RF-17-2331 a ENGINEERING 4225 SW 71 Ave Miami. FI 33155 Tel: 786-398-9179 fax: 786-800-2627 a1 roofinspectionV)gmail.com LAB CERTIFICATION #16-0510.15 SITE SPECIFIC INFORMATION UPLIFT TEST—TAS #106 01/03/2018 I&Pk PC— a k1 --233 Roofing Contractor DESIGN BUILDERS Permit# RF17-233 Job Address 10555 NE 2 CT Owner's Name JORGE DEL RIOS Type of Tile BELAIR EAGLE Date Installed Approximate Roof Height 12" feet Roof Pitch 4/12 Type of Access to Roof, LADDER Approximate Square Footage of Roof 39 ftZ Required Testing Force 35 Lbs Date Tested 01/03/2018 Number of Tests 77 Testing Equipment F.G.E.100 Contact Name MARY Phone# 305-628-9696 LOCATION #OF TEST PASS #OF TEST FAIL Corner 9 Tests 9 Pass Test Fail Perimeter 12 Tests 12 Pass Test Fail Field 39 Tests 39 Pass Test Fail Ridge 17 Tests 17 Pass Test Fail TOTAL 77 Tests 77 Pass 0 Test 0 Fail IN ACCORDANCE WITH THE CRITERIA OF PROTOCOL PA 106,THIS ROOF ASSEMBLY HAS PASSED THE STATIC UPLIFT QUALITY CONTROL TEST.THIS TAS 106 TEST HAS BEEN PERFORMED IN FULL ACCORDANCE TO THE REQUIREMENTS OF DADE COUNTRY,WITH NO DEVIATIONS.THIS REPORT IS NOT GUARANTEED IN CASE OF CASE OF NATURAL DISASTERS.THIS REPORT IT IS NOT VALID FOR INSURANCE CLAIMS. r N YENAN T. LEYVA PE 67416