RF-18-1811Miami Shores Village
10050 N.E. 2nd Avenue NW
Miami Shores, FL 33138-0000
Phone: (305)795-2204
Project Address
Permit
Issue Date: 7/3/2018
Permit NO. F-7-18-1' 811
Permit Type: Roof
Work Classification: Tile
Permit Status: APPROVED
Expiration: 12/30/2018
Parcel Number
Applicant
30 NW 100 Terrace
Miami Shores, FL 33138-
1131010180340
Block: Lot:
JEAN LEE
Owner Information
Address
Phone
CeII
JEAN LEE
30 NW 100 TERR
MIAMI SHORES FL 33150-1208
Contractor(s)
T&S ROOFING SYSTEMS INC.
Phone
305/265-2654
CeII Phone
Type of Work: Re Roof
Additional Info: RE -ROOF TILE
Classification: Residential
Scanning: 3
Fees Due
Bond Type - Contractors Bond
CCF
DBPR Fee
DCA Fee
Education Surcharge
Permit Fee - New Roof
Scanning Fee
Technology Fee
Total:
Amount
$500.00
$7.80
$4.13
$2.75
$2.60
$275.00
$9.00
$10.40
$811.68
Pay Date Pay Type
Invoice # RF-7-18-68123
07/03/2018 Check #: 34802
Bond #: 3816
$ 811.68 $ 0.00
Amt Paid Amt Due
1.1
Available Inspections:
Inspection Type:
Up Lift Report
Tin Cap
Final Roof
Tile In Progress
Renailing Affidavit
Review Roof
Cap Sheet
In consideration of the issuance to me of this permit, I agree to perform the work covered hereunder in compliance with all ordinances and regulations
pertaining thereto and in strict conformity with the plans, drawings, statements or specifications submitted to the proper authorities of Miami Shores Village. In
accepting this permit I assume responsibility for all work done by either myself, my agent, servants, or employes. I understand that separate permits are
required for ELECTRICAL, PLUMBING, MECHANICAL, WINDOWS, DOORS, ROOFING and SWIMMING POOL work.
OWNERS AFFIDAVIT: I certify that all the foregoin inf ation is accurate and that all work will be done in compliance with all applicable laws regulating
construction and zoning. Futhermore, I authorize the boon med contractor to do the work stated.
Authorized Signature: Owner / Applicant / Contractor / Agent
July 03, 2018
Date
Building Department Copy
July 03, 2018
1
ACB2 Engineering Inc.
Testing & Engineering Services
Certificate of Authorization # 8131
Tel: 954-245-8976 Fax: 954-301-7776
5230 NE 18TH Avenue
Fort Lauderdale, FL 33334
Roof Tile Uplift Test Report
Attention:
Miami Shores Village, Building Division,
10050 NE 2nd Avenue, Miami Shores, FL 33138
Client: T & S Roofing Systems
Test Date: 11/09/2018
Permit # RF-7-18-1811
Property Address:
30 NW 100 Terrace ,Miami Shores, FL
Roof Pitch:
Type of Tile:
Roof Area:
3 in 12
Ceramica Verea Roof Tile
17.00 squares
Tile Attachment Method:
Two Component Polyurethane Foam Adhesive -Poly Pro H 160
Field Instrument :
IMADA Force Gauge 0-100 Serial number: 243454
Test Location
Total Number of Tests
Perimeter Area: (T1-T7) 7.00 sq.
Field Area: (T8-T17) 10.00 sq.
No. of Corner (T18-T31) 14
Ridge Areas: (T32-T42) 110 pcs.
7
10
14
11
Important:
Field Uplift Pull Test Test results
As per FBC 2017
As per FBC 2017
As per FBC 2017
As per FBC 2017
Passed
Passed
Passed
Passed
These laboratory results can change due to future weather impacts and/or unavoidable roof
traffic. Therefore, this report represents the TAS 106 results at the time of the test.
Please see attached a Roof Sketch for this project.
Cordi
ACB
eering Inc. (NOA 09-1005.01)
A "o .'o Acevedo, PE
Reg. No: 36466
ACB2 Engineering Inc.
Engineering and Laboratory Services
5230 NE 18th Avenue
Fort Lauderdale, Florida 33334
Phone: (954) 245-8976 Fax: (954) 301-7776
To
T(
T5-
7-3
TSB
Tio
T
tt tiJ.23
3S
r
3`r
9
BUILDING
PERMIT APPLICATION
BUILDING ❑ ELECTRIC
El PLUMBING ❑ MECHANICAL ❑PUBLIC WORKS
JOB ADDRESS: ' ()0 N J 100 i
e(
City: Miami Shores 0 County:
Folio/Parcel#: I \" T\O \ — 0 ` - 3� 0
Occupancy Type: Load:
Master Permit N
RECEIVED
JU 03208
BY.
FBC 20(9-0
oZ"���j —I8\\
Sub Permit No.
❑ REVISION ❑ EXTENSION ❑ RENEWAL
❑ CHANGE OF ❑ CANCELLATION ❑ SHOP
CONTRACTOR DRAWINGS
Miami Dade Zip:
Is the Building Historically Designated: Yes NO
Construction Type: Flood Zone: BFE: FFE:
OWNER: Name (Fee Simple Titleholder):
Address:
CONTRACTOR: Company Name:
ii/
Address: (yfl f V.W
City: /4 / / State:
Qualifier Nam : tab 5 Ve'CiC
State Certification or Registration #:7e; 37 Certificate of Competency #:
10 Ivy)
City: t \Cf 1M 5\ncf e S
Tenant/Lessee Name: Phone#:
Miami Shores Village
Building Department
10050 N.E.2nd Avenue, Miami Shores, Florida 33138
Tel: (305) 795-2204 Fax: (305) 756-8972
INSPECTION LINE PHONE NUMBER: (305) 762-4949
ROOFING
�G4N ez
\G ' ter
3er 7Y-
Phone#: i
Zip: 3-51;\-- It
State:
Email:
fi J
Phone#: r- Z6E- Zf'Cl7
Zip:
`-"5'3/ (12
Phone#:
DESIGNER: Architect/Engineer: Phone#:
Address: City: State: Zip:
t
Value of Work for this Permit: $ / Z j 7 SC Square/Linear Footage of Work: 17tI�
Type of Work: ❑ Addition ❑ Alteration
Description of Work: /J�,ZZ2/ rile
❑ New
❑ Repair/Replace
❑ Demolition
Specify color of color thru tile: 'Fero ca )fit?
Submittal Fee $ Permit Fee $ a•s • Q CCF $ / / CO/CC $
y
Scanning Fee $ Radon Fee $ -- • S DBPR $ ' ( Notary $
Technology Fee $ Training/Education Fee $ Double Fee $
Structural Reviews $ Bond $ � • C5ZZ.
TOTAL FEE NOW DUE$ .3(k • P.
(Revised02/24/2014)
8H -69
identification and who did take an oath.
NOTARY PUBLIC:
Sign: /
Print:f
Seal:
*****************
DANIEI_ PE"
Notary Public - Et -
Commission
My Comm. Expires . ,.2020
Bonding Company's Name (if applicable)
Bonding Company's Address
City State Zip
Mortgage Lender's Name (if applicable)
Mortgage Lender's Address
City State Zip
Application is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has
commenced prior to the issuance of a permit and that all work will be performed to meet the standards of all laws regulating
construction in this jurisdiction. I understand that a separate permit must be secured for ELECTRIC, PLUMBING, SIGNS, POOLS,
FURNACES, BOILERS, HEATERS, TANKS, AIR CONDITIONERS, ETC
OWNER'S AFFIDAVIT: I certify that all the foregoing information is accurate and that all work will be done in compliance with all
applicable laws regulating construction and zoning.
"WARNING TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY
RESULT IN YOUR PAYING TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. IF YOU INTEND
TO OBTAIN FINANCING, CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING
YOUR NOTICE OF COMMENCEMENT."
Notice to Applicant: As a condition to the issuance of a building permit with an estimated value exceeding $2500, the applicant must
promise in good faith that a copy of the notice of commencement and construction lien law brochure will be delivered to the person
whose property is subject to attachment. Also, a certified copy of the recorded notice of commencement must be posted at the job site
for the first inspection which occurs seven (7) days after the building permit is issued. In the absence of such posted notice, the
inspection will not be approved and a reinspection fee will be charged.
Signature Rr / Signature
OWN ,` or AGENT
The foregoing instrument was acknowledged before me this
CONTRACTOR
The foregoing 1 strument was acknowledged before me this
day of \-V\ , 20 (/ , by .7_ day of LA. , 20 (x , by
e_G(L ee , , who is personally known LLB S) `"LC , who i.?..Rerconally knnwn-to
me who has produced as me or who has produced as
identification and who did take an oath.
NOTARY PUBLIC:
Sign:
Print:
Seal:
DANIEL PEREL
Notary Public - State.,` FI. ri0a
Commission =G(44,7 9
My Comm. Expires N 'v 2020
********************** * * * * *******************************
APPROVED BY Plans Examiner
Zoning
(Revised02/24/2014)
Structural Review
Clerk
Property Search Application - Miami -Dade County
Page 1 of 1
Summary Report
Property Information
Folio:
11-3101-018-0340
Property Address:
30 NW 100 TER
Miami Shores, FL 33150-1208
Owner
GEOFFREY LEE &W JEAN C
Mailing Address
30 NW 100 TERR
MIAMI SHORES, FL 33150-1208
PA Primary Zone
0800 SGL FAMILY - 1701-1900 SQ
Primary Land Use
0101 RESIDENTIAL - SINGLE
FAMILY : 1 UNIT
i
Beds / Baths / Half
2/1/0
Floors
1
Living Units
1
Actual Area
1,598 Sq.Ft
Living Area
1,193 Sq.Ft
Adjusted Area
1,390 Sq.Ft
Lot Size
11,523.6 Sq.Ft
Year Built
1938
Assessment Information
Year
2018
2017
2016
Land Value
$253,801
$253,801
$253,801
Building Value
$104,250
$96,744
$96,744
XF Value
$0
$0
$0
Market Value
$358,051
$350,545
$350,545
Assessed Value
$124,364
$121,807
$119,302
Benefits Information
Benefit
Type
2018
2017
2016
Save Our Homes
Cap
Assessment
Reduction
$233,687
$228,738
$231,243
Homestead
Exemption
$25,000
$25,000
$25,000
Second
Homestead
Exemption
$25,000
$25,000
$25,000
Note: Not all benefits are applicable to all Taxable Values (i.e. County,
School Board, City, Regional).
Short Legal Description
NAVARRO SUB PB 12-59
LOT 1 & 2 BLK 4
LOT SIZE 106.700 X 108
OR 17370-4478 0996 1
Generated On : 7/3/2018
Taxable Value Information
2018
2017
2016
County
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
$74,364
$71,807
$69,302
School Board
Exemption Value
$25,000
$25,000
$25,000
Taxable Value
$99,364
$96,807
$94,302
City
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
$74,364
$71,807
$69,302
Regional
Exemption Value
$50,000
$50,000
$50,000
Taxable Value
$74,364
$71,807
$69,302
Sales Information
Previous
Sale
Price
OR Book -
Pa 9a
Qualification Description
09/01/1996
$88,500
17370-
4478
Sales which are qualified
12/01/1992
$75,900
15766
2022
Sales which are qualified
09/01/1992
$34,000
15653-
1109
Sales which are qualified
05/01/1992
$0
15547-
1479
Sales which are disqualified as a result of
examination of the deed
The Office of the Property Appraiser is continually editing and updating the tax roll, This website may not reflect the most current information on record. The Property Appraiser
and Miami -Dade County assumes no liability, see full disclaimer and User Agreement at http://www.miamidade.gov/info/disclaimer.asp
Version:
https://www.miamidade.gov/propertysearch/
7/3/2018
ScctioniA/B
"Delivering Excellence Every Day"
Master Permit No:
MIN
Contractor's Name:
Job Address:
Miami -Dade County HVHZ Electronic Roof Permit Form
Section A (General Information) •
Process No:
ANDS ROOFING
30 nw 100 ter
❑ Low Slope
❑ Asphaltic Shingles
❑ Sprayed Polyurethane Foam
Roof Category
❑ Mechanically Fastened Tile
❑ Metal Panel/Shingles
❑ Other:
. •..
. .
• •.•.
• • ▪ •
❑f l/Vt r/Adhesiv2 Set Tile
0• Mod ShiOlbSfhakes
•..• ••..
. .
.. ..
• .
••
. .
..•
•.
•
.
Roof Type •. •
❑ New Roof 0 Re -Roofing ❑ Recovering ❑ Repair ❑ Mainten2r1ce • • • •
.. . • •
If yes, what type? ❑ Natural • LJ LPGX
Are there Gas Vent Stacks located on the roof? ❑ Yes ❑ No
Roof System Information
Low slope roof area (ft.2)
Steep Sloped area (ft.2)
1700
Section B (Roof Plan)
Total (ft.2)
1700
Sketch Roof Plan: Illustrate all levels and sections, roof drains, scuppers, overflow scuppers and overflow drains. Include
dimensions of sections and levels, clearly identify dimensions of elevated pressure zones and location of parapets.
Perimeter Width (a'):
Corner Size (a' x a'):
St 11,11 CT TO COMP IANCE WITH ALL FEDERAL
1 /M I AND COl1N l Y RUI FS AND RFGUI A110NS
Tile Re,of System
"Delivering Excellence Every Day"
Roof System Manufacturer:
Miami -Dade County HVHZ Electronic Roof Permit Form
Section D Tile Roof System
CERAMICA VEREA
Notice of Acceptance Number (NOA):
18-0119.03
Minimum Design Wind Pressures, If Applicable (from RAS 127 or Calculations):
P1:
39.1
P 2:
68.1
P 3:
Maximum Design Wind Pressures, (From the NOA Specific system): 118.31 psf
Fill in the specific roof assembly components. if a component is not required, insert not applicable Qi%))in the el box.
•••
100.7
....
. .
• ....
. • • ... •
• •
00
Roof Slope:
Roof Mean Height:
"/12"
15
Method of Tile Attachment:
ft.
Adhesive, Medium Paddy Polyfoam Polypro
Altemate Method of Tile Attachment per NOA:
Drip Edge Size & Gauge:
Drip Edge Material Type:
Drip Edge Fastener Type:
-3" face 26 ga.--
--Galvinized Metal--
k 1/4 RS NAILS
Hook Strip/Cleat gauge or weight:
-- Select Hook Strip --
•
Deck Type:
Optional Insulation:
mt. • .
.. •.
• . .
• • • •
• •
.. ..
• . .
• . .
Optional Nailable Substrate:
Optional Nailable Substrate Attachment:
Basesheet Type:
•• •
fr30 ASTM TYPE II
Fastener Type for Basesheet Attachment:
'1 1/4 RS NAILS 6" OC AND 12" FIELD
Tile Underlayment (Cap Sheet ) Type:
TILE SEAL
Tile Underlayment Attachment Method:
SELF ADHERED
Tile Profile:
SPANISH S
Section
MIAMI•DADE
COUNTY
"Delivering Excellence Every Day"
Miami -Dade County HVHZ Electronic Roof Permit Form
Section E (Tile Calculations)
Method 1 "Moment Based Tile Calculations Per RAS 127"
For Moment based tile systems, use Method 1. Compare the values for Mr with the values from Mf. If the Mf values are
greater than or equal to the Mr values, for each area of the roof, then the tile attachment method is acceptable.
P 1:
P 2:
P 3:
39_1 _
`68.1
1100.7
x?
x A,
1.260
.260
x1.260
10.16
17.70
=126.18
- Mg:
- Mg:
- Mg:
331111
14.11
14.11
= Mr1:
= Mr2:
= Mr3:
6.05
13.59
22.07
118.31;
118.31
< 1118.31
.............
Method 3 "Uplift Based Tile Calculations Per RAS 127"
• •
• . •
�QQ.M
•
NQQ Mf
• •
•• ••
• •• ••
• •••
• •
• • • •
•.• •
• •
•
•••.
• •
• • • •
• •
• • •
.• .•
•
• •
•
•
•
•.
•
•
•
• •
� •
For Uplift based tile systems use Method 3. Compare the values for F' with the values for Fr. If the F' values are greatth er ar:or equal to the Fr values.fiv;
each area of the roof, then the tile attachment method is acceptable. • • . •
• . .
P1:
P2:
P3:
>
ll
xl:
11111
X w:
x w:
TIN
=1 I-W:
-W:j1=1
-W:=
x cos A: j] = Fr1: <_ NOA F'
x cos 8: 71= Fr2:[7771 <17771 NOA F'
x cos A: = Fr3:
UM
Where to Obtain Information to complete tile calculations
Mil
NOA F'
Description
Symbol
Where to Find
Design Pressure
P1 or P2 or P3
Table 1 RAS 127, or by an engineer analysis prepared, signed and sealed by a professional
engineer based on ASCE 7.
4 Mean Roof Height
H
Job Site
, Roof Slope
6
Job Site
Aerodynamic Multiplier
a,
Product Approval (NOA)
Restoring Moment due to Gravity
Mg
Product Approval (NOA)
Attachment Resistance
Mf
Product Approval (NOA)
Required Moment Resistance
Mr
Calculated
Minimum Attachment Resistance
F'
Product Approval (NOA)
1 Required Uplift Resistance
Fr
Calculated
Average Tile Weight 1W
111
Product Approval (NOA)
Tile Dimensions
I = length
w = width
Product ApprovalNOA
(NOA)
4
SECTION 1524
HIGH VELOCITY HURRICANE ZONES — REQUIRED OWNERS NOTIFICATION FOR ROOFING
CONSIDERATIONS
1524.1 Scope. As it pertains to the section, it is the responsibility of roofing contractor to provide the owner with
the required roofing permit, and to explain to the owner the content of the section. The provisions of 800ttor.R4402
govern the minimum requirements and standards of the industry for roofing system inseallatlols. Addjtjgpally, the •
•
following items should be addressed as part of the agreement between the owner ant ttiecoetractor. Theoiner's •
initial in the designated space indicates that the item has been explained. •
•... •• •...• • •
••.. ••••
Renailing wood decks: When replacing roofing, the existing wooalrocr deckcia hve to
be/fenailed in accordance with the current provisions of Section R4403. (The gqq,fiWk is usually
ncealed prior to removing the existing roof system). • •
• ••
• . •
4. U Exposed Ceiling: Exposed, open beam ceilings are where the underside of the•reofoecking
can a viewed from below. The owner may wish to maintain the architectural appearance; therefore,
ro mg nail penetration of the underside of the decking may not be acceptable. This provides the option of
maintaining the appearance.
Overflow scuppers (wall outlets): It is required that rainwater flows off so that the roof is
overloaded from a buildup of water. Perimeter/edge wall or other roof extension may block this
ischarge if overflow scuppers (wall outlets) are not provided. It may be necessary to install overflow
scuppers in accordance with the requirements of Sections R4402, R4403 and R4413.
r/Agent' ignature Date
36 A)
Property Addr ss
Revised on 7/9/2009 LD;07/01/2015;
Co�"ctor Signature
I
Date
Permit Number
• •
� •
• •
•
•1
Miami Shores Viiiage
Building Department
10050 N.E.2nd Avenue
Miami Shores, Florida 33138
Tel: (305) 795.2204
Fax: (305) 756.8972
OWNERS'S AFFIDAVIT OF EXEMPTION
ROOF TO WALL CONNECTION HURRICANE MITIGATION RETROFIT FOR EXISTING SITE -
BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
PERSUANT TO SECTION 553.844 F.S. • • • • • •
To: Miami Shores Village Building Department
10050 NE 2nd Ave
Miami Shores, FI 33138
Re: Owner's Name:-ec\J1 Lee
Property Address: 36 N lid re -(e(
Roofing Permit Number:
•
• • •
.••
.•..
.
•.. . .
•. .
..
..•.
. .
. .
....
• ••
.••• •
•
• • • •
• .
.•
• .
....
•
. .
. .
.
•
'
.
• • .
• .•
.. . . • •.••
.
Dear B /ding Official: • • •
IC certifythat I
am not required to retrofit the roof to wall connections of my
building because:
The just valuation for the structure for purpose of ad valorem taxation is less than $300,000.00. Please attach proof of ad
valorem taxation.
o The building was constructed in compliance with the provisions of the Florida Building Code (FBC) or with the provisions
of 1994 edition of the South Florida Building Code (1994 SFBC)
1
Print Name
Sworn to and subscribed before me this
State of Florida
County of Dade
The undersigned, being the first duly sworn, deposes and says that he/she is the owner for the above property mentioned.
... day o �_ ZC'
Notary Public, Sate of Florida at Large
.
Revised on 5/21/2009
i
When the lust valuation of the structure for purpose of ad valorem taxation equal to
_ ...,..1.,... P'J non 00,00i and the building was not constructed with Gar nor a 1994
.... DANIELPEREZ
Notary Public— State of Florida
Commission 4 GG 44769
My Comm, Expires Nov 3, 2020
SFBC. Then you must provide a building application from a General Contractor for the Roof to Wall connection Hurricane Mitigation.
e ,i�
•
MIA 11
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
BOARD AND CODE ADMINISTRATION DIVISION
NOTICE OF ACCEPTANCE (NOA)
ICP Adhesives and Sealants, Inc.
12505 NW 44th Street
Coral Springs, FL. 33065
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
Miami, Florida 33175-2474
T (786)315-2590 F (786) 315-2599
www.miamidade.gov/economv
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been' reviewed and accepted by Miami -Dade County RER P.foduct Contibj 1ektion to•12s • •
used in Miami Dade County and'other areas where allowed by the Authority Having Jurisdraioti;A_HJ).... . •
This NOA shall not be valid after the expiration date stated below. The Miami -Dade Co}ty,Product Control Section •
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve t14 fight to hayg /ljis prod: tee • •
or material tested for quality assurance purposes. If this product or material fails to perform in t acceptedzaenner, tbM..
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, nodi4y, or spend the xsa..'
of such product or material within their jurisdiction. RER reserves the right to revoke this accesuptunea, if its is. • • •
determined by Miami -Dade County Product Control Section that this product or material frls Id meet the requirements • •
This product is approved as described herein, and has been designed to comply with'tbe' Florida B▪ uilding Cade• ' • •
including the High Velocity Hurricane Zone of the Florida Building Code.
ofthe applicable building code.
•
DESCRIPTION: ICP Adhesives Polyset® AH-160
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERNIINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews NOA 16-0315.01 and consists of pages 1 through 11.
The submitted documentation was reviewed by Alex Tigera.
1.14°11.
MIAMI•DADE COUNTY
APPROVED
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 1 of 11
ROOFING COMPONENT APPROVAL:
Category:
Sub Category:
Materials:
Roofing
Roof tile adhesive
Polyurethane
SCOPE:
This approves ICP Adhesives Polyset® AIi-160 as manufactured by ICP Adhesives and Sealants, Inc. as described
in this Notice of Acceptance. For the locations where the design pressure requirements, as determined by applicable
building code, do not exceed the design pressure values obtained by calculations in compliance with Roofing
Application Standard RAS 127. For use with approved flat, low, and high profile roof tile systems using ICP
Adhesives Polyset® AH-160.
PRODUCTS MANUFACTURED BY APPLICANT:
Product Dimensions
ICP Adhesives N/A
Polyset®AH-160
ICP Adhesives Foam N/A
Dispenser RTF1000
ICP Adhesives ProPack® N/A
30 & 100
Test
Specifications
TAS 101
• •
• • •
•. •
.•.•
••
....
••• •
•.
Productixewtription
.•.. ••••
• • •
•
st
•
Two component pojMtiane foam adhesive•
• • • • .
•• •. •. ••
Dispensing Equipmett • • • •
• •
Dispensing Equipment . •
•
• •
•
•
• •
• . •
•• .
•
PRODUCTS MANUFACTURED BY OM i RS:
Any Miami -Dade County Product Control Accepted Roof Tile Assembly having a current NOA which list attachment
resistance values with the use of ICP Adhesives Polyset® AH-160 roof tile adhesive.
MANUFACTURING LOCATION:
1. Tomball, TX.
PHYSICAL PROPERTIES:
Property
Density
Compressive Strength
Tensile Strength
Water Absorption
Moisture Vapor Transmission
Dimensional Stability
Closed Cell Content
Test
ASTM D 1622
ASTMD 1621
ASTM D 1623
ASTM D 2127
ASTM E 96
ASTM D 2126
ASTM D 2856
Results
1.6 lbs./ft.3
18 PSI Parallel to rise
12 PSI Perpendicular to rise
28 PSI Parallel to rise
0.08 Lbs./Ft2
3.1 Perm / Inch
+0.07% Volume Change @ -40° F., 2 weeks
+6.0% Volume Change @158°F., 100% Humidity, 2
weeks
86%
Note: The physical properties listed above are presented as typical average values as determined by
accepted ASTM test methods and are subject to normal manufacturing variation.
MIAMI•DADE COUNTY
APPROVED
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 2 of 11
EVIDENCE SUBMITTED:
Test Agency
Center for Applied Engineering
Miles Laboratories
Polymers Division
Ramtech Laboratories, Inc.
Southwest Research Institute
Trinity Engineering
Celotex Corp. Testing Services
Test Identifier
#94-060
257818-1PA
25-7438-3
25-7438-4
25-7438-7
25-7492
NB-589-631
9637-92
01-6743-011
01-6739-062b[1]
7050.02.96-1
P36700.04.12
P39740.02.12
Test Name/Report
TAS 101
TAS 101
SSTD 11-93
Date
04/08/94
12/16/96
10/25/95
SSTD 11-93 11/02/95
SSTD 11-93 12/12/95
ASTM D 1623 02/01/94
ASTM E 108 04/30/93
ASTM E 108 A1.6694
ASTM E 84 : • • • Otf1frf95
TAS 114 ••• 03/14716
..
ASTM D 1623 • • • • 04/1$/12 • •
TAS 101 • • • • • • n/2.1 it2
TAS 123 • •
•
••
528454-2-1 TAS 101
528454-9-1
528454-10-1
520109-1 TAS 101
520109-2
520109-3
520109-6
520109-7
520191-1 TAS 101 03/02/99
520109-2-1
. .
.• ..
• . .
. .
• . •
•. .
• • .
..• •.
10/2i/98
•• .
.
•
.•
•
•
•
•
•
LIMITATIONS:
1. Fire classification is not part of this acceptance. Refer to the Prepared Roof Tile Assembly for fire rating.
2. ICP Adhesives Polyset' AH-160 shall solely be used with flat, low, & high tile profiles.
3. Minimum underlayment shall be in compliance with the Roofing Application Standard RAS 120.
4. Roof Tile manufactures acquiring acceptance for the use of ICP Adhesives Polyset® AH-160 roof tile adhesive
with their tile assemblies shall test in accordance with TAS 101.
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61G20-3 of the Florida Administrative Code.
MIAMI.DADE COUNTY
APPROVED
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 3 of 11
INSTALLATION:
1. ICP Adhesives Polyset® AH-160 may be used with any roof file assembly having a current NOA that lists
attachment resistance values with the use of ICP Adhesives Polyset® AH-160.
2. ICP Adhesives Polyset® AH-160 shall be applied in compliance with the Component Application section and the
corresponding Placement Details noted herein. The roof tile assembly's adhesive attachment with the use of ICP
Adhesives Polyset® AH-160 shall provide sufficient attachment resistance to meet or exceed the resistance value
determined in compliance with Miami -Dade County Roofing Application Standards RAS 127. The adhesive
attachment data is noted in the roof tile assembly NOA.
3. ICP Adhesives Polyset® AH-160 and its components shall be installed in accordance with Roofing Application
Standard RAS 120, and ICP Adhesives and Sealants, Inc.'s Operating Instruction and Maintenance Booklet.
4. Installation must be by a Factory Trained 'Qualified Applicator' approved and licensed by ICP Adhesives and
Sealants, Inc. ICP Adhesives and Sealants, Inc. shall supply a list of approved applicators to the authority having
jurisdiction.
5. Calibration of the ICP Adhesives Foam Dispenser RTF1000 dispensing equipment is required befgieapglication
of any adhesive. The mix ratio between the "A" component and the "B" component s2iall13e.maintartied'betwedif • •; •
••• . ..
1.0-1.15 (A): 1.0 (B). .
6. ICP Adhesives Polyset® AH-160 shall be applied with ICP Adhesives Foam Dispenser..13F4.000 or IGP • •
Adhesives ProPack® 30 & 100 dispensing equipment only.
.... ....
• . .
. .
1••• ••••
7. ICP Adhesives Polyset® AH-160 shall not be exposed permanently to sunlight. • •
•
8. Tiles must be adhered in freshly applied adhesive. Tile must be set within 1 to 2 minutes eter ICP Adhesives .
Polyset® AH-160 has been dispensed. . • • • • •
9. ICP Adhesives Polyset® AH-160 placement and minimum patty weight shall be in accordance with fee • • • •
'Placement Details' herein. Each generic tile profile requires the specific placement noted'herein. • • . • .
MIAMI•DADE COUNTY
APPROVED
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 4 of 11
Table 1: Adhesive Placement For Each Generic Tile Profile
Tile Profile
Placement Detail
Minimum Paddy Contact
Area
Minimum Paddy Gram
Weight
Eave Course - Flat, Low, High
Profiles
All Eave Course
17-23 sq. inches
45-65
Flat, Low, High Profiles
#1
17-23 sq. inches
45-65
Flat Profile
#2
10-12 sq. inches
30
Low Profile
#2
12-14 sq. inches
30
High Profile
#2
17-19 sq. inches
30
Flat, Low, High Profiles
#3
Two Paddys: 8-9 sq. inches at
head of tile 9-11 sq. inches at
overlap -
12 grams per paddy
Two Piece Barrel (Cap Tile)
Two Piece
2 Beads (1 each longitudinal
edge) 20-25 sq. inches each • ..
bead ......
17 grams pe! bead
.. . ...
• ; ... . .
• •
• • 0001
Two Piece Barrel (Pan Tile)
Two Piece
65-70 sq. inches ....34
gramm uder pan` • • •
LABELING:
••••
• •
•. ••
• •
••••
• • •
•••
•.
••
•
•
•
••
•
• •
All approved products listed herein shall be labeled and shall bear the imprint or identifiable 3nai:'ki.>3g of the. .
manufacturer's name or logo and following statement: "Miami -Dade County Product Control:Approved" or. the Miami.
Dade County Product Control Seal as shown below. • • • • • • •
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or applicable building code in order to properly evaluate the installation of this
system.
MIAMI•DADE COUNTY
APPROVED
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 5 of 11
•
•
ADHESIVE PLACEMENT DETAIL # 1
tbrrughpiaztk.srsncet Pa ally Wi amlbTel
Nail irsth9phistit cement-
] lwhen requirsd
Ntidf
-Pass&
Weerhate
tarke C ias!ree
LINpp edged
MIAMI•DADE COUNTY
APPROVED
Flat/Low Profile Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown,
under the strengthening rib closest to the overlock
of the tile being set.
2. Continue in same manner. Tnsure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.
Medium Profile / Double Pin Tile
•. • •
• •
....
.•. •
• •
• •
•
• •.
•
1. Starting at the eave course apply a minimum 2" •
(50.8 mm) x 10" (254 rrica) i" (25!4•}foam•
paddy onto the underlaytmtpositionpd as show>a •: • . •
under the pan portion of tfttire closisst tb the
overlock of the tile beinrsetr •
• •
2. Continue in same manner. Iptyre approximately r4 •
(109.7 cm2) — 23 (148.4 eth2) s'quareetet, t.dhesiv2
contact with the underside of the tile. • • •
•
High Profile / Single Pan Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 nun) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as shown
under the pan portion of the tile closest to the
overlock of the tile being set.
2. Continue in same manner. Insure approximately 17
(109.7 cm2) — 23 (148.4 cm2) square inch adhesive
contact with the underside of the tile.
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 6 of 11
•
••
•
•
VolliThi*Agk onifint
aF rsgsrzsdi..
UJrailraimRi9rn7
milf'orn;gat !Azad cement
When requrr 1
MIAMI•DADE COUNTY
APPROVED
ADHESIVE PLACEMENT DETAIL # 2
Flat/Low Profile Tile
1. Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
strengthening rib of the tile closest to the overlock of
the tile being set. Insure approximately 17 (109.7 cm2)
— 23 (148.4 cm2) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 mm) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the
strengthening rib closest to the overlock of the tile
being set. • .
3. Continue in same manner. JNapproximtty 10"
(64.5 cm2) - 12 (77.4 cm2) squ'inch adhesive
contact with the underside of tke tile.
Medium Profile / Double Pad Tile
. • .
..•.
• .
.• .
....
•
•
.
.
......
.
1. Starting at the eave course, apply a mini t " (50.1
mm) x 10" (254 mm) x 1" f24. i im) foagi paddy
onto the underlayment positioned as short tinier the
pan portion of the tile closest to the overlock of the
tile being set. Insure approximately 17 (109.7 cm2) —
23 (148.4 cm2) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 mm) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the pan
portion of the tile closest to the overlock of the tile
being set.
3. Continue in same manner Insure approximately 12"
(77.4 cm2) -14 (90.3 cm2) square inch adhesive
contact with the underside of the tile.
(Instructions continued on next page)
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 7of11
•
•
•
ADHESIVE PLACEMENT DETAIL # 2 (CONTINUED)
�afl6t�r�u�yh_piaai4sceers�i
010.1-ii:mr6WuiFea s t13ci Tiler
4Y_
MIAMJ.DADE COUNTY
APPROVED
High Profile / Single Pan Tile
1. Starting at the eave course, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown under the
pan portion of the tile closest to the overlock of the
tile being set. Insure approximately 17 (109.7 cm2) —
23 (148.4 cm2) square inch adhesive contact with the
underside of the tile.
2. At the second course, apply a minimum 2" (50.8mm)
x 7" (177.8 mm) x 1" (25.4 mm) foam paddy onto the
underlayment positioned as shown under the pan
portion of the tile closest to the overloc$ t1f'thQ tile
being set. •' • •
3. Continue in same manner.liagric.approximitely 17".
(109.7 cm2) - 19 (122.6 cm)§gyare inchipidivsive
contact with the underside bfth4 tile. •.... •
. . .
.. •
.. ..•
.•
•
• •
. • •
.• • •. •
• • •
•
•
•
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 8 of 11
ADHESIVE PLACEMENT DETAIL # 3
NATthrosrghlila§tic cement
ltihenrequiredl:.
Battensoptional
Y
Single paddy
on top of We
Az4in.
single paddy
nrtdertrle,4
Stngle paddy
anumdeztay/neat
Paddy (Fietiireen ;tiles)
I.Patfdy gimlet tile)
--- Dive Closure
FlatiL.ovirl rcrflleTlin
Nall through.plastic cement & rigle paddy under trle
twhen required)
ittx4in.
Single.paddyan
undaymeny
Eave Course
idlutE il3ltil+�'il:£
MIAMI•DADE COUNTY
APPROVED
Paaalri6etw n tit 1
Paddy [undertileY
Eave#Jos:ure<
F`a
1. On the eave course only, apply a minimum 2" (50.8
mm) x 10" (254 mm) x 1" (25.4 mm) foam paddy
onto the underlayment positioned as shown, under
the strengthening rib for flat tile or under the pan
portion of the tile for low or high profile tile closest
to the overlock of the tile being set. Leave
approximately 4" (101.6 mm) up from the eave
edge free of foam to prevent the expanded adhesive
from blocking the weep holes. Insure
approximately 17-23 in2 (109.7-148.4 cm2) of
adhesive contact with the underside of the tile
2. Apply a 4" (101.6 mm) x 4" (101.6mi i 1" (25.4
mm) foam paddy onto the underlaynientiwst beloim • • • •
•
the second course line positioned foams •
under the strengtheningZtb fdrflat tile, orleider the • • • •
pan portion of the tile, didSctt to the und&rlock fo>;
the second course tile to.f a Metalled.. Wile •
approximately 8-9 in2 (5 f t!5'8.1 cm2) of adhesive •
contact with the undersierJe tile!.. • •
•
• • •
••
(Instructions continued on ntaxt4st4e) •
•
•• • •• •
• • •
•• •
•
•
•
••
• •
• •
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 9 of 11
ADHESIVE PLACEMENT DETAIL # 3 (CONTINUED
Nad through plastic
utien7e4 Tired rf
Single pad
oaun erfaympaN
4xdin.
BattBatreiris
ptiana
simile 2x4 in. js
paddy on
top of Ifle--
to in.
5innlepaddyunderIff
O
Faddy thari aatitft)
Paddy lundertrlel
l` Fascia
Weephole
. Eavetlrfsure
Qrip,edge
High Profile1'ie
MIAMI.DADE COUNTY
APPROVED
3. Also apply a 2" (50.8 mm) x 4" (101.6 mm) x 3/4"
(19 mm) paddy on top of the eave course tile
surface as shown, on top of the strengthening rib
for flat tile or on top of the pan portion of the tile,
closest to the underlock of the first course of tile.
Install second course of tile. Insure approximately
9 (58.1 cm2) - 11 (71cm2) square inch adhesive
contact with the underside of the tile at the overlap
and 7 (45.2 cm2) - 9 (58.1 cm2) square inch
adhesive contact with the underside of the tile at
the head of the tile. Continue in same manner.
... •
• • ....
• . .
.. . ... .•
•
..
•
• • •
.... .... • •
• •
.... .. • .
.
.
•
. . .
• . • .
• . • • .
• . •
.. • .. . • •
• • •
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 10 of 11
ADHESIVE PLACEMENT DETAIL
TWO PIECE BARREL
1) Place enough adhesiveto achieve 65 to 70 sq. iri.
in contact with the pan tile.
2) Turn covers upside down.Place adhesive iri
to l in.from outside edge of cover tile.
Then install the tffe.Ensare20to
25 sq. in. coniact area.
Underlayment
Eavectosure
(motarshown)
Weephole
Fascia Board
Steep pitch applications
(when required}
Slieathing
Remove top portion of the eave course cover tile.Abut to second course of
pan tiles. Ensure eave end of pan and.covertifes ace flush at eave line.
Two Piece Barrel - High Profile Tile
MIAMI.DADE COUNTY
APPROVED
Two Piece Barrel (Cap and Pan) Tile
1. Starting at the eave course, apply a minimum 2"
(50.8 mm) x 10" (254 mm) x 1" (25.4 mm) foam
paddy onto the underlayment positioned as
shown under two adjacent pan tiles. Support eave
tiles from rocking until adhesive has a chance to
cure.
2. Continue in same manner bringing two pan
courses up toward the ridge. Insure
approximately 65 (419.4 cm2) — 70 (451.6 cm2)
square inch adhesive contact with the underside
of the pan tile.
3. Turn covers upside down exposina. time underside
um of the tile. Apply a minim1" (5.44rgm) x 19'i • •. •
(254 mm) bead of adhesive tlirectlm the inner • •
edge of each side of the t..49017Er tile. Lea!•
approximately 3/4" (1Vmm3 to 1" (25.'4 mm) •
from the outside edge of •t1a' •tile, iy r ct iree of
foam to allow for exp $io.
•
. . .
.. .. .. •.
•
•
.
•
4. Turn cover tile over aites foam is applied and • •
place onto pan tile course Insure amini.num ofi •
20 (129 cm2) - 25 (163.3 cm,;) squal-e inch
contact area on each side of the coydfialtto the'
pan tile. Continue in same manner. 'trim away
any cured exposed foam adhesive. Pointing of
longitudinal edges of the cover tiles are
considered optional.
5. When additional nailing is required, 2" (50.8
nun) x 4" (101.6 mm) milers or the tie wire
system using galvanised, stainless steel, or
copper wire and compatible nails may be used.
END OF THIS ACCEPTANCE
NOA No.: 17-0322.03
Expiration Date: 05/10/22
Approval Date: 04/27/17
Page 11 of 11
•
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
BOARD AND CODE ADMINISTRATION DIVISION
NOTICE OF ACCEPTANCE (NOA)
Boral Roofing LLC.
7575 Irvine Center Drive, Suite 100
Irvine, CA 92618
MLAMI DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
ww w.miamidade. Qov/economy
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately p.oke, Modify:or •
suspend the use of such product or material within their jurisdiction. RER reserves the right resoke tkisooctptance, • •
if it is determined by Miami -Dade County Product Control Section that this product or materlt1Ms to meet th8
requirements of the applicable building code. •
This product is approved as described herein, and has been designed to comply with the Flortca .lieii1dingode•
including the High Velocity Hurricane Zone of the Florida Building Code.• •
DESCRIPTION: BORAL TileSeal
. .
. • .
.. .. .. ..
. . .
. • .
•
.•
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,:city,•state acid following •
statement: "Miami Dade County Product Control Approved", unless otherwise noted herein. ' . • .•
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed
by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then
it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This renewer NOA#13-1113.05 and consists of pages 1 through 4.
The submitted documentation was reviewed by Freddy Semino
t4IAMI•DADE COUNTY
APPROVED
NOA No.: 17-0530.10
Expiration Date: 07/31/18
Approval Date: 07/27/17
Page 1 of 4
•
•
ROOFING COMPONENT APPROVAL
Category:
Sub -Category:
Material:
Roofing
Underlayment
SBS
PRODUCTS DESCRIPTION:
Product
BORAL TileSeal
Dimensions
36" x 36' rolls
36" x 72' rolls
MANUFACTURING LOCATION:
1. Brentwood, NH
EVIDENCE SUBMITTED:
Test Agency
Underwriters Laboratories, Inc.
IRT Arcon, Inc.
PRI Asphalt Technologies, Inc.
PRI Asphalt Technologies, Inc.
PRI Construction Materials
Technologies, LLC.
MIAM4DADE COUNTY
APPROVED
Test
Specification
TAS 103
ASTM D 1970
Test Identifier
R14610
02-012
NEI-006-02-01
NEI-008-02-01
NEI-045-02-01
NEI-053-02-01
NEI-076-02-01
NEI-034-02-02
Product
Description
SBS self -adhering asphalt sheet material with a
white glass re -enforced polyester surfacing fabric;
for use as an underlayment in sloped roof
assemblies.
• •
• • •
.
Test Name/Report
Follow up Service . • • • • •
TAS 103-
TAS 103
TAS 114 (H)
....
.. ..
. . .
..
•
ASTM D 4798 & ASTM
ASTM D 4798 & ASTM G 155
TAS 103 / ASTM D4798
ASTM D 1970
. • .. •
• ....
... .
•.
..
• Date
. • •03/28/02 •
....
. 02/Z8/02
••04/D1/02
• 0W30/02
• •
• .04/08/07 •
•..0 /O1/08
02/14/11
01/29/13
NOA No.: 17-0530.10
Expiration Date: 07/31/18
Approval Date: 07/27/17
Page 2 of 4
APPROVED ASSEMBLIES:
Deck Type 1: Wood, non -insulated
Deck Description: 15/32" or greater plywood or wood plank
System E(1): Anchor sheet mechanically fastened deck, membrane adhered.
Base Sheet: One or more plies of ASTM D 226 Type II or ASTM D 2626 with a minimum 4" head lap and a
6" end lap mechanically fastened to deck with approved nails and tin caps 6" o.c. at the laps and
two staggered rows 12" o.c. the field of the roll.
Membrane:
No nails or tin caps shall be exposed.
One or more plies of BORAL TileSeal Underlayment with a minimum 3" head lap and minimum
6" end lap. Place the first course of membrane parallel to the eave, rolling the membrane to
obtain maximum contact. Remove the release membrane as the membrane is applied. Vertical
strapping of the roof with BORAL TileSeal Underlayment is acceptable. All end laps and laps
without black selvage area shall be sealed under lap using an SBS modified mastic.
Note: When used in Tile roof systems BORAL TileSeal Underlayment shall be backentaiTed to
deck with approved annular ring shank nails and tin caps at a maximurf& " C.c. at 'Sid:laps.
•
Surfacing: Approved for Approved Adhesive Set Roof Tile Systems, Mechanically' ,stened Epprxile,
Metal Roofing, Wood Shake & Shingles, and Asphaltic Shingle asser bliss,..
MIAM1•DADE COUNTY
APPROVED
. .
.. ..
• .
.. .
..•
..
•
• .
• .
•
•
•
NOA No.: 17-0530.10
Expiration Date: 07/31/18
Approval Date: 07/27/17
Page 3 of 4
•
LIMITATIONS:
1. Fire classification is not part of this acceptance.
2. This acceptance is for prepared roofing applications. Minimum deck requirements shall be in compliance with
applicable building code. BORAL TileSeal underlayment shall be installed in strict compliance with applicable
Building Code.
3. BORAL TileSeal underlayment shall be applied to a smooth, clean and dry surface with deck free of irregularities.
4. BORAL TileSeal underlayment shall not be applied over an existing roof membrane as a recover, but may be
applied over a roofing Base/Anchor sheet underlayment.
5. BORAL TileSeal underlayment shall not be left exposed as a temporary roof for longer than 180 days of
application.
6. The standard maximum roof pitch for BORAL TileSeal underlayment shall be 6:12 when tiles are loaded directly
to the BORAL TileSeal underlayment; loading boards or battens are required on roof pitches greater than 6:12".
7. Refer to Prepared Roofing system Product Control Notice of Acceptance for listed approval of this product with
specific prepared roofing products.
8. Tiles shall be stored on battens on roof pitches greater than 6:12".
9. BORAL TileSeal underlayment may be used with any approved roof covering Notice of Accepfance listin
BORAL TileSeal underlayment as a component part of an assembly in the Notice of prcceptance • BOR ••
TileSeal underlayment is not listed, a request may be made to the Authority Having .1ki,stliction (A ._) or tjlc • • ; •
Miami -Dade County Product Control Department for approval provided that app of ate documentation as •
provided to detail compatibility of the products, wind uplift resistance, and fire testing resrlts.• • • • • • •
10. All nails in the deck shall be carefully checked for protruding heads. Re -fasten any loose Peking pSiien. Sweel3:•
the deck thoroughly to remove any dust and debris prior to application. • • •' .
11. When applying the membrane in the valley, start at the low point and work to the high poiirtrrvlling the membrane •
from the center outward in both directions. For ridge applications, center the membraaie an4 roll from the center • • : •
outward in both directions. •
• •• •
12. Roll or broom the entire membrane surface so as to have 100% contact with the surface, giving specii: ttention to
overlap areas.
13. Flash vent pipes, stacks, chimneys and penetrations in compliance with Roof Assembly current Product Control
Notice of Acceptance and applicable Building Code.
14. All protrusions or drains shall be initially taped with a 6" piece of underlayment. This target piece shall be pressed
in place and formed around the protrusion to ensure a tight fit. A second layer of BORAL TileSeal underlayment
shall be applied over the underlayment, and sealed using an SBS modified mastic.
O. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61G20-3 of the Florida Administrative Code.
16. All membranes or packaging shall bear the imprint or identifiable marking of the manufacturer's name or logo, city
and state of manufacturing facility, and the following statement: "Miami -Dade County Product Control Approved"
or the Miami -Dade County Product Control Seal as shown below
MIAMI-DADE COUNTY
APPROVED
END OF THIS ACCEPTANCE
MIAMI•DADE COUNTY
APPROVED
NOA No.: 17-0530.10
Expiration Date: 07/31/18
Approval Date: 07/27/17
Page 4 of 4
M IAMI
Otiaff
DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
BOARD AND CODE ADMINISTRATION DIVISION
NOTICE OF ACCEPTANCE (NOA)
Ceramica Verea
Lanza S/N 15685
Mesia (Coruna) Spain
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208
Miami, Florida 33175-2474
T (786) 315-2590 F (786) 315-2599
www.miamidade.6ov/economy
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami -Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(in Miami -Dade County) and/or the AHJ (in areas other than Miami -Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami Dade County Product Control Section that this product or material fails to nl2et'thg
requirements of the applicable building code. • .•' . ""
•
This product is approved as described herein, and has been designed to comply with the Florida Building Coq
including the High Velocity Hurricane Zone of the Florida Building Code
DESCRIPTION: Verea Barrel Tile Grade 1
•
••••
• •
•.••
•
••••
• •
.•••
•
• • •' • •
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo,'d1t3r, State and'folro'wing
•
statement: "Miarni-Dade County Product Control Approved", unless otherwise noted herein• • •
• •
•
. •
• •
RENEWAL of this NOA shall be considered after a renewal application has been filed and'thefe $.as beep go.change.
in the applicable building code negatively affecting •the performance of this product. '
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official.
This NOA renews and revises NOA# 16-0921.09 and consists of pages 1 through 7.
The submitted documentation was reviewed by Alex Tigera.
MIAMI•DADE COUNTY
APPROVED
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 1 of 7
•
ROOFING ASSEMBLY APPROVAL
Category:
Sub Category:
Material:
Roofing
Roofing Tiles
Clay
1. SCOPE
This approves a roofing system using Verea Barrel Tile Grade 1 manufactured by Ceramica Verea in La
Coruna, Spain and is distributed by Ceramica Verea, USA Corp., as described in Section 2 of this Notice of
Acceptance. For locations where the pressure requirements, as determined by applicable Building Code, do not
exceed the design pressure values obtained by calculations in compliance with RAS 127 using the values listed
in section 4 herein. The attachment calculations shall be done as a moment based system.
2. PRODUCT DESCRIPTION
Manufactured by Applicant
Verea Barrel Tile Grade 1
Trim Pieces
Dimensions
L =19.5"
W= 8.15"
Length: varies
Width: varies
varying thickness
Verea Hurricane Clip 2.95" x 0.47" x 0.09" diam.
2.1 MANUFACTURING LOCATION
2.1.1. Mesia (La Coruna) Espana
MIAMI•DADE COUNTY
APPROVED
Test
Specifications
ASTM C1167
Type I
Grade 1
ASTM C1167
Product
Description
High profile two-piece clay roof
tile. For direct deck, adhesive set
applications. ••••
• •
• • ••••
• • •
Accessory trim, clay roof••pieces
for uses �� ti}s, rakes, rrctges anct
•'
•
•
valley tvnations >factur? • • • •
•
for each file profile. • • • •'
• •
•
(Optioh2l)•Stainless Stte2 Clip.
•
• • •
• •
• •
• • .
.. •
•
..
• . •
•
•
••
•
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 2 of 7
2.2 EVIDENCE SUBMITTED
Test Agency
PRI Construction Materials
Technologies
American Test Lab of South
Florida
IBA Consultants, Inc.
Redland Technologies
The Center for Applied
Engineering, Inc.
MIAMI•DADE COUNTY
APPROVED
Test Identifier
CVER-012-02-01
RT0517.01-11
RT0621.02-16
RT0202.01-18
4709-2
4709-4
7161-03 Appendix III
Letter
P09647-01
P0402
25-7094-(3, 6 & 9)
25-7120-(1 & 2)
25-7183-(3 & 4)
25-7214-(3, 4, &7)
25-7804-4
Test Name/Report
TAS 101
TAS 101
ASTM C 1167
ASTM C 1167
ASTM C 1167
TAS 101
PA 102 & PA 102(A)
PA 108 (Nail -On)
PA 108 (Mortar Set)
Withdrawal Resistance Testing of
screw vs. smooth shank nails
PA 102
.PA 102
PA 102
PA 102
PA 102
• •
• • •
•. •
•
• • • •
• •
•••
••
• • •
• •
• • •
•• •
Date
02/19/14
06/13/11
09/09/16
02/10/18
11/12/07
12/21/07
Dec. 1991
Aug. 1994
July 1994
Sept. 1993
• •bcc•1994
• nov..1994
Feb.:1995
Mach, 1995
••9elt.•1996 •
• • • •
•
• • •
••
•
• •
•
•• •
• .•
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 3 of 7
Table 2: Aerodynamic Multipliers - A (ft3)
• •
•
•.i
Tile
Profile
A (ft3)
Batten Application
•.. •A•ft3
Direct Deck Ap
.
ltelbn
• •
Verea Barrel Tile Grade 1
N/A
• • 0'.26
. • •. •.
•
Table 3: Restoring Moments due to Gravity - Mg (ft-Ibf)
Tile
Profile
2":12"
3":12"
4":12"
5":12"
6":12"
7":12"
or Greater
Verea
Barrel Tile
Grade 1
Direct Deck
Direct Deck
Direct Deck
Direct Deck
Direct Deck
Direct Deck
4.19
4.11
4.01
3.87
3.69
3.47
MIAMI•DADE COUNTY
APPROVED
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 4 of 7
3. LIMITATIONS:
3.1 Fire classification is not part of this acceptance.
3.2 For mortar or adhesive set tile applications, a static field uplift test shall be performed in accordance with
TAS 106.
3.3 Applicant shall retain the services of a Miami -Dade County Certified Laboratory to perform quarterly test in
accordance with TAS 112, appendix 'A'. Such testing shall be submitted to the Miami -Dade County Product
Control Section for review.
3.4 Minimum underlayment shall be in compliance with the applicable Roofing Applications Standards listed
section 4.1 herein.
3.5 30/90 hot mopped underlayment applications may be installed perpendicular to the roof slope unless stated
otherwise by the underlayment material manufacturers published literature.
3.6 This acceptance is for wood deck applications. Minimum deck requirements shall be in compliance with
applicable building code.
4. INSTALLATION
4.1 Verea Barrel Tile Grade 1 and its components shall be installed in strict compliance with Roofmg
Application Standard RAS-118, RAS 119, and RAS-120.
4.2 Data For Attachment Calculations.
••. •
• •
• • •---
Table 1: Average Weight (W) and Dimensions (I x w) • • •
° •
• • • •
Tile Profile
•
Weight-W (Ibf)
Length-1 (ft)
'
'
Width-w (ft)
• •,
cottO
Verea Barrel Tile Grade 1
5.5
1.625
• •
• `• •
p.'�r .
•
••
•••
•
•••
•
••
• •
••
.• •
•
•
•
•.
•
•••
Table 4: Attachment Resistance Expressed as a Moment - Mf (ft-Ibf)
for Mechanically Attached Systems
Tile
Profile
Fastener Type
Direct Deck
(min 15/32"
plywood)
Direct Deck
(min. 19/32"
plywood)
Battens
Verea Barrel Tile Grade
1
2-10d Ring Shank Nails
28.6
41.2
n/a
1-10d Smooth or Screw Shank
Nail
5.1
6.8
n/a
2-10d Smooth or Screw Shank
Nails
6.9
9.2
n/a
1 #8 Screw
20.7
20.7
n/a
2 #8 Screw
43.2
43.2
n/a
1-10d Smooth or Screw Shank
Nail (Field Clip)
23.1
23.1
n/a
1-10d Smooth or Screw Shank
Nail (Eave Clip)
29.3
29.3
n/a
•
2-10d Smooth or Screw Shank
Nails (Field Clip)
27.6
27.6• .
• • •
• •
• •
•
• • •n/a • •
•. ••
••
• •
•
•
2-10d Smooth or Screw Shank
Nails (Eave Clip)
38.1
3� •9 ..
• • • •
•
• n/a .
• • • •
•..•
••
••
Table 5: Attachment Resistance Expressed as a Moment - M 1MM) • • ••
• for Mechanically Attached Systems •
Tile
Profile
Fastener Type
Direct Deck
(min 15/32"
plywood)
Direct Detk
(mitt 19/3Q
plywood)
:. P.dt#ens • • •
•
• • •
• • , • •
•
Verea Barrel Tile Grade
1
2-10d Ring Shank Nails'
33.1
48.1
n/a
1 Installation with a 4" tile headlap and fasteners are located a min. of 21/2" from head of tile.
Table 6: Attachment Resistance Expressed as a Moment - Mf (ft-Ibf)
for Single Patty Adhesive Set Systems
Tile
Profile
Tile Application
Minimum Attachment
Resistance
Verea Barrel Tile
Grade 1
ICP Adhesives Polyset AH-160
118.311
1 Medium paddy placement weight 34.6 grams of ICP Adhesives Polyset AH-160 for the pan tiles. 17.3g on each
side of the cap tiles.
MIAMI•DADE COUNTY
APPROVED
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 5 of 7
••
.
•
•••
•
•
•
•••
.
•0•
•
Table 7: Attachment Resistance Expressed as a Moment - Mf (ft-Ibf)
for Mortar Set Systems
Tile
Profile
Tile Application
Minimum Attachment
Resistance
Verea Barrel Tile
Grade 1
Quikrete Roof Tile Mortar, FL-15
45.38
5. LABELING
5.1 All tiles shall bear the imprint or identifiable marking of the manufacturer's name or logo as detailed
below, or following statement: "Miami Dade County Product Control Approved".
VEREA SPAIN CE
LABEL FOR VEREA BARREL TILE GRADE 1
(LOCATED ON 'ifli SIDE OF TILE)
6. BUILDING PERMIT REQUIREMENTS:
....
•
• . ....
. . . .
.. . ... . .
.. •
.
.... ••••
• • • •
••••....
As required by the Building Official or the applicable Building Code in order to prt fly*valuat8 tile;
installation of this system. This Notice of Acceptance on its own cannot be used to obtain a builctin permit.
MIAMI•DADE COUNTY
APPROVED
• • •
•
• .
•
..
•.
.. • .. . • •
• . •
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 6 of 7
8.15"
PROFILE DRAWING
VEREA BARREL TILE GRADE 1
19.5"
. .
• . ....
• .. •
.. • ... •
• •
00
•
• • •
....
• •
....
• •
. • • • •
.. .. .. ..
• •
.....
••
•
•
• . .
•
• .
• • .
.. • .. • • •
•
VERSA HURRICANE CLIP
NOTE: USE OF CLIP IS OPTIONAL. REFER TO MANUFACTURERS PUBLISHED INSTRUCTIONS FOR
INSTALLATION DETAIL
END OF THIS ACCEPTANCE
MIAMI•DADE COUNTY
APPROVED
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 7 of 7
GREEN SUSTAINABLE ATTRIBUTES (GSA)
SCOPE: This document is solely for the purpose of verification of Sustainable Attributes of construction materials. The
documentation submitted has been reviewed by Miami -Dade County Product Control Section.
Component Name
Initial
Aged
Initial
Aged
Solar Reflectance
Reflectance
Reflectance
Emmitance
Emmitance
Index (SRI)
1. Verea Barrel Tile
Grade 1
0.39
Pending
0.83
Pending
41
MANMADE COUNTY
APPROVED
• . .
.. • ••• •
•
•
.
. •
.... •... • .
• . .
.... ....
•
. • • • .
.. .. •• ..
•
. •
•.. .
•
.
•• . -
.• . ••
•• • •• • • •
• • •
NOA No.: 18-0119.03
Expiration Date: 03/13/23
Approval Date: 03/22/18
Page 8 of 7