RF-17-2331 a
ENGINEERING
4225 SW 71 Ave Miami. FI 33155
Tel: 786-398-9179 fax: 786-800-2627
a1 roofinspectionV)gmail.com
LAB CERTIFICATION #16-0510.15
SITE SPECIFIC INFORMATION
UPLIFT TEST—TAS #106
01/03/2018 I&Pk PC— a k1 --233
Roofing Contractor DESIGN BUILDERS Permit# RF17-233
Job Address 10555 NE 2 CT
Owner's Name JORGE DEL RIOS
Type of Tile BELAIR EAGLE Date Installed
Approximate Roof Height 12" feet Roof Pitch 4/12 Type of Access to Roof, LADDER
Approximate Square Footage of Roof 39 ftZ Required Testing Force 35 Lbs
Date Tested 01/03/2018 Number of Tests 77 Testing Equipment F.G.E.100
Contact Name MARY Phone# 305-628-9696
LOCATION #OF TEST PASS #OF TEST FAIL
Corner 9 Tests 9 Pass Test Fail
Perimeter 12 Tests 12 Pass Test Fail
Field 39 Tests 39 Pass Test Fail
Ridge 17 Tests 17 Pass Test Fail
TOTAL 77 Tests 77 Pass 0 Test 0 Fail
IN ACCORDANCE WITH THE CRITERIA OF PROTOCOL PA 106,THIS ROOF ASSEMBLY HAS PASSED THE STATIC UPLIFT QUALITY CONTROL TEST.THIS TAS 106 TEST HAS BEEN PERFORMED IN FULL ACCORDANCE TO THE
REQUIREMENTS OF DADE COUNTRY,WITH NO DEVIATIONS.THIS REPORT IS NOT GUARANTEED IN CASE OF CASE OF NATURAL DISASTERS.THIS REPORT IT IS NOT VALID FOR INSURANCE CLAIMS.
r
N
YENAN T. LEYVA
PE 67416