifically stated in the specific conditions of this Acceptance. 3. Renewals of Acceptance will not be considered if a) There has been a change in the South Florida Building Code affecting the evaluation of this product and the product is not it. compliance with the code changes; b) The product is no longer the same product (identical) as the one originally approved; c) If the Acceptance holder has not complied with all the requirements of this acceptance, including the correct installation of the product; d) The engineer who originally prepared, signed and sealed the required documentation initially submitted, is no longer practicing the engineering profession. 4. Any revision or change in the materials, use, and/or manufacture of the product or process shall automatically be cause for termination of this Acceptance, unless prior written approval has been requested (through the filing of a revision application with appropriate fee) and granted by this office. 5. Any of the following shall also be grounds for removal of this Acceptance: a) Unsatisfactory performance of this product or process; b) Misuse of this Acceptance as an endorsement of any product, for sales, advertising or any other purposes. 6. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the expiration date may be displayed in advertising, literature. If any portion of the Notice of Acceptance is displayed, then it shall be done in its entirety. 7. A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at all times. The copies need not be resealed by the engineer. 8. Failure to comply with any section of this Acceptance shall be cause for termination and removal of Acceptance. 9. This Acceptance contains pages 1, through 96. END OF THIS ACCEPTANCE Frank Zulm, Plans Exam 96 f — ou Product Control No.: 95.1128.12 PROFIId; DRAWINGS (CONTINUED) Z,a^ cur �u oea APPROVED Scitrw roll SCREW DATA IN Moo 3 IIA16 From Zulonga Plans Examiner, Product Control Division Pioneer Concrete Tile 1340 Southwest 341h Avenue Deerfield Beach, Ff. 33442 Product Control No.: 95. 1128.12 ACCEPTANCENO.: —25- 1128.12 APPROVED Feb.06.1996 EXPIRES Feb.06.1999 NOTICE OFA . .PTAN STANDARD CONDITION 1. Renewal of this Acceptance (approval) shall be considered offer a renewal application has been filed and the original submitted documentation, including test supporting data, engineering documents, are no older than eight (8) years. 2. Any and all approved products shall be permanently labeled with the manufaclurer s name, city, state, and the following statement: "Dade County Product Control Approved ", or as specifically stated in ilia specific conditions of this Acceptance. 3. Renewals of Acceptance will not be considered if: a) There has been a change in the South Florida Building Code affecting ilia evaluation of this product and the product is not in compliance with Ilia code changes; b) The product is no longer the same product (identical) as the one originally approved; c) tribe Acceptance holder has not complied with all the requirements of this acceptance, Including the correct Installation of the product; d) The engineer who originally prepared, signed and scaled the required documentation Initially submitted , is no longer practicing the engineering profession. 4. Any revision or change in the materials, use, and/or manufacture of lbe product or process shall automatically be cause for termination of this Acceptance, unless prior written approval has been requested (through ilia filing of a revision application with appropriate fee) and granted by this office. 5. Any of the following shall also be grounds for removal of lhis Acceptance: a) Unsatisfactory performance of this product or process; b) Misuse of this Acceptance as an endorsement of a y product, for sales, advertising or any other purposes. 6. The Notice of Acceptance number preceded by the words Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the Notice of Acceptance is displayed, then it shall be done in its entirety. 7. A copy of this Acceptance as well as approved drawings and other documents, where it applies, shall be provided to the user by lite manufacturer or its distributors and shall be available for inspection at the job site at all times. The copies need not he resealed by the engineer. 8. Failure to comply with any section of this Acceptance shall because for termination and removal of Acceptance. 9. This Acceptance contains pages I through 18. END OF THIS ACCEPTANCE IIA17 Fran u oaga Plans Examiner, Product Control Division Product Control No.: 95. 1128.1 Z DATA FOR ATTACIIMENT CALCULATIONS (CONTINUED) Table 3 -A: Attachment Resistance Expressed as a Moment - M, (ft -lbf) for Nail -On Systems Tile Tile Two (2) 10d x 3" long nails' Profile Application Adhesive Set Pioneer -Hacienda- Direct Deck New Construction 87.50 (min. nl,i plywood) Direct Deck 43.00 Recover/Reroof (min. '%," pfywoW) Battens 50.90 New Construction Tile Installation with a 4' headlap using two (2) Approved 10d x 3- long polymer waled. corrosion resistant, ring shank nails installed In manufactured holes located 2%- from the head of the file. Clips on save life are not required for this attachment configuration unless the Required Moment of Resistance exceeds the values noted above. Table 4: Attachment Resistance Expressed as a Moment - M, (fl -lbf) for Mortar or Adhesive Set Systems Tile Profile Tile Application Attachment Reslstance Pioneer'Hacienda' Mortar Set 20.80 Adhesive Set 88.81 IIA14 Frank Zuloaga Plans Gxnmincr, Product Control Division Product Control No.: 93-11211-12 PROFILE DRAWINGS 1 t3' �`• ' � � � �.) lie .J' PiwarR "IIACIF1,10 " IIA15 Fra oaga Plans Rxandncr. Product Control Division Product Control No.: 95- 1128.12 .SYSTFhi Lirtit9'A'1'IONS I. The standard utininunn roof pitch for Pioneers "I Incienda." low profile tic shall comply with Dade County Application Standards PA 118, PA 119 or PA 120, depending nn the method of installation. 2. For nail -mu applications, fasteners for mechanical auachtncnl of tiles shall Imvc a head diameter larger thin that of the preformed holes in the tile. 3. Systent installation shall be in compliance with the system specifications outlined in this Product Control Approval. 'I'ho method of attachment utilized shall provide sufficient attachment resistance expressed as a moment to nice[ or exceed the required moment of resistance determined in compliance with Dade County Protocol PA I IS or PA 127. Pioneer's "Ilacicnda" life profile has been tested for bolls wind characteristics and static uplift performance, therefore, attachment calculations for installation in compliance with PA IIS or PA 127 shell be done as a'Moment Rased System'. 4. For mortar or adhesive set tile applications, a field static uplift test by n Dade County accredited testing agency, in compliance with Dade County Protocol PA 106, shall be performed. 5. For mortar set life applications. 30/90 hot mopped undcrlaymcnt applications tinny be installed perpendicular to the roof pitch unless stated otherwise by the undcrlaymcnt material manufacturces published literature. 6 All tiles shell bear the imprint or identifiable marking of the mmoufacturces name or logo for identification in the field. The identifiable mark for the "I lacienda," low profile the shall be the word "Pioneer" on the back side of the tile. 7. Applications for roofing permits shall include a completed Section II of the Uniform Building Permit, a copy of Pioneer's current specifications and details, a copy of this Product Control Approval and a copy of the Product Control Approval of any Roofing Component used in the proposed tile application. Reference shall be made to appropriate data for the required fire rating. R. 'file applicant shall retain the services of a Dade County certified testing laboratory to maintain quality control in compliance with the South Florida Building Code and related protocols. Samples taken shall be in compliance with Dade County Protocol PA 112, Appendix'A'. c IIA12 Fr n _ u oaga Plans Examiner, Product Control Division Product Control No.: -' SJ12fi.1: DATA FOR ATTAcubwNT CALCULATIONS Table 1: Aerodynamic Multipliers _ A (ft') Tile Profile )L (f 3) Batten Application r, (fl') Direct Dock Application Pioneer "Hacienda" 0.27 0.29 Table 2: Restoring Moments due to Gravity - Mo (ft -Ibf) Tile 3 ":12" 4 ":12" VAT' 6 ":12" Greaterthan Profile 2 nails 1 screw 12 screws 1 nail 7":12" 1 nab Battens Direct Battens Direct Battens Direct Battens Direct Batten Direct 32.20 Deck Dock 25.80 Deck 24.30 Deck 19.00 Deck Pioneer 5.02 6.80 5.82 6.60 5.70 6.65 5.56 6.30 5.41 NrA " Hacenda' Table 3: Attachment Resistance Expressed as a Moment - M, (fl -Ibf) for Nail -On Systems' Tile Profile Tile Application Approved Nails Approved Screws' Approved Field Clip With: Approved Eave Clip With: 1 nail 2 nails 1 screw 12 screws 1 nail 2 nails 1 nab 2 nails Pioneer "Hacienda° Ballens 4.10 [11.80 7.10 22.90 40.10 24.20 34.80 22.10 32.20 Direct Deck 21.90 25.80 47.10 24.30 35.50 19.00 31.90 Data noted In Table 3 Is for installation with a 3' tile headlap. ' Approved screws are as noted In the Trade Names of Products Manufactured By Others' and 'Profile Drawings' sections of this Approval. Clips on save Ole are not required for this attachment configuration unless the Required Moment of Resistance exceeds the values noted above. IIA13 Frank u oaga Plans Examiner, Product Control Division Product Control No.: 95- 1128.12 SYSTEDIS (CONTINUED) Deck Type: Wood, Non- insulated Deck Description: New construclion'% „” or greater plywood or wood plank. SYSTEM C: I lorizonlal Batten Application Slope Range: 4 ":12" or greater Note: Horizontal battens, as noted below, sure required for slopes in excess of 7 ":12" and are optional for slopes of 4 ":12" to 7 ":12 ". For slopes less than 4 ":12 ", refer to System A. Underlaymenk Install undcrinynicnt system in compliance with Dade County Application Standard PA 119. Ilorizonlul Battens: Install horizontal battens in compliance with Dade Cranny Application Standard PA 119. Roofing Tiie: Install tilt in compliance with Dade County Application Standard PA 119. (Sec "Data for Attachment Calculations" included in this Approval.) Continents: I. For re -roof opplications. "/,." plywood is on acceptable substrate. HA 10 FrAR75Ti oaga — Plans Examiner, Product Control Division Product Control No.: 95- 1128 -12 SYSTENIS (CONTINUED) Deck Type: Wood,Noo- insulated Deck Description: New constmelion'% „” or greater plywood or wood plank. SYSTEM D: Mortar or Adhesive Set Application Slope Range: 2 ":12" to 7 ":12" Note: System D is only acceptable in this slope range. For slopes in excess of 7 ":12 ", refer to System C. Underlayment: Install underlaymcnt system in compliance with Dade Ctnouy Applicntion Standard PA 120. (Sec System Limitation 115.) Roofing Tile: Install lilt in compliance with Dade County Application Standard PA 120. (Sec "Data for Attachment Calculations" inchuled in this Approval.) Comments: I. For re -roof opplicalions. 10 /,," plywood is an acceptable substrate. HAll Fran • .0 oagn Plans Examiner, Product Control Division Product Control No.: 95-1118.12 SYS't'rols Deck Type: Wood, Non - insulated Deck Description: New Construction Deck Type: " /„" or greater plywood or wood plank. SYSTEM A: Counter- Batten Application Slope Range: 2 ":12" to 7 ":12" Slope Range: Note: Can n ter-Ili ttens, as noted below, are required for slope range 2 ": 12" to less Ilion 4 ": 12" and are optional for slopes of 4 ":12" to T *12 ". ror slopes exceeding V %12 ", refer to System C. Underlayment: Install undcrinymcnt system in complionce with Dade County Application Underlayment: Standard I'A 118. Vertical linitens: Install vertical battens in compliance with Dade County Application Standard Rooling Tile: PA 118 Horizontal Battens: Install horizontal battens in compliance with Dade County Application Comments: Standard PA 118. Roofing Tile: Install file in compliance with Dade County Application Standard PA II8. (See "Data for Attachment Calculations" included in this Approval.) Comments: 1. ror re- roofapplications, " /t;" plywood is an acceptable substrate. IIA8 Fran 7.uloagn Plans Examiner, Product Control Division Product Control No.: 95.1178. 12 IIA9 'K� FraakB oaga Plans Examiner, Product Control Division SYSTEMS (CONTINUED) Deck Type: Wood, Non - insulated Deck Description: New construction 1°/ „” or greater plywood or wood plank. SYSTEM 11: Direct Deck Application Slope Range: 4 ":12" to 7 ":12" Note: System D Is only acceptable In this slope range. For slopes less Ilion 4 ":12 ", refer to System A. ror slopes in excess of 7 ":12 ", refer to System C. Underlayment: Install underlayment system in compliance with Dade County Application Standard PA 118. Rooling Tile: Install file in compliance with Dade County Application Standard PA 118. (See "Data for Attachment Calculations" included in this Approval.) Comments: 1. ror re -roof applications, 11/a" plywood is an acceptable substrate. IIA9 'K� FraakB oaga Plans Examiner, Product Control Division i__.rte— ...��..•� -. -- -- IIA6 HA7 rArzu oaga Fra saga Plans Examiner, Product Control Division Plans Examiner, Product Control Division Prnduct Control No.: 95- 1128.12 Product Control No.: 95-1129.12 TEST RmirrS lest gent: Test Idenllfic Test Name /Repgrt Rate The Center for Applied 25- 7214.6 Static Uplift Testing March, 1995 T LArma Too- filrnlilirr Tssl.Nanlr /Iirourt Dale Engineering, Inc. PA 102 Itedland Technologies 7161.03 Static Uplin Testing Dcc. 1991 (I Quik -Drive Screw, Battens) Appendix nt PA 102 Redland Technologies 7161.03 Static Uplift Testing Dec. 1991 Redland Technologies 7161 -03 Appendix If Wind •funnel T•csting PA 108 Dec. 1991 Appendix III PA 102(A) (Nail-011) The Center for Applied 94.084 Static Uplift Testing May 1994 Redland Technologies Letter Dated Aug. I, 1994 Wind Tunnel Testing Aug. 199.1 Engineering. Inc. PA 101 PA 108 (Mortar Set) (Nail -Orr) The Center for Applied 94.060n Static Uplin Testing March, 1994 Redinnd Technologies P0631.01 Wind Tunnel Testing July 199.1 Engineering, Inc. PA 101 PA 108 (Adhesive Set) (Mortar Set) The Center for Applied 25.7094.1 Static Uplift Testing Oct. 1994 Redland Technologies P0402 Withdrawal Resistance Sept. 1993 Engineering, Inc. PA 102 Testing of screw vs. smooth (4" I lcadlap, Nails, Direct shank nails Deck, New Construction) The Center for Applied Project No. 307025 Wind Driven Rain Oct. 1994 The Center for Applied 25- 7094.7 Static Uplift Testing Oct. 1994 Engineering, Inc. Test I/MDC -76 PA 100 Engineering, Inc. PA 102 (4" 1leadlap, Nails, Battens) Professional Service 224.47099 Physical Properties Sept. 1994 Industries, Inc. PA 112 The comer for Applied 25- 7094 -4 Static Uplift Testing Oct. 1994 Engineering, Inc. PA 102 (4" Headlap, Nails, Direct Deck, Recover /Reroof) The Center for Applied 25.7183 -1 Static Uplift Testing Feb. 1995 Engineering, Inc. PA 102 (2 Quik -Drive Screws, Direct Deck) The Center for Applied 25. 7183.2 Static Uplift Testing Fcb. 1995 Engineering, Inc. PA 102 (2 Quik -Drive Screws, Battens) The Center for Applied 25.7214 -2 Static Uplift Testing March, 1995 Engineering, Inc. PA 102 (I Quik -Drive Screw, Direct Deck) i__.rte— ...��..•� -. -- -- IIA6 HA7 rArzu oaga Fra saga Plans Examiner, Product Control Division Plans Examiner, Product Control Division Product Control No.: —9S-LOA Product Control No.: 95.1128,E Test Product Test Product Product p[mS11319ns ,'5pecificaIfoil Dwriathm Manufaclurs Product Dimensions SaCS111maaas priciiltllau Manufacturer Asphalt Primer N/A ASTM D 41 Cut back, asphalt generic Roof Tile Mortar N/A PA 123 Prepared mortar mix W.R. Donal Co. based coating used to ( "BONSALO Roof designed for mortar with current PCA facilitate hooding of Tile Mortar Mix ") set roof life dissimilar materials. applications. Roofing Nails min. 12 ga. with PA 114 Annular ring shank, generic Roof Tile Adhesive N/A Sec PCA Two component 1101yfoam Products, head Appendix li hot dipped, cicciro or ( "Polypro® AN160 ") polyurethane adhesive Inc. mechanically gale. designed for adhesive with current PCA roofing nails for use set roof life in underlayment applications. attachment. I lurricane Clip & Clio PA 114 Corrosion resistant generic Tin Caps min. 32 go. PA 114 Corrosion resistant generic rasteners min. %," width Appendix E bronze, aluminum, min. 1' /," CA. Appendix H circular disc for use in min. 0.060" thick stainless steel, max. 2" CA. underlayment galvanized steel or allachmenl cha- rostencr5 plastic attachment min. 8d x 1V.." clips for supplemental Wood Battens xntilsnl Wood Preservers Salt pressure treated generic tile attachment. Clips min. I" x 4" Institute LP . 2 or decay resistant are Installed will, lumber battens corrosion resistant hariza0ial touring nails min. I" x 4" for use compatible Willi the Willi vertical battens clip. A hurricane clip is required on all or min. I" x 2" for use nail-oil cave tiles. alone Valley Plashing min. 26 ga. AS'rM A 525 Galvanized steel generic Tile Nails min. 8d x 2'A" or PA 114 Corrosion resistant, generic min. 16" width valley flashing min. I Od x 3" Appendix E screw or smooth shank nails. Drip Edge min. 26 ga. PA I I I Galvanized steel drip generic min. 2" face flange edge Tile Screws 118 x 2%," long PA 114 Corrosion resistant, generic min. 2" deck flange 0.335" head din. Appendix E coated, square drive, 0.131" shank dia. galvanized, coarse 0.175" screw thread thread wood screws diameter Roof Tile Mortar N/A PA 123 Prepared mortar mix Bermuda Roar ( "TileTiteTN ") designed for mortar Company, Inc. set roof tile with current PCA application. Roof Tile Mortar N/A PA 123 Prepared mortar mix Quikrctc Constructio ( "Quikrctc(ID Roar designed for mortar Products Tile Mortar Ill 140 ") set roof tale with current PCA applications. BA4 IIAS rr ZlTago ` - -_ rrnn u oago — Plans Examiner, Product Control Division Plans Examiner, Product Control Division Product Control No.: 95-1128-12 TRAm, NARIES OF PRODUCTS MANUrAcru m OR LABCLFD BY APPLICANT 'rest Product Prodlict 12hucnslons SII4Sirial lls Ilescriptlian Pioneer, "Ilacienda" 1- 171W PA 112 Low profile, interlocking high Trim Pieces w = 13" pressure extruded concrete roof tilt %" Mick equipped will% two nail hole and double roll ribs. For direct deck or battened PRODUC`rS MANDrACTURFD nail -on, mortar or adbesive set applications. I = varies PA 112 Accessory trim, concrete roof pieces w = varies for use at hips, rakes, ridges and valley varying tbickncss terminations. Manufactured for each Sltesifical ans file profile. HA2 F , n . u oaga Plans Examiner, Product Control Division "4 Product Control No.: 95-112&L7 TRADE NAMCS Or PRODUC`rS MANDrACTURFD 01-11FRS Test Product Product Dimensions Sltesifical ans Rcscditiw mmtufaclurse 930 relt N/A ASTM D 226 Saturated organic felt generic type 11 to lie used as a nailed anchor sheet. 943 Coated Base N/A ASTM D 2626 Saturated and coated generic Sheet organic base sbect for single or double ply undcrlaymctnt. Mineral Surface Cup N/A ASTM D 249 Mineral surfaced generic Sheet asphall roll roofing for use as a lop ply in a double ply undcrlaymcnt system. Lcnzingtcx -ZB 140 59"x 164' roll PA 104 Single ply, nail -on Lenzing Undcrlayment 22 Ibs/roll undcrlaymcnt. Performance, life. with current PCA Rainproof II 30" x 75' roll PA 104 Single ply, nail -on Protect -O -Wrap, Inc. 36" x 75'roll undcrlaymcnt with 2" with current PCA or self- adhering lop 60" x 75' roll edge. Ice and Winer Shield 36" x 75' roll PA 103 Self - adhering W.R. Grace Co. underlaym cnt for use wills current PCA as a top ply in a Iwo ply undcrlaymcnt systgnn with Approved 930 or 943 as the base payer. Mopping Asphalt N/A ASTM D 312 Asphalt for bonding a generic type 111 or IV mineral surface cap to a meth. nllached base sheet in a double ply undcrlaymcnt system. Flashing Ccment N/A ASTM D4586 Cut back, asphalt generic based, asbestos free. Fiber reinforccd, trowel grade "anent for repair and nashing applications. HA3 �- Y I �FD F • omllin Plans Examiner, Product Control Division "4 YET110•pAUE METROPOLITAN DADE COUNTY, FLORIDA w METRO-DADE FLAGLER BUILDING 1rRQA I1 rf Cotv'1'R0.L NQT1C_g OF ACCFISANU'- Pioneer Concrete Tile 1340 Southwest 341h Avenue Deerfield Beach. Fl. 33442 BUILDING CODE COMPLIANCE OFFICE SUITE 1603 METRO DADE FLAGLER BUILDING 140 WEST FLAGLER STREET MIAMI, FLORIDA 33130.1563 (305)375.2901 FAX (305) 375.2906 INTEnNET: mdce0l Ashndaw.nol PRODUCT CONTROL SECTION (305) 375.2902 FAX (305) 372-6339 Your application for Product Approval of: Ploncer Nall -On, Mortar Set orArlheslve Set "llaclenda" Roofleg Tile under Chapter 8 of the Mcimimman Dade County Code governing the use of Alternate Materials and 'Types of Construction, and completely described in lite plans, specifications and calculations as submitted by: Redland Technologies, Tire Center for Applied L•'nghtecrieg, lie., and professional Service Industries, lee.. has been recommended for acceptance by ilia Building Code Compliance Department to be used in Dade County, Florida under the specific conditions set forth on pages 2 through 17 and the standard conditions set forth on page 18. The approval shall not be valid after the expiration dale stated below. The Building Code Compliance Office reserves the right to secure this product or material at any (line for a jobsite or manufacturer's plant for quality control testing. If this'product or material fails to perform in the approved manner, the Building Code Compliance Office may revoke, modify or suspend ilia use of such product or material immediately. The applicant shall re- evaluate this product or material should any nntcndments to the South Florida Building Code be enacted affecting this product or material. The Building Code Compliance OMcc reserves the right to revoke this approval, if it is determined by the Building Code Compliance Officc that this product or material fails to meet the requirements o I to Smith Florida Building Code. The expense of such testing will be incurred by thZod"Itodriguez ctur. r. Acceptance No.: 95- 112L13_ Revises No. 95- 0330.02 Expires: Feb. 06, 1999 Product Control Supervisor 1111S.ISSIIF COYERS11EEL-5EE ADD1T1 CON This application for Product Approval has been reviewed by the Metropolitan Dade County Building Code Compliance Department and approved by ilia Building Code Committee to used in Dade County, Florida under the conditions set forth above. f Approved: -Fsb, —096 - uldes Danger, P.E. Director Building Code Compliance Dept. Metropolitan Dade County IIA ROOFING SYSTEhi APPROYAi. APAUGfint: Pioneer Concrete Tile 1340 Southwest 341h Avenue Deerfield Bcnch, FL 33442 nt orv: Prepared Roofing Suub- .ategorv: Low Profile Tile Type: Nail- on/Mortar Set/Adhesive Set Sub -Tyre: Concrete Product Control No.: 95-1128.12 Product Control No.: 95- 1128.12 Approval Dale: Jrchali.122ft_ Expiration Date: Feb. 06. 1999 System DescriPhan Pioneer Concrete Tile is a domestic manufacturer of concrete roof the with mm�ufacluring facilities stretching from the West Coast to the Southeast. All tile is manufactured from extruded concrete consisting of Portland Cement, plasticizer, iron and metallic oxides, and blended aggregates. This Product Control Approval relates to Pigncer s " Hacienda" tole profile. Refer to AlImpLlate Product Control AoApproypls for other the pi:Qr es. Pioneer tile is fabricated with a wide ridged and grooved sidelap providing a water channel at vertical joints. Tine ridged sidelaps provide a self-aligning function, creating a uniform appearance. All profiles have matching trim pieces used for rake hip, ridge hip, and valley terminations. Tile system accessories are also available to make up a complete tile system. Pioneer's "Hacienda" roof tile has been tested in compliance with the South Florida Building Code requirements for concrete, nail -on, mortar set and adhesive sal rile applications. The minimum roof slope for Pioneer's "Hacienda" nail -on, mortar set or adhesive set tiles shall be 2 ":12 ". See the "Profile Drawing" section in (his Approval for the "Hacienda" profile drawing. The Pioneer "I Incicnda" tile profile has been tested for both wind characteristics and static uplift performance, therefore, any consideration for installation shall be done as a 'Moment Based System'. Data for attachment calculations is noted in Tables I through 4 of this Approval. Contact: Joe Zanlbruski Customer Service Representative 1340 Southwest 34th Avenue Deerfield Beach, FL 33442 (800) 624 -4152 IIA1 Fr� _-� rik:iWo—asaf, Plans Examiner, Product Control Division -r DADE COUNTY BUILDING CODE COMPLIANCE OFFICE APPLICATION STANDARD PA 120 -95 01995 Metro -Dade Building Code Compliance Office SYSTEM #3: MODEL MORTAR OR ADHESIVE SET TILE SPECIFICATION INCLUDING APPROVED UNDERLAYMENT ASSEMBLIES Notes: This Application Standard is published as a compilation information relevant to data contained in Metro-Dade Product Control Approvals and its use with respect to consistent installation of Approved Roofing Components and Roof System Assemblies in compliance with South Florida Building Code requirements. The following specification was developed for use within the jurisdiction of the South Florida Building Code. The following table provides the contractor with the choices available for underlayment systems. These systems can only be used on pitches designated in the tables below. Roof Pitch' Application Choice of Underlayment Plastic or Compatible Cement at Nails Penetrating Underlayment 2":12" to 7 ":12" Direct Deck 1 No. 30 or No. 43 organic base nailed to deck, min. Required 74# organic cap sheet in type IV hot asphalt. (Two ply hot mopped underlayment) " 2 No. 30 or No. 43 organic base nailed to deck, Required Product Control Approved min. 3.5 mm, granular .surfaced SBS modified cap sheet bonded in type IV asphalt. " 3 No. 30 or No. 43 organic base nailed to deck, min. Required 74# organic cap sheet in Product Control Approved cold applied adhesive. " 4 No. 30 or No. 43 organic base nailed to deck, Required Product Control Approved, granular surfaced, self - adhered membrane bonded to base ply'. " 5 Product Control Approved underlayment or coating Refer to Approval component. JAN Applications for roof pitch > 7 ":12" require provisions set forth in Dade County Application standard NA i i9. Granular surfaced, SBS modified bitumen manufactuer shall have Product Control Approval for application as a tile underlayment over an organic base sheet. Membrane shall have Product Control Approval detailing the application. Page - I. PA 120 DIVISION 7 This guide specification covers Flat Profile, Low Profile and High Profile Roof Tile (See Dade County Protocol PA 112 for definition) using a minimum 3" tile headlap, or a designed limited headlap, on minimum 13/32" (reroofing) and t9 /32" (new construction) solid decking nailed in compliance with the requirements of The South Florida Building Code or poured in place concrete, or structural concrete plank. 07300 - Shingles and Roofing Tiles. 320 - Roofing Tiles. - Mortar -Set Tile Specification. This mortar or adhesive set tile specification is a model specification document developed to comply with the Code requirements of the South Florida Building Code. It is important to recognize that these recommendations are neither warranties explicit or implicit, nor representative of the only method by which a mortar or adhesive set tile system can be installed. This document has summarized a guide method of installation of mortar or adhesive set tiles which has been developed from actual trade practice; trade industry recommendations and in compliance with the requirements of the South Florida Building Code. Refer to Tile System Assembly Product Control Approval for any specific requirements. PART GENERAL 1.01 Related Work Specified Elsewhere A. Rough carpentry - Section 06100 B. Roof and deck insulation - Section 07220 C. Flashing and deck insulation - Section 07600 D. Roof accessories - Section 07700 E. Concrete deck - Section 03500 1.02 Quality Assurance A.. Products 1. Concrete Roof Tile -In compliance with Dade County Protocol PA 112. 2. Clay Roof Tile -In compliance with ASTM Standard C 1167. B. Requirements of regulatory agency 1. South Florida Building Code, Chapters 23 and 34 - 1994 Edition. 1.03 Submittals Page - 2 JAN PA 120 A. Samples - the type and color as selected. B. Manufacturer's literature - including product descriptions and recommended installation procedures. C. Tile System Assembly Product Control Approval. D. The underlayment manufacturer's Roofing Component Product Control Approval, indicating approval for use with the Tile System Assembly. E. Roofing Component Product Control Approval for any roofing component used in installation which is not listed in the Tile System Assembly Product Control Approval. 1.04 Product Delivery, Storage and Handling A. Distribute stacks -of the uniformly, not in concentrated loads. B. When stacking tile on roof top prior to installation, install battens under nose of tile stacks where required in the underlayment Product Control Approval. C. Care shall be taken to protect the underlayment during the tile loading and stacking process. 1.05 Job Conditions A. Do not install underlayment or tiles on wet deck surfaces. B. Insure other trades are aware of precautions required when loading and stacking of tile, and their responsibility for protection of tile during and upon loading and stacking completion. C. Any punctures or tears in the underlayment which occur during the loading and stacking of tile shall be immediately repaired with like materials. 1.06 Warranty A. Materials - manufacturer's limited warranty against defects in roof tile for years. (NOTE: Fill in appropriate number of years'.) PART H PRODUCTS ' This is provided for reference only. A warranty is not required under the provisions of the South Florida Building Code. Page - 3 JAN PA 120 r 2.01 Roof tile shall be manufactured by a manufacturer who has obtained Product Control Approval for use of the Tile System Assembly from the Metro -Dade Product Control Supervisor. A. Tile Manufacturer: B. Tile Type: C. Accessory Tile Type: D. Surface Finish: E. Color: F. Approximate Weight: G. Roof tile shall meet or exceed the minimum requirements set forth in Dade County Protocol PA 112 for concrete tile and ASTM Standard C 1167 for clay tile. 2.02 Asphalt Saturated Roofing Underlayments A. Organic, type II, commonly called No. 30 or 30 #, specifically ASTM Standard D 226, type II organic saturated felt used as an anchor sheet. B. Organic, type I, commonly called No. 43 or #43, specifically ASTM D 2626 asphalt coated base sheet used as an anchor sheet. C. Mineral surface roll roofing felt minimum 74# (commonly called 90 #), specifically ASTM D 249. D. Modified Bitumen single ply membrane in compliance with Dade County Protocol PA 104. E. Self adhered membrane in compliance with Dade County Protocol PA 103. F. Granular surface SBS modified bitumen membrane, minimum 3.5mm at the selvage edge, Product Control Approved for use in the South Florida Building Code jurisdiction. G. Product Control Approved underlayment or coating. 2.03 Membranes A. Organic - Asphalt impregnated cotton membrane, minimum 4" wide. B. Inorganic - Asphalt impregnated fiberglass membrane, minimum 4" wide. Page - 4 JAN PA 120 2.04 Fasteners A. Nails - corrosion resistant in compliance with Dade County Protocol PA 114 (i.e. hot dipped galvanized, aluminum, copper or stainless steel) of sufficient length to properly penetrate the deck a minimum 3/4" or through thickness of deck a minimum of 3/16 ", whichever is less. B. Screw Fasteners- corrosion resistant fasteners formed from, coated or plated steel; silicone bronze brass; aluminum; copper; or stainless steel of sufficient length to properly penetrate the deck a minimum of 3/4" or through a deck a minimum of 3/16 ", whichever is less. Screw fasteners shall be in compliance with Dade County corrosion resistance testing set forth in Appendix 'E' (DIN 50018) of Dade County Protocol PA 114. C. Storm clips and storm clip fasteners - refer to specific manufacturer's Product Control Approval. 2.05 Metal Flashing A. Flashing shall be minimum 26 ga., G -90 corrosion resistant metal - conforming to ASTM A 525 and A 90, or other metal or composition profile materials which are approved under the South Florida Building Code, or have received Product Control Approval. B. Lead sheet shall be minimum 2.5 lbs. per ft.Z. 2.06 Adhesive / Sealant A. Asphalt plastic roof cement - conforming to ASTM D 4586, type II, non - asbestos, non - running, heavy body material composed of asphalt and other mineral ingredients, and shall be approved for use in Dade County B. Cold process modified bitumen adhesive - conforming to ASTM D 3019, type II, and shall be approved for use in Dade County. C. Structural bonding adhesive - conforming to ASTM C 557 or ASTM D 3498. D. Asphalt - conforming to ASTM D 312, type III and IV. (Note slope requirements in Chapter 34 of the South Florida Building Code). E. All roof top sealants shall be in compliance with the minimum requirements set forth in Dade County Protocol PA 132. Page - S JAN PA 120 F. Tile adhesive shall be Approved for use in Dade County for limited repair and as a bonding agent for 'nail -on systems' in strict compliance with the Tile System Assembly Product Control Approval. Tile adhesive shall be in compliance with the minimum physical property criteria set forth in Dade County Protocol PA 123(A). 2.07 Mortar A. Mortar mix shall have a Roofing Component Product Control Approval for use with mortar set Tile System Assembly and shall be in compliance with Dade County Protocol PA 123. B. Mortar shall be premixed and bagged as specified in the mortar manufacturer's Product Control Approval. 2.08 Foam Tile Adhesive A. Foam Tile Adhesive shall have a Roofing Component Product Control Approval for use with the specified Tile System Assembly and shall be in compliance with Dade County Protocol PA 134. B. Foam Tile Adhesive shall be installed with the application equipment detailed in the Product Control Approval. C. Foam Tile Adhesive Applicators shall be certified by the manufacturer and shall hold proof of certification. 2.09 Eave Closure A. Prefabricated EPDM synthetic rubber conforming to ASTM C 1056. . B. Prefabricated metal eave closure. C. Prefabricated concrete or clay eave closure. D. Mortar - color optional. 2.10 Coating A. Paint - color coordinated paint for painting tile, flashing and/or accessories, as required. B. Acrylic sealer - for point -up mortar (optional). C. Tint Seal - color coordinated sealer for staining tile or accessories as required. Page - 6 JAN PA 120 2.11 Lumber A. Sheathing - material shall conform to APA rated sheathing. 1. New Construction - 40/20 19/32" APA rated sheathing . 2. Re- roofing - 32/16 15/32' APA rated sheathing. 2.12 Concrete A. Poured structural concrete or structural concrete plank in compliance with the minimum requirements set forth in Chapter 25 of the South Florida Building Code. PART III EXECUTION JAN 3.01 Inspection A. Verify that surfaces to receive underlayment and roof tile are uniform, smooth, clean, and dry. B. Fill any voids with compatible material. C. Do not start roofing, installation in new construction applications until the Building Official has inspected and approved the decking installation 3.02 Underlayment Application - choose one of the following Note: Sidelap is defined as the machine direction overlap; endlap is defined as the cross machine overlap. A. Hot Mop 30/90 ( #1 in Table) A two ply roof application commonly called a 'Hot Mop' system. The roof cover is terminated at approved metal flashings. A No. 30 ASTM D 226, type II asphalt saturated anchor sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12" grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be a minimum of 6 ". Over properly installed anchor sheet, apply one layer of ASTM D 249 mineral surfaced cap sheet in a full mopping of ASTM D 312, type IV asphalt applied within the EVT range. Asphalt shall be applied uniformly so that the felts do not touch. Side laps shall be a minimum of 2 ", and end laps shall be a minimum of 6 ", and back - nailed 12" o.c. with approved roofing nails. Anchor sheet and cap sheet shall be applied parallel to the roof slope unless otherwise approved for Page - 7 PA 120 application perpendicular to the slope by the two ply manufacturer and specified as such in published application instructions or in a Product Control Approval. B. Hot Mop 43/90 ( #1 in Table) A two ply roof application commonly called a 'Hot Mop' system. The roof cover is terminated at approved metal flashings. A No. 43 ASTM D 2626, type II anchor sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12" grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be a minimum of 6 ". Over properly installed anchor sheet, apply one layer of ASTM D 249 mineral surfaced cap sheet in a full mopping of ASTM D 312, type IV asphalt applied within the EVT range. Asphalt shall be applied uniformly so that the felts do not touch. Side laps shall be a minimum of 2 ", and end laps shall be a minimum of 6 ", and back - nailed 12 "o.c with approved roofing nails. Anchor sheet and cap sheet shall be applied parallel to the roof slope unless otherwise approved for application perpendicular to the slope by the two ply manufacturer and specified as such in published application instructions or in a Product Control Approval. C. Hot Mop 30 /'Modified Bitumen Cgp' ( #2 in Table) A two ply roof application commonly called a 'Hot Mop' system. The roof cover is terminated at approved metal flashings. A No. 30 ASTM D 226, type H asphalt saturated anchor sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12 grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be a minimum of 6 ". Over properly installed anchor sheet, apply one layer of Product Control Approved, minimum 3.5mm, SBS cap sheet in a full mopping of ASTM D 312, type IV asphalt applied within the EVT range. Asphalt shall be applied uniformly so that the felts do not touch. Side laps shall be a minimum of 2 ", and end laps shall be 6 ", and back - nailed 12 "o.c. with approved roofing nails. Anchor sheet and cap sheet shall be applied parallel to the roof slope unless otherwise approved for application perpendicular to the slope by the two ply manufacturer and specified as such in published application. instructions or in a Product Control Approval. D. Hot Mop 43 /'Modified Bitumen Cap' ( #2 in Table) A two ply roof application commonly called a 'Hot Mop' system. The roof cover is terminated at approved metal flashings. A No. 43 ASTM D 2626, type II anchor sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12" grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be a minimum of 6 ". Over properly installed anchor sheet, apply one layer of Product Control Approved, minimum 3.5mm, SBS cap sheet in a full mopping of ASTM D 312, type IV Page - 8 JAI PA 120 JAN asphalt applied within the EVT range. Asphalt shall be applied uniformly so that the felts do not touch. Side laps shall be a minimum of 2 ", and end laps shall be a minimum of 6 ", and back - nailed 12 "o.c. with approved roofing nails. Anchor sheet and cap sheet shall be applied parallel to the roof slope unless otherwise approved for application perpendicular to the slope by the two ply manufacturer and specified as such in published application instructions or in a Product Control Approval. E. Cold Process 30/90 ( #3 in Table) A two ply roof application commonly called a 'Cold Process' system. The roof cover is terminated at approved metal flashings. A No. 30 ASTM D 226, type II anchor sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12" grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be a minimum of 6 ". Over properly installed anchor sheet, apply one layer of ASTM D 249 mineral surfaced cap sheet in a continuous layer of Dade County Approved, ASTM D 3019, type III cold process adhesive applied at the rate of 1.5 gal/sq. or such other rate of application detailed in the Cold Adhesive Product Control Approval. Adhesive shall be applied uniformly, with a notched squeegee or knotted brush, so that felts do not touch. Side laps shall be a minimum of 2 ", and end laps shall be a minimum of 6 ", and back - nailed 12 "o.c. with approved roofing nails. Anchor sheet and cap sheet shall be applied parallel to the roof slope unless otherwise approved for application perpendicular to the slope by the two ply manufacturer and specified as such in published application instructions or in a Product Control Approval. F. Cold Process 43/90 (# 4 in Table) A two ply roof application commonly called a 'Cold Process' system. The roof cover is terminated at approved metal flashings. A No. 43 ASTM D 2626, type II anchor sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12" grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be a minimum of 6 ". Over properly installed anchor sheet, apply one layer of ASTM D 249 mineral surfaced cap sheet in a continuous layer of Dade County Approved, ASTM D 3019, type III cold process adhesive applied at the rate of 1.5 gal/sq. Adhesive shall be applied uniformly with a squeegee or knotted brush, so that felts do not touch. Side laps shall be a minimum of 2 ", and end laps shall be a minimum of 6 ", and back - nailed 12 "o.c. with approved roofing nails. Anchor sheet and cap sheet shall be applied parallel to the roof slope unless otherwise approved for application perpendicular to the slope by the two ply manufacturer and specified as such in published application instructions or in a Product Control Approval. G. Anchor Sheet / Granular Surfaced Self- Adhered Underlayment (#4 in Table) Page - 9 PA 120 A two ply roof application utilizing a Product Control Approved, self - adhered single ply underlayment, in compliance with Dade County Protocol PA 103. The roof cover is terminated at approved metal fleshings. Any approved No. 30 or No. 43 sheet shall be mechanically attached to the wood deck with approved nails and tin caps spaced in a 12" grid staggered in two rows in the field, and 6" o.c. at the laps. Extend anchor sheet a minimum of 4" up vertical surfaces. Anchor sheet side laps shall be a minimum of 2" and end laps shall be 6 ". Over properly installed anchor sheet, apply one layer of any approved, self - adhered underlayment in compliance with the Roofing Component Product Control Approval. Anchor sheet shall be installed perpendicular to the roof slope, mineral surfaced top ply shall be applied parallel to the roof slope unless otherwise approved in the Product Control Approval. H. Altemative/Product Control Approved Underlayment or Coating ( #5 in Table) Any product consisting of one or more water shedding layers applied to a sloped wood or concrete roof deck prior to the application of a Prepared Roof Covering having been tested in compliance with Product Control Approval guidelines. The primary purpose of an underlayment is defined as a water shedding layer to function in combination with a Prepared Roof Covering. The alternate product shall be tested in compliance with Dade County Protocol PA 100 and any other test requirement directed by the Dade County Product Control Supervisor for Approval. 3.03 Drip Edge Metal A. Edge metal shall be installed over the anchor sheet at all perimeters in a minimum 3 /16" bead of continuous ASTM D 4586 , type 11 flashing cement installed at the drip edge bend, and fastened 4" o.c. with 912 ga. x .11/4" annular ring shank, corrosion resistant roof nails placed not greater than 1" from the outside edge of the deck flange. All bonding surfaces shall be fully primed with ASTM D 41 primer. All joints shall be lapped an minimum of 4" (5" at corners) in a maximum 1 /g" bed of flashing cement. The cap sheet shall be bonded to the metal with ASTM D 312, type IV asphalt. B. Continue from eave up rake/gable in same manner, insuring water shedding capabilities of all metal laps. C. CARE SHALL BE TAKEN NOT TO COMBINE HOT ASPHALT WITH FLASHING CEMENT. 3.04 Valley A. Pre - formed or rolled valley metal shall have a finished width not less than 16 "; shall be fully primed with ASTM D 41 primer; and, shall be fastened 18" o.c. with corrosion resistant, 12 ga. x 11/4" annular ring shank nails with fastener rows Page - 10 JAN PA 120 located not greater than 1" from the outside edge of the valley metal. The valley metal shall be installed: 1. over the anchor or cap sheet and an additional 36" wide ply of granule surfaced roll roofing centered on, and running the length of the valley bonded to the anchor sheet in a full mopping of ASTM D 312, type IV asphalt or a maximum, `/$" continuous bed of cold adhesive; or, B. All valley metal overlaps shall be a minimum of 4" and shall be bonded with hot asphalt or flashing cement. C. Strip in the rolled valley metal: 1. If Over Anchor Sheet - Lap the cap sheet a minimum of 4" or a maximum of 6" over the edge of the valley metal and bond to a primed surface with ASTM D 312, type IV asphalt or approved cold adhesive, or 2. If Over Cap Sheet - The valley metal and cap sheet shall be joined with a minimum 8" wide strip of mineral surfaced roll roofing centered at the joint and bonded with ASTM D 312, type IV asphalt or approved cold adhesive. 3.05 Flashing and Counterflashings at Wall Abutments A. Install "L" metal, a minimum 4" on the roof deck in all applications, 5" on the vertical in reroof application and, 8" on the vertical leg in new construction. flush to base of walls. Flashing shall be installed over the base underlayment and nailed 6" o.c. within 1" of metal edges. Lap joints 4" and apply approved flashing cement between laps. Start at lower portion and work up the roof incline. B. Seal along top edge of vertical flange, covering all nail penetrations with approved flashing cement and asphalt saturated cotton or fiberglass reinforcement membrane where required. C. When installing counterflashing, lap top flange of base flashing a minimum of 3 ". Nail metal within I" of metal edge not less than 6" o. c. or set into reglets (secured properly) and thoroughly caulked Lap joints a minimum of 3" and apply approved flashing cement between laps. D. All head flashing shall be installed over top of the cap sheet (top ply). Insure the deck flange conforms to the pitch of the roof and extends a minimum of 4" onto the deck. Seal along edge with flashing cement and fabric. E. Install apron flashing a minimum of 4" on to the tile surface. Nail vertical flange of flashing V from the metal edge. Lap metal 6" and seal laps with approved flashing cement. Seal the vertical as detailed in W. Page - 11 JAN PA 120 3.06 Standard Curb Mounted Skylights, Chimneys, Etc. A. Install in compliance with regular flashing installation procedures. See Section 3.05 -A above. Note: For self curbing or prefabricated skylights refer to skylight manufacturer's installation instructions and the Roofing Component Product Control ApprovaL The Product Control Approval shall take precedence. 3.07 Pipes, Turbines, Vents. Etc. A. Apply approved flashing cement around base of protrusion and on the bottom side of metal flanges sealing unit base flashing to deck. B. Secure the penetration in strict compliance with the Product Control Approval Installation instructions. Note: Each tile manufacturer requires specialty accessories. Their accessories shall be installed in compliance with the Tile System Assembly Product Control ApprovaL 3.08 Granular Surface Top Ply (commonly called cap sheet) A. All cap sheet shall be installed in compliance with the cap sheet manufacturers published application details or the Product Control Approval. (The Product Control Approval shall take precedence). Apply in hot asphalt or approved cold adhesive between anchor sheet and cap sheet so that no felt touches felt. Back nail using approved roofing nails spaced at a maximum of 12" o.c. at side laps and 6" o.c. at the end laps, approximately 1" from edge of the top ply. B. Apply each succeeding course in same manner. C. Overlap hip and ridge a minimum of 6 ". D. • Insure weave pattern in valley where valley metal is placed over the cap sheet or trim a maximum 3" past nail penetrations. When using pre - formed valley metal, seal edge of the cap sheet with approved flashing cement and asphalt saturated cotton or fiberglass reinforced membrane. E. Prime all metal flashings and roof protrusions to insure a weatherproof application. F. Trim any felt overhanging at eave and gable. G. Cut any fishmouths and seal with approved flashing cement and reinforcing membrane. Page - 12 JAN PA 120 't > JAN H. Apply approved flashing cement or hot asphalt along edge of felt wherever it meets wall bases. I. If top is a Product Control Approved waterproofing layer, the installation 3.08 Top -ply (commonly called cap sheet) 3.09 Tile Installation Methods Note: Installation instructions set forth in the Tile System Assembly Product Control Approval shall take precedence. A. Layout - horizontal 1. Chalk horizontal lines beginning one tile length from eave less desired overhang. Overhang shall be W to 2 ", depending on tile type, use of gutter, or other functional requirements. 2. Chalk succeeding lines for a minimum 3" headlap unless restricted by product design and approved in the Product Control Approval.. 3. Increase headlap when necessary for equal course spacing, or as 'needed for unusual application conditions. B. Layout - vertical - choose one of the following 1. Staggered/cross bond tile installation a. Gable end i. Chalk vertical lines one full tile and one half tile width plus 1" to 2" from starting gable to accommodate rake tile. M, i Chalk verticals lines one full tile and one half tile width plus 1/4" from starting gable to accommodate flush finish. ii. Chalk additional lines, if necessary, to maintain alignment. b. Hip roof i. Chalk vertical line 90 degrees from eave line. ii. Chalk second line parallel to first to accommodate staggered/cross bonded tile. Page - 13 PA 120 JA-ti iii. Chalk additional lines, if necessary, to maintain alignment. W 1. Straight bond tile installation (not recommended for flat tile) a. Gable end i. Chalk vertical line one full the width plus 1" to 2" from starting gable. ii. Chalk additional lines, if necessary, to maintain alignment. b. Hip roof i. Chalk vertical lines, if necessary, to maintain alignment. C. Tile Installation 1. Stack tile to facilitate installation and minimize tile movement. Tile stacks shall not be greater than ten high. Battens shall be placed under the nose of tile stacks where required by the underlayment Product Control Approval. 2. Eave treatment - choose one of the following options a. Prefabricated Rubber Eave Closure - install closure strip along eave in compliance with the Tile System Assembly Product Control Approval. M, a. Metal Eave Closure - install closure strip along eave in compliance with the Tile System Assembly Product Control Approval. RO a. Raised Fascia/Wood Starter Strip- when using a 1'/2" raised fascia, a 2" x 2" wood starter strip must be installed behind fascia. i. Install fascia board approximately 3/4" above roof deck or a 1" x 2" wood starter strip at roof edge. ii. Install S" tapered cant strip at eave behind fascia and/or starter strip to support metal flashing when using drip edge. Tapered cant strip is optional when using anti - ponding metal. Page - 14 PA 120 iii. Install a minimum 8" wide anti - ponding metal flashing of to insure positive drainage over fascia/starter strip. Nail top edge of flange onto roof. iv. Apply underlayment as per Section 3.02 W a. Mortar Application for Eave Closure i Apply mortar along the eave edge, applying enough mortar to fill all voids in the profile to securely close the eave. ii Point and smooth finish flush to eave line. iii Apply minimum 3/8" weephole flush with the roof deck at spacing of not less than one weephole per tile. 3.10 Flat, Low, and High Profile Tile Note: Mortar set tiles shall have the first three courses of tile nailed with not less than one nail per tile. As an alternate the first three courses shall be applied in mortar over a single layer of minimum 12 ga. wire mesh with square openings of not less than 3/8" which is mechanically attached to the deck with not less than one roofmg nail every square foot. For pitches from 6 ":12" to 7':12" every third tile of every fifth course, beginning at the eighth course shall be nailed. A. Starting at lower left corner (facing down roof) install first course of tile. Make certain all tile overhangs drip edge evenly along entire first course. B. Bond and/or secure field, perimeter and corner tile in compliance with the Tile System Assembly Product Control Approval and the mortar or tile adhesive Product Control Approval. C. Cutibreak tile for proper staggering of tile courses when using the staggered/cross bond method of installation. D. Set tile in stepped course fashion or in a horizontal and/or vertical fashion when utilizing straight bond method. E. Lay succeeding courses of field the in same manner. F. If the Tile System Assembly has been tested for wind characteristics in compliance with Dade County Protocol PA 108, the the shall be attached to resist the aerodynamic moment determined in compliance with the attachment calculations set forth in Dade County Protocol PA 115 or PA 127. (See Dade County Page - 15 JAN _ PA 120 Protocol PA 127 for limitations of use.) Confirmation of bonding performance shall be determined by the Building. Official in compliance with Dade County Protocol PA 106 not less than 30 days after project completion. Foam tile adhesive application may be tested not less than seven days after project completion. G. If the Tile System Assembly has not been tested for wind characteristics in compliance with Dade County Protocol PA 108, the tile shall be attached to resist the required uplift force determined in compliance with the attachment calculations set forth in Dade County Protocol PA 115 or PA 127. (See Dade County Protocol PA 127 for limitations of use.) Confirmation of bonding performance shall be determined by the Building Official in compliance with Dade County Protocol PA 106 not less than 30 days after project completion. Foam tile adhesive application may be tested not less than seven days after project completion. H. Cutibreak field tile to form straight edge at center of hip /ridge. I. Mortar or Adhesive Application - One -Piece Flat, Low or High Profile Tile 1. Set tile in a bed of Approved mortar or adhesive, forming a mortar or foam patty as detailed in the in the mortar or adheisve manufactuer's Product Control Approval for the specific tile profile placing mortar or adhesive vertically under pan closest to underlock of previously installed tile. For flat tile, place mortar or adhesive adjacent to underlock of previously installed tile. Mortar or adhesive should be placed from head of tile in previous course to head of tile being set. Do not apply mortar or adhesive under headlug of tile, or onto the underlock of adjacent tile which may create a tilted or cocked tile. Mortar or adhesive shall be placed in general compliance with the detail drawings attached to the mortar or adhesive manufacturer's Roofing Component Product Control Approval. 2. Use half starter /finisher tile when provided or cut/break tile for proper staggering of tile courses when using the staggered/cross bond method of installation. 3. Set tile in stepped course fashion or in a horizontal and / vertical fashion when utilizing straight bond method. 4. Lay succeeding courses of field tile in same manner. Bed of mortar or adhesive should make contact with head of the lower course of tile and underside of tile being set. J. Mortar or Adhesive Application- Two -Piece Barrel Tile Page - 16 JAN PA 120 4 JAN 1. Apply sufficient mortar or adhesive to form a mortar or foam patty as detailed in the mortar or adheive manufacturer's Product Control Approval for two -piece barrel tile vertically over chalk line and under center of each pan with narrow end facing down roof. 2. Place bed of mortar or adhesive along inside edges of pans and set covers with wide end facing down roof. 3. Point mortar or adhesive to next acceptable straight -edge finish insuring good strong contact along edges. 4. Lay succeeding courses of field tile in same manner. Bed of mortar or adhesive should make contact with head of lower course of tile and underside of tile being set. K. Adhesive Application 1. Apply Approved adhesive material to the underlayment and/or tile in strict compliance with the adhesive manufacturer's Product Control Approval. 2. Placement of adhesive shall be in compliance with the detail drawings attached to the adhesive manufactuer's Product Control Approval. 3.11 Valleys Note: It is not recommended to install trim tile in valleys. It may be necessary to remove the lugs from the field tile at walls and valley flashings for proper positioning of cut field tiles. A. Standard Roll Valley 1. Closed Valley - Miter tile to meet at center of valley. 2. Open Valley - Chalk a line minimum 2" on both sides valley center. Place bed of color coordinated mortar along outside edge of chalk lines. Miter tile to form straight border and point to match tile surface. W A. Pre - formed Metal Without Returns 1. Closed Valley - Miter tile to form straight border on either side of water diverter. Page - 17 PA 120 IAN 2. Open Valley - Miter tile to form straight border on either side of two water diverters. 3.12 Hip Starter - choose one of the following A. Prefabricated hip starter 1. Miter tile as hip starter to match eave lines. A. Use standard hip tiles as starter. 3.13 Hip and Ridge Installation- Choose one of the following A. Set hip and ridge tile in a continuous bed of color coordinated mortar, lapping tile minimum V. Insure bed of mortar does not protrude in center of hip or ridge junction. Approximately 1" of field tile shall extend beyond bed of mortar. Point mortar and finish to match tile surface. Insure mortar is in continuous contact with lip and ridge tile elements. M, A. Mechanically fasten hip and ridge tiles to nailer board. (See section 3.14). B. A ridge vent or venting within 18" of ridge is required on- all tile applications. Ridge vents shall have Roofing Component Product Control Approval. 3.14 Nailer Boards - as required by some Tile System Assemblies A. Install salt pressure treated nailer boards secured directly to trusses. B. Install self adhered membrane over nailer board and seal to tile surface. Care should be taken to ensure no self adhered membrane is exposed to sunlight. C Fasten with nails or screws of sufficient length to penetrate minimum of 3/4" into each truss. D. Use approved adhesive or clips at overlaps. 3.15 Rake/Gable Tile A. Rake /Gable Tile Page - 18 PA 120 1. Install first rake tile to exposed length of first course of field tile with factory finish of rake tile towards the eave. 2. Nail rake tile with minimum two approved annular ring shank nails of sufficient length to penetrate the framing a minimum of 3/4 ", whichever is more restrictive. 3. Abut each succeeding rake tile to the nose of the field tile above and maintain a constant headlap. B. Metal Finish 1. Install prefabricated gable metal with 1" water return. 2. Fasten by clipping 24" on center. Note: Rake tile application at finishing end may need special consideration to provide proper drainage, i.e. flashing or sealant may be needed. Refer to Tile System Assembly Product Control Approval. 3.16 Wall Abutments A. Cut tile to fit approximately 1/2" to base of walls. Point -up mortar not recommended. Note: It may be necessary to remove the lugs from the field tile at wall flashing for proper positioning of cut field tiles. 3.17 Plumbing Stacks A. Metal Finish 1. Cut file to fit close to plumbing stack. Over plumbing stack install a lead pipe flashing. Pipe flashing shall have a minimum 18" x 18" base. Flashing base shall be set in approved adhesive and form fitted to match the tile profile. Install pipe flashing in such a manner to allow shedding of water. The ridge edge of the pipe flashing base shall be installed under the nose of the tile above. Note: Rigid corrosion resistant metal may be substituted for lead on flat tile installations. 3.18 Coatings - optional A. Acrylic sealer may be applied to exposed mortar as in accordance with the Tile System Assembly as outlined in the Product Control Approval. B. Color coordinated paint may be applied to all metal flashings. Page - 19 JAN PA 120 JAN 3.19 Tile Replacement A. Damaged Tile 1. Break out and replace damaged roof tile. Do not disturb underlayment Repair underlayment if necessary. 2. Apply minimum of 3/8" x 2" bead of Approved adhesive on tile in course below replacement tile. 3. Immediately set replacement tile in position assuring proper contact. B. Small Valley and Hip Cuts 1. Elevate nose end of tile in course above small cut tile, apply a minimum of 3/$" x 2" bead of approved adhesive at head of cut tile. 2. Immediately set tile in course above in position which assures proper contact. Note: For roof pitches > 7":12" , mechanical fastening is required. Refer to Tile System Assembly Product Control Approval and Dade County Application Standard PA 119. 3.20 Clean-Up A. Remove all broken tile, debris and excess tile from roof. 3.21 Miscellaneous recommendations A. Instructions shall be given to all parties involved cautioning against traffic of any kind allowed on finished roof. Damage to roof tiles and/or sub -roof may result. Refer to Tile System Assembly Product Control Approval for proper procedures for traffic on roof tile. - END OF APPLICATION STANDARD - Page - 20 PA 120 � \'W 999 Northwest 53rd. Court • Ft. Lauderdale, Florida 33309 • (954) 772 -3446 LATRE ROOFING & SHEET METAL R., INC. arch 26 —. 1998 Miami Shores Village Building Department Miami Shores Village, FL Re: Deirer residence reroof 1420 NE 102 Street Miami Shores Village, FL Permit No. 42581 Dear Sirs, We have installed the valley metal between the #30 felt and the #90 felt on subject project. We feel this application is much higher quality than installing the metal flashing on top of the mopped in place #90 for the following reasons: 1. The metal has no exposure to the outside elements as it is fully laminated between the plies. 2. No nails are penetrating the finished plies of the underlayment as would be if the metal flashing was installed on top of the #90. 3. This application does not create the backward laps in plies which would occur when stripping in the sides of any metal flashing installed on top of the #90. 4. Our application is in line with other industry standards such as the FRSA/ NTRMA and the NRCA. The only industry standards we have found which show metal flashings installed on top of underlayments are for single layer, unsealed underlayments; not two ply, fully mopped systems as the #30/ #90 system we have used here. Please be advised that Latite Roofing and Sheet Metal Company holds harmless the City of Miami Shores Village from any and all problems which may arise in the future which are directly and specifically attributable to the installation of the valley metal flashing used on this project. Respectfully submitted James D. Engs l r State CertifiecYKRo g Contractor # CCC 025467 '�Y � tA�, M!M! E. ALLBRITTON OCOMMiSSION # CC489020 ES AUG. 16,1999 X fip�pA Page 1 of 1